Академический Документы
Профессиональный Документы
Культура Документы
Generator Protection
Instruction Manual
Preface
Introduction
This guide and the relevant operating or service manual documentation for the equipment provide
full information on safe handling, commissioning and testing of this equipment.
Before carrying out any work on the equipment, the user should be familiar with the contents of
this manual, and read relevant chapter carefully.
This chapter describes the safety precautions recommended when using the equipment. Before
installing and using the equipment, this chapter must be thoroughly read and understood.
The information in this chapter of the equipment documentation is intended to ensure that
equipment is properly installed and handled in order to maintain it in a safe condition.
When electrical equipment is in operation, dangerous voltages will be present in certain parts of
the equipment. Failure to observe warning notices, incorrect use, or improper use may endanger
personnel and equipment and cause personal injury or physical damage.
Before working in the terminal strip area, the equipment must be isolated.
Proper and safe operation of the equipment depends on appropriate shipping and handling,
proper storage, installation and commissioning, and on careful operation, maintenance and
servicing. For this reason, only qualified personnel may work on or operate the equipment.
Are familiar with the installation, commissioning, and operation of the equipment and of the
system to which it is being connected;
Are able to safely perform switching operations in accordance with accepted safety
engineering practices and are authorized to energize and de-energize equipment and to
isolate, ground, and label it;
Are trained in the care and use of safety apparatus in accordance with safety engineering
practices;
DANGER!
It means that death, severe personal injury, or considerable equipment damage will occur if safety
precautions are disregarded.
WARNING!
It means that death, severe personal, or considerable equipment damage could occur if safety
precautions are disregarded.
CAUTION!
It means that light personal injury or equipment damage may occur if safety precautions are
disregarded. This particularly applies to damage to the device and to resulting damage of the
protected equipment.
WARNING!
The firmware may be upgraded to add new features or enhance/modify existing features, please
make sure that the version of this manual is compatible with the product in your hand.
WARNING!
During operation of electrical equipment, certain parts of these devices are under high voltage.
Severe personal injury or significant equipment damage could result from improper behavior.
Only qualified personnel should work on this equipment or in the vicinity of this equipment. These
personnel must be familiar with all warnings and service procedures described in this manual, as
well as safety regulations.
In particular, the general facility and safety regulations for work with high-voltage equipment must
be observed. Noncompliance may result in death, injury, or significant equipment damage.
DANGER!
Never allow the current transformer (CT) secondary circuit connected to this equipment to be
opened while the primary system is live. Opening the CT circuit will produce a dangerously high
voltage.
WARNING!
Exposed terminals
Do not touch the exposed terminals of this equipment while the power is on, as the high voltage
generated is dangerous
Residual voltage
Hazardous voltage can be present in the DC circuit just after switching off the DC power supply. It
takes a few seconds for the voltage to discharge.
CAUTION!
Earth
Operating environment
The equipment must only be used within the range of ambient environment detailed in the
specification and in an environment free of abnormal vibration.
Ratings
Before applying AC voltage and current or the DC power supply to the equipment, check that they
conform to the equipment ratings.
Do not attach and remove printed circuit boards when DC power to the equipment is on, as this
may cause the equipment to malfunction.
External circuit
When connecting the output contacts of the equipment to an external circuit, carefully check the
supply voltage used in order to prevent the connected circuit from overheating.
Connection cable
Copyright
Manual: R1.01 NR ELECTRIC CO., LTD.
P/N: EN_YJBH2041.0086.0002 69 SuYuan. Avenue, Nanjing 211102,China
Copyright © NR 2012. All rights reserved
Tel: 86-25-87178185, Fax: 86-25-87178208
We reserve all rights to this document and to the information Website: www.nari-relays.com
contained herein. Improper use in particular reproduction and Email: NR_TechSupport@nari-relays.com
dissemination to third parties is strictly forbidden except where
expressly authorized.
Table of contents
Preface .............................................................................................................................................. i
Introduction..................................................................................................................................i
1.3 Features...................................................................................................................... 5
4.4.7 Viewing event records via RCSPC support software ........................................... 106
10.6.1 Medium and heavy duty terminal block connections ......................................... 280
11.6.2 Connection way of protection equipment and personal computer ..................... 298
Chapter1 Introduction
1.1 Application
RCS-985G is a microprocessor based generator protection relay integrated with main and backup
protection. It provides complete electrical protection for large-sized generators, including
turbo-generator, hydro-generator, gas turbine generator and pumped-storage generator. The
RCS-985G relay is suited for wall surface mounted or flush mounted into a control panel. Figure
1.1-1 shows a typical application of RCS-985G.
B B
Exciting
Transformer
Generator B B
For a large-sized generator, panel A and B are both equipped with generator differential protection
and exciting transformer (exciter) differential protection. RCS-985G is equipped with two kinds of
percentage differential protection (variable slope percentage differential protection and DPFC
percentage differential protection) in order to meet high performance not only in speed but also in
security.
Panel A and B are equipped with a complete set of backup protection for generator and use two
groups of independent CTs.
For earth fault protection of rotor, two sets of such protection cannot work simultaneously as
influence between them will appear. Therefore only one set of earth fault protection of rotor can be
enabled during operation. If the other set will be switched on at anytimes, this current set shall first
quit before letting the other set operates.
Main protection and backup protection adopt one common group of CTs.
Panel A and B shall adopt different potential transformer VTs or its different windings so far as
possible.
For turn-to-turn fault protection of generator, in order to prevent unwanted operation due to VT
circuit failure at HV side which is used dedicatedly for this protection, one set of protection shall
adopt two groups of VT. However, if we consider adopting only independent VT windings, then
too many VTs will be installed at generator terminal which is not reasonable. Therefore it is
recommended to equip three VTs at generator terminal, named VT1, VT2 and VT3.
Panel A adopts voltage from VT1 and VT3 while panel B from VT2 and VT3. During normal
operation, panel A adopts VT1 and panel B adopts VT2 while VT3 is as a backup VT to both of
them. If circuit of VT1 or VT2 fails, VT3 will be switched over to automatically by the software.
For zero sequence voltage, there are no two independent windings adopted by two sets of
protection equipments simultaneously in general.
Circuit breaker failure initiation is very important to a power plant. In general, generator protection
tripping contact is an essential condition to circuit breaker failure initiation. Considering importance
of such protection, it is recommended to realize it as follows:
In order to make it more reliable, circuit breaker failure initiation function can‘t be integrated into
1.2 Functions
1.3 Features
1.3.1 High performance hardware
The hardware of any one CPU system comprises a 32 bit microprocessor and two digital signal
processors (DSP). The two CPU systems can operate in parallel acompanied by a fast A/D
converter. The 32-bit microprocessor performs logic calculations and the DSPs perform the
protection calculation. A high performance hardware ensures real time calculation of all protection
relays within a sampling interval.
On the premise of 24 samples per cycle, all data measurement, calculation and logic
discrimination could be done within one sampling period. The event recording and protection logic
calculation are completed simultaneously.
There is a set of independent fault detectors in the CPU processor in the RCS-985G relay. Its
operation supervises the tripping outputs. They will connect power supply to output relays when in
operation. There are different fault detectors in the CPU module used for various protective
functions. The relay can drive a tripping output only when the fault detectors in the CPU module
and the fault detectors in the MON module operate simultaneously. This kind of independent
supervision of tripping outputs using fault detectors can avoid any maloperation possibly caused
by any hardware component failures. This highly increases the security to a very high level.
Main and backup protection are integrated in one set of protection equipment. Protection
information such as sampled data and binary inputs are shared by all protective elements and no
more than one CT or VT at the same side of the transformer needs to be input into the equipment
for different protective elements. Shunt connection of VT and serial connection of CT that is
usually seen in secondary circuits before can be avoided. This greatly reduces the possibility of
circuit failure.
The equipment can gather all information of any fault and record all relevant waveforms of it for
offline analysis.
Elaborately designed tripping matrix makes it possible for the operation circuit to be suitable for
various circuit breakers.
The percentage differential protection adopts variable slope restraint characteristics and the actual
unbalanced differential current effect can be simulated. In order to prevent unwanted operation of
differential protection due to CT saturation, countermeasures to discriminate CT saturation are
provided by means of waveform identification of phase current at each side.
DPFC percentage differential protection reflects only deviation components of differential current
and restraint current and is not affected by load current. It can detect slight fault within generator.
Besides this, it is insensitive to CT saturation since its restraint coefficient is set comparatively
higher than that of conventional differential protection.
Current from CTs of each side under different ratios are corrected to a single standard before
calculation.
Two discrimination principles for inrush current are provided: harmonics restraint and waveform
distortion restraint.
Based on the operation sequence of DPFC restraint current element and the DPFC differential
current element of differential protection, external fault with CT saturation and internal fault can be
distinguished correctly.
In case of internal fault, the relay will operate immediately, while in case of external fault with CT
saturation, the criterion of current waveform is adopted. The relay will not operate in case of a
persisting external fault with CT saturation which occur no less than 5ms after the fault detectors
pickup. The relay will operate quickly though when an evolving external to internal fault occurs.
Transverse differential protection adopts a percentage phase current restraint and floating
threshold to get high sensitivity in internal fault and high security in external fault.
In addition, by adopting a frequency tracking technique, digital filter technique and Fourier
transformation technique, the filtration ratio of third component can reach more than 100. These
countermeasure guarantees the reliability of the protection in all occasions as mentioned below:
(1)The transverse differential protection can get reliable restraint effect as the faulty phase
current increases greatly while transverse differential current increases less in external fault
situation.
(2)The protection has very high operation sensitivity because the transverse differential current
increases exponentially in comparison to phase current change whose increase is minimal in
slight interturn fault situation.
(3)The insensitive stage of transverse differential current protection will operate quickly and
reliably when severe interturn fault occurs in stator winding.
(4)In case of phase-to-phase fault of stator winding, not only does the transverse differential
current increase greatly, but so also the phase current. Therefore just low percentage restraint by
phase current guarantees the reliable operation of transverse differential protection against the
fault.
(5)As for other increment of transverse differential unbalanced current in normal operation
condition, transverse differential current protection uses float threshold technique to avoid
unwanted operation.
By adopting frequency tracking technique, digital filter technique and Fourier transformation
technique, the filtration ratio of the third harmonic component can reach more than 100.
(1)Fault current increases greatly while longitudinal residual voltage increase less in external
three-phase fault, therefore the protection tends to be reliably restrained thanks to current
increment as restraint quantity.
(2)If external asymmetric fault occurs, phase current increases greatly with negative sequence
current, but the longitudinal residual voltage has very little increment, therefore the protection
tends to be reliably restrained by the mixing the quantity of current increment and the
negative-sequence component.
(3)The protection has very high operation sensitivity as the longitudinal residual voltage increase
is comparatively large whereas the phase current hardly changes in the situation of slight interturn
fault.
(4)The high-setting stage of transverse differential current protection will operate quickly and
reliably when severe interturn fault occurs in stator winding.
(5)As for the other increment of unbalanced longitudinal residual voltage in normal operation
condition, the protection uses floating-threshold technique to avoid unwanted operation.
(1)By adopting frequency tracking techniques, digital filter techniques and Fourier transformation
techniques, the filtration ratio of third component can reach more than 100.
(2)The sensitive stage of foundational residual voltage protection operates and issues trip
command only if the dual criteria of residual voltages of generator terminal and neutral point are
satisfied at the same time.
(3)The ratio settings of third harmonic of generator terminal to that of neutral point used in third
harmonic ratio criteria, which will automatically suit to the change of ratio of third harmonic voltage
of the plant unit fore-and-aft incorporated in the power network. This automation adjustment
function ensures the correctness of signals generated and issued by the third harmonic voltage
criteria even during incorporation or during isolation course of generator.
(4) The ratio and phase-angle difference of third harmonic voltage of generator terminal to that of
neutral point which is kept almost stable when the generator is in normal operation condition; also
it is a slow developing course. Through real time adjustment of coefficient of amplitude value and
phase, RCS-985 makes differential voltage between generator terminal and neutral point as 0 in
normal operation condition. When stator earth fault occurs, the criteria tend to operate reliably and
sensitively.
If one point earth fault protection only issues alarm signals instead of tripping after operation, then
the two-points earth fault protection will be automatically put into service with a certain fixed delay
and will operate to trip when two-point earth fault of rotor occurs.
Loss-of-excitation protection adopts optimizing protection scheme in which the stator impedance
criteria, reactive power criteria, rotor voltage criteria, busbar voltage criteria and criteria of stator
active power decrement,could be optionally combined to meet various demands of operation of
the unit for different generators.
Two groups of VT inputs are equipped at generator terminal. If one group fails, the equipment will
issue an alarm and switch over to the healthy one automatically. It does not need to block any
protective elements relevant to voltage.
This function adopts percentage differential principle. Detection ability of CT circuit failure can be
enhanced significantly and unwanted operations can be avoided.
1.3.3 Intellectuality
The HMI interface with a LCD and a 9-button keypad on the front panel is very user friendly. Real
time data, connection diagram, phase current, differential current and voltage can be displayed on
LCD during normal condition.
1.3.3.2 Transparency
More than 500 sampled data including differential current and phase angle etc. can be displayed
on LCD and more than 1500 internal data of the equipment can be supervised through dedicated
auxiliary software RCSPC that provides the user with a greater convenience to know about the
operational situation of RCS-985.
CPU module: the latest 32 groups of fault data and event sequence, 8 groups of fault oscillograms,
32 status changes of binary inputs and 32 self-supervision reports can be recorded.
MON module: when the equipment picks up, oscillograms of all analog sampling quantity,
differential current and operation of the protection equipment can be recorded with duration of up
to 4 seconds or 8 seconds (depending on the sample rate configured).
The format of event or fault report is compatible with the international COMTRADE format.
Two rear RS-485 ports with IEC 60870-5-103 protocol or MODBUS protocol which can be
re-configured as optical fiber ports.
Various GPS clock synchronizations: second/minute pulse via binary input or RS-485, message
via communication ports and IRIG-B synchronization.
Operating <70W
condition
Rear interface for local HMI with personal computer via RCSPC software
RS-232 (EIA) Port number 1
Application Local human-machine communication
Download program of protection relay
Baud rate 4800 ~ 9600bps
Connector type 9 pin D-type female connector
Safety level Isolation to ELV level
Interfaces for communicating with a printer
RS-232 (EIA) Port number 1
Baud rate 4800 ~ 38400bps
Printer type EPSON® LQ-300K
Safety level Isolation to ELV level
Frequency sweep
-Radiated amplitude-modulated 10V/m(rms), f=80…1000MHz
Spot frequency
-Radiated amplitude-modulated 10Vm(rms), f=80MHz/160MHz
/450MHz/900MHz
- Radiated pulse-modulated 10Vm(rms), f=900MHz
Fast transient disturbance tests IEC60255-22-4:2002 (idt IEC 61000-4-4)
- Power supply, I/O & Earth terminals Class IV, 4kV, 2.5kHz, 5/50ns
- Communication terminals Class IV, 2kV, 5.0kHz, 5/50ns
Surge immunity tests IEC60255-22-5:2002 (idt IEC
61000-4-5:1995) , Class III
- Power supply, AC inputs, I/O terminals 1.2/50us,
2kV, line to earth;
1kV, line to line
Conducted RF electromagnetic disturbance IEC60255-22-6, Class III
- Power supply, AC, I/O, Comm. terminal 10V(rms), 150kHz~80MHz
Power frequency magnetic field immunity IEC61000-4-8:1993, Class V
100A/m for 1min
1000A/m for 3s
Pulse magnetic field immunity IEC61000-4-9:1993, Class V
6.4/16 us
1000A/m for 3s
Damped oscillatory magnetic field immunity IEC61000-4-10:1993, Class V
100kHz & 1MHz – 100A/m
2.6 Certifications
ISO9001: 2000
ISO14001:2004
OHSAS18001: 1999
ISO10012:2003
CMMI L4
Current: 0.05In~20In
Voltage: 0.4V~100V
frequency: 45Hz~55Hz
df/dt: 0.3Hz/s~10Hz/s
Scope: 2 Ie – 14 Ie
≤25 ms (Id≥2×[I_Pkp_PcntDiff_Gen])
≤20 ms (Id≥1.5×[I_InstDiff_Gen])
Note:
Id—differential current
Scope: 2 Ie – 14 Ie
≤25 ms (Id≥2×[I_Pkp_PcntSPTDiff_Gen])
≤20 ms (Id≥1.5×[I_InstSPTDiff_Gen])
Note:
Id—differential current
Scope: 0 s – 10 s
Scope: 1 V – 10 V
Scope: 1 V – 20 V
Scope: 0 s – 10 s
Scope: ≤40 ms
Scope: 0.1 V – 50 V
Scope: 0.1 V – 50 V
Scope: 0.5 – 10
Scope: 0 s – 10 s
Scope: 0s – 10s
0.1 A – 20 A
0.05 A – 5 A
0.05 A – 5 A
Note:
0.5% - 10% Pn
0.01s – 10s
0 s – 100 s
0.0 s – 10 s
Measurements
Voltage: 0.05…2Vn
Performance
Every protective element has its own fault detector element in CPU and DSP respectively. When
the fault detector in CPU picks up, power supply of output relays will be connected. When both the
detector elements and operational element pick up, the protection element will operate to trip.
+24V QDJ
controlled by fault
detectors in MON +24V
module
trip
relay R
trip
contact
tripping G1
1
commands >=1 1
tripping
from CPU 1 transistor
module "or" gate
QDJ contact is controlled by general fault detectors calculated independently in MON module.
When the contact closes, the DC power supply source of tripping relay is provided. The function of
gate G1 is to receive the tripping commands issued by the CPU module. When a tripping
command arrives at the gate G1, the driving transistor will be activated, and the trip relay‘s contact
will close to trip the breaker.
The general fault detectors calculated in MON module and operation elements calculated in CPU
module use their own independent data samples. This ensures that the equipment will not operate
by mistake due to any of module‘s data channel‘s failure.
I d max [I_Pkp_PcntDiff_Gen ]
(Equation 3.2-1)
Where:
I d 1.25I dt I dth
I d I 1 I 2 ... I m (Equation 3.2-2)
Where:
I dt
is the floating threshold value which will arise automatically and gradually according to the
increasing of the output of the deviation component. In order to ensure that the threshold value of
the voltage is slightly higher than the unbalance output, the deviation component gets multified by
1.25 which is reasonable.
I 1 …. I m are the DPFC current of each side of generator respectively.
I d
is the half-cycle integral value of differential current.
I dth
is the fixed threshold.
This fault detector is not influenced by the direction of power flow and so it is very sensitive. The
setting is already fixed and need not to be set on site. It is used to enable DPFC percentage
differential protection of generator.
The fault detector will operate when the transverse differential current is greater than the setting
[I_SensTrvDiff_Gen].
The fault detector will operate when the longitudinal zero sequence voltage is greater than the
setting [V_SensROV_Longl_Gen].
The fault detector will operate when the calculated directional element meets operating condition.
The fault detector will operate when the calculated zero sequence voltage is in excess of the
setting [V_SensROV_Sta].
The fault detector will operate when the ratio of 3rd harmonics voltage of neutral point to 3rd
harmonics voltage at the terminal is greater than its ratio setting [k_V3rdHRatio_PreSync_Sta] or
[k_V3rdHRatio_PostSync_Sta].
The fault detector will operate when the differential 3rd harmonic voltage of neutral point and 3rd
harmonics voltage at the terminal of generator is greater than its setting [k_V3rdHDiff_Sta].
3.2.4.4 Fault detector of stator earth fault protection with injection principle
The fault detector will operate when the calculated grounded resistor is less than the resistor
setting [R_Trp_Inj_EF_Sta].
The fault detector operates when grounded resistance of rotor is less than its setting.
The fault detector operates when change of rotor grounding location is greater than its setting.
The fault detector operates when the maximum value of three-phase current is greater than its
setting [I_OvLd_Sta].
The fault detector operates when any of three phase currents is greater than its setting
[I_InvOvLd_Sta].
The fault detector operates when negative sequence current is greater than its setting.
The fault detector operates when negative sequence current is greater than its setting.
The fault detector operates when measured U/F is greater than definite time setting.
The fault detector operates when over excitation value is greater than inverse time pickup setting.
The fault detector operates when frequency is lower than its setting for a specified period.
The fault detector operates when frequency is greater than its setting for a specified period.
The fault detector operates when maximum phase current of generator is greater than setting of
unwanted closing protection.
The fault detector operates when negative sequence current of generator is greater than setting of
circuit breaker flashover protection.
The fault detector operates when the maximum value of three phase differential current is greater
than its setting.
The fault detector operates when the maximum value of three phase current is greater than its
setting.
The fault detector operates when maximum value of three phase current of rotor winding is greater
than its definite time setting.
The fault detector operates when inverse time accumulated value is greater than inverse time
setting.
Note:
In the following logic diagrams, all logic inputs starting with ―En_**‖ represent enabling logic
settings which will be explained in Chapter7. All logic inputs starting with ―EBI_**‖ represent
enabling binary inputs from panel, those starting with ―Flg_**‖ represent internally generated flags
indicating whether or not a certain element is met, those words begin with ―Alm_‖ and ―Op_‖
represent output for alarming and operation of protective elements respectively.
unrestraint operation
Id
area
Icdsd
operation Kbl2
area
restraint
area
Kbl1
Icdqd
0
Ie nIe Ir
I d K bl I r I cdqd ( I r nIe )
K bl K bl1 K blr ( I r / I e )
I d K bl 2 ( I r nIe ) b I cdqd ( I r nIe )
K blr ( K bl 2 K bl1 ) /( 2 n)
b ( K bl1 K blr n) nIe
(Equation 3.3-1)
I 1 I2
Ir
2
I d I 1 I 2
Where:
I d is differential current,
I r is restraint current,
For differential protection of generator and exciter, I 1 and I 2 are currents of terminal and neutral
point respectively.
K bl1 is the initial slope [Slope1_PcntDiff_Gen] of percentage differential with setting range 0.05 –
K bl2 is the maximum slope [Slope2_PcntDiff_Gen] of percentage differential with setting range
n is the multiple of restraint current at maximum percentage restraint coefficient and is fixed at 4.
In order to prevent unwanted operation of steady state percentage differential protection due to CT
transient or steady state saturation during external fault, the discrimination of waveform of
differential current principle is adopted as criterion of CT saturation.
When fault occurs, the equipment decides first whether it is an internal or an external fault. If it is
external fault, criterion of CT saturation is enabled. If any differential current of differential
protection meets the criterion, the differential current will be recognised due to CT saturation and
the percentage differential protection will be blocked.
A percentage differential protection with high percentage and high setting is equipped with the
equipment to prevent operation of percentage differential protection from being delayed by CT
saturation and other factors during serious internal faults. It can prevent influence of steady state
and transient CT saturation during external fault due to its percentage restraint characteristic and
can operate correctly and quickly during internal fault and when CT is saturated. Operation
criterion of this high setting percentage differential protection is
I d 1.2 I e
I d 1.0 I r (Equation 3.3-2)
Where differential current Id and restraint current Ir are the same as mentioned in section 3.3.1.1.
When fault occurs, the operation criterion will be discriminated phase by phase and percentage
differential protection will operate if the criterion is met.
Parameters of this protection are configured during manufacturing and not need to be configured
on site.
This protection will operate and trip immediately if differential current of any phase is greater than
its setting.
Abnormal differential current alarm function with percentage restraint characteristic and blocking
functions in case of miniature CT open circuit or short circuit are equipped with the equipment. See
section 3.3.25.
Id.max>[I_InstDiff_Gen]
[EBI_Diff_Gen]
&
& Op_InstDiff_Gen
[En_Diff_Gen]
[En_InstDiff_Gen]
[FD_Diff_Gen]
[Op_InsensDiff_Gen]
[EBI_Diff_Gen]
& & &
[En_Diff_Gen]
[En_PcntDiff_Gen]
[Flg_InstanCTS]
Op_PcntDiff_Gen
≥1
[FD_Diff_Gen]
[Flg_Sat_CT]
[Op_PcntDiff_Gen]
[EBI_Diff_Gen]
& &
&
[En_Diff_Gen]
[En_PcntDiff_Gen]
[Flg_InstanCTS]
[FD_Diff_Gen]
Where:
[EBI_Diff_Gen] is the position flag of binary input for enabling all kinds of differential protection of
generator.
[FD_Diff_Gen] is the internally generated flag indicating that fault detector of differential protection
picks up.
[Op_InsensDiff_Gen] is the internally generated flag indicating that equation 3-4 is met.
[Flg_IntanCTS] is the internally generated flag indicating that CT supervision program detects
failure of CT circuit with no delay considered into account.
Where:
2
I r is the restraint current, I r I i , for RCS-985G, the number 1,2 represents terminal
i 1
2
I d is the DPFC differential current, I d I
i 1
i
I dt is the floating threshold value which will arise automatically and gradually according to the
increment of deviation component. In order to ensure that the threshold value is slightly higher
than the unbalance output, multiple 1.25 of the deviation component is reasonable and the
unwanted operation of relays will not occur during power swing or power frequency deviation.
I 1 … I m are DPFC phase currents on each side of generator.
Note:
Calculation of restraint current of DPFC percentage differential protection is different from the
steady state percentage differential protection, it is difficult to test this function on site, so we
recommend only qualitative function test on site.
DPFC differential protection is equipped to each phase of generator, but user should know that the
restraining DPFC quantity for every phase is the same maximum value among the three phases.
The following figure shows operating characteristic of DPFC percentage differential protection.
0.6
0.2 Ie
restraint current
2 Ie
The criteria are checked phase by phase. If the criterion mentioned above is met, the DPFC
percentage differential protection will operate. Tripping command will be issued under control of
inrush current and overexcitation discrimination.
This protective element has high ability to eliminate the effects of transient and steady saturation
of CT during the external fault because the restraint coefficient is set at a higher value.
[Flg_DPFC_Diff_Gen]
0 20
& &
[EBI_Diff_Gen] Extend &
20ms
[En_Diff_Gen] Op_DPFC_Diff_Gen
[En_DPFC_Diff_Gen]
[Flg_InstanCTS] 1
0 500
[FD_Diff_Gen]
Extend 500ms
In the figure:
[EBI_Diff_Gen] is the position flag of binary input for enabling all kinds of differential protection of
generator.
[Flg_IntanCTS] is the internally generated flag indicating that CT supervision program detects
Settings of DPFC percentage differential protection is are fixed and need not to be set on site.
Transverse differential protection installed on connection between two neutral points of the
generator is used as the main protection for short circuit interturn fault of generator‘s stator
winding, open circuit fault of branches and short circuit fault between phases.
Since this protection adopts frequency tracking technique, digital filtering and full cycle Fourier
algorithm, the third harmonic can be reduced to 1/100 within the frequency tracking range and the
protection can respond to the fundamental component only.
This protection comprises two stages: insensitive stage (high setting stage) and sensitive stage.
This stage is equivalent to traditional transverse differential protection. When the transverse
differential current is in excess of the setting [I_InsensTrvDiff_Gen], the protective element
operates.
Phase current percentage restraint principle is used for this stage. The operation criterion is
Where:
I hcZD
is the transverse differential current setting [I_SensTrvDiff_Gen],
Phase current percentage restraint transverse differential principle can ensure no unwanted
operation during external fault and sensitivity during internal fault. As this principle is adopted,
current setting of the transverse differential protection shall be only higher than unbalance current
during normal operation and much less than that of traditional transverse differential current
This protection also has a floating threshold for high transverse differential unbalance current
during other normal operating conditions.
Operation of the high sensitive transverse differential protection will lead to a tripping immediately.
When the rotor of a generator is grounded at one point, a configurable time delay [t_TrvDiff_Gen]
will be inserted in the tripping course.
[Alm_1PEF_RotWdg]
[En_1PEF_RotWdg] & t
&
[En_Alm_1PEF_RotWdg]
[Flg_TransDiff_Gen]
=1
&
Op_SensTrvDiff_Gen
[En_IntTurn_Gen] &
&
[En_Sens_TransDiff_Gen]
[EBI_IntTurn_Gen]
[FD_Diff_Gen]
Where:
[Alm_1PEF_RotWdg] is internally generated flag indicating the one-point earth fault protection of
rotor operates.
[EBI_1PEF_RotWdg] is enabling binary input for one-point earth fault protection of rotor. ―1‖
means enabled.
Longitudinal zero sequence voltage protection is configured for inter-turn fault of stator winding of
generator. It uses open-delta voltage of dedicated VT at the terminal of generator as the criterion.
Since this protection adopts frequency tracking technique, digital filtering and full cycle Fourier
algorithm, the third harmonic can be reduced to less than 1/100 within the frequency tracking
range and the protection can respond to the basic wave component only.
This protection comprises two stages: insensitive stage (high setting stage) and sensitive stage.
Setting of this stage shall be higher than the maximum unbalanced voltage during external fault,
during this time the directional flag indicating internal fault must be satisfied. When measured
longitudinal zero sequence voltage is in excess of the setting [V_InsensROV_Longl_Gen] and
lasts for longer than the delay setting [t_ROV_Longl_Gen], this protective element will trip
breakers according to the configuration of [TrpLog_IntTurn_Gen].
Phase current percentage restraint principle is used for this stage. The operation criterion is
U zo [ 1 K zo I m / I e ] U zozd
I m 3 I 2 when I MAX I e (Equation 3.3-5)
I m (I MAX - I e ) 3 I 2 when I MAX I e
Where:
U zozd
is the zero sequence voltage setting [V_SensROV_Longl_Gen],
K z0
is the restraint coefficient.
Like transverse differential principle, this protective element can ensure no unwanted operation
during external fault and sensitive operation during internal fault. As for the percentage restraint
characteristic, zero sequence voltage setting of the zero sequence voltage protection shall be only
higher than the unbalanced voltage during normal operation. Sensitivity for interturn fault of
generator can be enhanced then.
This protective element also has a floating threshold for high unbalanced longitudinal zero
sequence voltage during other operational conditions.
Longitudinal zero sequence voltage protection for inter-turn fault of stator shall be blocked when
the dedicated VT2 circuit at the terminal of generator fails. There are two criteria to decide on
whether not block or block the protection.
In the above three criterion, if one of the former two and the third are met simultaneously, the
longitudinal zero sequence voltage protection will be blocked.
U AB - U ab 5V
U BC - U bc 5V
(1) U - U 5V (Equation 3.3-6)
CA ca
U BC U CA U ab U bc U ca
Where: U AB , , are phase-to-phase voltages of VT1 and , , are
phase-to-phase voltages of VT2.
That one of these three sub-criteria in (1) and (2) is met will result in pickup of criterion 2.
When any of criterion 1 and criterion 2 operates, alarm of VT2 circuit failure will be issued after a
delay of 40 ms and zero sequence voltage protection will be blocked.
After the VT circuit failure reverts to normal condition, blocking can be released by pressing the
Target-reset button on the faceplate of the protection.
[Flg_NegDir_Gen]
[Flg_InsensROV_Longi_Sta] &
[En_InsensROV_Longl_Gen]
[EBI_IntTurn_Sta]
[FD_Diff_Gen]
[Flg_SensROV_Longi_Sta]
&
[Flg_VTS] & & t
Op_SensROV_Sta
[En_IntTurn_Gen]
[En_SensROV_Longl_Gen]
[EBI_IntTurn_Sta]
[FD_Diff_Gen]
Where:
F =Re[ U 2 I 2 e j ] 1.25 dF
(a)
U 2 0.5V 1.25du
(b) (Equation 3.3-7)
If the three criterions are met simultaneously, the directional flag of protection is set. Under
negative sequence voltage and negative sequence current controlling, the protection operates
after 0.2-0.5s time delay.
AC current and voltage input used in directional DPFC protection are from the generator terminal
directly. When the VT1 at the generator terminal fails, the directional DPFC protection is blocked.
The sensitivity is about 3V of longitudinal zero sequence voltage.
Directional DPFC protection for inter-turn fault cannot responsd to inter-turn fault before the
generator is connected into the power grid.
The Two stage impedance protection is equipped at the terminal of the generator as its
phase-to-phase backup protection. Phase-to-phase current used in impedance relay is derived
from CT at the neutral point of generator. Circular impedance, directional circular impedance or
drifted circular impedance characteristic can be selected to act for these two stages. Circular
characteristic suits case of forward setting of a zone being equal to its reverse setting. Directional
circular characteristic suits case of reverse setting of a zone being set as 0. Drifted circular
characteristic suits case of forward setting of a zone which is greater than its reverse setting.
Reach angle of impedance protection is 78°. Positive direction of the impedance protection is
configurable and generally points to generator.
Operation criterion:
(U I Z P )
90 Arg
270
(U I Z n ) (Equation 3.3-8)
DPFC of phase-to-phase current and negative current element are adopted as fault detector of
impedance protection. Initiation of the fault detector will be extended to 500 ms and will be kept if
impedance relay operates during this time interval. Operation criterion of the fault detector is
I 1.25I t I th
(Equation 3.3-9)
Where:
I t is floating threshold which increases gradually along with DPFC increment. Take its multiple
as 1.25 can ensure threshold voltage always a bit higher than unbalance voltage.
jX
I Zp
U I Zp
m
U
R
U I Zn
I Zn
Therefore unwanted operation of the equipment can be avoided during system swing and
frequency deviation conditions. I th is the fixed threshold. When DPFC of phase-to-phase current
The protection adopts two sets of VT at the terminal of generator. If one set of VT circuit fails,
another set of VT can be switched over automatically on the premise of the funciton of voltage
balance is enabled.
[Flg_VTS]
&
[Flg_Zn_Gen]
& [Op_Zn_Gen]
& t
[En_PPF_Gen]
[EBI_PPF_Gen]
[FD_PPF_Gen]
Where:
[EBI_PPF_Gen] is the position flag of binary input for enabling phase-to-phase backup protection
of generator which including phase-to-phase distance protection and voltage-controlling
overcurret protection. ―1‖ means enabled.
This protection is used as a backup protection of generator, main transformer, HV busbar and
neighboring power lines. There are two stages with their own delay settings respectively. Stage 1
is used to trip bus couple breaker or other circuit breaker and stage 2 to shut down the generator.
Figure 3.3-9 shows its logic diagram.
For generators with self shunt excitation, current will decrease so quickly during fault that it may be
lower than overcurrent setting before tripping. So function to remember fault current is equipped
with this protection. Logic setting [Opt_ExcMode_Gen] is used for configuration of this function.
See details about the setting in section 7.3.4.
the overcurrent protection will not be blocked and becomes a pure overcurrent protection.
Upp<[Vpp_VCE_Gen]
=1
&
U2>[V_NegOV_VCE_Gen]
=1 Op_VCE_Gen
[Flg_VTS]
[Opt_VTS_Ctrl_OC_Gen] &
[Opt_ExcMode_Gen] &
[Flg_OCn_Gen] =1
&
[Op_VCE_Gen]
& t Op_OCn_Gen
=1
[En_VCE_Ctrl_OCn_Gen]
[En_PPF_Gen]
&
[EBI_PPF_Gen]
[FD_PPF_Gen]
Figure 3.3-9 Logic diagram of overcurrent relay with composite voltage blocking
Where:
Single-phase earth fault within 85% - 95% range from terminal of stator winding can be protected
by fundamental zero-sequence overvoltage protection.
This protection comprises two stages: sensitive stage and insensitive stage (high setting stage).
U n0 U0zd
(Equation 3.3-10)
Where:
U 0zd K rel U unb.max , U 0zd is operation threshold setting of fundamental zero sequence voltage
[V_SensROV_Sta].
To assure its security, this device is designed to use the open-delta voltage obtained from the VT
at the generator terminal.
The voltage is a blocking element for a sensitive stage of this function. If the voltage is in excess of
the automatically-set setting according to the VT ratio of both at terminal and at the neutral point
set by user in system parameter item, the function will be blocked.
U n0 U0hzd
(Equation 3.3-11)
Where:
[ U 0hzd ] is the zero sequence voltage high setting. 20V ~ 25V is recommended generally.
This protection is designed to cover only about 25% of earth fault of the stator. Third harmonic
voltage of generator terminal is got from its open-delta zero sequence voltage. Third harmonic
voltage of neutral point side is got from neutral point VT of the generator.
U 3T / U 3N K3wzd
(Equation 3.3-12)
Where:
U 3T and U 3N are third harmonic voltage of generator terminal and neutral point respectively.
[k_3rdHRatio_PostSync_Sta].
owing to variation of equivalent capacitive reactance at the generator terminal. So two different
settings are designed for protection before and after the connection of generator with system.
These two settings can be switched over with alternation of contacts‘ position of the terminal
breaker.
In addition, the settings are provided for deciding whether the ratio protection of third harmonics
voltage is used for alarming or tripping or both.
U 3T K t U 3 N Kre U 3 N
(Equation 3.3-13)
Where:
U 3T and U 3 N are third harmonic vector voltage of generator terminal and neutral point,
This protection is enabled automatically when the generator has been connected with the system
and load current is greater than 0.2 Ie (generator rated current). It only issues alarms if it is
operating.
(1) Open-delta VT circuit failure alarm of terminal and neutral point of generator
Since open-delta voltages of VT at neutral point and generator terminal are taken for zero
sequence voltage protection of stator, failure of these VT circuits will make this protection fail to
operate and an alarm shall be issued in this case. The third harmonic voltage ratio criterion and
third harmonic voltage differential criterion shall be disabled during VT circuit failure at the
generator neutral point.
Positive sequence voltage of secondary winding of the generator terminal is greater than 0.9Un
and the third harmonic of zero sequence voltage is lower than 0.1V.
VT circuit failure alarm will be issued after a delay of 10s and reverted automatically after delay of
10s when the failure vanishes.
Secondary circuit failure of VT1 at generator terminal will not influence earth fault protection of
stator. Primary circuit failure of VT1 at generator terminal will cause fundamental component of
zero sequence voltage increase and third harmonic component decrease, and so will not lead to
unwanted operation of fundamental zero sequence voltage protection and third harmonic voltage
ratio protection. However, it will cause unwanted operation of third harmonic voltage differential
protection, so this protection shall be blocked during this failure. Operation criterion of this failure
is:
When these criterion are met, VT1 primary circuit failure alarm will be sent with short delay and
third harmonic voltage differential protection will be blocked.
Figure 3.3-10 shows logic diagram of fundamental zero sequence voltage earth fault protection
and Figure 3.3-11 shows logic diagram of third harmonic voltage earth fault protection
respectively.
[En_Alm_ROV_Sta]
[Flg_VTS]
& t Alm_ROV_Sta
[Flg_SensROV_Sta] &
[En_EF_Sta]
& t
[En_Trp_ROV_Sta] & Op_SensROV_Sta
[EBI_ROV_Sta]
[FD_EF_Sta]
Figure 3.3-10 Logic diagram of fundamental zero sequence overvoltage earth fault protection of
stator
Where:
[EBI_ROV_Sta] is binary input of enabling fundamental zero sequence overvoltage and zero
sequence overcurrent earth fault protection of stator.
[En_Alm_V3rdHRatio_Sta]
[Flg_VTS]
& t Alm_V3rdHRatio_Sta
&
[Flg_V3rdHRatio_Sta]
[En_EF_Sta]
[En_Trp_V3rdHRatio_Sta] & t
& Op_V3rdHRatio_Sta
[EBI_V3rdH_Sta]
[FD_EF_Sta]
[En_Alm_V3rdHDiff_Sta]
[Flg_VTS]
& t Alm_V3rdHDiff_Sta
&
[Flg_V3rdHDiff_Sta]
[En_EF_Sta]
[En_Trp_V3rdHDiff_Sta] & t
& Op_V3rdHDiff_Sta
[EBI_V3rdH_Sta]
[FD_EF_Sta]
Where:
If one-point earth fault of rotor occurs, insulation resistance between rotor winding and the axis will
drop down.
Rotor earth fault protection measures earthing resistance Rg of the winding by an unbalance
bridge as shown in Figure 3.3-12. Corresponding equations can be got by switching over S1 and
S2 alternately, and earthing resistance Rg and location of the earthing point ― ― can be found by
calculation.
There are two stages equipped for one-point earth protection: sensitive stage and regular stage.
Sensitive stage is used for alarm and regular stage for tripping or alarm.
U
+ aU -
rotor
R Rg R
R S1 S2 R
If one-point earth protection is used for alarm only, when earth resistance Rg is less than the
setting of its regular stage, it will switch over to two-point ground protection program with a delay
automatically. If the location of the earthing point varies and the variation reaches its setting value
(fixed value 3%), two-point ground protection will trip.
Figure 3.3-13 and Figure 3.3-14 show logic diagram of one-point and two-point earth fault
protection of rotor.
Rg < [R_Sens_1PEF_RotWdg]
t Alm_Sens_1PEF_RotWdg
&
[En_Alm_Sens_1PEF_RotWdg]
[En_Alm_1PEF_RotWdg]
Alm_1PEF_RotWdg
& t
Rg <[R_1PEF_RotWdg]
&
[t_1PEF_RotWdg]
[En_EF_RotWdg]
[En_Trp_1PEF_RotWdg] &
& t Op_1PEF_RotWdg
[EBI_1PEF_RotWdg] [t_1PEF_RotWdg]
[FD_EF_RotWdg]
t
[Op_1PEF_RotWdg]
[Flg_2PEF_RotWdg] &
[En_EF_RotWdg]
[Flg_V2ndH_VCE_2PEF_RotWdg] t Op_2PEF_RotWdg
&
=1
[En_VCE_2PEF_RotWdg]
[En_2PEF_RotWdg]
[EBI_EF_RotWdg]
[FD_EF_RotWdg]
Where:
Flg_2PEF_RotWdg: is internally generated flag indicating two-point earth element operates
There are two stages equipped with definite time stator overload protection: one for alarm and the
other for tripping. Figure 3.3-16 shows its logic diagram.
Inverse time stator overload protection consists of three parts: low setting initiator, inverse time
part and upper limit definite time part.
Inverse time part can simulates generator-heating process including heat accumulation and
dissipation. When stator current reaches its low setting I SZD ([I_InvOvLd_Sta]), inverse time part
initiates and the heat is accumulated. When the stator current is lower than rated value, the heat
accumulation will decrease accordingly.
Figure 3.3-15 shows the inverse time curve. In the figure, t min is delay of upper limit of inverse
Iszd
t min t max
(Equation 3.3-14)
Where:
Figure 3.3-17 shows logic diagram of inverse time stator overload protection.
I>[I_OvLd_Sta]
& t Definite time stator
& overload protection trips
[En_OvLd_Sta]
[TrpLog_OvLd_Sta].bit0 &
[EBI_Ovld_Sta]
[FD_Ovld_Sta]
I > [I_InvOvLd_Sta]
& &
[TrpLog_InvOvLd_Sta].bit0 tmin
& Op_InvOvLd_Sta
[TrpLog_InvOvLd_Sta].bit0
&
[EBI_EF_Sta]
[FD_OvLd_Sta]
There are two stages equipped with definite time negative sequence overload protection: one for
alarm and the other for tripping. Figure 3.3-19 shows its logic diagram.
Inverse time negative sequence protection consists of three parts: low setting initiator, inverse
time part and upper limit definite time part.
Inverse time part can simulate generator-heating process including heat accumulation and
dissipation. When negative sequence current reaches its low setting [I_InvNegOC_Gen], inverse
time part initiates and the heat is accumulated. When the stator current is lower than permissive
continuous negative sequence current [I_Neg_Perm_Gen], the heat accumulation will decrease
accordingly.
[(I 2 / I ezd ) 2 (I 2 l ) 2 ] t A
(Equation 3.3-15)
Where:
Figure 3.3-18 shows the inverse time curve. In the figure, t min ([tmin_InvNegOC_Gen]) is delay of
upper limit of inverse time curve and I 2 SZD ([I_InvNegOC_Gen]) is setting of the inverse time
I2zd
t min t max
Figure 3.3-18 Operation curve of inverse time negative sequence overload protection of stator
[En_NegOC_Gen]
t Alm_NegOC_Gen
&
I2>[I_Alm_NegOC_Gen]
[t_Alm_NegOC_Gen]
I2>[I_NegOCn_Gen]
& & t Op_NegOCn_Gen
[En_NegOC_Gen] [t_NegOCn_Gen
]
[TrpLog_NegOCn_Gen].bit0
&
[EBI_NegOC_Gen]
[FD_PPF_Gen]
Figure 3.3-19 Logic diagram of definite time negative sequence overload protection
I >[I_InvNegOC_Gen]
& &
[En_NegOC_Gen] t min
& Op_InvNegOC_Gen
[TrpLog_InvNegOC_Gen].bit0
&
[EBI_NegOC_Sta]
[FD_PPF_Gen]
Figure 3.3-20 Logic diagram of inverse time negative sequence overload protection
Loss of excitation represents abnormal operation of generator due to excitation failure. There are
four criterions used for loss-of-excitation protection: under voltage, stator side impedance, rotor
side undervoltage/excitation voltage and power output reduction.
Three phase voltages on bus generally and those at generator terminal sometimes are taken as
this criterion. Criterion of simultaneous three phases under voltage is
U pp U lezd
(Equation 3.3-16)
Where:
The protection will be blocked, when bus voltage is taken as the criterion and the bus VT circuit
fails. When the generator terminal voltage is taken as the criterion, if one group of VT circuit fails,
the other group of VT will be switched over to automatically.
This criterion is impedance circle including asynchronous impedance circle and steady state
stabilization limit circle. The operation criterion is
Z jX B
270 Arg 90
Z jX A (Equation 3.3-17)
Where:
X A can be set as the system impedance Xs for steady state stabilization limit circle and
X B is taken as Xd 1/2X ' for round rotor generator and (X X )/2 X ' /2 for salient pole
d d q d
generator.
The impedance criterion can be combined with reverse reactive power criterion, i.e.,
Q [Q_RevQ_LossExc_Gen].
Figure 3.3-21 (a) and (b) show operation characteristics of steady state stabilization impedance
relay and asynchronous impedance relay, where the hatched area is operating area, and the
dotted line is operation limit of reverse reactive power.
jx jx
Z1
R Z1
R
-Qzd -Qzd
Z2 Z2
a) b)
(a) (b)
Besides operation criterion mentioned above, there are also auxiliary operation criterions, namely:
Negative sequence voltage U2 is lower than 0.1 Un (rated voltage of generator); and
Where:
Ur is exciting voltage.
Xs is equivalent reactance on system side connected with the generator (per unit value);
U f0
is rated voltage of exciter during generator without load;
K r is reliability coefficient.
If Ur drops to zero or goes to minus value suddenly during loss of excitation, the rotor under
voltage criterion will be met quickly before steady state stability limit of the generator is reached. If
Ur drops to zero or reduces to a value gradually during loss of excitation, the variable excitation
voltage criterion will be reached. Excitation under voltage or loss of excitation will cause
out-of-step, and then excitation voltage and output power of the generator will swing seriously. In
this case, the rotor under voltage criterion and the variable excitation voltage criterion will be met
and withdrawn periodically in general. So the excitation voltage element will revert with delay
during out-of-step condition while the impedance entering the steady state stability limit circle.
When out-of-step occurs during loss of excitation, power output of generator will swing within a
certain range. P represents average power output within an oscillation period. Pzd is the setting
[P_LossExc_Gen].
Three stages are equipped with loss-of-excitation protection: stage 1 is used for reduction of
power output and alarm, stage 2 (with bus undervoltage criterion) is used for tripping, stage 3 is
used for tripping with long delay.
Figure 3.3-22 shows logic diagram of stage 1 of loss-of-excitation protection. If excitation is lost,
this stage will be used to reduce power output to a pre-set level and issue alarm.
[En_Alm_LossExc1_Gen]
Alm_LossExc_Gen
& t
P > [P_OvPwrLossExc_Gen]
&
≥1
[En_P_LossExc1_Gen]
Ur<[V_RotUV_LossExc_Gen] t Op_LossExc1_Gen
&
≥1
Ur Kr XdzSn Uf0 &
≥1
[En_RotUV_LossExc1_Gen]
Z jX B
270 Arg 90
Z jX A &
&
[En_Z_LossExc1_Gen] ≥1
&
Q>[Q_RevQ_LossExc_Gen]
[En_RevQ_LossExc_Gen]
[En_LossExc_Gen]
[EBI_LossExc_Gen]
[TrpLog_LossExc1_Gen].bit 0
[FD_LossExc&OOS_Gen]
Figure 3.3-23 shows logic diagram of stage 2 of loss of excitation protection. If excitation is lost
and voltage on HV side bus of main transformer is lower than its setting, this stage will trip with
delay. In configuring this stage with consideration to security, it is strongly recommended that
impedance criterion should be used as well as busbar criterion rather than the model where only
busbar undervoltage criterion and rotor undervoltage criterion are used.
Upp<[V_UV_LossExc_Gen
&
[En_UV_LossExc2_Gen] ≥1
Ur<[V_RotUV_LossExc_Gen]
≥1
&
Ur Kr Xdz Sn Uf0
≥1
t Op_LossExc2_Gen
&
[En_RotUV_LossExc2_Gen]
Z jX
270 Arg B
90 &
Z jX
&
A
≥1
[En_Z_LossExc2_Gen]
Q>[Q_RevQ_LossExc_Gen]
&
[En_RevQ_LossExc_Gen]
[En_LossExc_Gen]
[EBI_LossExc_Gen]
[TrpLog_LossExc2_Gen].bit 0
[FD_LossExc&OOS_Gen]
Figure 3.3-24 shows logic diagram of stage 3 of loss of excitation protection. It is used for
switching over backup excitation or for tripping. It is also used for tripping with long delay in case of
failure of all measures taken by the former stages, such as power output reduction and switching
over backup excitation and has no effects on the more and more worse system.
Ur<[V_RotUV_LossExc_Gen]
≥1
Ur Kr Xdz Sn Uf0 &
≥1
[En_RotUV_LossExc3_Gen]
Z jX
270 Arg B
90
Z jX A & &
[En_Z_LossExc3_Gen] t Op_LossExc3_Gen
≥1 &
Q>[Q_RevQ_LossExc_Gen]
&
[En_RevQ_LossExc_Gen]
[En_LossExc_Gen]
[EBI_LossExc_Gen]
[TrpLog_LossExc3_Gen].bit 0
[FD_LossExc&OOS_Gen]
shows operation characteristic of this protection that comprises three parts: lens part, boundary
part and reactance line part.
jx
Za
U
D
Zc
OL
IL 3
2
1 IR 1
OR
0
R
L R
Zb
In Figure 3.3-25, lens ① divides impedance plane into inside part I and outside part O, boundary
② divides the impedance plane into left part L and right part R, and reactance line ③ divides the
impedance plane into upper part U and lower part D.
Considering lens ① and boundary ② comprehensively, the impedance plane is divided into four
areas: OL, IL, IR and OR. If trace of impedance is passing through these four areas in sequence
from right to left or vice versa, and staying in each area for a moment longer than the setting, this
case is considered as system swing. Times of the passing through are accumulated and the grand
total is considered as the times of pole sliding. When the grand total reaches its setting value,
out-of-step protection operates.
As to reactance line ③, if the impedance trace passes through the upper part U, the swing center
is considered outside the generator; if the trace passes through the lower part D, the swing center
is considered within the generator. Settings of times of pole sliding can be configured separately
for these two cases.
Out-of-step protection can be used either for alarm only or tripping. Minimum swing period which
can be identified by this protection is 120 ms.
[En_Alm_Ext(Int)_OOS_Gen]
[Flg_Blk_OOS] t
&
[En_OOS_Gen]
[TrpLog_OOS_Gen].bit0 &
Op_Ext(Int)_OOS_Gen
& t
[EBI_OOS_Gen]
[FD_LossExc&OOS_Gen]
[TrpLog_OVn_Gen].bit0 t_OVn_Gen
[EBI_VoltProt_Gen]
[FD_Volt&OvExc_Gen]
tripping.
Upp>[V_OVn_Gen]
&
[En_VoltProt_Gen] &
& t Op_OVn_Gen
[TrpLog_OVn_Gen].bit0 t_OVn_Gen
[EBI_VoltProt_Gen]
[FD_Volt&OvExc_Gen]
[BI_SyncCondenser]
Upp.max<[V_UV_Gen] &
&
& t Op_UV_Gen
[En_VoltProt_Gen]
t_UV_Gen
[TrpLog_UV_Gen].bit0
[EBI_VoltProt_Gen]
[FD_Volt&OvExc_Gen]
Two stages for tripping and one stage for alarm are equipped for definite over excitation protection.
Their time delay can be configured.
n U pu / Fpu
(Equation 3.3-18)
U pu Fpu
Where and are per unit value of voltage and frequency respectively.
Figure 3.3-30 shows logic diagram of definite time over excitation protection.
Inverse time over excitation protection realizes inverse time characteristic by linear processing on
given inverse time operation characteristic, obtaining multiple of over excitation by calculation, and
getting corresponding operation delay by sectional linear insertion. It reflects heat accumulation
and radiation.
Figure 3.3-30 shows inverse time operation characteristics of over excitation protection. It can be
specified by 8 over excitation multiple settings n0 – n7.
U/F
n0
n1
n2
n3
n4
n5
n6
n7
t0 t1 t2 t3 t4 t5 t6 t(s) t7
The over excitation multiple settings n (= U/F) are within range of 1.0 – 1.5 in general. Maximum
time delay t is considered as long as 3000 s. Relation between various settings of n and t are:
n0 ≥ n1 ≥ n2 ≥ n3 ≥ n4 ≥ n5 ≥ n6 ≥ n7
t0 ≤ t1 ≤ t2 ≤ t3 ≤ t4 ≤ t5 ≤ t6 ≤ t7
[En_OvExc_Gen]
t Alm_OvExc_Gen
&
U/F > [k_Alm_OvExc_Gen] [t_Alm_OvExc_Gen]
[FD_Volt&OvExc_Gen]
[TrpLog_InvOvExc_Gen].bit0
&
[EBI_OvExc_Gen]
[FD_Volt&OvExc_Gen]
Reverse power protection can prevent turbine blades or gears from damage in the case when
the generator transforms into a motor mode and flows reverse power due to loss of its motive
force.
power calculated from three phase voltage and current and [P_RevP_Gen] is the reverse power
setting.
One stage for tripping and the other stage for alarm with independent delay setting respectively
are equipped with this protection.
Range of reverse power setting is 0.5% - 10% Pn, where Pn is rated active power of the generator.
Range of delay is 0.1 s – 600 s.
Sometimes, when overload, over excitation or loss-of-excitation protection of generator initiate and
tripping is needed, the steam valve of turbine has to be closed first. Sequent-tripping reverse
power protection is used for this condition. Such protection is a reverse power protection that is
blocked by the position contact of steam valve and circuit breaker of generator. It can trip relevant
circuit breakers with a certain delay since the steam valve being closed. Its setting range is 0.5% -
10% Pn.
P>-[P_RevP_Gen]
& &
[En_PwrProt_Gen] & t Op_RevP_Gen
[TrpLog_RevP_Gen].bit0 [t_Trp_RevP_Gen]
[EBI_PwrProt_Gen]
[FD_Pwr&AccEnerg_Gen]
[BI_52b_GCB]
[BI_Valve_Turbine]
&
Op_SeqTrpRevP_Gen
P>-[P_SeqTrp_RevP_Gen]
& t
&
[En_PwrProt_Gen]
[t_SeqTrp_RevP_Gen]
[TrpLog_SeqTrp_RevP_Gen].bit0
[EBI_PwrProt_Gen]
[FD_Pwr&AccEnerg_Gen]
Three stages of underfrequency protection are equipped for RCS-985G, of which stages 1 is
fixedly configured as accumulating time underfrequency protection, but stage 2 and stage 3 are
designed as continuous time underfrequency characteristic.
As to over frequency protection, two stages are equipped for RCS-985G and they will issue alarm
or trip when it operates.
[En_Alm_UFn_Gen]
& [t_Alm_UF_Gen]
f<[f_UFn_Gen]
[En_FreqProt_Gen]
[EBI_FreqProt_Gen] [t_UFn_Gen]
[FD_FreqProt_Gen]
[En_Alm_OFn_Gen]
& [t_Alm_OF_Gen]
f<[f_OFn_Gen]
[En_FreqProt_Gen]
[FD_FreqProt_Gen]
(1) In the course of generator‘s hand turning (low frequency condition), if it has been excited,
breaker closure by accident may lead to asynchronous starting of the generator. The protection is
put into use automatically with time delay t1 when two groups of voltage derived from two
independent VTs are all less than undervoltage setting and exit with time delay t2 (designed to
cooperate with low-frequency blocking criterion) when the two groups of voltage revert to normal
level.
(2) In the case of the generator breaker being closed by accident in excited condition but the
frequency is under normal level which may occur in startup-and-shutdown process. The protection
is put into use automatically with a time delay t3 during which the Low Frequency criterion is met
and it returns with a time delay t4 after the frequency criteria is released. Here, t4 should be set so
long as to ensure the completion of the tripping course.
(3) If the circuit breaker is closed by accident when the phase angle difference of bus and
generator voltage is very high, say, around 180°, the through closing current will also be too high.
In this case the excitation shall be shut off first and the breaker of the generator can be tripped
until the generator current falls to a level below the standard setting.
In considering the security of the protection, both currents from generator terminal and neutral
point are used in the logic as criteria.
During the process of synchronization of generator, flashover in circuit breaker is possible when
the difference of phase angle of bus voltage and generator voltage is around 180°. Breaker
flashover protection is provided for this fault. One phase and two phases flashover is considered
by this protection but three phase flashovers are ignored.
Excitation has been applied to generator, and generator voltage is greater than setting.
Operation of this protection will shut off excitation and activate circuit breaker failure protection.
Figure 3.3-37 shows logic diagram of breaker flashover protection. Generally, the protection is
equipped with two delay settings, the first is for shut off excitation and the second is for tripping the
local line breaker.
[Flg_UV_Blk] & t1 t2
F<[f_UF_AccEnerg_Gen] =1
& t3 t4
[En_UF_Ctrl_AccEnerg_Gen]
[BI_52b_CB]
[Flg_NoCurr_CB_Gen] t3 t4 =1
&
[En_CB_Ctrl_AccEnerg_Gen]
I_T>[I_OC_AccEnerg_Gen]
&
I_N>[I_OC_AccEnerg_Gen]
[FD_Pwr&AccEnerg_Gen]
[BI_52b_CB]
U>Uset.fix t>[t_Flash11_GCB]
[En_AccEnerg_Gen] Op_Flash12_GCB
t
[EBI_AccEnerg_Gen] t>[t_Flash12_GCB]
[FD_Pwr&AccEnerg_Gen]
Breaker failure initiation (BFI) in RCS-985 is initiated by one of three elements: phase overcurrent
element, zero sequence current element or negative sequence current element.
[BI_52b_GCB]
≥1
[En_CB_Ctrl_BFP_GCB]
[BI_ExtProtTrp]
≥1
[En_ExtTrpCtrlBFP_GCB]
I>[I_BFP_GCB]
I2>[I_NegOC_BFP_GCB]
& & & t Op_BFP11_GCB
& ≥1
[En_NegOC_BFP_GCB]
[t_BFP11_GCB]
3I0>[I_ROC_BFP_GCB]
t Op_BFP12_GCB
&
[En_ROC_BFP_GCB]
[t_BFP12_GCB]
[En_BFP_GCB]
&
[EBI_BFP_Gen]
[FD_Bak_Gen]
Differential current protections are provided for faults of generator. A zero sequence overvoltage
protection is provided for stator earth fault.
Since frequency during startup and shutdown process is usually very low, algorithm independent
of frequency is used for this protection.
Whether the protection should be blocked or not by frequency element or auxiliary contact of
circuit breaker can be determined by logic setting.
F<[f_UF_Ctrl_StShut_Gen] t0
T>[t_**_StShut_Gen]
[En_StShut_Gen] & &
& t
Op_**_StShut_Gen
[Flg_**_StShut_Gen]
[TrpLog_**_StShut_Gen].bit0
[EBI_StShut_Gen]
[FD_StShut_Gen]
Where:
―**‖ represent one of the three protective elements, ―GenDiff‖, ―UF_OC‖ and ―StaROV‖. The three
protective elements‘ diagrams are so likely that they can be expressed in a figure instead of three
for them respectively.
Excitation winding protection comprises definite time and inverse time protection.
One stage of alarm and one stage of tripping are equipped for definite time excitation winding
overload protection.
Figure 3.3-41 shows logic diagram of definite time excitation winding overload protection.
Inverse time excitation winding overload protection consists of three parts: low setting initiator,
inverse time part and high setting definite part. Minimum operation time delay
([tmin_InvOvLd_RotWdg]) is provided for extreme overload condition.
When current in excitation circuit reaches the low setting [I_InvOvLd_RotWdg], the inverse time
protection initiates and the heating accumulation process starts. When the heating accumulation
reaches its setting, alarm will be issued. The inverse time protection can simulate heating
accumulation and radiation process.
Il
Ilh
Ilszd
t min tmax t
Figure 3.3-40 Operation characteristic of inverse time overload protection of excitation winding
In the figure,
[( I l I jzzd) 1] t KLzd
2
(Equation 3.3-19)
Where:
I>[I_InvOvLd_RotWdg]
& &
[En_OvLd_RotWdg]
tmin Op_InvOvLd_RotWdg
[TrpLog_InvOvLd_RotWdg].bit0 &
[EBI_OvLd_RotWdg] &
[FD_Prot_Exc]
circuit.
Figure 3.3-42 shows logic diagram of inverse time excitation winding overload protection.
I>[I_Alm_OvLd_RotWdg]
& t Alm_OvLd_RotWdg
[En_OvLd_RotWdg]
I>[I_OvLd_RotWdg]
& & t Op_OvLd_RotWdg
[En_OvLd_RotWdg]
[TrpLog_OvLd_RotWdg].bit0
&
[EBI_OvLd_RotWdg]
[FD_Prot_Exc]
Figure 3.3-41 Logic diagram of definite time excitation winding overload protection
I>[I_InvOvLd_RotWdg]
& &
[En_OvLd_RotWdg]
tmin Op_InvOvLd_RotWdg
[TrpLog_InvOvLd_RotWdg].bit0 &
[EBI_OvLd_RotWdg] &
[FD_Prot_Exc]
Figure 3.3-42 Logic diagram of inverse time excitation winding overload protection
I d K bl I r I cdqd ( I r nI e )
K bl K bl1 K blr ( I r / I e )
I d K bl 2 ( I r nIe ) b I cdqd ( I r nIe )
K blr ( K bl 2 K bl1 ) /( 2 n)
b ( K bl1 K blr n) nIe
. (Equation 3.3-20)
I 1 I2
Ir
2
I d I 1 I 2
The criterion is the same to Equation 3-1 except the differential current and restraint current. Here:
For excitation transformer: I 1 and I 2 are currents of HV side and LV side respectively.
Two stages of overcurrent protection are equipped for excitation transformer or exciter overcurrent
protection as backup protection. These two stages will trip the circuit breaker with configurable
delay.
[I>[I_OC n_Exc]
t Op_OC n_Exc
&
[En_Bak_Exc]
[t_OC n_Exc]
[EBI_Bak_Exc] &
[TrpLog_OC n_Exc].bit0
[FD_Prot_Exc]
Where:
I max
is maximum phase current.
If this criterion is met, CT circuit failure alarm will be issued with 10s delay. Once the condition
reverts to normal condition, the alarm will be reset with a 10s delay.
This function is enabled only when relevant differential protection logic setting is set as enabled.
If the criterion is met, the alarm will be sent after a delay of 10 s and corresponding differential
protection will not be blocked. When the differential current is eliminated, the alarm will be reset
with a delay of 10 s.
In order to increase sensitivity of this alarm, the percentage restraint differential current alarm
criterion is adopted as shown below.
I d I dbjzd
I d k bj I res (Equation 3.3-22)
If the differential current reaches its threshold and also reaches the differential alarm level of
percentage restraint factor multiplied by the restraint current, the differential current alarm will be
issued.
If internal fault occurs, at least one of following four conditions will be present:
(2) Any phase current of a certain side increases after fault detector picks up;
(4) At least three phase-currents increase after the fault detector picks up.
If none of the above four conditions occur within 40 ms of the differential protection‘s fault
detectors being picked up, the protection treats it as a CT circuit failure. If the logic setting
[Opt_CTS_Blk_PcntDiff_Gen] is set as ―1‖, the differential protection will be blocked and an alarm
will be issued. If this logic setting is set as ―0‖, the differential protection will trip and an alarm will
be issued simultaneously.
If the alarm is issued, the signal can be removed only when the failure is removed and the
equipment is reset manualy.
(1) Positive sequence voltage is less than 18V and any phase current is greater than 0.04 In;
If any one condition occurs, VT circuit failure alarm will be issued with delay 10 s, and the alarm
will be removed automatically by delay 10 s when the failure is removed.
Two groups of VT are equipped at generator terminal. VT circuit failure can be detected by
comparison of phase voltage and positive sequence voltage of these two groups of VT.
U AB1 - U AB2 5 V ;
U BC1 - U BC2 5 V ;
U CA1 - U CA2 5 V ; (Equation 3.3-23)
U11 - U12 3 V ;
Where:
UAB1, UBC1, UCA1 and U11 are phase-to-phase voltage and positive sequence voltage of VT
group 1;
UAB2, UBC2, UCA2 and U12 are phase-to-phase voltage and positive sequence voltage of VT
group 2.
If any of the conditions mentioned above occurs, the VT circuit failure alarm will be issued with a
delay of 0.2 s and the VT group used will be switched over.
When only a VT fails, it will not influence the functioning of related protection such as
loss-of-excitation, out-of-step, overvoltage, over-excitation, reverse power, frequency, impedance
protection and overcurrent protection.
If only one group of VT is provided at generator‘s terminal, user can set this function to ―disable‖.
Ia>[I_BO_OC_Gen]
Operates
Ib>[I_BO_OC_Gen] ≥1
&
Ic>[I_BO_OC_Gen]
[En_BO_OC_Gen]
Figure 3.3-44 Blocking logic diagram of overcurrent element for driving output contact
4.1 Self-supervision
If hardware failure of the equipment is detected, protection functions of the equipment will be
blocked and an equipment blocking alarm will be issued. Hardware failure includes those on RAM,
EPROM, settings, power supply, DSP and tripping coil.
When the following abnormal statuses are detected, an abnormal warning will be issued: AC
voltage or current circuit failure, persist pickup, mismatch state of pickup between CPU and DSP
and alarm of protection element.
The relay includes a number of self-monitoring functions to check the operation of its hardware
and software when it is in service. These are included so that if an error or fault occurs within the
relay‘s hardware or software, the relay is able to detect and report the problem and attempt to
resolve it by performing a re-boot. This involves the relay being out of service for a short period of
time that is indicated by the ‗Healthy‘ LED on the faceplate of the relay being off and the watchdog
contact at the rear operating.
If the restart fails to resolve the problem, then the relay will make itself permanently out of service.
Again this will be indicated by the ‗ALARM‘ LED and watchdog contact. If a problem is detected by
the self-monitoring functions, the relay attempts to store a maintenance record in battery
backed-up SRAM to allow the nature of the problem to be notified to the user.
The self-monitoring is implemented in two stages: firstly a thorough diagnostic check which is
performed when the relay is booted-up, e.g. at power-on, and secondly a continuous self-checking
operation which checks the operation of the relay‘s critical functions during the time it is in service.
The integrity of the flash memory is verified using a checksum before the program code and the
data stored in it is copied into the SRAM to be used for execution by the processor. When the data
has been copied to the SRAM, the data is compared to that in the flash to ensure the two are the
same and no errors have occurred in the transfer of data from flash to SRAM. The entry point of
the software code in SRAM is then called which is the relay initialization code.
The initialization process includes the operations of initializing the processor registers and
interrupts, starting the watchdog timers (used by the hardware to determine whether the software
is still running), starting the real-time operating system and creating and starting the supervisor
task. In the course of the initialization process the relay checks:
• The integrity of the battery backed-up SRAM that is used to store event, fault and disturbance
records.
• The correctness of the settings that ensures relay‘s proper response to fault.
• The voltage level of the field voltage supply which is used to drive the opto-isolated inputs.
At the conclusion of the initialization software the supervisor task begins the process of starting the
platform software.
In starting the platform software, the relay checks the integrity of the data held in non-volatile
memory with a checksum. The final test that is made concerns the input and output of data, the
presence and healthy condition of the input board is checked and the analog data acquisition
system is checked through sampling of the reference voltage.
At the successful conclusion of all of these tests the relay is entered into service and the protection
started-up.
• The flash containing all program code, setting values and language text is verified by a
checksum
• The code and constant data held in SRAM is checked against the corresponding data in flash to
check for data corruption
• The SRAM containing all data other than the code and constant data is verified with a checksum
• The integrity of the digital signal I/O data from the opto-isolated inputs and the relay contacts is
checked by the data acquisition function every time it is executed. The operation of the analog
data acquisition system is continuously checked by the acquisition function every time it is
In the unlikely event that one of the checks detects an error within the relay‘s subsystems, the
platform software is notified and it will attempt to log a maintenance record in the battery
backed-up SRAM. If the problem is of no importance (no possibility of leading to mal-operation),
the relay will continue in operation.
However, for problems detected in any important area the relay will initiate a shutdown and re-boot.
This will result in a period of up to 5 seconds when the protection is unavailable, but the complete
restart of the relay including all initializations should clear most problems that could occur. As
described above, an integral part of the start-up procedure is a thorough diagnostic self-check. If
this detects the same problem that caused the relay to restart, i.e. the restart has not cleared the
problem; the relay will then make itself permanently out of service. This is indicated by the
‗Healthy‘ LED on the front of the relay, which will be off, and the watchdog contact that will operate.
If the alarm is issued, the alarm signal can be reset only when the failure is removed and the
equipment is reset by pressing ―RESET‖ button on panel or re-power it up.
• Overload Alarm
On the condition that the relay does not pick up due to adding of current in excess of the setting of
the overload protection, an alarm message is displayed and ALARM LED is lit after the timer stage
duration has elapsed.
Tripping output relay driving transistor is always monitored in a normal program, and a blocking
message will be issued when the equipment finds abnormality of the tripping output circuit.
Note:
There are three alarm LEDs on HMI module: ―ALARM‖ LED, ―CT ALARM‖ LED and ―VT ALARM‖
LED. In following tables ―ALARM‖, ―CT ALARM‖ or ―CT ALARM‖ means the corresponding LED is
turned on.
Abnormality information printed or displayed on LCD and trouble shooting are described in
following table.
8. Alm_DSP_CPUBrd Note8
9. Alm_DSP_MONBrd Note9
Note:
Note1: Alarm of the mechanical protection due to inconsistance of input signal and repeated
output signal.
Note2: The power supply of mechanical protection is lost.
Note3: Mismatch of pickup of same type fault detectors in CPU and MON.
Note4: Duration of pickup of any fault detector in CPU board is in excess of 10s.
Note5: Duration of pickup of any fault detector in MON board is in excess of 10s.
Note6: Any one of binary input sampled directly doesn‘t match with that of reorganization of
protection itself.
Note7: Alarm indicating that the communication between MON and CPU interrupts.
Note8: The sampled statuses of auxiliary contact of generator terminal breaker‘s don‘t match
with that of operation condition identified from calculation of voltage and currents.
8. Alm_VTS_NP_Gen Note8
9. Alm_DeltVTS1_Term_Gen Note9
Note:
Note1: Alarm indicating VT1 circuit failure and start to switch over voltage circuit.
Note2: Alarm indicating VT2 circuit failure and start to switch over voltage circuit.
Note3: Alarm indicating VT1 circuit failure and blocking 3rd harmonics voltage differential
protection.
Note4: Alarm indicating VT2 circuit failure and blocking interturn protection.
Note5: Alarm indicating secondary circuit failure of VT at HV side of main transformer.
Note6: Alarm indicating secondary circuit failure of VT1 at generator terminal.
Note7: Alarm indicating secondary circuit failure of VT2 at generator terminal.
Note8: Alarm indicating secondary circuit failure of VT at the neutral point of generator.
Note9: Alarm indicating secondary circuit failure at open-delta side of VT1 at generator terminal.
Note10: Alarm indicating secondary circuit failure at open-delta side of VT2 at generator terminal.
Note11: Alarm indicating rotor voltage circuit failure which used by loss-of-excitation protection.
Note12: Alarm indicating secondary circuit abnormality of spare CT at generator terminal.
Note13: Alarm indicating secondary circuit abnormality of CT at generator terminal.
Note14: Alarm indicating secondary circuit abnormality of CT at the neutral point of generator.
Note15: Alarm indicating secondary circuit abnormality of CT installed in splitting-phase branch1
at the neutral point of generator .
Note16: Alarm indicating secondary circuit abnormality of CT installed in splitting-phase branch2
at the neutral point of generator.
Note17: Alarm indicating differential current of generator is in excess of normally endurable level.
Note18: Alarm indicating splitting-phase transverse differential current of generator is in excess of
normally endurable level.
Note19: Alarm indicating secondary circuit failure of CTs used for differential protection.
Note20: Alarm indicating secondary circuit failure of CTs used for splitting-phase transverse
differential protection.
Note21: Alarm indicating secondary circuit failure of CT at side1 of excitation set used in
differential protection of excitation.
Note22: Alarm indicating secondary circuit failure of CT at side2 of excitation set used in
differential protection of excitation.
Note23: Alarm indicating differential current of excitation transformer is in excess of normally
endurable level.
Note24: Alarm indicating differential current of exciter is in excess of normally endurable level.
Note25: Alarm indicating secondary circuit failure of CT used in excitation transformer differential
protection.
Note26: Alarm indicating secondary circuit failure of CT used in exciter differential protection.
NoteI: Locate the position of failure by checking sampled data in protection and secondary
circuit to decide the maintenance scheme.
5. Alm_Int_OOS_Gen Note5
6. Alm_Accel_OOS_Gen Note6
7. Alm_Decel_OOS_Gen Note7
8. Alm_LossExc_Gen Note8
9. Alm_OvExc_Gen Note9
Note:
Note1: Alarm indicating operation of DPFC interturn protective element.
Note2: Alarm indicating operation of overcurrent element used for driving a set of contact to
block other circuit.
Note3: Alarm indicating 2 points earth fault protection has been put input operation after
operation of 1 point earth fault protection of rotor.
Note4: Alarm indicating out-of-step of system occurs while its oscillation center is outside
protective zone.
Note5: Alarm indicating out-of-step of system occurs and its oscillation center is inside protective
zone.
Note6: Alarm indicating accelerate out-of-step occurs.
Note7: Alarm indicating decelerate out-of-step occurs.
Note8: Alarm indicating operation of loss-of-excitation protective element.
Note9: Alarm indicating operation of over excitation protective element.
Note10: Alarm indicating operation of overload element of stator.
Note11: Alarm indicating operation of negative overcurrent protective element of stator.
Note12: Alarm indicating operation of overload protective element of rotor.
Note13: Alarm indicating operation of fundamental zero-sequence overvoltage earth fault
protective element of stator.
rd
Note14: Alarm indicating operation of 3 harmonics ratio earth fault protective element of stator.
rd
Note15: Alarm indicating operation of 3 harmonics differential earth fault protective element of
stator.
Note16: Alarm indicating operation of sensitive stage of 1 point earth fault protective element of
rotor.
Note17: Alarm indicating operation of normal stage of 1 point earth fault protective element of
rotor.
Note18: Alarm indicating operation of stage 1 of under frequency protective element of generator.
Note19: Alarm indicating operation of stage 2 of under frequency protective element of generator.
Note20: Alarm indicating operation of stage 3 of under frequency protective element of generator.
Note21: Alarm indicating operation of stage 1 of over frequency protective element of generator.
Note22: Alarm indicating operation of stage 2 of over frequency protective element of generator.
Note23: Alarm indicating operation of reverse power protective element of generator.
Note24: Alarm indicating operation of mechanical repeater 4. In this project, this alarm means
operation of stage 2 of 1PEF of rotor.
Note25: Alarm indicating operation of mechanical repeater 3. In this project, this alarm means
operation of stage 1 of 1PEF of rotor.
Note26: Alarm indicating operation of mechanical repeater 2. In this project, this alarm means
failure of condenser vacuum.
Note27: Alarm indicating operation of mechanical repeater 1. In this project, this alarm means
operation of manual emergency tripping.
NoteI: Treat according to specific application requirement.
4.2 Metering
The relay produces a variety of both directly and calculated power system quantities. These
measurement values are updated on a per half second basis and can be viewed in the menu
―VALUES‖ of the relay or via relay communication.
This relay is able to measure and display the following quantities as summarized:
I2_NP_Gen: 000.00 A
I0_NP_Gen: 000.00 A
I_BakCT_Gen: 000.00 000.00 000.00 A
I1_BakCT_Gen: 000.00 A
I2_BakCT_Gen: 000.00 A
I0_BakCT_Gen: 000.00 A
I_PwrProt_Gen: 000.00 000.00 000.00 A
I1_PwrProt_Gen: 000.00 A
I2_PwrProt_Gen: 000.00 A
I0_PwrProt_Gen: 000.00 A
Figure 4.2-1 Differential current and related values in CPU and MON
Where:
[I0_BakCT_Gen]: Calculated zero sequence component of the current derived from backup CT at
generator neutral point.
Access path in menu is ―VALUES CPU METERINGGEN DIFF CURR‖ and ―VALUES MON
Note:
The contents inside the first window are the default display seen by user entering this submenu.
User can navigate to the following items (as shown in the other two windows) by scrolling the
arrow keys on the faceplate of the relay. What user meets similar to this case later can be dealt
with in same way.
4.2.7.2 Transverse differential current and related values in CPU and MON
Id_TrvDiff_Gen: 000.00 A
Id_3rdH_TrvDiff_Gen: 000.00 A
Id_SPTDiff_Gen: 000.00 000.00 000.00 Ie
Ir_SPTDiff_Gen: 000.00 000.00 000.00 Ie
Icorr_SP1_Gen: 000.00 000.00 000.00 Ie
Icorr_SP2_Gen: 000.00 000.00 000.00 Ie
I_SP1_Gen: 000.00 000.00 000.00 A
I1_SP1_Gen: 000.00 A
Figure 4.2-2 Transverse differential current and related values in CPU and MON
Where:
current of generator.
Access path in menu is ―VALUES CPU METERING GEN TRVDIFF CURR‖ and VALUES
MON METERING GEN TRVDIFF CURR‖.
GEN VOLTAGE
GEN VOLTAGE
GEN VOLTAGE
U0_3rdH_Longl_Gen: 000.00 V
U_Busbar: 000.00 V
Where:
[U_VT1_Term_Gen]: Phase A, B and C of voltage derived from VT1 at the generator‘s terminal.
[U_VT2_Term_Gen]: Phase A, B and C of voltage derived from VT2 at the generator‘s terminal.
[U0_DeltVT1_Term_Gen]: Zero sequence voltage derived from open-delta side of VT1 at the
generator‘s terminal.
[U0_NP_Gen]: Zero sequence voltage derived from open-delta side of VT at the neutral point of
generator.
[Ud_3rdH_Sta]: 3rd harmonics differential voltage between the terminal and the neutral point of
generator.
Access path in menu is ―VALUES CPU METERING GEN VOLTAGE‖ and VALUES MON
METERING GEN VOLTAGE‖.
P_Gen: + 000.00 %
Q_Gen: + 000.00 %
Accu_InvOvLd_Sta: 000.00 %
Accu_InvNegOC_Gen: 000.00 %
U/F_OvExc_Gen: 00.000
Accu_InvOvExc_Gen: 000.00 %
f_Gen: 000.00 Hz
Accu_UF1_Gen: 000.00 Min
Where:
Access path in menu is ―VALUES CPU METERING GEN MISC VALUES‖ and VALUES
MON METERING GEN MISC VALUES‖.
RotWdg METERING
U(+)_RotWdg: 0000.0 V
U(-)_RotWdg: 0000.0 V
U_RotWdg: 0000.0 V
Rg_RotWdg: 000.00 kΩ
Location_EF_RotWdg: 050.00 %
I_RotWdg: -0000 A
I_Exc: 000.00 A
Accu_InvOvLd_RotWdg: 000.00 %
Where:
Access path in menu is ―VALUES CPU METERING RotWdg METERING‖ and VALUES
MON METERING ROTWDG METERING‖.
EXC AC METERING
EXC AC METERING
I0_S1_Exc: 000.00 A
I_S2_Exc: 000.00 000.00 000.00 A
I1_S2_Exc: 000.00 A
I2_S2_Exc: 000.00 A
I0_S2_Exc: 00.00 A
Where:
[Icorr_S1_Exc]: Phase A, B and C of corrected current on the high voltage side of excitation
transformer or terminal side of exciter (Side 1).
[Icorr_S2_Exc]: Phase A, B and C of corrected current on the low voltage side of excitation
transformer or neutral point side of exciter (Side 2).
Access path in menu is ―VALUES CPU METERING EXC AC METERING‖ and VALUES
MON METERING EXC AC METERING‖.
GEN PH ANG
o
φ_Term_&_NP_Gen: 000 000 000
o
φ_SP1_&_SP2_Gen: 000 000 000
o
φipp_Term_Gen: 000 000 000
o
φipp_NP_Gen: 000 000 000
o
φipp_PwrProt_Gen: 000 000 000
o
φipp_SP1_Gen: 000 000 000
o
φipp_SP2_GenTV1: 000 000 000
o
φvpp_VT1_Term_Gen: 000 000 000
GEN PH ANG
o
φvpp_VT2_Term_Gen: 000 000 000
o
φv_VT1_&_VT2_Gen: 000 000 000
o
φ_V3rdH_Gen: 000.0
o
φvi_Term_Gen: 000 000 000
o
φvi_Term_&_Bak_Gen: 000 000 000
Where:
[φipp_Term_Gen]: phase angle between phase A and B, B and C, C and A of current derived from
CT at generator‘s terminal.
[φipp_NP_Gen]: phase angle between phase A and B, B and C, C and A of current derived from
CT at generator‘s neutral point.
[φipp_PwrProt_Gen]: phase angle between phase A and B, B and C, C and A of current specially
used for power protection.
[φipp_SP1_Gen]: phase angle between phase A and B, B and C, C and A of current derived from
CT at the phase-splitting branch 1.
[φipp_SP2_Gen]: phase angle between phase A and B, B and C, C and A of current derived from
CT at the phase-splitting branch 2.
[φv_VT1_&_VT2_Gen]: phase angle between same-phase voltages derived from VT1 and VT2 at
generator‘s terminal.
[φ_V3rdH_Gen]: phase angle between phase A and B, B and C, C and A of 3rd harmonics voltage
derived from VT1 at generator‘s terminal.
[φvi_Term_Gen]: phase angle between same-phase voltage and current of generator‘s terminal.
[φvi_Term_&_Bak_Gen]: phase angle between same-phase voltage from VT1 and current derived
from spare CT at generator‘s terminal.
EXC PH ANG
o
φi_S1_&_S2_Exc: 000 000 000
o
φipp_S1_Exc: 000 000 000
o
φipp_S2_Exc: 000 000 000
Where:
[φipp_S1_Exc]: phase angle between phase A and B, B and C, C and A of current derived from
CT at side 1 of excitation transformer or exciter.
[φipp_S2_Exc]: phase angle between phase A and B, B and C, C and A of current derived from
CT at side 2 of excitation transformer or exciter.
4.3 Signaling
Signals here mean changes of binary inputs. All these signals can be displayed on LCD, locally
printed or sent to automation system of substation via communication channel.
EBI_Diff_Gen: 0
EBI_SPTDiff_Gen: 0
EBI_PPF_Gen: 0
EBI_IntTurn_Gen: 0
EBI_ROV&ROC_Sta: : 0
EBI_V3rdH_Sta: 0
EBI_1PEF_RotWdg: 0
EBI_2PEF_RotWdg: 0
EBI_AccEnerg_Gen: 0
EBI_SeqTrpRevP_Gen: 0
EBI_StShut_Gen: 0
EBI_BFP_GCB: 0
Where:
Access path in menu is ―VALUES CPU BI STATE GEN PROT EBI‖ and ―VALUES MON BI
STATE GEN PROT EBI‖.
EBI_Diff_Exc: 0
EBI_Bak_Exc: 0
EBI_OvLd_Exc: 0
Where:
Access path in menu is ―VALUES CPU BI STATE EXC PROT EBI‖ and ―VALUES MON BI
STATE EXC PROT EBI‖.
Mech Prot BI
EBI_Trp_MechRly1: 0
EBI_Trp_MechRly2: 0
EBI_Trp_MechRly3: 0
EBI_Trp_MechRly4: 0
BI_MechRly1: 0
BI_MechRly2: 0
BI_MechRly3: 0
BI_MechRly4: 0
Where:
[BI_MechRly 1]: Binary input indicating operation of mechanical repeater 1(manual emergency
tripping).
[BI_MechRly 2]: Binary input indicating operation of mechanical repeater 2(failure of condenser
vacuum).
[BI_MechRly 3]: Binary input indicating operation of mechanical repeater 3(stage 1 of 1PEF of
rotor).
[BI_MechRly 4]: Binary input indicating operation of mechanical repeater 4(stage 2 of 1PEF of
rotor).
Access path in menu is ―VALUES CPU BI STATE EXC PROT EBI‖ and ―VALUES MON BI
STATE EXC PROT EBI‖.
AUX BI
BI_52b_GCB: 0
BI_ExtProtTrp: 0
BI_Valve_Turbine: 0
BI_UrgBrake: 0
BI_SyncCondenser: 0
BI_Pwr_Superv: 0
Where:
terminal.
[BI_ExcProtTrp]: Binary input indicating the external trip contact of other protection is closed.
[BI_Valve_Turbine]: Binary input indicating the valve of steam turbine is in close position.
[BI_SyncCondenser]: Binary input indicating the synchronous condenser is put into operation.
[BI_Pwr_Superv]: Binary input indicating the power supply for all binary input circuit is working in
good condition.
Access path in menu is ―VALUES CPU BI STATE AUX BI‖ and ―VALUES MON BI STATE
AUX BI‖.
INTER GENERATED BI
FD_Diff_Gen: 0
FD_EF_Sta: 0
FD_EF_RotWdg: 0
FD_OvLd_Sta: 0
FD_PPF_Gen: 0
FD_Volt&OvExc_Gen: 0
FD_FreqProt_Gen: 0
FD_LossExc&OOS_Gen: 0
INTER GENERATED BI
FD_Pwr&AccEnerg_Gen: 0
FD_StShut_Gen: 0
FD_Prot_Exc: 0
FD_MechRly: 0
Where:
[FD_EF_Sta]: Internally generated binary input indicating operation of fault detector of earth fault
protection of stator.
[FD_EF_RotWdg]: Internally generated binary input indicating operation of fault detector of earth
fault protection of rotor.
[FD_OvLd_Sta]: Internally generated binary input indicating operation of fault detector of overload
protection of stator.
[FD_PPF_Gen]: Internally generated binary input indicating operation of fault detector of backup
protection of generator.
[FD_StShut_Gen]: Internally generated binary input indicating operation of fault detector of startup
and shutdown protection of generator.
Access path in menu is ―VALUES CPU BI STATE MONF FD‖ and ―VALUES MON BI
STATE MON FD‖.
PS SUPERV BI
BI_Pwr_MechRly: 1
BI_Pwr_Opto: 1
BI_RstTarg: 0
BI_Pulse_GPS: 0
BI_Print: 0
Where:
[BI_Pwr_MechRly]: binary input indicating the power supply of mechanical repeater is in proper
working condition.
[BI_Pwr_Opto]: binary input indicating the power supply of optical isolators is in proper working
condition.
Access path in menu is ―VALUES CPU BI STATE PS SUPERV BI‖ and ―VALUES MON BI
STATE PS SUPERV BI‖ .
available space is exhausted, the oldest event is automatically overwritten by the new one.
The real time clock within the relay provides the time tag to each event, to a resolution of 1ms. The
event records are available for viewing either via the frontplate LCD or remotely, via the
communications ports (courier and MODBUS versions only).
Local viewing on the LCD is achieved in the menu column entitled ―REPORT‖. This column allows
viewing of event and fault records and is shown by setting sequence No. of the event or fault
report by user. Refer to section 8 for details of operation method.
Where ―Record NO.‖ means the sequence No. of the record which is generated by RCS-985G
automatically. ―Date: DD-MM-YY‖ and ―Time: HH:MM:SS:xxxxms‖ commonly comprise the
absolute time tag of the record. ―Binary input Name‖ shows the name of the binary input whose
state changes. ―Changing manner‖ shows how to change of the state of the binary input. For
instance:
All the binary input that may be shown in the menu can be found in section 4.3, here list them
again.
The above figure shows the abbreviated description that is given to the various alarm conditions
and also a corresponding value between 0 and 31. This value is appended to each alarm event in
a similar way as for the input events previously described. It is used by the event extraction
software, such as RCSPC, to identify the alarm and is therefore invisible if the event is viewed on
the LCD.
The following table shows all of the alarm elements that may be displayed in this item.
Where:
―Record NO.‖ means the sequence No. of the record which is generated by RCS-985G
automatically.
―Date: xxxx-xx-xx‖ and ―Time: xx:xx:xx:xxxxms‖ commonly comprise the absolute time tag of the
record.
―Operation Element‖ shows the name of the operating element. If there are more than one
elements operating, they will scroll one by one to display on LCD.
―xxx ms‖ shows the relative time of operation element to fault detector of the relay.
The following table lists all the operation elements that may be displayed on LCD.
The MON board can store up to 4 seconds (24 sampling points per cycle) or 8 seconds (12
sampling points per cycle) continual waveform, which include all channels analog quantities
(sampled data, diferential currents and so on), all binary input changing states, binary output, pick
up flags of fault detectors, alarm signals, operation signals and tripping signals.
Disturbance records continue to be recorded until the available memory is exhausted, at which
time the oldest record(s) are overwritten to make space for the newest one.
It is not possible to view the disturbance records locally via the LCD; they must be extracted using
suitable software such as RCSPC. This process is fully explained in the section 11.6.
The CPU board can also record the latest 8 cycles of waveform in normal operatin condition,
which is composed of three phase current, corrected current of each side for differential protection,
three phases voltage and zero sequence voltage of each side. This function can help the user to
check the pole‘s correctness of secondary circuit by comparing the phase of related quantities
shown in wave figure. This manual gives the detail instruction of getting normal operation
waveform in section 8.2.6.
Note:
The case materials of the relay are constructed from pre-finished steel that has a conductive
covering of aluminum and zinc. This provides good earthing at all joints giving a low impedance
path to earth that is essential for performance in the presence of external noise.
The boards and modules use a multi-point earthing strategy to improve the immunity to external
noise and minimize the effect of circuit noise. Ground planes are used on boards to reduce
impedance paths and spring clips are used to ground the module metalwork. Heavy duty terminal
blocks are used at the rear of the relay for the current and voltage signal connections. Medium
duty terminal blocks are used for the digital logic input signals, the output relay contacts, the power
supply and the rear communication port. A BNC connector may be used for the optional IRIG-B
signal. 9-pin and 25-pin female D-connectors are used at the front of the relay for data
communication.
Inside the protection the PCBs plug into the connector blocks at the rear, and can be removed
from the rear of the relay only. The connector blocks to the relay‘s CT inputs are provided with
internal shorting links inside the relay which will automatically short the current generator circuits
before they are broken when the board is removed. The front panel consists of a membrane
keypad with tactile dome keys, an LCD and 5 LEDs mounted on an aluminum face plate.
RCS-985
GENERATOR PROTECTION
HEALTHY
GRP
VT ALARM
CT ALARM
ALARM
ENT
ESC
TRIP
Components mounted on its front include a 240×128 dot matrix LCD, a 9 button keypad, 5 LED
indicators, a signal reset button, a DB9 connector for communication with HELP-90A or PC and a
DB15 connector for analog quantity inputs during commissioning.
ALARM: Abnormal;
As to the buttons of the keypad, ―ENT‖ is ―enter‖, ―GRP‖ is ―setting group selector‖ and ―ESC‖ is
―escape‖.
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29
1 1 1 1
A2 4 6 8 10 12 14 16 18 20 22 24 26 28
A30 B2 4 6 8 10 12 14 16 18 20 22 24 26 B
28 30
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29
2 2 2 2
A2 4 6 8 10 12 14 16 18 20 22 24 26 28
A30 B2 4 6 8 10 12 14 16 18 20 22 24 26 B
28 30
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29
3 3 3 3
A2 4 6 8 10 12 14 16 18 20 22 24 26 28A30 B2 4 6 8 10 12 14 16 18 20 22 24 26 B
28 30
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29
4 4 4 4
A2 4 6 8 10 12 14 16 18 20 22 24 26 28A30 B2 4 6 8 10 12 14 16 18 20 22 24 26 B
28 30
51 3 5 7 9 11 13 15 17 19 21 23 25 27529
B2 4 6 8 10 12 14 16 18 20 22 24 26 B28 30
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29
6 6
B2 4 6 8 10 12 14 16 18 20 22 24 26B
28 30
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29
7 7
B2 4 6 8 10 12 14 16 18 20 22 24 26B
28 30
1 3 5 7 9 11 13 15 17
8
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29
8 8
B2 4 6 8 10 12 14 16 18 20 22 24 26B C
28 30
2 4 6 8 10 12 14 16 18
1 3 5 7 9 11 13 15 17 1 3 5 7 9 11 13 15 17
9 9
B C
2 4 6 8 10 12 14 16 18 2 4 6 8 10 12 14 16 18
opto- binary
AC current DSP1 status
and voltage
LPF A/D DSP2 coupler input
CPLD
output
MMI CPU1 relay
LCD
CPU module
MMI-CPU QDJ
comm ports and
port to printer
E+
MMI
DSP3 opto- binary
LPF A/D coupler status
DSP4 input
DC 220 V
or 110 V
+5 V
CPLD
DC/DC
±12 V
+24 V
MMI CPU2
±24 V to
optic-coupler management module
The equipment RCS-985G uses Motorola 32 bits monolithic microprocessor MC68332 as control
kernel for output logic and management functions, and high-speed digital signal processor DSP
for protection calculation. Sampling rate of the equipment is 24 points per cycle. Real time data are
processed in parallel for all algorithms during whole fault process. So the equipment can ensure
very high inherent reliability and security.
AC currents and voltages of CT and VT are transferred to low voltage signals by isolating
transformers and are inputted to the CPU module and MON module. Data and logic are processed
respectively in these two modules with same type of hardware. The CPU module carries out
functions of protection algorithms, tripping logic, event record and printing. The MON module
comprises of general fault detector and the fault recorder. The fault detector will connect to the
positive pole of power supply of output relays after pickup. Format of the record is compatible with
COMTRADE, and the data recorded can be uploaded via separate serial port for communication
or printing.
AC current and voltage are converted to low voltage signals in modules AC1 and AC2. Two ratings
of AC current are option, 1A or 5A. It shall be stated definitely during ordering and checked during
commissioning.
Binary outputs of tripping commands, tripping signal outputs and status binary input parts are
comprised in three modules: RLY, SIG1 and SIG2. 24V and 250/220/125/110V opto-couplers are
used here for binary input.
Briefly, the equipment is composed of ten modules to achieve the work of generator protection.
The modules are AC voltage and current input module1(AC1), AC current input modules(AC2),
management/record module(MON), protection CPU module(CPU), power supply module(DC),
binary input module (OPT2), signal modules(SIG1 and SIG2), tripping contacts output(RLY), and
human machine interface(HMI).
The relay hardware is based on a modular design whereby the relay is made up of an assemblage
of several modules.
Connectors with 30 pins are used for DC power supply, binary input, communication and printer,
tripping, alarm and other signal output and AC voltage input. Numbers of these connectors are 1A,
1B, 2A, 2B, 3A, 3B, 4A, 4B, 5B, 6B, 7B and 8B. Figure 5.2-1 a) shows layout of 30 pins of these
connectors.
Connectors with 18 pins are used for current input. Numbers of these connectors are 8C, 9B and
9C. Figure 5.2-1 b) shows layout of pins of these connectors.
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 1 3 5 7 9 11 13 15 17
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 2 4 6 8 10 12 14 16 18
Attention:
For showing the relation of each terminal clearly, the terminal‘s location shown in the Figure may
be different from the real physical location, and we needn‘t figure out the blank terminals.
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
1A1,1A30 blank
Binary output of tripping:
1A3-1A5 BO_TripOutp1-1 (TJ1-1) Tripping output channel 1-1
1A7-1A9 BO_TripOutp1-2 (TJ1-2) Tripping output channel 1-2
1A11-1A13 BO_TripOutp1-3 (TJ1-3) Tripping output channel 1-3
1A15-1A17 BO_TripOutp1-4 (TJ1-4) Tripping output channel 1-4
1A19-1A21 BO_TripOutp2-1 (TJ2-1) Tripping output channel 2-1
1A23-1A25 BO_TripOutp2-2 (TJ2-2) Tripping output channel 2-2
1A27-1A29 BO_TripOutp2-3 (TJ2-3) Tripping output channel 2-3
1A2-1A4 BO_TripOutp3-1 (TJ3-1) Tripping output channel 3-1
1A6-1A8 BO_TripOutp3-2 (TJ3-2) Tripping output channel 3-2
1A10-1A12 BO_TripOutp3-3 (TJ3-3) Tripping output channel 3-3
1A14-1A16 BO_TripOutp3-4 (TJ3-4) Tripping output channel 3-4
1A18-1A20 BO_TripOutp4-1 (TJ4-1) Tripping output channel 4-1
1A22-1A24 BO_TripOutp4-2 (TJ4-2) Tripping output channel 4-2
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
1 7 13 19 25 3 9 15 21 27 5 11 17 23 29
2 8 14 20 26 4 10 16 22 28 6 12 18 24 30
Note:
Signals contacts for stator earth fault protection will be driven when stator zero sequence
overvoltage elements operates in generator startup and shutdown.
Signals contacts for generator differential protection will be driven when differential current
element operates in generator startup and shutdown.
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
3B2 blank
Binary output of abnormality contact:
3B1-3B3 BO_OC_InitBFP Normal opened contact indicating
operation of generator terminal
overcurrent element for initial breaker
failure protection
3B5-3B7 BO_OC_InitBFP Normal closed contact indicating
operation of generator terminal
overcurrent element for initial breaker
failure protection
3B9-3B11 Reserved
3B13-B15 Reserved
3B17-3B19 Reserved
3B21-3B23 Reserved
3B25-3B27 Blank
Binary output of event record signal:
3B2 blank
3B4 COMMON Event record: common terminal
3B4-3B6 BO_Alm_CTS CT circuit failure alarm
3B4-3B8 BO_Alm_VTS VT circuit failure alarm
3B4-3B10 BO_Alm_OvLd Overload alarm
3B4-3B12 BO_Alm_NegOC Negative sequence overload alarm
3B4-3B14 BO_Alm_OvLd_RotWdg Excitation overload alarm
3B4-3B16 BO_Alm_EF_Sta Stator earth fault alarm
3B4-3B18 BO_Alm_1PEF_Gen Generator coasting alarm
3B4-3B20 BO_Alm_LossExc_Gen Loss-of-excitation alarm
3B4-3B22 BO_Alm_OOS_Gen Out-of-step alarm
3B4-3B24 BO_Alm_FreqProt_Gen Under frequency alarm
3B4-3B26 BO_FAIL Equipment being blocked
+ -
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29
+24
V
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 0V
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29
+-
+24V
DC/DC
0V
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
5B24 Blank
5B26 Blank
5B28 Blank
5B29 Earth
5B30 Earth
Note:
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29
A B A B A B TX RX Earth
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
G
1 2 7 8 9 10 13 14 17 18 21 22 25 26 29 30
3 4 5 6 11 12 15 16 19 20 23 24 27 28
1 3 5 7 9 11 13 15 17
20K
UR+2 UR-2 IR+ IR-
UR+ UR-
2 4 6 8 10 12 14 16 18
1 2 3 4 5 6 7 8 9 10 11 12
I AN IA I BN IB ICN IC I AN IA I BN IB ICN IC
TO LPF TO LPF
TO LPF
I ' trans I trans I ' shaft I shaft U '0TV1 U0TV1
13 14 15 16 17 18
Note:
Current channel of side 1 can be configured as the current of HV side of excitation transformer or
the neutral current of exciter.
Current channel of side 2 can be configured as the current of LV side of excitation transformer or
the terminal current of exciter.
1 2 3 4 5 6 7 8 9 10 11 12
I AN IA I BN IB I CN IC I AN IA I BN IB I CN IC
TO LPF TO LPF
TO LPF
I AN IA I BN IB I CN IC
13 14 15 16 17 18
Note:
9C13—9C18 can be configured as the current of phase-splitting branch2, dedicate current for
reverse power protection and current used for distance protection of voltage-controlled
overcurrent protection.
The protection can either use zero sequence voltage derived from 9B17, 9B18 or calculated zero
sequence voltage of TV1 depending on the setting way of the related logic setting.
5.3 Output
5.3.1 Tripping outputs
The equipment provides 12 groups of tripping relays with 29 pairs of contacts totally as shown in
the following figure. These tripping relays can be configured by tripping output logic setting, and
practical and flexible tripping modes can be provided by each protective function then. The tripping
output logic setting is a specific setting of each certain protective function. Please refer to Chapter
7 for details of setting.
The tripping output logic setting is a 4 digits hexadecimal number or a 16 bits binary number.
Every bit corresponds to a circuit breaker. The breaker will be tripped if the corresponding bit is set
as ―1‖ and not tripped if the bit is set as ―0‖.
BO_OC_InitBFP
3B01 3B03
BO_OC_InitBFP
3B05 3B07
Protection& control
Measurement and event, fault & disturbance
Software records
Protection
task
Scheme logic
Relay hardware
To control the logging of records that are generated by the protection software, including alarms
and event, fault, and maintenance records.
To store and maintain a database of all of the relay‘s settings in non-volatile memory.
To provide the internal interface between the settings database and each of the relay‘s user
interfaces, i.e. the front panel interface and the front and rear communication ports, using
whichever communication protocol has been specified (Courier, MODBUS, and IEC
60870-5-103).
supervisor task that controls the start-up of the task and deals with the exchange of messages
between the task and the platform software.
After initialization at start-up, the protection and control task is suspended until there are sufficient
samples available for it to process. The acquisition of samples is controlled by a ‗sampling
function‘ which is called by the system services software and takes each set of new samples from
the input module and stores them in a two-cycle buffer. The protection and control software
resumes execution when the unprocessed sample‘s in the buffer reaches a certain number. For
the RCS-985G protection relay, the protection task is executed at the same speed as the sampling
rate, i.e. the calculation of all relays is finished before next sampling process. During the residual
time, operations by other software tasks take place.
The sampling function provides filtering of the digital input signals from the opto-isolators and
frequency tracking of the analog signals. The digital inputs are checked against their previous
value over 15ms. Hence a change in the state of one of the inputs must be maintained at least
15ms before it is registered with the protection and control software.
The frequency tracking of the analog input signals is achieved by a recursive Fourier algorithm
which is applied to one of the input signals, and works by detecting a change in the measured
signal‘s phase angle. The calculated value of the frequency is used to modify the sample rate
being used by the AC modules so as to achieve a constant sample rate of 24 samples per cycle of
the power waveform. The value of the frequency is also stored for use by the protection and
control task.
A change in any digital input signal, protection element output signal, operation flags of fault
detectors, tripping flags causes an event record to be created. When this happens, the protection
and control task sends a message to the supervisor task to indicate that an event is available to be
processed and writes the event data to a fast buffer in SRAM which is controlled by the supervisor
task. When the supervisor task receives either an event or fault record message, it instructs the
platform software to create the appropriate log in the battery backed-up SRAM. The operation of
the record logging to battery backed-up SRAM is slower than the supervisor‘s buffer. This means
that the protection software is not delayed waiting for the records to be logged in by the platform
software.
The disturbance recorder operates as a separate task from the protection and control task. It can
record the waveforms for up to 32 analog channels and the values of all digital signals of
RCS-985G. The recording time is user selectable up to a maximum of 8 seconds. The disturbance
recorder is supplied with data by the protection and control task once per sampling period.
The disturbance recorder collates the data that it receives into the required length disturbance
record. The disturbance records can be extracted by RCSPC that can also store the data in
COMTRADE format, thus allowing the use of other packages to view the recorded data.
Hardware requirement
Software requirement:
Downloading method
Note:
Ensure that the board is not blank before downloading software to it, i.e., certain versions of
software already exists on the board.
Warning:
If some unexpected cases occur, please do inform the factory first instead of dealing with it by
yourself.
RCS-985
GENERATOR PROTECTION
HEALTHY
GRP
VT ALARM
CT ALARM
ALARM
ENT
ESC
TRIP
2
3
5
2
3
5
Steps:
1. Connect RS-232 communication port of the computer and that mounted on front panel of
RCS-985G protection equipment by a cable with DB-9 connectors on both ends, see Figure 6.4-1.
2. Run the program RCSPC. If the connection and settings are correct, the screen will display
―RCS-985G connected‖, such as Figure 6.4-2. But if it is not connected, please check whether the
parameter setting of RCSPC corresponds with the relay, such as ―COM port‖ and ―Baud rate‖, see
Figure 6.4-3.
3. Download CPU program. At first, make sure it is at CPU mode as ―CPU>‖, then press the button
and select the correct program file, such as CPU.s19, to download into the CPU module.
Make sure that the file FLASHCPU.s19 is in the same folder as the program file.
4. Download MON program. Change it to MON mode by typing ―MON‖, then ―MON>‖ will appear.
Then repeat step 3 to download MON.s19 to MON module. Make sure the file FLASHMON.s19 is
in the same folder as the program file. See Figure 6.4-4.
5.After downloading CPU and MON programs, reset the equipment and download default settings.
Then the ‗HEALTHY‘ LED on the front panel of the relay will illuminate.
6. Download FACE program. Change it to FACE mode by typing ―FACE‖ or ―PNL‖, then ―PNL>‖
will appear. Press the button and select the 985xx_FACE.hex file to download it into the
panel module. Make sure the file FLASH_FACE.hex is in the same folder as the program file.
7. The user should now check and ensure that the software version, CRC code and the generating
time of software are same as those recorded in the relevant documentations. Enter the menu
―Version‖, then new version of protection will be displayed on the LCD, see Figure 6.4-5.
VERSION
CPUBrd: RCS-985G3QM 1.00
ABCDEFGH
2007-01-01 09:00
MONBrd: RCS-985G3QM 1.00
ABCDEFGH
2007-01-01 09:00
HMI: RCS-985G3QM 1.00 ABCD
2007-01-01 09:00 T_060902
SUBQ_ID: SUBQ_12345678
Chapter7 Settings
The relay must be configured to the system and application by means of appropriate settings. The
settings of this relay include system parameters, protection element settings and scheme logic
settings.
Note:
Symbols of the parameter listed in above table are used for communication, printing and
displaying on LCD.
1 No.1-- [Active_Grp]
Two setting groups can be configured for the equipment, and only one is active at one time.
However, equipment parameters and system parameters are common for all protection setting
groups.
2 No.2-- [Equip_ID]
The setting consists of ASCII codes, which is identification for report printing only. It can be
configured according to the name or number of generator.
3 No.3-- [Comm_Addr]
The address used for the host computer to identify the equipment, usually provided by substation
system. If the equipment is not connected to automation system, equipment address may be
random.
4 No.4-- [Com1_Baud]
The baud rate of serial port 1 shall be selected from specified range.
5 No.5-- [Com2_Baud]
The baud rate of serial port 2 shall be selected from specified range.
6 No.6--[Printer_Baud]
The baud rate used for printer port shall be selected from specified range.
7 No.7-- [Protocol]
The logic setting consists of 16 binary digits but four hexadecimal digits can be viewed through
device LCD screen. Every digit has a dedicated meaning and some digits have no definition.
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
B: MODBUS
A: MODBUS
B: LFP
A: LFP
B: 103
A: 103
The definitions of digits are:
Bit Definition
0 communication port A using protocol IEC 60870-5-103
1 communication port A using proprietary protocol LFP
2 communication port A using MODBUS protocol
3 No definition
4 communication port B using protocol IEC 60870-5-103
5 communication port B using proprietary protocol LFP
6 communication port B using MODBUS protocol
7-15 No definitions
For example, if logic setting [Protocol] is set as ―0011‖, it means communication both port A and B
use IEC 60870-5-103 protocol.
8 No.8-- [En_Auto_Print]
This setting shall be set as ―1‖ if automatic report printing is expected after the relay operates
when a fault occurs. Otherwise it shall be set as ―0‖. It is suggested that the user may set this
parameter of the equipment as ―1‖ (i.e. automatic printing), if the equipment is always connected
directly with a printer, or set as ―0‖ (i.e. not automatic printing) if the equipment is connected with a
printer by through switch on panel.
9 No.9-- [En_Net_Print]
Set it as ―1‖ if shared network printer is used for printing. Set it as ―0‖ if dedicated printer is used.
Network printer means several protection equipments share one printer through a printer
management unit and RS-485 port. Dedicated printer means the protection equipment is
connected with a printer through RS232 port directly.
10 No.10--[En_Remote_Cfg]
Set it as ―0‖ if only local configuration is permitted. Set it as ―1‖ if local and remote configurations
are both permitted.
11 No.11-- [GPS_Pulse]
Set it as ―1‖ for minute pulse and ―0‖ for second pulse.
Main Menu -> SETTINGS -> EQUIP SETTINGS -> [setting symbol]
15 En_StShut_Gen 0/1 0
16 En_AccEnerg_Gen 0/1 0
17 En_Diff_Exc 0/1 0
18 En_Bak_Exc 0/1 0
19 En_OvLd_RotWdg 0/1 0
20 En_MechRly 0/1 0
21 En_VTComp_Term_Gen 0/1 0
22 En_BFP_GCB 0/1 0
23 En_TestMode(#) Disable/Enable Disable
Note:
Symbols of the parameter listed in above table are used for communication, printing and
displaying on LCD. Setting marked with “#” means that it is can not be seen on LCD or by
printing and only can be seen through RCSPC software.
1 No.1-- [En_Diff_Gen]
This logic setting is used for configuration of protection functions. Setting it as ―1‖ means the
generator differential protection is enabled and setting as ―0‖ means the protection is disabled.
2 No.2-- [En_SPTDiff_Gen]
3 N0.3-- [En_IntTurn_Gen]
4 No.4-- [En_PPF_Gen]
5 No.5-- [En_EF_Sta]
6 No.6-- [En_EF_RotWdg]
7 No.7-- [En_OvLd_Sta]
8 No.8-- [En_NegOC_Gen]
This logic setting is used to enable negative sequence overcurrent protection of stator.
9 No.9-- [En_LossExc_Gen]
10 No.10-- [En_OOS_Gen]
11 No.11-- [En_VoltProt_Gen]
This logic setting is used to enable overvoltage and undervoltage protection of generator.
12 No.12-- [En_OvExc_Gen]
13 No.13-- [En_PwrProt_Gen]
This logic setting is used to enable overpower and underpower protection of generator.
14 No.14-- [En_FreqProt_Gen]
This logic setting is used to enable overfrequency and underfrequency protection of generator.
15 No.15-- [En_StShut_Gen]
This logic setting is used to enable all relevant protections in Startup/shutdown conditions of
generator.
16 No.16-- [En_AccEnerg_Gen]
This logic setting is used to enable relevant protection in case of accident energization of
generator.
17 No.17-- [En_Diff_Exc]
This logic setting is used to enable differential protection of exciting transformer or exciter.
18 No.18-- [En_Bak_Exc]
This logic setting is used to enable backup protection of exciting transformer or exciter.
19 No.19-- [En_OvLd_RotWdg]
20 No.20-- [En_MechRly]
21 No.21-- [En_VTComp_Term_Gen]
This logic setting is used to enable comparison function of VTs at the generator terminal.
22 No.22-- [En_BFP_GCB]
This logic setting is configured especially for equipment debugging status. It is only seen by
RCSPC, which is used for generating messages of alarm or operation element for remote PC.
―Enable‖: enable sending all tripping contacts signals, protection tripping signals, alarm signals
and monitoring signals through DBU2000 software.
All logic settings of configuring functions are accessible in the following path:
Main Menu -> SETTINGS -> SYSTEM SETTINGS -> PROT CONFIG -> [setting symbol]
Note:
Symbol of the parameters listed in above table are used for communication, printing and
displaying on LCD.
1 No.1-- [fn_Gen]
This setting indicates the nominal frequency of power system in which the generator protection
equipment is in service.
2 No.2-- [Pn_Gen]
Capacity of active power of the generator shall be configured as its name plate stated.
3 No.3-- [PF_Gen]
4 No.4-- [U1n_Gen]
System rated voltage at the terminal of generator. This setting is used for calculating the rated
current of generator. It should be set according to the real operating voltage of the power system.
5 No.5-- [U1n_VT_Term_Gen]
Rated primary voltage of VT at the terminal of generator. This parameter can be configured as
either phase voltage or phase-to-phase voltage value. For example, if the terminal VT ratio is
6 No.6-- [U2n_VT_Term_Gen]
7 No.7-- [U2n_DeltVT_Term_Gen]
8 No.8-- [U1n_VT_NP_Gen]
9 No.9-- [U2n_VT_NP_Gen]
10 No.10-- [I1n_CT_Term_Gen]
11 No.11-- [I2n_CT_Term_Gen]
12 No.12-- [k_SP1_Gen]
Branching coefficient of the first group of windings to the whole stator. At the generator neutral
point, two channels of CT input are reserved which can meet the requirement of both differential
protection and phase-splitting transverse differential protection. The branching coefficient can be
set according to the proportion of per branch occupying in the whole winding. For the case that
only one branch can be drawn out from the neutral point of generator, the branching coefficient of
the first one group branch must be set as 100% and the other branching coefficient must be set as
0%.
13 No.13-- [k_SP2_Gen]
14 No.14-- [I1n_CT_SP1_Gen]
15 No.15-- [I2n_CT_SP1_Gen]
16 No.16-- [I1n_CT_SP2_Gen]
17 No.17-- [I2n_CT_SP2_Gen]
18 No.18-- [I1n_CT_TrvDiff_Gen]
19 No.19-- [I2n_CT_TrvDiff_Gen]
20 No.20-- [I1n_RotWdg]
Primary rated current of rotor. This setting and the next one can be set conveniently by inputting
the rated primary and secondary parameters of the shunt.
21 No.21-- [U2n_Shunt_RotWdg]
All settings of generator system parameters are accessible in the following path:
Main Menu -> SETTINGS -> SYSTEM SETTINGS -> GEN SYS SETTINGS -> [setting symbol]
Note:
These parameters are as important as the settings. They have to be configured according to
actual application on site.
1 No.1-- [fn_Exc]
This setting indicates the nominal frequency of exciter. If excitation transformer is used, this setting
can be set as 50Hz and the other settings in this table should be set according to relevant
parameters of excitation transformer.
2 No.2-- [Sn_Exc]
Capacity of the exciter or excitation transformer shall be configured as its name plate stated.
3 No.3-- [U1n_S1_Exc]
The system rated voltage on HV side of the excitation transformer. This setting is used to calculate
the correction coefficient of differential protection of excitation transformer.
If exciter is used, this setting and NO.4 setting are all set as the rated voltage of exciter.
4 No.4-- [U1n_S2_Exc]
System rated voltage on LV side of the excitation transformer. This setting is used to calculate the
correction coefficient of differential protection of excitation transformer.
5 No.5-- [I1n_CT_S1_Exc]
Primary rated current of the CT on HV side of the excitation transformer or CT at the terminal of
the exciter.
6 No.6-- [I2n_CT_S1_Exc]
Secondary rated current of the CT on HV side of the excitation transformer or CT at the terminal of
the exciter.
7 No.7-- [I1n_CT_S2_Exc]
Primary rated current of the CT on LV side of the excitation transformer or CT at the neutral point
of the exciter.
8 No.8-- [I2n_CT_S2_Exc]
Secondary rated current of the CT on LV side of the excitation transformer or CT at the neutral
point of the exciter.
9 No.9-- [Opt_Exc]
Exciter is used in the system. If this setting is set as ―1‖, that means exciter is used in the generator
system instead of excitation transformer. Otherwise means the contrary.
10 No.10-- [Yy12_Conn_ET]
Note:
In the symbol of ―Yy-12‖, the first letter ―Y‖ represents the connection mode of windings on HV side,
and the other ―y‖ represents the connection mode of windings on LV side, ―12‖ represents
connection group between HV and LV windings. The following four settings are similar to this one.
11 No.11-- [Dd12_Conn_ET]
12 No.12-- [Dy11_Conn_ET]
13 No.13-- [Yd11_Conn_ET]
14 No.14-- [Dy1_Conn_ET]
All settings of generator system parameters are accessible in the following path:
Main Menu -> SETTING -> SYSTEM SETTINGS -> EXC SYS Settings -> [setting symbol]
Note:
Setting marked with ―#‖ means that it is can not be seen on LCD or by printing, but only can be
seen through RCSPC software.
1 No.1-- [Opt_Polar_CT](#)
This is the logic setting of CT polarity definition, which consists of sixteen binary digits. Every digit
has specified meaning and some digits have no definition.
Generally, CT polarity definition is as Figure 1.1-1 show. However if some CT polarity direction is
reversed by incorrect wiring connection, there is still a chance to correct it by configuring this logic
setting easily. Please set the corresponding digit of the logic setting.
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Curr_Chann4(CT_Term_Gen)
Curr_Chann6(SpareCT_Gen)
Curr_Chann3(SpareCT1)
Curr_Chann2(CT2_Exc)
Curr_Chann1(CT1_Exc)
Curr_Chann5(CT_NP)
Bit Definition
0 CTs polarity of current channel 1 (CT1_Exc) reversed
1 CTs polarity of current channel 2 (CT2_Exc) reversed
2 CTs polarity of current channel 3 (SpareCT1) reversed
3 CTs polarity of current channel 4 (CT_Term_Gen) reversed
4 CTs polarity of current channel 5 (CT_NP) reversed
Logic setting of selecting three-phase current channel for backup protection of generator.
Logic setting of selecting three-phase current channel for reverse-power protection of generator.
Logic setting of selecting measuring CT for reverse-power protection of generator. If the external
CT is measuring class, then the setting is remanded to set as ―Yes‖. Otherwise if the external CT is
protection class, then the setting is set as ‖No‖.
5 No.5-- [Opt_Gen_V0_by_Calc](#)
Logic setting of enabling zero sequence voltage is calculated from the terminal TV of generator.
Settings [Opt_SLD_1] as ―1‖ means the scheme type consists of only the generator.
Settings [Opt_SLD_2] as ―1‖ means the scheme type consists of generator and excitation
transformer.
Note:
7 No.9--[Opt_WaveRec_MON] (#)
8 No.10--[Opt_Debug_MON] (#)
This logic setting is provided especially for software developing, not for ordinary users.
9 No.11--[Opt_Dur_WaveRec_MON] (#)
10 No.12--[En_Displ_Pickup] (#)
This logic setting is provided especially for software developing, not for ordinary users.
Note:
Note:
Symbol of the parameters listed in above table are used for communication, printing and
displaying on LCD.
1 No.1-- [I_Pkp_PcntDiff_Gen]
This is a pickup setting of percentage current differential protection, which is also the setting of
fault detector of percentage differential protection. It shall be higher than the maximum
unbalanced current when the generator is operating on normal rated load, i.e.
Where:
I f 1n
I f 2n
n fLH
Where:
Pn / cos
I f 1n
3U f 1n
Where:
I unb.0 is the measured actual unbalance current during rated load of generator, 0.2 I f 2 n -0.3
Where:
2 No.2-- [I_InstDiff_Gen]
3 No.3-- [Slope1_PcntDiff_Gen]
K bl1 K rel K cc K er
(Equation 7.3-2)
Where:
K cc
is the type factor of CT, 0.5 in general;
K er
is error factor of CT ratio, no more than 0.1.
K bl1
represents [Slope1_PcntDiff_Gen] which is set as 0.05~0.1 in general.
4 No.4-- [Slope2_PcntDiff_Gen]
With type factor of CT not taken into account, the maximum unbalance current is, ,
Where:
K ap
is non periodic component factor, usually no less than 2.0;
K er
is error factor of CT ratio, no more than 0.1;
I k . max
is periodic component of secondary value of external three phase short circuit current and it
can be taken as 4 times of rated current if it is less than 4 times of rated current.
where:
If the percentage differential protection is configured based on rules mentioned above, then when
the phase-to-phase metallic short circuit fault occurs at the terminal of generator, sensitivity factor
K sen
will meet requirement ≥ 2 surely.
5 No.5-- [TrpLog_Diff_Gen]
Tripping output logic setting of differential protection is used to specify which breaker or breakers
will be tripped by this protection. This word comprises of 16 binary bits as follows and is displayed
as a hexadecimal number of 4 digits from 0000H to FFFFH on LCD of equipment. The tripping
output logic setting is specified as follows:
bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Protection Enabled
TJ12: TrpOutp 12
TJ11: TrpOutp 11
TJ10: TrpOutp 10
TJ9: TrpOutp 9
TJ8: TrpOutp 8
TJ7: TrpOutp 7
TJ6: TrpOutp 6
TJ5: TrpOutp 5
TJ4: TrpOutp 4
TJ3: TrpOutp 3
TJ2: TrpOutp 2
TJ1: TrpOutp 1
No definition
No definition
No definition
Function
Note:
Set bit 0 as ―1‖ means this protection element will trip breaker or breakers when operating. The bit
corresponding to the output channal shall be set as―1‖ and other bits shall be ―0‖. For example, if
differential protection is defined to trip output channel 5, the bit ―0‖ and ―5‖ bit shall be set as ―1‖
and other bits ―0‖. Then a hexadecimal number 0021H is formed as the tripping output logic
setting.
Please note that tripping output logic settings of the equipment have to be set on the basis of
application-specific drawings.
All the tripping logic settings mentioned below is defined as same as this one.
6 No.6-- [En_InstDiff_Gen]
Unrestrained instantaneous differential protection enabled. If this setting is set as ―1‖, it means this
protection is enabled. Otherwise it means the protection is disabled.
7 No.7-- [En_PcntDiff_Gen]
8 No.8-- [En_DPFC_Diff_Gen]
9 No.9-- [Opt_CTS_Blk_PcntDiff_Gen]
If this logic setting is set as ―1‖, it means percentage differential protection will be blocked when CT
circuit failure take place. Otherwise it means the blocking function is disabled.
All settings of differential protection settings are accessible in the following path:
Main Menu -> SETTINGS -> PROT SETTINGS -> GEN DIFF PROT --> [setting symbol]
1 No.1-- [I_Pkp_PcntSPTDiff_Gen]
This is pickup setting of splitting-phase transverse percentage current differential protection, which
is also the setting of fault detector of this protection. It shall be higher than maximum unbalance
current when the generator operates on normal rated load, i.e.
Where:
I ' unb.1 : is unbalance current due to amplitude error between the CTs used in this protection in
current of CT.
I ' unb.2 : the second type unbalance current. Because each shunt branch of every phase is
distributed in different grooves on the surface of rotor for hydro generator and the air gap field of
each groove is different, therefore this second type of unbalance current appears.
User can also get the maximum unbalance current value by metering the real transverse
unbalance current in full load condition of the generator. Generally speaking, the value is a little
greater than the one of differential protection of generator.
2 No.2-- [I_InstSPTDiff_Gen]
3 No.3-- [Slope1_PcntSPTDiff_Gen]
4 No.4-- [Slope2_PcntSPTDiff_Gen]
5 No.5-- [TrpLog_SPTDiff_Gen]
6 No.6-- [En_InstSPTDiff_Gen]
7 No.7-- [En_PcntSPTDiff_Gen]
8 No.8-- [Opt_CTS_PcntSPTDiff_Gen]
If this logic setting is set as ―1‖, it means percentage splitting-phase transverse differential
protection will be blocked when CT circuit failure happens. Otherwise it means the function is
disabled.
Setting path
Settings of generator phase-splitting transverse protection are accessible in the following path:
Main Menu -> SETTINGS -> PROT SETTINGS -> GEN SPTDIFF PROT->[setting symbol]
1 NO.1—[I_SensTrvDiff_Gen]
Setting of this protection shall be higher than the maximum unbalanced current during normal
operating condition. Reliability factor can be more than 2. The setting value is usually:
I op 0.05 I f ln / n a
(Equation 7.3-6)
Where:
I f ln
is primary rated current of generator and
na
is ratio of zero sequence CT of transverse differential protection.
2 NO.2—[I_InsensTrvDiff_Gen]
I op (0.20 ~ 0.30)I f ln / n a
(Equation 7.3-7)
Where:
I f ln
is primary rated current of generator and
na
is ratio of zero sequence CT of transverse differential protection.
3 NO.3—[t_TrvDiff_Gen]
Delay of transverse differential protection (act on only after the occurrence of one-point ground of
rotor).
When one point earth fault occurs within rotor of generator and one point earth fault protection
operates, in order to prevent unwanted operation of transverse protection due to instantaneous
two points earth fault within the rotor, operation of this protection shall be delayed for 0.5 s – 1 s.
Note:
When a turn-to-turn fault occurs, the equipment will trip relevant breakers without delay according
to the tripping output logic setting, but a time delay decided by user will be activated after the
occurrence of one-point ground of rotor.
4 NO.4—[V_SensROV_Longl_Gen]
Setting of this protection shall be higher than maximum unbalance voltage during normal
operation condition, usually:
U op 0.5 - 3 V
(Equation 7.3-8)
At beginning of configuration, 2 – 3 V is preferred. After fault waveform analysis, the setting can be
reduced properly and sensitivity of the protection can be improved than.
5 NO.5—[V_InsensROV_Longl_Gen]
Setting of this protection shall be higher than maximum unbalance voltage during external fault,
usually:
U op 8 - 12 V
(Equation 7.3-9)
6 NO.6—[t_ROV_Longl_Gen]
Delay of longitudinal zero sequence overvoltage. Short delay 0.10 s – 0.20 s is recommended for
operation and output of this protection.
7 NO.7—[TrpLog_IntTurn_Gen]
8 NO.8—[En_SensTrvDiff_Gen]
9 NO.9—[En_InsensTrvDiff_Gen]
10 NO.10—[En_SensROV_Longl_Gen]
11 NO.11—[En_InsensROV_Longl_Gen]
12 NO.12—[En_DPFC_IntTurn_Gen]
Main Menu -> SETTINGS -> PROT SETTINGS -> GEN INTTURN PROT --> [setting symbol].
1 No.1-- [V_NegOV_VCE_Gen]
Negative sequence voltage setting of composite voltage control element. Setting and displayed
value of negative sequence voltage are U2.
Setting of negative sequence voltage relay shall be higher than unbalance voltage during normal
operation, generally
Sensitivity factor shall be checked by phase-to-phase short circuit fault on HV side bus of main
transformer:
U 2. min
K sen
U op2
(Equation 7.3-11)
Where:
U 2. min is minimum negative sequence voltage at location of the equipment during phase-to-phase
short circuit fault on HV side bus of main transformer. K sen ≥ 1.5 is required.
2 NO.2—[Vpp_UV_VCE_Gen]
U gn
Where is rated phase-to-phase voltage of generator.
Sensitivity factor shall be checked by three-phase short circuit fault on HV side bus of main
transformer:
U op
K sen
X t I k(3. max
)
(Equation 7.3-12)
I k( 3. max
)
Where is maximum secondary fault current during three-phase short circuit on HV side bus
Xt X t Zt K sen
of main transformer; is reactance of main transformer, . ≥ 1.2 is required.
3 NO.3—[I_OC1_Gen]
K rel
I op I gn
Kr
(Equation 7.3-13)
Where:
K rel
is reliability factor, 1.3 – 1.5;
I gn
is secondary rated current of generator.
I k( 2. min
)
K sen
I op
(Equation 7.3-14)
I k( 2. min
)
Where is minimum fault current through location of the relay during phase-to-phase
K sen
metallic short circuit on HV side of main transformer. ≥ 1.2 is required.
4 NO.4—[t_OC1_Gen]
Time delay of overcurrent protection stage 1. Delay of this protection shall be higher than that of
operation of backup protection of step-up transformer. This protection is used for islanding and
generator shut off.
5 NO.5—[TrpLog_OC1_Gen]
6 NO.6—[I_OC2_Gen]
Setting of overcurrent protection stage 2. Setting of overcurrent relay shall be higher than rated
current of transformer.
7 NO.7—[t_OC2_Gen]
8 NO.8—[TrpLog_OC2_Gen]
9 NO.9—[Z1_Fwd_Gen]
Positive direction impedance setting of distance protection stage1. Here positive direction means
the direction is pointing to the transformer instead of generator itself.
If the value of this setting is greater than the next one, then the characteristic of distance protection
is set as excursive impedance circle; if it is equal to the next one, the characteristic is a whole
impedance circle; if the next one is set as ―0‖, the characteristic becomes directional impedance.
Generally, low impedance protection is considered as the backup protection of generator in case
that voltage-controlled overcurrent protection can‘t satisfy the sensitivity requirement of the
generator.
10 NO.10—[Z1_Rev_Gen]
Negative direction impedance setting of distance protection stage1. In general, this setting is set
as 5-10% of the positive direction impedance setting.
11 NO.11—[t_Z1_Gen]
12 NO.12—[TrpLog_Z1_Gen]
13 NO.13—[Z2_Fwd_Gen]
14 NO.14—[Z2_Rev_Gen]
15 NO.15—[t_Z2_Gen]
16 NO.16—[TrpLog_Z2_Gen]
Tripping output logic setting of distance protection stage1. Please refer to the tripping output logic
setting of differential protection of main transformer for details.
17 NO.17—[I_BO_OC_Gen]
18 NO.18—[En_VCE_Ctrl_OC1_Gen]
19 NO.19—[En_VCE_Ctrl_OC2_Gen]
20 NO.20—[Opt_VTS_Ctrl_OC_Gen]
―1‖: when VT circuit failure at one side is detected, composite voltage element will be disabled if
corresponding logic setting is set as ―1‖.
―0‖: when VT circuit failure at one side is detected, the voltage-controlled overcurrent element will
become a pure overcurrent relay without composite voltage element controlling.
21 NO.21—[Opt_ExcMode_Gen]
That the setting is set as ―1‖ indicates the excitation mode of generator is self shunt excitation
mode. In that case, the protection will remember the current value at the initiation of fault, and
operates based on it, no matter whether the current will decrease due to the descending excitation
voltage result from terminal voltage‘s getting down when external fault occurs. Once this setting is
set as ―1‖, the backup overcurrent protection of generator is always controlled by composite
voltage element.
22 NO.22—[En_BO_OC_Gen]
Note:
In the above Table,current used in backup protection of generator comes from the backup current
input channel.
Settings of generator phase-to-phase backup protection are accessible in the following path:
Main Menu -> SETTINGS -> PROT SETTINGS -> GEN INTTURN PROT --> [setting symbol].
1 No.1-- [V_SensROV_Sta]
U op U unb. max
Setting of this protection shall be higher than maximum unbalance voltage of single
phase VT at neutral point during normal operation.
To assure its security, user should check the transferred zero sequence voltage through coupling
capacitance between HV side and LV side of transformer when external earth fault occurs on the
HV side of the transformer. Meanwhile, settings, including time delay and operation setting, should
be considered to cooperate with that of earth fault protection of the system.
Note:
The zero sequence voltage used in this protection comes from VT at the neutral point of generator.
2 NO.2—[V_InsensROV_Sta]
Only zero sequence voltage at neutral point is taken for the high setting zone of fundamental zero
sequence voltage protection. Its setting is usually 20 V – 25 V.
Zero sequence voltage transferred by coupling capacitance per phase between HV and LV side
windings of step-up transformer shall be checked when external fault occurs at HV side of the
transformer. Coordinating both on setting and delay between this protection and system earth fault
protection could be achieved then.
3 NO.3—[t_ROV_Sta]
4 NO.4—[k_V3rdHRatio_PreSync_Sta]
Let third harmonic voltage at the end and neutral point of generator be U t and U n , ratio setting of
third harmonic voltage percentage earth fault protection shall be
Ut Un
(Equation 7.3-16)
3 nTVN
and K rel during pre-configuration,
nTV 0
Where:
K rel
is reliability factor, 1.3 – 1.5 in general;
nTV 0
is ratio of open-delta zero sequence voltage at the terminal of generator;
n TVN
is ratio of zero sequence VT on neutral point.
U 3T / U 3N
During incorporation of generator to power system, the ratio changes considerably
owing to variation of equivalent capacitive reactance at generator terminal. So two different
settings are designed for protection before and after connection of generator with system, and
these two settings can be switched over with alternation of contacts‘ position of the terminal
breaker.
The setting shall be (1.3 – 1.5)× 1 before incorporation and (1.3 – 1.5)× 2 after that.
Where 1 and 2 are the maximum real-measured third harmonic voltage ratio before and
5 NO.5—[k_V3rdHRatio_PostSync_Sta]
6 NO.6—[k_V3rdH_Diff_Sta]
U t k p U n k zd U n
(Equation 7.3-17)
Where:
kp
is vectorial automatic tracing regulation factor;
k zd
is restraint factor [3rdHarm Diff. Ratio], 0.3 is recommended.
7 NO.7—[t_V3rdH_Sta]
Delay of percentage third harmonic voltage earth fault protection. It shall be longer than that of
backup protection against external fault .
8 NO.8—[TrpLog_EF_Sta]
9 NO.9—[En_Alm_ROV_Sta]
10 NO.10—[En_Trp_ROV_Sta]
11 NO.11—[En_Alm_V3rdHRatio_Sta]
12 NO.12—[En_Alm_V3rdHDiff_Sta]
13 NO.13—[En_Trp_V3rdHRatio_Sta]
14 NO.14—[En_Trp_InsensRov_Sta]
Settings of stator earth fault protection are accessible in the following path:
Main Menu -> SETTINGS -> PROT SETTINGS -> STA EF PROT --> [setting symbol].
1 NO.1—[R_Sens1PEF_RotWdg]
General specification of generator specifies that insulation resistance of its excitation winding shall
be higher than 1 MΩ for air cooled and hydrogen-cooled turbine generator during cooling state,
and 2 kΩ for water cooled excitation winding. General specification of hydro-generator specifies
that insulation resistance of its excitation winding shall be higher than 0.5 kΩ in any case.
Sensitive stage of this protection is used for alarm. Its setting could be 20 kΩ – 80 kΩ generally.
2 NO.2—[R_1PEF_RotWdg]
Setting of one point earth fault protection can be 20 kΩ for air cooled and hydrogen-cooled turbine
generator and 2.5 kΩ for water cooled excitation winding. This protection can be used for alarm or
generator shutting with delay.
3 NO.3—[t_1PEF_RotWdg]
4 NO.4--[V2ndH_VCE_2PEF_RotWdg]
5 NO.5—[t_2PEF_RotWdg]
6 NO.6—[TrpLog_EF_RotWdg]
7 NO.7—[En_Alm_Sens_1PEF_RotWdg]
Enable alarm function of sensitive stage of one-point earth fault protection of rotor.
8 NO.8—[En_Alm_1PEF_RotWdg]
9 NO.9—[En_Trp_1PEF_RotWdg]
10 NO.10—[En_2PEF_RotWdg]
11 NO.11—[En_VCE_2PEF_RotWdg]
Settings of rotor earth fault protection are accessible in the following path:
Main Menu -> SETTINGS -> PROT SETTINGS -> ROTWDG EF PROT --> [setting symbol].
1 NO.1—[I_OvLd_Sta]
Setting of this protection is determined by the requirement of reliable release during permissive
continuous load current of generator.
I gn
I OP K rel
Kr (Equation 7.3-18)
Where:
K rel
is reliability factor, 1.05 generally;
I gn
is secondary rated current of generator.
Delay of this protection shall be longer than maximum delay of backup protection. Alarm will be
issued or load will be reduced when it operates.
2 NO.2—[t_OvLd_Sta]
3 NO.3—[TrpLog_OvLd_Sta]
4 NO.4-- [I_Alm_OvLd_Sta]
5 NO.5—[t_Alm_OvLd_Sta]
6 NO.6—[I_InvOvLd_Sta]
Characteristic of this protection is indefinite time relationship between multiple of load current and
corresponding permissive duration which is determined by permissive overload capability of stator
provided by the factory.
K tc
t
I *2 K sr2 (Equation 7.3-19)
Where:
K tc
is heat capacity factor of stator winding;
K sr
is heat dissipation factor, 1.0 – 1.05 generally.
Minimum delay for upper limit of this protection shall coordinate with the unrestraint protection.
Current setting of lower limit of this protection will coordinate with definite time overload protection
mentioned above, namely
I gn
I OP. min K c 0 K rel
Kr (Equation 7.3-20)
KC 0
Where: is coordination factor, 1.05 in general.
7 NO.7—[tmin_InvOvLd_Sta]
8 NO.8—[A_Therm_Sta]
9 NO.9—[K_Disspt_Sta]
10 NO.10—[TrpLog_InvOvLd_Sta]
Main Menu -> SETTINGS -> PROT SETTINGS -> STA OVLD PROT --> [setting symbol].
1 NO.1—[I_NegOC1_Gen]
Setting of this protection is determined by the threshold under which this protection can release
reliably, that threshold value is continuously permissive negative sequence current I 2 . So,
I 2 I gn
I OP K rel
Kr (Equation 7.3-21)
Where:
K rel
is reliability factor, 1.05;
I gn
is secondary rated current of generator.
2 NO.2—[t_NegOC1_Gen]
Delay of this protection shall be longer than maximum delay of backup protection. Alarm will be
issued when it operates.
3 NO.3—[TrpLog_NegOC1_Gen]
Tripping output logic setting of stage 1 of definite time negative sequence overcurrent protection.
4 NO.4—[I_NegOC2_Gen]
Setting of stage 2 of definite time negative sequence overcurrent protection. The setting method
is as same as that of stage 1.
5 NO.5—[t_NegOC2_Gen]
Delay of this protection shall be longer than maximum delay of backup protection. This stage can
be used to trip breakers.
6 NO.6—[TrpLog_NegOC2_Gen]
Tripping output logic setting of stage 2 of definite time negative sequence overcurrent protection.
7 NO.7—[I_Alm_NegOC_Gen]
8 NO.8—[t_Alm_NegOC_Gen]
9 NO.9—[I_InvNegOC_Gen]
A
t
I 22* I 22 (Equation 7.3-22)
Where:
Minimum delay for upper limit of this protection shall coordinate with unrestraint protection.
10 NO.10—[I_Neg_Perm_Gen]
Permitted continuous currents of inverse time negative sequence overcurrent protection for lasting
operation.
Current setting of lower limit of this protection shall be the operating current corresponding to
delay 1000 s, namely
A
I OP. min I 22
1000 (Equation 7.3-23)
11 NO.11—[tmin_InvNegOC_Gen]
Delay of upper limit of inverse negative sequence overcurrent protection. Minimum delay for upper
limit of this protection shall coordinate with unrestraint protection.
12 NO.12—[A_Therm_RotBody]
13 NO.13—[TrpLog_InvNegOC_Gen]
Settings of stator negative sequence overcurrent protection are accessible in the following path:
Main Menu -> SETTINGS -> PROT SETTINGS -> GEN NEGOC PROT --> [setting symbol].
20 En_RotUV_LossExc2_Gen 0,1 1
21 En_Z_LossExc3_Gen 0,1 1
22 En_RotUV_LossExc3_Gen 0,1 1
23 En_Alm_LossExc1_Gen 0,1 1
24 Opt_Z_LossExc_Gen 0,1 1
25 En_RevQ_LossExc_Gen 0,1 1
26 Opt_UV_LossExc_Gen 0,1 0
1 NO.1—[X1_LossExc_Gen]
jx
Xc
R
Xa
Xb
Xa
For asynchronous impedance cycle, this setting represents for , and the next setting (NO.2) is
Xb
. Here
X d' U gn na
2
Xa
2 S gn nv
(Equation 7.3-24)
X d'
2
U gn na
X b ( X d )
2 S gn nv
(Equation 7.3-25)
Where:
'
X d and X d are unsaturated per unit value of transient reactance and synchronous reactance of
generator,
U gn S gn
and are rated voltage and rated apparent power of generator;
na nv
and are CT ratio and VT ratio.
XC
For steady state stability limit circle, this setting represents for , and the next setting (NO.2) is
Xb
, here
2
U gn na
Xc Xs
S gn nv
(Equation 7.3-26)
X' U gn na 2
X b ( X d d )
2 S gn nv
(Equation 7.3-27)
Where:
Xs
is equivalent reactance on system side (including step-up transformer) connected with the
generator (per unit value, reference capacity is apparent power of the generator).
Asynchronous impedance circle and steady state stability limit circle can be selected by logic
setting [Impedance Circle Option] (No. 24).
For practical projects, impedance between asynchronous impedance circle and steady state
stability limit circle can be selected for optimal combination of reliability and speed.
2 NO.2—[X2_LossExc_Gen]
3 NO.3—[Q_RevQ_LossExc_Gen]
Q jx
Q zd K rel
Pgn
(Equation 7.3-28)
Where:
K rel
is reliability factor, 1 - 1.3;
Q jx
is permissive incoming reactive power to the generator;
Pgn
is rated active power of the generator.
Reverse reactive power criterion can be selected by logic setting [Enable ReactPowRev Criterion]
(NO. 25).
4 NO.4—[V_RotUV_LossExc_Gen]
Low voltage setting of rotor. There are two low voltages setting of rotor, they are
U fd .op K rel U fd 0
(Equation 7.3-29)
Where:
U fd .op
is this setting.
K rel
is reliability factor, 0.20 – 0.50;
U fd 0
is rated excitation voltage of the generator without load, i.e. NO.5 setting.
U fd 0
For a generator connecting with power system, there is a necessary excitation voltage for
keeping steady state stability.
P Pt
U fd.op K xs U fd 0
Sn (Equation 7.3-30)
Where:
K xs
is rotor voltage criterion coefficient, i.e. NO. 6 setting.
K rel
is reliability factor, 0.70 – 0.85;
Xd Xs
and are per unit value of synchronous reactance of generator and equivalent reactance of
system connecting with the generator (referred to rated capacity of the generator);
U fd 0
is rated excitation voltage of generator without load;
5 NO.5—[V_RotNoLoad_LossExc_Gen]
6 NO.6—[k_RotUV_LossExc_Gen]
7 NO.7—[V_UV_LossExc_Gen]
This criterion is used mainly to prevent voltage collapse due to loss of excitation of generator for a
system without enough spare reactive power. Voltage on bus of system side is adopted for this
criterion.
Where:
K rel
is reliability factor, 0.85 – 0.90;
U h. min
is minimum normal operation voltage of HV side of the system.
This criterion can also be configured as 0.85 – 0.90 times of terminal voltage of generator.
8 NO.8—[P_OvPwr_LossExc_Gen]
Power setting for reducing power output. This criterion is configured as 40% - 50% of rated
capacity of the generator.
9 NO.9—[t_LossExc1_Gen]
10 NO.10—[t_LossExc2_Gen]
11 NO.11—[t_LossExc3_Gen]
12 NO.12—[TrpLog_LossExc1_Gen]
13 NO.13—[TrpLog_LossExc2_Gen]
14 NO.14—[TrpLog_LossExc3_Gen]
15 NO.15—[En_Z_LossExc1_Gen]
16 NO.16—[En_RotUV_LossExc1_Gen]
17 NO.17—[En_P_LossExc1_Gen]
18 NO.18—[En_UV_LossExc2_Gen]
Enable the low voltage criterion of busbar or generator terminal in loss-of-excitation protection
stage2
19 NO.19—[En_Z_LossExc2_Gen]
20 NO.20—[En_RotUV_LossExc2_Gen]
21 NO.21—[En_Z_LossExc3_Gen]
22 NO.22—[En_RotUV_LossExc3_Gen]
23 NO.23—[En_Alm_LossExc1_Gen]
24 NO.24—[Opt_Z_LossExc_Gen]
25 NO.25—[En_RevQ_LossExc_Gen]
26 NO.26—[Opt_UV_LossExc_Gen]
Note:
Main Menu -> SETTINGS -> PROT SETTINGS -> GEN LOSSEXC PROT --> [setting symbol].
Out-of-step protection operates only when out-of-step occurs in the power system. Then, based
on the situation at that time, the dispatching center will adopt islanding, generator shutting,
restraint or any other necessary measures. Only if the center of oscillation is situated within the
generator or near the generator, or the oscillation lasts too long, and the phase difference of
electro-motive force between the two sides of the breaker is less than 90°, this protection will then
trip.
Characteristic of this protection comprises three parts: lens part ②, boundary part ① and
reactance line part ③. See the following figure.
jx
Za
U
D
Zc 3
OL
IL
1 IR
OR
0
R
1
Zb
2
L R
1 NO.1—[Za_OOS_Gen]
Refer to Figure 7.3-2, this setting can be set by means of the following formula.
2
U gn na
Za ( X S X C )
S gn nv (Equation 7.3-33)
Where:
U gn S gn
and are rated voltage and rated apparent power of generator;
na nv
and are CT ratio and VT ratio.
2 NO.2—[Zb_OOS_Gen]
Refer to figure 7.3.2, this setting can be set by means of the following formula.
2
U gn na
Zb X '
S gn nv
d
(Equation 7.3-34)
Where:
3 NO.3—[Zc_OOS_Gen]
Impedance setting C of out-of-step protection. Reactance line is the dividing line of oscillation
center. Refer to Figure 7.3-2, this setting can be set by means of the following formula. In practice,
0.9 times of transformer impedance is recommended.
2
U gn na
Z c 0.9 X c
S gn nv
(Equation 7.3-35)
4 NO.4—[φ_Reach_OOS_Gen]
5 NO.5—[φ_Inner_OOS_Gen]
2Z r
180 2 arctan
Z a Zb
1
Zr RL. min
1.3 (Equation 7.3-36)
RL. min
Where is minimum load impedance of generator.
6 NO.6—[n_Slip_Ext_OOS_Gen]
Pole sliding number setting for external fault of generator. When the oscillation center is situated
outside the protected section, then the times of pole sliding shall be set as 2 – 15 for alarm and
more than 15 for tripping.
7 NO.7—[n_Slip_Int_OOS_Gen]
Pole sliding number setting for internal fault of generator. When the oscillation center is situated
within the protected section, the time of pole sliding shall be set as 1-2 in general.
8 NO.8—[Ibrk_GCB]
9 NO.9—[TrpLog_OOS_Gen]
10 NO.10—[En_Alm_Ext_OOS_Gen]
11 NO.11—[En_Trp_Ext_OOS_Gen]
12 NO.12—[En_Alm_Int_OOS_Gen]
13 NO.13—[En_Trp_Int_OOS_Gen]
Main Menu -> SETTINGS -> PROT SETTINGS -> GEN OOS PROT --> [setting symbol].
1 NO.1—[V_OV1_Gen]
Setting of overvoltage protection of stator shall base on permissive overvoltage capability provided
U op 1.3U gn
(Equation 7.3-37)
Where:
U gn
is the secondary rated phase-to-phase voltage.
This is used for islanding and excitation shutting with delay 0.5 s.
For hydro-generator,
U op 1.5U gn
(Equation 7.3-38)
This is used for islanding and excitation shutting with delay 0.5 s.
U op 1.3U gn
(Equation 7.3-39)
This is used for islanding and excitation shutting with delay 0.3 s.
2 NO.2—[t_OV1_Gen]
3 NO.3—[TrpLog_OV1_Gen]
4 NO.4—[V_OV2_Gen]
5 NO.5—[t_OV2_Gen]
6 NO.6—[TrpLog_OV2_Gen]
7 NO.7—[V_UV_Gen]
8 NO.8—[t_UV_Gen]
9 NO.9—[TrpLog_UV_Gen]
Main Menu -> SETTINGS -> PROT SETTINGS -> GEN VOLT PROT --> [setting symbol].
1 NO.1—[k_OvExc1_Gen]
U
B U gn
N U / f 1.3 or data provided by the factory
Bn f
f gn
2 NO.2—[t_OvExc1_Gen]
3 NO.3—[TrpLog_OvExc1_Gen]
Tripping output logic setting of stage 1 of definite time over excitation protection. The function of
this protection is used for islanding, excitation shutting or programming, excitation reducing etc.
4 NO.4—[k_OvExc2_Gen]
5 NO.5—[t_OvExc2_Gen]
6 NO.6—[TrpLog_OvExc2_Gen]
Tripping output logic setting of stage 2 of definite time over excitation protection.
7 NO.7—[k_Alm_OvExc_Gen]
Setting of over excitation alarm. Setting of alarm shall be lower than that of over excitation
protection. 1.1 is recommended.
8 NO.8—[t_Alm_OvExc_Gen]
9 NO.9—[k0_InvOvExc_Gen]
10 NO.10—[t0_InvOvExc_Gen]
11 NO.11—[k1_InvOvExc_Gen]
Inverse time over excitation factor1—n1. Setting range of various inverse times over excitation
coefficient is 1.0 – 2.0. However setting of upper limit (NO.9) of over excitation factor n0 shall be
higher than that of over excitation factor1 n1, which of factor1 n1 shall be higher than that of
factor2 n2, etc. Finally, setting of over excitation factor6 n6 (NO.21) shall be higher than that of the
lower limit.
12 NO.12—[t1_InvOvExc_Gen]
The range of delay of various inverse time over excitation protection stage is 1s to 3000s, ie.,0--50
min. Delay of upper limit (NO.10) of over excitation factor shall be shorter than that of over
excitation factor1 that the factor1 shall be shorter than that of factor2, etc.. Finally, delay of over
excitation factor6 (NO.22) shall be shorter than that of lower limit (NO.24).
13 NO.13—[k2_InvOvExc_Gen]
14 NO.14—[t2_InvOvExc_Gen]
15 NO.15—[k3_InvOvExc_Gen]
16 NO.16—[t3_InvOvExc_Gen]
17 NO.17—[k4_InvOvExc_Gen]
18 NO.18—[t4_InvOvExc_Gen]
19 NO.19—[k5_InvOvExc_Gen]
20 NO.20—[t5_InvOvExc_Gen]
21 NO.21—[k6_InvOvExc_Gen]
22 NO.22—[t6_InvOvExc_Gen]
23 NO.23—[k7_InvOvExc_Gen]
24 NO.24—[t7_InvOvExc_Gen]
25 NO.25—[TrpLog_InvOvExc_Gen]
Main Menu -> SETTINGS -> PROT SETTINGS -> GEN OVEXC PROT --> [setting symbol]
1 NO.1—[P_RevP_Gen]
Pop K rel ( P1 P2 )
(Equation 7.3-40)
Where:
K rel
is reliability coefficient, 0.5 – 0.8 generally;
P1 is minimum loss of turbine during reverse power operation, 2% - 4% of rated power generally;
Pgn
is rated power of generator.
Pop
is set as 1% - 2% of rated active power generally, and 1% is recommended.
2 NO.2—[t_Alm_RevP_Gen]
Delay of reverse power alarm. For reverse power protection without steam valve contact blocking,
delay 15 s for alarm.
3 NO.3—[t_Trp_RevP_Gen]
Delay of reverse power protection. For reverse power protection without steam valve contact
blocking, according to permissive operation time of reverse power, delay 1 min – 3 min is set for
islanding in general.
For program reverse power protection with steam valve contact blocking, delay 0.5 s – 1.00 s is
set for islanding.
4 NO.4—[TrpLog_RevP_Gen]
5 NO.5—[P_SeqTrpRevP_Gen]
6 NO.6—[t_SeqTrpRevP_Gen]
For sequent-tripping reverse power protection with steam valve contact blocking, delay 0.5 s –
1.00 s for islanding.
7 NO.7—[TrpLog_SeqTrpRevP_Gen]
Main Menu -> SETTINGS -> PROT SETTINGS -> GEN PWR PROT --> [setting symbol].
1 NO.1—[f_UF1_Gen]
Permissive range of frequency during operation for large turbo-generator with capacity more than
300 MW is 48.5 Hz – 50.5 Hz.
Recommended permissive operation time of abnormal frequency for large generator is as follows.
Three stages of under frequency protection are provided in which the function of accumulated
operating time is equipped for stage 1(NO.2 setting).
Two zones of over frequency protection are provided, in which no function of accumulated
operating time is equipped.
Each zone can be used for alarm or tripping by configuration of logic setting.
2 NO.2—[t_UF1_Gen]
3 NO.3—[f_UF2_Gen]
4 NO.4-- [t_UF2_Gen]
5 NO.5—[f_UF3_Gen]
6 NO.6—[t_UF3_Gen]
7 NO.7—[TrpLog_UF_Gen]
8 NO.8—[f_OF1_Gen]
9 NO.9—[t_OF1_Gen]
10 NO.10—[f_OF2_Gen]
11 NO.11—[t_OF2_Gen]
12 NO.12—[TrpLog_OF_Gen]
13 NO.13—[En_Alm_UF1_Gen]
14 NO.14—[En_Trp_UF1_Gen]
15 NO.15—[En_Alm_UF2_Gen]
16 NO.16—[En_Trp_UF2_Gen]
17 NO.17—[En_Alm_UF3_Gen]
18 NO.18—[En_Trp_UF3_Gen]
19 NO.19—[En_Alm_OF1_Gen]
20 NO.20—[En_Trp_OF1_Gen]
21 NO.21—[En_Alm_OF2_Gen]
22 NO.22—[En_Trp_OF2_Gen]
Main Menu -> SETTINGS -> PROT SETTINGS -> GEN FREQ PROT --> [setting symbol].
1 NO.1—[f_UF_Ctrl_StShut_Gen]
Startup and shutdown protection is used for earth fault and phase-to-phase fault of stator during
low speed operation of the generator. Its algorithm is insensitive to variation of frequency.
This protection is auxiliary protection of generator during low frequency operation. Blocking setting
of this protection is 0.8 – 0.9 times of rated frequency.
2 NO.2—[I_GenDiff_StShut_Gen]
Differential current setting for the differential protection of generator in startup and shutdown
condition. Setting of this protection shall be higher than unbalanced differential current in full load
and rated frequency condition,
I op K rel I unb
(Equation 7.3-41)
Where:
K rel
is reliability factor, 1.30 – 1.50 generally;
I unb
is the unbalance differential current in full load and rated frequency condition.
3 NO.3—[TrpLog_Diff_StShut_Gen]
Tripping output logic setting of low frequency differential protection of generator in startup and
shutdown condition.
4 NO.4—[I_UFOC_StShut_Gen]
5 NO.5—[t_UFOC_StShut_Gen]
Current setting of low frequency overcurrent protection in startup and shutdown condition.
6 NO.6—[TrpLog_Diff_StShut_Gen]
7 NO.7—[V_StaROV_StShut_Gen]
Zero sequence voltage setting of stator earth fault protection in startup and shutdown condition.
For earth fault, zero sequence voltage derived from neutral point is adopted as criterion with
setting 10 V in general and delay not shorter than that of fundamental zero sequence voltage earth
fault protection for stator in normal condition.
8 NO.8—[t_StaROV_StShut_Gen]
9 NO.9—[t_StaROV_StShut_Gen]
Tripping output logic setting of stator earth fault protection in startup and shutdown condition.
10 NO.10—[En_GenDiff_StShut_Gen]
11 NO.11—[En_UFOC_StShut_Gen]
12 NO.12—[En_ROV_StShut_Gen]
13 NO.13—[En_UF_Ctrl_StShut_Gen]
Enable low frequency element as blocking criterion in startup&shutup protection logic of generator.
Settings of generator startup and shutdown protection are accessible in the following path:
Main Menu -> SETTINGS -> PROT SETTINGS -> GEN STSHUT PROT --> [setting symbol].
1 NO.1—[f_UF_AccEnerg_Gen]
Frequency blocking setting shall be 80% - 90% of the rated frequency, i.e., 40 Hz – 45 Hz.
2 NO.2—[I_OC_AccEnerg_Gen]
Current setting shall be 50% of minimum accidental closing current (generator terminal side)
during process of generator starting up but having not been excited. If accidental closing current of
circuit breaker on auxiliary transformer side shall be taken into account, current setting shall base
on minimum accidental closing current during this condition. The current used for this setting is
derived from the CT at the terminal of generator.
In general, this setting shall be in excess of 1.3 times of the rated current of generator.
3 NO.3—[t_AccEnerg_Gen]
4 NO.4—[TrpLog_AccEnerg_Gen]
5 NO.5—[I_NegOC_Flash_GCB]
This setting shall be higher than the possible unbalanced current during normal operation. It must
be set according to the secondary current of the CT at the terminal of the generator.
6 NO.6—[t_Flash11_GCB]
7 NO.7—[TrpLog_Flash11_GCB]
If impulse current may be higher than capacity of circuit breaker during asynchronous closing, the
protection shall shut off the excitation firstly. If current passing through circuit breaker is lower than
permissive value, the protection can trip the circuit breaker on outlet.
Permissive tripping current of circuit breaker shall be configured as that provided by factory.
8 NO.8—[t_Flash12_GCB]
9 NO.9—[TrpLog_Flash12_GCB]
10 NO.10—[En_UF_Ctrl_AccEnerg_Gen]
11 NO.11—[En_CB_Ctrl_AccEnerg_Gen]
Settings of generator accidental energization protection are accessible in the following path:
Main Menu -> SETTINGS -> PROT SETTINGS -> GEN ACCENERG PROT --> [setting
symbol].
1 NO.1—[I_Pkp_PcntDiff_Exc]
In practice, for excitation transformer, the characteristics of CT on two sides may differ significantly
and the unbalanced differential current may be larger than that of the main transformer. So for
pickup setting, 0.5 Ie is recommended.
2 NO.2—[I_InstDiff_Exc]
3 NO.3—[Slope1_PcntDiff_Exc]
4 NO.4—[Slope2_PcntDiff_Exc]
5 NO.5—[k_Harm_PcntDiff_Exc]
6 NO.6—[TrpLog_Diff_Exc]
7 NO.7—[En_InstDiff_Exc]
8 NO.8—[En_PcntDiff_Exc]
9 NO.9—[Opt_Inrush_Ident_Exc]
10 NO.10—[Opt_CTS_Blk_PcntDiff_Exc]
Main Menu -> SETTINGS -> PROT SETTINGS -> EXC DIFF PROT --> [setting symbol].
1 NO.1—[I_OC1_Exc]
2 NO.2—[t_OC1_Exc]
3 NO.3—[TrpLog_OC1_Exc]
4 NO.4—[I_OC2_Exc]
5 NO.5—[t_OC2_Exc]
6 NO.6—[TrpLog_OC2_Exc]
Main Menu -> SETTINGS -> GEN PROT SETTINGS -> EXC BAK PROT --> [setting symbol].
Note:
The current used in the overcurrent protection is derived from the CT at the HV side of excitation
transformer or the CT at the neutral point of exciter.
14 Opt_AC_Input_S2_RotWdg 0,1 0
1 NO.1—[I_OvLd_RotWdg]
Setting of overload protection of rotor winding. If the measured current is inputted by DC type, the
unit of the setting is ‗kA‘. Otherwise, ‗A‘ is the unit of AC type current.
2 NO.2—[t_OvLd_RotWdg]
3 NO.3—[TrpLog_OvLd_RotWdg]
4 NO.4—[I_Alm_OvLd_RotWdg]
5 NO.5—[t_Alm_OvLd_RotWdg]
6 NO.6—[I_InvOvLd_RotWdg]
7 NO.7—[tmin_InvOvLd_RotWdg]
8 NO.8—[A_Therm_RotWdg]
9 NO.9—[Ib_InvOvLd_RotWdg]
10 NO.10—[TrpLog_InvOvLd_RotWdg]
11 NO.11—[Opt_AC_Input_RotWdg]
Type selection configuration logic setting of current input. ―1‖ is AC current input for overload
protection of rotor winding.
12 NO.12—[Opt_DC_Input_RotWdg]
Type selection configuration logic setting of current input. ―1‖ is DC current input for overload
protection of rotor winding.
13 NO.13—[Opt_AC_Input_S1_RotWdg]
Type selection configuration logic setting of current input. ―1‖ is the AC current input for overload
14 NO.14—[Opt_AC_Input_S2_RotWdg]
Type selection configuration logic setting of current input. ―1‖ is the AC current input for overload
protection of rotor winding is derived from LV side of excitation transformer.
Main Menu -> SETTINGS -> PROT SETTINGS -> EXC OVLD PROT --> [setting symbol].
1 NO.1—[t_MechRly1]
2 NO.2—[TrpLog_MechRly1]
3 NO.3—[t_MechRly2]
4 NO.4—[TrpLog_MechRly2]
5 NO.5—[t_MechRly3]
6 NO.6—[TrpLog_MechRly3]
7 NO.7—[t_MechRly4]
8 NO.8—[TrpLog_MechRly4]
Main Menu -> SETTINGS -> PROT SETTINGS -> MECH RLY PROT --> [setting symbol].
1 NO.1—[I_BFP_GCB]
2 NO.2—[I_ROC_BFP_GCB]
3 NO.3—[I_NegOC_BFP_GCB]
4 NO.4—[t_BFP11_GCB]
5 NO.5—[TrpLog_BFP11_GCB]
6 NO.6—[t_BFP12_GCB]
7 NO.7—[TrpLog_BFP12_GCB]
8 NO.8—[En_ROC_BFP_GCB]
Logic setting of enabling zero sequence current to block breaker failure protection.
9 NO.9—[En_NegOC_BFP_GCB]
Logic setting of enabling negative sequence current to block breaker failure protection.
10 NO.10—[En_ExtTrpCtrlBFP_GCB]
Logic setting of enabling external tripping signal to be a blocking condition of breaker failure
protection.
11 NO.11—[En_CB_Ctrl_BFP_GCB]
Logic setting of enabling the open position of breaker to be a blocking condition of breaker failure
protection.
Main Menu -> SETTINGS -> GEN PROT SETTINGS -> GEN BFP PROT --> [setting symbol].
5 I1b_CT_S2_Exc 0-60000 A
Secondary rated current
NO. Signal Range Note
1 I2b_CT_Gen 0-600.00 A
2 I2b_CT_SP1_Gen 0-600.00 A
3 I2b_CT_SP2_Gen 0-600.00 A
4 I2b_CT_S1_Exc 0-600.00 A
5 I2b_CT_S2_Exc 0-600.00 A
Secondary rated voltage
NO. Signal Range Note
1 U2b_Term_Gen 0-600.00 A
2 U2b_DeltVT_Term_Gen 0-600.00 A
3 U2b_NP_Gen 0-600.00 A
4 k_RV_Gen 0-60.00
Diff Corr Coef
NO. Signal Range Note
1 k_Diff_Gen 0-60.000
2 k_SP1_Diff_Gen 0-60.000
3 k_SP2_Diff_Gen 0-60.000
4 k_S1_Diff_Exc 0-60.000
5 k_S2_Diff_Exc 0-60.000
1 No.1-- [I1b_CT_Gen]
2 No.2-- [I1b_CT_SP1_Gen]
Primary rated current of the first splitting branch at the neutral point of generator calculated by
RCS-985G according to parameters input.
3 No.3-- [I1b_CT_SP2_Gen]
Primary rated current of the second splitting branch at the neutral point of generator calculated by
RCS-985G according to parameters input.
4 No.4-- [I1b_CT_S1_Exc]
Primary rated current at HV side of excitation transformer or terminal side of exciter calculated by
RCS-985G according to parameters input.
5 No.5-- [I1b_CT_S2_Exc]
Primary rated current at LV side of excitation transformer or neutral point side of exciter calculated
by RCS-985G according to parameters input.
6 No.6-- [I2b_CT_Gen]
7 No.7-- [I2b_CT_SP1_Gen]
Secondary rated current of the first splitting branch at the neutral point of generator calculated by
RCS-985G according to parameters input.
8 No.8-- [I2b_CT_SP2_Gen]
Secondary rated current of the second splitting branch at the neutral point of generator calculated
by RCS-985G according to parameters input.
9 No.9-- [I2b_CT_S1_Exc]
Secondary rated current at HV side of excitation transformer or terminal side of exciter calculated
by RCS-985G according to parameters input.
10 No.10-- [I2b_CT_S2_Exc]
Secondary rated current at LV side of excitation transformer or neutral point side of exciter
calculated by RCS-985G according to parameters input.
11 No.11-- [U2b_Term_Gen]
12 No.12-- [U2b_DeltVT_Term_Gen]
Secondary rated zero sequence voltage derived from open-delta side of VT at the terminal of
generator calculated by RCS-985G according to parameters input.
13 No.13-- [U2b_NP_Gen]
Secondary rated zero sequence voltage derived from open-delta side of VT at the neutral point of
generator calculated by RCS-985G according to parameters input.
14 No.14-- [k_RV_Gen]
Balance coefficient of zero sequence voltage of generator. The setting is used to adjust zero
sequence of generator terminal to the same base as the one of neutral point.
15 No.15-- [k_Diff_Gen]
16 No.16-- [k_SP1_Diff_Gen]
Correction coefficient of current of the first splitting branch at the neutral point side of generator for
generator differential protection.
17 No.17-- [k_SP2_Diff_Gen]
Correction coefficient of current of the second splitting branch at the neutral point side of generator
for generator differential protection.
18 No.18-- [k_S1_Diff_Exc]
Correction coefficient of current of HV side of excitation transformer or terminal side of exciter for
excitation differential protection.
19 No.19-- [k_S2_Diff_Exc]
Correction coefficient of current of LV side of excitation transformer or neutral point side of exciter
for excitation differential protection.
Main Menu -> SETTINGS -> CALC SETTINGS -> PRI RATED CURR -> [setting symbol]
Main Menu -> SETTINGS -> CALC SETTINGS -> SEC RATED CURR -> [setting symbol]
Main Menu -> SETTINGS -> CALC SETTINGS -> SEC RATED VOLT -> [setting symbol]
Main Menu -> SETTINGS -> CALC SETTINGS -> DIFF CORR COEF -> [setting symbol]
This chapter describes human machine interface (HMI), menu tree and LCD display. At the same
time how to input settings using keypad is described in detail. Finally, this chapter introduces the
RCSPC software and wave analysis software.
RCS-985G
GENERATOR PROTECTION 5
HEALTHY
VT ALM
GRP
CT ALM
ALARM
ENT
3
ESC
1 TRIP
The front panel of the relay includes the following, as indicated in Figure 8.2-1:
2 The relay front panel features control pushbutton switches with LEDs that facilitate local
control. Factory default settings associate specific relay functions with these 9
direct-action pushbuttons and LEDs e.g.
3 A 9-key keypad comprising 4 arrow keys (◄,►,▲and ▼), an plus key (+), a minus key
(-), a escape key ( ESC) and a active group setting key (GRP)
4 A 9-pin female D-type front port for communication with a PC locally to the relay (up to
15m distance) via an EIA(RS)232 serial data connection, which providing internal signal
monitoring and high speed local downloading of software.
5 Name of protection
6 Name of manufacture
8.2.2 LCD
A 320*240 dots liquid crystal display (LCD) with LED backlight. The backlight can be switched on
automatically whenever the keypad is operated or operation or alarm issued. Backlight will be
turned off after a while.
The front panel menu has a default display under normal state after power-up. If there is no
keypad activity during the 5 minute timeout period, default display will return again and the LCD
backlight will turn off. To provide more information, the default display a typical single-line scheme
generator system and relevant quantities in operation condition, as shown below.
F: 0.00 Hz Frequency
P: +0.00 %
Power
NP current 0.00A Q: +0.00 %
NP voltage 0.00V Ur: 0.0 V Rotor voltage
Rg: .....k Earth resistance
Whenever there is an un-eliminated fault record in the relay, the default display will be replaced by
a fault report.
protection of rotor
25 Op_OvLd_RotWdg Operation of definitive time overload protection of rotor
winding
26 Op_InvOvLd_RotWdg Operation of inverse time overload protection of rotor
winding
27 Op_OC1_Gen Operation of stage 1 of overcurrent protection of generator
28 Op_OC2_Gen Operation of stage 2 of overcurrent protection of generator
29 Op_OV1_Gen Operation of stage 1 of overvoltage protection of generator
30 Op_OV2_Gen Operation of stage 2 of overvoltage protection of generator
31 Op_UV_Gen Operation of undervoltage protection of generator
32 Op_OvExc1_Gen Operation of stage 1 of overexcitation protection of
generator
33 Op_OvExc2_Gen Operation of stage 2 of overexcitation protection of
generator
34 Op_InvOvExc_Gen Operation of inverse time stage of overexcitation protection
of generator
35 Op_UF1_Gen Operation of stage 1 of underfrequency protection of
generator
36 Op_UF2_Gen Operation of stage 2 of underfrequency protection of
generator
37 Op_UF3_Gen Operation of stage 3 of underfrequency protection of
generator
38 Op_OF1_Gen Operation of stage 1 of overfrequency protection of
generator
39 Op_OF2_Gen Operation of stage 2 of overfrequency protection of
generator
40 Op_Z1_Gen Operation of stage 1 of distance protection of generator
41 Op_Z2_Gen Operation of stage 2 of distance protection of generator
42 Op_LossExc1_Gen Operation of stage 1 of loss-of-excitation protection of
generator
43 Op_LossExc2_Gen Operation of stage 2 of loss-of-excitation protection of
generator
44 Op_LossExc3_Gen Operation of stage 3 of loss-of-excitation protection of
generator
45 Op_Ext_OOS_Gen Operation of out-of-step protection outside zone of
generator
46 Op_Int_OOS_Gen Operation of out-of-step protection inside zone of generator
47 Op_BFP11_Gen Operation of break failure protection of generator with time
delay 1
48 Op_BFP12_Gen Operation of break failure protection of generator time delay
2
49 Op_RevP_Gen Operation of reverse power protection of generator
50 Op_SeqTrpRevP_Gen Operation of under power protection of generator
51 Op_AccEnerg_Gen Operation of accidental energization protection of generator
52 Op_Flash11_GCB Operation of stage 1 of flashover protection of generator
53 Op_Flash12_GCB Operation of stage 2 of flashover protection of generator
54 Op_InstDiff_Exciter Operation of instantaneous differential protection of exciter
55 Op_PcntDiff_Exciter Operation of percentage differential protection of exciter
56 Op_InstDiff_ET Operation of instantaneous differential protection of
excitation transformer
57 Op_PcntDiff_ET Operation of percentage differential protection of excitation
transformer
58 Op_OC1_ET Operation of stage 1 of overcurrent protection of excitation
transformer
59 Op_OC2_ET Operation of stage 2 of overcurrent protection of excitation
transformer
60 Op_MechRly1 Operation of repeater of external mechanical input 1(Manual
emergency tripping)
61 Op_MechRly2 Operation of repeater of external mechanical input 2(Failure
of condenser vacuum)
62 Op_MechRly3 Operation of repeater of external mechanical input 3(Stage
1 of 1PEF of rotor)
63 Op_MechRly4 Operation of repeater of external mechanical input 4(Stage
2 of 1PEF of rotor)
Whenever there is an un-eliminated internal failure record in the relay, the default display will be
replaced by an alarm report.
conditions.
19. Alm_PwrLoss_MechRly The power supply of mechanical protection is lost.
20. Alm_InconsistFD Mismatch of pickup of same type fault detectors in
CPU and MON.
21. Alm_PersistFD_CPUBrd Duration of pickup of any fault detector in CPU board
is in excess of 10s.
22. Alm_PersistFD_MONBrd Duration of pickup of any fault detector in MON board
is in excess of 10s.
23. Alm_BI_CPUBrd Any one of binary input sampled directly doesn‘t match
with that of recognition of protection itself.
24. Alm_InnerComm Alarm indicating that the communication between
MON and CPU interrupts.
25. Alm_Pos_GCB The sampled status of auxiliary contact of generator
terminal breaker‘s don‘t match with that of operation
condition identified from calculation of voltage and
currents.
26. Alm_SwOv_VTS1_Gen Alarm indicating VT1 circuit failure and start to switch
over voltage circuit.
27. Alm_SwOv_VTS2_Gen Alarm indicating VT2 circuit failure and start to switch
over voltage circuit.
28. Alm_BlkV3rdHDiff_VTS1 Alarm indicating VT1 circuit failure and blocking 3rd
harmonics voltage differential protection.
29. Alm_BlkIntTurn_VTS2 Alarm indicating VT2 circuit failure and blocking
interturn protection.
30. Alm_VTS_HVS_Tr Alarm indicating secondary circuit failure of VT at HV
side of main transformer.
31. Alm_VTS1_Term_Gen Alarm indicating secondary circuit failure of VT1 at
generator terminal.
32. Alm_VTS2_Term_Gen Alarm indicating secondary circuit failure of VT2 at
generator terminal.
33. Alm_VTS_NP_Gen Alarm indicating secondary circuit failure of VT at the
neutral point of generator.
34. Alm_DeltVTS1_Term_Gen Alarm indicating secondary circuit failure at open-delta
side of VT1 at generator terminal.
35. Alm_DeltVTS2_Term_Gen Alarm indicating secondary circuit failure at open-delta
side of VT2 at generator terminal.
36. Alm_VTS_LossExc_RotWdg Alarm indicating rotor voltage circuit failure which used
by loss-of-excitation protection.
37. Alm_CTS_BakCT_Gen Alarm indicating secondary circuit abnormality of
backup CT at generator terminal.
38. Alm_CTS_Term_Gen Alarm indicating secondary circuit abnormality of CT at
generator terminal.
39. Alm_CTS_NP_Gen Alarm indicating secondary circuit abnormality of CT at
the neutral point of generator.
Whenever there is change of state of any binary input, the default display will be replaced by
change report of binary input as shown as below.
Change maner
generator
14 EBI_PwrProt_Gen Enabling binary input of reverse power protection of
generator
15 EBI_FreqProt_Gen Enabling binary input of frequency protection of generator
16 EBI_AccEnerg_Gen Enabling binary input of accidental energization protection
of generator
17 EBI_StShut_Gen Enabling binary input of startup and shutdown protection
of generator
18 EBI_Diff_Exc Enabling binary input of differential protection of excitation
set
19 EBI_Bak_Exc Enabling binary input of backup protection of excitation
set
20 EBI_Trp_MechRly3 Enabling binary input of tripping function of repeater of
mechanical input 3(Stage 1 of 1PEF of rotor)
21 EBI_Trp_MechRly4 Enabling binary input of tripping function of repeater of
mechanical input 4(Stage 2 of 1PEF of rotor)
22 EBI_Trp_MechRly2 Enabling binary input of tripping function of repeater of
mechanical input 2(Failure of condenser vacuum)
23 EBI_Trp_MechRly1 Enabling binary input of tripping function of repeater of
mechanical input 1(Manual emergency tripping)
24 EBI_PPF_Gen Enabling binary input of backup protection of generator
25 BI_SyncCondenser Binary input indicating synchronism condenser is put into
operation
26 BI_ExtProtTrp Binary input indicating the external contact state of other
operation element operates.
27 BI_Pwr_Superv Binary input indicating working condition of all other binary
inputs
28 EBI_OvLd_RotWdg Enabling binary input of overload protection of excitation
29 EBI_SeqTrpRevP_Gen Enabling binary input of sequence tripping function of
generator
30 EBI_BFP_Gen Enabling binary input of breaker failure protection of
generator.
31 BI_Print Binary input representing the position of printing button
32 BI_Pulse_GPS Binary input representing the state of GPS pulse
33 BI_RstTarg Binary input representing the position of signal reset
button
34 BI_Pwr_Opto Binary input indicating the working state of power supply
of optical isolators
35 BI_MechRly2 Binary input indicating the position of mechanical input
2(Failure of condenser vacuum)
36 BI_MechRly4 Binary input indicating the position of mechanical input
4(Stage 2 of 1PEF of rotor)
37 BI_MechRly3 Binary input indicating the position of mechanical input
HEALTHY
VT ALARM
CT ALARM
ALARM
TRIP
TARGET RESET
―Healthy‖ (Green) indicates that the relay is in correct working order, and should be on at all times.
It will be extinguished when some internal error in hardware or software has been detected by the
self-diagnosing facilities, such as setting error, RAM or ROM error, power source failure, output
circuit failure and so on. The state of the healthy LED is reflected by the watchdog contact at the
rear terminals of the relay. The healthy LED cannot come on again automatically even if the failure
is eliminated except through resetting the relay or through power up by manual.
―VT Alarm‖ (Yellow) indicates that the relay has found any failure of VT circuit.
―CT Alarm‖ (Yellow) indicates that the relay has found any failure of CT circuit.
―Alarm‖ (Yellow) indicates that the relay has registered an alarm. This may be triggered by one of
the following failures: defective pickup, failure of analog or digital input circuit, optical isolator
power loss and so on. The LED will constantly illuminate, and will extinguish, when the alarms
have been cleared.
The LED ―TRIP‖ (RED) will be lit up once the corresponding relays operate and remain lit even
after the trip commands go off. It can be turned off by pressing ―TAEGET RESET‖ button on
faceplate, or by pressing the RESET button on the protection panel to energized binary input
[BI_RstTarg], or by remote resetting command.
P
+
GR
ENT
ESC
-
Note!
Any setting change operation should start by simply pressing ―+‖, ―◄‖, ―▲‖,and ―-‖ in
sequence, as a password. Without the operation, modifying settings is invalid.
Report delete operation should executed by pressing ―+‖, ―-‖, ―+‖, ―-‖, ―ENT‖ in sequence
after exiting the main menu.
8.2.5 Menu
This part presents the main layout of the menu tree for the local human-machine interface (HMI).
The menu tree includes menus for:
VALUES
REPORT
SETTINGS
CLOCK
VERSION
DEBUG
N A R I - R E L A Y S
VALUES CPU METERING GEN DIFF CURR
The default display can be replaced by the menu when press―▲‖ or ―ESC‖.
The menu of this relay is arranged as a tree-shaped cascade structure. See Figure 8.2-9. The
menu can be browsed using the keypad.
Starting at the default display, to enter into main menu, press ―▲‖.
To enter the lower level menu, select the required item and press ―ENT‖.
To return to the upper level menu, press ―ESC‖ or select ―0. Exit‖ and push ―ENT‖.
The menu can be browsed using the four arrow keys, following the structure shown in Figure 8.2-8.
Thus, starting at the default display the ―▲‖ key will display the first column heading. To select the
required column heading use the ―▲‖and ―▼‖ keys. To return to the default display, press the clear
key ―ESC‖ from any of the column headings.
MENU
TRIP REPORT
GEN PH ANG
ALARM REPORT
EXC PH ANG
BI CHG REPORT
GEN DIFF PROT
GEN SPTDIFF PROT
SETTINGS
GEN INTTURN PROT ACTIVE SETTINGS
TRIP RECORD
GEN PPF BAK PROT EQUIP SETTINGS
ALARM REPORT
STA EF PROT TRIGGER SYSTEM SETTINGS
BI CHG REPORT
INJ STA EF PROT BI STATE PROT SETTINGS
PRESENT WAVE
ROTWDG EF PROT PHASE ANGLE CALC SETTINGS
The menu structure contains two levels of access. The level of access is enabled determines what
users can do by entry of password. The levels of access are summarized in the following table:
The password is 4 digits. The factory default passwords is sequent pressing of the keys ―+‖, ―◄‖,
―▲‖, ―-‖ and ―ENT‖.
Metering data consists of AC sampled data and phase angle in the submenu VALUES. Take
viewing data relevant to differential protection of CPU metering as an example. Users can view
data of MON in the same way by entering ―MON METERING‖ submenu.
Navigate the menu through the following path and you will see the interface of LCD as shown in
Figure 8.2-10.
A scroll bar appears on the right means there are more rows needed to be displayed. Please press
key ―▼‖to see the next page and press key ―ESC‖ to exit to the upper level submenu.
The status of binary input comprises of enabling binary inputs and other binary inputs of auxiliary
contacts.
For instance, navigate the menu through the following path and you will see the interface of LCD
to see binary inputs related to generator‘s protection sampled by the CPU.
Main menu -> CPU BI STATE-> -> GEN PROT EBI -> [symbols]
EBI_Diff_Gen: 0
EBI_CoastProt_Gen: 0
EBI_PPF_Gen: 0
EBI_IntTurn_Gen: 0
EBI_BFP_Gen: 0
EBI_ROV_Sta: : 0
EBI_V3rd_Sta: 0
EBI_1PEF_RotWdg: 0
Entering into ―PHASE ANGLE‖ submenu, the calculated angles between sampled voltages or
between sampled voltages and currents by CPU system will be displayed on LCD as shown below,
which can be used to check the correctness of secondary circuit wiring.
The angles displayed is that the former value leading to the later one, which varies from -180~+
180, as shown as figure below for example.
GEN PH ANG
o
φ_Term_&_NP_Gen: 000 000 000
o
φ_SP1_&_SP2_Gen: 000 000 000
o
φipp_Term_Gen: 000 000 000
o
φipp_NP_Gen: 000 000 000
o
φipp_PwrProt_Gen: 000 000 000
o
φipp_SP1_Gen: 000 000 000
o
φipp_SP2_GenTV1: 000 000 000
o
φvpp_VT1_Term_Gen: 000 000 000
REPORTTRIP REPORT
Scroll the cursor to this submenu and press ―ENT‖ key, the LCD will display the latest trip report if
it exists, otherwise ―NO TRIP REPORT‖ will appear. If there are several trip reports stored in
memory, user can look up historical record one by one by pushing ―▲‖ key.
RCS-985G can store up to 24 latest trip reports. When the available space is exhausted, the
oldest report is automatically overwritten by the new one.
REPORT—ALARM REPORT
Scroll the cursor to this submenu and press ―ENT‖ key, the LCD will display the latest alarm report
if it exists, otherwise a ―NO ALARM REPORT‖ will appear. If there are several alarm reports stored
in memory, user can look up historical record one by one by pushing ―▲‖ key.
RCS-985G can store up to 64 latest alarm reports. When the available space is exhausted, the
oldest report is automatically overwritten by the new one.
Scroll the cursor to this submenu and press ―ENT‖ key, the LCD will display the last BI CHG report
if it exists, otherwise ―NO BI CHG REPORT‖ will appear. If there are several BI CHG reports
stored in memory, user can look up historical record one by one by pushing ―▲‖ key.
RCS-985G can store up to 64 latest signaling reports at a resolution of 2ms. When the available
space is exhausted, the oldest report is automatically overwritten by the new one.
If you want to delete the contents of fault records or event records, you can follow the operating
steps. Note you cannot select which kind of records or which one record is to be deleted but only
delete all records.
Operating steps:
N A RI- R EL A Y S
VALUES
REPORT
PRINT
SETTINGS
CLOCK
VERSION
DEBUG
Press keys ―+‖, ―-‖, ―+‖, ―-‖, ―ENT‖ in sequence in the main menu to make LCD display Figure
8.2-14.
Press key ―ENT‖ to delete all records or press key ―ESC‖ to exit to main menu. If key ―ENT‖ is
pressed, LCD will display Figure 8.2-15 when equipment is in the process of deleting all records. If
key ―ESC‖ is pressed, Figure 8.2-13 will be displayed. LCD will automatically return to Figure
8.2-13 in 3 seconds without pressing any key.
Clearing reports...
PRINTSETTINGS [submenu]
Used for printing of settings. The following figure gives an example of the first submenu [ACTIVE
SETTINGS].
PRINTTRIP REPORT
Used for printing of trip report of protection. User can select the report that he wants to print by
pushing ―▲‖ and ―▼‖ keys to select the SOE number. Here is an example.
PRINTALARM REPORT
Used for printing of alarm. User can select the report that he wants to print by pushing ―▲‖ and ―▼‖
keys. Here is an example.
Used for printing of signaling report. User can select the report that he wants to print by pushing
―▲‖ and ―▼‖ keys. Here is an example.
PRINTPRESENT VALUES
Used for printing of present values of relay, including sampled binary inputs, analog quantities and
so on. If you want to see the normal recording waveform, please follow the operating steps.
Operating steps:
Press key ―▲‖ or ―▼‖to select ―PRINT‖ item by scrolling the cursor upward or downward and then
press the ―ENT‖ to the lower level submenu.
Then press key ―▲‖ or ―▼‖to select ―PRESENT WAVE‖ by scrolling the cursor upward or
downward. Press key ―ENT‖ to enter the lower level submenu.
Press ―TRIGGER‖ submenu to start recording. The equipment will record 5-cycle waveform after
pressing the key.
Please select the other items in the submenu ―PRESENT WAVE‖ by scrolling cursor to print the
waveform.
Here is an example.
SettingsEquip Settings
To change one of the values of the equipment settings, first navigate the ―SETTING‖ menu to
display the relevant cell. Press ―ENT‖ to enter the submenu and then proceed to ―Equip Settings‖
submenu.
Keys ―▲‖ and ―▼‖are used to select which kind of the settings to be modified by scrolling the
cursor upward or downward. Press key ―◄‖ or ―►‖ to move the cursor to the digit to be modified.
Press key ―+‖ and ―–‖ to modify data. Press key ―ESC‖ to return back without modification.
By pressing key ―ENT‖, the LCD will prompt user to input password, user should enter password
as mentioned in section 8.2.5.2 and quit to default display by pressing ―ESC‖ key.
After a time period where the ―HEALTHY‖ LED is extinguished and blocking of relay, the
RCS-985G is ready to perform any new operation against faults set according to the new settings,
the modification is completed. The following figure shows the path to access this submenu.
SettingsProtection settings
To change the value of a setting, first navigate the menu to ―SETTING‖ then corresponding
submenu to display the relevant cell. Please locate the setting you want to change after entering
the right submenu by operating the keypad as described before. Then go on to operate as
following steps.
Press key ―◄‖ or ―►‖ to move the cursor to the digit to be modified. Pressing key ―+‖ and ―–‖ to
change the digit. Press key ―+‖ once to add 1 to the digit and press key ―–‖ once to subtract 1 from
the digit.
Press key ―ESC‖ to cancel the modification and return to upper level submenu.
Press key ―ENT‖ to confirm the modification and the LCD will prompt you to input confirm code.
Password :
Press keys ―+‖,‖ ―◄‖, ―▲‖ and ―–‖ in sequence to complete the modification. If the password input
is wrong, prompt for password will appear again. If there is no operation for 3 seconds, the LCD
will return to last display.
If the password inputted is right, then the equipment will check setting and Figure 8.2-22 will be
displayed temporarily. If there is no error in checking setting, Equipment will modify setting with
Figure 8.2-23 displayed temporarily. Then LCD will return to upper level submenu automatically.
Checking settings...
Modifying settings...
If errors in settings are detected, the LCD will display wrong setting warning for 3 s.
Settings error in
I_Pkp_Pcnt_Gen
Then LCD will display the setting list for the operator to modify the wrong setting. The cursor will
stay at the first wrong setting needed to be modified.
Note:
If the group number or protection system parameter is changed, all protection settings will be
invalid and have to be configured again.
Attention: Before modifying the protection settings, the active group number in ―Equip Settings‖
should modified first, otherwise what is modified will be applied to the current active group.
SettingsSettings Copy
The relay stores 2 setting groups from No.0 through No.1. Only present setting group is active, the
others are provided for different operating conditions. The equipment settings are shared for the
two setting groups, but the protection settings are independent. Generally the equipment is
delivered with default settings stored in active setting group ―0‖. The contents of other setting
groups may be invalid. Therefore after application-specific settings for group No.0 have been
ready, it is necessary to copy settings of group No.0 to No. 1 setting groups, and make some
modification afterwards when necessary, so as to avoid entering all settings one by one. Please
copy settings through the following steps.
VALUES
REPORT
PRINT
SETTINGS
CLOCK
VERSION
DEBUG
Move cursor to ―SETTINGS‖ item and press key ―ENT‖ or key―►‖ to enter submenu.
N A RI- REL AY S
VALUES
REPORT
EQUP SETTINGS
PRINT
SYSTEM SETTINGS
SETTINGS
PROT SETTINGS
CLOCK SETTINGS COPY
VERSION CALC SETTINGS
DEBUG
Move cursor to ―SETTINGS COPY‖ item and press ―ENT‖ to display following interface.
Copying Settings
Active Group : 00
Target Group : 00
Press key ―+‖ and ―–‖ to change digit where the cursor stays. Pressing key ―+‖ once will add 1 to
the digit and pressing key ―–―once will subtract 1 from the digit. (For example: input 01)
Press ―ENT‖ the LCD will prompt to input confirm code. Please see the figure below.
Password :
Please press keys ―+‖, ―◄‖, ―▲‖ and ―–‖ in sequence, and then the equipment will copy setting and
display following interface.
Copying settings...
Then the contents of setting group 0 will be totally copied to setting group 1 and present active
setting group will be switched to Group1.
Note:
Press ―ENT‖ to confirm, then settings group 0 will be completely copied to settings group 1 and
present active group will be switched to group 01.
After you press key ―ENT‖, the following will be displayed on the LCD.
CLOCK
07-02-05 (YY-MM-DD)
09:08:39 (hh : mm : ss)
Press keys ―▲‖, ―▼‖, ―◄‖ and ―►‖ to select the digit to be modified. Press key ―+‖ and ―–‖ to modify
data. Pressing key ―+‖ once will add 1 to the digit and pressing key ―–‖ once will subtract 1 from the
digit.
Press key ―ENT‖ to confirm the modification and return to the main menu.
The equipment program has following parts. One is CPU module program, one is MON module
program, and another is HMI module program. There are totally independent.
After you press key ―ENT‖, the follow will be displayed on the LCD.
VERSION
2006-12-12 10:20: shows that CPU software creating time is 10:20 Dec 12th 2006.
2006-12-12 10:20: shows that MON software creating time is 10:20 Dec 12th 2006.
2006-12-11 08:15: shows that HMI software creating time is 08:15 Dec 11th 2006.
Note:
What Figure 8.2-31 shows is just an example to introduce the meaning of VERSION, the actual
program VERSION is application-specific.
COMM STATUS
This submenu is used to monitor communication condition of the equipment with external system.
Display of this submenu is as follows:
485A 485B
Data_Received NO YES
Frame_Valid NO YES
Address_Valid NO YES
Data_Sent NO YES
Columns 485A and 485B display communication condition of RS-485 port1 and RS-485 port2
respectively. If communication condition is normal, ―Y‖ will flash in the related position. If there is
flashing ―N‖ in the position, it mean there are problems. Please check communication.
―Data_Received‖ means the equipment has received data from external system. If ―N‖ flashes, it
means the circuit is open or no data is sent from the external system.
―Frame_Valid‖ means the equipment has received complete frame from the external system. If
―N‖ flashes, it means the configuration of the baud rate or protocol is wrong.
―Address_Valid‖ means the equipment has received related message from external system. If ―N‖
flashes, it means Configuration of the address is wrong.
―Data_Sent‖ means the equipment has sent data to external system. If ―N‖ flashes, it means there
is a problem with the message.
MEMPRY DEBUG
The LCD displays real time value in memory of CPU, DSP1 and DSP2. These datas are used
mainly for program debugging.
Chapter9 Communications
9.1 Introduction
This section outlines the remote communications interfaces of the RCS-985G. The protection
supports a choice of one of three protocols via the rear communication interface, selected via the
model number by setting.
The rear EIA (RS) 485 interface is isolated and is suitable for permanent connection of whichever
protocol is selected. The advantage of this type of connection is that up to 32 relays can be ‗daisy
chained‘ together using a simple twisted pair electrical connection.
It should be noted that the descriptions contained within this section do not aim to fully detail the
protocol itself. The relevant documentation for the protocol should be referred to for this
information. This section serves to describe the specific implementation of the protocol in the
relay.
The following figure shows typical scheme of communication via RS-485 port of RCS-985G used
in substation automation system.
EIA RS-485
SAS 120Ω
GND 120Ω
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29
A B A B A B TX RX Earth
485PORT 485PORT 485PORT Printer PORT
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
G
The protocol provided by the relay is indicated in the relay menu in the ‗SETTINGS‘ column. Using
the keypad and LCD, check the communication protocol being used by the rear port according to
the definition of relevant settings described in section 7.
Two-core screened cable is recommended. The specification of the cable will be dependent on the
application, although a multi-strand 0.5mm2 per core is normally adequate. Total cable length
must not exceed 1000m. The screen must be continuous and connected to ground at one end,
normally at the master connection point; it is important to avoid circulating currents, especially
when the cable runs between buildings, for both safety and noise reasons.
This product does not provide a signal ground connection. If a signal ground connection is present
in the bus cable then it must be ignored, although it must have continuity for the benefit of other
devices connected to the bus. At no stage must the signal ground be connected to the cables
screen or to the product‘s chassis. This is for both safety and noise reasons.
• It is extremely important that the 120Ω termination resistors are fitted. Failure to do so will result
in an excessive bias voltage that may damage the devices connected to the bus.
• As the field voltage is much higher than that required, NR cannot assume responsibility for any
damage that may occur to a device connected to the network as a result of incorrect application of
this voltage.
To use the rear port with IEC60870-5-103 communication, the relay‘s communication settings
must be configured. To do this use the keypad and LCD user interface. Please refer to section
8.2.5 for detail instructions.
Three settings apply to the rear port using IEC60870-5-103 that is described below.
[Equip_ID] controls the IEC60870-5-103 address of the relay. Up to 32 relays can be connected to
one IEC60870-5-103 spur, and therefore it is necessary for each relay to have a unique address
so that messages from the master control station are accepted by one relay only. IEC60870-5-103
uses an integer number between 0 and 254 for the relay address. It is important that no two relays
have the same IEC60870-5-103 address. The IEC60870-5-103 address is then used by the
master station to communicate with the relay.
9.3.2.1 Settings
Note:
If the item ―[En_Remote_Cfg]‖ in Equipment Settings is set as 0, to modify settings remotely will
not be allowed. Moreover, Equipment Settings & System Settings are not allowed to be modified
remotely whether the item ―[En_Remote_Cfg]‖ is true (=1) or not.
9.3.2.5 Metering
9.3.2.6 BinaryInput
The following information is provided primarily for users who wish to develop their own master
communication drivers and applies to the serial Modbus RTU protocol. The characteristics are
listed below:
Physical Layer Setup:RS485, 1 start bit,8 data bits, no bit for parity,1 stop bit
Parity: no
The following modbus function codes are supported but re-defined by the relay:
This function reads the ON/OFF status of discrete inputs in the slave. The status in the response
message is packed as one input per bit of the data field. Status is indicated as: 1 = ON; 0 = OFF.
The LSB of the first data byte contains the input addressed in the query. The other inputs follow
toward the high order end of this byte, and from ‗low order to high order‘ in subsequent bytes.
Example 1: If the master wants to fetch Trip Information (0000H~0003H), the query frame would
be as follows(Suppose the slave address was 1):
01 02 00 00 00 04 79 C9
CRC Hi
CRC Lo
Num of Status Lo
Num of Status Hi
The response fame would be as follows (Suppose the value of 0000H~0003H equal to 1,1,0,1
respectively):
01 02 01 0B E0 4F
CRC Hi
CRC Lo
Status
Length
Function Code
Slave Addr
Example 2: If the master wants to fetch Trip Information (0002H~000DH), the query frame would
be as follows (Suppose the slave address was 1):
01 02 00 02 00 0C D9 CF
CRC Hi
CRC Lo
Num of Status Lo
Num of Status Hi
The response fame would be as follows (Suppose the value of 0002H~000DH equal to
1,1,0,1,0,0,1,0,1,1,1,0 respectively):
01 02 02 07 4B FB BF
CRC Hi
CRC Lo
Status Lo
Status Hi
Length
Function Code
Slave Addr
000CH Op_InsensIntTurn_Gen
000DH Op_SensROV_Sta
000EH Op_InsensROV_Sta
000FH Op_V3rdHRatio_Sta
0010H Op_V3rdHDiff_Sta
0011H Op_1PEF_RotWdg
0012H Op_2PEF_RotWdg
0013H Op_OvLd_Sta
0014H Op_InvOvLd_Sta
0015H Op_NegOC1_Gen
0016H Op_NegOC2_Gen
0017H Op_InvNegOC_Gen
0018H Op_OvLd_RotWdg
0019H Op_InvOvLd_RotWdg
001AH Op_OC1_Gen
001BH Op_OC2_Gen
001CH Op_OV1_Gen
001DH Op_OV2_Gen
001EH Op_UV_Gen
001FH Op_OvExc1_Gen
0020H Op_OvExc2_Gen
0021H Op_InvOvExc_Gen
0022H Op_UF1_Gen
0023H Op_UF2_Gen
0024H Op_UF3_Gen
0025H Op_OF1_Gen
0026H Op_OF2_Gen
0027H Op_Z1_Gen
0028H Op_Z2_Gen
0029H Op_LossExc1_Gen
002AH Op_LossExc2_Gen
002BH Op_LossExc3_Gen
002CH Op_Ext_OOS_Gen
002DH Op_Int_OOS_Gen
002EH Op_BFP11_GCB
002FH Op_BFP12_GCB
0030H Op_RevP_Gen
0031H Op_SeqTrpRevP_Gen
0032H Op_AccEnerg_Gen
0033H Op_Flash11_GCB
0034H Op_Flash12_GCB
0035H Op_InstDiff_Exciter
0036H Op_PcntDiff_Exciter
0037H Op_InstDiff_ET
0038H Op_PcntDiff_ET
0039H Op_OC1_Exc
003AH Op_OC2_Exc
003BH Op_MechRly1
003CH Op_MechRly2
003DH Op_MechRly3
003EH Op_MechRly4
003FH TrpOutp1
0040H TrpOutp2
0041H TrpOutp3
0042H TrpOutp4
0043H TrpOutp5
0044H TrpOutp6
0045H TrpOutp7
0046H TrpOutp8
0047H TrpOutp9
0048H TrpOutp10
0049H TrpOutp11
004AH TrpOutp12
1014H Alm_DPFC_IntTurn_Gen
1015H Alm_CTS_Diff_Gen
1016H Alm_CTS_SPTDiff_Gen
1017H Alm_BO_OC_Term_Gen
1018H Alm_On_2PEF_RotWdg
1019H Alm_Ext_OOS_Gen
101AH Alm_Int_OOS_Gen
101BH Alm_Accel_OOS_Gen
101CH Alm_Decel_OOS_Gen
101DH Alm_LossExc_Gen
101EH Alm_OvExc_Gen
101FH Alm_OvLd_Sta
1020H Alm_NegOC_Gen
1021H Alm_OvLd_RotWdg
1022H Alm_ROV_Sta
1023H Alm_V3rdHRatio_Sta
1024H Alm_V3rdHDiff_Sta
1025H Alm_Sens1PEF_RotWdg
1026H Alm_1PEF_RotWdg
1027H Alm_UF1_Gen
1028H Alm_UF2_Gen
1029H Alm_UF3_Gen
102AH Alm_OF1_Gen
102BH Alm_OF2_Gen
102CH Alm_RevP_Gen
102DH Alm_CTS_S1_Exc
102EH Alm_CTS_S2_Exc
102FH Alm_Diff_ET
1030H Alm_Diff_Exciter
1031H Alm_CTS_Diff_ET
1032H Alm_CTS_Diff_Exciter
1033H Alm_MechRly2
1034H Alm_MechRly4
1035H Alm_MechRly3
1036H Alm_MechRly1
1037H Alm_Inconsist_MechRly
1038H Alm_PwrLoss_MechRly
1039H Alm_PM_DSP2_CPUBrd
103AH Alm_RAM_CPUBrd
103BH Alm_ROM_CPUBrd
103CH Alm_EEPROM_CPUBrd
103DH Alm_InvalidSetting
103EH Alm_ModifiedSetting
103FH Alm_PwrLoss_Opto
1040H Alm_TripOutput
1041H Alm_InnerComm
1042H Alm_DSP_CPUBrd
1043H Alm_PersistFD_CPUBrd
1044H Alm_InconsistFD
1045H Alm_Sample_CPUBrd
1046H Alm_BI_CPUBrd
1047H Alm_RAM_MONBrd
1048H Alm_ROM_MONBrd
1049H Alm_EEPROM_MONBrd
104AH Alm_DSP_MONBrd
104BH Alm_PersistFD_MONBrd
104CH Alm_MONBrd
104DH Alm_Sample_MONBrd
2017H EBI_SPTDiff_Gen
2018H BI_UrgBrake
2019H BI_SyncCondenser
201AH BI_Reserved3
201BH BI_Reserved2
201CH BI_Pwr_Superv
201DH EBI_OvLd_RotWdg
201EH EBI_BFP_GCB
201FH EBI_SeqTrpRevP_Gen
2020H BI_MechRly2
2021H BI_MechRly4
2022H BI_MechRly3
2023H BI_MechRly1
2024H BI_Pwr_MechRly
2025H BI_52b_GCB
2026H BI_Reserved4
2027H BI_ExtProtTrp
2028H BI_Reserved1
2029H BI_Valve_Turbine
The metering values in the response message are packed as two bytes per register. For each
register, the first byte contains the high order bits and the second contains the low order bits.
Bit3:En_2PEF_RotWdg
Bit4:En_VCE_2PEF_RotWdg
The function uses a two–byte subfunction code field in the query to define the type of test to be
performed. The slave echoes both the function code and subfunction code in a normal response.
The listing below shows the subfunction codes supported by the equipment.
0DH Return Bus Exception Error Cnt 0FH Return Slave No Response Cnt
0EH Return Slave Message Count
9.4.6 Exception Responses
Except for broadcast messages, when a master device sends a query to a slave device it expects
a normal response but If the slave receives the query without a communication error, but cannot
handle it (for example, if the request is to read a non–existent coil or register), the slave will return
an exception response informing the master of the nature of the error.
The listing below shows the exception codes supported by the equipment.
None of the other pins are connected in the relays. The relays should be connected to the serial
port of a PC, usually called as COM1 or COM2. The serial port pin connections, which is DB9 male,
is described below (if in doubt check you PC manual):
For successful data communication, the Tx pin on the relays must be connected to the Rx pin on
the PC, and Rx pin on the relay must be connected to Tx pin on the PC as shown in Figure 9.5-1.
Note:
1 3 5 7 9
2 4 6 8
1 3 5 7 9
2 4 6 8
There are no parameters needed to be set in RCS-985G for communication with the printer.
The printer‘s port used for communication with RCS-985G is a serial port of which the pin
definition is a little different with normal RS232 port as shown as below:
1 2 3 4 5
6 7 8 9
1 2 3 4 5
6 7 8 9
---Event recording
---Fault recording
---Present recording
---Self-supervision
When the relays are connected to the GPS clock, all the relay clocks are synchronized with the
external time standard. There are two way to adjust the relay clock.
Chapter10 Installation
Each printed circuit board incorporates the highest practicable protection for its semiconductor
devices. However, if it becomes necessary to remove a printed circuit board, the following
precautions should be taken to preserve the high reliability and long life for which the relay has
been designed and manufactured.
Before removing a printed circuit board, ensure that you are at the same electrostatic potential as
the equipment by touching the case.
Handle analog input modules by the front panel, frame or edges of the circuit boards.
Printed circuit boards should only be handled by their edges. Avoid touching the electronic
components, printed circuit tracks or connectors.
Do not pass the module to another person without first ensuring you are both at the same
electrostatic potential. Shaking hands achieves equipotential.
Place the module on an anti-static surface, or on a conducting surface that is at the same potential
as you.
If it is necessary to store or transport printed circuit boards removed from the case, place them
individually in electrically conducting anti-static bags.
In the unlikely event that you are making measurements on the internal electronic circuitry of a
relay in service, it is preferable that you are earthed to the case with a conductive wrist strap. Wrist
straps should have a resistance to ground between 500kΩ to 10MΩ. If a wrist strap is not available
you should maintain regular contact with the case to prevent a build-up of electrostatic potential.
Instrumentation which may be used for making measurements should also be earthed to the case
whenever possible.
More information on safe working procedures for all electronic equipment can be found in BS EN
100015: Part 1:1992. It is strongly recommended that detailed investigations on electronic circuitry
or modification work should be carried out in a special handling area such as described in the
British Standard document.
10.3 Storage
If relays are not to be installed immediately upon receipt, they should be stored in a place free from
dust and moisture in their original cartons. Where de-humidifier bags have been included in the
packing they should be retained.
To prevent battery drain during transportation and storage, a battery isolation strip is fitted during
manufacture. With the lower access cover open, presence of the battery isolation strip can be
checked by a red tab protruding from the positive polarity side.
Care should be taken on subsequent unpacking that any dust, which has collected on the carton,
does not fall inside. In locations of high humidity the carton and packing may become impregnated
with moisture and the de-humidifier crystals will lose their efficiency.
Prior to installation, relays should be stored at a temperature of between –25°C to +70°C (-13°F to
+158°F).
10.4 Unpacking
Care must be taken when unpacking and installing the relays so that none of the parts are
damaged and additional components are not accidentally left in the packing or lost. Ensure that
any User‘s CDROM or technique documentation is NOT discarded – this should accompany the
relay to its destination substation.
Note:
With the lower access cover open, the red tab of the battery isolation strip will be seen protruding
from the positive (―+‖) side of the battery compartment. Do not remove this strip because it
prevents battery drain during transportation and storage and will be removed as part of the
commissioning tests. Relays must only be handled by skilled persons.
The site should be well lit to facilitate inspection, clean, dry and reasonably free from dust and
excessive vibration.
IEC60297 and are supplied pre-assembled ready to use. On a standard 483mm rack system this
enables combinations of widths of case up to a total equivalent of size 80TE to be mounted side by
side.
Once the tier is complete, the frames are fastened into the racks using mounting angles at each
end of the tier.
482
285
465
RCS-985G
GENERATOR PROTECTION
HEALTHY
VT ALARM
GRP
CT ALARM
ALARM
ENT
ESC
354.8
279.4
76.2
TRIP
465
450
279.4
76.2
355
8- ¢6.8
Relays can be mechanically grouped into single tier (8U) or multi-tier arrangements by means of
the rack frame.
For applications where relays need to be semi-projection or projection mounted, a range of collars
are available. Where several relays are mounted in a single cutout in the panel, it is advised that
they are mechanically grouped together horizontally and/or vertically to form rigid assemblies prior
to mounting in the panel.
Note:
It is not advised that RCS-985G be fastened using pop rivets as this will not allow the relay to be
easily removed from the panel in future if repair is necessary.
If it is required to mount a relay assembly on a panel complying to IEC 60529 IP51 enclosure
protection, it will be necessary to fit a metallic sealing strip between adjoining relays and a sealing
ring around the complete assembly.
Loose relays are supplied with sufficient M4 screws for making connections to the rear mounted
terminal blocks using ring terminals, with a recommended maximum of two ring terminals per relay
terminal.
If required, NR can supply M4 90°crimp ring terminals in three different sizes depending on wire
size (see Table 10.6-1).
*To maintain the terminal block insulation requirements for safety, an insulating sleeve should be
Due to the limitations of the ring terminal, the maximum wire size that can be used for any of the
medium or heavy duty terminals is 6.0mm2 using ring terminals that are not pre-insulated.
Where it is required to only use pre-insulated ring terminals, the maximum wire size that can be
used is reduced to 2.63mm2 per ring terminal. If a larger wire size is required, two wires should be
used in parallel, each terminated in a separate ring terminal at the relay.
The wire used for all connections to the medium and heavy duty terminal blocks, except the
EIA(RS)485 port, should have a minimum voltage rating of 300Vrms.
It is recommended that the auxiliary supply wiring should be protected by a 16A high rupture
capacity (HRC) fuse of type NIT or TIA. For safety reasons, current transformer circuits must
never be fused. Other circuits should be appropriately fused to protect the wire used.
The relays can have an optional 10 or 100 Mbps Ethernet port. FO connection is recommended for
use in permanent connections in a substation environment. The 10Mbit port uses type ST
connector and the 100Mbit port uses type SC connector, both compatible with 850nm multi-mode
fiber-optic cable.
The user can connect to either a 10Base-T or a 100Base-TX Ethernet hub; the port will
automatically sense which type of hub is connected. Due to possibility of noise and interference on
this part, it is recommended that this connection type be used for short-term connections and over
short distance, ideally where the relays and hubs are located in the same cubicle.
The connector for the Ethernet port is a shielded RJ-45. The table shows the signals and pins on
the connector.
Chapter11 Commission
11.1 Introduction
This relay is fully numerical in their design, implementing all protection and non-protection
functions in software. The relay employs a high degree of self-checking and in the event of a
failure, will give an alarm. As a result of this, the commissioning test does not need to be as
extensive as with non-numeric electronic or electro-mechanical relays.
To commission numerical relays, it is only necessary to verify that the hardware is functioning
correctly and the application-specific software settings have been applied to the relay. It is
considered unnecessary to test every function of the relay if the settings have been verified by one
of the following methods:
- extracting the settings applied to the relay using appropriate setting software (preferred method)
- via the operator interface
Blank commissioning test and setting records are provided at the end of this manual for
completion as required.
WARNING!
Before carrying out any work on the equipment, the user should be familiar with the contents of the
safety and technical data sections and the ratings on the equipment‘s rating label.
11.2 Precautions
WARNING!
Hazardous voltages are present in this electrical equipment during operation. Non - observance of
the safety rules can result in severe personal injury or property damage.
Only qualified personnel shall work on and around this equipment after becoming thoroughly
familiar with all warnings and safety notices in this manual as well as with the applicable safety
regulations.
The earthing screw of the device must be connected solidly to the protective earth conductor
before any other electrical connection is made.
Hazardous voltages can be present on all circuits and components connected to the supply
voltage or to the measuring and test quantities.
Hazardous voltages can be present in the device even after disconnection of the supply voltage
(storage capacitors!).
The limit values stated in the technical data (Chapter 2) must not be exceeded at all, not even
during testing and commissioning.
When testing the device with secondary test equipment, make sure that no other measurement
quantities are connected. Take also into consideration that the trip circuits and maybe also close
commands to the circuit breakers and other primary switches are disconnected from the device
unless expressly stated.
DANGER!
Current transformer secondary circuits must have been short-circuited before the current leads to
the device are disconnected.
WARNING!
Primary test may only be carried out by qualified personnel, who are familiar with the
commissioning of protection system, the operation of the plant and safety rules and regulations
(switching, earthing, etc.)
--Multifunctional dynamic current and voltage injection test set with interval timer
--Multimeter with suitable AC current range and AC/DC voltage ranges of 0-200V and 0-250V
respectively.
Note:
Modern test set may contain many of the above features in one unit.
Optional equipment
--An electronic or brushless insulation tester with a DC output not exceeding 500 V (for insulation
resistance test when required);
--A portable PC, with appropriate software (this enables the rear communications port to be tested,
if this is to be used, and will also save considerable time during commissioning).
--RCSPC software.
-- A printer.
With the front cover in place all keys are accessible. All menu cells can be read. LEDs and alarms
can be reset. Protection or configuration settings can be changed, or fault and event records
cleared. However, menu cells will require the appropriate password to be entered before changes
can be made.
Alternatively, if a portable PC is available together with suitable setting software (such as RCSPC),
the menu can be viewed a page at a time to display a full column of data and text. This PC
software also allows settings to be entered more easily, saved to a file on disk for future reference
or printed to produce a setting record. Refer to the PC software user manual for details. If the
software is being used for the first time, allow sufficient time to become familiar with its operation.
If the application-specific settings have been applied to the relay prior to commissioning, it is
advisable to make a copy of the settings so as to allow restoration later. This can be done by
extracting the settings from the relay itself via printer or manually creating a setting record.
The following tests are necessary to ensure the normal operation of the equipment before it is first
put into use.
Hardware tests
These tests are performed for the following hardware to ensure that there are no hardware
defects. Defects of hardware circuits other than the following can be detected by
self-monitoring when the DC power is supplied.
Function tests
These tests are performed for the following functions that are fully software-based. Tests of
the protection schemes and fault locator require a dynamic test set.
Timers test
Conjunctive tests
The tests are performed after the relay is connected with the primary equipment and other
external equipment.
On-load test
After unpacking the product, check for any damage to the relay case. If there is any damage, the
internal module might also have been affected, contact the vendor. Following items listed is
necessary.
1. Protection panel
Carefully examine the protection panel, protection equipment inside and other parts inside to
see that no physical damage has occurred since installation.
The rated information of other auxiliary protections should be checked to ensure it is correct
for the particular installation.
2. Panel wiring
Check the conducting wire used in the panel to assure that their cross section meets the
requirement.
Carefully examine the wiring to see that they are no connection failure exists.
3. Label
Check all the isolator binary inputs, terminal blocks, indicators, switches and push buttons to
make sure that their labels meet the requirements of this project.
Check each plug-in module of the equipments on the panel to make sure that they are well
installed into the equipment without any screw loosened.
1 1 1 1
A A B B
2 2 2 2
A A B B
3 3 3 3
A A B B
4 4 4 4
A A B B
5 5
B B
6 6
B B
7 7
B B
8 8 8 8
B B C C
9 9 9 9
B B C C
5. Earthing cable
Check whether the earthing cable from the panel terminal block is safely screwed to the panel
steel sheet.
Check whether all the switches, equipment keypad, isolator binary inputs and push buttons
work normally and smoothly.
11.5.1.2 Insulation
Insulation resistances tests are only necessary during commission if it is required for them to be
done and they have not been performed during installation.
Isolate all wiring from the earth and test the insulation with an electronic or brushless insulation
tester at a DC voltage not exceeding 500V, terminals of the same circuits should be temporarily
connected together.
-Relay contacts
-Case earth
The insulation resistance should be greater than 100MΩ at 500V. On completion of the insulation
resistance tests, ensure all external wiring is correctly reconnected to the relay.
Check that the external wiring is correct to the relevant relay diagram and scheme diagram.
Ensure as far as practical that phasing/phase rotation appears to be as expected.
Check the wiring against the schematic diagram for the installation to ensure compliance with the
customer‘s normal practice.
The relay can be operated from either 110/125Vdc or 220/250Vdc auxiliary supply depending on
the relay‘s nominal supply rating. The incoming voltage must be within the operating range
specified in the following table, before energizing the relay, measure the auxiliary supply to ensure
it is within the operating range.
It should be noted that the relay can withstand an AC ripple of up to 15% of the upper rated voltage
on the DC auxiliary supply.
Energize the relay only if the auxiliary supply is within the specified operating ranges.
The current and voltage transformer connections must remain isolated from the protection for
these checks. The trip circuit should also remain isolated to prevent accidental operation of the
associated circuit breaker.
This test ensures that the LCD, LEDs and keys function correctly.
◆ LCD display
Only apply the rated DC voltage and check whether the LCD displays normal operation status
report as mentioned earlier. If there is a failure, for example, if the VT circuit fails because of not
applying the voltage, the LCD displays failure report. On pressing the ECS key for 1 second and
the LCD will return to normal operation status report.
◆ LED display
Apply the rated DC voltage and check that the "HEALTHY" LED is lit in green. We need to
emphasize that the "HEALTHY" LED is always lit in operation course except when the equipment
finds serious problems listed in chapter 4.
◆ Keypad
Press key ―ESC‖ or ―▲‖and enter the command menu. Do some jobs to ensure that all buttons are
in good condition.
Using a continuity tester, check the watchdog contacts (equipment being blocked, BSJ) are in
the states given in Table 11.5-1 below.
Terminals Contacts
Relay de-energized Relay energized
3A1-3A3 Closed Open
3A2-3A4
3B4-3B26
The method of setting will depend on whether accuracy is being maintained via the RS-485 port
(from GPS in the substation) on the rear of the protection or via the front panel user interface
manually.
Turn on the DC power supply of the equipment and check the software version and time through
the LCD Manual.
This test checks that all the binary inputs on the protection are functioning correctly. The binary
inputs should be energized one at a time. Ensuring correct polarity, connect the field supply
voltage to the appropriate terminals for the input being tested.
There two voltage levels of opto-couple for binary inputs, one is 24V DC and the other is
250/220/125/110V DC. The negative pole of DC 24V and negative pole of DC 250/220/125/110V
have been connected with the corresponding negative pole of opto-couplers through the inner rear
board in equipment. The positive pole terminals of opto-couplers have been connected to the rear
connectors for binary input connecting, and common positive pole has also be connected to the
rear connector.
Please see the panel diagram carefully and find the right connector terminal numbers of common
positive pole of DC 24V and DC 250/220/125/110V.
Note:
The binary inputs may be energized from an external DC auxiliary supply (e.g. the station battery)
in some installations. Check that this is not the case before connecting the field voltage otherwise
damage to the protection may result. The status of each binary input can be viewed using either
RCSPC software installed in a portable PC or by checking the front human-machine interface LCD.
When each binary input is energized the display will change to indicate the new status of the
inputs. Please check binary input both on CPU module and MON module and ensure they are
consistent.
Please note only the positive pole of opto-coupler for binary inputs are listed in following tables.
Path: Main Menu -> VALUES-> CPU(MON) BI STATE ->GEN PROT EBI
Path: Main Menu -> VALUES-> CPU(MON) BI STATE ->EXC PROT EBI
3 EBI_OvLd_Exc 5B17-5B1
Path: Main Menu -> VALUES-> CPU(MON) BI STATE ->MECH RLY EBI
When detecting a hardware failure in self-supervise, the relay will block all the output and the
―HEALTY‖ LED will not be lit.
If the entire operation element for alarm operates, the ―ALARM‖ LED will illuminate. At the same
time, the BJJ contact and other alarm contacts will be closed. According to the below table we can
check these contacts.
If the operation element for tripping operates, the ―TRIP‖ LED will illuminate. At the same time, the
tripping signal contacts will be closed. According to the below table we can check these contacts.
Setting the tripping logic settings refer to table 5-1. The output x will be closed only when the
correspond bit [Output x] is set as ―1‖. According to the below table we can check these contacts.
This test should only be performed where the protection is to be accessed from a remote location
and will vary depending on the communications standard being adopted.
It is not the intention of the test to verify the operation of the complete system from the relay to the
remote location, just the protection‘s rear communications port and any protocol converter
necessary.
Courier communications
Ensure that the RS-232 wire link the RS-232 port in front of the RCS-985G and the communication
baud rate in RCSPC must be set as ―9600‖.
Check that communications can be established with this protection using the portable PC.
Remote communication
This test is to check the status of communications between RCS-985G and the engineer‘s
In the menu of ―DEBUG‖->‖COMM STATUS‖ on the LCD display, ―485A‖or ―485B‖ indicates the
communication status of 485A port or 485B port. If ―Receive Data‖ is ―N‖, it means the equipment
has not received data from the external system. If ―Valid Frame‖ is ‗N‘, it indicates the setting error
of baud rate or protocol while ―Valid Address‖ is ―N‖, it means the communication address is set
wrongly. ‖Send Data‖ is "N‖ means datagram sent from the equipment is wrong. If all those status
are ‗Y‘, it means communication is established successfully.
This test verifies that the accuracy of current measurement is within the acceptable tolerances.
All protections will leave the factory with setting for operation at a system frequency of 50Hz or
60Hz.
All relays will be set for operation at a system frequency of 50Hz. If operation at 60Hz is required
then this must be set at menu.
Apply current equal to the current transformer secondary winding rating to each current
transformer input of the corresponding rating in turn, see the following table or external connection
diagram for appropriate terminal numbers, checking its magnitude using a multimeter/test set
readout. The corresponding reading can then be checked in the relays‘ menu.
The measurement accuracy of the relay is ±5%. However an additional allowance must be made
for the accuracy of the test equipment being used.
Note:
To avoid damage the equipment, we can‘t inject a high value current (such as 4In or more) to the
equipment for long time, we suggest that the time in high current condition should not be over 3
second every time.
The measurement accuracy of the protection is ± 5%. However, an additional allowance must be
made for the accuracy of the test equipment being used.
This test only needs to be performed on models with voltage transformer inputs as it verifies that
the accuracy of voltage measurement is within the acceptable tolerance levels.
Apply rated voltage to voltage transformer input, checking its magnitude using a multimeter/test
set readout. The corresponding reading can then be checked in the relays menu.
The measurement accuracy of the relay is ±5%. However an additional allowance must be made
for the accuracy of the test equipment being used.
Displayed in LCD
Input Angle Angle
No. Items
value PhA PhB PhC between between
A and B A and C
58V
1 U_VT1_Term_Gen
20V
58V
2 U_VT2_Term_Gen
20V
58V
3 U0_DeltVT1_Term_Gen
20V
100V
4 U0_DeltVT2_Term_Gen
20V
100V
5 U0_NP_Gen
20V
100V
6 U_Busbar
20V
7 U_RotWdg (DC) 220V
Note:
When checking the rotor current channel, 0.075V is equal to 1000A of rotor current, please refer to
section 7.2 [I1n_RotWdg] and [U2n_Shunt_RotWdg]
The measurement accuracy of the protection is ±5%. However, an additional allowance must be
Note:
The trip circuit should remain isolated during these checks to prevent accidental operation of the
associated circuit breaker.
Transfer them from a pre-prepared setting file to the relay using a portable PC running the
appropriate software via the relay‘s RS232 port located on the frontplate of the relay. This method
is preferred for transferring function settings as it is much faster and there is less possiblity for
error.
Tests mentioned above have already demonstrated that the relay is within calibration, thus the
purpose of these tests is as follows:
− To determine that the primary protection functions, such as generator differential protection,
overcurrent protection and so on, can trip according to the correct application settings.
− To verify correct assignment of the trip contacts, by monitoring the response to a selection of
fault injections.
It is not the intension of the test to verify the operation of the complete system from the relay to the
remote location, just the relay‘s rear communications port and any protocol converter necessary.
Connect a portable PC to the relay via a EIA (RS) 485-232 converter. Ensure that the relay
address and the baud rate settings in the application software are set the same as those in relay.
If the relay has the optional fiber optic communications port, then a fibre optic-RS232 converter
shall be applied.
-Confirm the external wiring to the current and voltage inputs is correct.
Remove all test leads, temporary shorting leads, etc. and replace any external wiring that has
been removed to allow testing.
If it has been necessary to disconnect any of the external wiring from the relay in order to perform
any the foregoing tests. It should be ensured that all connections are replaced in accordance with
the relevant external connection or scheme diagram.
Voltage connections
Using a multimeter to measure the voltage generator secondary voltages to ensure they are
correctly rated. Check that the system phase rotation is correct using a phase rotation meter.
Compare the values of the secondary phase voltages with the relays measured values, which can
be found in the menu.
Current connections
Measure the current transformer secondary values for each input using a multimeter connected in
series with the corresponding current input. (It is preferable to use a tong-test ammeter instead)
Check that the current transformer polarities are correct by measuring the phase angle between
the current and voltage either against a phase meter already installed on site and known to be
correct or by determining the direction of power flow by contacting the networks control center
(NCC).
Compare the values of the secondary phase currents and phase angle with the relay‘s measured
values, which can be found in menu.
Remove all test or temporary shorting leads, etc. If it has been necessary to disconnect any
of the external wiring from the relay in order to perform the wiring verification tests, it
should be ensured that all connections (wiring, fuses and links) are replaced in accordance
with the relevant external connection or scheme diagram.
Ensure that all event records, fault records, disturbance records, alarms and LEDs have been
reset before leaving the relay.
It comprises of four parts: sampled value display, settings reading and modification, report process
and test. These four parts correspond to 4 files RCS-985G_status, RCS-985G_set,
RCS-985G_rpt and RCS-985G_tst respectively and are described hereinafter. We have to say
that the four configuration file is relevant with a special version of protection program. That is,
when the protection program is upgraded, the above mentioned four configuration files must also
be upgrade at the same time; otherwise it may cause confusion to the equipment at the time of
setting.
Connect RS-232 communication port of the computer and that of RCS-985G protection equipment
by a cable with DB-9 connectors on both ends. Run the program RCSPC. If the connection is
correct, the screen will show ―RCS-985G connected‖, see Figure 11.6-1. Even if the computer is
off line, this picture will be still shown but the words about connection will disappear.
11.6.3.1 PC configuration
Set the PC com port‘s baud rate which is connected with front series port of RCS-985G as
9600bps.
There are 3 bars on top of the screen, from top to bottom: title bar, menu bar and tool bar, see
Figure 11.6-3.
First, click the first button of tool bar parameter, dialog box of communication parameters is
displayed, see Figure 11.6-4. Only the parameter of [COM port] shall be configured as the port of
computer which is actually connected with the equipment, all other parameters shall be configured
as the same as displayed in Figure 11.6-4.
This function is used for offline parameter setting. First, input setting parameters and save it in PC,
then connect PC with the protection equipment, executive ―DOWNLOAD‖ command, and the
settings saved in PC will be transferred to the protection equipment, so most parts of the setting
operation can be finished in office instead of in substation.
Before connecting PC with RCS-985G, run the software of RCSPC,click on ―setting‖ icon, a popup
dialog box will appear which will ask user whether or not to set parameter offline, click ―yes‖ and
input ―985Gxxx‖ (xxx represents program version, point ignored) to confirm the relay type and
version of the protection program, then parameter setting interface will appear. The settings
displayed first are default settings; user can replace them with application-specific settings. After
modifications, save the settings into a file. When the PC is connected with the protection
equipment, open the settings file and transfer setting to protection.
When PC is connecting with RCS-985G, run RCSPC, the PC screen will display ―RCS-985Gxxx
connected‖, click on ―SETTING‖ icon, then parameter setting interface will appear, the settings
uploaded from RCS-985G will be displayed, user can modify them to application-specific settings.
11.6.4.2 Status
Click button, user can observe real time sampled data and binary input status.
11.6.4.3 Report
Click button, entering report view part of the program, choose a report in the table, and click
―report record‖, save report data according to following clue on instruction. The data can be used
in the auxiliary analyze software to show us the fault course of power system and the logic
calculation course of RCS-985G again.
Click button, all magnetic latched output relays and signal relays will be reset.
Click button, entering trip test part of the program, click contacts to change the status of
relays displayed, a same operation command to breaker circuit will be issued. This function is
used to test breaker circuit without applying electric quantities to the protection equipment.
Chapter12 Maintenance
RCS series relays are self-supervising and so require less maintenance than earlier designs of
relay. Most problems will result in an alarm so that remedial action can be taken. However, some
periodic tests should be done to ensure that the relay is functioning correctly and the external
wiring is intact.
Before carrying out any work on the equipment, the user should be familiar with the
contents of the Safety and technique Data sections and the ratings on the equipment‘s
rating label.
12.2.1 Alarms
The alarm status LED should first be checked to identify if any alarm conditions exist. If so, try to
find the cause of the alarm and eliminate it and clear the alarms to extinguish the LED.
Alternatively, the values measured by the relay can be checked against known values injected into
the relay via the test block, if fitted, or injected directly into the relay terminals. Suitable test
methods can be found in relevant manuals. These tests will prove the calibration accuracy is being
maintained.
The preferred method is to replace the complete relay as it ensures that the internal circuitry is
protected against electrostatic discharge and physical damage at all times and overcomes the
possibility of incompatibility between replacement PCBs.
Replacing PCBs can reduce transport costs but requires clean, dry conditions on site and higher
skills from the person performing the repair. However, if the repair is not performed by an
approved service center, the warranty will be invalidated.
Before carrying out any work on the equipment, the user should be familiar with the contents of the
Safety and technique Data sections and the ratings on the equipment‘s rating label. This should
ensure that no damage is caused by incorrect handling of the electronic components.
Before working at the rear of the relay, isolate all voltage and current supplies to the relay.
Note:
The RCS serials relays have integral current transformer shorting switches which will close when
the connecting terminal is removed.
Disconnect the relay earth, IRIG-B and fiber optic connections, as appropriate, from the rear of the
relay.
Note:
The use of a magnetic bladed screwdriver is recommended to minimize the risk of the screws
being left in the terminal block or lost.
Without exerting excessive force or damaging the scheme wiring, pull the terminal blocks away
from their internal connectors.
Remove the screws used to fasten the relay to the panel, rack, etc. These are the screws with the
larger diameter heads on front of the faceplate of the relay.
Withdraw the relay carefully from the panel, rack, etc. because it will be heavy due to the internal
transformers.
To reinstall the repaired or replacement relay, follow the above instructions in reverse, ensuring
that each terminal block is relocated in the correct position and the case earth, and fiber optic
connections are replaced.
Once reinstallation is complete the relay should be re-commissioned using the instructions in
Chapter11 of this manual.
Before replacing a PCB the auxiliary supply must be removed, and wait 5s for capacitors to
discharge. It is also strongly recommended that the voltage and current transformer connections
and trip circuit are isolated.
The relay, being modular in design, allows for the withdrawal and insertion of modules. Modules
must only be replaced with like modules in their original factory configured slots.
NR Support teams are available world-wide, and it is strongly recommended that any repairs be
entrusted to those trained personnel. For this reason, details on product disassembly and
re-assembly are not included here.
This battery will periodically need changing. If the battery-backed facilities are not required to be
maintained during an interruption of the auxiliary supply, the steps below can be followed to
remove the battery.
Before carrying out any work on the equipment, the user should be familiar with the contents of the
safety and technique data sections and the ratings on the equipment‘s rating label.
Gently extract the battery from its socket. If necessary, use a small, insulated screwdriver to prize
the battery free.
Ensure that the metal terminals in the battery socket are free from corrosion, grease and dust.
The replacement battery should be removed from its packaging and placed into the battery holder,
taking care to ensure that the polarity markings on the battery agree with those adjacent to the
socket as shown as below.
Note:
Ensure that the battery is securely held in its socket and that the battery terminals are making
good contact with the metal terminals of the socket.
12.5 Cleaning
Before cleaning the equipment ensure that all AC and DC supplies, current transformer and
voltage transformer connections are isolated to prevent any chance of an electric shock whilst
cleaning.
The equipment may be cleaned using a lint-free cloth moistened with clean water. The use of
detergents, solvents or abrasive cleaners is not recommended as they may damage the relay‘s
surface and leave a conductive residue.
13.1 Decommissioning
13.1.1 Switching Off
To switch off the RCS-985G, switch off the external miniature circuit breaker of the power supply.
Disconnect the cables in accordance with the rules and recommendations made by relational
department.
DANGER: Before disconnecting the power supply cables that connected with the DC
module of the RCS-985G, make sure that the external miniature circuit breaker of the
power supply is switched off.
DANGER: Before disconnecting the cables that are used to connect analog input module
with the primary CTs and VTs, make sure that the circuit breaker for the primary CTs and
VTs is switched off.
13.1.3 Dismantling
The RCS-985G rack may now be removed from the system cubicle, after which the cubicles may
also be removed.
DANGER: When the station is in operation, make sure that there is an adequate safety
13.2 Disposal
In every country there are companies specialized in the proper disposal of electronic waste.
NOTE: Strictly observe all local and national regulations when disposing of the device.
Equipment type;
To be simplified, user can provide such information by finishing the following table and send it to
manufacture.
NR RCS-985G
Ordering form
Item RCS-985G * * * * * * *
Protective Functions
Standard Configuration
Communication Port
EIA-232 and 2 x EIA-485 A
EIA-232 and 2 x Optical converter B
EIA-232 and 2 x Ethernet*
Communication medium
Shielded twisted pair wires T
Optical Fiber O
Communication Protocol
IEC 60870-5-103 S
MODBUS M
IEC 61850* E
Terminal Type
Jointing Terminal C
Screw terminal Block S
Color of panel (Inter Grey, Apple green and light camel grey are recommended colors).
In the latest version of the instruction manual, several descriptions on existing features have been
modified.
Chapter16 ANNEX
Connect RS-232 communication port of the computer and that mounted on left side of front panel
of RCS- 985 protection equipment by a cable with DB-9 connectors on both ends. Run the
program RCSPC. If the connection is correct, the screen will display ―RCS-985B3YD connected‖,
see Figure 16.1-1 . Even if the computer is off line, this picture will be still displayed but the words
about connection will disappear.
There are 3 bars on top of the screen, from top to bottom: title bar, menu bar and tool bar, see
Figure 16.1-2.
First, click the first button of tool bar parameter, dialog box of communication parameters is
displayed, see Figure 16.1-3. Only the parameter of ―COM port‖ shall be configured as the number
of port of computer that is actually connected with the equipment, other parameters shall be
configured as the same as displayed values in figure.
The title bar shows only title of the program and needs no explanation. Menu bar and tool bar are
described as follows:
1) File
There is only one item in pull-down menu File, i.e., Exit. Click Exit(X), the program will be exited.
2) Execute
There are three items in pull-down menu Execute: Setting(E), Download(D) and Trip_Test(T).
Click Setting(E), entering settings reading and modification part of the program, please refer to
section 16.1.3 for details.
Click Trip_Test(T), entering trip test part of the program, please refer to section 16.1.5 for details.
3) View
There are five items in pull-down menu View: Toolbar(T), Status(S), Report(L), Status(Z) and
Message(M).
Item Toolbar specifies whether the tool bar shall be displayed. When the tool bar is displayed, a
symbol ―√‖ is put before ―Toolbar (T)‖. If this item is clicked then, the tool bar will be hidden and
the symbol ―√‖ will disappear.
Item Status(S) specifies whether status bar in the bottom of the picture shall be displayed.
Click Report(L), entering Report treatment part of the program, please refer to section 16.1.4 for
details.
Click Status(Z), entering Sampled value display part of the program, see section 16.1.2 for details
Click Message(M), data flow between RCSPC program and the protection equipment will be
displayed. This is used not for the user version but development version of the program.
4) Set
There are five items in pull-down menu Set: Switch_CPU_MON(P), Parameter(C), Back_color(B),
Font-Color(F) and Font(O).
If there is a symbol ―√‖ before item Switch_CPU_MON(P), that means data acquired by module
CPU are displayed currently, see Figure 16.1-1. If the item Switch_CPU_MON(P) is clicked then,
the data displayed will be changed to those acquired by module MON, see Figure 16.1-5.
Meanwhile, symbol ―√‖ will disappear.
Function of item Parameter(C) is the same as the first button of tool bar parameter. Click this
item, dialog box of communication parameters will be displayed, see Figure 16.1-3.
Click Back_Color(B), dialog box of background color is displayed. The user can select preferred
color for background displayed.
Click Font_Color(F), dialog box of font color is displayed. The user can select preferred color for
font displaying.
Click Font(O), dialog box of name, style and size of the font is displayed. The user can select the
preferred ones for font displaying.
5) Help
There are three items in pull-down menu Help: Help(H), Version(N) and About RCSPC.
Click Help(H), commands used for the program will be displayed. It is not necessary for the user
to use these commands, and no further information about them is presented here.
Click Version(N), historical record about time and description of updating of this program is
displayed.
Click About RCSPC, developer of this program and copyright declaration will be displayed.
1) Parameter
Function of this button is the same as that of item Parameter(C) of menu Set of the menu bar.
Click this button, dialog box of communication parameters will be displayed, see Figure 16.1-3.
2) Data parameter
Click this button, other parameters will be displayed. They are data start address, data block size,
single data block number, report data number, etc, 11 items in total. These parameters are
configured already in the coefficient y and needs no further Configuration on site.
3) Device type
Click this button, a small dialog box ―please enter device type‖ is displayed. Type of the
protection equipment shall be entered. In the RCS-985 case, the device type is 985B3YD. This is
used mainly for the user to make configuration in off line condition.
4) Setting
Function of this button is the same as item Setting(E) of menu Execute of menu bar. Click this
button, i.e. entering settings reading and modification part of the program; Please refer to section
16.1.3 for details.
5) Status
Function of this button is the same as item Status(Z) of menu View of menu bar. Click this button,
entering Sampled value display part of the program; Please refer to section 16.1.2 for details.
6) Report
Function of this button is the same as item Report(L) of menu View of menu bar. Click this button,
entering Report view part of the program; Please refer to section 16.1.2 for details.
7) Trip test
Click this button, entering trip test part of the program; Please refer to section 16.1.2 for details.
8) Switch to command
When several dialog boxes are displayed, and the operator wants to enter Command mode but
not close dialog box, this button can be used to switch on Command and hide dialog boxes.
However, it is not needed for the user on site generally.
9) Download program
10) CPU<–>MON
Function of this button is the same as item Switch_CPU_MON(P) of menu Set of menu bar. Click
this button, data displayed will be changed between those acquired by module CPU and module
MON one after another.
Function of this button is the same as item Font(O) of menu Set of menu bar.
Function of this button is the same as item Font_Color(F) of menu Set of menu bar.
Function of this button is the same as item Back_Color(B) of menu Set of menu bar.
Six buttons on right hand of are all gray. They are used not for this
version but others of this program.
Click this button, all activated output relays and signal relays will be reset.
16) Help
Function of this button is the same as item Help(H) of menu Help of menu bar.
Besides, some shortcut keys on keyboard of the computer have same functions with items of
menu of menu bar or buttons of tool bar:
F1 — same as item Help(H) of menu Help and button Help of tool bar;
F2 — same as item Parameter(C) of menu Set and button Parameter of tool bar;
F3 — same as item Switch_CPU_MON(P) of menu Set and button CPU<->MON of tool bar;
F4 — same as item Setting(E) of menu Execute and button Setting of tool bar;
F5 — same as item Status(S) of menu View and button Status of tool bar;
F6 — same as item Report(L) of menu View and button Report of tool bar.
Click item Status(S) of menu View or button Status of tool bar, real time sampled analog
values will be displayed.
exchanged to each other by clicking two arrows on left hand of the bottom or pull down
Page 2 shows mechanical protection inputs as well as others binary input status where ―1‖ is ―yes‖
and ―0‖ is ―no‖.
Page 3 shows pickup of protective elements where ―1‖ is ―activated‖ and ―0‖ is ―inactivated‖.
Figure 16.1-6 a) and b) are pictures of value of module CPU, and can be changed to value of
module MON by CPU-MON choose item at the right hand of bottom of this page.
Pull down box at right hand of the bottom is gray. That means these values exist only in module
MON and cannot be read from module CPU.
This part is used for reading and modification of settings of the equipment. Click item Setting(E)
of menu Execute or the fourth button Setting of tool bar, settings will be displayed. For
example, Figure 16.1-9 shows the parameters of the equipment.
In the same way, user can click other labels in picture of Setting(E) to read and modification all the
settings of the equipment.
There are 7 buttons in bottom of every picture of the part Settings reading and modification. From
left to right, they are: PRINT, DEFAULT, UPLOAD, DOWNLOAD, READ, SAVE and CLOSE and
depicted as follows:
2. DEFAULT Read and display default settings of RCS-985 from file of RCSPC.
3. UPLOAD Read and display actual settings of RCS-985 connected with the PC.
If default settings are displayed and button UPLOAD is pressed, default settings displayed will be
replaced by actual settings of the protection equipment, in which, the settings different from default
settings will be displayed in red. Vice versa, if actual settings are displayed and button DEFAULT
is pressed, actual settings displayed will be replaced by default settings of the protection
equipment, in which, the settings different from actual settings will be displayed in red.
16.1.4 Report
There are 3 kinds of reports in this program: tripping report, self-diagnose report and change of
status report. The tripping report is displayed first.
Click item Report(L) of menu View, or click the sixth button of tool bar, tripping report will be
displayed for a moment. It is the report of operation of protection relays, including number of the
report, time of pickup of protection, time interval from pickup to operation, name of the operating
protection element and the faulty phase, see Figure 16.1-12.
In order to save time for displaying, report of the latest 3 tripping is displayed firstly. Click the fifth
button REFRESH of eight buttons in the bottom of the picture, complete tripping report will be
displayed after a longer delay.
If oscillogram record of a fault tripping is needed, the record item shall be clicked first, color of this
item will be changed to light blue, click the fourth button RECORD at the bottom, then RCSPC
starts to read oscillogram data from the protection equipment.
Oscillogram data is massive and more time is needed to read it. A dialog block of saving the data
displayed as a file will be displayed when data reading is completed. If these data are saved in a
file and then oscillogram recorded can be displayed by oscillogram analysis program Drawing.exe
or Wave.exe developed by our Company. The oscillogram can be analyzed also if needed.
The sixth button SAVE at the bottom is used for saving the report as a file in the computer. The
seventh button PRINT is used to print the report. All reports of this program can be saved as file
or printed in this way. The eighth button CLOSE is used to close the picture displayed.
After click the second button FAIL at bottom of Figure 16.1-13, self-diagnose report will be
displayed for a moment. It is the report of hardware failures, overload, cooling system initiating or
other abnormal events detected by the equipment.
The records are stored in cyclic non-volatile memory and up to 32 events can be recorded.
After click the third button SW CHG at the bottom of Figure 16.1-13, change of status input report
will be displayed for a moment. It is the report of binary input, starting status of the equipment,
including serial number of record, time of the change and brief description about the change.
The records are stored in cyclic non-volatile memory and up to 32 events can be recorded.
Object of the tripping test is to check activation of the tripping or signal output relays of the
equipment during the test not by applying voltages and currents on the equipment but by operation
of the program.
Object of the communication with the host computer test is to check correctness of the message
sent from the equipment during the test not by applying voltages and currents on the equipment
but by operation of the program.
Then, click item Trip_Test(T) in menu Execute, or click the seventh button of tool bar Trip
test, picture of protection tripping test will be displayed as shown in Figure 16.1-14.
There is only one item in the picture, i.e., Test_Differential_Trip, differential protection tripping test,
click the test button , related output relays will operate, and correspondent signals
will be sent. Correctness of these operations can be checked and this button changes to
then.
Click the red reset button again, all of the operated relays will dropout, test status will be resumed
and the reset button will return to .
First, the parameters of [Test_Trip_Option] and [Test_Comm_Option] (if available) shall be set
as enabled.
Click label in Figure 16.1-15, picture of communication with the host computer will
Click test button of any item, relevant activation of this item will be recorded in the
report.
The report will be sent to the host computer, and correctness of the communication can be
checked then.