Вы находитесь на странице: 1из 111

PCS-996R

Disturbance & Fault Recorder


Instruction Manual

NR Electric Co., Ltd.


PCS-996R Disturbance & Fault Recorder

Preface

Introduction

This guide and the relevant operating or service manual documentation for the equipment provide
full information on safe handling, commissioning and testing of this equipment.

Documentation for equipment ordered from NR is dispatched separately from manufactured goods
and may not be received at the same time. Therefore this guide is provided to ensure that printed
information normally present on equipment is fully understood by the recipient.

Before carrying out any work on the equipment the user should be familiar with the contents of this
manual, and read relevant chapter carefully.

This chapter describes the safety precautions recommended when using the equipment. Before
installing and using the equipment, this chapter must be thoroughly read and understood.

Health and Safety

The information in this chapter of the equipment documentation is intended to ensure that
equipment is properly installed and handled in order to maintain it in a safe condition.

When electrical equipment is in operation, dangerous voltages will be present in certain parts of
the equipment. Failure to observe warning notices, incorrect use, or improper use may endanger
personnel and equipment and cause personal injury or physical damage.

Before working in the terminal strip area, the equipment must be isolated.

Proper and safe operation of the equipment depends on appropriate shipping and handling,
proper storage, installation and commissioning, and on careful operation, maintenance and
servicing. For this reason only qualified personnel may work on or operate the equipment.

Qualified personnel are individuals who:

 Are familiar with the installation, commissioning, and operation of the equipment and of the
system to which it is being connected;

 Are able to safely perform switching operations in accordance with accepted safety
engineering practices and are authorized to energize and de-energize equipment and to
isolate, ground, and label it;

 Are trained in the care and use of safety apparatus in accordance with safety engineering
practices;

 Are trained in emergency procedures (first aid).

NR ELECTRIC CO., LTD. i


PCS-996R Disturbance & Fault Recorder

Instructions and Warnings

The following indicators and standard definitions are used:

DANGER means that death, severe personal injury, or considerable equipment damage will
occur if safety precautions are disregarded.

WARNING means that death, severe personal, or considerable equipment damage could occur
if safety precautions are disregarded.

CAUTION means that light personal injury or equipment damage may occur if safety
precautions are disregarded. This particularly applies to damage to the device and to
resulting damage of the protected equipment.

WARNING!

The firmware may be upgraded to add new features or enhance/modify existing features, please
make sure that the version of this manual is compatible with the product in your hand.

WARNING!

During operation of electrical equipment, certain parts of these devices are under high voltage.
Severe personal injury or significant equipment damage could result from improper behavior.

Only qualified personnel should work on this equipment or in the vicinity of this equipment. These
personnel must be familiar with all warnings and service procedures described in this manual, as
well as safety regulations.

In particular, the general facility and safety regulations for work with high -voltage equipment must
be observed. Noncompliance may result in death, injury, or significant equipment damage.

DANGER!

Never allow the current transformer (CT) secondary circuit connected to this equipment to be
opened while the primary system is live. Opening the CT circuit will produce a dangerously high
voltage.

WARNING!

 Exposed terminals

Do not touch the exposed terminals of this equipment while the power is on, as the high voltage
generated is dangerous

 Residual voltage

Hazardous voltage can be present in the DC circuit just after switching off the DC power supply. It
takes a few seconds for the voltage to discharge.

ii NR ELECTRIC CO., LTD.


PCS-996R Disturbance & Fault Recorder

CAUTION!

 Earth

The earthing terminal of the equipment must be securely earthed

 Operating environment

The equipment must only be used within the range of ambient environment detailed in the
specification and in an environment free of abnormal vibration.

 Ratings

Before applying AC voltage and current or the DC power supply to the equipment, check that they
conform to the equipment ratings.

 Printed circuit board

Do not attach and remove printed circuit boards when DC power to the equipment is on, as this
may cause the equipment to malfunction.

 External circuit

When connecting the output contacts of the equipment to an external circuit, carefully check the
supply voltage used in order to prevent the connected circuit from overheating.

 Connection cable

Carefully handle the connection cable without applying excessive force.

Copyright
Version : R1.03 NR ELECTRIC CO., LTD.
P/N: EN_GZLB5118.0086.0004 69 Suyuan Avenue. Jiangning, Nanjing 211102,China
Tel: 86-25-87178185, Fax: 86-25-87178208
Copyright © NR 20 10. All rights reserved Website: www.nari-relays.com
Email: international@nari-relays.com
We reserve all rights to this document and to the information
contained herein. Improper use in particular reproduction and
dissemination to third parties is strictly forbidden except where
expressly authorized.

The information in this manual is carefully checked periodically,


and necessary corrections will be included in future editions. If
nevertheless any errors are detected, suggestions for correction or
improvement are greatly appreciated.

We reserve the rights to make technical improvements without


notice.

NR ELECTRIC CO., LTD. iii


PCS-996R Disturbance & Fault Recorder

iv NR ELECTRIC CO., LTD.


PCS-996R Disturbance & Fault Recorder

Table of Contents
Preface.............................................................................................................................................. i

Introduction .............................................................................................................................. i

Health and Safety ..................................................................................................................... i

Instructions and Warnings..................................................................................................... ii

Table of Contents ........................................................................................................................... v

Chapter 1 Overview........................................................................................................................ 1

1.1 Application......................................................................................................................... 1

1.2 Features ............................................................................................................................. 3

1.3 Ordering Options .............................................................................................................. 3

Chapter 2 Technical Data............................................................................................................... 7

2.1 Electrical Specifications................................................................................................... 7

2.1.1 Analog Input Ratings.............................................................................................. 7

2.1.2 Power Supply .......................................................................................................... 7

2.1.3 Binary Input............................................................................................................. 8

2.1.4 Binary Output.......................................................................................................... 8

2.1.5 Power Supply Output for Opto-coupler ............................................................... 8

2.2 Mechanical Specifications ............................................................................................... 8

2.3 Wiring Terminals ............................................................................................................... 9

2.4 Ambient Temperature and Humidity Range................................................................... 9

2.5 Communication Port......................................................................................................... 9

2.5.1 EIA-485 Port............................................................................................................. 9

2.5.2 Ethernet Port ......................................................................................................... 10

2.5.3 Optical Fiber Port.................................................................................................. 10

2.5.4 Print Port................................................................................................................ 10

2.5.5 Clock Synchronization Port................................................................................. 10

2.5.6 Debugging Port..................................................................................................... 10

2.6 Type Tests .........................................................................................................................11

2.6.1 Environmental Tests..............................................................................................11

NR ELECTRIC CO., LTD. v


PCS-996R Disturbance & Fault Recorder

2.6.2 Mechanical Tests ...................................................................................................11

2.6.3 Electrical Tests.......................................................................................................11

2.6.4 Electromagnetic Compatibility.............................................................................11

2.7 Performance .................................................................................................................... 12

2.7.1 Metering Scope and Accuracy ............................................................................ 12

2.7.2 Sampling................................................................................................................ 12

2.8 Certification ..................................................................................................................... 12

Chapter 3 Software Description.................................................................................................. 13

3.1 Trigger Mode.................................................................................................................... 13

3.2 Recording Mode .............................................................................................................. 13

3.3 Data Storage .................................................................................................................... 14

Chapter 4 Automatic Supervision .............................................................................................. 17

4.1 Understand Alarm Signals ............................................................................................. 17

4.2 Understand Triggering Signals...................................................................................... 18

Chapter 5 Hardware Description ................................................................................................ 23

5.1 Overview .......................................................................................................................... 23

5.2 Plug-in Modules .............................................................................................................. 26

5.2.1 CPU Module(NR1102) on B01 and B15 ............................................................... 26

5.2.2 DSP Module (NR1156A) on B03........................................................................... 29

5.2.3 AI Module(NR1401/NR1415)on B04~B11 (Optional)..................................... 30

5.2.4 BI Module(NR1502)on B10~B14 (Optional)................................................... 34

5.2.5 IO Module (NR1525) on B10~B14(Optional).................................................. 36

5.2.6 GOOSE Module (NR1126) on B14(Optional) ................................................. 38

5.2.7 PWR Module (NR1301) on B00 ............................................................................ 40

5.2.8 LCD & Keyboard ................................................................................................... 43

5.2.9 LED Indicators of the Front Panel ...................................................................... 44

Chapter 6 Human Machine Interface .......................................................................................... 47

6.1 Front Panel ...................................................................................................................... 47

6.2 Understand the HMI Menu Tree ..................................................................................... 47

6.2.1 Overview ................................................................................................................ 47

vi NR ELECTRIC CO., LTD.


PCS-996R Disturbance & Fault Recorder

6.2.2 DeviceStatus ......................................................................................................... 49

6.2.3 DeviceReports ....................................................................................................... 49

6.2.4 DeviceSetting ........................................................................................................ 49

6.2.5 LocalCommand..................................................................................................... 52

6.2.6 AdjustTime............................................................................................................. 54

6.2.7 Version ................................................................................................................... 54

6.2.8 Debug..................................................................................................................... 54

6.2.9 Environment .......................................................................................................... 54

Chapter 7 Settings ........................................................................................................................ 57

7.1 Overview .......................................................................................................................... 57

7.2 Settings ............................................................................................................................ 57

7.2.1 Voltage Level Setting of Binary inputs ............................................................... 57

7.2.2 Voltage setting for 1-wire measurement or 2-wire measurement ................... 58

7.2.3 Voltage setting for 3-wire measurement or 4-wire measurement ................... 59

7.2.4 Current setting for 1-wire measurement or 2-wire measurement ................... 62

7.2.5 Current setting for 3-wire measurement or 4-wire measurement ................... 63

Chapter 8 WEB.............................................................................................................................. 67

8.1 Overview .......................................................................................................................... 67

8.2 Device Information.......................................................................................................... 69

8.3 Status................................................................................................................................ 75

8.3.1 DeviceStatus ......................................................................................................... 75

8.3.2 DebugMenu ........................................................................................................... 79

8.4 Records ............................................................................................................................ 80

8.5 Settings ............................................................................................................................ 82

Chapter 9 Installation ................................................................................................................... 85

9.1 General ............................................................................................................................. 85

9.2 Safety Instructions.......................................................................................................... 85

9.3 Checking the Shipment .................................................................................................. 86

9.4 Material and Tools Required .......................................................................................... 86

9.5 Device Location and Ambient Conditions.................................................................... 87

NR ELECTRIC CO., LTD. vii


PCS-996R Disturbance & Fault Recorder

9.6 Mechanical Installation................................................................................................... 87

9.7 Electrical Installation and Wiring .................................................................................. 88

9.7.1 Grounding Guidelines.......................................................................................... 88

9.7.2 Cubicle Grounding ............................................................................................... 88

9.7.3 Ground Connection on the Device ..................................................................... 89

Chapter 10 Commissioning......................................................................................................... 91

10.1 General ........................................................................................................................... 91

10.2 Safety Instructions ........................................................................................................ 91

10.3 Product Checks............................................................................................................. 91

10.3.1 With the Device De-energized........................................................................... 91

10.3.2 With the Device Energized................................................................................. 92

10.3.3 Final Check.......................................................................................................... 93

Chapter 11 Maintenance .............................................................................................................. 95

11.1 Maintenance Schedule ................................................................................................. 95

11.2 Regular Testing ............................................................................................................. 95

11.3 Failure Tracing and Repair ........................................................................................... 95

11.4 Replace Failed Modules ............................................................................................... 95

11.5 Cleaning ......................................................................................................................... 96

11.6 Storage ........................................................................................................................... 96

Chapter 12 Decommissioning and Disposal ............................................................................. 99

12.1 Decommissioning ......................................................................................................... 99

12.1.1 Switching off ....................................................................................................... 99

12.1.2 Disconnecting cables......................................................................................... 99

12.1.3 Dismantling ......................................................................................................... 99

12.2 Disposal ......................................................................................................................... 99

Chapter 13 Manual Version History.......................................................................................... 101

viii NR ELECTRIC CO., LTD.


Chapter 1 Overview

Chapter 1 Overview

1.1 Application

Disturbance & fault recorders are mainly used for recording the dynamic fault processes of power
system.

The main tasks of the disturbance & fault recorders are to record the changing process of relative
electrical parameters of the system as well as the activities of relay protection and automatic
safety devices after the great system disturbance occurs.
Digital substation is the developing trend in the future. More and more substations have started the
digital construction and transformation. Application of digital technology can not only greatly
reduce cost but also bring much convenience for management and maintenance. At the same
time, application of digital technology has brought profound reforms to traditional management
mode. Based on a great deal of researches on the features of digital technology and practices of
the digital substation technology of our company, we specially designed the PCS-996R
disturbance & fault recorder applied for digital substations.

PCS-996R can be applied in a distributed system, so it is especially suitable for the system
measuring and recording of various substations in a wide area. The hardware and software have
truly realized the modular structure, which enables flexible assembly and high versatility, allowing
for batch process.

The hardware and software of the device adopt modular structure, the universal modules can be
applied conveniently. The device is suitable for mass production.

PCS-996R is designed with multiple reliability measures to ensure high reliability.

Typical application of the PCS-996R in a wide-area DFR system (Disturbance & fault recording
system) is shown in the following figure.

NR ELECTRIC CO., LTD. 1


2
电 源 电 源

1 1
0 1 1
0
M 5
C
P 0
2 M 5
C
P 0
2
1 1
2 1 P
S
D 件
插 1 1
2 1 P
S
D 件

4 0
1 1 4 0
1 1
送 器
变 插 件 送 器
变 插 件

4 0
1 1 4 0
1 1
送 器
变 插 件 送 器
变 插 件

1 1
0 M 5
C
P 0
2 1 1
0 M 5
C
P 0
2
P
S
D 件
插 P
S
D 件

1 1
2 1 1
2

4 0
1 1 4 0
1 1
送 器
变 插 件 送 器
变 插 件

1 5
2 开 入 5 2
1 开 入
1 5
2 开 入 5 2
1 开 入

1 5
2 开 入 5 2
1 开 入

1 5
2 开 出 5 2
1 开 出
Chapter 1 Overview

电 源 电 源

1 1
0 1 1
0
M 5
C
P 0
2 M 5
C
P 0
2
P
S
D 件
插 P
S
D 件

1 1
2 1 1 1
2 1

4 0
1 1 4 0
1 1
送 器
变 插 件 送 器
变 插 件

4 0
1 1 送 器
变 插 件 4 0
1 1 送 器
变 插 件

1 1
0 1 1
0
M 5
C
P 0
2 M 5
C
P 0
2
1 1
2 P
S
D 件
插 1 1
2 P
S
D 件

4 0
1 1 4 0
1 1
送 器
变 插 件 送 器
变 插 件

1 5
2 开 入 5 2
1 开 入
开 入 开 入
1 5
2 5 2
1
1 5
2 开 入 5 2
1 开 入

1 5
2 开 出 5 2
1 开 出


电 源

0 1
1 0 1
1
C
P
M 0
2
5 0 C
P
M 0
2
5 0
2 1
1 D 插 件
P
S 2 1
1 D 插 件
P
S

1 4
1
0 1 4
1
0
变 送
器 插
件 变 送
器 插

1 4
1
0 1 4
1
0
变 送
器 插
件 变 送
器 插

0 1
1 C
P
M 0
2
5 0 1
1 C
P
M 0
2
5
S
D 插 件
P S
D 插 件
P
2 1
1 2 1
1

1 4
1
0 1 4
1
0
变 送
器 插
件 变 送
器 插


开 入

1 5
2 2 1 5
2 2
1 5
2 2 入
开 1 5
2 2 入

1 5
2 2 入
开 1 5
2 2 入

1 5
2 2 出
开 1 5
2 2 出

Figure 1.1-2 Typical application of the PCS-996R in a digital substation


Figure 1.1-1 Typical application of the PCS-996R in a wide-area DFR system

Typical application of the PCS-996R in a digital substation is shown in the following figure.

NR ELECTRIC CO., LTD.


Chapter 1 Overview

1.2 Features

NR has developed the hardware platform UAPC with completely independent intellectual property
rights for digital substations. This advanced technology is adopted in PCS-996R.

In the aspect of synchronization technology, PCS-996R integrates relevant technologies of


PCS-915 digital differential protective device for busbar of our company to ensure synchronization
among the sampling data and recording data from different merging units.

in the aspects of fault analysis and fault location of power line, PCS-996R inherits the excellent
traditions of line relays.

In the aspect of communication management, designs and development fully conform to the
contents of IEC61850 protocol.

Advanced analysis software is developed by adopting cross-platform technology, many operation


systems such as Windows, Unix and Linux can be adopted.

PCS-996R supports various input signals. These input signals are introduced in the following
table.

Figure 1.2-1 The input signals description of PCS-996R

Type Subtype Description


12~48
Conventional Transformers Input signal type:
Analog
AC current, AC voltage
Inputs
8~16 bays
Electrical Transformers
Supporting IEC60044-8, IEC61850-9-2

Conventional Binary Inputs Max: 96.


Binary Inputs
Max: 64 GOOSE control blocks,
GOOSE Binary Inputs
Max: 160 GOOSE binary inputs.

1.3 Ordering Options


This device is very flexible to configure according to the practical engineering. The following table
shows the required information when ordering a PCS-996R.

NR ELECTRIC CO., LTD. 3


Chapter 1 Overview

Information Required with Order:

Device Type: PCS-996R- S1 S2 S3 H1 H2 H3 H4 H5 H6 H7

Application A

Standard

Software Version
Standard 1
Language
Chinese + English E
Chinese + French F
Chinese + Russian R
Chinese + Spanish S
Chinese + Portuguese P
Auxiliary Power
88~300 Vdc 1
Analog AC Inputs
Non available O
CT 1A A
CT 5A B
Digital AC Inputs
Non available 0
IEC60044-8, ST-Connector 1
IEC61850-9-2, ST-Connector 2
Other* 3
Analog Inputs, Binary Inputs/Binary Output (1)
36 Analog inputs + 84 Binary inputs+ 4 Binary Outputs A
36 Analog inputs + 90 Binary inputs B
48 Analog inputs + 48 Binary inputs+ 4 Binary Outputs C
48 Analog inputs + 54 Binary inputs D
24 Analog inputs + 120 Binary inputs+ 4 Binary
E
Outputs
24 Analog inputs + 126 Binary inputs F
Support to GOOSE
Non available 0
2 x 100Base-FX, ST-Connector 1
Other* 2
Communication Ports
4 x 10Base-T/100Base-TX, RJ45 A
2 x EIA-485 + 2 x 10Base-T/100Base-TX, RJ45 B
2 x 10Base-T/100Base-TX, RJ45 + 2 x 100Base-FX,
C
ST-Connector
Other* D

4 NR ELECTRIC CO., LTD.


Chapter 1 Overview

Protocol
IEC 61850* 1
IEC 60870-5-103 2
DNP 3.0 3

NOTE:The items marked with "*" are not included in the basic price and have an

additional cost.

NOTE: "Other" is selected for a certain option, please declare the concrete requirement.

NOTE: (1): Please specify the quantities of voltage/current channels, each quantity

should be a multiple of 12, e.g. :12 voltages + 24 currents .

Quantity of voltage channels:

Quantity of current channels: .

NR ELECTRIC CO., LTD. 5


Chapter 1 Overview

6 NR ELECTRIC CO., LTD.


Chapter 2 Technical Data

Chapter 2 Technical Data

2.1 Electrical Specifications

2.1.1 Analog Input Ratings


1. Analog current

Standard IEC 60255-27:2005


Phase rotation ABC
Nominal frequency 50±5Hz, 60±5Hz
Rated Current 1A 5A
Linear to 0.05In~40In
Thermal withstand
-continuously 4In 4In
-for 10s 30In 30In
-for 1s 100In 100In
-for half a cycle 250In 250In
Burden < 0.2VA/phase @In < 0.25VA/phase @In

2. Analog voltage

Standard IEC 60255-6, IEC60288


Phase rotation ABC
Nominal frequency 50±5Hz, 60±5Hz
Rated Voltage (Un) 100V, 110V 200V
Linear to 0.01Un~1.7Un
Thermal withstand
-continuously 2.0Un 1.1Un
-10s 2.6Un 1.9Un
-1s 3.0Un 2.1Un
Burden at rated < 0.25VA/phase @Un < 0.8VA/phase @Un

2.1.2 Power Supply

Standard IEC 60255-11:2008


Rated Voltage 110VDC/125VDC, 220VDC/250VDC
Variation 80%Un~120%Un
Permissible AC ripple
≤15% of the nominal auxiliary voltage
voltage
Burden
Quiescent condition <25W
Operating condition <55W

NR ELECTRIC CO., LTD. 7


Chapter 2 Technical Data

2.1.3 Binary Input

Rated Voltage (Un) 24V, 48V, 110V, 125V, 220V, 250V


Maximal pickup
70%Un
voltage
Minimum dropout
55%Un
voltage
Maximum
120%Un
permissible voltage
Withstand 2000VAC, 2800VDC
Resolving time for
<1ms
logic input

2.1.4 Binary Output

Item Signal contact


Output mode Potential free contact
8A@250V AC
Continuous carry
5A@30V DC
Pickup time <10ms
Breaking capacity 0.3A@220VDC resistance
Making capacity
3040VA
(L/R=40ms)
Maximal system 380V AC
voltage 250V DC
Test voltage across
1200V RMS for 1min
open contact
Short duration current 35A@0.5s
Loaded
100,000 operations minimum
contact
Durability
Unloaded
10,000,000 operations minimum
contact

2.1.5 Power Supply Output for Opto-coupler

Standard IEC 60255-1


Rated Voltage 24V
Rated Current 200mA
Maximal current 500mA

2.2 Mechanical Specifications

Enclosure dimensions
482.6mm×177.0mm×291.0mm(4U)
(W×H×D)
Mounting Way Flush mounted

8 NR ELECTRIC CO., LTD.


Chapter 2 Technical Data

Trepanning dimensions
450.0mm×179.0mm(4U), M6 screw
(W×H)
Housing color Silver grey
Weight per device Approx. 15kg
Housing material Aluminum
Location of terminal Rear panel of the device
Protection class
Standard IEC 60225-1:2009
Front side IP40, up to IP51 (Flush mounted)
Other sides IP30
Rear side, connection
IP20
terminals
Pollution degree 2

2.3 Wiring Terminals

AC current Crimp terminals,M4 screw, 2.5mm2~6.0mm 2 lead


AC voltage Jointing terminals, 1.5mm2~2.5mm 2 lead
Power supply, I/O Jointing terminals, 1.5mm2~2.5mm 2 lead
2
Earth BVR type, 2.5mm²~6.0mm lead, yellow and green stub connections

2.4 Ambient Temperature and Humidity Range

Standard IEC 60225-1:2009


Operating temperature -40°C to +70°C
Transport and storage
-40°C to +70°C
temperature range
Permissible humidity 5%-95%, condensation not permissible
Altitude <3000m

2.5 Communication Port

2.5.1 EIA-485 Port

Baud rate 4.8kbit/s, 9.6kbit/s, 19.2kbit/s, 38.4kbit/s, 57.6kbit/s, 115.2kbit/s


Protocol IEC 60870-5-103:1997
Maximal capacity 32
Transmission distance <500m
Safety level Isolation to ELV level
Twisted pair Screened twisted pair cable

NR ELECTRIC CO., LTD. 9


Chapter 2 Technical Data

2.5.2 Ethernet Port


Connector type RJ-45
Transmission rate 100Mbits/s
Transmission standard 10Base-T/100Base-TX
Transmission distance <100m
Protocol IEC 60870-5-103:1997 or IEC 61850
Safety level Isolation to ELV level

2.5.3 Optical Fiber Port

Characteristic Plastic optical fiber Glass optical fiber


Terminal BFOC/2.5 (OR F-SMA) BFOC/2.5 (OR F-SMA)
Fiber size Step-index 980/1000 μm Graded-index 62.5/125 μm
Transmission distance Up to 40m Up to 1000m
Wave length 660nm 820nm~860nm
Temperature range -5°C ~+55°C -5°C ~+55°C
Transmission power Min. -7dBm Min. -16dBm
Minimum receiving
Min. -20dBm Min. -24dBm
power
System reserve Min +3dB Min +3dB

2.5.4 Print Port

Type RS-232
Baud Rate 4.8kbit/s, 9.6kbit/s, 19.2kbit/s, 38.4kbit/s, 57.6kbit/s, 115.2kbit/s
Printer type EPSON® 300K printer
Safety level Isolation to ELV level

2.5.5 Clock Synchronization Port


Type RS-485
Transmission distance <500m
Maximal capacity 32
Timing standard PPS, IRIG-B
Safety level Isolation to ELV level

2.5.6 Debugging Port

Type RS-232
Baud Rate Recommended: 115.2kbit/s
Connector type 9-pin serial port
Safety level Isolation to ELV level

10 NR ELECTRIC CO., LTD.


Chapter 2 Technical Data

2.6 Type Tests

2.6.1 Environmental Tests

Dry cold test Per IEC60068-2-1:2007


Dry heat test Per IEC60068-2-2:2007
Damp heat test, cyclic Per IEC60068-2-30:2005

2.6.2 Mechanical Tests

Vibration Per IEC 60255-21-1:1988 Class I


Shock and bump Per IEC 60255-21-2:1988 Class I

2.6.3 Electrical Tests

Standard IEC 60255-27:2005


Dielectric tests Test voltage 2kV, 50Hz, 1min
Standard IEC 60255-5:2000
Impulse voltage tests Test voltage 5kV
Overvoltage category Ⅲ
Insulation resistance
Isolation resistance >100MΩ@500VDC
measurements

2.6.4 Electromagnetic Compatibility

Per IEC 60255-22-1:2007


1MHz burst disturbance test Common mode: class III 2.5kV
Differential mode: class III 1.0kV
Per IEC60255-22-2:2008 class IV
Electrostatic discharge test For contact discharge: 8kV
For air discharge: 15kV
Per IEC 60255-22-3:2007 class III
Frequency sweep
Radiated amplitude-modulated
10V/m (rms), f=80… 1000MHz
Radio frequency interference tests Spot frequency
Radiated amplitude-modulated
10V/m (rms), f=80MHz/160MHz/450MHz/900MHz
Radiated pulse-modulated
10V/m (rms), f=900MHz
Per IEC 60255-22-4:2008
Fast transient disturbance tests Power supply, I/O, Earth: class IV, 4kV, 2.5kHz, 5/50ns
Communication terminals: class IV, 2kV, 5kHz, 5/50ns
Per IEC 60255-22-5:2008
Surge immunity test Power supply, AC input, I/O port: class IV, 1.2/50us
Common mode: 4kV

NR ELECTRIC CO., LTD. 11


Chapter 2 Technical Data

Differential mode: 2kV


Per IEC 60255-22-6:2001
Conducted RF Electromagnetic
Power supply, AC, I/O, Comm. Terminal: Class III,
Disturbance
10Vrms,150 kHz~80MHz
Power Frequency Magnetic Field Per IEC 61000-4-8:2001
Immunity class V, 100A/m for 1min, 1000A/m for 3s
Per IEC 61000-4-9:2001
Pulse Magnetic Field Immunity
class V, 6.4/16μs, 1000A/m for 3s
Damped oscillatory magnetic field IEC 61000-4-10:2001
immunity class V, 100kHz & 1MHz–100A/m
Voltage short interruptions 200ms for interruption without de-energizing
Voltage dips Up to 10s for 60%Un dips without reset

2.7 Performance
2.7.1 Metering Scope and Accuracy

Range Accuracy
AC Current 0.2 ~ 1.5×In ≤ 1% In
AC Voltage 0.2 ~ 1.2×Un ≤ 1% Un
≤1% of reading at unity power
Active Power (W) 0.2 ~ 1.2×Un, 0.2 ~ 1.5×In
factor

2.7.2 Sampling

Sampling Rate 1.2kHz to 9.6kHz


Sampling Mode Synchronous sampling
SOE Resolution 1ms

2.8 Certification

 ISO9001: 2000

 ISO14001:2004

 OHSAS18001: 1999

 ISO10012:2003

 CMMI L3

 EMC: 89/336/EEC, EN50263: 2000

 Products safety(PS): 73/23/EEC, EN61010-1: 2001, EN60950: 2002

12 NR ELECTRIC CO., LTD.


Chapter 3 Software Description

Chapter 3 Software Description

3.1 Trigger Mode

 Sudden increase of phase voltage trigger and sudden increase of zero-sequence voltage
trigger.

 Sudden increase of phase current trigger and sudden increase of zero-sequence current
trigger.

 Phase overcurrent trigger.

 Phase overvoltage trigger and undervoltage trigger.

 Negative sequence component startup

 Overfrequency trigger, underfrequency trigger and rate of change of frequency trigger.

 Switching value startup

 Binary input trigger.

 Low-frequency oscillation trigger.

 Manual trigger and remote trigger

3.2 Recording Mode

t = 0ms: The start time of disturbance

A B C

S T

Figure 3.2-1 Time stage sequence of waveform recording

Where:

A, B, C are 3 time stages of waveform recording duration.

S is the start time of the time stage A.

T is a moment during the time stage B.

The waveform recording will be carried out in the sequence shown in above figure.

 Time stage A: Record the data before a disturbance, output original recorded waveform
and the recording duration ≥40ms.

NR ELECTRIC CO., LTD. 13


Chapter 3 Software Description

 Time stage B: Record the data of early stage after a disturbance, output original recorded
waveform and the recording duration ≥0.1s.

 Time stage C: Record the data of middle stage after a disturbance, output continuous RMS
values at standard power frequency (e.g.: 50Hz) and the recording time≥1s.

 Initial trigger: When any trigger condition is met, the wave recoding will be carried out from
the moment S in a sequence of time stages A, B, C.

 Repeated trigger: During the process of recording, if there is an output of a binary input or
a sudden change of quantity in the Time stage B, the recording will be carried out
repeatedly from the moment T in a sequence of Time stage B & Time stage C. Otherwise
the recording is carried out repeatedly from the moment S in a sequence of Time stage A,
Time stage B, Time stage C.

 Automatic recording termination condition: All trigger quantities reset.

NOTE: As for the timestamp of output data, the start time of a disturbance is taken as the

zero point of time coordinate for this event such as a short-circuit fault. Recording
durations and sampling rates of each time stage can be set manually.

3.3 Data Storage

2 waveform recording methods and 3 storage locations are adopted in the application of
PCS-996R:

1) Transient disturbance & fault recording and storage.

2) Continuous disturbance & fault recording and storage.

3) Storage in local DFR analysis workstation.

After the occurrence of system disturbance, PCS-996R will start disturbance & fault recording at
the sampling rate up to 9.6KHz, and the data will be stored in local CF card (Capacity: 2G). These
data are so-called transient disturbance & fault recording data.

No matter there is system disturbance or not, PCS-996R keeps on disturbance & fault recording at
the sampling rate of 1.2KHz continuously, and the data will be stored in local CF card (Capacity:
32G). These data are so-called continuous disturbance & fault recording data.

The transient disturbance & fault recording data and the continuous disturbance & fault
recording data can be sent to local DFR analysis workstation to be analyzed and stored. When
there is no spare storage space in the CF card of PCS-996R or the hard disk of the local DFR
analysis workstation, the latest data will overwrite the oldest data.

Thus the style of 2 waveform recording methods and 3 storage locations is realized to ensure the
integral reliability of the storage of the disturbance & fault recording data.

2 independent CPU modules are used to realize transient disturbance & fault recording and

14 NR ELECTRIC CO., LTD.


Chapter 3 Software Description

steady disturbance & fault recording respectively. In this way, the relative independence in
hardware and software are ensured and the integral reliability of the device is enhanced.

NR ELECTRIC CO., LTD. 15


Chapter 3 Software Description

16 NR ELECTRIC CO., LTD.


Chapter 4 Automatic Supervision

Chapter 4 Automatic Supervision

4.1 Understand Alarm Signals

Under some certain conditions, alarm signals will be issued on the LCD and can be sent out via
ethernet ports, the yellow “ALARM”LED indicator on the front panel of PCS-996R will also be lit
on, alarm contact outputs “BO_ALM”on the PWR module on B00 will also be provided.

Please refer to Chapter 4 for the “ALARM”LED indicator on the front panel.

NOTE:Please refer to Chapter 5 for the description of “B01”, “B02”… “B15”, “B00”.

Table 4.1-1 Description of alarm signals

No. Signal Description


If PCS-996R can not receive any clock synchronization
1 Alm_TimeSync signals,[Alm_TimeSync] will be issued and it can be sent
out via ethernet ports.
When dual network of the GOOSE module on B14 is
configured, if the NET A link of the GOOSE module is
2 GAlm_NetADisconnected
disconnected, [GAlm_NetADisconnected] will be issued
and it can be sent out via ethernet ports.
When dual network of the GOOSE module on B14 is
configured, if the NET B link of the GOOSE module is
3 GAlm_NetBDisconnected
disconnected, [GAlm_NetBDisconnected] will be issued
and it can be sent out via ethernet ports.
When single network of the GOOSE module on B14 is
configured, if the ethernet link of the GOOSE module on
4 GAlm_NetDisconnected
B14 is disconnected, [GAlm_NetDisconnected] will be
issued and it can be sent out via ethernet ports.

Some attributes (such as GoCBRef, GoID, DatSet,


ConfRev, numDatSetEntries, etc.) of the GOOSE control
blocks (GOCB for short) of the GOOSE publisher and the
5 GAlm_CfgUnmatched
GOOSE subscriber must be the same, and the data type
in the GOOSE data sets must be the same, otherwise
[GAlm_CfgUnmatched] will be issued.

The BI module (NR1502) gets the power supply via Pin


14 and Pin 15 of the BI module itself.
6 Alm_Pwr_BI_B10
The IO module (NR1525) gets the power supply via Pin
21 and Pin 22 of the IO module itself.
If Pin 14/15 of the BI module on B10 or Pin 21/22 of the

NR ELECTRIC CO., LTD. 17


Chapter 4 Automatic Supervision

IO module on B10 are not connected to valid binary input


auxiliary power, [Alm_Pwr_BI_B10] will be issued and it
can be sent out via ethernet ports.
If Pin 14/15 of the BI module on B11 or Pin 21/22 of the
IO module on B11 are not connected to valid binary input
7 Alm_Pwr_BI_B11
auxiliary power, [Alm_Pwr_BI_B11] will be issued and it
can be sent out via ethernet ports.
If Pin 14/15 of the BI module on B12 or Pin 21/22 of the
IO module on B12 are not connected to valid binary input
8 Alm_Pwr_BI_B12
auxiliary power, [Alm_Pwr_BI_B12] will be issued and it
can be sent out via ethernet ports.
If Pin 14/15 of the BI module on B13 or Pin 21/22 of the
IO module on B13 are not connected to valid binary input
9 Alm_Pwr_BI_B13
auxiliary power, [Alm_Pwr_BI_B13] will be issued and it
can be sent out via ethernet ports.
If Pin 14/15 of the BI module on B14 or Pin 21/22 of the
IO module on B14 are not connected to valid binary input
10 Alm_Pwr_BI_B14
auxiliary power, [Alm_Pwr_BI_B14] will be issued and it
can be sent out via ethernet ports.

4.2 Understand Triggering Signals

Under some certain conditions, waveform recording will be triggered and corresponding signals
will be issued on the LCD and can be sent out via ethernet ports,, the red “REC”LED indicator on
the front panel of PCS-996R will also be lit on, but there is no alarm contact output.

Please refer to Chapter 4 for the “REC”LED indicator on the front panel.

Please refer to Chapter 7 for the details of the settings (such as the [Up_SudnIncr]) in the
following table.

Table 4.2-1 Description of triggering signals

No. Signal Description


For any one of the 3 phase voltages of a
component, when [En_Up_SudnIncr] is set as
“1”, if the sudden increment of this voltage is
1 Pkp_xxxx_Up_SudnIncr greater than [Up_SudnIncr], the waveform
recording will be triggered, and a signal named
as [Pkp_xxxx_Up_SudnIncr] will be issued and
it can be sent out via ethernet ports.
For any one of the 3 phase voltages of a
component, when [En_Up_SudnDecr] is set as
2 Pkp_xxxx_Up_SudnDecr
“1”, if the sudden decrement of this voltage is
greater than [Up_SudnDecr], the waveform

18 NR ELECTRIC CO., LTD.


Chapter 4 Automatic Supervision

recording will be triggered, and a signal named


as
[Pkp_xxxx_Up_SudnDecr] will be issued and it
can be sent out via ethernet ports.
When [En_Up_UpLmt] is set as “1”, if Ua of a
component is greater than [Up_UpLmt], the
3 Pkp_xxxx_Ua_UpLmt waveform recording will be triggered, and a
signal named as [Pkp_xxxx_Ua_UpLmt] will be
issued and it can be sent out via ethernet ports.
When [En_Up_LowLmt] is set as “1”, if Ua of a
component is less than [Up_LowLmt], the
waveform recording will be triggered, and a
4 Pkp_xxxx_Ua_LowLmt
signal named as [Pkp_xxxx_Ua_LowLmt] will
be issued and it can be sent out via ethernet
ports.
When [En_Up_UpLmt] is set as “1”, if Ub of a
component is greater than [Up_UpLmt], the
5 Pkp_xxxx_Ub_UpLmt waveform recording will be triggered, and a
signal named as [Pkp_xxxx_Ub_UpLmt] will be
issued and it can be sent out via ethernet ports.
When [En_Up_LowLmt] is set as “1”, if Ub of a
component is less than [Up_LowLmt], the
waveform recording will be triggered, and a
6 Pkp_xxxx_Ub_LowLmt
signal named as [Pkp_xxxx_Ub_LowLmt] will
be issued and it can be sent out via ethernet
ports.
When [En_Up_UpLmt] is set as “1”, if Uc of a
component is greater than [Up_UpLmt], the
7 Pkp_xxxx_Uc_UpLmt waveform recording will be triggered, and a
signal named as [Pkp_xxxx_Uc_UpLmt] will be
issued and it can be sent out via ethernet ports.
When [En_Up_LowLmt] is set as “1”, if Uc of a
component is less than [Up_LowLmt], the
waveform recording will be triggered, and a
8 Pkp_xxxx_Uc_LowLmt
signal named as [Pkp_xxxx_Uc_LowLmt] will
be issued and it can be sent out via ethernet
ports.
When [En_U2_UpLmt] is set as “1”, if the
negative sequence voltage of a component is
greater than [U2_UpLmt], the waveform
9 Pkp_xxxx_U2_UpLmt
recording will be triggered, and a signal named
as [Pkp_xxxx_U2_UpLmt] will be issued and it
can be sent out via ethernet ports.
10 Pkp_xxxx_U0_SudnChg When [En_U0_SudnChg] is set as “1”, if the

NR ELECTRIC CO., LTD. 19


Chapter 4 Automatic Supervision

sudden change of the zero sequence voltage of a


component is greater than [U0_SudnChg], the
waveform recording will be triggered, and a
signal named as [Pkp_xxxx_U0_SudnChg] will
be issued and it can be sent out via ethernet
ports.
When [En_U0_UpLmt] is set as “1”, if the zero
sequence voltage of a component is greater than
[U0_UpLmt], the waveform recording will be
11 Pkp_xxxx_U0_UpLmt
triggered, and a signal named as
[Pkp_xxxx_U0_UpLmt] will be issued and it can
be sent out via ethernet ports.
When [En_f_UpLmt] is set as “1”, if the
frequency of a component is higher than
[f_UpLmt], the waveform recording will be
12 Pkp_xxxx_f_UpLmt
triggered, and a signal named as
[Pkp_xxxx_f_UpLmt] will be issued and it can
be sent out via ethernet ports.
When [En_f_LowLmt] is set as “1”, if the
frequency of a component is lower than
[f_LowLmt], the waveform recording will be
13 Pkp_xxxx_f_LowLmt
triggered, and a signal named as
[Pkp_xxxx_f_LowLmt] will be issued and it can
be sent out via ethernet ports.
When [En_f_df/dt] is set as “1”, If the df/dt of a
component is greater than [df/dt], the waveform
14 Pkp_xxxx_df/dt recording will be triggered, and a signal named
as [Pkp_xxxx_df/dt] will be issued and it can be
sent out via ethernet ports.
For any one of the 3 phase currents of a
component, when [En_Ip_SudnChg] is set as
“1”, if the sudden change of this current is greater
15 Pkp_xxxx_Ip_SudnChg than [Ip_SudnChg], the waveform recording will
be triggered, and a signal named as
[Pkp_xxxx_Ip_SudnChg] will be issued and it
can be sent out via ethernet ports.
When [En_Ip_UpLmt] is set as “1”, if Ia of a
component is greater than [Ip_UpLmt], the
16 Pkp_xxxx_Ia_UpLmt waveform recording will be triggered, and a
signal named as [Pkp_xxxx_Ia_UpLmt] will be
issued and it can be sent out via ethernet ports.
When [En_Ip_UpLmt] is set as “1”, if Ib of a
17 Pkp_xxxx_Ib_UpLmt component is greater than [Ip_UpLmt], the
waveform recording will be triggered, and a

20 NR ELECTRIC CO., LTD.


Chapter 4 Automatic Supervision

signal named as [Pkp_xxxx_Ib_UpLmt] will be


issued and it can be sent out via ethernet ports.
When [En_Ip_UpLmt] is set as “1”, if Ic of a
component is greater than [Ip_UpLmt], the
18 Pkp_xxxx_Ic_UpLmt waveform recording will be triggered, and a
signal named as [Pkp_xxxx_Ic_UpLmt] will be
issued and it can be sent out via ethernet ports.
When [En_I2_UpLmt] is set as “1”, if the
negative sequence current of a component is
greater than [I2_UpLmt], the waveform recording
19 Pkp_xxxx_I2_UpLmt
will be triggered, and a signal named as
[Pkp_xxxx_I2_UpLmt] will be issued and it can
be sent out via ethernet ports.
When [En_I0_SudnChg] is set as “1”, if the
sudden change of the zero sequence current of a
component is greater than [I0_SudnChg], the
20 Pkp_xxxx_I0_SudnChg waveform recording will be triggered, and a
signal named as [Pkp_xxxx_I0_SudnChg] will
be issued and it can be sent out via ethernet
ports.
When [En_I0_UpLmt] is set as “1”, if the zero
sequence current of a component is greater than
[I0_UpLmt], the waveform recording will be
21 Pkp_xxxx_I0_UpLmt
triggered, and a signal named as
[Pkp_xxxx_I0_UpLmt] will be issued and it can
be sent out via ethernet ports.
The setting [k_Ripple] is used for detecting
power swing. When [En_k_Ripple] is set as “1”,
If a power swing is detected by PCS-996R, the
22 Pkp_xxxx_k_Ripple
waveform recording will be triggered. , and a
signal named as [Pkp_xxxx_k_Ripple] will be
issued and it can be sent out via ethernet ports.

NOTE:In the above table, xxxx is the name of a component (i.e.: a busbar, a line or a

transformer branch). It can be composed of digits or characters.

NOTE:In the above tables, the total length of the alarm/triggering signals must be <=29

characters.

NR ELECTRIC CO., LTD. 21


Chapter 4 Automatic Supervision

22 NR ELECTRIC CO., LTD.


Chapter 5 Hardware Description

Chapter 5 Hardware Description

5.1 Overview

PCS-996R is made of a 4U height 19”chassis for panel flush mounting. Components mounted on
its front include a 320×240 dot matrix LCD, a 9 button keypad, 3 LED indicators and a 9 pin
connector for communication with PC.

The front panel of PCS-996R is shown in the following figure.

Figure 5.1-1 Front panel of PCS-996R

There is a multiplex RJ45 port in the front panel of PCS-996R. This port can be used as an
RS-232 serial port as well as a twisted-pair ethernet port. As shown in the following figure, a
customized cable is applied for debugging via this multiplex RJ45 port.

Figure 5.1-2 The corresponding cable of the RJ45 port in the front panel of PCS-996R

In the above figure and the following table:


P1: To connect the multiplex RJ45 port. An 8-core cable is applied here.
P2: To connect the twisted-pair ethernet port of the computer.
P3: To connect the RS-232 serial port of the computer.
The definition of the 8-core cable in the above figure is introduced in the following table.

NR ELECTRIC CO., LTD. 23


Chapter 5 Hardware Description

Table 5.1-1 The definition of the 8-core cable

PCS-996R Computer
Pin No. Core color Function
side(Left) side(Right)
1 Orange TX+ of the ethernet port P1-1 P2-1
2 Orange & white TX- of the ethernet port P1-2 P2-2
3 Green & white RX+ of the ethernet port P1-3 P2-3
TXD of the RS-232 serial
4 Blue P1-4 P3-2
port
RXD of the RS-232 serial
5 Brown & white P1-5 P3-3
port
6 Green RX- for the ethernet port P1-6 P2-6
7 Blue & white The ground connection of P1-7
P3-5
8 Brown the RS-232 port. P1-8

The rear view of PCS-996R in typical application is shown in the following figure. The details of
each module will be introduced in the following sections.
Portable PC for
DFR analysis Twisted-pair
Transient Wave Recording Continous Wave Recording
Optical Fiber
Cable
B01 B02 B03 B04 B05 B06 B07 B08 B09 B10 B11 B12 B13 B14 B15 B00
NR1102E NR1156A NR 1401 NR 1401 NR 1401 NR 1502 NR1502 NR1502 NR1502 NR 1126C NR 1102E NR 1301
1 2 3 5V OK ALM
ETHERNET 1 2 3

BO_ ALM BO_FAIL


4 5 6 4 5 6

TX

RX 1 BO _COM1

DANGER DANGER DANGER 2 BO_FAIL

3 BO_ALM
TX 4 BO _COM2

BO_FAIL
5
RX 6 BO_ALM

7 OPTO +

8 OPTO-

10 PWR +

11 PWR -

12 GND

GOOSE Network
Binary Inputs
Anolog Inputs

Figure 5.1-3 The rear view of PCS-996R in typical application

The PCS-996R adopts modularized hardware design. Different functional modules are
shown in the following table.

Table 5.1-2 Hardware Configuration of PCS-996R

Device Type The number of this module that


Module Type
Module Type can be equipped in PCS-996R
2 subtypes of CPU modules(i.e.:
CPU module 2 NR1102E, NR1102J ) are
optional.
DSP module 1 NR1156A

24 NR ELECTRIC CO., LTD.


Chapter 5 Hardware Description

2 subtypes of GOOSE modules


AI module 1 or 2 or 3 or 4 ( i.e.: NR1401,NR1415 ) are
optional.
2 subtypes of GOOSE modules
BI module 1 or 2 or 3 or 4 or 5 (i.e.: NR1502A,NR1502D) are
optional.
IO module 1 or 2 or 3 or 4 or 5 NR1525
4 subtypes of GOOSE modules
( i.e.:
GOOSE module 0 or 1
NR1126A,NR4126B,NR4126C,
NR4126C) are optional.
PWR module 1 NR1301

NOTE: The medium of the ethernet interface of the CPU module and GOOSE module is

optional. Different subtypes of the CPU module and GOOSE module correspond to
different ethernet interface medium.

NOTE: The hardware configuration of the PCS-996R must be definitely declared in the

technical scheme and the contract.

There are 16 slots in the rear panel of PCS-996R, these slots are named as B01~B1 5 and
B00 from left to right by the rear view of PCS-996R.

Table 5.1-3 Module/slot configuration list

Module Type Corresponding slot


B01 and B15 must be equipped with the CPU module.
CPU module
CPU module can only be installed in B01 or B15.
B03 must be equipped with the DSP module.
DSP module
DSP module can only be installed in B03.
B04~B11 can be equipped with the AI module.
B04~B09 can only be equipped with the AI module.
AI module can only be installed in B04~B11.
AI module
NOTE: 2 AI modules are optional: NR1401 occupies 2

slots, but NR1415 only occupy 1slot.

B10 ~ B14 can be equipped with the BI module.


BI module B12 ~ B13 can only be equipped with the BI module.
BI module can only be installed in B10 ~ B14.
B14 can be equipped with the GOOSE module.
GOOSE module
GOOSE module can only be installed in B14.

NR ELECTRIC CO., LTD. 25


Chapter 5 Hardware Description

B00 must be equipped with the PWR module.


PWR module
PWR module can only be installed in B00.

5.2 Plug-in Modules

5.2.1 CPU Module(NR1102) on B01 and B15


CPU module is a core module of PCS-996R.

NOTE:2 CPU modules must be configured in PCS-996R. One is installed in B01, and

the other is installed in B15.

CPU module is composed of embedded processor with high performance, FLASH, SRAM,
SDRAM, Ethernet controller and other peripheral equipments.

CPU module can realize the functions of waveform recording, management, HMI, communication
and other functions of PCS-996R.

CPU module receives data from other modules via internal bus.

CPU module communicates LCD via RS-485 bus.

2 types of CPU modules(i.e.: NR1102E, NR1102J)are optional as shown in the following 2


figures.

The 1st type of CPU module (NR1102E) as shown in the following figure has 2 electrical ethernet
ports, but has no fiber ethernet port.

26 NR ELECTRIC CO., LTD.


Chapter 5 Hardware Description

NR1102E

ETHERNET

Ethernet 1

Ethernet 2

CF Card Slot

1 SYN+
GPS IRIG-B Signal
2 SYN-
3 SGND
4 Reserved

5 RXD To the Printers or


6 TXD Printer Controllers
7 SGND

Figure 5.2-1 CPU module (NR1102E)

The connectors of both the 2 types of the CPU modules have the same connectors as shown in
the following table.

NR ELECTRIC CO., LTD. 27


Chapter 5 Hardware Description

Table 5.2-1 Pin description of CPU module

Pin No. Description

RS-485 serial port to receive PPS or


1 A of the RS-485 port. IRIG-B clock synchronization signals.
IRIG-B is recommended.
Shield cables with 2 pairs of twisted-pair
cable are recommended.
One pair of the twisted-pair cable should
2 B of the RS-485 port.
be connected to the Pin 1 and Pin 2 of
the RS-485 port respectively.
Another pair of the twisted-pair cable
SGND: should be connected to Pin 3.
The ground connection of the The SGND of all the devices connected in
3
RS-485 port. the same bus should be connected
together with this pair of twisted-pair cable.

4 Reserved Reserved

5 RXD of the RS-232 port.

6 TXD of the RS-232 port. RS-232 serial port to link printers or printer
controllers.

SGND:
7 The ground connection of the
RS-232 port.

The 2nd type of CPU (NR1102J) as shown in the following figure has 2 ST multimode type fiber
ethernet ports and 2 twisted-pair ethernet ports.

28 NR ELECTRIC CO., LTD.


Chapter 5 Hardware Description

NR1102J

TX
Ethernet 1 ST Fiber optic
RX

TX
Ethernet 2 ST Fiber optic
RX

Ethernet 3 Twisted-pair

Ethernet 4 Twisted-pair

1 SYN+
GPS IRIG-B Signal
2 SYN-
3 SGND
4 Reserved

5 RXD To the Printers or


6 TXD Printer Controllers
7 SGND

Figure 5.2-2 CPU module (NR1102J)

5.2.2 DSP Module (NR1156A) on B03

NOTE:1 DSP modules must be configured in B03 of PCS-996R.

This module consists of DSP with high performance, A/D sampler and etc.

DSP module (NR1156A) supports the conventional analog sampling, and can realize the function
of data acquisition, logic calculation and triggering disturbance & fault recording.

The DSP module(NR1156A) is shown in the following figure.

NR ELECTRIC CO., LTD. 29


Chapter 5 Hardware Description

Figure 5.2-3 DSP module(NR1156A)

There are 6 LED indicators in the front of the DSP module(NR1156A).

The LED indicators of the DSP module(NR1156A) are described in the following table.

Table 5.2-2 Description of the LED indicators of the DSP module(NR1156A)

Pin No. Description

1 Lit on during the initialization of the device. Steady off during normal operation.
2 Reserved.
3 Reserved.
4 Reserved.
5 Reserved.
6 Flash during normal operation. It will be lit on every second.

5.2.3 AI Module(NR1401/NR1415)on B04~B11 (Optional)

NOTE:AI module(NR1401/NR1415)is an optional module. But in application, this

module is often applied because analog inputs are often necessary for PCS-996R.

Several analog inputs module (AI module for short) are optional for PCS-996R.

The optional subtypes of AI module are shown in the following table.

30 NR ELECTRIC CO., LTD.


Chapter 5 Hardware Description

Table 5.2-3 The optional subtypes of AI module

Pin No. Sign Description Remark


01 12 voltage inputs. Occupy 2 slots
02 NR1401 12 current inputs. Occupy 2 slots
03 6 voltage inputs & 6 current inputs. Occupy 2 slots
6 clamp-on current inputs

AI module(NR1415) is designed
04 NR1415 Occupy 1 slot
for a special clamp-on CT whose
rated secondary current is 200mA.

The AI module(NR1401) with 12 voltage inputs and its pin description are shown in the following
figure.

NR1401
NR1401
U1 01 U1n 02

01 02 U2 03 U2n 04

03 04 U3 05 U3n 06
05 06
07 08 U4 07 U4n 08

09 10 U5 09 U5n 10

11 12 U6 11 U6n 12
13 14
U7 13 U7n 14
15 16
17 18 U8 15 U8n 16

19 20 U9 17 U9n 18
21 22
23 24 U10 19 U10n 20
U11 21 U11n 22
U12 23 U12n 24

Figure 5.2-4 AI module(NR1401) with 12 voltage inputs

The AI module(NR1401) with 12 current inputs and its pin description are shown in the following
figure.

NR ELECTRIC CO., LTD. 31


Chapter 5 Hardware Description

Figure 5.2-5 AI module(NR1401) with 12 current inputs

The AI module(NR1401) with 6 voltage inputs & 6 current inputs and its pin description are shown
in the following figure.

NR1401
NR1401
IA1 01 IA1 n 02

01 02 IB1 03 IB1 n 04
03 04
IC1 05 IC1 n 06
05 06
07 08 IA2 07 IA2 n 08

09 10 IB2 09 IB2 n 10
11 12
IC2 11 IC2 n 12
13 14
UA1 13 UA1n 14
15 16
17 18 UB1 15 UB1n 16
19 20 UC1 17 UC1n 18
21 22
23 24 UA2 19 UA2n 20

UB2 21 UB2n 22

UC2 23 UC2n 24

Figure 5.2-6 AI module(NR1401) with 6 voltage inputs & 6 current inputs

Typical wiring method of the AI module(NR1401) with 6 voltage inputs & 6 current inputs is shown
in the following figure.

32 NR ELECTRIC CO., LTD.


Chapter 5 Hardware Description

A
B CB
C

01 IA 13 UA
02 14

03 IB 15 UB
04 16

05 IC 17 UC
06 18

Figure 5.2-7 Typical wiring method of AI module with 6 voltage inputs and 6 current inputs

The AI module(NR1415) and its pin description are shown in the following figure.

Figure 5.2-8 AI module (NR1415) with 6 clamp-on current inputs

NR ELECTRIC CO., LTD. 33


Chapter 5 Hardware Description

5.2.4 BI Module(NR1502)on B10~B14 (Optional)

NOTE:BI module(NR1502)is an optional module. But in application, this module is

often applied because analog inputs are often necessary for PCS-996R.

Intelligent binary input module (BI module for short) (NR1502) can supervise 24 binary inputs at
the same time and transmit binary inputs to other modules by inner bus.

NR1502A and NR1502D share the same pin definition, only their working voltages of all the binary
inputs are different.

For NR1502D, the rated working voltage of all the binary inputs is 24V/48V;

For NR1502A, the rated working voltage of all the binary inputs is 220/110V.

When the voltage of binary input is greater than 70% of rated working voltage, the binary input is
energized;

When the voltage of binary input is smaller than 60% of rated working voltage, the binary input is
de-energized.

BI module (NR1502A) and its typical wiring connection are shown in the following figure.

In this figure, the BI module (NR1502A) gets the 110V/220V power supply from Pin 10 and Pin 11
of the PWR module of the device itself.

Pin 14 of the BI module(NR1502A) is connected to Pin 10 of the PWR module.

Pin 15 of the BI module(NR1502A) is connected to Pin 11 of the PWR module.

PWR Module
10 110 V/220 V PWR+ Output
11 110V/ 220V PWR- Output

NR1502 14 110 V/220V OPTO_ H+ Input


15 110 V/220 V OPTO_H- Input
01 Binary Input01
02 Binary Input02
01 03 Binary Input03
02
03 04 Binary Input04
04
05 05 Binary Input05
06
07 06 Binary Input06
08
09 07 Binary Input07
10
11 08 Binary Input08
12
09 Binary Input09
14
15 10 Binary Input10
17 11 Binary Input11
18
19 12 Binary Input12
20
21 17 Binary Input13
22
23 18 Binary Input14
24
25 19 Binary Input15
26
27 20 Binary Input16
28
29 21 Binary Input17
22 Binary Input18
23 Binary Input19
24 Binary Input20
25 Binary Input21
26 Binary Input22
27 Binary Input23
28 Binary Input24

Figure 5.2-9 BI module (NR1502A) and its typical wiring connection

34 NR ELECTRIC CO., LTD.


Chapter 5 Hardware Description

BI module (NR1502D) and its typical wiring connection are shown in the following figure.

In this figure, the BI module(NR1502D) gets the 24V power supply from Pin 07 and Pin 08 of the
PWR module of the device itself.

Pin 14 of the BI module(NR1502D) is connected to Pin 07 of the PWR module.

Pin 15 of the BI module(NR1502D) is connected to Pin 08 of the PWR module.

PWR Module
07 24V OPTO+ Output
08 24V OPTO- Output

NR1502 14 24V/48V OPTO_ L+ Input

15 24V/48V OPTO_ L- Input

01 Binary Input01
02 Binary Input02
01 03 Binary Input03
02
03 04 Binary Input04
04
05 05 Binary Input05
06
07 06 Binary Input06
08
09 07 Binary Input07
10
11 08 Binary Input08
12
09 Binary Input09
14
15 10 Binary Input10
17 11 Binary Input11
18
19 12 Binary Input12
20
21 17 Binary Input13
22
23 18 Binary Input14
24
25 19 Binary Input15
26
27 20 Binary Input16
28
29 21 Binary Input17
22 Binary Input18
23 Binary Input19
24 Binary Input20
25 Binary Input21
26 Binary Input22
27 Binary Input23
28 Binary Input24

Figure 5.2-10 BI module (NR1502D) and its typical wiring connection

Pin descriptions of the BI module are shown in the following table.

Table 5.2-4 Pin description of the BI module

Pin No. Sign Description Remark


01 Binary Input 01
02 Binary Input 02
03 Binary Input 03
04 Binary Input 04
05 Binary Input 05
06 Binary Input 06
07 Binary Input 07
08 Binary Input 08
09 Binary Input 09
10 Binary Input 10
11 Binary Input 11
12 Binary Input 12

NR ELECTRIC CO., LTD. 35


Chapter 5 Hardware Description

13 Reserved.
Positive pole of power supply for
OPTO_H+
opto-coupler (110V/220V).
(In NR1502A)
14 (In NR1502A)
OPTO_L+ Positive pole of power supply for Power supply of all
(In NR1502D) opto-coupler (24V/48V). the binary inputs on
OPTO_H- Negative pole of power supply for this module
(In NR1502A) opto-coupler (110V/220V)
15
OPTO_L- Negative pole of power supply for
(In NR1502D) opto-coupler(24V/48V).
16 Reserved.
17 Binary Input 13
18 Binary Input 14
19 Binary Input 15
20 Binary Input 16
21 Binary Input 17
22 Binary Input 18
23 Binary Input 19
24 Binary Input 20
25 Binary Input 21
26 Binary Input 22
27 Binary Input 23
28 Binary Input 24
29 Reserved.
30 Reserved.

5.2.5 IO Module (NR1525) on B10~B14(Optional)

NOTE:IO module(NR1525)is an optional module.

Binary inputs and binary outputs module (IO module for short) (NR1525) and its typical wiring
connection are shown in the following figure.

In this figure, the IO module gets the 110V/220V power supply from Pin 10 and Pin 11 of the PWR
module of the device itself.

Pin 21 of the IO module(NR1525) is connected to Pin 10 of the PWR module.

Pin 22 of the IO module(NR1525) is connected to Pin 11 of the PWR module.

36 NR ELECTRIC CO., LTD.


Chapter 5 Hardware Description

PWR Module
NR1525 10 110 V/ 220V PWR+ Output
11 110V/ 220V PWR- Output

01
21 110 V/220 V OPTO+ Input
02
03 22 110 V/220 V OPTO- Input

04 01
Tripping Output1
05 02
06 03
Tripping Output2
07 04
08 05
Tripping Output3
09 06
10 07
11 Tripping Output4
08
12 09 Binary Input 01
13 10 Binary Input 02
14
11 Binary Input 03
15
12 Binary Input 04
16
13 Binary Input 05
17
14 Binary Input 06
18
15 Binary Input 07
19
20 16 Binary Input 08
21 17 Binary Input 09
22 18 Binary Input 10
19 Binary Input 11
20 Binary Input 12

Figure 5.2-11 IO module(NR1525) and its typical wiring connection

Pin descriptions of the IO module(NR1525) are shown in the following table.

Table 5.2-5 Pin description of the IO module(NR1525)

Pin No. Sign Description Remark


01
Tripping Output1
02
03
Tripping Output2
04
05
Tripping Output3
06
07
Tripping Output4
08
09 Binary Input 01
10 Binary Input 02
11 Binary Input 03
12 Binary Input 04
13 Binary Input 05
14 Binary Input 06
15 Binary Input 07
16 Binary Input 08
17 Binary Input 09
18 Binary Input 10

NR ELECTRIC CO., LTD. 37


Chapter 5 Hardware Description

19 Binary Input 11
20 Binary Input 12
Positive pole of power supply for
21 OPTO+ Power supply of all
opto-coupler (110V/220V).
the binary inputs on
Negative pole of power supply for
22 OPTO- this module.
opto-coupler (110V/220V).

5.2.6 GOOSE Module (NR1126) on B14(Optional)


This module consists of high-performance digital signal processor, two 100M optical fiber Ethernet
and other peripherals. The module supports GOOSE function and IEC61850-9-2 protocol. Its
functions include that the device receives data from the merging unit and sending GOOSE
command to the intelligent control device etc. This module is not required when the GOOSE
function is not applied.

GOOSE module(NR1126) has 2 functions:

1) GOOSE module can be used for binary inputs/outputs (i.e.: tripping signals, open/close
of contacts, the state of CB/DS). This device can receive the message from GOOSE
network, and records GOOSE binary inputs if required.

2) GOOSE module can be used for analog sampling by adopting IEC61850-9-2 protocol.

In this way, GOOSE module can realize the function of data acquisition, logic calculation
and triggering fault disturbance recording.

4 optional types of the GOOSE module for this device are introduced in the following figure.

38 NR ELECTRIC CO., LTD.


Chapter 5 Hardware Description

Figure 5.2-12 Optional subtypes of GOOSE module

Table 5.2-6 Description of the optional subtypes of GOOSE module

Module ID Interface Physical Layer Description


NR1126A 2 Ethernet SC multi-mode optical fiber port
2 Ethernet SC multi-mode optical fiber port
NR1126B Support GOOSE and
IRIG-B ST multi-mode optical fiber port
IEC61850-9-2, receiving and
NR1126C 2 Ethernet ST multi-mode optical fiber port
sending data.
2 Ethernet ST multi-mode optical fiber port
NR1126D
IRIG-B ST multi-mode optical fiber port

There are 6 LED indicators on the GOOSE module.

The LED indicators of the GOOSE module are described in the following table.

NR ELECTRIC CO., LTD. 39


Chapter 5 Hardware Description

Table 5.2-7 Description of the LED indicators of the GOOSE module

LED No. Display Description Remarks

1 Reserved

No data is transmitted via


Off the 1st fiber optical port
from this device. The TX LED indicator of the 1st fiber
2
This device is transmitting optical port.
Flash as Green data via the 1st fiber optical
port.
No data is transmitted via
Off the 2nd fiber optical port
from this device. The TX LED indicator of the 2nd
3
This device is transmitting fiber optical port.
Flash as Green data via the 2nd fiber optical
port.
4 Reserved
No data is received via the
Off 1st fiber optical port from
The RX LED indicator of the 1st fiber
5 this device.
optical port.
This device is receiving data
Flash as Green
via the 1st fiber optical port.
No data is received via the
Off 2nd fiber optical port from
The RX LED indicator of the 2nd
6 this device.
fiber optical port.
This device is receiving data
Flash as Green
via the 2nd fiber optical port.

5.2.7 PWR Module (NR1301) on B00

NOTE:1 PWR module must be configured in B00 of PCS-996R.

The front view of the power supply module (PWR module for short)(NR1301) is shown in the
following figure.

40 NR ELECTRIC CO., LTD.


Chapter 5 Hardware Description

Figure 5.2-13 Front view of the PWR module(NR1301)

A 12-Pin male connector is fixed on the front of the PWR module. The pin definition of the
connector is described as below.

Table 5.2-8 Pin description of the PWR module(NR1301)

Pin No. Signal Description


1 BO_COM1 Common of the first group of binary outputs.
2 BO_FAIL Equipment failure output 1.
3 BO_ALM Equipment alarm output 1.
4 COM2 Common of the second group of binary outputs.
5 BO_FAIL Equipment failure output 2.

NR ELECTRIC CO., LTD. 41


Chapter 5 Hardware Description

6 BO_ALM Equipment alarm output 2.


7 OPTO+ The positive pole of the 24V DC output.
8 OPTO- The negative pole of the 24V DC output.
9 Not used.
10 PWR+ Positive pole of the 24V/110V/220V DC power supply.
11 PWR- Negative pole of the 24V/110V/220V DC power supply.
12 GND The frame ground connection for shielding.

The illustrative diagram of the contact outputs of the PCS-996R is shown in the following figure.
For a certain reason (e.g. standby, power loss or faulty condition), the PWR module is switched off,
the “BO_FAIL”(binary output of failure) contact will close and the “BO_ALM”(binary output of
alarm) contact will open.

Figure 5.2-14 Two groups of outputs of the PWR module(NR1301)

There are 4 LED indicators for the PWR module. These indicators can signal the operation state
of the PWR module.

The following figure shows the LED indicators of the PWR module.

Figure 5.2-15 LED indicators of the PWR module

The following table shows the description the LED indicators of the PWR module.

Table 5.2-9 Indicators description of the PWR module

Label Display Description


Off When the board is out of DC power supply or any fault in it.
5V OK
Steady Green Lit when the board works normally.
Off When the board is in normal operating condition.
ALM
Steady Yellow Lit when any abnormality alarm is issued.
Off when the board is in normal operating condition
Lit when there is a certain fault (hardware or software fault) in the
BO_ALM device. It is the same state with the “ALARM”indicator on the front
Steady Red
panel. Its state is also same with the contact outputs “BO_ALM”
(pin 3) and “BO_ALM”(pin 6) on this board.

42 NR ELECTRIC CO., LTD.


Chapter 5 Hardware Description

Off when the board is in normal operating condition


Lit when there is a certain fault that makes the device not work
BO_FAIL normally any more. It is the opposite state with the “HEALTHY”
Steady Red
indicator on the front panel. Its state is also same with the contact
outputs “BO_FAIL”(pin 2) and “BO_FAIL”(pin 5) on this board.

5.2.8 LCD & Keyboard


PCS-996R has a 320×240 dot matrix LCD and a 9 button keypad.
The keypad of PCS-996R is shown in the following figure.

Figure 5.2-16 Keypad of PCS-996R

The descriptions of the buttons on the keypad of PCS-996R are introduced as below.

1) “ESC”:

 Cancel the operation

 Quit the current menu

2) “ENT”:

 Execute the operation

 Confirm the interface

3) “GRP”

 Activate the switching interface of setting group

4) Leftward and rightward direction keys (“◄ ”and “► ”):

 Move the cursor horizontally

 Enter the next menu or return to the previous menu

5) Upward and downward direction keys (“▲ ”and “▼ ”)

 Move the cursor vertically

 Select command menu within the same level of menu

6) Plus and minus sign keys (“+”and “-”)

NR ELECTRIC CO., LTD. 43


Chapter 5 Hardware Description

 Modify the value

 Modify and display the message number

 Page up/down

5.2.9 LED Indicators of the Front Panel


There are 3 LED indicators on the front panel of PCS-996R. These indicators can signal the status
of the device.

The LED indicators of the PCS-996R are shown in the following figure.

Figure 5.2-17 LED indicators of the PCS-996R

The LED indicators of the PCS-996R are shown in the following figure.

Table 5.2-10 Description of LED indicators of the PCS-996R

Label Display Remarks


When the device is out of power supply or any hardware
defect (such as chip damage, check error of setting, etc.) is
Off
detected during self-test,
the “HEALTHY”LED will be off.
When the device runs normally after it is energized,
Steady Green
the “HEALTHY”LED will be lit on as green all the time.

When the device operates normally,


Off
the “ALARM”LED is off.

If any abnormality alarm is issued,


Steady Yellow
the “ALARM”LED will be lit on as yellow.

If this device is not recording disturbance & fault wave,


Off
the “REC”LED is off.

If this device is not recording disturbance & fault wave,


Steady Red the “REC”LED will be lit on as red.

The “REC” LED will be lit on when disturbance & fault

44 NR ELECTRIC CO., LTD.


Chapter 5 Hardware Description

recording is triggered.

Reserved.

NR ELECTRIC CO., LTD. 45


Chapter 5 Hardware Description

46 NR ELECTRIC CO., LTD.


Chapter 6 Human Machine Interface

Chapter 6 Human Machine Interface

6.1 Front Panel

The front panel of PCS-996R is shown in the following figure.

C G RP
ES

Figure 6.1-1 Front panel of PCS-996R

6.2 Understand the HMI Menu Tree


6.2.1 Overview

This section will mainly show the menu structure of the PCS-996R.

The following figure shows the menu tree structure of PCS-996R.

NOTE: An example of the menu tree of PCS-996R is shown in the following figure. In

engineering applications, the menu tree of PCS-996R may be different because some of
the submenus can be configured.

NR ELECTRIC CO., LTD. 47


Chapter 6 Human Machine Interface

Main menu

1.DeviceStatus 1. Unit1Measurment

2. Unit2Measurment

3. Unit3Measurment

4. Unit4Measurment
2.DeviceReports 1. FaultRecords 5. Unit5Measurment
2. BinaryEvents 6. Unit6Measurment
3. SelfSupervEvents
7. Unit7Measurment
4. DeviceLogs
8. Unit8Measurment

9. Unit9Measurment
3.DeviceSetting 1. DeviceParameter 10. Unit10Measurment

2. CalibrateSetting 11. Unit11Measurment

12. Unit12Measurment
3. VIRTUAL_LINK
13. Unit13Measurment

14. Unit14Measurment
4.LocalCommand 1. ManualTrigger
15. Unit15Measurment
2. Calibrate 16. Unit16Measurment

17. GOOSEBin
5.AdjustTime 18. NormalBin

19. SelfSupervInfo
6.Version

8.Debug 1. GooseInfo

2. BoardInfo

3. ItemActionReport

9.Environment 1. Language

Figure 6.2-1 “Main menu”of PCS-996R

The menus in this menu tree are introduced in the following sections.

48 NR ELECTRIC CO., LTD.


Chapter 6 Human Machine Interface

6.2.2 DeviceStatus

This menu is used for displaying the values of analog inputs, binary inputs and self-check
information.

6.2.3 DeviceReports
This menu is used for displaying the reports stored in this device.

There are 4 submenus in this menu:

1) FaultRecords:

This menu is used for displaying the fault records.

2) BinaryEvents:

This menu is used for displaying the state changes of the binary inputs.

3) SelfSupervEvents:

This menu is used for displaying the self-check information.

4) DeviceLogs:

This menu is used for displaying the operation logs of this device.

6.2.4 DeviceSetting

There are 3 submenus in this menu:

1) DeviceParameter:

This menu is used for setting the parameters of this device itself.

The parameters list of “DeviceParameter”of PCS-996R is introduced in the following table.

Table 6.2-1 Parameters list of “DeviceParameter”of PCS-996R

No. Name Example [Min:Max] (Step)(Unit)


1 StationID 0 [0:65535] (1)
2 IP_addr 198.120.0.33 (1)
3 Subnet_mask_addr 198.120.0.33 (1)
4 Gateway_addr 198.120.0.254 (1)
5 t_Prefault 0.040 s [0.040:1.000] (0.001)(s)
6 t_Postfault 0.1000s [0.100:1.000] (0.001)(s)
7 tmax_Duration_DFR 3.000 s [0.140:5.000] (0.001)(s)
8 En_StageC_RMS 0 [0:1] (1)

The description of “DeviceParameter”of PCS-996R is introduced in the following table.

NR ELECTRIC CO., LTD. 49


Chapter 6 Human Machine Interface

Table 6.2-2 Parameters description of “DeviceParameter”of PCS-996R

No. Name Description


The station ID of the device. This setting is used when this
1 StationID
device is connected to the DFR Manager System.
2 IP_addr The IP address of the device.
3 Subnet_mask_addr The subnet mask of the device.
4 Gateway_addr The gateway address of the device.
The setting of the duration for PCS-996R to record
5 t_Prefault
waveform before fault.
The setting of the duration for PCS-996R to record
6 t_Postfault
waveform after fault.
The setting of the maximum permissible total duration for
7 tmax_Duration_DFR
PCS-996R to record waveform at 1 time.
“1”:
To enable PCS-996R to record the data of Time stage C
after a disturbance, and to output continuous RMS values at
standard power frequency (e.g.: 50Hz).
8 En_StageC_RMS “0”:
To disable PCS-996R to record the data of Time stage C
after a disturbance, and to output continuous RMS values at
standard power frequency (e.g.: 50Hz).
Please refer to Figure 3.2-1 for details about Time stage C.

2) CalibrateSetting:

This menu is used for manual accuracy calibration.

The parameters list of “CalibrateSetting”of PCS-996R is introduced in the following table.

Table 6.2-3 Parameters list of “CalibrateSetting”of PCS-996R

Name Default Value [Min:Max] (Step)(Unit)


CalibrationEnable 0 [0:1] (1)
Voltage_xxxxCh0_gain 10000 [0:65535] (1)
Voltage_xxxxCh1_gain 10000 [0:65535] (1)
Voltage_xxxxCh2_gain 10000 [0:65535] (1)
Voltage_xxxxCh3_gain 10000 [0:65535] (1)
Line_xxxxCh0_gain 10000 [0:65535] (1)
Line_xxxxCh1_gain 10000 [0:65535] (1)
Line_xxxxCh2_gain 10000 [0:65535] (1)
Line_xxxxCh3_gain 10000 [0:65535] (1)
Line_xxxxCh0_Pa_gain 10000 [0:65535] (1)

50 NR ELECTRIC CO., LTD.


Chapter 6 Human Machine Interface

Name Default Value [Min:Max] (Step)(Unit)


Line_xxxxCh0_Qa_gain 0 [0:65535] (1)
Line_xxxxCh0_Pb_gain 10000 [0:65535] (1)
Line_xxxxCh0_Qb_gain 0 [0:65535] (1)
Line_xxxxCh0_Pc_gain 10000 [0:65535] (1)
Line_xxxxCh0_Qc_gain 0 [0:65535] (1)

The description of “CalibrateSetting”of PCS-996R is introduced in the following table.

Table 6.2-4 Parameters description of “CalibrateSetting”of PCS-996R

Name Description
“1”: To enable automatic accuracy calibration.
This setting must be set as “1” when automatic accuracy
calibration starts.
CalibrationEnable
“0”: To disable automatic accuracy calibration.
This setting must be set as “0”to save the calibration result
when automatic accuracy calibration ends.
The correction factor of the 1st voltage of Line xxxx during
Voltage_xxxxCh0_gain
manual accuracy calibration.
The correction factor of the 2nd voltage of Line xxxx during
Voltage_xxxxCh1_gain
manual accuracy calibration.
The correction factor of the 3rd voltage of Line xxxx during
Voltage_xxxxCh2_gain
manual accuracy calibration.
The correction factor of the 4th voltage of Line xxxx during
Voltage_xxxxCh3_gain
manual accuracy calibration.
The correction factor of the 1st current of Line xxxx during
Line_xxxxCh0_gain
manual accuracy calibration.
The correction factor of the 2nd current of Line xxxx during
Line_xxxxCh1_gain
manual accuracy calibration.
The correction factor of the 3rd current of Line xxxx during
Line_xxxxCh2_gain
manual accuracy calibration.
The correction factor of the 4th current of Line xxxx during
Line_xxxxCh3_gain
manual accuracy calibration.
The correction factor of phase A active power of Line xxxx
Line_xxxxCh0_Pa_gain
during manual accuracy calibration.
The correction factor of phase A reactive power of Line xxxx
Line_xxxxCh0_Qa_gain
during manual accuracy calibration.
The correction factor of phase B active power of Line xxxx
Line_xxxxCh0_Pb_gain
during manual accuracy calibration.
Line_xxxxCh0_Qb_gain The correction factor of phase B reactive power of Line xxxx

NR ELECTRIC CO., LTD. 51


Chapter 6 Human Machine Interface

Name Description
during manual accuracy calibration.
The correction factor of phase C active power of Line xxxx
Line_xxxxCh0_Pc_gain
during manual accuracy calibration.
The correction factor of phase C reactive power of Line xxxx
Line_xxxxCh0_Qc_gain
during manual accuracy calibration.

NOTE:In the above table, xxxx is the name of a component (i.e.: a busbar, a line or a

transformer branch). It can be composed of digits or characters.

3) VIRTUAL_LINK:

This menu is used for viewing and modifying enabling binary inputs.

6.2.5 LocalCommand

There are 2 submenus in this menu:

1) ManualTrigger:

This menu is used for triggering disturbance & fault recording manually.

2) Calibrate:

This menu is used for automatic accuracy calibration.

The parameters list of “Calibrate”of PCS-996R is introduced in the following table.

Table 6.2-5 Parameters list of “Calibrate”of PCS-996R

Name Default Value [Min:Max] (Step)(Unit)


Voltage_xxxxUaStdValue 57.740V [0:255] (0.001)(V)
Voltage_xxxxUbStdValue 57.740V [0:255] (0.001)(V)
Voltage_xxxxUcStdValue 57.740V [0:255] (0.001)(V)
Voltage_xxxxU0StdValue 57.740V [0:255] (0.001)(V)
Line_xxxxIaStdValue 1.000A [0:99] (0.001)(A)
Line_xxxxIbStdValue 1.000A [0:99] (0.001)(A)
Line_xxxxIcStdValue 1.000A [0:99] (0.001)(A)
Line_xxxxI0StdValue 1.000A [0:99] (0.001)(A)
Line_xxxxPaStdValue 0.000W [0:999] (0.001)(W)
Line_xxxxQaStdValue 0.000Var [0:999] (0.001)( Var)
Line_xxxxPbStdValue 0.000W [0:999] (0.001)(W)
Line_xxxxQbStdValue 0.000Var [0:999] (0.001)( Var)
Line_xxxxPcStdValue 0.000W [0:999] (0.001)(W)
Line_xxxxQcStdValue 0.000Var [0:999] (0.001)( Var)

52 NR ELECTRIC CO., LTD.


Chapter 6 Human Machine Interface

The description of “Calibrate”of PCS-996R is introduced in the following table.

Table 6.2-6 Parameters description of “Calibrate”of PCS-996R

Name Description
The standard reference value of the 1st voltage of Line xxxx
Voltage_xxxxUaStdValue
during automatic accuracy calibration.
The standard reference value of the 2nd voltage of Line xxxx
Voltage_xxxxUbStdValue
during automatic accuracy calibration.
The standard reference value of the 3rd voltage of Line xxxx
Voltage_xxxxUcStdValue
during automatic accuracy calibration.
The standard reference value of the 4th voltage of Line xxxx
Voltage_xxxxU0StdValue
during automatic accuracy calibration.
The standard reference value of the 1st current of Line xxxx
Line_xxxxIaStdValue
during automatic accuracy calibration.
The standard reference value of the 2nd current of Line xxxx
Line_xxxxIbStdValue
during automatic accuracy calibration.
The standard reference value of the 3rd current of Line xxxx
Line_xxxxIcStdValue
during automatic accuracy calibration.
The standard reference value of the 4th current of Line xxxx
Line_xxxxI0StdValue
during automatic accuracy calibration.
The standard reference value of phase A active power of Line
Line_xxxxPaStdValue
xxxx during automatic accuracy calibration.
The standard reference value of phase A reactive power of Line
Line_xxxxQaStdValue
xxxx during automatic accuracy calibration.
The standard reference value of phase B active power of Line
Line_xxxxPbStdValue
xxxx during automatic accuracy calibration.
The standard reference value of phase B reactive power of
Line_xxxxQbStdValue
Line xxxx during automatic accuracy calibration.
The standard reference value of phase C active power of Line
Line_xxxxPcStdValue
xxxx during automatic accuracy calibration.
The standard reference value of phase C reactive power of
Line_xxxxQcStdValue
Line xxxx during automatic accuracy calibration.

NOTE:In the above table, xxxx is the name of the power line. It can be composed of

digits or characters.

NOTE:The method for automatic accuracy calibration is introduced as below:

1) AC analog input for the device:

The AC analog input should be:

NR ELECTRIC CO., LTD. 53


Chapter 6 Human Machine Interface

Ua.Ub.Uc =57.74V,

Ia.Ib.Ic =1A,

The voltage should lead the current by 45°.

2) Access the submenu “CalibrateSetting” of the menu “DeviceSetting”, set


“CalibrationEnable”as “1”.

3) Access the menu “LocalCommand”, input the password “111”, and then the automatic
accuracy calibration will start.

4) Access the submenu “CalibrateSetting” of the menu “DeviceSetting”, set


“CalibrationEnable”as “0”to save the calibration result.

6.2.6 AdjustTime

This submenu is used for adjusting the internal clock of PCS-996R.

6.2.7 Version

This submenu is used to show the version of the device.

6.2.8 Debug
There are 3 submenus in this menu:

1) GOOSEInfo:

This menu is used for the information of GOOSE.

2) BoardInfo:

This menu is used for the information of boards (i.e.: modules) of PCS-996R.

3) ItemActionReport:

This menu is used for the item information of the action reports.

6.2.9 Environment

This menu only has 1 submenu “LANGUAGE”.


The submenu “LANGUAGE”.is used for selecting the languages of PCS-996R.

1: Chinese

2: English.

The following figure shows the “LANGUAGE”display of PCS-996R.

54 NR ELECTRIC CO., LTD.


Chapter 6 Human Machine Interface

Please Select Language:

1.
2.English

Figure 6.2-2 “LANGUAGE”display of PCS-996R

NR ELECTRIC CO., LTD. 55


Chapter 6 Human Machine Interface

56 NR ELECTRIC CO., LTD.


Chapter 7 Settings

Chapter 7 Settings

7.1 Overview
This chapter will introduce the hidden settings of PCS-996R.

These settings are not displayed in the menus on the LCD display, but they can be viewed and
modified by a debugging tool.

Each power line can adopt 1-wire measurement, 2-wire measurement, 3-wire measurement or
4-wire measurement.

If a power line adopts 1-wire measurement or 2-wire measurement, the corresponding settings are
the same, but if this power line adopts 3-wire measurement or 4-wire measurement, the
corresponding settings will be different.

The following sections will introduce the settings of PCS-996R.

7.2 Settings
7.2.1 Voltage Level Setting of Binary inputs

The voltage level setting of binary inputs is introduced in the following table.

Table 7.2-1 List of voltage level setting of binary inputs

No. Name Default Value [Min:Max] (Step)(Unit)


1 Un_BinaryInput 0 [0:3] (1)

The description for the voltage level setting of binary inputs is introduced in the following table.

Table 7.2-2 Description of the voltage level setting of binary inputs

No. Name Description


“0”:
The power supply of all the binary inputs of this
device is 24V DC.
“1”:
The power supply of all the binary inputs of this
device is 48V DC.
1 Un_BinaryInput
“2”:
The power supply of all the binary inputs of this
device is 110V DC.
“3”:
The power supply of all the binary inputs of this
device is 220V DC.

NR ELECTRIC CO., LTD. 57


Chapter 7 Settings

7.2.2 Voltage setting for 1-wire measurement or 2-wire measurement

The voltage settings for 1-wire measurement or 2-wire measurement are introduced in the
following table.

The following table only shows the voltage settings of 1 line.

Each line has similar voltage setting as the setting listed below.

Table 7.2-3 Voltage settings list for 1-wire measurement or 2-wire measurement

No. Name Default Value [Min:Max] (Step)(Unit)


1 U_SudnIncr 0.05 Un [0.01:2.00] (0.01)(Un)
2 U_SudnDecr 0.05 Un [0.01:2.00] (0.01)(Un)
3 U_UpLmt 1.10 Un [0.01:2.00] (0.01)(Un)
4 U_LowLmt 0.90 Un [0.01:2.00] (0.01)(Un)
5 Uth 0.15 Un [0.01:2.00] (0.01)(Un)
6 En_U_SudnIncr 0 [0:1] (1)
7 En_U_SudnDecr 0 [0:1] (1)
8 En_U_UpLmt 0 [0:1] (1)
9 En_U_LowLmt 0 [0:1] (1)
10 En_Uth 0 [0:1] (1)

The voltage settings description for 1-wire measurement or 2-wire measurement is introduced in
the following table.

Table 7.2-4 Voltage settings description in 1-wire measurement or 2-wire measurement

No. Name Description


If the sudden increment of the voltage of a
1 U_SudnIncr component (i.e.: busbar or line, etc.) is greater than
this setting, the waveform recording will be triggered.
If the sudden decrement of the voltage of a
2 U_SudnDecr component is greater than this setting, the waveform
recording will be triggered.
If the voltage of a component is greater than this
3 U_UpLmt
setting, the waveform recording will be triggered.
If the voltage of a component is less than this setting,
4 U_LowLmt
the waveform recording will be triggered.
If the variation of the voltage of a component before
and after triggering waveform recording is greater
5 Uth
than this setting, this component will be regarded as
a fault component.
6 En_U_SudnIncr “1”:

58 NR ELECTRIC CO., LTD.


Chapter 7 Settings

No. Name Description


To enable the setting [U_SudnIncr].
“0”:
To disable the setting [U_SudnIncr].
“1”:
To enable the setting [U_SudnDecr].
7 En_U_SudnDecr
“0”:
To disable the setting [U_SudnDecr].
“1”:
To enable the setting [U_UpLmt].
8 En_U_UpLmt
“0”:
To disable the setting [U_UpLmt].
“1”:
To enable the setting [U_LowLmt].
9 En_U_LowLmt
“0”:
To disable the setting [U_LowLmt].
“1”:
To enable the setting [Uth].
10 En_Uth
“0”:
To disable the setting [Uth].

7.2.3 Voltage setting for 3-wire measurement or 4-wire measurement

The voltage settings for 3-wire measurement or 4-wire measurement are introduced in the
following table.

The following table only shows the voltage settings of 1 line.

Each line has similar voltage setting as the setting listed below.

Table 7.2-5 Voltage settings list for 3-wire measurement or 4-wire measurement

No. Name Default Value [Min:Max] (Step)(Unit)


1 Up_SudnIncr 0.05 Un [0.01:2.00] (0.01)(Un)
2 Up_SudnDecr 0.05 Un [0.01:2.00] (0.01)(Un)
3 Up_UpLmt 1.10 Un [0.01:2.00] (0.01)(Un)
4 Up_LowLmt 0.90 Un [0.01:2.00] (0.01)(Un)
5 U2_UpLmt 0.05 Un [0.01:2.00] (0.01)(Un)
6 U0_SudnChg 0.05 Un [0.01:2.00] (0.01)(Un)
7 U0_UpLmt 0.05 Un [0.01:2.00] (0.01)(Un)
8 Uth 0.15 Un [0.01:2.00] (0.01)(Un)
9 f_UpLmt 50.50 [45.00:55.00] (0.01) (Hz)
10 f_LowLmt 49.50 [45.00:55.00] (0.01) (Hz)

NR ELECTRIC CO., LTD. 59


Chapter 7 Settings

No. Name Default Value [Min:Max] (Step)(Unit)


11 df/dt 2.00 [0.10:50.00] (0.01) (Hz/s)
12 En_Up_SudnIncr 0 [0:1] (1)
13 En_Up_SudnDecr 0 [0:1] (1)
14 En_Up_UpLmt 0 [0:1] (1)
15 En_Up_LowLmt 0 [0:1] (1)
16 En_U2_UpLmt 0 [0:1] (1)
17 En_U0_SudnChg 0 [0:1] (1)
18 En_U0_UpLmt 0 [0:1] (1)
19 En_Uth 0 [0:1] (1)
20 En_f_UpLmt 0 [0:1] (1)
21 En_f_LowLmt 0 [0:1] (1)
22 En_df/dt 0 [0:1] (1)

The voltage settings description for 3-wire measurement or 4-wire measurement is introduced in
the following table.

Table 7.2-6 Voltage settings description in 3-wire measurement or 4-wire measurement

No. Name Description


For any one of the 3 phase voltages of a component,
1 Up_SudnIncr if the sudden increment of this voltage is greater than
this setting, the waveform recording will be triggered.
For any one of the 3 phase voltages of a component,
if the sudden decrement of this voltage is greater
2 Up_SudnDecr
than this setting, the waveform recording will be
triggered.
If any one of the 3 phase voltages of a component is
3 Up_UpLmt greater than this setting, the waveform recording will
be triggered.
If any one of the 3 phase voltages of a component is
4 Up_LowLmt less than this setting, the waveform recording will be
triggered.
If the negative sequence voltage of a component is
5 U2_UpLmt greater than this setting, the waveform recording will
be triggered.
If the sudden change of the zero sequence voltage of
6 U0_SudnChg a component is greater than this setting, the
waveform recording will be triggered.
If the zero sequence voltage of a component is
7 U0_UpLmt
greater than this setting, the waveform recording will

60 NR ELECTRIC CO., LTD.


Chapter 7 Settings

No. Name Description


be triggered.
For any one of the 3 phase voltages of a component,
if the variation of this voltage before and after
8 Uth triggering waveform recording is greater than this
setting, this component will be regarded as a fault
component.
If the frequency of a component is higher than this
9 f_UpLmt
setting, the waveform recording will be triggered.
If the frequency of a component is lower than this
10 f_LowLmt
setting, the waveform recording will be triggered.
If the df/dt of a component is greater than this
11 df/dt
setting, the waveform recording will be triggered.
“1”:
To enable the setting [Up_SudnIncr].
12 En_Up_SudnIncr
“0”:
To disable the setting [Up_SudnIncr].
“1”:
To enable the setting [Up_SudnDecr].
13 En_Up_SudnDecr
“0”:
To disable the setting [Up_SudnDecr].
“1”:
To enable the setting [Up_UpLmt].
14 En_Up_UpLmt
“0”:
To disable the setting [Up_UpLmt].
“1”:
To enable the setting [Up_LowLmt t].
15 En_Up_LowLmt
“0”:
To disable the setting [Up_LowLmt].
“1”:
To enable the setting [U2_UpLmt].
16 En_U2_UpLmt
“0”:
To disable the setting [U2_UpLmt].
“1”:
To enable the setting [U0_SudnChg].
17 En_U0_SudnChg
“0”:
To disable the setting [U0_SudnChg].
“1”:
To enable the setting [U0_UpLmt].
18 En_U0_UpLmt
“0”:
To disable the setting [U0_UpLmt].

NR ELECTRIC CO., LTD. 61


Chapter 7 Settings

No. Name Description


“1”:
To enable the setting [Uth].
19 En_Uth
“0”:
To disable the setting [Uth].
“1”:
To enable the setting [f_UpLmt].
20 En_f_UpLmt
“0”:
To disable the setting [f_UpLmt].
“1”:
To enable the setting [f_LowLmt].
21 En_f_LowLmt
“0”:
To disable the setting [f_LowLmt].
“1”:
To enable the setting [df/dt].
22 En_df/dt
“0”:
To disable the setting [df/dt].

7.2.4 Current setting for 1-wire measurement or 2-wire measurement

The current settings for 1-wire measurement or 2-wire measurement are introduced in the
following table.

The following table only shows the current settings of 1 line.

Each line has similar current setting as the setting listed below.

Table 7.2-7 Current settings list for 1-wire measurement or 2-wire measurement

No. Name Default Value [Min:Max] (Step)(Unit)


1 I_SudnChg 0.05 Un [0.01:5.00] (0.01)(In)
2 I_UpLmt 1.10 Un [0.01:5.00] (0.01)(In)
3 Ith 0.05 Un [0.01:5.00] (0.01)(In)
4 En_I_SudnChg 0 [0:1] (1)
5 En_I_UpLmt 0 [0:1] (1)
6 En_Ith 0 [0:1] (1)

The current settings description for 1-wire measurement or 2-wire measurement is introduced in
the following table.

Table 7.2-8 Current settings description in 1-wire measurement or 2-wire measurement

No. Name Description


If the sudden change of the current of a component
1 I_SudnChg (i.e.: line or transformer branch) is greater than this
setting, the waveform recording will be triggered.

62 NR ELECTRIC CO., LTD.


Chapter 7 Settings

No. Name Description


If the current of a component is greater than this
2 I_UpLmt
setting, the waveform recording will be triggered.
If the variation of the current of a component before
and after triggering waveform recording is greater
3 Ith
than this setting, this component will be regarded as
a fault component.
“1”:
To enable the setting [I_SudnChg].
4 En_I_SudnChg
“0”:
To disable the setting [I_SudnChg].
“1”:
To enable the setting [I_UpLmt].
5 En_I_UpLmt
“0”:
To disable the setting [I_UpLmt].
“1”:
To enable the setting [Ith].
6 En_Ith
“0”:
To disable the setting [Ith].

7.2.5 Current setting for 3-wire measurement or 4-wire measurement

The current settings for 3-wire measurement or 4-wire measurement are introduced in the
following table.

The following table only shows the current settings of 1 line.

Each line has similar current setting as the setting listed below.

Table 7.2-9 Current settings list for 3-wire measurement or 4-wire measurement

No. Name Default Value [Min:Max] (Step)(Unit)


1 Ip_SudnChg 0.05 In [0.01:5.00] (0.01)(In)
2 Ip_UpLmt 1.10 In [0.01:5.00] (0.01)(In)
3 I2_UpLmt 0.05 In [0.01:5.00] (0.01)(In)
4 I0_SudnChg 0.05 In [0.01:5.00] (0.01)(In)
5 I0_UpLmt 0.05 In [0.01:5.00] (0.01)(In)
6 Ith 0.05 In [0.01:5.00] (0.01)(In)
7 k_Ripple 0.10 [0.01:5.00] (0.01)
8 En_Ip_SudnChg 0 [0:1] (1)
9 En_Ip_UpLmt 0 [0:1] (1)
10 En_I2_UpLmt 0 [0:1] (1)
11 En_I0_SudnChg 0 [0:1] (1)

NR ELECTRIC CO., LTD. 63


Chapter 7 Settings

No. Name Default Value [Min:Max] (Step)(Unit)


12 En_I0_UpLmt 0 [0:1] (1)
13 En_Ith 0 [0:1] (1)
14 En_k_Ripple 0 [0:1] (1)

The current settings description for 3-wire measurement or 4-wire measurement is introduced in
the following table.

Table 7.2-10 Current settings description in 3-wire measurement or 4-wire measurement

No. Name Description


For any one of the 3 phase currents of a component,
1 Ip_SudnChg if the sudden change of this current is greater than
this setting, the waveform recording will be triggered.
If any one of the 3 phase currents of a component is
2 Ip_UpLmt greater than this setting, the waveform recording will
be triggered.
If the negative sequence current of a component is
3 I2_UpLmt greater than this setting, the waveform recording will
be triggered.
If the sudden change of the zero sequence current of
4 I0_SudnChg a component is greater than this setting, the
waveform recording will be triggered.
If the zero sequence current of a component is
5 I0_UpLmt greater than this setting, the waveform recording will
be triggered.
For any one of the 3 phase currents of a component,
if the variation of this current before and after
6 Ith triggering waveform recording is greater than this
setting, this component will be regarded as a fault
component.
This setting is used for detecting power swing. If a
7 k_Ripple power swing is detected by PCS-996R, the
waveform recording will be triggered.
“1”:
To enable the setting [Ip_SudnChg].
8 En_Ip_SudnChg
“0”:
To disable the setting [Ip_SudnChg].
“1”:
To enable the setting [Ip_UpLmt].
9 En_Ip_UpLmt
“0”:
To disable the setting [Ip_UpLmt].
10 En_I2_UpLmt “1”:

64 NR ELECTRIC CO., LTD.


Chapter 7 Settings

No. Name Description


To enable the setting [I2_UpLmt].
“0”:
To disable the setting [I2_UpLmt].
“1”:
To enable the setting [I0_SudnChg].
11 En_I0_SudnChg
“0”:
To disable the setting [I0_SudnChg].
“1”:
To enable the setting [I0_UpLmt].
12 En_I0_UpLmt
“0”:
To disable the setting [I0_UpLmt].
“1”:
To enable the setting [Ith].
13 En_Ith
“0”:
To disable the setting [Ith].
“1”:
To enable the setting [k_Ripple].
14 En_k_Ripple
“0”:
To disable the setting [k_Ripple].

NR ELECTRIC CO., LTD. 65


Chapter 7 Settings

66 NR ELECTRIC CO., LTD.


Chapter 8 WEB

Chapter 8 WEB

8.1 Overview

With the rise and development of the Internet technology, during the management and interaction
of the embedded equipments, the application based on WEB acts an important role in the main
stream nowadays.

PCS-996R supports the WEB browsing function. On the computer which acts as the WEB client,
the information of PCS-996R can be viewed by WEB browser conveniently. The WEB browsing
function will be introduced in this chapter.

Firstly, PCS-996R should be ensured to be connected to the computer via RJ45 ethernet ports,
and then an appropriate IP address and a correct subnet mask should be assigned to the RJ45
ethernet port of the computer.

Such an example will be taken in this chapter:

Suppose the [IP addrA] setting of PCS-996R is set as “198.120.0.33”,

and the [Subnet mask addrA] setting of PCS-996R is set as “255.255.255.0”.

The IP address of the RJ45 ethernet port of the computer can be set as “198.120.0.x”.
(x=1,2,3… 254, i.e.: x can be any integer between 1 and 254, but x can not be 33 because the IP
address of the computer must be different from the [IP addrA] of PCS-996R).

The subnet mask of the RJ45 ethernet port of the computer must be configured as
“255.255.255.0”. (i.e.: the subnet mask of the computer must be the same as the [Subnet mask
addrA] of PCS-996R).

NOTE: 2 CPU boards can be configured in PCS-996R , but the WEB browsing

function can only be realized by connecting the RJ45 ethernet port of the computer to
the RJ45 ethernet port of the left CPU board (viewed from the back of PCS-996R), or by
connecting it to the RJ45 multiplex port on the front panel of PCS-996R.

I.e.: the WEB browsing function can not be realized by connecting the RJ45
ethernet port of the computer to the RJ45 ethernet port of the right CPU board (viewed
from the back of PCS-996R).

NOTE: All the RJ45 ethernet ports of the left CPU board (viewed from the back of

PCS-996R) and the RJ45 multiplex port on the front panel share the same IP address
([IP addrA]) and the same subnet mask([Subnet mask addrA]).

Now the WEB browsing function can be realized by this computer. Please input the IP
address ([IP addrA], in this example, it is “198.120.0.33”.) of PCS-996R in the address bar of
Internet Explorer to connect PCS-996R. A login interface will appear as shown in the following

NR ELECTRIC CO., LTD. 67


Chapter 8 WEB

figure. At the same time, a small dialog box will pop up to configure language. Chinese and
English are optional now. New language options can be developed according to requirements.

Figure 8.1-1

Figure 8.1-2

As shown in the above figure, select the language as “English”and then click the button “OK”to
access the WEB interface as shown in the following figure.

68 NR ELECTRIC CO., LTD.


Chapter 8 WEB

A menu tree list lies in the left part of the WEB interface, while the details of the selected item are
shown in the right part.

The left menu tree list consists 4 menus: Device Information, Status, Records, Settings.

The details about these 4 menus will be introduced in the following sections of this chapter.

Figure 8.1-3

8.2 Device Information

The information about the menu “Device Information”will be introduced in this section.

“Device Information”consists of 7 submenus: Version, Hardware Config, Analog Channels,


Binary Channels, Components, Parameters, Settings.

The interface of the submenu “Version”is shown in the above in the above section.

NOTE: The above figure is only an example to show the interface of the submenu

“Version” in the WEB browser. Please refer to the interface in engineering


application for the actual interface. It is the same for all the other figures in this
chapter.

The interface of the submenu “Hardware Config”is shown in the following figure.

NR ELECTRIC CO., LTD. 69


Chapter 8 WEB

Figure 8.2-1

The interface of the submenu “Analog Channels”is shown in the following 2 figures.

The analog channels of busbar voltage components and line current components are listed in the
following figure.

Figure 8.2-2

70 NR ELECTRIC CO., LTD.


Chapter 8 WEB

The analog channels of line current components and transformer branch current components are
listed in the following figure.

Figure 8.2-3

The interface of the submenu “Binary Channels”is shown in the following figure.

NR ELECTRIC CO., LTD. 71


Chapter 8 WEB

Figure 8.2-4

The interface of the submenu “Components”is shown in the following figure.

Figure 8.2-5

72 NR ELECTRIC CO., LTD.


Chapter 8 WEB

The interface of the submenu “Parameters”is shown in the following 2 figures.

The parameters of busbar voltage components and line current components are listed in the
following figure.

Figure 8.2-6

The parameters of line current components and transformer branch current components are listed
in the following figure.

NR ELECTRIC CO., LTD. 73


Chapter 8 WEB

Figure 8.2-7

The interface of the submenu “Settings”is shown in the following 3 figures.

The settings of busbar voltage components are listed in the following figure.

Figure 8.2-8

The settings of line current components are listed in the following figure.

74 NR ELECTRIC CO., LTD.


Chapter 8 WEB

Figure 8.2-9

The settings of transformer branch current components are listed in the following figure.

Figure 8.2-10

8.3 Status

The information about the menu “Status”will be introduced in this section.

“Status”consists of 2 submenus: DeviceStatus, DebugMenu.

8.3.1 DeviceStatus
The information about the submenu “DeviceStatus”will be introduced in this section.

“DeviceStatus”consists of 5 types of submenus: BusxMeasure, LinexMeasure, TranxMeasure,


GOOSEBin, NormalBin.

NR ELECTRIC CO., LTD. 75


Chapter 8 WEB

NOTE:“DeviceStatus”and “NormalBin”are required to be included in “DeviceStatus”.

“BusxMeasure”, “LinexMeasure”, “TranxMeasure”are optional, but the total number of


these 3 types of submenus must be 16.(x=01,02… 10,11… .).

3 examples of “BusxMeasure”, “LinexMeasure”, “TranxMeasure”are listed in the following 3


figures.

The detailed information of the submenu “Bus01Measure”is listed in the following figure.

Figure 8.3-1

The detailed information of the submenu “Line02Measure”is listed in the following figure.

76 NR ELECTRIC CO., LTD.


Chapter 8 WEB

Figure 8.3-2

The detailed information of the submenu “Tran01Measure”is listed in the following figure.

Figure 8.3-3

The details of GOOSE binary inputs are listed in the submenu “GOOSEBin”as shown in the
following figure.

NR ELECTRIC CO., LTD. 77


Chapter 8 WEB

Figure 8.3-4

The details of normal binary inputs are listed in the submenu “NormalBin” as shown in the
following figure.

78 NR ELECTRIC CO., LTD.


Chapter 8 WEB

Figure 8.3-5

8.3.2 DebugMenu
The information about the submenu “DebugMenu”will be introduced in this section.

“DebugMenu”only consists of submenu: GooseInfo.

The detailed information for reference during debugging is listed in the submenu “GooseInfo”as
shown in the following figure.

NR ELECTRIC CO., LTD. 79


Chapter 8 WEB

Figure 8.3-6

8.4 Records

The information about the menu “Records”will be introduced in this section.

“Records”consists of 4 submenus: Disturb Records, Superv Events, Binary Events, Equip


logs.

Disturbance & fault recording reports are stored in the submenu “Disturb Records”.

Self-supervision reports are stored in the submenu “Superv Events”.

Status change reports of binary inputs are stored in the submenu “Binary Events”.

Running logs of PCS-996R are stored in the submenu “Equip logs”.

The interface of the submenu “Disturb Records”is shown in the following figure.

80 NR ELECTRIC CO., LTD.


Chapter 8 WEB

The interface of the submenu “Superv Events”is shown in the following figure.

Figure 8.4-1

The interface of the submenu “Binary Events”is shown in the following figure.

Figure 8.4-2

The interface of the submenu “Equip logs”is shown in the following figure.

Figure 8.4-3

NR ELECTRIC CO., LTD. 81


Chapter 8 WEB

Figure 8.4-4

8.5 Settings

The information about the menu “Settings”will be introduced in this section.

“Settings”only consists of 1 submenu: DeviceSetting.

“DeviceSetting”consists of 3 submenus: DEVICE-PARAMETER, CalibrateSetting, VIRTUAL


LINK.

NOTE: Compared to the submenu “Settings” of the menu “Device Information”

mentioned in section 8.2, the menu “Settings”in this section refers to the settings of
PCS-996R itself, while the submenu “Settings” of the menu “Device Information”
emphasis on the settings of the components (i.e.: the busbar voltage components, the
line current components and the transformer branch current components).

The interface of the submenu “DEVICE-PARAMETER”is shown in the following figure.

Figure 8.5-1

The interface of the submenu “CalibrateSetting”is shown in the following figure.

82 NR ELECTRIC CO., LTD.


Chapter 8 WEB

Figure 8.5-2

The interface of the submenu “VIRTUAL LINK”is shown in the following figure.

Figure 8.5-3

NR ELECTRIC CO., LTD. 83


Chapter 8 WEB

84 NR ELECTRIC CO., LTD.


Chapter 9 Installation

Chapter 9 Installation

9.1 General

The equipment must be shipped, stored and installed with the greatest care.

Choose the place of installation such that the communication interface and the controls on the
front of the device are easily accessible.

Air must circulate freely around the equipment. Observe all the requirements regarding place of
installation and ambient conditions given in Chapter 2 of this instruction manual.

Take care that the external wiring is properly brought into the equipment and terminated correctly
and pay special attention to grounding. Strictly observe the corresponding guidelines contained in
this section.

9.2 Safety Instructions

This section contains safety information. Warning signs are presented which attend the user to be
careful during certain operations in order to avoid human injuries or damage to equipment.

DANGER: Strictly follow the company and country safety regulations. Working in a high

voltage environment requires serious approach to avoid human injuries and damage to
equipment.

DANGER: Do not touch circuitry during operation. Potentially lethal voltages and currents

are present.

DANGER: Never connect or disconnect a wire and/or a connector to or from a protection

equipment during normal operation. Hazardous voltages and currents are present that
may be lethal. Operation may be disrupted and protection equipment and measuring
circuitry may be damaged.

DANGER: Always connect the protection equipment to protective ground, regardless of

the operating conditions. This also applies to special occasions such as bench testing,
demonstrations and off-site configuration. Operating the protection equipment without
proper grounding may damage both terminal and measuring circuitry, and may cause
injuries in case of an accident.

DANGER: Never open the front or back cover from a powered equipment or from a

protection equipment connected to powered circuitry. Potentially lethal voltages and

NR ELECTRIC CO., LTD. 85


Chapter 9 Installation

currents are present.

WARNING: The modules of this equipment may only be inserted in the designated slots.

Components can be damaged or destroyed by inserting boards in the wrong slots.

WARNING: Only insert or withdraw the other boards while the power supply is switched

off.

The basic precautions to guard against electrostatic discharge are as follows:

 Should boards have to be removed from PCS-996R installed in a grounded cubicle in an HV


switchgear installation, discharge yourself by touching station ground (the cubicle)
beforehand.

 Only hold electronic boards at the edges, taking care not to touch the components.

 Only works on boards that have been removed from the cubicle on a workbench designed for
electronic equipment and wear a grounded wristband. Do not wear a grounded wristband,
however, while inserting or withdrawing units.

 Always store and ship the electronic boards in their original packing. Place electronic parts in
electrostatic screened packing materials.

9.3 Checking the Shipment

Check that the consignment is complete immediately upon receipt. Notify the nearest NR
Company or agent, should departures from the delivery note, the shipping papers or the order be
found.

Visually inspect all the material when unpacking it. When there is evidence of transport damage,
lodge a claim immediately in writing with the last carrier and notify the nearest NR Company or
agent.

If the equipment is not going to be installed immediately, store all the parts in their original packing
in a clean dry place at a moderate temperature. The ambient temperature and humidity required
for storage please refer to Chapter 2.

9.4 Material and Tools Required

The necessary mounting kits will be provided, including screws, pincers and assembly
instructions.

A suitable drill and spanners are required to secure the cubicles to the floor using the plugs
provided (if PCS-996R is mounted in cubicles).

86 NR ELECTRIC CO., LTD.


Chapter 9 Installation

9.5 Device Location and Ambient Conditions

The place of installation should permit easy access especially to front of the device, i.e. to the
human-machine interface of the equipment.

There should also be free access at the rear of the equipment for additions and replacement of
electronic boards.

Since every piece of technical equipment can be damaged or destroyed by inadmissible ambient
conditions, such as:

1) The location should not be exposed to excessive air pollution (dust, aggressive substances).

2) Severe vibration, extreme changes of temperature, high levels of humidity, surge voltages of
high amplitude and short rise time and strong induced magnetic fields should be avoided as
far as possible.

3) Air must not be allowed to circulate freely around the equipment.

The equipment can in principle be mounted in any attitude, but it is normally mounted vertically
(visibility of markings).

WARNING: Excessively high temperature can appreciably reduce the operating life of

the PCS-996R.

9.6 Mechanical Installation

This device is made of a single layer 4U height with some connectors on its rear panel. The
following two figures show the dimensions and cut-out size in the cubicle of PCS-996R for
reference in mounting.

Figure 9.6-1 Dimensions of PCS-996R (unit: mm)

NR ELECTRIC CO., LTD. 87


Chapter 9 Installation

179.00
101.60
Figure 9.6-2 Cut-out size of PCS-996R in the cubicle (unit: mm)

NOTE: It is necessary to leave enough space top and bottom of the cut-out in the cubicle

for heat emission of the PCS-996R.

All the modules must be plugged into the proper slots of the PCS-996R respectively. The safety
instructions must be abided by when installing the boards, see Section 9.2”Safety Instructions”.

In the case of equipment supplied in cubicles, place the cubicles on the foundations that have
been prepared. Take care while doing so not to jam or otherwise damage any of the cables that
have already been installed. Secure the cubicles to the foundations.

9.7 Electrical Installation and Wiring

9.7.1 Grounding Guidelines


Switching operations in HV installations generate transient over voltages on control signal cables.
There is also a background of electromagnetic RF fields in electrical installations that can induce
spurious currents in the devices themselves or the leads connected to them.

All these influences can influence the operation of electronic apparatus.

On the other hand, electronic apparatus can transmit interference that can disrupt the operation of
other apparatus.

In order to minimize these influences as far as possible, certain standards have to be observed
with respect to grounding, wiring and screening.

NOTE: All these precautions can only be effective if the station ground is of good quality.

9.7.2 Cubicle Grounding

The cubicle must be designed and fitted out such that the impedance for RF interference of the
ground path from the electronic device to the cubicle ground terminal is as low as possible.

Metal accessories such as side plates, blanking plates etc., must be effectively connected
surface-to-surface to the grounded frame to ensure a low-impedance path to ground for RF

88 NR ELECTRIC CO., LTD.


Chapter 9 Installation

interference. The contact surfaces must not only conduct well, they must also be non -corroding.

NOTE: If the above conditions are not fulfilled, there is a possibility of the cubicle or parts

of it forming a resonant circuit at certain frequencies that would amplify the transmission
of interference by the devices installed and also reduce their immunity to induced
interference.

Movable parts of the cubicle such as doors (front and back) or hinged equipment frames must be
effectively grounded to the frame by three braided copper strips (see Figure 9.7-1 Cubicle
grounding system).

The metal parts of the cubicle housing and the ground rail are interconnected electrically
conducting and corrosion proof. The contact surfaces shall be as large as possible.

NOTE: For metallic connections please observe the voltage difference of both materials

according to the electrochemical code.

The cubicle ground rail must be effectively connected to the station ground rail by a grounding strip
(braided copper).

Figure 9.7-1 Cubicle grounding system

9.7.3 Ground Connection on the Device

There is a ground terminal on the PWR module of the device, and the ground braided copper strip
can be connected with it. Take care that the grounding strip is always as short as possible. The
main thing is that the device is only grounded at one point. Grounding loops from unit to unit are
not allowed. When the PWR module is plugged into the proper slots of the device, the ground
terminals of the PWR module is connected with the metal parts of the cubicle housing. There are
some ground terminals on some other connectors of this relay. All the ground terminals are
connected in the cabinet of this relay. So, the ground terminal on the PWR module is the only
ground terminal of this device.

NR ELECTRIC CO., LTD. 89


Chapter 9 Installation

90 NR ELECTRIC CO., LTD.


Chapter 10 Commissioning

Chapter 10 Commissioning

10.1 General

PCS-996R is set in normal working mode when it is sent to the users, it can operate normally
when energized. If any question is found, please contact the vendors.

NOTE: Before carrying out any work on the equipment, the user should be familiar with

the contents of the safety and technical data sections and the ratings on the equipment’
s
rating label.

10.2 Safety Instructions

WARNING: Hazardous voltages are present in this electrical equipment during operation.

Non-observance of the safety rules can result in severe personal injury or property
damage.

WARNING: Only qualified personnel shall work on and around this equipment after

becoming thoroughly familiar with all warnings and safety notices of this manual as well
as with the applicable safety regulations.

Particular attention must be drawn to the following:

 The earthing screw of the device must be connected solidly to the protective earth conductor
before any other electrical connection is made.

 The limit values stated in the technical data (See Chapter 2) must not be exceeded at all, not
even during testing and commissioning.

WARNING: Only qualified personnel can commission relative tests:

10.3 Product Checks

These product checks cover all aspects of this device which should be checked to ensure that it
has not been physically damaged prior to commissioning, is functioning correctly and all input
quantity measurements are within the stated tolerances.

10.3.1 With the Device De-energized

The following tests must be applied to ensure the device can operate normally when it is put into
operation.

NR ELECTRIC CO., LTD. 91


Chapter 10 Commissioning

10.3.1.1 Visual Inspection

After unpacking the product, check for any damage to the device case. If there is any damage, the
internal module might also have been affected, contact the vendors or their agents.

10.3.1.2 Insulation Test (If required)

Insulation resistance tests are only necessary during commissioning if it is required for them to be
done and they have not been performed during installation.

Isolate all wiring from the earth and test the isolation with an electronic or brushless insulation
tester at a DC voltage not exceeding 500V, the circuits need to be tested should include:

 Power supply

 Communication Interface

 Ground terminals

The insulation resistance should be greater than 100MΩ at 500V.On completion of the insulation
resistance tests, ensure all external wiring is correctly reconnected to the device.

10.3.1.3 Check the External Wiring

Check whether the external wiring is consistent with the wiring scheme and the engineering design
scheme.

Check the wiring according to the principle scheme to ensure the wiring is consistent with the
application of the users.

10.3.1.4 Check power Supply

The device can be operated from either 110/125Vdc or 220/250Vdc auxiliary power supply
depending on the device’
s nominal supply rating. The incoming voltage must be within the
operating range specified in the following table, before energizing the relay, measure th e auxiliary
supply to ensure it within the operating range.

Table 10.3-1 Power supply range

Rated Voltage 110/125Vdc 220/250Vdc


Variation (80% ~ 120%)Un

It should be noted that the device can withstand an AC ripple of up to 15% of the upper rated
voltage on the DC auxiliary supply.

WARNING: Energize the device only if the auxiliary supply is within the specified

operating ranges.

10.3.2 With the Device Energized

The following groups of checks verify that the hardware and software is functioning correctly and
should be carried out with the power supply applied to the device.

92 NR ELECTRIC CO., LTD.


Chapter 10 Commissioning

10.3.2.1 Testing the LED Indicators

When the device is out of power supply or any hardware defect (such as chip damage, check error
of setting, etc.) is detected during self-test, the “HEALTHY”LED will be off.

When the device runs normally after it is energized, the “HEALTHY”LED will be lit on as green all
the time.

When the device operates normally, the “ALARM”LED is off.

If any abnormality alarm is issued, the “ALARM”LED will be lit on as yellow.

If this device is not recording disturbance & fault wave, the “REC”LED is off.

If this device is not recording disturbance & fault wave, the “REC”LED will be lit on as red.

The “REC”LED will be lit on when disturbance & fault recording is triggered.

10.3.3 Final Check

After the above tests are completed, remove all test or temporary shorting leads, etc. If it has been
necessary to disconnect any of the external wiring from the device in order to perform the wiring
verification tests, it should be ensured that all connections are replaced in accordance with the
relevant external connection or scheme diagram.

NR ELECTRIC CO., LTD. 93


Chapter 10 Commissioning

94 NR ELECTRIC CO., LTD.


Chapter 11 Maintenance

Chapter 11 Maintenance

11.1 Maintenance Schedule

It is recommended that products supplied by NR receive periodic monitoring after installation. In


view of the critical nature of the device and their infrequent operation, it is desirable to confirm that
they are operating correctly at regular intervals.

This device is self-supervised and so requires less maintenance. Most problems will result in an
alarm so that remedial action can be taken. However, some periodic tests should be done to
ensure that the device is functioning correctly and the external wiring is intact.

11.2 Regular Testing

The device is almost completely self-supervised. Therefore regular testing can be minimized to
check the unsupervised aspects.

11.3 Failure Tracing and Repair

Failures will be detected by automatic supervision or regular testing.

When a failure is detected by supervision, a remote alarm is issued and the failure is indicated on
the front panel with LED indicators.

When a failure is detected during regular testing, confirm the following:

 Modules are securely inserted in position.

 Correct power voltage is applied.

 Test circuit connections are correct.

 Test procedures comply with those stated in the manual.

11.4 Replace Failed Modules

If the failure is identified to be in the module of this device and the user has spare modules, the
user can recover the protection by replacing the failed modules.

Repair at the site should be limited to module replacement. Maintenance at the component level is
not recommended.

Check that the replacement module has an identical module name ( NR1301,… , etc.) and
hardware type-form as the removed module. Furthermore, the CPU module replaced should have
the same software version. Furthermore, the PWR module replaced should have the same

NR ELECTRIC CO., LTD. 95


Chapter 11 Maintenance

ratings. The example to pull out a board is shown in the following figure.

Figure 11.4-1 Example of pulling out a board

WARNING: Units and modules may only be replaced while the supply is switched off and

only by appropriately trained and qualified personnel. Strictly observe the basic
precautions to guard against electrostatic discharge.

WARNING: When handling a module, take anti-static measures such as wearing an

earthed wrist band and placing modules on an earthed conductive mat. Otherwise, many
of the electronic components could suffer damage. After replacing the CPU module,
check the settings.

DANGER: After replacing modules, be sure to check that the same configuration is set

as before the replacement. If this is not the case, there is a danger of the unintended
operation of switchgear taking place or of protections not functioning correctly. Persons
may also be put in danger.

11.5 Cleaning

Before cleaning the equipment ensure that all AC and DC supplies, current transformer and
voltage transformer connections are isolated to prevent any chance of an electric shock whilst
cleaning. Use a smooth cloth to clean the front panel. Do not use abrasive material or detergent
chemicals.

11.6 Storage

The spare device or module should be stored in a dry and clean room. Based on IEC standard
60255-1 the storage temperature should be -40°C to 70°C, but the temperature of -10°C to 40°C is

96 NR ELECTRIC CO., LTD.


Chapter 11 Maintenance

recommended for long-term storage.

NR ELECTRIC CO., LTD. 97


Chapter 11 Maintenance

98 NR ELECTRIC CO., LTD.


Chapter 12 Decommissioning and Disposal

Chapter 12 Decommissioning and Disposal

12.1 Decommissioning

12.1.1 Switching off

To switch off the PCS-996R, switch off the external miniature circuit breaker of the power supply.

12.1.2 Disconnecting cables


Disconnect the cables in accordance with the rules and recommendations made by relational
department.

DANGER: Before disconnecting the power supply cables that connected with the PWR

module of the PCS-996R, make sure that the external miniature circuit breaker of the
power supply is switched off.

DANGER: Before disconnecting the cables that are used to connect analog input module

with the primary CTs and VTs, make sure that the circuit breaker for the primary CTs and
VTs is switched off.

12.1.3 Dismantling

The PCS-996R rack may now be removed from the system cubicle, after which the cubicles may
also be removed.

DANGER: When the station is in operation, make sure that there is an adequate safety

distance to live parts, especially as dismantling is often performed by unskilled personnel.

12.2 Disposal

In every country there are companies specialized in the proper disposal of electronic waste.

NOTE: Strictly observe all local and national regulations when disposing of the device.

NR ELECTRIC CO., LTD. 99


Chapter 12 Decommissioning and Disposal

100 NR ELECTRIC CO., LTD.


Chapter 13 Manual Version History

Chapter 13 Manual Version History


In the current version of the instruction manual, several descriptions on existing features have
been modified.

Manual version and modification history records

Manual Version Software


Date Description of change
Source New Version
1.00 2.0 2009-11-30 Form the original manual.
Delete original “Chapter8 Waveform recording”;
Add “Chapter 3 Software Description”, “Chapter4 Automatic
Supervision”,”Chapter8 WEB”;
1.00 1.01 3.0 2010-05-10 Add description for newly added settings in ”Chapter7
Settings”;
Add description for newly added contents in ”Chapter5
Hardware Description”.
1.01 1.02 3.0 2010-07-19 Add section 1.3 “Order Information”.
1.02 1.03 3.0 2010-08-27 Update section 1.3 “Order Information”.

NR ELECTRIC CO., LTD. 101

Вам также может понравиться