Академический Документы
Профессиональный Документы
Культура Документы
Psychrometric Processes
The various psychrometric processes involved in air conditioning to vary the psychrometric
properties of air according to the requirement are as follows:
1- Sensible Heating
The heating of air, without any change in its specific humidity, is known as sensible heating.
Let air at temperature (td1) passes over a heating coil of temperature, (td3) as shown in Fig. (1).a .It
may be noted that the temperature of air leaving the heating coil (td2) will be less than (td3). The
process of sensible heating, on the psychrometric chart, is shown by a horizontal line 1-2 extending
from left to right as shown in Fig. (1).b. The point 3 represents the surface temperature of the
heating coil. The heat absorbed by the air during sensible heating may be obtained from the
psychrometric chart by the enthalpy difference (h2-h1) as shown in Fig. (1) b. It may be noted that
the specific humidity during the sensible heating remains constant (i.e. W 1 = W2). The dry bulb
temperature increases from (td1) to (td1) and relative humidity reduces from 1 to 2 as shown in
Fig. (1) b. The amount of heat added during sensible heating may also be obtained from the
relation:
q h2 h1
c pa ( t d 2 t d 1 ) Wc pv ( t d 2 t d 1 )
( c pa Wc pv )( t d 2 t d 1 )
c pm ( t d 2 t d 1 )
The term (cpa+ W cpv) is called humid specific heat (cpm) and its value is taken as 1.022 kJ /kg
K.
Heat added,
q 1.022( t d 2 t d 1 )kJ / kg (1)
Notes: For sensible heating, steam or hot water is passed through the heating coil. The heating coil
may be electric resistance coil.
The heat rejected by air during sensible cooling may be obtained from the psychrometric chart by
the enthalpy difference (h1-h2) as shown in Fig. (2)b.
q h1 h2
c pa ( t d 1 t d 2 ) Wc pv ( t d 1 t d 2 )
( c pa Wc pv )( t d 1 t d 2 )
c pm ( t d 1 t d 2 )
Heat rejected,
It may be noted that the specific humidity during the sensible cooling remains constant
(i.e. W1= W2). The dry bulb temperature reduces from (td1) to (td2) and relative humidity increases
from 1 to 2 as shown in Fig. (2)b.
For air conditioning purposes, the sensible heat per minute is given as:
Q s = ma cpm ∆T = V̇ ρ cpm ∆T kJ/min
Where:
𝑚3
V̇ = Rate of dry air flowing in ( ),
𝑚𝑖𝑛
Density of moist air at 20ºC and 50% relative humidity = 1.2 kg/m3 of dry air,
cpm = Humid specific heat = 1.022 kJ 1kg K, and
T t d 1 t d 2 = Difference of dry bulb temperatures between the entering and leaving
conditions of air in o C. Substituting the values of and c pm in the above expression, we get
1.22 V̇ ∆T kJ
Qs = = 𝟎. 𝟎𝟐𝟎𝟒𝟒 𝐕̇ ∆𝐓 = kW
60 s
Note: For sensible cooling, the cooling coil may have refrigerant, cooling water or cool gas
flowing through it. The sensible cooling can be done only up to the dew point temperature
(tdp) as shown in Fig.(2)b. The cooling below this temperature will result in the condensation
of moisture.
Q s UAc t m (6)
Fig. (4)
Where
U = Overall heat transfer coefficient,
As = Surface area of the coil, and
t m = Logarithmic mean temperature difference
td 2 td 1
tm , and (7)
td 3 td 1
ln
td 3 td 2
t t
1 / BPF d 3 d 1
td 3 td 2
td 2 td 1 (8)
tm
ln1 / BPF
We have already discussed that the heat added during sensible heating,
Q s m a c pm t d 2 t d 1 (10)
where
c pm = Humid specific heat =1.022 kJ/kg K, and
m a = Mass of air passing over the coil.
Note The performance of a heating or cooling coil is measured in terms of a by-pass factor. A coil
with low by-pass factor has better performance
td 3 td 2 td 2 td 1
H 1 BPF 1 (12)
td 3 td 1 td 3 td 1
Example (2):
A quantity of air having a volume of 300 m 3 30ºC dry bulb temperature and 25ºC wet bulb
temperature is heated to 40ºC dry bulb temperature. Estimate the amount of heat added, final
relative humidity and wet bulb temperature. The air pressure is 1.01325 bar.
Example (3):
The air enters a duct at 10ºC and 80% RH at the rate of 150 m 3 / min and is heated to 30ºC
without adding or removing any moisture. The pressure remains constant at 1 atmosphere.
Determine the relative humidity of air at exit from the duct and the rate of heat transfer.
Example (4):
Atmospheric air with dry bulb temperature of 28ºC and a wet bulb temperature of 17ºC is cooled
to 15ºC without changing its moisture content. Find: 1. Original relative humidity, 2. Final relative
humidity and 3. Find wet bulb temperature.
H.W:
The moist air is heated by steam condensing inside the tubes of a heating coil as shown in Fig.
below The part of the air passes through the coil and part is by-passed around the coil. The
barometric pressure is 1 bar. Determine: 1. The air per minute (in 3 ) which by-pass the coil ; and
2. The heat added by the coil
H.W:
The atmospheric air at 760 mm of Hg, dry bulb temperature 15ºC and wet bulb temperature 11ºC
enters a heating coil whose temperature is 14ºC. Assuming by-pass factor of heating coil as 0.5,
determine dry bulb temperature; wet bulb temperature and relative humidity of the air leaving the
coil. Also determine the sensible heat added to the air per kg of dry air.
Mathematically:
qL = (h2-h1) = hfg (W2 –W1) (14)
where hfg is the latent heat of vapourisation at dry bulb temperature (t dl).
Notes:
1. for dehumidification: qL = (h1-h2) = hfg (W1 – W2)
2.In air conditioning, the latent heat load per minute is given as:
Q L = ma ℎ𝑓𝑔 ∆W = V̇ ρ ℎ𝑓𝑔 ∆W kJ/min
where
V̇ = Rate of dry air flowing in
Density of moist air 1.2 kg / m 3 of dry air,
h fg Latent heat of vapourisation = 2500 kJ /kg , and
Substituting these values in the above expression, we get:
1.2 × 2500 × V̇ × ∆W kJ
QL = = 𝟓𝟎 𝐕̇ ∆𝐖 = kW
60 s
Note: The dehumidification may be accomplished chemicals. In the air-washer system, the outside
or entering air is cooled below its dew point temperature so that it looses moisture by condensation.
The moisture removal is also accomplished when the spray water is chilled water and its
temperature is lower than the dew point temperature of the entering air. Since the air leaving the
air washer has its dry bulb temperature much below the desired temperature in the room, therefore
a heating coil is placed after the air-washer. The dehumidification may also be achieved by using
chemicals which have the capacity to absorb moisture in them. Two types of chemicals known as
absorbents (such as calcium chloride) and adsorbents (such as silica gel and activated alumina) are
commonly used for this purpose.
Let
t d1 Dry bulb temperature of air entering the coil,
t dp1 Dew point temperature of the entering air t d 3 , and
t d4 Effective surface temperature or ADP of the coil.
Under ideal conditions, the dry bulb temperature of the air leaving the cooling coil (i.e. td4 ) should
be equal to the surface temperature of the cooling coil (i.e. ADP), but it is never possible due to
inefficiency of the cooling coil. Therefore, the resulting condition of air coming out of the coil is
shown by a point 2 on the straight line joining the points 1 and 4. The by-pass factor in this case
is given by:
𝑊2 − 𝑊4 ℎ2 − ℎ4
𝐵𝑃𝐹 = = (16)
𝑊1 − 𝑊4 ℎ1 − ℎ2
Also,
t d 2 t d 4 t d 2 ADP
BPF (17)
t d 1 t d 4 t d 1 ADP
Actually, the cooling and dehumidification process follows the path as shown by a dotted curve in
Fig. (6) a, but for the calculation of psychrometric properties, only end points are important. Thus
the cooling and dehumidification process shown by a line 1-2 may be assumed to have followed a
Sensible heat SH h h2
SHF A (18)
Total heat LH SH h1 h2
Note: The line 1-4 (i.e. the line joining the point of entering air and the apparatus dew point) in
Fig. (6)b is known as sensible heat factor line.
Example (5):
In a cooling application, moist air enters a refrigeration coil at the rate of 100 kg of dry air per
minute at 35ºC and 50% RH. The apparatus dew point of coil is 5ºC and by-pass factor is 0.15.
Determine the outlet state of moist air and cooling capacity of coil in TR.
Example (6):
The atmospheric air at 30ºC dry bulb temperature and 75% relative humidity enters a cooling coil
at the rate of 200 m 3 / min The coil dew point temperature is 14ºC and the by-pass factor of the
coil is 0.1. Determine 1. the temperature of air leaving the cooling coil; 2. the capacity of the
cooling coil in tonnes of refrigeration and in kilowatt; 3. the amount of water vapour removed per
minute; and 4. the sensible heat factor for the process.
H.W:
Moist air enters a refrigeration coil at 35ºC dry bulb temperature and 55 percent relative humidity
at the rate of 100 m 3 / min . The barometric pressure is 1.013 bar. The air leaves at 27ºC. Calculate
the tonnes of refrigeration required and the final relative humidity. If the surface temperature of
the cooling coil is 100oC and by-pass factor 0.1, calculate the tonnes of refrigeration required and
the condensate flow.
In an ideal case i.e. when the humidification is perfect (or the humidifying efficiency of the spray
chamber is 100%), the final condition of the air will be at point 3 (i.e. at temperature td3 and relative
humidity 100%). In actual practice, perfect humidification is never achieved. Therefore, the final
condition of air at outlet is represented by point 2 on the line 1-3, as shown in Fig. (7)b.
The effectiveness or the humidifying efficiency of the spray chamber is given by:
t d 1 t d 2 W 2 W1
H (20)
t d 1 t d 3 W 3 W1
2. When the sprays of water are maintained at a temperature higher than the wet bulb temperature
of the entering air (i.e. t1 is greater than t w1 ) but lower than the dry bulb temperature of the
entering air ( t d 1 ) by heating the spray water by heaters before it is pumped to the spray nozzles,
then for the ideal condition, the process follows the path 1 3 as shown in Fig. (7)b. In such
cases, the effectiveness or the humidifying efficiency of the spray chamber is given by
t t W W1
η H d1 d2 2 (21)
t d1 t d3 W 3 W1
where t d 3 is greater than t w1
mw
h2 h1 h fw
ma (23)
h1 ( W 2 W 1 ) h fw
Since W2 W1 h fw is very small as compared to h1 and h2 , therefore it may be neglected. Thus
the water injection process is a constant enthalpy process, irrespective of the temperature of water
injected (i.e. whether the temperature t1 t w or t1 t w ).
Example (7):
200 m 3 of air per mm. is passed through the adiabatic humidifier. The condition of air at inlet is
40ºC dry bulb temperature and 15% relative humidity and the outlet condition is 25ºC dry bulb
temperature and 20ºC wet bulb temperature. Find the dew point temperature and the amount of
water vapour added to the air per minute.
Example (8):
A drying room is to be maintained at 32ºC and 30% RH. The sensible heat gain to the room is
150000 kJ/h. The moisture to be evaporated from the objects during drying is 18kg/h. If there is
no direct heat source to provide for evaporation in the room, calculate the state and rate of supply
air at 15ºC dry bulb temperature.
H.W:
Determine the final dry bulb temperature and relative humidity of air washed with recirculated
spray water if the air is initially at dry bulb temperature 35ºC and 50% relative humidity as it enters
an air washer which has humidifying efficiency of 85 per cent.
H.W:
At a certain locality, the dry bulb temperature of air is 30ºC and the relative humidity is 40%.
Determine the specific humidity and the dew point and wet bulb temperatures of air. If this air is
cooled in an air washer using recirculated spray water and having a humidifying efficiency of 0.9,
what are dry bulb temperature and dew point temperature of air leaving the air washer?
H.W:
The atmospheric air at 40ºC dry bulb temperature and 18ºC wet bulb temperature is flowing at the
rate of 100 m 3 / min through the space. Water at 18ºC is injected into the air stream at the rate of
48kg/ h. Determine the specific humidity and enthalpy of the leaving air. Also determine the dry
bulb temperature, wet bulb temperature and relative humidity of the leaving air.
(a) (b)
or
m w 2 m w 1 ma W 2 W1 (24)
h2 h1
m w1
ma
h fw1 h fw 2 W 2 W 1 h fw 2 (26)
The temperatures t s1 and t s 2 shown in Fig. (9)a denote the temperatures of entering and leaving
spray water respectively. The temperature t 3 is the mean temperature of the spray water which the
entering air may be assumed to approach. Actually, the heating and humidification process follows
the path as shown by dotted curve in Fig. (9)b, but for the calculation of psychrometric properties,
only the end points are important. Thus, the heating and humidification process shown by a line
1-2 on the psychrometric chart may be assumed to have followed the path 1-A (i.e. heating) and
A-2 (i.e. humidification), as shown in Fig. (9)b. We see that the total heat added to the air during
heating and humidification is
14 | P a g e Dr. Omar M. Hamdoon
Air Conditioning System Lecture (6)
Note: The line 1-2 in Fig. (9)b is called sensible heat factor line.
Example (10):
Atmospheric air at a dry bulb temperature of 16ºC and 25% relative humidity passes through a
furnace and then through a humidifier, in such a way that the final dry bulb temperature is 30ºC
and 50% relative humidity. Find the heat and moisture added to the air. Also determine the sensible
heat factor of the process.
H.W:
Air at 10ºC dry bulb temperature and 90% relative humidity is to be heated and humidified to
35 o C dry bulb temperature and 22.5ºC wet bulb temperature. The air is pre-heated sensibly before
passing to the air washer in which water is recirculated. The relative humidity of the air coming
out of the air washer is 90%. This air is again reheated sensibly to obtain the final desired condition.
Find: 1. the temperature to which the air should be preheated. 2. the total heating required; 3. the
makeup water required in the air washer; and 4. the humidifying efficiency of the air washer.
m1 m 2 m (31)
For the energy balance,
m1 h1 m 2 h2 m 3 h3 (32)
Similarly, substituting the value of m3 from equation (33) in equation (34), we have
m1 W3 W2
(35)
m 2 W1 W 3
m 1 h3 h2 W 3 W 2
(36)
m 2 h1 h3 W1 W 3
Fig. (12)
The adiabatic mixing process is represented on the psychrometric chart as shown in Fig. (11)b.
The final condition of the mixture (point 3) lies on the straight line 1-2. The point 3 divides the
line 1-2 in the inverse ratio of the mixing masses. By calculating the value of W3 from equation
(36), the point 3 is plotted on the line 1-2.
It may be noted that when warm and high humidity air is mixed with cold air, the resulting mixture
will be a fog and the final condition (point 3) on the psychrometric chart will be to the left or above
the saturation curve which represents the fog region, as shown in Fig. (12). The temperature of the
fog is that of the extended wet bulb line passing through point 3.
The fog may also result when steam or a very fine water spray is injected into air in a greater
quantity than required to saturate the air. Even lesser quantity of steam, if not mixed properly, may
result fog.
The fog can be cleared by heating the fog, mixing the fog with warmer unsaturated air or
mechanically separating the water droplets from the air.
Example (11)
One kg of air at 40ºC dry bulb temperature and 50% relative humidity is mixed with 2 kg of air at
20ºC dry bulb temperature and 20ºC dew point temperature. Calculate temperature and specific
humidity of the mixture.
H.W:
800 m3/min of recirculated air at 22ºC DBT and 10ºC dew point temperature is to be mixed with
300 m3/min of fresh air at 30ºC DET and 50% RH. Determine the enthalpy, specific volume,
humidity ratio and dew point temperature of the mixture.