Main Sheet UTKALBIDYUT

DESIGN OF SOLAR PANEL / BATTERY BANK / INVERTOR MANAS RANJAN SUBUDHI, E-MAIL : m.of.subudhi@gmail.com
Battery Bank Details
Solar System Type Without Grid System Nominal cell voltage 2 Volt
Battry Back requirement YES Battery type VRLA ENTER LOAD DETAIL
Battery Back Up Time Requiremet Hours 15 Hours OK End cell voltage 1.75 Volt
Load Type AC 1PH 900 15 Cell voltage after satisfactory charging 2.2 Volt
220 Volt 15 No. of 2 Volt cells selected 120 Nos
Solar System Single Battery Sytem type Single
Future Spare capacity 10% Design Margin 25%
Largest Motor /AC details 2500.00 Watt Ageing Factor (As per IEEE 485-1997) 1.25 =>1.25 BATTERY DUTY CYCLE
Solar system Cost / KW With Batteries Rs. 75,000.00 Min Ambient Temp 25 0
C Sl.no. Load Duration(Min.) Load (A)
Annual Intrest & Depriciation cost 4.0% Temperature Correction Factor 1 1 0 to 1 Hour. 70.83
Electrical Load Running By DG YES (As per Manufacturer's Standard) 2 1 to 2 Hour 70.83
Solar Panel Detail Capacity Rating Factor 'Kt' for Battery performance 3 2 to 3 Hour 70.83
Losses in Wire,Connection,Battery 10% % For 15 Hours 9.7 4 3 to 4 Hour 70.83
Daily Sunshine Hours 5 4 to 5 Hour 13.54
In Winter 5.5 Hrs. (For India 4 To 6 Hrs) No. of 2 Volt cells selected 120 Nos 6 5 to 6 Hour 13.54
In Summer 6 Hrs. 7 6 to 7 Hour 13.54
In Monsoon 5.5 Hrs. Number of String of Battries 1 8 7 to 8 Hour 13.54
Minimum Daily Sunshine Hours 5.5 Hrs. 19.0 1140 Battery Bank's Voltage 240 Volt 9 8 to 9 Hour 0.00
Total Solar Power need 205200.00 Watt.Hr/Day 10 9 to 10 Hour 13.54
Total Solar Power after Correction Factor 287280.00 Watt.Hr/Day Minimum Capacity required 417.92 AH 11 10 to 11 Hour 13.54
Solar Array Size Requirement 52232.73 Watt Design Margin 125% 12 11 to 12 Hour 18.23
Select Size of Solar Panel 250 watt 12 Volts Ageing Factor 1.25 13 12 to 13 Hour 18.23
Solar Panel Connetion Series-Parallel Temp. Correction Factor 1 14 13 to 14 Hour 18.23
Number of Parallel String for Solar Panel 15 Total Battery Capacity 652.99 AH 15 14 to 15 Hour 18.23
Number of Series String for Solar Panel 20 16 15 to 16 Hour 18.23
The Selected Battery Size : 800 AH 17 16 to 17 Hour 18.23
18 17 to 18 Hour 75.52
19 18 to 19 Hour 75.52
:Result of Solar Panel Design: 20 19 to 20 Hour 75.52
Size of Each Solar Panel 250 watt 12 Volts BATTERY DUTY CYCLE DIAGRAM
Type of Connection For Solar Panel Series-Parallel Connection 75000
Selection of Solar Panel Connection: OKEY 80
Total Solar Panel string Voltage 240 Volt
Total Watt of Each Solar Panel String 250 Watt 21 Amp 70
Number of String for Solar Panel 15 Nos
Total No of Solar Panel in Each String 20
60

Total Watts of Solar Panel 75000 Watt 313 Amp


Total Nos of Solar Panels 300 Nos
50

40
:Size of Invertor:
32
Maximum Continuous Load 14500 Watt 75 30
Spare capacity 1450 Watt 25 26
Full load current of largest motor 2500 Watt 25
Effieciency of Invertor 90% 20
Required UPS Size 22.15 KVA

The Selected Battery Size : 25 KVA 10

FINAL BOQ AND SPECIFICATION FOR SOLAR PANEL, BATTERIES AND INVERTOR
0
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Wattage Solar Panel 250 Watt
Voltage of Solar Panel 12 Volt
Current Of Each Solar Panel 20.83 A
Number Of Solar Panel 300 Nos.
Conection of solar Panels Series-Parallel
Annual Saving and Pay Back Period
Total Wattage of Solar Panel System 75000 Watt Before Soslar System Calculate Efficiency & Unit Rate of Power of D.G set
Total Volatge of Solar Panel System 240 Volt Electricity Charge / Kw 35 Rs D.G Size ( Kva ) 25
Total Current of Solar Panel System 313 A Unit Consumed / Year 74898 Kwh Diesel Consumption (Liter) 100
Battieries Back up Time Hours 15 Energy Charge/Year Rs. 2,621,430 KWH Reading of Meter 200
Battieries Capacity 800 AH After Solar system M.F of KWH Meter 1
Battieries Voltage 2 Volt Unit Consumed / Year 0 Kwh Diesel Rate /Liter (Rs) Rs. 70
End Cell Volatge 1.75 Volt Energy Charge/Year Rs. 0 KWH/Liter (Unit Per Liter) 2
Number of Battieries 120 Nos. Capital Cost of Solar system Rs. 5,625,000
Battieries System Type Single Annual Interest and Deprecation Rs. 225,000
Invertor Size 25 KVA Annual Saving Rs. 2,396,430
Load Type AC 1PH 230 Volt
Pay Back Period 2.35 Years Unit Rate of Power (Rs) 35

LOAD DUTY CYCLE DIAGRAM


16000

14000

12000

10000
Wattage -->

8000

6000

4000

2000

0
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
HOUR 2600 2600 3500 3500 3500 3500 3500 3500 14500 14500 14500 14500 14500 14500 13600 13600 13600 13600 13600 13600 2600 2600 2600 2600