IOCL SANGANER AFS
By
TO Ref. : 2035/SEE/19
Date : 12/09/2019
THE SR APTM ,
IOCL,
SANGANER AFS ,
JAIPUR (RAJASTHAN)
Dear Sir,
We are Pleased to inform you that the complete Electrical audit of electrical installation of
your station has carried out by us and also discussed with your technical staff about the
total electrical installation of your station.
Thanking you,
2
Electrical Audit Report 2019
IOCL SANGANER AFS
Ref. : 1095/SEE/15
Date : 04/09/2015
EXECUTIVE SUMMRY
Electricity has become an integral part of our everyday life and we better
understand its importance in our life during a few minutes of power outages. In
recent times, with the rapid growth of industries and commercial space, we are
witnessing an exponential increase in the number of electrical accidents. The
accidents not only cause loss of business but also cause a loss of life, brand
image, business continuity and loss of confidence among the employees in
workplace. It is high time to have Electrical Safety Audit at regular intervals to
check the status of electrical systems.
……………………………………………
…………………………………………….
3
Electrical Audit Report 2019
IOCL SANGANER AFS
The primary objective of Electrical Audit is to review the continuation and safe operation of
the Aviation Fueling Station, Jaipur with respect to all Electrical equipment and also to
identify areas necessitating rectification action or other appropriate measures.
This audit would cover major areas of Electrical system and verify/indicate the details of
Audit findings and recommendations for rectification and corrective action.
4
Electrical Audit Report 2019
IOCL SANGANER AFS
SCOPE OF WORK : Inspection of Electrical Equipment as per OISD Standard 235 , IE Rules
and as per Petroleum Rules on the following equipments :-
5
Electrical Audit Report 2019
IOCL SANGANER AFS
6
Electrical Audit Report 2019
IOCL SANGANER AFS
The Survey covered the examination and inspection of the entire electrical installation
giving particular stress on the following aspects.
a) Perfect and soundness of all installed electrical equipment as per relevant Indian
Standard IS 2148-1980/1981 and as per OISD Standards.
d) The possibility of any arcs and sparks at any of the electrical apparatus contained
inside the flameproof enclosure during normal operation as in the instance of a
switch or push button JB or terminal box etc. due to internal faults in the electrical
apparatus.
7
Electrical Audit Report 2019
IOCL SANGANER AFS
C. UNIT LIGHTING
C-01 All lighting fixture flame proof as per area YES
classification.
C-02 Whether flame proof condition of fixtures NO
ensured?
C-03 Whether proper earthing of fixture provided? YES
C-04 Condition of wiring good? YES
C-05 Does water enter and accumulate in fixture NO
distribution boxes etc ?
C-06 Whether lighting DB, switches, MCB well YES
maintained?
C-07 Any other unsafe point observed. NO
10
Electrical Audit Report 2019
IOCL SANGANER AFS
D-04 Condition of flood lights:
a) Is gasket present? YES
b) Is glass cover in good condition? YES
c) Is control gear condition OK YES
D-05 Is earthing electrode of mast OK and its YES
connection with mast proper?
11
Electrical Audit Report 2019
IOCL SANGANER AFS
Recommendations :-
1. Main electrical MCB DB of ADMN Building is very congested and wire are criss cross
and working space is very less so new Vertical type DB need to provide for proper
working space and safe operation.
2. Lighting system to be replaced with energy efficient lights like LED. Specially for High
Mast Lighting .
3. ELCB Provided in Building lighting DB but not working /Tripping from End point
,earthing need to connect up to end point of every equipment and socket to insure
proper working of ELCB,s.
4. Some cable are laying loose in Underground cable trenches ,which need to lay
through cable trays and proper dressing.
5. Unused gearboxes & cables from Pole lights need to Isolate/disconnect and removed
from existing position.
6. Flameproof condition of pump motor for Pump no-1 & 2 is not up to mark so
replacement of new motor is suggested .
12
Electrical Audit Report 2019
IOCL SANGANER AFS
7. Two separate Earth pit need to provide for Lightning arrestor for Solar system.
TEST CERTIFICATE
13
Electrical Audit Report 2019
IOCL SANGANER AFS
25. Earth Pit No-25 0.88 0.76 0.35 0.36 HMT L/A ok
26. Earth Pit No-26 1.7 1.5 Solar ok
27. Earth Pit No-27 1.2 1.1 Solar ok
28. Earth Pit No-28 1.3 1.2 Solar ok
Tested by Checked by
Earthing
Earth Electrode
A metal plate, pipe or other conductor embedded in the soil that makes a direct
contact to the general mass of the earth.
Earth Connection
14
Electrical Audit Report 2019
IOCL SANGANER AFS
15