Вы находитесь на странице: 1из 4

VOLUME FOUR NUMBER ONE

(SUPERSEDES VOLUME ONE NUMBER ONE)

SYNOPSIS
A N H V A C N E W S L E T T E R F O R B U I L D I N G O W N E R S A N D M A N A G E R S

In this issue... Your Mechanical Room and


• ASHRAE 15-1994
What’s the connection to your
ASHRAE 15-1994: 2001 Update
mechanical room? . . . . . . . . . . . . 1
How familiar are you with your build- embodied in Standard 15-1994 of
• Your Liability ing’s mechanical equipment room? These the American Society of Heating,
When must you comply with areas are often “out of sight, out of mind” Refrigeration and Air Conditioning
ASHRAE 15-1994? . . . . . . . . . . . . 2 for building owners and managers. But Engineers (ASHRAE). It’s important,
operational and safety guidelines for therefore, that you be familiar with this
mechanical rooms document and how
• Check It Out are spelled out in The standard is intentionally written it affects the design,
Safety checklist for your industry standards operation and upgrad-
in code language so it can be
mechanical room . . . . . . . . . . . . . 2 that you, as a profes- ing of your building.
sional, are liable to adopted nearly verbatim by model The standard
comply with just by code associations — and it can be is intentionally written
• Compliance
being aware of difficult to understand. in code language so it
What steps should you take to them. And since can be adopted nearly
comply with ASHRAE 15-1994? . . . 3 these standards are commonly verbatim by model code associations —
used to draft municipal and it can be difficult to understand.
• Refrigerants building codes, they This issue of Synopsis provides a basic
Understanding their properties . . . . . 4 may also be the law overview of mechanical room safety
in your locale. issues in relation to the standard.
Today’s mechan- It is not intended to be a comprehensive
ical room safety review of all requirements, nor should
Want to know more about ASHRAE
standards it be a substitute for reading the doc-
15-1994: 2001 Update? Visit our are ument itself. It will, however, help
web site at www.carrier.com, click you to know what to look for
when reading the standard
on Commercial/Industrial Heating and discussing it with
and Cooling Systems and see Newsletter consulting/specifying
engineers and con-
under Resource Center, download tractors. Also
the publication HVAC Analysis, provided are sugges-
Vol. 4, No. 1, written specifically tions based on good
practice installations.
for consulting engineers.
FIGURE 1
Mechanical Room Safety Check C H E C K I T O U T
Location of
roof drains? 5 Location of inlet
vents in relation

3 4 to exhaust outlets?

Rupture disk
Whether you’re evaluating an existing mechanical room or
2 outlet locations?
assessing the situation before acquiring a building, a compre-
Purge
vents to Are common headers
hensive safety check is a must. Here’s a checklist of some key
outside? used only for common
refrigerant?
6
Is access to
mechanical
potential trouble spots, as illustrated in Figure 1.
8 room restricted?
Are safety
rupture
lines the 1 Are there low areas in the mechanical room?
9 right size?
Are chiller drain
Is there
Check the condition of pits or other areas below floor
valves secure?
a tight seal
on doors? level. They may hold chemical residues such as acids,
Are rubber mats
used to cover spilled refrigerant, cleaning solvents, etc.
Are there any the drains when
pit areas in
the room?
not in use? 2 Where does the purge vent?
Where do the
1 floor drains
empty?
A conventional purge (not high efficiency) loses up
7 to 20 pounds of refrigerant for every pound of non-
condensible air it removes from the system. All purges
should vent outside. If high efficiency purges are used,
they should be specified per the new ARI (American
Refrigeration Institute) Standard 580-2000. Some new
A Standard For Mechanical standard. ASHRAE 15 typically high efficiency purges have been vented to relief disk
Room Safety applies in several ways. pipes. This is not a good practice as refrigerant may
condense to the thin rupture disk resulting in failure
ASHRAE Standard 15 was first issued Mechanical Room Changes due to corrosion.
as a safety code in 1930, the same year The CFC and HCFC (hydrochlorofl- 3 Where are safety rupture disk outlets located?
that CFC (chlorofluorocarbon) refriger- urocarbons, i.e. R-123, R-22) refrigerant Thin carbon rupture disks are often vented through
ants were introduced in the United production phaseout has raised the the roof or side wall. Locations should be at least 15
States. With increasing refrigerant critical issue of what to do with existing feet above ground level.
regulations and phaseouts, as well as the chillers. There are pros and cons to each 4 Could roof drains collect refrigerant? If you lose
development of alternative refrigerants, possible solution — containment, con- refrigerant from an exhaust outlet and it vents above a
2
the standard has undergone unusually version or replacement — and therefore, flat, curbed roof, the refrigerant could lay across the roof
rapid change over the last decade. a thorough evaluation is necessary. and find the first exit — probably down the roof drains
It was revised in 1992 and again in It is particularly important to understand and into a sewer system.
1994, followed by that if the type 5 Are exhaust outlets near inlet vents? Chiller
several addenda in Your local building codes may of refrigerant in a safety relief devices typically vent outdoors, usually
the late 1990s. have already been rewritten to reflect chiller is changed through the roof. Check the vent’s proximity to air
The primary ASHRAE 15-1994. or if the chiller intakes — they should be at least 20 feet apart.
goal of the standard itself is replaced, 6 Is access to the mechanical room restricted?
is to mitigate risks to the environment, ASHRAE 15-1994 applies. Section 5.3 These potentially hazardous spaces contain systems
to mechanical room operators and, of the standard reads: “A change in the critical to a building’s operation. The mechanical room
ultimately, to the general public. type of refrigerant in a system shall not door should have a tight seal to isolate the room in an
Since refrigerants have varying degrees be made without the notification of the emergency, as well as prominent signage limiting
of toxicity and flammability, specific authority having jurisdiction, the user access to trained personnel only.
procedures and training are needed and due observance of safety require- 7 Where do the floor drains empty? If your chiller
to use them safely. ments. The refrigerant being considered and occupied space share the same floor, they may also
shall be evaluated for suitability.” (The share a drainage system. Check to see if drains in the
ASHRAE 15-1994: Your addition of containment devices, such as occupied space (i.e., in restrooms) are connected to
Liability high efficiency purges and back-up relief those in the mechanical room. Imagine losing a full
valves to your existing equipment, how- charge and “finding” it in a restroom!
Even if your local codes haven’t ever, does not trigger application of 8 Are rupture lines the right size and length?
yet been updated to reflect ASHRAE the standard.) For convenience, safety devices will run into a common
15-1994, compliance with the standard Upgrading a mechanical room header if they have common refrigerants. Chillers with
can minimize your legal liability by to meet the standard typically adds different refrigerants should never share common
demonstrating that you have gone to 11 to 13% to the total chiller headers. An improperly sized header can exacerbate
the furthest extent possible to promote conversion/replacement project problems in an emergency, when the discharge capacity
mechanical room safety. And, as previ- cost, depending on the room’s age of safetylines is put to the test.
ously noted, as a building professional and location. This expense should 9 Are chiller drain valves secured? These valves are
or owner, you are considered liable for be factored into your refrigerant an easy way for an inexperienced technician to get into
compliance if you are aware of the planning cost analysis. trouble. Make sure the valves are locked off.

SYNOPSIS
Building Code Compliance Key Steps to Compliance Sizing of Relief and Rupture Devices
Your local building codes may ASHRAE 15-1994 specifies the
already have been rewritten to reflect When examining your mechanical appropriate sizing of pressure relief
ASHRAE 15-1994. Many of the major equipment room for compliance with devices. It also includes rating formulas
U.S. building code jurisdictions have ASHRAE 15-1994, here are some of for discharge capacity of rupture mem-
incorporated the standard into their the primary issues to consider. bers and maximum length of discharge
model codes, and state and municipal piping. When converting a chiller to
authorities are following suit. Do I Need a Mechanical Room? a new refrigerant, it is critical to check
To find out what’s happening with The standard lists allowances for the size of existing safety devices to
codes in your area, meet with your all refrigerants in pounds of refrigerant be sure they are suitable.
local building inspector. It’s important per 1,000 cu. ft. of occupied space
to be as well informed as possible, (this allowance is calculated for the Refrigerant Sensors
especially before making any mechanical occupied space in the building and All mechanical rooms must have sen-
room changes. does not apply to the mechanical room). sors capable of detecting refrigerant loss.
These figures represent the maximum They should be positioned where vapor
Equipment Design refrigerant levels allowable for refrigera- from a refrigerant leak would most likely
Manufacturers’ labels reference com- tion equipment installed in “occupied” concentrate, providing early warning
pliance with the standard, so it’s easy to portions of the building. If your system so that personnel can prevent dangerous
check to ensure that anything installed has more than the allowable amount exposure and catastrophic refrigerant
in your building will comply. of refrigerant, it must be housed in a loss. The sensors should trigger an alarm
separate mechanical room. and mechanical ventilation, as well as
Contracts activate visual and audible alarms inside
It’s a good idea to include the specifi- Purge System and Relief Devices and outside the mechanical room.
3
cation that all equipment and service The standard specifies that all purge
“must be in compliance with the latest systems (including high efficiency sys- Mechanical Ventilation to
the Outdoors
ASHRAE 15” as standard language for tems) and other relief devices must vent
all your installation submittals, outside. Even the highest-efficiency Mechanical rooms must be vented
service agreements purges lose some to the outdoors using mechanical
and contracts. refrigerant. If vented ventilation. ASHRAE provides a
to the chiller relief formula for calculating ventilation
piping, refrigerant can capacity requirements.
condense, coming into
contact with safety rupture disks Access Restrictions
and promoting corrosion. Mechanical rooms must have tight-
fitting doors that open and close freely
(i.e., no fire doors), and any other open-
ing that would permit the passage of
refrigerant must be sealed. Each entrance
to a refrigerating machinery
room must have a legible
permanent sign that reads
“Refrigerating Machinery
Room — Authorized
Personnel Only,” and should commu-
nicate that when an alarm has been
activated, entry is forbidden except
by trained personnel who can
address emergencies.

SYNOPSIS
FIGURE 2
ASHRAE 34 Safety Group
Type A Type B
Lower Toxicity Higher Toxicity

High A3 B3
Flammability Propane
Refrigerant Storage Many of these sensors require fre-
Section 11.5 of ASHRAE quent calibration. (Higher quality
15-1994 reads: “The total amount sensors using infrared technology are
of refrigerant stored in a machinery preferred over metal-oxide types, as Low A2 B2
room in all containers not provided they remain close to set calibrations.) Flammability R-142b, 152a Ammonia
with relief valves and piped in
accordance with the standard, should Emergency Planning
not exceed 330 lbs.” This is designed The original version of ASHRAE No Flame A1 B1
to allow building owners to store 15-1994 mandated the availability Propagation R-11,12,22, R-123, SO2
adequate quantities of refrigerant for of self-contained breathing apparatus 114,500,134a
chiller servicing in separate, approved (SCBA) for refrigerant leak situations.
storage tanks. However, you should Addendum “d” to the standard has
check your local building and fire removed this requirement because R E F R I G E R A N T S
codes for possible exceptions. of the difficulty of implementation
for many commercial buildings.
Relief Discharge Location The addendum mandates an Determining which particulars of ASHRAE 15 apply to your
The discharge location of relief emergency response plan that will situation depends in part on the type of refrigerant your air
devices must be at least 20 feet away allow appropriate measures according conditioning system uses. Another important document,
from any ventilation openings, and to the severity of each potential ASHRAE 34-1992, “Number Designation and Safety
not less than 15 feet above ground emergency. Some considerations for Classification of Refrigerants,” classifies refrigerants in two
level (to avoid spraying someone the plan include: types of detection ways: toxicity and flammability (Figure 2). Generally, the
with refrigerant). and alarms; ventilation activation; higher the toxicity and flammability, the higher the potential
respiratory protection; evacuation; for risk and liability.
4 Combustion Device Limitation and, most importantly, a properly Toxicity
ASHRAE 15-1994 prohibits the trained response team. ASHRAE 34 divides refrigerant compounds into two
location in a mechanical room of any groups: (A) low-toxicity and (B) high-toxicity. The designa-
open-flame device using combustion Read ASHRAE 15-1994 tion is determined by each compound’s allowable exposure
air from inside the room. On the Clearly, there are many issues limit (AEL). Compounds with AELs of more than 400 parts
other hand, an open-flame device to consider in order to achieve per million (ppm) are classified as type A, while those with
such as a boiler may be located in a compliance with ASHRAE 15- AELs of less than 400 ppm are classified as type B. The
mechanical room — if combustion 1994 and its addenda. Your best refrigerants of the past, such as CFC-11 and HCFC-22
air is drawn from a sealed outside strategy is to obtain a copy of the had very high safe exposure limits, as does the alternative
source, or the boiler is shut off standard. This issue of Synopsis refrigerant HFC-134a. One popular alternative refrigerant,
through the use of refrigerant and consultation with an HVAC HCFC-123 has a very low allowable exposure limit (30 ppm)
sensor cut outs. expert can help you clarify and and is classed along with ammonia and sulfur dioxide as
understand the standard as it higher in toxicity.
Room Dimensions applies to your building. Flammability
The new standard defines an ASHRAE 15-1994 offers many ASHRAE 34 further classifies refrigerants according to
appropriately sized mechanical room good, safe solutions, which can and their flammability: (1) no flame propagation; (2) low flamma-
as one that allows access to all equip- should become part of your overall bility; and (3) high flammability. Ammonia, for example, is
ment, including adequate space for strategic refrigerant planning. considered a low-flammability refrigerant, while HCFC-22
service and maintenance, as well A sound plan will help you to meet and HFC-134a have no flame propagating properties.
as operation. the increasingly complex challenges Building owners and managers should also be aware
surrounding refrigerant regulation — that some of the newer alternative refrigerant blends contain
Periodic Testing and maintain a safe environment flammable ingredients. Although their flammability is lowered
Ventilation systems and sensors for your building’s employees when they are mixed into a blend, flammability may still
must be periodically tested in and occupants. be an issue in leak situations. When blends leak, the
accordance with the manufacturer’s highest-pressure compound exits first. The lowest-pressure
recommendation and/or local compound is likely to be left in the vessel, and in this state
jurisdiction. This is particularly the mixture may be highly flammable. A recent addendum to
important for refrigerant sensors ASHRAE 34 requires a blend to be classified according to the
that are detecting compounds with highest potential flammability or toxicity of its components.
low allowable exposure limits.

Вам также может понравиться