SPECIFICATION FOR INVERTER

I. APPLICABLE STANDARDS

1. IEC 62109–1: Safety of power converters for use in photovoltaic power


systems – Part 1: General requirements.
2. IEC 62109–2: Safety of power converters for use in photovoltaic power
systems – Part 2: Particular requirements for inverters.
3. IEC 61683: Photovoltaic systems – Power conditioners – Procedure for
measuring efficiency.
4. IEC 62116: Utility-interconnected photovoltaic inverters – Test procedure
of islanding prevention measures.
5. IEC 61727: Photovoltaic systems – Characteristics of the utility interface.

II. TECHNICAL REQUIREMENTS

Stt Technical Characteristics Requirements


1 Standards for manufacturing, testing and See Section I
safety
2 Basic Technical Parameters
Maximum DC Input Voltage 1000 V
Rated AC Output Voltage 220 V/ 380 V
AC Grid Frequency 50 Hz
Power Control MPPT
Number of MPP Trackers 1 or more
Maximum Efficiency of Inverter ≥ 98%
Power Factor ≥ 0,9
Total Harmonic Distortion < 3%
Minimum Allowable Operating Temperature 0 – 600C
of Inverter
Enclosure Protection IP 65 (outdoor)
IP 54 (Indoor)
3 Minimum Protection Functions of Inverter
DC Reverse Polarity Protection Required
AC Short Circuit Protection Required
Over/under Voltage and Over/under Required
Frequency Protection according to IEC 61727
Islanding Protection according to IEC 62116 Required
Response to Utility Recovery according to Required
IEC 61727
4 Monitoring and Communication
Requirements

1
The Inverter must be equipped with local Required
monitor which is capable of displaying and
warning at least the following parameters:
 DC String Voltage/ Current for each
string or MPPT
 Output Voltage/ Current
 Generation Output
 Power Factor
 Power Energy generated
Inverter shall have the remote monitoring Required
function based on internet for at least the
following parameters:
 DC String Voltage/ Current for each
string or MPPT
 Output Voltage/ Current
 Generation Output
 Power Factor
 Power Energy generated
Communication Interface: RS 485 Required
5 Lightning and Earthing Requirements:
The AC and DC Combiner Boxes must be Required
integrated inside the Inverter. If those Boxes
are separate from Inverter, the manufacturer
shall confirm the conformance of
interconnection between the AC, DC
Combiner Boxes and the Inverter.
Inverter shall be equipped with anti-over Required
induce voltage protection for both AC and DC
sides of the Inverter

Otherwise, Manufacturers should provide the following further information:


1. Submit the Track Record expressing about name of similar projects, the
number of similar Inverters provided and operation history of such
Inverters, that they will be imported/used in Viet Nam.
2. Experiences and Capacity of Manufacturer (Beginning year of
manufacturing, Material Standard, manufactured Standard, Testing
Standard and Testing Result of similar Inverter.
3. Operation life of Inverter (how many year?), how about maintenance
period/condition and which parts of Inverter will be regularly maintained
or replaced during operation life of Inverter.