Вы находитесь на странице: 1из 43

GAS INSULATED SUBSTATION

TABLE OF CONTENTS

INDEX PAGE NO.

1. ABSTRACT 2

2. INTRODUCTION 3

3. NEEDS OF GIS 7

4.SF6 CIRCUIT BREAKER 10

5.ELECTRICAL CONNECTION DIAGRAM 16

6.CURRENT TRANSFORMER 17

7.GAS INSULATED TRANSFORMER 20

8.ADVANTAGES OF GAS INSULATED TRANSFORMER 22

9.INTER-CONNECTION TRANSFORMER 23
10.DISCONNECTOR AND EARTHING SWITCHES 24
11.INTERNAL STRUCTURE OF GAS INSULATED
TRANSFORMER 31

12.V-I SENSOR CURRENT &VOLTAGE MEASUREMENT 34

13.SURGE ARRESTER CVT –WAVE TRAP 35

14.ADVANTAGES OF GIS 37

15.DISADVANTAGES OF GIS 40

16. ADVANCEMENTS IN GIS TECHNOLOGY 41

17.CONCLUSION 42

18.REFERENCE 43

Department of Electrical Engineering GGS Polytechnic 1


GAS INSULATED SUBSTATION

ABSTRACT
Due to rapid industrialization and increasing population all over the world, the need of
efficient and reliable power source has become the prime demand. But since
geographic area has reduced due to increasing population, creation of a compact but
efficient power supplying medium is required. Gas Insulated Substation is the solution
to such problems. Gas Insulated Substation uses Sulfur hexafluoride (SF6) gas which
has a superior dielectric property used at moderate pressure for phase to phase and
phase to ground insulation. In Gas Insulated Substationthe high-voltage conductors,
circuit breaker interrupters, switches, current transformers, voltage transformers and
lightning arresters are encapsulated in SF6 gas inside grounded metal enclosures.
Because of its compact nature, the size of the plant is reduced and hence the space
consumed is decreased. This paper presents a study of Gas Insulated Substation (GIS)
with reference to the 220/33kV GIS, Himachal Pradesh power transmission
corporation ltd.
The steps of technical development, stages of technical design, state of the art in the
production, and quality insurance are explained with practical examples. Focus is
given to applications worldwide with typical projects shown, including on-site works,
sequences of erection, testing, and civil works. Explanations are given about the
operational primary equipment (switching, grounding, disconnecting), secondary
system, gas handling, maintenance, and monitoring. All requirements are met to have a
safe handling of SF6 even under the assumption of an increasing demand for the use in
the electrical power supply.

Department of Electrical Engineering GGS Polytechnic 2


GAS INSULATED SUBSTATION

INTRODUCTION
Gas Insulated Substations are high voltage Substations that are compact, requiring
little maintenance when compared to air-insulated conventional Substations.
Compressed Gas Insulated Substations (CGIS) consist basically a conductor supported
on insulators inside an enclosure which is filled with sulfur hexafluoride gas (SF6).
The compactness is with the use of SF6 gas, which has high dielectric strength. The
voltage withstand capability of SF6 Busduct is strongly dependent on field
perturbations, such as those caused by conductor surface imperfections and by
conducting particle contaminants. The contaminants can be produced by abrasion
between components during assembly or operations.

Electrical insulation performance of compressed gas insulated Substation is adversely


affected by metallic particle contaminants. Free conducting particles, depending upon
their shape, size and location, may lead to serious deterioration of the dielectric
strength of the system and also one of the major factors causing breakdown of the
system and leading to power disruption. These particles can either be free to move in
the Gas Insulated Busduct (GIB) or they may be stuck either to an energized electrode
or to an enclosure surface. The presence of contamination can therefore be a problem
with gas insulated substations operating at high fields. If a metallic particle crosses the
gap and comes into contact with the inner electrode or if a metallic particle adheres to
the inner conductor, the particle will act as a protrusion on the surface of the electrode.
Consequently, voltage required for breakdown of the GIS will be significantly
decreased. Several methods have been used to reduce the effect of conducting
particles, including electrostatic trapping, use of adhesive coatings, and discharging of
conducting particles through radiation. Dielectric coating of a metallic electrode
surface affects the particle charge mechanism.

The charge acquired by a particle, the equation of motion, the bounce and the drag are
discussed by several authors. The present work makes use of the equation proposed by
H. Anis, K.D.Srivastava and M.M.Morcos, it also includes the concept of random

Department of Electrical Engineering GGS Polytechnic 3


GAS INSULATED SUBSTATION

motion along axial direction. The random motion is due to the cross-sectional
irregularities of the metallic particles.

Present work analyses the movement pattern of metallic particles in Gas Insulated
Substation (GIS) or Gas Insulated Busduct (GIB). In order to determine the particle
trajectories in a GIB, an inner diameter of 55 mm and outer enclosure diameter of 152
mm were considered. Aluminum, Copper and Silver particles of 0.2 mm/12 mm
(diameter/length) were considered to be present on the enclosure surface. The motion
of the metallic particle was simulated using the charge acquired by the particle, the
gravitational force on the particle, field intensity at the particle location, drag force,
gas pressure, restitution co-efficient and the Reynold‟s number. The distance traveled
by the particle, calculated using the appropriate equations, is found to be in good
agreement with the published work for a given set of parameters. The results are also
presented for other set of parameters.

In order to determine the random behavior of moving particles, the calculation of


movement in axial and radial directions was carried out by Monte-Carlo technique.
Typically for Aluminum particle for a given Busduct voltage of 100 kV RMS, the
movement of the particle (0.25 mm/12 mm) for 1.5 s was computed to be 30.839 mm
in radial and 841.12 mm in axial directions. Similar calculations are also extended for
other types of voltages. Typical results for aluminum, copper and silver particles are
presented in this thesis.

The effect of various parameters like radii and length of particles, co-efficient of
restitution, pressure in the Busduct and the applied voltage has been examined and
presented. Different metallic contaminants viz., Al, Cu and Ag have been considered
for the above study. Typically, a GIB of 55mm/152mm (inner conductor diameter is
55mm and outer enclosure diameter is 152mm) has been considered for a 132-kV
system.

The thesis presents the movement pattern of metallic particles at different operating
voltages in a Gas insulated Busduct (GIB) which has been simulated with and without

Department of Electrical Engineering GGS Polytechnic 4


GAS INSULATED SUBSTATION

enclosure coating. The purpose of dielectric coating is to improve the insulation


performance. Free conducting particles situated inside the GIS enclosure decrease
high local fields caused by conductor roughness. The coating reduces the charge on
the particle colliding with the coated enclosure, which in turn reduces the risk of
breakdown due to increase of the lift-off field of particles. The movement of a particle
has been carried out not only by its electric field effect on the particle but also
considers electromagnetic field and image charge effects. The simulated results are
presented at Power frequency, lightning/switching impulse superimposed on power
frequency, triangular, square and asymmetric voltages. Particle trajectories obtained
for various voltages of aluminum, copper and silver particles are presented and duly
discussed.

Gas Insulated Substations (GIS) is a compact, multicomponent assembly enclosed in a


ground metallic housing which the primary insulating medium is compressed sulphur
hexafluoride (SF6) gas. GIS generally consists components of

1. Circuit Breakers
2. Operating mechanism of circuit breaker
3. Current transformers
4. Disconnector
5. Maintenance Earthing switches
6. Fast acting Earthing switches
7. Voltage transformers
8. SF6 Bushing
9. Gas supply and gas monitoring equipment
10. Bus Bar
11. Voltage Transformer
12. Gas supply and Monitoring eqipment

Department of Electrical Engineering GGS Polytechnic 5


GAS INSULATED SUBSTATION

Department of Electrical Engineering GGS Polytechnic 6


GAS INSULATED SUBSTATION

NEEDS OF GIS

Gas Insulated Substations are used where there is space for providing the substation is
expensive in large cities and towns. In normal substation the clearances between the
phase to phase and phase to ground is very large. Due to this, large space is required
for the normal or Air Insulated Substation (AIS). But the dielectric strength of SF6 gas
is higher compared to the air, the clearances required for phase to phase and phase to
ground for all equipments are quite lower. Hence, the overall size of each equipment
and the complete substation is reduced to about 10% of the conventional air insulated
substation.
Extremely high dielectric properties of SF6 have long been recognized. Compressed
SF6 has been used as an insulating medium as well as arc quenching medium in
electrical apparatus in a wide range of voltages.
Gas Insulated Substations (GIS) can be used for longer times without any periodical
inspections. Conducting contamination (i.e. aluminum, copper and silver particles)
could, however, seriously reduce the dielectric strength of gas-insulated system.
A metallic particle stuck on an insulator surface in a GIS will also cause a significant
reduction of the breakdown voltage.
Gas insulated Substations have found a broad range application in power systems over
the last three decades because of their high reliability Easy maintenance, small ground
space requirements etc...
Because of the entire equipment being enclosed in enclosures, filled with pressurized
SF6 gas, installation is not subject to environmental pollutions, as experienced along
coastal areas or certain types of industries.
a) Such installations are preferred in cosmopolitan cities, industrial townships, etc.,
where cost of land is very high and higher cost of SF6 insulated switchgear is
justified by saving due to reduction in floor area requirement. It is not necessary
that high voltage or extra high voltage switchgear to be installed outdoors.
b) Since most of the construction is modular and the assembly is done in the works,
one site erection time both for supporting structures and switchgear is greatly
reduced.

Department of Electrical Engineering GGS Polytechnic 7


GAS INSULATED SUBSTATION

Locations where Gas Insulated Substation is preferred: -


i. Large cities and towns
ii. Under ground stations
iii. Highly polluted and saline environment Indoor GIS occupies very little space
iv. Substations and power stations located Off shore Mountains and valley regions

Explanation:
The SF6 Gas Insulated Substation (GIS) contains the same compartments as in the
conventional outdoor substations. All the live parts are enclosed in metal housings
filled with SF6 gas. The live parts are supported on cast resin insulators. Some of the
insulators are designed as barriers between neighboring modules such that the gas
does not pass through them. The entire installation is sub divided into compartments

Department of Electrical Engineering GGS Polytechnic 8


GAS INSULATED SUBSTATION

which are gas tight with respect to each other. Thereby the gas monitoring system of
each compartment can be independent and simpler.
The enclosures are of non magnetic materials such as aluminum or stainless steel and
are earthed. The gas tightness is provided with static „O‟ seals placed between the
machined flanges. The „O‟- rings are placed in the grooves such that after assembly,
the „O‟-rings are get squeezed by about 20%. Quality of the materials, dimension of
grooves and „O‟-seals are important to ensure gas tight performance of Gas Insulated
Substation.
Gas Insulated Substation has gas monitoring system. Gas inside each compartment
should have a pressure of about 3kg/cm2.The gas density in each compartment is
monitored. If the pressure drops slightly, the gas is automatically trapped up. With
further gas leakage, the low-pressure alarm is sounded or automatic tripping or lock-
out occurs.

Department of Electrical Engineering GGS Polytechnic 9


GAS INSULATED SUBSTATION

SF6 CIRCUIT BREAKER


Sulfur Hexafluoride (SF6) is an excellent gaseous dielectric for high voltage power
applications. It has been used extensively in high voltage circuit breakers and other
switchgears employed by the power industry. Applications for SF6 include gas
insulated transmission lines and'gas insulated power distributions. The combined
electrical, physical, chemical and thermal properties offer many advantages when used
in power switchgears. Some of the outstanding properties of SF6 making it desirable
to use in power applications are:
• High dielectric strength
• Unique arc-quenching ability
• Excellent thermal stability
• Good thermal conductivity

General Information:
Elimsan SF6 circuit breaker is equipped with separated poles each having its own gas.
In all types of the circuit breakers, gas pressure is 2 bars (absolute 3 bars). Even if the
pressure drops to 1 bar, there will not be any change in the breaking properties of the
circuit breaker due to the superior features of SF6 and Elimsan's high safety factor for
the poles. During arcing, the circuit breaker maintains a relatively low pressure (max
5-6 bars) inside the chamber and there will be no danger of explosion and spilling of
the gas around. Any leakage from the chamber will not create a problem since SF6 can
undergo considerable decomposition, in which some of toxic products may stay inside
the chamber in the form of white dust. If the poles are dismantled for maintenance, it
needs special attention during removal of the parts of the pole. This type of
maintenance should be carried out only by the experts of the manufacturer.
(According to ELIMSAN Arcing Products and Safety Instruction for Working on SF6
Circuit Breakers)

Operation of Circuit Breaker:


In general, the circuit breakers consist of two main parts, the poles and the
mechanism. The poles consist of contact and arc-extinguishing devices. The
mechanism is the part to open or close the contacts in the poles at the same time

Department of Electrical Engineering GGS Polytechnic 10


GAS INSULATED SUBSTATION

instantaneously (with max. 5 milisec. Tolerance). The closing and opening procedures
are performed through springs which are charged by a servomotor and a driving lever.
In the system, the closing springs are first charged. If "close" button is pressed the
opening springs get charged while the contacts get
closed. Thus, circuit breaker will be ready for opening. The mechanical operating
cycle of the circuit breaker is (OPEN-3 Min CLOSE/OPEN-3 Min- CLOSE/OPEN) or
(OPEN-0.3 sec-CLOSE/OPEN-3 Min CLOSE/OPEN). The second cycle is valid
when the circuit breaker is used with re-closing relay. In that case, after the closing
operation, the closing springs are charged by the driving lever or by driving motor (if
equipped). Thus, the circuit breaker will be ready for opening and re-closing.

Mechanical Life and Maintenance of The Mechanism:


Elimsan breaker mechanism can perform 10.000 opening-closing operations without
changing any component. The mechanical life of the circuit breaker is minimum lO’.
OOO operations. However, it needs a periodical maintenance depending on its
environment. In ideal working conditions, lubrication once a year or after every 1000
operations is sufficient. In dusty and damp environment, the mechanism should be
lubricated once every 3 - 6 months or after every 250 - 500 operations.
Thin machine oil and grease with molybdenum must be used for lubricating. Owing to
mechanism's capability of operating between -5°C and + 40 °C, it does not require a
heater.

Department of Electrical Engineering GGS Polytechnic 11


GAS INSULATED SUBSTATION

Auxiliary Switch:
The auxiliary switch mounted on the circuit breaker has 12 contacts. One of them is
for antipumping circuit, four of them are allocated for opening and closing coils. The
remaining 7 contacts are spare. Three of them are normally opened and four are
normally closed. When it is necessary, the number of the contacts can be increased.

Rapid Automatic Reclosing:


The circuit breaker which opens due to a short circuit failure, can be re-closed
automatically after a pre selected time by arc closing relay, assuming the fault is
temporary. Thus, we avoid long time power loss in case of temporary short circuits.
But, if the fault lasts after re-closure, the protection relay will trip to open the circuit
breaker again.

What to Specify on The Order?


1- Rated voltage of the circuit breaker
2- Rated current of the circuit breaker
3- Rated short circuit breaking current
4- Voltages of opening and closing coils
5- Motor supply voltage (if equipped)

Department of Electrical Engineering GGS Polytechnic 12


GAS INSULATED SUBSTATION

Closing and Opening Operation of the Circuit Breaker:

When manual or motor-drive is used, the circuit breaker will be ready to close. The
closure can be actuated pressing the closing button located on the circuit breaker. It is
recommended to close it using remote control system for secure operations. The
opening can be performed either by opening button or remote-controlled opening coil.
In case of a fault, the relay signal actuates the opening coil and circuit breaker opens.
(This is mechanically a primary protection system). In addition, there is an anti-
pumping relay for preventing the re-closing and opening of the circuit breaker more
than one cycle (O - C - O) and for preventing possible troubles created by remote
closing button.

Commissioning:
The outer surfaces of epoxy insulating tubes of the poles are to be wiped out with a
clean and dry cloth. The wiring and connections of the auxiliary circuit are to be
carefully examined. DC voltage should be checked to see whether it is suitable for coil
and motor or not (if equipped). The opening-closing coils are to be operated 15-20
times and the accuracy of the relay circuit is to be checked before energizing the
circuit breaker. The circuit breaker is to be mounted with two MI2 bolts through its
anchoring shoes. It should not move during operation. No excessive load should be
exerted to the poles and if possible, flexible cables should be used. The incoming and
outgoing contacts must have clean surfaces and their contact resistance should be as
low as possible. When connecting the circuit breaker to protection system and
auxiliary supply, the cable cross sections should be according to the table given. The
circuit breaker must be grounded through at least 16 mm steel tape (by cable shoe).
After all, the following procedure must be performed:
1. Open the isolator of circuit breaker,
2. Prepare the circuit breaker for closing operation by driving mechanism,
3. Close the isolator of circuit breaker firmly,
4. Send the closing signal to the circuit breaker,

Department of Electrical Engineering GGS Polytechnic 13


GAS INSULATED SUBSTATION

The Maintenance of Circuit Breaker During Operation:


Normally, at least once a year or after every 500 operations, the circuit breaker must
be maintained. During maintenance, the moving parts of the mechanism must be
lubricated carefully. The insulating parts are to be wiped out by a clean and dry cloth.
When maintaining, the circuit breaker should be open and high voltage sides must be
grounded. Auxiliary power supply should also be disconnected. On saline areas near
seaside, the insulating parts of the circuit breaker must be carefully cleaned, at least
once every two months. If not, the microscopic salt particles drawn by wind from the
sea will create conductive layers on the insulating surfaces and may cause surface
flashover. Before maintenance, first circuit breaker, then isolator should be opened
and grounded carefully. The maintenance of circuit breaker must be done after
checking the open position of isolator contacts by eye.

Main Dimensions (In mm)

Department of Electrical Engineering GGS Polytechnic 14


GAS INSULATED SUBSTATION

Department of Electrical Engineering GGS Polytechnic 15


GAS INSULATED SUBSTATION

ELECTRICAL CONNECTION DIAGRAM

Department of Electrical Engineering GGS Polytechnic 16


GAS INSULATED SUBSTATION

CURRENT TANSFORMER
Current transformers are used in electrical grids for measurement and protective
applications to provide signals to equipment such as meters and protective relays by
stepping down the current of that system to measurable values. Their role in electrical
systems is of primary importance because the data sent by current transformers
represent the heartbeat of the entire system.
RHM Internationals proprietary dry type Current Transformers are unique as they
provide a rugged, reliable option for high voltage metering and protection operations
up to 550 kV.
Our high-quality Current Transformers are based on a unique U-shaped bushing
design for the primary winding. The bushing is a very fine capacitance graded
insulator. In a new approach to dry designs, our advanced proprietary HV
DryShieldTM composite insulation system uses reliable materials like PTFE
(Polytetrafluoroethylene) and silicon rubber to provide a low stress, uniform field
distribution between the conductor and the outside structure.
The primary and secondary windings are independently sealed resulting in a totally
weather resistant design. Oil or gas is not required for insulation. Therefore, our
environmentally friendly Current Transformers completely eliminate the risk of
explosion and toxic leaks.
Considering the difficulty for our customers to schedule circuit outages for routine
upgrades and maintenance, the high cost of maintenance, and environmental issues,
RHM International‟s Current Transformers provide exceptionally low cost of
ownership and offer you peace of mind as they are truly maintenance free.

Customer benefits:
• Totally safe – no risk of explosion
• Totally maintenance free – exceptional low cost of ownership
• Environmentally friendly – no risk of toxic leak and recyclable insulation materials
• 2 to 3 times lighter than conventional oil or gas-based products
• Mature and Innovative with unmatched quality records – not a single failure in 20
000 HV DryShieldTM equipped products in the field

Department of Electrical Engineering GGS Polytechnic 17


GAS INSULATED SUBSTATION

• A new approach to dry design without the limitations of conventional dry Current
Transformers
• All products are developed and manufactured in an ISO 9001 certified plant and
compliant to IEC and IEEE international standards.

Main Characteristics:
1.Performance:
Highest voltage for equipment: 40.5-550 kV
Rated frequency: 50, 60 Hz
Rated primary current: 5-5000 A (up to 8000 A under specific conditions – please
contact us)
Rated secondary current: 5 A, 1 A
Rated output: 10-50 VA
Accuracy class for measuring current transformer: 0.2S, 0.2, 0.5S and 0.5 class
Instrument security factor: 5, 10
Accuracy class for protective current transformer: 5P, 10P and TPY (TPS, TPX and
TPZ on demand)
Accuracy limit factor for protective current transformer: 5,10, 15, 20, 30, 40
Secondary cores: 1-8
2. Environmental Condition:
Places of operation: Indoors and outdoors
Environmental temperature: -45°c [-49F] / +45°c [113F]
Altitude: <1000m above sea level (when higher than 1000m, specific design available.
Please contact us)
Pollution level: fully compliant to Class IV environments (IEC category – very heavy
pollution level)
3. Type tests and special tests include:
• Measurement of capacitance and Dielectric Dissipation under Um/√3 and 10kV, the
Dielectric dissipation factor (tanδ) is less than 0.004
• Short-time current tests: Thermal short-time current (Ith): 50 kA, 3s Rated dynamic
current (Idyn): 125 kA (peak value)
• Temperature-rise test: 75 K

Department of Electrical Engineering GGS Polytechnic 18


GAS INSULATED SUBSTATION

• Mechanical tests (see table 2)


• Determination of errors
• Insulation and thermal stability test (36h according to standard but tested 72h for
550kV)
4. Routine tests: Before leaving the factory, the following routine tests are
carried out:
on primary winding:
• Power-frequency withstand test
• Power-frequency withstand test between sections of primary
• Partial discharge measurement
• Capacitance and dielectric dissipation factor measurement
• Verification of terminal markings

on secondary windings:
• Power-frequency withstand test
• Power-frequency withstand test between sections of secondary windings
• Inter-turn over-voltage test
• Determination of errors

Department of Electrical Engineering GGS Polytechnic 19


GAS INSULATED SUBSTATION

GAS INSULATED TRANSFORMER


Introduction:
Since gas insulated transformer does not need the conservator, the height of
transformer room can be reduced. In addition, its non-flammability and non
tankexplosion characteristics can remove the fire fighting equipment from transformer
room. As a result, gas insulated transformer, gas insulated shunt reactor and GIS
control panels can be installed in the same room. With such arrangement, a fully SF6
gas insulated substation can be recognized.

Specifications and Ratings:


Rising demand for electric power in large cities has encouraged large-scale substations
to be tucked away underground in overpopulated urban areas, leading to strong
demand for incombustible and non-explosive, large-capacity gas insulated
transformers from the view point of accident prevention and compactness of
equipment. In line with this requirement, several types of large-capacity gas insulated
transformer have been developed.

The gas-forced cooling type was considered to be available for up to approximately


60MVA, while all other gas insulated transformer with higher ratings are liquid
cooled. But the liquid cooling type has the disadvantage of a complex structure for
liquid cooling. Thus, TOSHIBA began development of gas forced cooling type gas
insulated transformer, making best use of accumulated experience, latest analyzing
technique and the results of innovative research activities. As a result, TOSHIBA has
delivered 275kV- 300MVA gas cooled and gas insulated transformer, of which its
structure is as simple as the oil immersed type and is the largest capacity gas insulated
transformer in the world.

Realization of gas insulated transformer:


Since heat capacity of SF6 gas is much smaller than that of insulating oil, the
following measures are taken into account.
1. Raise the SF6 gas pressure to 0.5MPa

Department of Electrical Engineering GGS Polytechnic 20


GAS INSULATED SUBSTATION

2. Produce as large flow as possible by optimizing the layout of gas ducts in the
windings
3. Develop high capacity gas blower with high reliability
4. Apply highly thermal-resistant insulating materials to raise the limit of winding
temperature rises.

Department of Electrical Engineering GGS Polytechnic 21


GAS INSULATED SUBSTATION

ADVANTAGE OF GAS INSULATED TRANSFORMER

1. Non-flammability: Gas insulated transformers, using incombustible SF6 gas as a


insulation and cooling medium, enable to remove a fire fighting equipment from
transformer room.
2. Tank-explosion Prevention: Pressure tank enables to withstand the pressure rise
in case of internal fault.
3. Compactness: By directly coupling with gas-insulated switchgear, substation
space can be minimized as the result of compact facilities.
4. Easy installation: Oil or liquid purifying process is not necessary in case of gas
insulated transformer.
5. Easy inspection and maintenance work: Only SF6 gas pressure shall be
basically monitored during periodically inspection.
6. Environmentally Friendly: The use of SF6 gas abolishes the risk of oil leakage.

Department of Electrical Engineering GGS Polytechnic 22


GAS INSULATED SUBSTATION

INTER CONNECTING TRANSFORMER


▪ An autotransformer is an electrical transformer with only one winding.
▪ The winding has at least three electrical connection points called taps. The voltage
source and the load are each connected to two taps.
▪ One tap at the end of the winding is a common connection to both circuits (source
and load). Each tap corresponds to a different source or load voltage.
▪ An autotransformer for power applications is typically lighter and less costly than a
two-winding transformer, up to a voltage ratio of about 3:1 beyond that range a
two-winding transformer is usually more economical.
▪ In an autotransformer a portion of the same winding acts as part of both the
primary and secondary winding.

Department of Electrical Engineering GGS Polytechnic 23


GAS INSULATED SUBSTATION

DISCONNECTOR AND EARTHING SWITCHES


Disconnectors and earthing switches are used to protect personnel while working on
operational equipment and must therefore be very reliable and operationally safe even
under adverse climatic conditions. Disconnectors and earthing switches are often
offered as a combination of both.
Disconnectors have to isolate downstream operational equipment – i.e., de-energised
equipment – from the connected circuits. Thus, they establish a visible isolating
distance in air towards downstream operational equipment.
The task of an earthing switch is to earth de-energised parts of the switchgear and – in
the case of multi-pole earthing switches – to short-circuit them at the same time.

Department of Electrical Engineering GGS Polytechnic 24


GAS INSULATED SUBSTATION

Application:
Disconnectors and earthing switches are suitable for indoor installations up to 36 kV.
Due to their cast-resin ribbed insulators, the disconnectors and earthing switches can
also be used with high air humidity and occasional condensation, e.g., in tropical
areas.
The devices are protected against corrosion. Steel parts are either galvanised and
yellow-passivated, or electrostatically coated with epoxy-resin powder over a
phosphate layer.
The switching devices can be installed in any position with horizontal shaft. Designs
for installation with the shaft in vertical position are also available.

Endurance:
Normally, disconnectors and earthing switches are operated very rarely. Therefore
they are not designed for a high number of operating cycles. The mechanical
endurance and the contact endurance are:
– 5,000 operating cycles for the disconnector
– 1,000 operating cycles for the earthing switch.

Functions of the switching devices:


3DA/3DC disconnectors have the following functions:
– Opening or closing circuits when either negligibly small currents have to be
switched off/on or when there is no significant voltage difference between the circuits
to be disconnected or connected.
– Establishing an isolating distance between the terminals of each pole in the open
position.
The task of 3DD/3DE earthing switches is to earth deenergised parts of the switchgear
and – in the case of multi-pole earthing switches – to short-circuit them at the same
time.
Short-circuit capability:
The short-circuit capability of closed disconnectors and earthing switches is tested
according to VDE. Due to the loopless circuit, the disconnectors need not be
interlocked against being opened by short-circuit forces.

Department of Electrical Engineering GGS Polytechnic 25


GAS INSULATED SUBSTATION

Earthing switches built on disconnectors or used as independent devices have to be


interlocked in presence of peak withstand currents above 50 kA if the earthing switch
is installed with the peak withstand current flowing through the earthing switch in
direction 2 according to the drawing shown on the right. In this direction, strong
opening forces are effective.
Sufficient interlocking is guaranteed for motor operating mechanisms as well as for
self-blocking manual operating mechanisms (e.g., spherical joint mechanism). For
earthing switches built on a disconnector, the mechanical interlock between the
disconnector and the earthing switch is a simple means to exclude the disadvantages
of the energy direction with opening force effect.
Description
Operating mechanisms
Motor operating mechanism:
The motor operating mechanism – provided for disconnectors and earthing switches
type 3D– mainly consists of a DC compound-wound motor, degree of protection IP00,
which drives the eccentric shaft of a free-wheeling mechanism via a single-step spur
gearing. The free-wheeling mechanism makes the crank (2) rotate counter-clockwise.
The crank is linked with the drive lever through a short drive rod, and the drive lever
is connected with the operating shaft (4).
A 180° turn of the crank produces a switching angle of 90° at the operating shaft. In
the end positions of the switching device, the drive motor is de-energised via built-in

Department of Electrical Engineering GGS Polytechnic 26


GAS INSULATED SUBSTATION

position switches. If an AC motor operating mechanism is required, a rectifier is


installed additionally.

The time from initiation of the command until reaching the end position or arrival of
the feedback (total operating time) is 3 s as a maximum at the lowest value of the
operating voltage.

Manual operating mechanisms:


Instead of being operated by a motor, the operating shaft can also be actuated
manually. Operation by means of a switching rod depends on the mounting position
and the accessibility. Switching rods are made of glass-fibre reinforced polyester tube
and can be used in switchgear with rated voltages above 1 kV. These switching rods
are used to actuate the switching rod lever (available as an accessory) mounted on the
operating shaft.
Switching rod levers made of insulating material are always used where the necessary
minimum distances are not reached. For fixing in the end positions, an elastic latch is
always provided for switching rod actuation (see interlocks).

Interlocks

Department of Electrical Engineering GGS Polytechnic 27


GAS INSULATED SUBSTATION

Latch:
For disconnectors and earthing switches a latch can be supplied, which latches tight in
the end positions in an elastic way. Such a latch must be provided when these
switching devices are operated manually with a switching rod.

Mechanical interlocking:
Disconnectors with built-on earthing switch can be equipped with a mechanical
interlock if the earthing switch is actuated by means of a switching rod.
Power-operated switching devices must be interlocked with the means belonging to
the operating mechanism, i.e., actuation must be prevented. For this purpose, the part
without power operating mechanism requires an auxiliary switch.
If neither the disconnector nor the earthing switch is power-operated, mechanical
interlocking is possible in connection with an electromechanical lockout. The
electromechanical lockout is then mounted on the disconnector.

Department of Electrical Engineering GGS Polytechnic 28


GAS INSULATED SUBSTATION

Electromechanical lockout:
Electromechanical lockout devices can be installed on all disconnectors and earthing
switches without power operating mechanism. The lockout devices block the
switching devices in the end positions when the solenoid is not excited. In the
intermediate position (faulty position) the lockout is not effective. The magnet coils
are suitable for continuous operation.

Interlocks for motor operating mechanisms:


Via switchgear interlocking system:
For operation in connection with a switchgear interlocking device 8TJ2, a poled relay
is required to prevent maloperation. Interlocks on the disconnector can be omitted.
For operation in connection with a switchgear interlocking device 8TK, no other
auxiliary contactors are required.
Via auxiliary contactor:
With an auxiliary contactor (with or without command execution) and pushbuttons,
additional protective measures must be taken against impermissible switching
operations.
Via changeover switch:
The simplest possibility of control is a changeover switch. However, adequate
protective measures against impermissible switching operations must be taken here as
well.

The opening of the line isolator or busbar section isolator is necessary for safety, but
not sufficient. Grounding must be conducted at both the upstream and downstream
sections of the device under maintenance. This is accomplished by earthing switches.

Department of Electrical Engineering GGS Polytechnic 29


GAS INSULATED SUBSTATION

Disconnect switches are designed to continuously carry load currents and momentarily
carry short circuit currents for a specified duration.
They are designed for no-load switching, opening, or closing circuits where negligible
currents are made or interrupted (including capacitive current and resistive or
inductive current, or when there is no significant voltage across the open terminals of
the switch.

Department of Electrical Engineering GGS Polytechnic 30


GAS INSULATED SUBSTATION

INTERNAL STRUCTURE OF GAS


INSULATED TRANSFORMER

MERITS IF GIT OVER OIT: -


• Nonflammability – Gas insulated transformers, using incombustible SF6 gas
as insulation and cooling medium, enable to remove a fire fighting equipment
from transformer room.
• Non-Tank – explosion - Pressure tank enables to withstand the pressure rise in
case of internal fault.
• Compactness – Since conservator or pressure relief equipment is not
necessary, height of transformer room can be reduced approximately 2 – 2.5
meters.

Department of Electrical Engineering GGS Polytechnic 31


GAS INSULATED SUBSTATION

• Easy installation – oil or liquid purifying process is not necessary in case of


gas-insulated 60 transformer.
• Easy inspection and maintenance work -Only SF6 gas pressure shall be
basically monitored during periodically inspection.

SMART GIS - Integration of Electronic CT’s & PT’s:


• The Combined sensors are the Rogowski coil for current measurement and the
capacitive divider for voltage measurement

• A combined current and voltage sensor have been developed to replace the
conventional current and voltage transformers in GIS.

Department of Electrical Engineering GGS Polytechnic 32


GAS INSULATED SUBSTATION

Why Combined Voltage & current Sensor?


Advanced CT‟s without a magnetic core (Rowgowski coil) & Capacitive sensor have
been developed to save space and reduce the cost of GIS. The output signal is at a low
level, so it is immediately converted by an enclosure mounted device to a digital
signal
• Small size - Helps to optimize the use of space in the switchgear
• Lighter weight means less material usage and lower life cycle costs (LCC)
• Large dynamic range - permits minimization of number of sensor types needed
and
• improvement of some protection functions.
• Protection and measurement functions combined.
• Lower losses mean lower LCC (Life Cycle Cost)

Department of Electrical Engineering GGS Polytechnic 33


GAS INSULATED SUBSTATION

V-I SENSOR CURRENT & VOLTAGE


MEASURMENT

• Current Measurement – Current Sensor instead of Current Transformer


• The current sensor is based on a Rogowski coil (a coreless inductive current
transformer).
• Voltage Measurement – Voltage Sensor instead of Voltage Transformer
• The voltage sensor is based on a capacitive electrical field sensor (Capacitive
ring sensor).
• The capacitive ring, which acts as a voltage sensor, also has a linear
characteristic and is very simple in terms of the insulation.

Department of Electrical Engineering GGS Polytechnic 34


GAS INSULATED SUBSTATION

SURGE ARRESTER-CVT-WAVE TRAP


Capacitor Voltage Transformers convert transmission class voltages to standardized
low and easily measurable values, used for metering, protection and control of the
high voltage system.

Additionally, Capacitor Voltage Transformers serve as a coupling capacitor for


coupling high frequency power line carrier signals to the transmission line.

Lightning Arresters or Surge Arresters are always connected in Shunt to the


equipment to be protected, they provide a low impedance path for the surge current to
the ground

Line trap also is known as Wave trap. It traps Hi-frequency communication signals
sent on the line from the remote substation and diverting them to the telecom/tele
protection panel in the substation control room (through coupling capacitor 38 and
LMU).

Department of Electrical Engineering GGS Polytechnic 35


GAS INSULATED SUBSTATION

This is relevant in Power Line Carrier Communication (PLCC) systems for


communication among various substations without dependence on the telecom
company network.

Department of Electrical Engineering GGS Polytechnic 36


GAS INSULATED SUBSTATION

ADVANTAGES OF GIS

A GIS has many advantages over a conventional substation, including a space saving
and flexible design, less field construction work resulting in quicker installation time,
reduced maintenance, higher reliability and safety, and excellent seismic withstand
characteristics. Aesthetics of GIS are far superior to that of a conventional substation,
due to its substantially smaller size.

A GIS can even be installed in a building, if desired. When all of these advantages are
taken into consideration, a GIS is a cost-effective alternative to a conventional
substation that offers many benefits to the end user.

i. Special Features: - Enhanced insulating properties and reduced long-term


operational costs by means of sealed metal enclosure filled with SF6 gas.

ii. Reliability: -Extensive experience in designing optimum phase and feeder


spacing dimensions according to site conditions enable compact dimensions
that reduce space requirements to less than 20% of conventional air insulated
substations

iii. Compact Design: -Ensured personnel safety by earthed enclosure, numerous


interlocks and lockout devices. Increased stability during earthquakes with a
low center of gravity.

iv. Maintenance: -Virtual elimination of long-term maintenance costs and


contamination of critical components by means of SF6 gas-filled metal
enclosures, automatic monitoring of operating mechanisms and SF6 gas
system.

v. Efficient Installation: -Assembly at factory and shipment in one complete bay


dramatically reduces installation time and customer's costs.

Department of Electrical Engineering GGS Polytechnic 37


GAS INSULATED SUBSTATION

vi. Environmental: -Minimized operation noise levels allow installation in urban


and sub-urban indoor substations. Elimination of radio interference problems
and individual painting of enclosures with the colour of customer choice.

vii. Space Saving: - SF6 switchgear installations take up only 10% of the space
required for the conventional installations.

viii. Economical: - Initial high investment is required for installation but the cost
can be comparable for the less maintenance, reliable, safe operation against
conventional substation. Ability to interrupt out-of-phase

ix. Compatibility: - It is incombustible, non toxic, colourless and chemically


inert.

x. Low Weight: - due to aluminium enclosure, corresponds to low cost


foundations and buildings.

xi. The dielectric strength of SF6 gas at atmospheric pressure is approximately


three times that of air.

xii. It has arc-quenching properties 3 to 4 times better than air at equal pressure.

xiii. Ability to interrupt short-line faults

xiv. Overvoltage is kept to a minimum.

xv. Minimum gas leakage (less than 0.1% per year).

xvi. The use of SF6 gas as an insulating medium in switchgear reduces the clearance
distance between active and non-active parts of a switchgear facilitating the
following advantages of gas insulated applications compared to air insulated
applications:

Department of Electrical Engineering GGS Polytechnic 38


GAS INSULATED SUBSTATION

● Less space requirements - especially in congested city areas


● Less sensitivity to pollution, as well as salt, sand or even large amounts of
snow
● Less operation & maintenance costs

Department of Electrical Engineering GGS Polytechnic 39


GAS INSULATED SUBSTATION

DISADVANTAGES OF GIS

a) It requires huge amount of area.

b) Cost is higher compared to Air Insulated Substation or conventional substation.


Maintenance cost is more.

c) Normally this type of substations is indoor type and requires separate building.
Each and every component of substation is exposed to air and pollution.

d) Maintaining Cleanliness is very important. Dust or moisture inside the


compartment causes the flash overs so frequent flashovers and breakdown
occurs.

e) When fault occurs internally, the outage period will be very long. The damage
effect will also be severe.

f) Installation time is also more.

Department of Electrical Engineering GGS Polytechnic 40


GAS INSULATED SUBSTATION

ADVANCEMENTS IN GIS TECHNOLOGY

(For Further Space reduction)


• Gas Insulated Transformer (GIT) Instead of Oil Immersed Transformer
(OIT).
• SMART GIS - Integration of Electronic CT‟s & PT‟s
• Combined Earthing Switch & Disconnector

COMBINED DISCONNECTOR/EARTHING SWITCH:

The DSES incorporates the two functions of a disconnector and a maintenance


earthing switch as a result saving the space in GIS.

This is achieved by a sliding contact characterized by three defined positions:


• disconnector open / earthing switch closed
• disconnector closed / earthing switch open
• disconnector open / earthing switch open

The use of one moving contact for the disconnector and the earthing switch inhibits
simultaneous closed position of both switches.

Combined disconnector and earthing switch are mounted at the front, and acts via
bevel gears and an insulating shaft on the three parallel contact pins.

Depending on the direction of movement the contacts act as disconnector or earthing


switch (maintenance earthing switch).

By means of a crank handle, manual operation of the combined disconnector and


earthing switch is also possible.

Department of Electrical Engineering GGS Polytechnic 41


GAS INSULATED SUBSTATION

CONCLUSION

GIS are necessary for EHV&UHV and some important areas to be studied include
more conservative designs better particle control&improved gas
handling&decomposition product management techniques Achieving&maintaining
high levels of availability requires a more integrated approach to quality control by
both users and manufactures.

Department of Electrical Engineering GGS Polytechnic 42


GAS INSULATED SUBSTATION

REFERENCES
I prepared this report on “GAS INSULATED SUBSTATION” by using
following web sites.

Web Sites: -
• www.wikipedia.com

• www.scribd.com

• www.google.com

Department of Electrical Engineering GGS Polytechnic 43

Вам также может понравиться