Electrical Audit Report 2019

­IOCL SANGANER AFS 

ELECTRICAL SAFETY AUDIT REPORT


OF
INDIAN OIL CORPORATION LTD
AVATION FUELING STATION
SANGANER JAIPUR (RAJ)

By

Shivalika Electricals & Engineers

Period of Audit : 17th Aug’19 – 18th Aug’19


Report Submitted on : 12th Sept’19
1
Electrical Audit Report 2019
­IOCL SANGANER AFS 

TO Ref. : 2035/SEE/19
Date : 12/09/2019
THE SR APTM ,
IOCL,
SANGANER AFS ,
JAIPUR (RAJASTHAN)

SUB. : ELECTRICAL SAFETY AUDIT OF IOCL SANGANER AFS JAIPUR (RAJ).

Dear Sir,

We are Pleased to inform you that the complete Electrical audit of electrical installation of
your station has carried out by us and also discussed with your technical staff about the
total electrical installation of your station.

The findings, observations and conclusions are summarized in Audit report.

Thanking you,

For Shivalika Electricals & Engineers.

2
Electrical Audit Report 2019
­IOCL SANGANER AFS 
Ref. : 1095/SEE/15
Date : 04/09/2015

EXECUTIVE SUMMRY

Electricity has become an integral part of our everyday life and we better
understand its importance in our life during a few minutes of power outages. In
recent times, with the rapid growth of industries and commercial space, we are
witnessing an exponential increase in the number of electrical accidents. The
accidents not only cause loss of business but also cause a loss of life, brand
image, business continuity and loss of confidence among the employees in
workplace. It is high time to have Electrical Safety Audit at regular intervals to
check the status of electrical systems.

An Electrical Safety Audit (ESA) is a systematic approach to evaluate potential


hazards and to recommend suggestions for improvement. It is an important tool
for identifying areas of risks, hazards and potential accidents in plants,
deterioration of standards, for determining actions to minimize hazards.

……………………………………………
…………………………………………….

3
Electrical Audit Report 2019
­IOCL SANGANER AFS 

OBJECTIVE OF ELECTRICAL AUDIT

The primary objective of Electrical Audit is to review the continuation and safe operation of
the Aviation Fueling Station, Jaipur with respect to all Electrical equipment and also to
identify areas necessitating rectification action or other appropriate measures.
This audit would cover major areas of Electrical system and verify/indicate the details of
Audit findings and recommendations for rectification and corrective action.

Electrical Safety Audit helps in identifying:

 Electrical hazards to minimize the risk of accidents,

 Areas of risk or vulnerability in electrical systems and installations,

 Ensuring longevity of expensive electronic equipment like computers and


other machines,

 Development of a dynamic record of safety performance,

 Creation of positive cycle of safety improvement,

 Ensuring compliance with Regulatory and industrial safety related best


practices.

4
Electrical Audit Report 2019
­IOCL SANGANER AFS 

SCOPE OF WORK : Inspection of Electrical Equipment as per OISD Standard 235 , IE Rules
and as per Petroleum Rules on the following equipments :-

1. ELECTRICAL MCC ROOM, LIGHTING DISTRIBUTION SYSTEM


2. 50 KVA DG SET , AMF PANEL
3. TLD / TLF BAY
4. PUMP HOUSE
5. OFFICE BUILDING, STAFF ROOM, CONFRENCE ROOM, STORE ROOM AND LAB.
6. TANK FARM AREA
7. EARTHIG NETWORK
8. SOLAR SYSTEM


5
Electrical Audit Report 2019
­IOCL SANGANER AFS 

6
Electrical Audit Report 2019
­IOCL SANGANER AFS 

SURVEY AND EXAMINATION :

The Survey covered the examination and inspection of the entire electrical installation
giving particular stress on the following aspects.

a) Perfect and soundness of all installed electrical equipment as per relevant Indian
Standard IS 2148-1980/1981 and as per OISD Standards.

b) Routine Checking of equipments as per Preventive Maintenance Schedule to insuring


the maintaining of Flameproof condition of the equipments used

c) Installation and cable entry arrangement taken up

d) The possibility of any arcs and sparks at any of the electrical apparatus contained
inside the flameproof enclosure during normal operation as in the instance of a
switch or push button JB or terminal box etc. due to internal faults in the electrical
apparatus.

e) Necessary recommendations to substantially improve the safety of the entire AFS.



7
Electrical Audit Report 2019
­IOCL SANGANER AFS 

ELECTRICAL SAFETY AUDIT REPORT AS PER OISD VOL. 235

Location :- IOCL AFS SANGANER JAIPUR Date- 04/09/2015

A. ELECTRICAL SUBSTATION / SWITCH ROOM


A-01 Is Line Diagram of power /lighting distribution Need to update
and shock chart provided
A-02 Is the equipment easily accessible for OK
operation, inspection &maintenance
A-03 MCC Panel condition:
a) Doors okay and closed Door lock need to provided
b) Dust/soot/cobweb not existed YES
c) Lugs existing at each cable, YES
termination not loose. OK
d) Visual condition of switch contact
Fuse etc. OK
e) Control wiring condition
satisfactory. OK
f) Jumper condition between bus
and distribution ok OK
g) Grounding
h) Alarm/trip circuit working

A-04 Live Parts of equipment made inaccessible by OK


barriers /shrouds

A-05 No temporary electrical connection existing. NO


A-06 Condition of cable duct Filled with Sand YES
a) Cables are on rack Cable tray need to Provide
8
Electrical Audit Report 2019
­IOCL SANGANER AFS 
b) Cable deck clear YES
c) Sealing of duct OK
d) Cable identification tags. OK
A-07 Insulation mats (with ISI mark) existing are YES
enough in number
A-08 Protective relays set at recommended values YES
A-09 All fuses are of proper type and rating as YES
specified in single line diagram.
A-10 Fire extinguishers are of proper type and are in YES
working condition
A-11 Lighting condition OK (fixtures/ tubes/ YES
switches etc.)
A-12 Emergency lighting system in order. YES
A-13 All energized equipment provided with caution Need to provide in DG
boards. Room
A-14 Condition of transformer: NA
a) Grounding OK NA
b) No oil leak NA
c) Silica gel OK NA
d) Oil level OK NA
e) Terminal box earthing OK NA
f) Oil / winding temp. OK NA
g) Periodic oil quality test conducted NA
A-15 Whether location/type of transformer in NA
conformity with area classification drawings
A-16 Housekeeping is good YES

B. MOTORS IN PUMP HOUSE / COMPRESSOR ROOM

B-01 Is double independent earthing connection for YES


all motors provided.
B-02 Is grounding wire OK (not loose). YES
B-03 a) Is terminal box and gland OK, Flame YES
proofing maintained and not tampered.
b) Existing cable termination are proper? YES
B-04 a) Is push button earthed properly and flame YES
9
Electrical Audit Report 2019
­IOCL SANGANER AFS 
proof condition not tampered.
b) General condition of push button good. YES
B-05 Ground resistance at motor/ push button YES
measured and found okay.
B-06 No motor abnormality Vibration/ bearing NO
condition, faulty guard, fan condition,
excessive noise, high body temperature.
B-07 Existing preventive maintenance schedule OK. YES
B-08 a) Earthing resistance test schedules/ records YES
satisfactory.
b) Earthing pit condition OK YES
B-09 First-aid chart for treating electrical shocks YES
displayed
prominently in MCC room.

C. UNIT LIGHTING
C-01 All lighting fixture flame proof as per area YES
classification.
C-02 Whether flame proof condition of fixtures NO
ensured?
C-03 Whether proper earthing of fixture provided? YES
C-04 Condition of wiring good? YES
C-05 Does water enter and accumulate in fixture NO
distribution boxes etc ?
C-06 Whether lighting DB, switches, MCB well YES
maintained?
C-07 Any other unsafe point observed. NO

D. MAST LIGHTS (AREA LIGHTING)

D-01 Whether grounding of mast OK? L/A Earth pit to be separate


from existing grid
D-02 Condition of junction boxes, switch board, YES
fuses etc. OK
D-03 Approach to electrical installation and ladder YES
good and safe.

10
Electrical Audit Report 2019
­IOCL SANGANER AFS 
D-04 Condition of flood lights:
a) Is gasket present? YES
b) Is glass cover in good condition? YES
c) Is control gear condition OK YES
D-05 Is earthing electrode of mast OK and its YES
connection with mast proper?

E. TANFARM AREA, PIPELINES, LOADING/UNLOADING GANTRY

E-01 Are pipelines provided with flange earth YES


jumper connection for electrical continuity?
E-02 Are earthing provision on storage tanks well YES
maintained?
E-03 Condition of grounding electrode OK YES
E-04 Continuity of location, hoses maintained. YES
E-05 Grounding resistance at inlet of grounding YES
connection checked/date
E-06 Connection of earth-bonding of railway track YES
OK.
F. GENERAL
F-01 a) Area classification drawings duly approved YES
by PESO?
b) Conditions if any, specified by PESO for YES
electrical
substation, switch room etc. and their
compliance.
F-02 Certificate in respect of FLP for each electrical YES
equipment records maintained
F-03 Earthing network diagram available and site YES
checks done from
time to time.
F-04 Records for electrical testing/ checks YES
maintained up-to date.
F-05 Work permit system is effective and records YES
are maintained.

11
Electrical Audit Report 2019
­IOCL SANGANER AFS 

Recommendations :-

1. Main electrical MCB DB of ADMN Building is very congested and wire are criss cross
and working space is very less so new Vertical type DB need to provide for proper
working space and safe operation.

2. Lighting system to be replaced with energy efficient lights like LED. Specially for High
Mast Lighting .

3. ELCB Provided in Building lighting DB but not working /Tripping from End point
,earthing need to connect up to end point of every equipment and socket to insure
proper working of ELCB,s.

4. Some cable are laying loose in Underground cable trenches ,which need to lay
through cable trays and proper dressing.

5. Unused gearboxes & cables from Pole lights need to Isolate/disconnect and removed
from existing position.

6. Flameproof condition of pump motor for Pump no-1 & 2 is not up to mark so
replacement of new motor is suggested .

12
Electrical Audit Report 2019
­IOCL SANGANER AFS 
7. Two separate Earth pit need to provide for Lightning arrestor for Solar system.

TEST CERTIFICATE

Earth Tester Detail Frequency – Half Yearly


Make- WACO Sr no- 335864
Calibration Certi. NO. & validity- 54739I-8)1001/29/09/2019
Resistance in ohms
S.NO Earth Pit -No. Pit resistance Grid resistance Location Remark
Point- Point- Point- Point-
1(Max.) 2(Min.) 1(Max) 2(Min.)
1. Earth Pit No-1 0.78 0.68 0.48 0.38 DG N E.P. ok
2. Earth Pit No-2 0.88 0.78 0.68 0.58 PMCC ok
3. Earth Pit No-3 0.98 0.85 0.78 0.65 PMCC ok
4. Earth Pit No-4 0.78 0.67 0.65 0.55 PMCC ok
5. Earth Pit No-5 0.65 0.55 0.55 0.45 Workshop area ok
6. Earth Pit No-6 0.58 0.47 0.48 0.38 200 KL Tank-4 ok
7. Earth Pit No-7 0.98 0.86 0.62 0.52 200 KL Tank-5 ok
8. Earth Pit No-8 0.78 0.68 0.51 0.41 200 KL Tank-4 ok
9. Earth Pit No-9 0.98 0.88 0.60 0.50 200 KL Tank-5 ok
10. Earth Pit No-10 0.88 0.75 0.63 0.53 Tank No -3 ok
11. Earth Pit No-11 0.98 0.88 0.72 0.62 Tank No -2 ok
12. Earth Pit N-12 1.66 1.56 1.25 1.12 Tank No - 1 ok
13. Earth Pit No-13 0.92 0.82 0.75 0.65 Shift Room ok
14. Earth Pit No-14 0.98 0.82 0.65 0.55 Pump House ok
15. Earth Pit No-15 0.88 0.78 0.65 0.49 Pump House ok
16. Earth Pit No-16 0.82 0.72 0.62 0.52 Admn Building ok
17. Earth Pit No-17 0.68 0.57 0.48 0.38 Staff Room ok
18. Earth Pit No-18 1.8 1.7 1.2 1.1 Behind Conference hall ok
19. Earth Pit No-19 0.88 0.68 0.62 0.53 PMCC ok
20. Earth Pit No-20 0.64 0.54 0.43 0.36 PMCC ok
21. Earth Pit No-21 0.85 0.65 0.65 0.55 CCTV ok
22. Earth Pit No-22 0.78 0.68 0.66 0.56 DG Room ok
23. Earth Pit No-23 0.89 0.76 0.62 0.52 PMCC ok
24. Earth Pit No-24 0.45 0.35 0.76 0.78 HMT L/A ok

13
Electrical Audit Report 2019
­IOCL SANGANER AFS 
25. Earth Pit No-25 0.88 0.76 0.35 0.36 HMT L/A ok
26. Earth Pit No-26 1.7 1.5 Solar ok
27. Earth Pit No-27 1.2 1.1 Solar ok
28. Earth Pit No-28 1.3 1.2 Solar ok

Tested by Checked by

Earthing

Earthing is the provision of a safe path of electrical current to ground, in order to


protect structures,
plant and equipment from the effects of stray electrical current, and
electrostatics discharge.

Earth Electrode

A metal plate, pipe or other conductor embedded in the soil that makes a direct
contact to the general mass of the earth.

Earth Connection

A connection to the general mass of earth by means of an earth electrode. An


object is said to be Earthed when it is Electrically Connection to an earth
electrode and a conductor is said to be ‘Solidly Earthed’ when it is electrically
connected to earth electrode without a fuse, switch, circuit-breaker,
resistance or impedance in the earth connection.

14
Electrical Audit Report 2019
­IOCL SANGANER AFS 

15