Вы находитесь на странице: 1из 16

Power System Protection Dr.Prof.

Mohammed Tawfeeq Alzuhairi


Tutorial Nos. 4 & 5

1.A radial distributor line consists of four substations designated A,B,C,and D of powers 40
, 30, 25, and 20 MW respectively . The substations are connected by transmission lines
having the following impedances per phase (p.u.):

AB = j 0.20 ; BC = j 0.10 ; CD = j 0.10 .

The system is fed at A with 33 kV from a source of negligible impedance. All circuit breakers
having operating time of 0.1 second and are controlled by relays fed from current
transformers with ratios: 400/5A at D, 800/5A at C, 1000/5A at B and 1500/5A at A. The
characteristic of the overcurrent relay used is given in Fig. 1. Sketch the arrangement of the
system and determine the satisfactory relay settings of breakers at D and C considering only
3-phase fault with short circuit MVA = 75.

Fig.1

1
2. Figure 2 shows a simple radial transmission line system. Lines AB , BC and BD have an
impedances of 0.8 Ω / km , 1.0 Ω / km and 0.8 Ω / km respectively. The distance relay at bus A is fed
by current transformers rated at 2000/5 A and a voltage transformers rated at 354 kV/ 120V. Find
zone 1 and zone 2 setting of the relay.

A B

100km D

100 km

40 km

Fig.2

3. Consider the 230 kV transmission system shown in Fig.3 Assume that the positive –
sequence impedances of lines LAB and LBC are 1+j 10 and 1.5 + j 15 Ω respectively. If the
maximum peak load supplied by the line LAB is 100 MVA with a lagging power factor of 0.9,
design a three – zone distance relaying system for RAB impedance relay by determining the
following:

(a) Maximum load current.

(b) CT ratio.

(c) VT ratio.

(d) Impedance measured by relay.

(e) Load impedance base on secondary ohms.

(f) Zone 1 setting of relay RAB.

(g) Zone 2 setting of relay RAB.

(h) Zone 3 setting of relay RAB.

(i) Draw the zones of protection for the system and suggest time setting for each
zone.

2
A B C

RAB RBC RCD

Fig.3

4. A single –phase two – winding 100kVA 2400 / 240 V step down transformer is to be
differentially protected as shown in Fig.4.

(a) Choose appropriate CT ratios.

(b) Verify that the relay will not operate with the chosen CT ratios.

(c) Determine the ratio k= Nr: No such that the relay will tolerate a mismatch in current up to
20% of I1

Fig.4

5. (a) Consider a three-phase Delta-Wye-connected two-winding transformer bank that is to


be protected by using percentage differential relays. Assume that the high-voltage side is
connected in delta and sketch the necessary wiring diagram for connecting three differential
relays one for each phase.

(b) For a 1000kVA, 11kV/400V, delta/star, three-phase transformer, (i) calculate the turns
ratio of the current transformers of a nominal 5A secondary current.
(ii) Determine the ratio k if the relay is to tolerate a mismatch in current of up to 30 %.

3
6. Fig. 5 shows a 345kV transmission loop (ring system). Table 1 gives positive – sequence
line impedances as well as CT and VT ratios at B12 for the system shown.

(a) Determine the impedance relay settings (Z1, Z2, Z3) for the B12 three-zone, directional
impedance relay connected as shown in Fig.3B. Consider only solid, three-phase fault.

(b) The maximum current for line 1-2 during emergency loading conditions is 1500 A at a
power factor of 0.95 lagging. Verify that B12 does not trip during normal and emergency
loadings.

Table 1

Fig.5

7. (a) Consider a three-phase 138 / 69 kV ,75 MVA , delta-wye – connected two – winding
transformer bank that is to be protected by using percentage differential relays. Assume that
the high voltage side is connected in delta and sketch the necessary wiring diagram for

4
connecting three differential relays one for each phase. indicate in your diagram all the
currents flowing through the restrain windings of all relays.

(b) For the above transformer, choose CTs ratio of the relays for both the primary and
secondary sides. Also find the ratio of the CT secondary of the HV side to the restrain
winding current at LV side.

(Ans: HV side 400/5 , LV side : 700/5 , )

8. Consider the system shown in Fig. 6. Assume that the three lines are identical with positive
sequence impedance Z1 = j 0.1 p.u. Assume that the six line breakers are controlled by zone
distance and directional relays. Consider only three-phase faults:

(a) Determine zone 1, Zone 2 and Zone 3 settings for all distance relays in per-unit.

(b) If the CTs are rated 400:5 A , and the VTs 133kV:115 V, convert the settings into ohms .

( c) Discuss relay operations for a fault at point X, assuming X is 10% down the line L31
from bus 3.

Fig.6

5
Power System Protection

Tutorial 4 Typical problem solutions

Problem-1

6
7
Problem -2

Solution

8
Problem -3

9
Problem 4
Solution

10
Problem 5
Solution

11
12
Problem 6
Solution

(a)

13
14
Problem 7
Solution
The solution is shown in figure below:

(b)

15
Problem 8
Solution
(a) The reach are given by :

Zone 1 : Z1 = 0.1 x 80% = 0.08

Zone 2 : Z2 = 0.1 X 120% = 0.12

Zone 3 : Z3 = 0.1 x 250% = 0.25

Because of systems symmetry, all six sets of relays have identical settings.

(b) Recall that

The equivalent instrument transformer’s secondary quantities are :

(c ) Locate point X on the diagram in Figure . We comment on all line breaker operations:

B31 fault is in zone 1 , instantaneous operation ,

B32 directional unit blocks operation.

B23 fault is in zone 2 , delayed operation. B31 should trip first , preventing from
tripping .

B21 fault duty is light. Fault in zone 3 if detected.

B12 directional unit blocks operation.

B13 fault is in zone 2 (just outside of zone 1) , delayed operation.

16

Вам также может понравиться