Liebert® DS™ Thermal Management Unit

System Design Manual - 28-105kW (8-30 Tons), Downflow/Upflow, 60Hz


Floor Mounted, Air-Cooled, Water/Glycol-Cooled, GLYCOOL Economizer Coil, Dual-Cool DX with
Secondary Chilled Water Coil
TABLE OF CONTENTS
LIEBERT DS MODEL NUMBER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
1.0 LIEBERT DS CONFIGURATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
1.1 Cooling Configurations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.2 Blower Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.3 Component Location Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.0 LIEBERT DS AIR-COOLED SYSTEM DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
3.0 LIEBERT DS WATER-COOLED SYSTEM DATA. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
4.0 LIEBERT DS GLYCOL-COOLED SYSTEM DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
5.0 LIEBERT DS GLYCOOL™ SYSTEM DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
6.0 ELECTRICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
6.1 Air-cooled Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
6.2 Water/Glycol-Cooled Electrical Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
7.0 WEIGHTS AND DIMENSIONS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
7.1 Downflow Model Dimensions and Primary Connections—Water/Glycol/GLYCOOL™
Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
7.2 Downflow Models with Front and/or Rear Discharge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
7.3 Disassembly Dimensions—Downflow Air-Cooled Systems . . . . . . . . . . . . . . . . . . . . . . . . . . 47
7.4 Disassembly Dimensions—Downflow, Water/Glycol/GLYCOOL™ Systems . . . . . . . . . . . . 53
7.5 Upflow Model Dimensions and Primary Connections—Air-Cooled Systems with
EC Fans. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
7.6 Upflow Model Dimensions and Primary Connections—Water/Glycol/GLYCOOL™
Cooled Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
7.7 Upflow Model Dimensions and Primary Connections—Air-Cooled Systems with
Forward-Curved Blowers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
7.8 Upflow Model Dimensions and Primary Connections—Water/Glycol/GLYCOOL™
Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
8.0 BLOWER OUTLET AND DECK DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
8.1 Disassembly Dimensions—Upflow Air-Cooled Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
8.2 Disassembly Dimensions—Upflow, Water/Glycol/GLYCOOL™ Systems . . . . . . . . . . . . . . . 97
9.0 ANCILLARY ITEMS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
9.1 Floor Stands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
9.2 Plenums . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
9.3 Rear Return Filter Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
10.0 PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .108
10.1 Piping Schematics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
10.1.1 Typical System Configurations—Liebert MC™ Condensers . . . . . . . . . . . . . . . . . . . . . . . . . 110
10.1.2 Typical System Configurations—Fin/Tube . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
11.0 ELECTRICAL FIELD CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
11.1 Standard Electrical Field Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
11.2 Optional Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123

i
11.3 Optional Low Voltage Terminal Package Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
12.0 HEAT REJECTION—LIEBERT MC™ CONDENSER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
12.1 Liebert MC Selections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
12.2 Condenser and Options Net Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
12.3 Sound Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
12.4 Electrical Data—Liebert MC™ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
12.5 Liebert MC™ Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
12.6 Piping Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
12.7 Electrical Field Connections—Liebert MC™. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
13.0 HEAT REJECTION—LIEBERT FIN/TUBE CONDENSERS . . . . . . . . . . . . . . . . . . . . . . . . . . . 134
13.1 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135
13.2 Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
13.2.1 Electrical Data—Fin/Tube Condensers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
13.2.2 Electrical Field Connections—Liebert Fin/Tube Condensers . . . . . . . . . . . . . . . . . . . . . . . . 138
13.3 Piping Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
14.0 HEAT REJECTION—LIEBERT PIGGYBACK CONDENSERS, AIR-COOLED . . . . . . . . . . . . . . . 143
14.1 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144
14.2 Electrical Field Connections—Liebert Piggyback Condensers . . . . . . . . . . . . . . . . . . . . . . 146
14.3 Connection Locations—Liebert Piggyback Condensers . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147
15.0 HEAT REJECTION—LIEBERT FIN/TUBE DRYCOOLERS AND PUMPS . . . . . . . . . . . . . . . . . . 148
15.1 Drycooler Selection—Prop Fan Drycoolers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148
15.2 Liebert Drycooler Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148
15.3 Dimensional Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149
15.3.1 Dimensions—Prop Fan Drycoolers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149
15.4 Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151
15.4.1 Electrical Data—Prop Fan Drycoolers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151
15.5 Piping Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 155
16.0 HEAT REJECTION—PIGGYBACK DRYCOOLERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 158
16.1 Drycooler Selection—Indoor Piggyback Drycoolers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 158
16.2 Electrical Data—Piggyback Drycoolers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 158
16.3 Dimensions—Indoor Piggyback Drycoolers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 159
16.4 Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 160
17.0 PUMP PACKAGES AND EXPANSION TANK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 161

APPENDIX A - U.S. DEPARTMENT OF ENERGY (DOE) PERFORMANCE DATA . . . . . . . . . . . . . . . . 165

APPENDIX B - GUIDE SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 171

ii
Liebert DS Model Number

LIEBERT DS MODEL NUMBER

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
D S 0 3 5 A U A 0 E I * * * *

Air Distribution
DS = Downflow Standard
VS = Upflow Standard
Factory Configuration
Nominal kW
Number
028, 035, 042, 053, 070, 077, 105
(8, 10, 12, 15, 20, 22, 30 tons) Humidification
Cooling Type 0 - None
A = Air-Cooled I - Infrared
D = Dual-Cool, Air-Cooled S - Steam Generating
H = Dual-Cool, Water-Cooled Canister
K = GLYCOOL (Liebert Economizer Coil)
W = Water/Glycol Reheat Type
0 - None
Compressor E - 3-Stage Electric
D - Digital Scroll, R-407C S - SCR
S - Scroll, R-407C
Voltage Fan Type
U - Semi-Hermetic with Four-Step, R-407C
A - 460/3/60 0 = Forward-Curved
V- Semi-Hermetic with Four-Step, R407C
B - 575/3/60 Blowers
(DS105 water/glycol/GLYCOOL only)
C - 208/3/60 1 = Electronically
D - 230/3/60 Commutated (EC)
2 - 380/3/60 Fans

Not all combinations of options are available on all units.


Digital Scroll Compressors
• Not available on 077 and 105
• Not compatible with SCR reheat because digital scroll provides variable capacity control
Scroll Compressors
• Not available on 077 and 105 water/glycol/GLYCOOL models after 12/31/15
EC Fans, Direct-Drive
• Liebert Econ-O-Coil™ not available on 028, 035, 042 models with 208/230V
Steam Generating Canister Humidifier
• Not available on upflow (VS) configurations
• Not available on EC fan configurations
575 Volt Option Limitations
• Digital scroll compressors available only on 053, 070 models
GLYCOOL Liebert Economizer Models
• 105 model requires semi-hermetic compressors only, so as to prevent potential coil freezing
Turning Vanes
• Not available on floor stands 6" (152.4mm) tall
• Not available or required on units with EC fans
High Pressure Water Regulating Valve
• Not available on 042 models with semi-hermetic and scroll compressors

1 Liebert® DS™
Liebert DS Configurations

1.0 LIEBERT DS CONFIGURATIONS

1.1 Cooling Configurations

NOTE
All field-installed piping must comply with applicable local, state and federal codes.

AIR-COOLED GLYCOL-COOLED
Air-cooled unit piping is spun closed from the Glycol-cooled units are factory-charged and
actory and contains a nitrogen holding charge. tested. Field-supplied and field-installed piping is
ach installation requires field-supplied required from the unit to the drycooler and pump
efrigerant and piping to a condenser. package.

GLYCOOL-INTEGRATED FLUID ECONOMIZER WATER-COOLED


YCOOL units are factory-charged and tested. Field-supplied Water-cooled units are factory-charged and
d field-installed piping is required from the unit to the tested. Field-supplied and field-installed
ycooler and pump package. An additional Liebert Economizer water piping is required from the unit to the
l is included for use when fluid temperatures are sufficiently cooling tower.
w (below room temperature). Economizer cooling is provided
circulating cold glycol through this second coil, reducing or
minating compressor operation.

DUAL-COOL
This system has all of the features of a compressorized
system, but adds a second cooling coil that is connected
to a source of chilled water. Cooling is provided by
circulating chilled water, when available, through this
second coil and reducing compressor operation.

Liebert® DS™ 2
Liebert DS Configurations

1.2 Blower Configurations


Figure 1 Blower configurations—Downflow, front and rear supply models, EC fans
Return Air Return Air
Filter Filter

Front Front

Coil Coil

Supply
Blower
Air
Blower Raised Supply
Floor Air
Raised
Floor

Front Supply, EC Fans Rear Supply, EC Fans


Applicable to installations Applicable to installations
without raised floors without raised floors

Figure 2 Blower configurations—Downflow, bottom supply and under-floor supply models, EC fans
Return Air Return Air
Filter Filter

Front Front

Coil Coil

Blower
Raised Blower Raised
Floor Floor Floor Stand
(optional )

Floor Supply Air Supply


Stand Air
Supply (optional)
Air

Bottom Supply, EC Fans Under-Floor Supply, EC Fans


(requires 24" minimum height)

3 Liebert® DS™
Liebert DS Configurations

Figure 3 Blower configurations—Upflow models, EC fans in plenum

Supply Supply Supply Supply


Air Air Air Air

EC Fan EC Fan

Front Front
Coil Coil

Filter
Filter
Return Air
Return
Air Ductwork

Upflow, Front Return, EC Fan in Plenum Upflow, Rear Return, Ducted, EC Fan in Plenum

Figure 4 Blower configurations—Upflow, front return models, forward-curved blowers

Supply Air Supply Air

Blower Blower
Front Front

Coil Coil

Filter Filter

Return Return
Air Air

Top Supply, Front Throw Forward-Curved Blowers Top Supply, Rear Throw Forward-Curved Blowers

Liebert® DS™ 4
Liebert DS Configurations

Figure 5 Blower configurations—Upflow, rear return models, forward-curved blowers

Supply Air Supply Air

Blower Blower
Front Front

Coil Coil

Filter Filter
Return Return
Air Air

Ductwork Ductwork

Top Supply, Front Throw, Forward-Curved Blowers Top Supply, Rear Throw, Forward-Curved Blowers

5 Liebert® DS™
Liebert DS Configurations

1.3 Component Location Drawings


Figure 6 Downflow model component locations
1

17

16
15
3
14

13 5
12
11 10
9
8
7

6 18
18
1. Condenser Cleanout Plugs, 10. Infrared Humidifier, optional
fluid-cooled units only 11. Econ-O-Coil Valve, GLYCOOL/Dual Cooling
2. Filters 12. Evaporator Coil
3. Liebert iCOM 13. Condenser Drain Plugs, fluid-cooled units only
4. Smoke Sensor, optional 14. Compressor Section
5. Fan Pulley 15. Electric Box
6. Motor 16. Disconnect, optional
7. Motor Sheave and Belts 17. Variable Frequency Drive (optional on
8. Blower digital scroll units only) DPN000958
9. Condensate Pump, optional 18. EC Fans, optional Rev. 4

Liebert® DS™ 6
Liebert DS Configurations

Figure 7 Upflow model component locations

18
1

2
17 4

16
6

15
7

14

13
9

12 11 10

1. Condenser Cleanout Plugs 10. Smoke Sensor (optional)


(fluid-cooled units only) 11. Infrared Humidifier (optional)
2. Blower 12. Condensate Pump (optional)
3. Filters - not shown for clarity 13. Econ-O-Coil Valve (GLYCOOL/Dual Cooling)
4. Fan Pulley 14. Condenser Drain Plugs ( fluid-cooled units only)
5. Motor Sheave and Belts 15. Electric Box
6. Liebert iCom Control Display 16. Compressor Section
7. Motor 17. Disconnect (optional)
8. Evaporator Coil 18. EC Fans (optional)
DPN001222
9. Variable Frequency Drive (optional on
digital scroll units only) Rev. 2

7 Liebert® DS™
Liebert DS Air-Cooled System Data

2.0 LIEBERT DS AIR-COOLED SYSTEM DATA


1
Table 1 Application data—Air-cooled, EC fan, under-floor discharge
Model Size 028 035 042 053 070 077 105
APPLICATION DATA with EC Fans
Net Application Data BTUH (kW), Standard Air Volume and Evaporator Fan Motor
Semi Hermetic Compressors (4 Step Cooling) with EC Fans
85°F DB, 64.5°F WB, 52.3°F DP (29.4°C DB, 18.1°C WB) 32.4% RH
116.4 143.6 163.6 210.6 247.1 270.3 352.5
Total kBTUH (kW)
(34.1) (42.1) (47.9) (61.7) (72.4) (79.2) (103.3)
116 141.2 160.9 210.2 245.9 269.2 337.5
Sensible kBTUH (kW)
(34) (41.4) (47.9) (61.6) (72) (78.9) (98.9)
80°F DB, 62.9°F WB, 52.3°F DP (26.7°C DB, 17.1°C WB) 38.2% RH
110.5 136.8 156.1 198.9 234.8 257.1 338.2
Total kBTUH (kW)
(32.4) (40.1) (45.7) (58.3) (68.8) (75.3) (99.1)
105.9 128.1 146.2 193.9 226.6 248.8 307.2
Sensible kBTUH (kW)
(31) (37.5) (45.7) (56.8) (66.4) (72.9) (90)
75°F DB, 61.1°F WB, 52.3°F DP (23.9°C DB, 16.2°C WB) 45.1% RH
105.3 130.8 149.5 189 223.9 245.8 325
Total kBTUH (kW)
(30.9) (38.3) (43.8) (55.4) (65.6) (72) (95.2)
93.9 113.8 129.9 173.3 201.3 221.5 80
Sensible kBTUH (kW) (64.9) (273.1)
(27.5) (33.3) (43.8) (50.8) (59)
Net Application Data BTUH (kW), Standard Air Volume and Evaporator Fan Motor
Scroll or Digital Scroll Compressors with EC Fans Scroll Compressors Only
85°F DB, 64.5°F WB, 52.3°F DP (29.4°C DB, 18.1°C WB) 32.4% RH
120.8 137.1 155.3 216.8 258.6
Total kBTUH (kW) 277.6 (81.3) 353.7 (103.6)
(35.4) (40.2) (45.5) (63.5) (75.8)
120 136.4 154.7 215.7 255.6
Sensible kBTUH (kW) 275.1 (80.6) 338.3 (99.1)
(35.2) (40) (45.3) (63.2) (74.9)
80°F DB, 62.9°F WB, 52.3°F DP (26.7°C DB, 17.1°C WB) 38.2% RH
113.9 130.4 148.1 206.5 248
Total kBTUH (kW) 265.8 (77.9) 340.2 (99.7)
(33.4) (38.2) (43.4) (60.5) (72.7)
108.7 124.6 141.9 199.1 235
Sensible kBTUH (kW) 253 (74.1) 308.2 (90.3)
(31.8) (36.5) (41.6) (58.3) (68.9)
75°F DB, 61.1°F WB, 52.3°F DP (23.9°C DB, 16.2°C WB) 45.1% RH
107.8 124.7 141.9 197.4 69.9
Total kBTUH (kW) 255.5 (74.9) 327.8 (96)
(31.6) (36.5) (41.6) (57.8) (238.4)
96.1 110.8 126.3 177.6 209.4
Sensible kBTUH (kW) 224.9 (65.9) 274.3 (80.4)
(28.2) (32.5) (37) (52) (61.4)
FAN SECTION - Downflow Models - EC Models Under Floor
3
Standard Air Volume - f /m (m3/h) 4,400 5,200 6200 8,000 9,600 11,000 13,700
0.2" external static (7,476) (8,835) (10533.9) (13,592) (16,310) (18,689) (23,276)
Standard Fan Motor hp (kW) 3.75 (2.8) 3.75 (2.8) 3.75 (2.8) 3.4 (2.5) 5.4 (4.0) 7.9 (5.9) 10.5 (7.8)
Number of Fans 1 1 1 2 2 2 3
1. Refer to Appendix A for U.S. Department of Energy Performance Data.
2. Application data is rated and factory-certified per ASHRAE 127-2012 with a 5% tolerance.
3. Some options or combinations of options may result in reduced air flow—Contact factory for recommendations.
4. Digital scroll not available on 077 and 105 models; units available with semi-hermetic and standard scroll compressors only

Liebert® DS™ 8
Liebert DS Air-Cooled System Data

Table 2 Application data—Air-cooled with forward-curved blowers 1


Model Size 028 035 042 053 070 077 105
APPLICATION DATA with Forward-Curved Blowers
Net APPLICATION DATA BTUH (kW), Standard Air Volume and Evaporator Fan Motor
Semi Hermetic Compressors (4 Step Cooling) with Forward-Curved Blowers
85°F DB, 64.5°F WB, 52.3°F DP (29.4°C DB, 18.1°C WB) 32.4% RH
137.6 140.0 157.6 205.3 240.6 262.6 345.6
Total kBTUH (kW)
(40.3) (41.0) (46.2) (60.2) (70.5) (76.9) (101.3)
129.6 137.6 155.3 203.8 237.9 259.9 329.6
Sensible kBTUH (kW)
(38.0) (40.3) (45.5) (59.7) (69.7) (76.2) (96.6)
80°F DB, 62.9°F WB, 52.3°F DP (26.7°C DB, 17.1°C WB) 38.2% RH
131.8 133.3 150 195.1 229.3 250.6 331.5
Total kBTUH (kW)
(38.6) (39.1) (43.9) (57.2) (67.2) (73.4) (97.1)
117.2 124.6 140.5 187.1 217.7 238.2 299.4
Sensible kBTUH (kW)
(34.3) (36.5) (41.2) (54.8) (63.8) (69.8) (87.7)
75°F DB, 61.1°F WB, 52.3°F DP (23.9°C DB, 16.2°C WB) 45.1% RH
126.5 127.2 143.3 185.6 218.9 239.7 318.4
Total kBTUH (kW)
(37.1) (37.3) (42) (54.4) (64.1) (70.2) (93.3)
104.2 110.3 124.2 166.2 192.9 210.9 265.4
Sensible kBTUH (kW)
(30.5) (32.3) (36.4) (48.7) (56.5) (61.8) (77.8)
Net APPLICATION DATA BTUH (kW), Standard Air Volume and Evaporator Fan Motor
Scroll or Digital Scroll Compressors with Forward-Curved Blowers Scroll Compressors Only
85°F DB, 64.5°F WB, 52.3°F DP (29.4°C DB, 18.1°C WB) 32.4% RH
116.4 135.5 149.2 212.1 252.6
Total kBTUH (kW) 270.1 (79.1) 346.9 (101.6)
(34.1) (39.7) (43.7) (62.1) (74.0)
136.9 116.0 148.9 209.3 246.6
Sensible kBTUH (kW) 265.6 (77.8) 330.4 (96.8)
(40.1) (34.0) (43.6) (61.3) (72.3)
80°F DB, 62.9°F WB, 52.3°F DP (26.7°C DB, 17.1°C WB) 38.2% RH
110.5 130.8 141.9 202.5 243
Total kBTUH (kW) 259 (75.9) 333.5 (97.7)
(32.4) (38.3) (41.6) (59.3) (71.2)
105.9 123.2 136.1 191.6 225
Sensible kBTUH (kW) 242.6 (71.1) 300.4 (88.0)
(31.0) (36.1) (39.9) (56.1) (65.9)
75°F DB, 61.1°F WB, 52.3°F DP (23.9°C DB, 16.2°C WB) 45.1% RH
105.3 125.4 135.7 194.2 233.9
Total kBTUH (kW) 249.3 (73) 321.1 (94.1)
(30.9) (36.7) (39.8) (56.9) (68.5)
93.9 109.4 120.6 170.4 200.1
Sensible kBTUH (kW) 215.2 (63.1) 266.6 (78.1)
(27.5) (32.1) (35.3) (49.9) (58.6)
FAN SECTION - Downflow Models - Fixed Pitch, Two Belts
3 3
Standard Air Volume - f /m (m /h) 4,400 5,200 6,300 7,500 9,000 10,400 13,700
0.2" external static (7,476) (8,835) (10,704) (12,743) (15,291) (17,670) (23,276)
Standard Fan Motor hp (kW) 2 (1.5) 3 (2.2) 5 (3.7) 3 (2.2) 5 (3.7) 7.5 (5.6) 10 (7.5)
Optional Fan Motor hp (kW) 3 (2.2) 5 (3.7) 7.5 (5.6) 5 (3.7) 7.5 (5.6) 10 (7.5) 15 (11.2)
Number of Fans 1 1 1 2 2 2 3
1. Refer to Appendix A for U.S. Department of Energy Performance Data.
2. APPLICATION DATA is rated and factory-certified per ASHRAE 127-2012 with a 5% tolerance.
3. Some options or combinations of options may result in reduced air flow—Contact factory for recommendations.
4. Digital scroll not available on 077 and 105 models; units available with semi-hermetic and standard scroll compressors only

9 Liebert® DS™
Liebert DS Air-Cooled System Data

Table 3 Physical data—Air-cooled systems


Model Size 028 035 042 053 070 077 105
EVAPORATOR COIL- A-Frame - Copper Tube/Aluminum Fin
Face Area, sq. ft. (m2) 17.1 (1.6) 17.1 (1.6) 17.1 (1.6) 24.7 (2.3) 24.7 (2.3) 24.7 (2.3) 32.3 (3.0)
Rows of Coil 3 3 3 3 3 3 3
REHEAT SECTION
Electric Reheat - Three-Stage, Stainless Steel Fin Tubular; capacity does not include fan motor heat
Capacity - kBTUH (kW) - Standard 102.4
51.2 (15.0) 51.2 (15.0) 51.2 (15.0) 85.3 (25.0) 85.3 (25.0) 85.3 (25.0)
Selection (30.0)
Capacity, kBTUH (kW) - Optional
34.1 (10.0) 34.1 (10.0) 34.1 (10.0) 51.2 (15.0) 51.2 (15.0) 51.2 (15.0) 68.3 (20.0)
Selection
Electric Reheat - SCR Control, Stainless Steel Fin Tubular (optional selection)
51.2 51.2 51.2 85.3 85.3 85.3 102.4
Capacity, kBTUH (kW)
(15.0) (15.0) (15.0) (25.0) (25.0) (25.0) (30.0)
HUMIDIFIER SECTION
Infrared Humidifier (Steam canister humidifiers available on downflow models)
Capacity, lb./hr. (kg/h) 11.0 (5.0) 11.0 (5.0) 11.0 (5.0) 22.0 (10.0) 22.0 (10.0) 22.0 (10.0) 22.0 (10.0)
FILTER SECTION
Disposable Type - Nominal Sizes and Quantities, Standard MERV 8 or Optional MERV 11 (Filter types cannot be mixed, must
be all MERV 8 or all MERV 11.)
Downflow Models
Quantity 3 3 3 4 4 4 4
2 @ 25x20 2 @ 25x20 2 @ 25x20
Nominal Size, inches 4 @ 25x20 4 @ 25x20 4 @ 25x20 4 @ 25x20
1 @ 25x16 1 @ 25x16 1 @ 25x16
Upflow Models
(Front and Rear return) Filters located in separate filter box on rear return; located on lower unit panel on front return
Quantity 4 4 4 6 6 6 8
Nominal Size, inches 25x20 25x20 25x20 25x20 25x20 25x20 25x20
PIPING CONNECTION SIZES - Air-cooled Liebert DS Indoor Unit (Not External Line Sizes)
Liquid Line, O.D. Copper (2/unit) 1/2 1/2 1/2 5/8 5/8 5/8 5/8
Hot Gas Line, O.D. Copper (2/unit) 5/8 5/8 5/8 7/8 7/8 7/8 1-1/8
Infrared Humidifier, O.D. Copper 1/4 1/4 1/4 1/4 1/4 1/4 1/4
Condensate Drain, FPT 3/4 3/4 3/4 3/4 3/4 3/4 3/4
Condensate Drain w/Optional
1/2 1/2 1/2 1/2 1/2 1/2 1/2
Condensate Pump, OD
OUTDOOR AIR-COOLED CONDENSER, STANDARD 95°F AMBIENT SELECTION
See Tables 46 and 56 for other selections
Model (R-407C refrigerant) MCM056_8 MCM056_8 MCM056_8 MCM056_8 MCM080_8 MCM080_8 MCL110_8
Number of Fans 2 2 2 2 2 2 2
DUAL-COOL UNITS DATA, Water (0% Glycol), Net Application Data kBTUH (kW)
CAUTION: CuNi coil option must be specified when Econ-O-Coil is applied to open water tower.
75°F DB, 61.1 WB (23.9°C DB, 16.2°C WB) 45% RH, 45°F EWT, 55°F LWT Based on Forward-Curved Blowers
89.2 101.6 109.8 170.4 188.8 196.8 258.8
Total Capacity, kBTUH (kW)
(26.2) (29.8) (32.2) (49.9) (55.3) (57.7) (75.8)
Sensible Capacity, kBTUH (kW) 85 (24.9) 98.2 (28.8) 107.8 (31.6) 157.1 (46) 176.4 (51.7) 185.4 (54.3) 249.1 (73)
Flow Rate GPM (I/m) @ 10°F Rise 19 (71.9) 22.4 (84.8) 25.5 (96.5) 36.4 (138) 41.7 (158) 46 (174) 59.4 (225)
10.50 10.40
Pressure Drop, ft. (kPa), valve, coil 6.1 (18.23) 8.3 (24.81) 13.3 (39.8) 15.9 (47.6) 15.9 (47.5)
(31.39) (31.09)
4400 5500 6600 8000 9600 11000 13,700
Airflow, f3/m (m3/h)
(7475) (9344) (11213) (13592) (16310) (18689) (23,256)
Fluid Volumes
Econ-O-Coil Fluid Volume, gal (l) 5 (19.0) 5 (19.0) 5 (19.0) 8 (30.4) 8 (30.4) 8 (30.4) 10 (38.0)
Application data is rated per ASHRAE 127-2012 with a 5% tolerance

Liebert® DS™ 10
Liebert DS Water-Cooled System Data

3.0 LIEBERT DS WATER-COOLED SYSTEM DATA


1
Table 4 Application data—Water-cooled, EC fans
Model Size 28 35 42 053 070 077 105U 105V
APPLICATION DATA WITH EC FANS
Net Application Data BTUH (kW), Standard Air Volume and Evaporator Fan Motor
Semi Hermetic Compressors (Four-Step Cooling) with EC Fans
85°F DB, 64.5°F WB, 52.3°F DP (29.4°C DB, 18.1°C WB) 32.4% RH
143.8 132 171 220 268.3 297.1 382.3 356.1
Total kBTUH (kW)
(42.1) (38.7) 50.1) (65.1) (78.6) (87.1) (112.1) (104.3)
135 108.2 166.9 212.9 258.2 285.4 354.6 345.8
Sensible kBTUH (kW)
(39.6) (31.7) (48.9) (63.4) (75.7) (83.6) (103.9) (101.3)
80°F DB, 62.9°F WB, 52.3°F DP (26.7°C DB, 17.1°C WB) 38.2% RH
138.1 135.4 163.4 212.1 256.9 284.7 367.7 339.7
Total kBTUH (kW)
(40.5) (39.7) (47.9) (62.2) (75.3) (83.4) (107.8) (99.5)
122.4 117.3 151.4 197.7 68.9 76 94.3 93.2
Sensible kBTUH (kW)
(35.9) (34.4) (44.4) (58) (235) (259.5) (321.9) (318.2)
75°F DB, 61.1°F WB, 52.3°F DP (23.9°C DB, 16.2°C WB) 45.1% RH
38.9 41.4 45.9 59.4 245.8 273 352.9 327.8
Total kBTUH (kW)
(132.7) (141.4) (156.7) (202.6) (72) (80) (103.4) (96.0)
109.3 131.9 134.7 176.4 209 230.8 285.7 283.7
Sensible kBTUH (kW)
(32) (38.7) (39.5) (51.7) (61.2) (67.6) (83.7) (83.1)
Net Application Data BTUH (kW), Standard Air Volume and Evaporator Fan Motor
Scroll Compressors Only
Scroll or Digital Scroll Compressors with EC Fans (not available after 12/31/15)
85°F DB, 64.5°F WB, 52.3°F DP (29.4°C DB, 18.1°C WB) 32.4% RH
120 143.3 162.1 224.1 275.6 301.9 379.9
Total kBTUH (kW) —
(35.2) (42) (47.5) (66.3) (80.8) (88.5) (111.3)
119.9 142.1 161 215.6 262.6 288.3 353.4
Sensible kBTUH (kW) —
(35.1) (41.6) (47.2) (64.3) (77) (84.5) (103.6)
80°F DB, 62.9°F WB, 52.3°F DP (26.7°C DB, 17.1°C WB) 38.2% RH
116.1 136.7 154.8 216.1 264.6 290.2 365.9
Total kBTUH (kW) —
(34) (40.1) (45.4) (63.3) (77.5) (85) (107.2)
111 129.4 147 200.1 238.9 262.3 321.1
Sensible kBTUH (kW) —
(32.5) (37.9) (43.1) (58.6) (70) (76.9) (94.1)
75°F DB, 61.1°F WB, 52.3°F DP (23.9°C DB, 16.2°C WB) 45.1% RH
111.8 131 148.4 206.5 253.5 279.1 352.2
Total kBTUH (kW) —
(32.8) (38.4) (43.5) (60.5) (74.3) (81.8) (103.2)
99.2 115.2 130.9 178.3 212.7 233.6 285.9
Sensible kBTUH (kW) —
(29.1) (33.8) (38.4) (52.2) (62.3) (68.5) (83.8)
FAN SECTION - Downflow Models - EC Fans Under Floor
Standard Air Volume f3/m (m3/h) 4,400 5,200 6200 8,000 9,600 11,000 13700 13700
0.2" External Static (7,476) (8,835) (10534) (13,592) (16,310) (18,689) (23276) (23276)
Standard Fan Motor, Nominal kW (hp) 3.75 3.75 3.75 3.4 5.4 7.9 10.5 10.5
(Total for All Fans) (2.8) (2.8) (2.8) (2.5) (4.0) (5.9) (7.8) (7.8)
Number of Fans 1 1 1 2 2 2 3 3
1. Refer to Appendix A for U.S. Department of Energy Performance Data.
2. Canister humidifier not available with EC fans.
3. Application data is rated and factory certified per ASHRAE 127-2012 with a 5% tolerance.
4. Some options or combinations of options may result in reduced air flow—Contact factory for recommendations.
5. Digital scroll not available on 077 and 105 models; units available with semi-hermetic and standard scroll compressors only

11 Liebert® DS™
Liebert DS Water-Cooled System Data

1
Table 5 Application data—Water-cooled units with forward-curved blowers
Model Size 28 35 42 053 070 077 105U 105V
APPLICATION DATA WITH FORWARD-CURVED BLOWERS
Net Application Data, BTUH (kW), Standard Air Volume and Evaporator Fan Motor
Semi-Hermetic Compressors (Four-Step Cooling) with Forward-Curved Blowers
85°F DB, 64.5°F WB, 52.3°F DP (29.4°C DB, 18.1°C WB) 32.4% RH
141.6 144.7 165.2 211.9 262.5 289.9 376.4 348.9
Total kBTUH (kW)
(41.5) (42.4) (48.4) (62.1) (76.9) (85.0) (110.3) (102.2)
132.8 141.9 161.7 194.6 248.4 274.4 348.7 338.8
Sensible kBTUH (kW)
(38.9) (41.6) (47.4) (57) (72.8) (80.4) (102.2) (99.3)
80°F DB, 62.9°F WB, 52.3°F DP (26.7°C DB, 17.1°C WB) 38.2% RH
135.9 137.9 157.4 205.2 251.6 278.1 361.8 332.8
Total kBTUH (kW)
(39.8) (40.4) (46.1) (59.7) (73.7) (81.5) (106) (97.5)
120.2 128.3 146.1 180.6 225.5 248.8 315.9 311.7
Sensible kBTUH (kW)
(35.2) (37.6) (42.8) (51.9) (66.1) (72.9) (92.6) (91.3)
75°F DB, 61.1°F WB, 52.3°F DP (23.9°C DB, 16.2°C WB) 45.1% RH
130.5 131.9 150.7 196.9 240.8 266.7 346.9 321.1
Total kBTUH (kW)
(38.3) (38.6) (44.2) (57.2) (70.6) (78.2) (101.7) (94.1)
107.1 113.8 129.3 162.1 200.3 220.8 279.8 277.9
Sensible kBTUH (kW)
(31.4) (33.3) (37.9) (46.4) (58.7) (64.7) (82) (81.4)
Net Application Data BTUH (kW), Standard Air Volume and Evaporator Fan Motor
Scroll Compressors Only
Scroll or Digital Scroll Compressors with Forward-Curved Blowers (not available after 12/31/15)
85°F DB, 64.5°F WB, 52.3°F DP (29.4°C DB, 18.1°C WB) 32.4% RH
117.8 139.7 156.3 219.6 269.6 295.1 374
Total kBTUH (kW) —
(34.5) (40.9) (45.8) (64.9) (79.0) (86.5) (109.6)
117.7 138.5 155.5 207.9 252.5 277.3 347.5
Sensible kBTUH (kW) —
(34.5) (40.6) (45.6) (62.0) (74.0) (81.3) (101.8)
80°F DB, 62.9°F WB, 52.3°F DP (26.7°C DB, 17.1°C WB) 38.2% RH
113.9 133.2 148.8 212.1 259.1 283.6 360
Total kBTUH (kW) —
(33.4) (39.0) (43.6) (62.2) (75.9) (83.1) (105.5)
108.8 125.8 141.6 192.6 229.3 251.5 315.2
Sensible kBTUH (kW) —
(31.9) (36.9) (41.5) (56.4) (67.2) (73.7) (92.4)
75°F DB, 61.1°F WB, 52.3°F DP (23.9°C DB, 16.2°C WB) 45% RH
109.6 127.5 142.3 202.9 248.5 272.9 346.3
Total kBTUH (kW) —
(32.1) (37.4) (41.7) (59.5) (72.8) (80) (101.5)
97 111.7 125.5 171.5 203.9 223.7 280
Sensible kBTUH (kW) —
(28.4) (32.7) (36.8) (50.3) (59.8) (65.5) (82.1)
FAN SECTION - Downflow Models - Fixed Pitch, Two Belts
3 3
Standard Air Volume f /m (m /h) 4,400 5,200 6200 7,500 9,000 10,400 13,700 13,700
0.2" External Static (7,476) (8,835) (10534) (12,743) (15,291) (17,670) (23,276) (23,276)
Standard Fan Motor, hp (kW) 2 (1.5) 3 (2.2) 5 (3.7) 3 (2.2) 5 (3.7) 7.5 (5.6) 10 (7.5) 10 (7.5)
Optional Fan Motor, hp (kW) 3 (2.2) 5 (3.7) 7.5 (5.6) 5 (3.7) 7.5 (5.6) 10 (7.5) 15 (11.2) 15 (11.2)
Number of Fans 1 1 1 2 2 2 3 3
1. Refer to Appendix A for U.S. Department of Energy Performance Data.
2. Application data is rated and factory certified per ASHRAE 127-2012 with a 5% tolerance.
3. Some options or combinations of options may result in reduced air flow—Contact factory for recommendations.
4. Digital scroll not available on 077 and 105 models; units available with semi-hermetic and standard scroll compressors only

Liebert® DS™ 12
Liebert DS Water-Cooled System Data

Table 6 Physical data—Water-cooled units


Model Size 028 035 042 053 070 077 105U 105V
EVAPORATOR COIL- A-Frame - Copper Tube/Aluminum Fin
Face Area, sq. ft. (sq. m) 17.1 (1.6) 17.1 (1.6) 17.1 (1.6) 24.7 (2.3) 24.7 (2.3) 24.7 (2.3) 32.3 (3.0) 32.3 (3.0)
Rows of Coil 3 3 3 3 3 3 3 3
REHEAT SECTION
Electric Reheat - Three-stage, Stainless Steel Fin Tubular, capacity does not include fan motor heat

Capacity, kBTUH (kW), Standard Selection 51.2 51.2 51.2 85.3 85.3 85.3 102.4 102.4
(15.0) (15.0) (15.0) (25.0) (25.0) (25.0) (30.0) (30.0)
Capacity, kBTUH (kW), Optional Selection 34.1 (10.0) 34.1 (10.0) 34.1 (10.0) 15.0 (51.2) 15.0 (51.2) 15.0 (51.2) 20.0 (68.3) 20.0 (68.3)
Electric Reheat - SCR Control, Stainless Steel Fin Tubular (optional selection)

Capacity, kBTUH (kW) 51.2 51.2 51.2 85.3 85.3 85.3 102.4 102.4
(15.0) (15.0) (15.0) (25.0) (25.0) (25.0) (30.0) (30.0)
HUMIDIFIER SECTION
Infrared Humidifier
Capacity, lb./hr. (kg/h) 11.0 (5.0) 11.0 (5.0) 11.0 (5.0) 22.0 (10.0) 22.0 (10.0) 22.0 (10.0) 22.0 (10.0) 22.0 (10.0)
FILTER SECTION
Disposable Type - Nominal Sizes and Quantities, Standard MERV 8 or Optional MERV 11 (Filter types cannot be mixed, must be all MERV 8 or all
MERV 11.)
Downflow Models
Quantity 3 3 3 4 4 4 4 4

Nominal Size, inches 2 @ 25x20 2 @ 25x20 2 @ 25x20 4 @ 25x20 4 @ 25x20 4 @ 25x20 4 @ 25x20 4 @ 25x20
1 @ 25x16 1 @ 25x16 1 @ 25x16
Nominal Size, inches 25x20 25x20 25x20 25x20 25x20 25x20 25x20 25x20
Upflow Models (Front and Rear Return)—Filters located in separate filter box on rear return, located on lower unit panel on front return
Quantity 4 4 4 6 6 6 8 8
WATER COOLED SYSTEM
Semi-Hermetic Compressors, based on 75°F/45% room conditions with EC Fans
Condenser Flow Requirements - Maximum design water pressure 150psi (1034kPa), 350psi (2413kPa) available as option

THR, kBTUH (kW) 167.7 172.3 204.3 255 316.5 360.4 475.5 475.5
(49.2) (50.5) (59.9) (74.7) (92.7) (105.6) (139.3) (139.3)

83°F (28.3°C) EWT, GPM (l/m) 28 29 (109.7) 34 (128.7) 43 (162.7) 53 (200.6) 60 (227.1) 79 (299.0) 79 (299.0)
(105.90)
Pressure Drop, ft. of water (kPa), with valve 8.9 (26.70) 9.5 (28.4) 12.8 (38.3) 11.2 (33.5) 16.6 (49.6) 20.9 (62.5) 31.3 (93.6) 31.3 (93.6)
Standard Scroll Compressors Only
WATER COOLED SYSTEM - Digital Scroll Compressors, based on 75°F/45% room conditions (not available after 12/31/15)
Condenser Flow Requirements - Maximum design water pressure 150psi (1034kPa), 350psi (2413kPa) available as option; with EC Fans

THR, kBTUH (kW) 141.8 169.8 194.5 258.5 325.3 365.6 459.6 —
(41.6) (49.8) (57) (75.8) (95.3) (107.2) (134.7)
28.5 55.5 236.6 295.3
83°F (28.3°C) EWT, GPM (l/m) 24 (90.85) (107.9) 32.5 (123) 44 (166) (210.1) (62.5) (78) —

Pressure Drop, ft. of water (kPa), valve 19.7 (6.6) 27.5 (9.2) 35.3 (11.8) 35 (11.7) 54.1 (18.1) 67.5 (22.6) 91.4 (30.6) —
PIPING CONNECTION SIZES -Water-Cooled Liebert DS Indoor Unit
Water Supply, O.D. Copper 1-5/8" (41) 1-5/8" (41) 2-1/8" (54) 2-1/8" (54) 2-1/8" (54) 2-1/8" (54) 2-1/8" (54) 2-1/8" (54)
Water Return, O.D. Copper 1-5/8 1-5/8" (41) 2-1/8" (54) 2-1/8" (54) 2-1/8" (54) 2-1/8" (54) 2-1/8" (54) 2-1/8" (54)
Infrared Humidifier, O.D. Copper 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4
Condensate Drain, FPT 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4
Condensate Drain w/Optional Condensate 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2
Pump, OD
Hot Water Reheat, O.D. Copper 5/8 5/8 5/8 5/8 5/8 5/8 5/8 5/8
DUAL-COOL UNITS APPLICATION DATA, Water (0% Glycol), Net Application Data kBTUH (kW)
CAUTION: CuNi coil option must be specified when Econ-O-Coil is applied to open water tower.
75°F DB, 62.57 WB (23.9°C DB, 16.9°C WB) 45% RH, 45°F EWT, 55°F LWT; with EC Fans

Total Capacity, kBTUH (kW) 89.2 101.6 109.8 170.4 198.1 196.8 280.1 280.1
(26.2) (29.8) (32.2) (49.9) (58) (57.7) (82.1) (82.1)

Sensible Capacity, kBTUH (kW) 85 98.2 107.8 157.1 181.4 185.4 63.7 63.7
(24.9) (28.8) (31.6) (46) (53.2) (54.3) (4) (4)
19 22.4 25.5 36.4 47.2 46.1 54.9 54.9
Flow Rate, GPM (I/m) @ 10°F Rise (1.2) (1.4) (1.6) (2.3) (3.0) (2.9) (3.5) (3.5)

Pressure Drop, ft. (kPa), valve, coil 6.1 (18.23) 8.3 (24.81) 10.50 10.40 17.2 15.9 (47.6) 18 (53.80) 18 (53.80)
(31.39) (31.09) (51.41)
FLUID VOLUMES
Econ-O-Coil Fluid Volume, gal (l) 5 (19.0) 5 (19.0) 5 (19.0) 8 (30.4) 8 (30.4) 8 (30.4) 10 (38.0) 10 (38.0)
Unit Volume, Without Econ-O-Coil, gal, (l) 4 (15.2) 4 (15.2) 4 (15.2) 7 (26.6) 7 (26.6) 7 (26.6) 8 (30.4) 8 (30.4)

13 Liebert® DS™
Liebert DS Glycol-Cooled System Data

4.0 LIEBERT DS GLYCOL-COOLED SYSTEM DATA


1
Table 7 Application data—Glycol-cooled units with EC fans
Model Size 028 035 042 053 070 077 105U 105V
APPLICATION DATA with EC Fans
Net Application Data BTUH (kW), Standard Air Volume and Evaporator Fan Motor,
Semi-Hermetic Compressors (4 Step Cooling) with EC Fans
85°F DB, 64.5°F WB, 52.3°F DP (29.4°C DB, 18.1°C WB) 32.4% RH
125.3 130.4 149.9 194.8 238.9 265.7 346.3 330.9
Total kBTUH (kW)
(36.7) (38.2) (43.9) (57.1) (70) (77.9) (101.5) (97.0)
124.4 130.4 149.9 193.5 237.7 263.8 333.4 329.8
Sensible kBTUH (kW)
(36.4) (38.2) (43.9) (56.7) (69.7) (77.3) (97.7) (96.6)
80°F DB, 62.9°F WB, 52.3°F DP (26.7°C DB, 17.1°C WB) 38.2% RH
119.1 122.3 141 185.1 226.8 252.9 331.4 306.1
Total kBTUH (kW)
(34.9) (35.8) (41.3) (54.2) (66.5) (74.1) (97.1) (89.7)
112.9 120.9 138.8 177.6 218.1 242.2 304 301.4
Sensible kBTUH (kW)
(33.1) (35.4) (40.7) (52.1) (63.9) (71.0) (89.1) (88.3)
75°F DB, 61.1°F WB, 52.3°F DP (23.9°C DB, 16.2°C WB) 45.1% RH
113.6 115.8 133.8 176 215.9 241.5 317.1 288.5
Total kBTUH (kW)
(33.3) (33.9) (39.2) (51.6) (63.3) (70.8) (92.9) (84.5)
100.3 107.6 123.6 158.4 194.5 215.7 269.6 267.4
Sensible kBTUH (kW)
(29.4) (31.5) (36.2) (46.4) (57.0) (63.2) (79.0) (78.4)
Net Application Data BTUH (kW), Standard Air Volume and Evaporator Fan Motor
Scroll Compressors Only
Scroll or Digital Scroll Compressors with EC Fans (not available after 12/31/15)
85°F DB, 64.5°F WB, 52.3°F DP (29.4°C DB, 18.1°C WB) 32.4% RH
108.7 128 145.2 203.6 244.5 272.6 344.6
Total kBTUH (kW) —
(31.9) (37.5) (42.5) (59.7) (71.6) (79.9) (101.0)
108.7 128 145.2 203 242.2 269.2 332.3
Sensible kBTUH (kW) —
(31.9) (37.5) (42.5) (59.5) (71.0) (78.9) (97.4)
80°F DB, 62.9°F WB, 52.3°F DP (26.7°C DB, 17.1°C WB) 38.2% RH
103 120.6 136.8 193.4 233.1 260.5 330.7
Total kBTUH (kW) —
(30.2) (35.3) (40.1) (56.7) (68.3) (76.3) (96.9)
102.6 119.6 135.9 187 221.1 246.6 303.6
Sensible kBTUH (kW) —
(30.1) (35.1) (39.8) (54.8) (65.1) (72.3) (89.0)
75°F DB, 61.1°F WB, 52.3°F DP (23.9°C DB, 16.2°C WB) 45% RH
97.6 114.7 130.2 184.1 223.2 249.8 317.6
Total kBTUH (kW) —
(28.6) (33.6) (38.2) (54.0) (65.4) (73.2) (93.1)
92 107.1 121.8 167.2 198.4 219.7 270
Sensible kBTUH (kW) —
(27.0) (31.4) (35.7) (49.0) (58.1) (64.4) (79.1)
FAN SECTION - Downflow Models - EC Fans Under Floor
Standard Air Volume f /m (m3/h) 4,400
3
5,200 6200 8,000 9,600 11,000 13.700 13.700
0.2" External Static (7,476) (8,835) (10534) (13,592) (16,310) (18,689) (23,276) (23,276)
Standard Fan Motor, Nominal hp (kW) 3.75 3.75 3.75 3.4 5.4 7.9 10.5 10.5
(total for all fans) (2.8) (2.8) (2.8) (2.5) (4.0) (5.9) (7.8) (7.8)
Number of fans 1 1 1 2 2 2 3 3
1. Refer to Appendix A for U.S. Department of Energy Performance Data.
2. Application data is rated and factory certified per ASHRAE 127-2012 with a 5% tolerance.
3. Some options or combinations of options may result in reduced air flow—Contact factory for recommendations.
4. Digital scroll not available on 077 and 105 models; units available with semi-hermetic and standard scroll compressors only
5. 40% ethylene glycol

Liebert® DS™ 14
Liebert DS Glycol-Cooled System Data

Table 8 Application data—Glycol-cooled units with forward-curved blowers 1


Model Size 028 035 042 053 070 077 105U 105V
APPLICATION DATA WITH FORWARD-CURVED BLOWERS
Net Application Data BTUH (kW), Standard Air Volume and Evaporator Fan Motor, Semi-Hermetic Compressors
Semi-Hermetic Compressors (4Step Cooling) with Forward-Curved Blowers
85°F DB, 64.5°F WB, 52.3°F DP (29.4°C DB, 18.1°C WB) 32.4% RH
123.1 126.8 144.4 194.8 233.2 258.8 340.4 324.4
Total kBTUH (kW)
(36.1) (37.2) (42.3) (57.1) (68.3) (75.9) (99.8) (95.1)
122.2 126.8 144.4 193.5 229.9 254.9 327.4 323.1
Sensible kBTUH (kW)
(35.8) (37.2) (42.3) (56.7) (67.4) (74.7) (96.0) (94.7)
80°F DB, 62.9°F WB, 52.3°F DP (26.7°C DB, 17.1°C WB) 38.2% RH
116.9 118.8 135.3 185.1 221.8 246.6 325.5 300.0
Total kBTUH (kW)
(34.2) (34.8) (39.6) (54.2) (65) (72.3) (95.4) (87.9)
110.7 117.3 133.4 177.6 209.7 232.5 298 295.3
Sensible kBTUH (kW)
(32.4) (34.4) (39.1) (52.1) (61.5) (68.1) (87.3) (86.5)
75°F DB, 61.1°F WB, 52.3°F DP (23.9°C DB, 16.2°C WB) 45% RH
111.4 112.3 128 176 211.5 235.6 311.2) 282.6
Total kBTUH (kW)
(32.7) (32.9) (37.5) (51.6) (62) (69.1) (91.2 (82.8)
98.1) 104.1 118.3 158.4 186.4 206.2 263.7 262.2
Sensible kBTUH (kW)
(28.7) (30.5) (34.7) (46.4) (54.6) (60.4) (77.3) (76.8)
Net Application Data BTUH (kW), Standard Air Volume and Evaporator Fan Motor
Scroll Compressors Only
Scroll or Digital Scroll Compressors with Forward-Curved Blowers (not available after 12/31/15)
85°F DB, 64.5°F WB, 52.3°F DP (29.4°C DB, 18.1°C WB) 32.4% RH
106.5 124.5 139.4 199.3 239 265.7 338.7
Total kBTUH (kW) —
(31.2) (36.5) (40.8) (58.4) (70.1) (77.9) (99.3)
106.5 124.5 139.4 197.1 234.3 259.8 326.3
Sensible kBTUH (kW) —
(31.2) (36.5) (40.8) (57.8) (68.7) (76.1) (95.6)
80°F DB, 62.9°F WB, 52.3°F DP (26.7°C DB, 17.1°C WB) 38.2% RH
100.8 117 130.8 189.8 228.3 254.3 324.8
Total kBTUH (kW) —
(29.6) (34.3) (38.3) (55.6) (66.9) (74.5) (95.2)
100.4 116.1 130.2 180.5 213.5 236.7 297.7
Sensible kBTUH (kW) —
(29.4) (34) (38.1) (52.9) (62.6) (69.4) (87.2)
75°F DB, 61.1°F WB, 52.3°F DP (23.9°C DB, 16.2°C WB) 45% RH
95.4 111.2 124 181.1 218.8 244 311.6
Total kBTUH (kW) —
(28) (32.6) (36.4) (53.1) (64.1) (71.5) (91.3)
89.8 103.5 116.3 161 190.1 210.1 264
Sensible kBTUH (kW) —
(26.3) (30.3) (34.1) (47.2) (55.7) (61.6) (77.4)
FAN SECTION - Downflow Models - Fixed Pitch, Two Belts
Standard Air Volume f /m (m3/h) 4,400
3
5,200 6,300 7,500 9,000 10,400 13,700 13,700
0.2" External Static (7,476) (8,835) (10,704) (12,743) (15,291) (17,670) (23,276) (23,276)
Standard Fan Motor hp (kW) 2 (1.5) 3 (2.2) 5 (3.7) 3 (2.2) 5 (3.7) 7.5 (5.6) 10 (7.5) 10 (7.5)
Optional Fan Motor hp (kW) 3 (2.2) 5 (3.7) 7.5 (5.6) 5 (3.7) 7.5 (5.6) 10 (7.5) 15 (11.2) 15 (11.2)
Number of Fans 1 1 1 2 2 2 3 3
1. Refer to Appendix A for U.S. Department of Energy Performance Data.
2. Application data is rated and factory certified per ASHRAE 127-2012 with a 5% tolerance.
3. Some options or combinations of options may result in reduced air flow—Contact factory for recommendations.
4. Digital scroll not available on 077 and 105 models; units available with semi-hermetic and standard scroll compressors only
5. 40% ethylene glycol

15 Liebert® DS™
Liebert DS Glycol-Cooled System Data

Table 9 Physical data—Glycol-cooled units


Model Size 028 035 042 053 070 077 105U 105V
EVAPORATOR COIL - A-Frame - Copper Tube/Aluminum Fin
Face Area, sq. ft. (sq. m) 17.1 (1.6) 17.1 (1.6) 17.1 (1.6) 24.7 (2.3) 24.7 (2.3) 24.7 (2.3) 32.3 (3.0) 32.3 (3.0)
Rows of Coil 3 3 3 3 3 3 3 3
REHEAT SECTION
Electric Reheat - Three-Stage, Stainless Steel Fin Tubular, Capacity Does Not Include Fan Motor Heat
Capacity, kBTUH (kW),
Standard Selection 51.2 (15.0) 51.2 (15.0) 51.2 (15.0) 85.3 (25.0) 85.3 (25.0) 85.3 (25.0) 102.4 (30.0) 102.4) (30.0

Capacity, kBTUH (kW),


34.1 (10.0) 34.1 (10.0) 34.1 (10.0) 51.2 (15.0) 51.2 (15.0) 51.2 (15.0) 20.0 (68.3) 20.0 (68.3)
Optional Selection
Electric Reheat - SCR Control, Stainless Steel Fin Tubular (Optional Selection)
Capacity, kBTUH (kW) 51.2 (15.0) 51.2 (15.0) 51.2 (15.0) 85.3 (25.0) 85.3 (25.0) 85.3 (25.0) 30.0 (102.4) 30.0 (102.4)
HUMIDIFIER SECTION
Infrared Humidifier
Capacity, lb/hr (kg/h) 11.0 (5.0) 11.0 (5.0) 11.0 (5.0) 22.0 (10.0) 22.0 (10.0) 22.0 (10.0) 22.0 (10.0) 22.0 (10.0)
FILTER SECTION - Disposable Type - Nominal Sizes and Quantities, Standard MERV 8 or Optional MERV 11
(Filter types cannot be mixed, must be all MERV 8 or all MERV 11)
Downflow Models
Quantity 3 3 3 4 4 4 4 4
2 @ 25x20 2 @ 25x20 2 @ 25x20
Nominal Size, inches 4 @ 25x20 4 @ 25x20 4 @ 25x20 4 @ 25x20 4 @ 25x20
1 @ 25x16 1 @ 25x16 1 @ 25x16
Upflow Models (Front and Rear Return)
Filters located in separate filter box on rear return, located on lower unit panel on front return
Quantity 4 4 4 6 6 6 8 8
Nominal Size, inches 25x20 25x20 25x20 25x20 25x20 25x20 25x20 25x20
OUTDOOR DRYCOOLERS - STANDARD 95°F AMBIENT SELECTION; SEE Table 72 FOR OTHER SELECTIONS
Model Number D-174 D-174 D-225 D-260 D-310 D-350 D-466 D-466
Number of Fans 2 2 2 3 3 3 4 4
CONDENSER FLOW REQUIREMENTS—with 40% Ethylene Glycol
GLYCOL-COOLED SYSTEM -Semi-Hermetic Compressors, based on 75°F/45% room conditions with EC fans
THR, kBTUH (kW) 154.9 (45.4) 159.1 (46.6) 189 (55.4) 238.3 (69.8) 297.7 (87.2) 341.8 (100.2) 456.9 (133.9) 456.9 (133.9)
104°F (40°C) EGT, GPM 32 33.5 39 49 62 70 96 96
(l/m) (121.1) (135) (148) (185) (234.7) (265) (363) (363)
Pressure Drop, ft. of water 12.9 14 18.6 16 25 31.3 50.6 50.6
(kPa), (38.5) (41.9) (55.7) (47.7) (74.7) (93.6) (151.3) (151.3)
Standard Scroll Compressors
GLYCOL-COOLED SYSTEM - Digital Scroll Compressors, based on 75°F/45% room with EC Fans
conditions with EC Fans (not available after 12/31/15)
THR, kBTUH (kW) 134.5 (39.4) 162.4 (47.6) 186.8 (54.7) 248 (72.7) 311.1 (91.2) 353.7 (103.7) 440.1 (129) —
104°F (40°C) EGT, GPM
(l/m) 28 (106) 33.5 (127) 39 (148) 52 (163.5) 64 (242) 73.5 (278) 91.5 (264.9) —

Pressure Drop, ft. of water


10.0 (29.8) 14.0 (41.9) 18.6 (55.6) 17.9 (53.5) 26.6 (79.5) 34.4 (102.8) 46.2 (138.1) —
(kPa)
PIPING CONNECTION SIZES - Glycol-Cooled Liebert DS Indoor Unit
Glycol Supply, O.D. Copper 1-5/8" (41) 1-5/8" (41) 2-1/8" (54) 2-1/8" (54) 2-1/8" (54) 2-1/8" (54) 2-1/8" (54) 2-1/8" (54)
Glycol Return, O.D. Copper 1-5/8" (41) 1-5/8" (41) 2-1/8" (54) 2-1/8" (54) 2-1/8" (54) 2-1/8" (54) 2-1/8" (54) 2-1/8" (54)
Infrared Humidifier, O.D.
1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4
Copper
Condensate Drain, FPT 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4
Condensate Drain w/Optional 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2
Condensate Pump, OD
Hot Water Reheat, O.D.
Copper 5/8 5/8 5/8 5/8 5/8 5/8 5/8 5/8

Liebert® DS™ 16
Liebert DS GLYCOOL™ System Data


5.0 LIEBERT DS GLYCOOL SYSTEM DATA
Table 10 Application data—GLYCOOL units with EC fans 1
Model Size 028 035 042 053 070 077 105U 105V
APPLICATION DATA with EC Fans
Net Application Data BTUH (kW), Standard Air Volume and Evaporator Fan Motor,

Semi-Hermetic Compressors (Four-Step Cooling) with EC Fans


85°F DB, 64.5°F WB, 52.3°F DP (29.4°C DB, 18.1°C WB) 32.4% RH
124.6 129.3 148.4 197.9 236.3 263.7 342.6 327.4
Total kBTUH (kW)
(36.5) (37.9) (43.5) (58.0) (69.3) (77.3) (100.4) (95.9)
123.7 129.3 148.4 197.8 235.1 259.7 328.7 325.1
Sensible kBTUH (kW)
(36.3) (37.9) (43.5) (58.0) (68.9) (76.1) (96.3) (95.2)
80°F DB, 62.9°F WB, 52.3°F DP (26.7°C DB, 17.1°C WB) 38.2% RH
118.4 121.2 139.5 187.4 224.2 251.5 327.8 302.7
Total kBTUH (kW)
(34.7) (35.5) (40.9) (54.9) (65.7) (73.7) (96.1) (88.7)
112.3 119.8 137.2 182.3 215.5 237.2 299.1 296.8
Sensible kBTUH (kW)
(32.9) (35.1) (40.2) (53.4) (63.2) (69.5) (87.7) (87)
75°F DB, 61.1°F WB, 52.3°F DP (23.9°C DB, 16.2°C WB) 45.1% RH
112.9 114.7 132.3 177.7 213.3 240.5 313.7 285.3
Total kBTUH (kW)
(33.1) (33.6) (38.8) (52.1) (62.5) (70.5) (91.9) (83.6)
99.6 106.6 122 163 192 210.9 265.1 263.5
Sensible kBTUH (kW)
(29.2) (31.2) (35.8) (47.8) (56.3) (61.8) (77.7) (77.2)
Net Application Data BTUH (kW), Standard Air Volume and Evaporator Fan Motor
Scroll Compressors Only
Scroll or Digital Scroll compressors with EC Fans (not available after 12/31/15)
85°F DB, 64.5°F WB, 52.3°F DP (29.4°C DB, 18.1°C WB) 32.4% RH
108 127.1 143.5 201.6 241.9 263.7 340.9
Total kBTUH (kW) —
(31.7) (37.2) (42.1) (59.1) (70.9) (77.3) (99.9)
108 127.1 143.5 201.1 239.6 257.9 327.6
Sensible kBTUH (kW) —
(31.7) (37.2) (42.1) (58.9) (70.2) (75.6) (96.0)
80°F DB, 62.9°F WB, 52.3°F DP (26.7°C DB, 17.1°C WB) 38.2% RH
102.4 119.6 135.1 191.4 230.6 252.3 327.1
Total kBTUH (kW) —
(30) (35.1) (39.6) (56.1) (67.6) (73.9) (95.9)
102 118.6 134.1 185.1 219.5 234.8 298.8
Sensible kBTUH (kW) —
(29.9) (34.8) (39.3) (54.2) (64.3) (68.8) (91.2)
75°F DB, 61.1°F WB, 52.3°F DP (23.9°C DB, 16.2°C WB) 45% RH
96.9 113.7 128.5 182.3 220.7 242 314.1
Total kBTUH (kW) —
(28.4) (33.3) (37.6) (53.4) (64.7) (70.9) (92.0)
91.4 106.1 120.1 165.5 195.8 208.3 265.4
Sensible kBTUH (kW) —
(26.8) (31.1) (35.2) (48.5) (57.4) (61.0) (77.8)
FAN SECTION - Downflow Models - EC Fans Under Floor
Standard Air Volume f /m (m3/h) 4,400
3
5,200 6200 8,000 9,600 10,400 13,500 13,500
0.2" External Static (7,476) (8,835) (10,534) (13,592) (16,310) (17670) (22937) (22937)
Standard Fan Motor, Nominal hp (kW) 3.75 3.75 3.75 3.4 5.4 7.9 10.5 10.5
(total for all fans) (2.8) (2.8) (2.8) (2.5) (4.0) (5.9) (7.8) (7.8)
Number of fans 1 1 1 2 2 2 3 3
1. Refer to Appendix A for U.S. Department of Energy Performance Data.
2. Application data is rated and factory certified per ASHRAE 127-2012 with a 5% tolerance.
3. Some options or combinations of options may result in reduced air flow—Contact factory for recommendations.
4. Digital scroll not available on 077 and 105 models; units available with semi-hermetic and standard scroll compressors only
5. 40% ethylene glycol

17 Liebert® DS™
Liebert DS GLYCOOL™ System Data

Table 11 Application data—GLYCOOL™ units with forward-curved blowers 1


Model Size 028 035 042 053 070 077 105U 105V
APPLICATION DATA WITH FORWARD-CURVED BLOWERS
Net Application Data BTUH (kW), Standard Air Volume and Evaporator Fan Motor, Semi-Hermetic Compressors
Semi-Hermetic Compressors (4 Step Cooling) with Forward-Curved Blowers
85°F DB, 64.5°F WB, 52.3°F DP (29.4°C DB, 18.1°C WB) 32.4% RH
122.4 125.7 142.8 193.2 230.8 255.7 336.5 319.1
Total kBTUH (kW)
(35.9) (36.8) (41.9) (56.6) (67.6) (74.9) (98.6) (93.5)
121.5 125.7 142.8 191.9 227.5 251.7 322.6 316.8
Sensible kBTUH (kW)
(35.6) (36.8) (41.9) (56.2) (66.7) (73.8) (94.6) (92.8)
80°F DB, 62.9°F WB, 52.3°F DP (26.7°C DB, 17.1°C WB) 38.2% RH
116.2 117.7 133.7 183.4 219.4 243.5 321.7 295.2
Total kBTUH (kW)
(34.1) (34.5) (39.2) (53.8) (64.3) (71.4) (94.3) (86.5)
110 116.3 131.9 176 207.3 229.2 293 289.5
Sensible kBTUH (kW)
(32.3) (34.1) (38.6) (51.6) (60.8) (67.2) (89.5) (84.8)
75°F DB, 61.1°F WB, 52.3°F DP (23.9°C DB, 16.2°C WB) 45% RH
110.7 111.1 126.5 174.4 209 232.4 307.6 278.2
Total kBTUH (kW)
(32.5) (32.6) (37.1) (51.1) (61.3) (68.1) (90.1) (81.5)
97.4 103 116.7 156.8 184 202.8 258.9 256.9
Sensible kBTUH (kW)
(28.5) (30.2) (34.2) (45.9) (53.9) (59.4) (75.9) (75.3)
Net Application Data BTUH (kW), Standard Air Volume and Evaporator Fan Motor
Scroll Compressors Only
Scroll or Digital Scroll Compressors with Forward-Curved Blowers (not available after 12/31/15)
85°F DB, 64.5°F WB, 52.3°F DP (29.4°C DB, 18.1°C WB) 32.4% RH
105.8 123.5 137.8 197.4 236.6 262 334.8
Total kBTUH (kW) —
(31) (36.2) (40.4) (57.9) (69.3) (76.8) (98.1)
105.8 123.5 137.8 195.3 231.8 256.2 321.5
Sensible kBTUH (kW) —
(31) (36.2) (40.4) (57.2) (67.9) (75.1) (94.2)
80°F DB, 62.9°F WB, 52.3°F DP (26.7°C DB, 17.1°C WB) 38.2% RH
100.2 116.1 129.3 187.9 225.9 250.6 321
Total kBTUH (kW) —
(29.4) (34) (37.9) (55.1) (66.2) (73.4) (94.1)
99.8 115.1 128.6 178.8 211.1 233.1 292.7
Sensible kBTUH (kW) —
(29.2) (33.7) (37.7) (52.4) (61.9) (68.3) (89.4)
75°F DB, 61.1°F WB, 52.3°F DP (23.9°C DB, 16.2°C WB) 45% RH
94.7 110.2 122.5 179.1 216.4 240.3 307.9
Total kBTUH (kW) —
(27.8) (32.3) (35.9) (52.5) (63.4) (70.4) (90.3)
89.1 102.5 114.7 159.2 187.6 206.6 259.3
Sensible kBTUH (kW) —
(26.1) (30) (33.6) (46.7) (55) (60.5) (76)
FAN SECTION - Downflow Models - Fixed Pitch, Two Belts
3 3
Standard Air Volume f /m (m /h) 4,400 5,200 6,300 7,500 9,000 10,400 13,700 13,700
0.2" External Static (7,476) (8,835) (10,704) (12,743) (15,291) (17,670) (23,276) (23,276)
Standard Fan Motor hp (kW) 2 (1.5) 3 (2.2) 5 (3.7) 3 (2.2) 5 (3.7) 7.5 (5.6) 10 (7.5) 10 (7.5)
Optional Fan Motor hp (kW) 3 (2.2) 5 (3.7) 7.5 (5.6) 5 (3.7) 7.5 (5.6) 10 (7.5) 15 (11.2) 15 (11.2)
Number of Fans 1 1 1 2 2 2 3 3
1. Refer to Appendix A for U.S. Department of Energy Performance Data.
2. Application data is rated and factory certified per ASHRAE 127-2012 with a 5% tolerance.
3. Some options or combinations of options may result in reduced air flow—Contact factory for recommendations.
4. Digital scroll not available on 077 and 105 models; units available with semi-hermetic and standard scroll compressors only
5. 40% ethylene glycol

Liebert® DS™ 18
Liebert DS GLYCOOL™ System Data

Table 12 Physical data—GLYCOOL™ units


Model Size 028 035 042 053 070 077 105U 105V
EVAPORATOR COIL - A-Frame - Copper Tube/Aluminum Fin
Face Area, sq. ft. (sq. m) 17.1 (1.6) 17.1 (1.6) 17.1 (1.6) 24.7 (2.3) 24.7 (2.3) 24.7 (2.3) 32.3 (3.0) 32.3 (3.0)
Rows of Coil 3 3 3 3 3 3 3 3
REHEAT SECTION
Electric Reheat - Three-Stage, Stainless Steel Fin Tubular, Capacity Does Not Include Fan Motor Heat
Capacity, kBTUH (kW), Standard
51.2 (15.0) 51.2 (15.0) 51.2 (15.0) 85.3 (25.0) 85.3 (25.0) 85.3 (25.0) 102.4 (30.0) 102.4 (30.0)
Selection
Capacity, kBTUH (kW), Optional
34.1 (10.0) 34.1 (10.0) 34.1 (10.0) 51.2 (15.0) 51.2 (15.0) 51.2 (15.0) 68.3 (20.0) 68.3 (20.0)
Selection
Electric Reheat - SCR Control, Stainless Steel Fin Tubular (Optional Selection)
Capacity, kBTUH (kW) 51.2 (15.0) 51.2 (15.0) 51.2 (15.0) 85.3 (25.0) 85.3 (25.0) 85.3 (25.0) 102.4 (30.0) 102.4 (30.0)
HUMIDIFIER SECTION
Infrared Humidifier
Capacity, lb/hr (kg/h) 11.0 (5.0) 11.0 (5.0) 11.0 (5.0) 22.0 (10.0) 22.0 (10.0) 22.0 (10.0) 22.0 (10.0) 22.0 (10.0)
FILTER SECTION - Disposable Type - Nominal Sizes and Quantities, Standard MERV 8 or Optional MERV 11
(filter types cannot be mixed, must be all MERV 8 or all MERV 11)
Downflow Models
Quantity 3 3 3 4 4 4 4 4
2 @ 25x20 2 @ 25x20 2 @ 25x20
Nominal Size, inches 1 @ 25x16 1 @ 25x16 1 @ 25x16 4 @ 25x20 4 @ 25x20 4 @ 25x20 4 @ 25x20 4 @ 25x20

Upflow Models (Front & Rear Return) Filters located in separate filter box on rear return, located on lower unit panel on front return
Quantity 4 4 4 6 6 6 8 8
Nominal Size, inches 25x20 25x20 25x20 25x20 25x20 25x20 25x20 25x20
OUTDOOR DRYCOOLERS - Standard 95°F Ambient Selection; See Table 72 for other selections
Model Number D-174 D-174 D-225 D-260 D-310 D-350 D-466 D-466
Number of Fans 2 2 2 3 3 3 4 4
CONDENSER FLOW REQUIREMENTS—40% Ethylene Glycol
GLYCOOL SYSTEM - Semi-Hermetic Compressors, Based on 75°F/45% Room Conditions with EC Fans
THR, kBTUH (kW) 154.9 (45.4) 159 (46.6) 189.2 (55.5) 240.8 (70.6) 297.7 (87.2) 339.3 (99.4) 455.9 (133.6) 455.9 (133.6)
104°F (40°C) EGT, GPM (l/m) 32 (121) 33 (125) 40 (151) 49 (185) 62 (235) 71 (269) 95 (360) 95 (360)
Pressure Drop, ft. of water (kPa), 12.9 (38.50) 13.6 (40.60) 19.6 (58.59) 16.0 (47.83) 25.0 (74.73) 32.2 (96.25) 49.6 (148.30) 49.6 (148.30)
GLYCOOL SYSTEM - Digital Scroll Compressors, Based on 75°F/45% Room Conditions with EC Scroll Compressors Only
Fans (not available after 12/31/15)
THR, kBTUH (kW) 134.5 (39.4) 162.4 (47.6) 186.8 (54.7) 248 (72.7) 311.1 (91.2) 351.1 (102.9) 439.1 (128.7) —
104°F (40°C) EGT, GPM (l/m) 28 (98.4) 33.5 (127) 39 (148) 51 (193) 64 (242) 72 (273) 89 (337) —
Pressure Drop, ft. of water (kPa) 10.0 (29.89) 14.0 (41.85) 18.6 (55.60) 17.2 (51.41) 26.6 (79.51) 33.1 (98.84) 43.8 (130.92) —
PIPING CONNECTION SIZES - Glycol-Cooled Liebert DS Indoor Unit
Glycol Supply, O.D. Copper 1-5/8" (41) 1-5/8" (41) 2-1/8" (54) 2-1/8" (54) 2-1/8" (54) 2-1/8" (54) 2-1/8" (54) 2-1/8" (54)
Glycol Return, O.D. Copper 1-5/8" (41) 1-5/8" (41) 2-1/8" (54) 2-1/8" (54) 2-1/8" (54) 2-1/8" (54) 2-1/8" (54) 2-1/8" (54)
Infrared Humidifier, O.D. Copper 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4
Condensate Drain, FPT 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4
Condensate Drain w/Optional
1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2
Condensate Pump, OD
Hot Water Reheat, O.D. Copper 5/8 5/8 5/8 5/8 5/8 5/8 5/8 5/8
ECON-O-COIL APPLICATION DATA (GLYCOOL Units), 40% Ethylene Glycol, Net Application Data, kBTUH (kW)
75°F DB, 62.57°FWB (23.9°C, 16.9°C) 45% RH, 45°F EGT Room Conditions with EC Fans
Total capacity kBTUH (kW) 82.8 (24.3) 93.9 (27.5) 103.9 (30.4) 156.8 (45.9) 182.3 (53.4) 182.3 (57.2) 243.3 (71.3) 243.3 (71.3)
Sensible Capacity 82.4 (24.1) 93.9 (27.5) 103.9 (30.4) 152.6 (44.7) 176.9 (51.8) 176.9 (55.3) 238.2 (69.8) 238.2 (69.8)
Flow rate, GPM (l/m) 28 (106) 33.5 (127) 39 (148) 51 (193) 64 (242) 72 (273) 89 (337) 89 (337)
Pressure Drop, ft. of water (kPa) 18.4 (55.0) 25.7 (76.82) 33.8 (101.03) 38.9 (116.27) 59.1 (176.65) 73.5 (219.70) 75.2 (224.78) 75.2 (224.78)
FLUID VOLUMES
Unit Volume Without Econ-O-Coil,
4 (15.2) 4 (15.2) 4 (15.2) 7 (26.6) 7 (26.6) 7 (26.6) 8 (30.4) 8 (30.4)
gal (l)
Unit Volume w/Econ-O-Coil, gal (l) 9 (34.2) 9 (34.2) 9 (34.2) 14 (53.2) 14 (53.2) 14 (53.2) 17 (64.6) 17 (64.6)

19 Liebert® DS™
Electrical Data

6.0 ELECTRICAL DATA

6.1 Air-cooled Electrical Data


Table 13 Electrical data—Air-cooled systems with EC fans
Reheat Electric Electric Electric, Electric,
Options Standard, kW None Standard kW None Downsized kW Downsized kW

Humidifier
Options Infrared Infrared None None Humidifier No Humidifier

Model
# Volts 208 230 460 575 208 230 460 575 208 230 460 575 208 230 460 575 208 230 460 575 208 230 460 575

FLA 67.3 64.8 32.1 25.5 56.3 54.1 26.9 24.2 67.3 64.8 32.1 25 43 43 21.1 16.8 56.3 54.1 26.9 24.2 53.5 51.9 25.6 19.9
DS028 WSA 82 78.9 39.2 31.9 60.6 58.4 29.1 25.9 82 78.9 39.2 30.5 47.3 47.3 23.3 18.5 64.8 62.8 31.1 25.9 64.8 62.8 31.1 24.1
OPD 80 80 40 30 70 70 35 30 80 80 40 30 60 60 30 25 70 70 35 30 70 70 35 25
FLA 70.7 68.2 33.4 25.5 63.1 60.9 29.5 25.2 70.7 68.2 33.4 25.5 49.8 49.8 23.7 17.8 63.1 60.9 29.5 25.2 56.9 55.3 26.9 20.4
DS035 WSA 86.3 83.2 40.8 31.9 68.3 66.1 32 27.1 86.3 83.2 40.8 31.1 55 55 26.2 19.7 69 67 32.7 27.1 69 67 32.7 24.8
OPD 90 90 45 30 80 80 40 30 90 90 45 30 70 70 35 25 80 80 40 30 80 80 35 25
FLA 78.2 75.9 37.7 33 78.1 75.9 37.7 33 78.2 75.7 37.5 29.4 64.8 64.8 31.9 25.6 78.1 75.9 37.7 33 64.8 64.8 31.9 25.6
DS042 WSA 95.7 92.5 46 36 85.2 83 41.2 35.8 95.7 92.5 46 36 71.9 71.9 35.4 28.4 85.2 83 41.2 35.8 78.4 76.4 37.8 29.6
OPD 110 110 50 45 110 110 50 45 110 110 50 40 100 100 45 35 110 110 50 45 100 100 45 35
FLA 119.9 116 57.1 43.5 109.2 104.8 52.4 42 119.9 116 57.1 43.5 82.6 82.6 40.8 30.4 109.2 104.8 52.4 42 92.1 89.6 44.1 33.5
DS053 WSA 145.3 140.4 69.4 53.9 117.2 112.8 56.5 45 145.3 140.4 69.4 52.8 90.6 90.62 44.9 33.4 117.2 112.8 56.5 45 110.52 107.4 53.1 40.3
OPD 150 150 70 50 125 125 70 50 150 150 70 50 110 110 60 45 125 125 70 50 125 125 60 45
FLA 129.2 125.3 59.9 46.4 127.8 123.4 58 46.4 129.2 125.3 59.9 45.7 101.2 101.2 46.4 34.8 127.8 123.4 58 46.4 101.4 101.2 46.9 35.7
DS070 WSA 156.9 152 72.9 55.5 138.2 133.8 62.8 50 156.9 152.0 72.9 55.5 111.6 111.6 51.2 38.4 138.2 133.8 62.8 50 122.15 119.02 56.6 43
OPD 175 175 80 60 175 175 80 60 175 175 80 60 150 150 70 50 175 175 80 60 150 150 70 50
FLA 139.2 134.8 61.4 50 139.2 134.8 61 50 134.9 131 61.4 47.5 112.6 112.6 49.4 38.4 139.2 134.8 61 50 112.6 112.6 49.4 38.4
DS077 WSA 164 159.2 74.8 57.8 151. 146.6 66.2 54 164.0 159.2 74.8 57.8 124.37 124.4 54.6 42.4 151 146.6 66.2 54 129.27 126.15 58.5 45.3
OPD 175 175 80 70 175 175 80 70 175 175 80 60 150 150 70 50 175 175 80 70 150 150 70 50
FLA 171.5 167.1 83.7 69.1 171.5 167.1 83.7 69.1 164 163.5 79.8 62.6 144.9 144.9 72.1 57.5 171.5 167.1 83.7 69.1 144.9 144.9 72.1 57.5
DS105 WSA 198.8 198.2 97.4 76.4 186.5 182.1 91.6 75.4 198.8 198.2 97.4 76.4 159.9 159.9 80 63.8 186.5 182.1 91.6 75.4 169.3 165.5 81.3 63.9
OPD 225 225 110 100 225 225 110 100 225 225 110 90 200 200 110 80 225 225 110 100 200 200 110 80
1. Reduced reheat for 028, 035, and 042 models is 10kW.
2. Reduced reheat for 053, 070, and 077 models is 15kW.
3. Consult local representative for SCR reheat values.
4. Reduced reheat for 105 kW models is 20kW.
5. SCCR - Short Circuit Current Rating 65,000 amps rms symmetrical maximum.
6. Steam canister humidifiers not available on models with EC fans.

Liebert® DS™ 20
Electrical Data

Table 14 Electrical data—Air-cooled systems with forward-curved blowers


Reheat Options Electric, Std. kW None Electric, Std. kW None
Infrared or Steam Infrared or Steam
Humidifier Options Generating Canister Generating Canister None None
Motor
Model hp Volts 208 230 460 575 208 230 460 575 208 230 460 575 208 230 460 575
FLA 66.4 63.2 31.8 25.2 55.4 52.5 26.6 23.9 66.4 63.2 31.8 24.7 42.1 41.4 20.8 16.5
028 2.0 WSA 81.1 77.3 38.9 31.5 59.7 56.8 28.8 25.6 81.1 77.3 38.9 30.2 46.4 45.7 23 18.2
OPD 80 80 40 30 70 70 35 30 80 80 40 30 60 60 30 25
FLA 69.5 66.0 33.2 26.4 58.5 55.3 28.0 25.1 69.5 66.0 33.2 25.9 45.2 44.2 22.2 17.7
028 3.0 WSA 84.2 80.1 40.3 33 62.8 59.6 30.2 26.8 84.2 80.1 40.3 31.4 49.5 48.5 24.4 19.4
OPD 90 80 40 30 80 70 35 30 90 80 40 30 60 60 30 25
FLA 72.9 69.4 34.5 26.4 65.3 62.1 30.6 26.1 72.9 69.4 34.5 26.4 52.0 51.0 24.8 18.7
035 3.0 WSA 88.5 84.4 41.9 33.0 70.5 67.3 33.1 28.0 88.5 84.4 41.9 32.0 57.2 56.2 27.3 20.6
OPD 90 90 45 35 90 80 40 35 90 90 45 35 70 70 35 25
FLA 79.0 75.0 37.3 28.6 71.4 67.7 33.4 28.3 79.0 75.0 37.3 28.6 58.1 56.6 27.6 20.9
035 5.0 WSA 94.6 90.0 44.7 35.8 76.6 72.9 35.9 30.2 94.6 90.0 44.7 34.2 63.3 61.8 30.1 22.8
OPD 100 100 45 35 90 90 45 35 100 100 45 35 80 80 40 30
FLA 86.5 82.7 41.6 36.1 86.4 82.7 41.6 36.1 86.5 82.5 41.4 32.5 73.1 71.6 35.8 28.7
042 5.0 WSA 104 99.3 49.9 39.1 93.5 89.8 45.1 38.9 104.0 99.3 49.9 39.1 80.2 78.7 39.3 31.5
OPD 110 110 50 50 110 110 50 50 110 110 50 45 100 100 50 40
FLA 94.0 89.5 45.0 39.0 93.9 89.5 45.0 39.0 94.0 89.3 44.8 35.4 80.6 78.4 39.2 31.6
042 7.5 WSA 111.5 106.1 53.3 42.0 101.0 96.6 48.5 41.8 111.5 106.1 53.3 42.0 87.7 85.5 42.7 34.4
OPD 125 110 60 50 125 110 60 50 125 110 60 45 110 110 50 45
FLA 112.1 107.2 53.9 41 101.4 96 49.2 39.5 112.1 107.2 53.9 41 74.8 73.8 37.6 27.9
053 3.0 WSA 137.5 131.6 66.2 50.8 109.4 104.0 53.3 42.5 137.5 131.6 66.2 50.3 82.8 81.8 41.7 30.9
OPD 150 125 70 50 125 125 60 50 150 125 70 50 110 110 50 40
FLA 118.2 112.8 56.7 43.2 107.5 101.6 52.0 41.7 118.2 112.8 56.7 43.2 80.9 79.4 40.4 30.1
053 5.0 WSA 143.6 137.2 69.0 53.5 115.5 109.6 56.1 44.7 143.6 137.2 69.0 52.5 88.9 87.4 44.5 33.1
OPD 150 150 70 50 125 125 70 50 150 150 70 50 110 110 60 45
FLA 127.5 122.1 59.5 46.1 126.1 120.2 57.6 46.1 127.5 122.1 59.5 45.4 99.5 98 46 34.5
070 5.0 WSA 155.2 148.8 72.5 55.2 136.5 130.6 62.4 49.7 155.2 148.8 72.5 55.2 109.9 108.4 50.8 38.1
OPD 175 150 80 60 175 150 80 60 175 150 80 60 150 125 70 50
FLA 135.0 128.9 62.9 49.0 133.6 127.0 61.0 49.0 135.0 128.9 62.9 48.3 107.0 104.8 49.4 37.4
070 7.5 WSA 162.7 155.6 75.9 58.1 144.0 137.4 65.8 52.6 162.7 155.6 75.9 58.1 117.4 115.2 54.2 41.0
OPD 175 175 80 60 175 175 80 60 175 175 80 60 150 150 70 50
FLA 145 138.4 64.4 52.6 145.0 138.4 64.0 52.6 140.7 134.6 64.4 50.1 118.4 116.2 52.4 41.0
077 7.5 WSA 169.8 162.8 77.8 60.4 156.8 150.2 69.2 56.6 169.8 162.8 77.8 60.4 130.2 128.0 57.6 45.0
OPD 200 175 90 70 200 175 80 70 175 175 90 70 175 175 70 60
FLA 151.6 144.4 67.4 54.6 151.6 144.4 67.0 54.6 147.3 140.6 67.4 52.1 125.0 122.2 55.4 43.0
077 10.0 WSA 176.4 168.8 80.8 62.4 163.4 156.2 72.2 58.6 176.4 168.8 80.8 62.4 136.8 134.0 60.6 47.0
OPD 200 200 90 70 200 200 90 70 200 175 90 70 175 175 80 60
FLA 177.4 170.2 88.4 72.6 177.4 170.2 88.4 72.6 169.9 166.6 84.5 66.1 150.8 148 76.8 61.0
105 10.0 WSA 204.7 201.3 102.1 79.9 204.7 201.3 102.1 79.9 204.7 201.3 102.1 79.9 165.8 163.0 84.7 67.3
OPD 250 225 125 100 250 225 125 100 225 225 110 90 225 200 110 90
FLA 192.3 184.2 95.4 78.6 192.3 184.2 95.4 78.6 185.3 180.6 91.5 72.1 166.2 162.0 83.8 67.0
105 15.0 WSA 220.1 215.3 109.1 85.9 220.1 215.3 109.1 85.9 220.1 215.3 109.1 85.9 181.2 177.0 91.7 73.3
OPD 250 250 125 100 250 250 125 100 250 250 125 100 225 225 110 90
1. Reduced reheat for 028, 035, and 042 models is 10kW.
2. Reduced reheat for 053, 070, and 077 models is 15kW.
3. Consult local representative for SCR reheat values.
4. Reduced reheat for 105 kW models is 20kW.
5. SCCR - Short Circuit Current Rating 65,000 amps rms symmetrical maximum.

21 Liebert® DS™
Electrical Data

Table 14 Electrical data—Air-cooled systems with forward-curved blowers (continued)


Reheat Options Electric, Downsized kW
Humidifier Options Infrared or Steam Generating Canister None
Model Motor, hp Volts 208 230 460 575 208 230 460 575
FLA 55.4 52.5 26.6 23.9 52.6 50.3 25.3 19.6
028 2.0 WSA 63.9 61.2 30.8 25.6 63.9 61.2 30.8 23.8
OPD 70 70 35 30 70 70 35 25
FLA 58.5 55.3 28 25.1 55.7 53.1 26.7 20.8
028 3.0 WSA 67.0 64.0 32.2 26.8 67.0 64.0 32.2 25.0
OPD 80 70 35 30 70 70 35 25
FLA 65.3 62.1 30.6 26.1 59.1 56.5 28.0 21.3
035 3.0 WSA 71.2 68.2 33.8 28.0 71.2 68.2 33.8 25.7
OPD 90 80 40 35 80 80 40 30
FLA 71.4 67.7 33.4 28.3 65.2 62.1 30.8 23.5
035 5.0 WSA 77.3 73.8 36.6 30.2 77.3 73.8 36.6 27.9
OPD 90 90 45 35 90 80 40 30
FLA 86.4 82.7 41.6 36.1 73.1 71.6 35.8 28.7
042 5.0 WSA 93.5 89.8 45.1 38.9 86.7 83.2 41.7 32.7
OPD 110 110 50 50 100 100 50 40
FLA 93.9 89.5 45.0 39.0 80.6 78.4 39.2 31.6
042 7.5 WSA 101.0 96.6 48.5 41.8 94.2 90.0 45.1 35.6
OPD 125 110 60 50 110 110 50 45
FLA 101.4 96.0 49.2 39.5 84.3 80.8 40.9 31
053 3.0 WSA 109.4 104.0 53.3 42.5 102.7 98.6 49.9 37.8
OPD 125 125 60 50 110 110 60 45
FLA 107.5 101.6 52.0 41.7 90.4 86.4 43.7 33.2
053 5.0 WSA 115.5 109.6 56.1 44.7 108.8 104.2 52.7 40.0
OPD 125 125 70 50 125 125 60 45
FLA 126.1 120.2 57.6 46.1 99.7 98 46.5 35.4
070 5.0 WSA 136.5 130.6 62.4 49.7 120.5 115.8 56.2 42.7
OPD 175 150 80 60 150 125 70 50
FLA 133.6 127.0 61.0 49.0 107.2 104.8 49.9 38.3
070 7.5 WSA 144.0 137.4 65.8 52.6 128.0 122.6 59.6 45.6
OPD 175 175 80 60 150 150 70 50
FLA 145 138.4 64.0 52.6 118.4 116.2 52.4 41.0
077 7.5 WSA 156.8 150.2 69.2 56.6 135.1 129.8 61.5 47.9
OPD 200 175 80 70 175 175 70 60
FLA 151.6 144.4 67.0 54.6 125.0 122.2 55.4 43.0
077 10.0 WSA 163.4 156.2 72.2 58.6 141.7 135.8 64.5 49.9
OPD 200 200 90 70 175 175 80 60
FLA 177.4 170.2 88.4 72.6 150.8 148 76.8 61.0
105 10.0 WSA 192.4 185.2 96.3 78.9 175.2 168.6 86.0 67.4
OPD 250 225 125 100 225 200 110 90
FLA 192.8 184.2 95.4 78.6 166.2 162.0 83.8 67.0
105 15.0 WSA 207.8 199.2 103.3 84.9 190.6 182.6 93.0 73.4
OPD 250 250 125 100 225 225 110 90
1. Reduced reheat for 028, 035, and 042 models is 10kW.
2. Reduced reheat for 053, 070, and 077 models is 15kW.
3. Consult local representative for SCR reheat values.
4. Reduced reheat for 105 kW models is 20kW.
5. SCCR - Short Circuit Current Rating 65,000 amps rms symmetrical maximum.

Liebert® DS™ 22
Electrical Data

6.2 Water/Glycol-Cooled Electrical Data


Table 15 Electrical data—Water/glycol-cooled systems with EC fans
Reheat Electric Electric Electric, Electric,
Options Standard, kW None Standard kW None Downsized kW Downsized kW

Humidifier
Options Infrared Infrared None None Humidifier None

Model# Volts 208 230 460 575 208 230 460 575 208 230 460 575 208 230 460 575 208 230 460 575 208 230 460 575

FLA 67.3 64.8 32.1 25.5 56.3 54.1 26.9 24.2 67.3 64.8 32.1 25 43 43 21.1 16.8 56.3 54.1 26.9 24.2 53.5 51.9 25.6 19.9
028 WSA 82 78.9 39.2 31.9 60.6 58.4 29.1 25.9 82 78.9 39.2 30.5 47.3 47.3 23.3 18.5 64.8 62.8 31.1 25.9 64.8 62.8 31.1 24.1
OPD 80 80 40 30 70 70 35 30 80 80 40 30 60 60 30 25 70 70 35 30 70 70 35 25
FLA 70.7 68.2 33.4 25.5 63.1 60.9 29.5 25.2 70.7 68.2 33.4 25.5 49.8 49.8 23.7 17.8 63.1 60.9 29.5 25.2 56.9 55.3 26.9 20.4
035 WSA 86.3 83.2 40.8 31.9 68.3 66.1 32 27.1 86.3 83.2 40.8 31.1 55 55 26.2 19.7 69 67 32.7 27.1 69 67 32.7 24.8
OPD 90 90 45 30 80 80 40 30 90 90 45 30 70 70 35 25 80 80 40 30 80 80 35 25
FLA 78.2 75.9 37.7 33 78.1 75.9 37.7 33 78.2 75.7 37.5 29.4 64.8 64.8 31.9 25.6 78.1 75.9 37.7 33 64.8 64.8 31.9 25.6
042 WSA 95.7 92.5 46 36 85.2 83 41.2 35.8 95.7 92.5 46 36 71.9 71.9 35.4 28.4 85.2 83 41.2 35.8 78.4 76.4 37.8 29.6
OPD 110 110 50 45 110 110 50 45 110 110 50 40 100 100 45 35 110 110 50 45 100 100 45 35
FLA 119.9 116 57.1 43.5 109.2 104.8 52.4 42 119.9 116 57.1 43.5 82.6 82.6 40.8 30.4 109.2 104.8 52.4 42 92.1 89.6 44.1 33.5
053 WSA 145.3 140.4 69.4 53.9 117.2 112.8 56.5 45 145.3 140.4 69.4 52.8 90.6 90.62 44.9 33.4 117.2 112.8 56.5 45 110.5 107.4 53.1 40.3
OPD 150 150 70 50 125 125 70 50 150 150 70 50 110 110 60 45 125 125 70 50 125 125 60 45
FLA 129.2 125.3 59.9 46.4 127.8 123.4 58 46.4 129.2 125.3 59.9 45.7 101.2 101.2 46.4 34.8 127.8 123.4 58 46.4 101.4 101.2 46.9 35.7
070 WSA 156.9 152 72.9 55.5 138.2 133.8 62.8 50 156.9 152.0 72.9 55.5 111.6 111.6 51.2 38.4 138.2 133.8 62.8 50 122.2 119.02 56.6 43
OPD 175 175 80 60 175 175 80 60 175 175 80 60 150 150 70 50 175 175 80 60 150 150 70 50
FLA 139.2 134.8 61.4 50 139.2 134.8 61 50 134.9 131 61.4 47.5 112.6 112.6 49.4 38.4 139.2 134.8 61 50 112.6 112.6 49.4 38.4
077 WSA 164 159.2 74.8 57.8 151. 146.6 66.2 54 164.0 159.2 74.8 57.8 124.4 124.4 54.6 42.4 151 146.6 66.2 54 129.3 126.15 58.5 45.3
OPD 175 175 80 70 175 175 80 70 175 175 80 60 150 150 70 50 175 175 80 70 150 150 70 50
FLA 171.5 167.1 83.7 69.1 171.5 167.1 83.7 69.1 164 163.5 79.8 62.6 144.9 144.9 72.1 57.5 171.5 167.1 83.7 69.1 144.9 144.9 72.1 57.5
105U WSA 198.8 198.2 97.4 76.4 186.5 182.1 91.6 75.4 198.8 198.2 97.4 76.4 159.9 159.9 80 63.8 186.5 182.1 91.6 75.4 169.3 165.5 81.3 63.9
OPD 225 225 110 100 225 225 110 100 225 225 110 90 200 200 110 80 225 225 110 100 200 200 110 80
FLA 164 163.5 82.5 64.7 158.6 154.2 75.7 62.2 164 163.5 82.5 64.7 132 132 64.1 50.6 158.6 154.2 75.7 62.2 140.4 137.4 69.6 54.7
105V WSA 198.8 198.2 100.1 78.5 173.6 169.2 83.6 68.5 198.8 198.2 100.1 78.5 147 147 72 56.9 173.6 169.2 84 68.5 169.3 165.5 84 66
OPD 225 225 110 90 225 225 110 90 225 225 110 90 200 200 100 80 225 225 110 90 200 200 100 80
1. Reduced reheat for 028, 035, and 042 models is 10kW.
2. Reduced reheat for 053, 070, and 077 models is 15kW.
3. Consult local representative for SCR reheat values.
4. Reduced reheat for 105 kW models is 20kW.
5. SCCR - Short Circuit Current Rating 65,000 amps rms symmetrical maximum.
6. Steam canister humidifiers not available on models with EC fans.

23 Liebert® DS™
Electrical Data

Table 16 Electrical data—Water/glycol-cooled systems with forward-curved blowers


Reheat Options Electric, Std. kW None Electric, Std. kW None
Humidifier Infrared or Steam Infrared or Steam
Options Generating Canister Generating Canister None None
Model Motor hp Volts 208 230 460 575 208 230 460 575 208 230 460 575 208 230 460 575
FLA 66.4 63.2 31.8 25.2 55.4 52.5 26.6 23.9 66.4 63.2 31.8 24.7 42.1 41.4 20.8 16.5
028 2.0 WSA 81.1 77.3 38.9 31.5 59.7 56.8 28.8 25.6 81.1 77.3 38.9 30.2 46.4 45.7 23 18.2
OPD 80 80 40 30 70 70 35 30 80 80 40 30 60 60 30 25
FLA 69.5 66.0 33.2 26.4 58.5 55.3 28.0 25.1 69.5 66.0 33.2 25.9 45.2 44.2 22.2 17.7
028 3.0 WSA 84.2 80.1 40.3 33 62.8 59.6 30.2 26.8 84.2 80.1 40.3 31.4 49.5 48.5 24.4 19.4
OPD 90 80 40 30 80 70 35 30 90 80 40 30 60 60 30 25
FLA 72.9 69.4 34.5 26.4 65.3 62.1 30.6 26.1 72.9 69.4 34.5 26.4 52.0 51.0 24.8 18.7
035 3.0 WSA 88.5 84.4 41.9 33.0 70.5 67.3 33.1 28.0 88.5 84.4 41.9 32.0 57.2 56.2 27.3 20.6
OPD 90 90 45 35 90 80 40 35 90 90 45 35 70 70 35 25
FLA 79.0 75.0 37.3 28.6 71.4 67.7 33.4 28.3 79.0 75.0 37.3 28.6 58.1 56.6 27.6 20.9
035 5.0 WSA 94.6 90.0 44.7 35.8 76.6 72.9 35.9 30.2 94.6 90.0 44.7 34.2 63.3 61.8 30.1 22.8
OPD 100 100 45 35 90 90 45 35 100 100 45 35 80 80 40 30
FLA 86.5 82.7 41.6 36.1 86.4 82.7 41.6 36.1 86.5 82.5 41.4 32.5 73.1 71.6 35.8 28.7
042 5.0 WSA 104 99.3 49.9 39.1 93.5 89.8 45.1 38.9 104.0 99.3 49.9 39.1 80.2 78.7 39.3 31.5
OPD 110 110 50 50 110 110 50 50 110 110 50 45 100 100 50 40
FLA 94.0 89.5 45.0 39.0 93.9 89.5 45.0 39.0 94.0 89.3 44.8 35.4 80.6 78.4 39.2 31.6
042 7.5 WSA 111.5 106.1 53.3 42.0 101.0 96.6 48.5 41.8 111.5 106.1 53.3 42.0 87.7 85.5 42.7 34.4
OPD 125 110 60 50 125 110 60 50 125 110 60 45 110 110 50 45
FLA 112.1 107.2 53.9 41 101.4 96 49.2 39.5 112.1 107.2 53.9 41 74.8 73.8 37.6 27.9
053 3.0 WSA 137.5 131.6 66.2 50.8 109.4 104.0 53.3 42.5 137.5 131.6 66.2 50.3 82.8 81.8 41.7 30.9
OPD 150 125 70 50 125 125 60 50 150 125 70 50 110 110 50 40
FLA 118.2 112.8 56.7 43.2 107.5 101.6 52.0 41.7 118.2 112.8 56.7 43.2 80.9 79.4 40.4 30.1
053 5.0 WSA 143.6 137.2 69.0 53.5 115.5 109.6 56.1 44.7 143.6 137.2 69.0 52.5 88.9 87.4 44.5 33.1
OPD 150 150 70 50 125 125 70 50 150 150 70 50 110 110 60 45
FLA 127.5 122.1 59.5 46.1 126.1 120.2 57.6 46.1 127.5 122.1 59.5 45.4 99.5 98 46 34.5
070 5.0 WSA 155.2 148.8 72.5 55.2 136.5 130.6 62.4 49.7 155.2 148.8 72.5 55.2 109.9 108.4 50.8 38.1
OPD 175 150 80 60 175 150 80 60 175 150 80 60 150 125 70 50
FLA 135.0 128.9 62.9 49.0 133.6 127.0 61.0 49.0 135.0 128.9 62.9 48.3 107.0 104.8 49.4 37.4
070 7.5 WSA 162.7 155.6 75.9 58.1 144.0 137.4 65.8 52.6 162.7 155.6 75.9 58.1 117.4 115.2 54.2 41.0
OPD 175 175 80 60 175 175 80 60 175 175 80 60 150 150 70 50
FLA 145 138.4 64.4 52.6 145.0 138.4 64.0 52.6 140.7 134.6 64.4 50.1 118.4 116.2 52.4 41.0
077 7.5 WSA 169.8 162.8 77.8 60.4 156.8 150.2 69.2 56.6 169.8 162.8 77.8 60.4 130.2 128.0 57.6 45.0
OPD 200 175 90 70 200 175 80 70 175 175 90 70 175 175 70 60
FLA 151.6 144.4 67.4 54.6 151.6 144.4 67.0 54.6 147.3 140.6 67.4 52.1 125.0 122.2 55.4 43.0
077 10.0 WSA 176.4 168.8 80.8 62.4 163.4 156.2 72.2 58.6 176.4 168.8 80.8 62.4 136.8 134.0 60.6 47.0
OPD 200 200 90 70 200 200 90 70 200 175 90 70 175 175 80 60
FLA 177.4 170.2 88.4 72.6 177.4 170.2 88.4 72.6 169.9 166.6 84.5 66.1 150.8 148 76.8 61.0
105U 10.0 WSA 204.7 201.3 102.1 79.9 204.7 201.3 102.1 79.9 204.7 201.3 102.1 79.9 165.8 163.0 84.7 67.3
OPD 250 225 125 100 250 225 125 100 225 225 110 90 225 200 110 90
FLA 192.3 184.2 95.4 78.6 192.3 184.2 95.4 78.6 185.3 180.6 91.5 72.1 166.2 162.0 83.8 67.0
105U 15.0 WSA 220.1 215.3 109.1 85.9 220.1 215.3 109.1 85.9 220.1 215.3 109.1 85.9 181.2 177.0 91.7 73.3
OPD 250 250 125 100 250 250 125 100 250 250 125 100 225 225 110 90
FLA 169.9 166.6 84.5 66.1 164.5 157.3 77.7 63.6 169.9 166.6 84.5
66.1 137.9 135.1 66.1 52
105V 10.0 WSA 204.7 201.3 102.1 79.9 179.9 172.3 85.6 69.9 204.7 201.3 102.1 79.9 152.9 150.1 74 58.3
OPD 225 225 110 90 225 225 110 90 225 225 110
90 200 200 100 80
FLA 185.3 180.6 91.5 72.1 179.9 171.3 84.7 69.6 185.3 180.6 91.5
72.1 153.3 149.1 73.1 58
105V 15.0 WSA 220.1 215.3 109.1 85.9 194.9 186.3 92.6 79.5 220.1 215.3 109.1 85.9 168.3 164.1 81 64.3
OPD 250 250 125 100 250 225 110 100 250 250 125 100 225 200 110 80
1. Reduced reheat for 028, 035, and 042 models is 10kW.
2. Reduced reheat for 053, 070, and 077 models is 15kW.
3. Consult local representative for SCR reheat values.
4. Reduced reheat for 105 kW models is 20kW.
5. SCCR - Short Circuit Current Rating 65,000 amps rms symmetrical maximum.

Liebert® DS™ 24
Electrical Data

Table 16 Electrical data—Water/glycol-cooled systems with forward-curved blowers (continued)


Reheat Options Electric, Downsized kW
Humidifier Options Infrared or Steam Generating Canister None
Model Motor, hp Volts 208 230 460 575 208 230 460 575
FLA 55.4 52.5 26.6 23.9 52.6 50.3 25.3 19.6
028 2.0 WSA 63.9 61.2 30.8 25.6 63.9 61.2 30.8 23.8
OPD 70 70 35 30 70 70 35 25
FLA 58.5 55.3 28 25.1 55.7 53.1 26.7 20.8
028 3.0 WSA 67.0 64.0 32.2 26.8 67.0 64.0 32.2 25.0
OPD 80 70 35 30 70 70 35 25
FLA 65.3 62.1 30.6 26.1 59.1 56.5 28.0 21.3
035 3.0 WSA 71.2 68.2 33.8 28.0 71.2 68.2 33.8 25.7
OPD 90 80 40 35 80 80 40 30
FLA 71.4 67.7 33.4 28.3 65.2 62.1 30.8 23.5
035 5.0 WSA 77.3 73.8 36.6 30.2 77.3 73.8 36.6 27.9
OPD 90 90 45 35 90 80 40 30
FLA 86.4 82.7 41.6 36.1 73.1 71.6 35.8 28.7
042 5.0 WSA 93.5 89.8 45.1 38.9 86.7 83.2 41.7 32.7
OPD 110 110 50 50 100 100 50 40
FLA 93.9 89.5 45.0 39.0 80.6 78.4 39.2 31.6
042 7.5 WSA 101.0 96.6 48.5 41.8 94.2 90.0 45.1 35.6
OPD 125 110 60 50 110 110 50 45
FLA 101.4 96.0 49.2 39.5 84.3 80.8 40.9 31
053 3.0 WSA 109.4 104.0 53.3 42.5 102.7 98.6 49.9 37.8
OPD 125 125 60 50 110 110 60 45
FLA 107.5 101.6 52.0 41.7 90.4 86.4 43.7 33.2
053 5.0 WSA 115.5 109.6 56.1 44.7 108.8 104.2 52.7 40.0
OPD 125 125 70 50 125 125 60 45
FLA 126.1 120.2 57.6 46.1 99.7 98 46.5 35.4
070 5.0 WSA 136.5 130.6 62.4 49.7 120.5 115.8 56.2 42.7
OPD 175 150 80 60 150 125 70 50
FLA 133.6 127.0 61.0 49.0 107.2 104.8 49.9 38.3
070 7.5 WSA 144.0 137.4 65.8 52.6 128.0 122.6 59.6 45.6
OPD 175 175 80 60 150 150 70 50
FLA 145 138.4 64.0 52.6 118.4 116.2 52.4 41.0
077 7.5 WSA 156.8 150.2 69.2 56.6 135.1 129.8 61.5 47.9
OPD 200 175 80 70 175 175 70 60
FLA 151.6 144.4 67.0 54.6 125.0 122.2 55.4 43.0
077 10.0 WSA 163.4 156.2 72.2 58.6 141.7 135.8 64.5 49.9
OPD 200 200 90 70 175 175 80 60
FLA 177.4 170.2 88.4 72.6 150.8 148 76.8 61.0
105U 10.0 WSA 192.4 185.2 96.3 78.9 175.2 168.6 86.0 67.4
OPD 250 225 125 100 225 200 110 90
FLA 192.8 184.2 95.4 78.6 166.2 162.0 83.8 67.0
105U 15.0 WSA 207.8 199.2 103.3 84.9 190.6 182.6 93.0 73.4
OPD 250 250 125 100 225 225 110 90
FLA 164.5 157.3 77.7 63.6 146.3 140.5 71.6 56.1
105V 10.0 WSA 179.5 172.3 86 69.9 175.2 168.6 86 67.4
OPD 225 225 110 90 200 200 110 80
FLA 179.9 171.3 84.7 69.6 161.7 154.5 78.6 62.1
105V 15.0 WSA 194.9 186.3 93 75.9 190.6 182.6 93 73.4
OPD 250 225 110 100 225 225 110 90
1. Reduced reheat for 028, 035, and 042 models is 10kW.
2. Reduced reheat for 053, 070, and 077 models is 15kW.
3. Consult local representative for SCR reheat values.
4. Reduced reheat for 105 kW models is 20kW.
5. SCCR - Short Circuit Current Rating 65,000 amps rms symmetrical maximum.

25 Liebert® DS™
Weights and Dimensions

7.0 WEIGHTS AND DIMENSIONS


Table 17 Liebert DS shipping and unit weights—approximate
Downflow Upflow Upflow Shipping
Downflow Weights, lb (kg)
Shipping
EC Fan EC Fan Forward- w/Forward-Curved
Weights, lb (kg) Blowers
Unit Unit Curved Unit
Compressor Cooling Weight Domestic Export Weight Weight Domestic Export
Model # Type Type lb (kg) lb (kg) lb (kg) lb (kg) lb (kg) lb (kg) lb (kg)
1470 1608 1778 1370 1520 1658 1828
Air Cooled
(668) (730) (807) (621) (689) (753) (830)
1620 1758 1928 1520 1670 1808 1978
Dual Cool
Scroll or (736) (798) (875) (689) (758) (821) (898)
Digital Scroll 1780 1918 2088 1680 1830 1968 2138
Water/Glycol
(809) (870) (948) (762) (830) (893) (970)
GLYCOOL/ 1930 2068 2238 1830 1980 2118 2288
Dual Cool (877) (939) (1016) (830) (898) (961) (1038)
DS028-042
1780 1918 2088 1680 1830 1968 2138
Air Cooled
(809) (870) (948) (762) (830) (893) (970)
1930 2068 2238 1830 1980 2118 2288
Dual Cool
(877) (939) (1016) (830) (898) (961) (1038)
Semi-Hermetic
1930 2068 2238 1830 1980 2118 2288
Water/Glycol
(877) (939) (1016) (830) (898) (961) (1038)
GLYCOOL/ 2080 2218 2388 1980 2130 2268 2438
Dual Cool (945) (1007) (1084) (898) (966) (1029) (1106)
1920 2070 2260 1900 2070 2220 2410
Air Cooled
(871) (939) (1026) (862) (939) (1007) (1094)
2100 2250 2440 2080 2250 2400 2590
Dual Cool
Scroll or (953) (1021) (1107) (943) (1021) (1089) (1175)
Digital Scroll 2220 2382 2582 2200 2370 2532 2732
Water/Glycol
(1010) (1081) (1172) (998) (1075) (1149) (1240)
GLYCOOL/ 2400 2562 2762 2380 2550 2712 2912
Dual Cool (1091) (1163) (1253) (1080) (1157) (1231) (1321)
DS053
2350 2512 2712 2180 2350 2512 2712
Air Cooled
(1069) (1140) (1231) (989) (1069) (1140) (1231)
2530 2692 2892 2360 2530 2692 2892
Dual Cool
(1150) (1222) (1312) (1070) (1150) (1222) (1312)
Semi-Hermetic
2650 2812 3012 2480 2650 2812 3012
Water/Glycol
(1205) (1276) (1367) (1125) (1205) (1276) (1367)
GLYCOOL/ 2830 2992 3192 2660 2830 2992 3192
Dual Cool (1287) (1358) (1448) (1207) (1287) (1358) (1448)
1970 2120 2310 1900 2070 2220 2410
Air Cooled
(894) (962) (1048) (862) (939) (1007) (1094)
2150 2300 2490 2080 2250 2400 2590
Dual Cool
Scroll or (975) (1044) (1130) (943) (1021) (1089) (1175)
Digital Scroll 2270 2432 2632 2200 2370 2532 2732
Water/Glycol
(1032) (1104) (1194) (998) (1075) (1149) (1240)
GLYCOOL/ 2450 2612 2812 2380 2550 2712 2912
Dual Cool (1114) (1185) (1276) (1080) (1157) (1231) (1321)
DS070
2400 2562 2762 2330 2500 2662 2862
Air Cooled
(1091) (1163) (1253) (1057) (1134) (1208) (1299)
2580 2742 2942 2510 2680 2842 3042
Dual Cool
(1173) (1244) (1335) (1139) (1216) (1290) (1380)
Semi-Hermetic
2700 2862 3062 2630 2800 2962 3162
Water/Glycol
(1228) (1299) (1389) (1193) (1270) (1344) (1435)
GLYCOOL/ 2880 3042 3242 2810 2980 3142 3342
Dual Cool (1310) (1380) (1471) (1275) (1352) (1426) (1516)

Liebert® DS™ 26
Weights and Dimensions

Table 17 Liebert DS shipping and unit weights—approximate (continued)


Downflow Upflow Upflow Shipping
Downflow Weights, lb (kg)
Shipping w/Forward-Curved
EC Fan EC Fan Forward-
Weights, lb (kg) Blowers
Unit Unit Curved Unit
Compressor Cooling Weight Domestic Export Weight Weight Domestic Export
Model # Type Type lb (kg) lb (kg) lb (kg) lb (kg) lb (kg) lb (kg) lb (kg)
2020 2170 2360 1900 2070 2220 2410
Air Cooled
(916) (985) (1071) (862) (939) (1007) (1094)
2200 2350 2540 2080 2250 2400 2590
Dual Cool
Scroll or (998) (1066) (1153) (943) (1021) (1089) (1175)
Digital Scroll 2320 2470 2660 2200 2370 2532 2732
Water/Glycol
(1055) (1121) (1207) (998) (1075) (1149) (1240)
GLYCOOL/ 2500 2650 2840 2380 2550 2712 2912
Dual Cool (1137) (1203) (1289) (1080) (1157) (1231) (1321)
DS077
2450 2612 2812 2330 2500 2662 2862
Air Cooled
(1114) (1185) (1276) (1057) (1134) (1208) (1299)
2630 2792 2992 2510 2680 2842 3042
Dual Cool
(1196) (1267) (1358) (1139) (1216) (1290) (1380)
Semi-Hermetic
2750 2912 3112 2630 2800 2962 3162
Water/Glycol
(1250) (1321) (1412) (1193) (1270) (1344) (1435)
GLYCOOL/ 2930 3092 3292 2810 2980 3142 3342
Dual Cool (1332) (1403) (1494) (1275) (1352) (1426) (1516)
2660 3103 3323 2640 2880 3063 3283
Air Cooled
(1207) (1408) (1508) (1197) (1306) (1390) (1490)
3015 3463 3683 2970 3210 3393 3613
Dual Cool
Scroll or (1368) (1571) (1671) (1347) (1456) (1540) (1639)
Digital Scroll 3030 3473 3693 3010 3250 3433 3653
Water/Glycol
(1374) (1576) (1676) (1365) (1474) (1558) (1657)
GLYCOOL/ 3385 3833 4053 3340 3580 3763 3983
Dual Cool (1535) (1739) (1839) (1515) (1624) (1707) (1807)
DS105
2780 3223 3443 2760 3000 3183 3403
Air Cooled
(1261) (1462) (1562) (1252) (1361) (1444) (1544)
3135 3583 3803 3090 3330 3513 3733
Dual Cool
(1422) (1626) (1726) (1402) (1510) (1594) (1694)
Semi-Hermetic
3150 3593 3813 3130 3370 3553 3773
Water/Glycol
(1429) (1630) (1730) (1420) (1529) (1612) (1712)
GLYCOOL/ 3505 3953 4173 3460 3700 3883 4103
Dual Cool (1590) (1794) (1893) (1569) (1678) (1762) (1862)

27 Liebert® DS™
Weights and Dimensions

Figure 8 Cabinet and floor planning dimensions—Downflow, air-cooled, 28-42kW (8-12 tons), scroll or
digital scroll compressors with EC fans

Secondary Refrigerant
Piping Entrance
56-7/8" (1445mm) Filters are accessible
Opening through top of unit only.
Downflow electrical
connections can be made
from top or bottom of unit.
33"
(838mm) 24-3/8"
AIR INLET OPENING (619mm)
35"
(889mm) Opening
1-3/4" (44mm)
Handle
5/16"
Bezel
(8mm)

Secondary Entrance TOP VIEW Secondary Entrance


High-Voltage Connection(s) Low-Voltage Connection(s)

73" (1854mm) Minimum required


for filter replacement

5"
(127mm)

76"
(1930mm)

34" (864mm)
Shaded area indicates a
recommended minimum
clearance from floor to top
of unit and plenum for
component access.
2" 72" (1829mm) DPN003131
(51mm)
FRONT VIEW Rev. 1

Liebert® DS™ 28
Weights and Dimensions

Figure 9 Primary connection locations—Downflow, air-cooled, 28-42kW (8-12 tons), EC fans, scroll or
digital scroll compressor models

All dimensions from


A rear corner of unit
NOTES: A
1. Drawing not to scale. including panels
FRONT VIEW
2. Tolerance on all piping dimensions
is ±1/2" (13mm). SECTION A-A X O

Y
R
L1 L2 G1 G2
4" (102mm) 35"
(889mm)
11.19" BLOWER
(284mm) ECS OUTLET

LV1
HUM LV2
CD LV3
E1 E2 ECR B

4.5"
73" (1854mm)
(114mm)
FRONT OF UNIT DPN003239
Rev. 0

Table 18 Piping data—Downflow, air-cooled, 28-42kW (8-12 tons), with EC fans, scroll or digital scroll
compressor models
Point Description X Y Connection Size / Opening
R Refrigerant Access 59-5/16 (1507) 14-3/4 (375) 11-3/16 x 4 (284 x 102)
L1 Liquid Line System 1 69-15/16 (1776) 16-13/16 (411) 1/2" Cu Sweat
L2 Liquid Line System 2 67-5/8 (1718) 16-13/16 (411) 1/2" Cu Sweat
G1 Hot Gas Discharge 1 65-1/2 (1664) 16-13/16 (411) 5/8" Cu Sweat
G2 Hot Gas Discharge 2 62-7/16 (1586) 16-13/16 (411) 5/8" Cu Sweat
Condensate Drain 1
46 (1168) 29-1/2 (749) 3/4" FPT
(Infrared Humidifier or No Humidifier)
CD Condensate Drain 1
46 (1168) 29-1/2 (749) 1-1/4" FPT
(Steam Generating Humidifier)
w/Optional Pump 46 (1168) 29-1/2 (749) 1/2" Cu Sweat
HUM Humidifier Supply Line 53-1/2 (1359) 29 (737) 1/4" Cu Sweat
ECS Econ-O-Coil Supply 54-7/8 (1394) 22-9/16 (573) 1-5/8" Cu Sweat
ECR Econ-O-Coil Return 49-3/8 (1254) 30-3/4 (781) 1-5/8" Cu Sweat
HS Hot Water Reheat Supply Consult Factory
HR Hot Water Reheat Return Consult Factory
E1 Electrical Connection (High-Voltage) 55-1/2 (1410) 31-1/4 (794) 2-1/2"
E2 Electrical Connection (High-Voltage) 52-7/16 (1332) 31-1/4 (794) 2-1/2"
LV1 Electrical Connection (Low-Voltage) 2-1/4 (57) 27 (686) 7/8"
LV2 Electrical Connection (Low-Voltage) 2-1/4 (57) 29 (737) 7/8"
LV3 Electrical Connection (Low-Voltage) 2-1/4 (57) 31 (787) 7/8"
B Blower Outlet 4-1/2 (114) 33 (838) 31 x 31 (787 x 787)
1. Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Source: DPN003239, Rev. 0

29 Liebert® DS™
Weights and Dimensions

Figure 10 Cabinet and floor planning dimensions—Downflow, air-cooled, 28-42kW (8-12 tons),
semi-hermetic compressors with EC fans

Secondary Refrigerant
Piping Entrance
56-7/8"
Opening
(1445mm)

Filters are accessible


through top of unit only.
33" 24-3/8" Downflow electrical
(838mm) AIR INLET OPENING
(619mm) connections can be made
35" Opening
1-3/4" from top or bottom of unit.
(889mm)
(44mm) Handle
5/16"
(8mm) Bezel
Secondary Entrance TOP VIEW
High-Voltage Connection(s) Secondary Entrance
Minimum required
Low-Voltage Connections
for filter replacement
86" (2184mm)

5"
(127mm)

76"
(1930mm)

34"
(864mm)
Shaded area indicates a
recommended minimum
clearance from floor
to top of unit and plenum DPN003130
2" 85" (2159mm) for component access. Rev. 1
(51mm)
FRONT VIEW

Liebert® DS™ 30
Weights and Dimensions

Figure 11 Primary connection locations—Downflow, air-cooled, 28-42kW (8-12 tons), EC fans,


semi-hermetic compressor models

All dimensions from


NOTES: rear corner of unit
A A including panels
1. Drawing not to scale.
2. Tolerance on all piping dimensions FRONT VIEW
is ±1/2" (13mm). X O

Y
R
L1 L2 G1 G2
4" (102mm) BLOWER 35"
OUTLET (889mm)
16-7/16"
ECS
(418mm) LV1
HUM
LV2
CD
E1 E2 ECR B LV3
SECTION A-A
4.5"
FRONT OF UNIT 86" (114mm)
(2184mm)
DPN003598
Rev. 0

X Y Connection Size / Opening


Point Description in. (mm) in. (mm) in. (mm)
R Refrigerant Access 63 (1600) 13-13/16 (351) 16-7/16 x 4 (418 x 102)
L1 Liquid Line System 1 79-3/16 (2011) 16-3/4 (425) 1/2 Cu Sweat
L2 Liquid Line System 2 76-1/2 (1943) 16-3/4 (425) 1/2 Cu Sweat
G1 Hot Gas Discharge 1 73-7/8 (1876) 16-3/4 (425) 5/8 Cu Sweat
G2 Hot Gas Discharge 2 70-1/8 (1780) 16-3/4 (425) 5/8 Cu Sweat
Condensate Drain 1
46 (1168) 29-1/2 (749) 3/4 FPT
(Infrared Humidifier or No Humidifier)
CD Condensate Drain 1
46 (1168) 29-1/2 (749) 1-1/4 FPT
(Steam Generating Humidifier)
w/Optional Pump 46 (1168) 29-1/2 (749) 1/2 Cu Sweat
HUM Humidifier Supply Line 53-1/2 (1359) 29 (737) 1/4 Cu Sweat
ECS 2 Econ-O-Coil Supply 54-7/8 (1394) 22-9/16 (573) 1-5/8 Cu Sweat
ECR 2 Econ-O-Coil Return 49-3/8 (1254) 30-3/4 (781) 1-5/8 Cu Sweat
E1 Electrical Connection (High-Voltage) 55-1/2 (1410) 31-1/4 (794) 2-1/2
E2 Electrical Connection (High-Voltage) 52-7/16 (1332) 31-1/4 (794) 2-1/2
LV1 Electrical Connection (Low-Voltage) 2-1/4 (57) 27 (686) 7/8
LV2 Electrical Connection (Low-Voltage) 2-1/4 (57) 29 (737) 7/8
LV3 Electrical Connection (Low-Voltage) 2-1/4 (57) 31 (787) 7/8
B Blower Outlet 4-1/2 (114) 33 (838) 31 x 31 (787 x 787)
1. Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on dual cooling systems only (4 pipe system).
3. Source: DPN003598, Rev. 0

31 Liebert® DS™
Weights and Dimensions

Figure 12 Cabinet and floor planning dimensions—Downflow, air-cooled, 53-77kW (15-22 tons), scroll or
digital scroll compressors with EC fans

Second Refrigerant Digital scroll compressors


Piping Entrance not available on DS 077.
80" (2032mm)
Opening Filters are accessible
through top of unit only.
33" 24-5/8"
(838mm) AIR INLET OPENING (625mm) Downflow electrical
35" Opening connections can be made
(889mm) from top or bottom of unit.
5/16"
(8mm) Minimum required
1-3/4" Bezel for filter replacement
Secondary Entrance (44mm) Handle
Secondary Entrance
High-Voltage Connection(s) TOP VIEW Low-Voltage Connections
5"
98" (2489mm) (127mm)

76"
(1930mm)

34"
(864mm)
Shaded area indicates a
recommended minimum
clearance from floor to top
2" 97" (2464mm) DPN003138
of unit and plenum
(51mm)
FRONT VIEW for component access. Rev. 2

Liebert® DS™ 32
Weights and Dimensions

Figure 13 Primary connection locations—Downflow, air-cooled, 53-77kW (15-22 tons), scroll or digital
scroll compressors, EC fans
Digital scroll compressors not
available on 077 models.

NOTE: Drawing not to scale. All dimensions from


Tolerance on rear corner of unit
A A including panels
all piping dimensions
FRONT VIEW X
is ± 1/2" (13mm).
SECTION A-A O

R Y
4" (102mm)
L1 L2 G1 G2 BLOWER
OUTLET 35"
12-3/16" (889mm)
(310mm)
ECS ECR LV1
CD B1 LV2
LV3
E1 E2 HUM
98" (2489mm)
DPN002182
FRONT OF UNIT Rev. 3
Table 19 Piping details—Downflow, air-cooled, 53-77kW (15-22 tons), EC fans, scroll or digital scroll
compressors 3
X Y Connection Size / Opening
Point Description in. (mm) in. (mm) in. (mm)
R Refrigerant Access 81-3/4 (2076) 14-3/4 (374) 12-3/16x4 (310x102)
53kW (15 tons)/ 70 & 77kW (20 & 22 tons)
L1 Liquid Line System 1 94-11/16 (2405) 16-3/4 (425) 1/2 / 5/8 Cu Sweat
L2 Liquid Line System 2 91-7/8 (2334) 16-3/4 (425) 1/2 / 5/8 Cu Sweat
G1 Hot Gas Discharge 1 88-3/4 (2254) 16-3/8 (416) 7/8 / 1-1/8 Cu Sweat
G2 Hot Gas Discharge 2 85-9/16 (2173) 16-3/8 (416) 7/8 / 1-1/8 Cu Sweat
Condensate Drain
68-3/8 (1737) 31-3/8 (797) 3/4 FPT
CD 1 (Infrared Humidifier or No Humidifier)
W/ Optional Pump 68-3/8 (1737) 31-3/8 (797) 1/2 Cu Sweat
HUM Humidifier Supply Line 76-1/2 (1943) 29 (736) 1/4 Cu Sweat
ECS 2 Econ-O-Coil Supply 78-5/8 (1997) 22-1/4 (565) 2-1/8 Cu Sweat
2
ECR Econ-O-Coil Return 73-15/16 (1862) 26-9/16 (675) 2-1/8 Cu Sweat
E1 Electrical Conn. (High-Voltage) 78-1/2 (1994) 31-1/8 (790) 2-1/2
E2 Electrical Conn. (High-Voltage) 75-3/8 (1915) 31-1/8 (790) 2-1/2
LV1 Electrical Conn. (Low-Voltage) 2 (51) 29 (737) 7/8
LV2 Electrical Conn. (Low-Voltage) 2 (51) 30-7/8 (784) 7/8
LV3 Electrical Conn. (Low-Voltage) 2 (51) 32 (813) 7/8
B1 Blower Outlet 4-1/2 (114) 33 (838) 58-3/8x30 (1483x762)
1. Field-pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on dual-cool systems only (four-pipe system).
3. Digital scroll compressors not available on 077 models.
4. Piping dimensions shown are connection sizes; field piping sizes may be different, depending on distance. Refer to user manual,
SL-18825.
5. Source: DPN002182, Rev. 3

33 Liebert® DS™
Weights and Dimensions

Figure 14 Cabinet and floor planning dimensions—Downflow, air-cooled, 53-77kW (15-22 tons),
semi-hermetic compressors with EC fans

Second Refrigerant
Piping Entrance
80" (2032mm)
Opening
Filters are accessible
33" 24-5/8" through top of unit only.
(838mm) AIR INLET OPENING (625mm)
35" Opening Downflow electrical
(889mm) connections can be made
from top or bottom of unit.
5/16"
(8mm)
1-3/4" Bezel
Secondary Entrance (44mm) Handle Secondary Entrance
High-Voltage Connection(s) TOP VIEW Low-Voltage Connections
Minimum required
109" (2769mm) for filter replacement

5"
(125mm)

76"
(1930mm)

34"
(864mm)
108" (2743mm) Shaded area indicates a
2" recommended minimum
(51mm) FRONT VIEW clearance be provided for DPN003137
component access. Rev. 2

Liebert® DS™ 34
Weights and Dimensions

Figure 15 Primary connection locations—Downflow, air-cooled 53-77kW (15-22 tons), semi-hermetic


compressors with EC fans

All dimensions from


rear corner of unit
including panels
NOTE
Drawing not to scale. A A
Tolerance on all piping FRONT VIEW
dimensions is ± 1/2" (13mm). X
SECTION A-A O

R Y
L1 L2 G1 G2
4" (102mm) BLOWER 35"
OUTLET (889mm)
16-7/16"
(418mm)
ECS ECR LV1
CD B1 LV2
LV3
E1 HUM
109" (2769mm)
DPN002179
FRONT OF UNIT
Rev. 1

Table 20 Piping details—Downflow, air-cooled 53-77kW (15-22 tons), EC fans, semi-hermetic


compressors
X Y Connection Size / Opening
Point Description in. (mm) in. (mm) in. (mm)
R Refrigerant Access 82-3/4 (2102) 13-7/8 (352) 16-7/16 x 4 (4181x102)
53kW (15 tons) /70 & 77kw (20 & 22 tons)
L1 Liquid Line System 1 97 (2464) 16-7/8 (428) 1/2 / 5/8 Cu Sweat
L2 Liquid Line System 2 93-5/16 (2370) 16-7/8 (428) 1/2 / 5/8 Cu Sweat
G1 Hot Gas Discharge 1 90-5/8 (2302) 16-5/8 (422) 7/8 / 1-1/8 Cu Sweat
G2 Hot Gas Discharge 2 88 (2235) 16-5/8 (422) 7/8 / 1-1/8 Cu Sweat
Condensate Drain
68-3/8 (1737) 31-3/8 (797) 3/4 FPT
CD 1 (Infrared Humidifier or No Humidifier)
W/ Optional Pump 68-3/8 (1737) 31-3/8 (797) 1/2 Cu Sweat
HUM Humidifier Supply Line 76-1/2 (1943) 29 (736) 1/4 Cu Sweat
2
ECS Econ-O-Coil Supply 78-5/8 (1997) 22-1/4 (565) 2-1/8 Cu Sweat
ECR 2 Econ-O-Coil Return 73-15/16 (1862) 26-9/16 (675) 2-1/8 Cu Sweat
E1 Electrical Conn. (High-Voltage) 78-1/2 (1994) 31-1/8 (790) 2-1/2
E2 Electrical Conn. (High-Voltage) 75-3/8 (1915) 31-1/8 (790) 2-1/2
LV1 Electrical Conn. (Low-Voltage) 2 (51) 29 (737) 7/8
LV2 Electrical Conn. (Low-Voltage) 2 (51) 30-7/8 (784) 7/8
LV3 Electrical Conn. (Low-Voltage) 2 (51) 32 (813) 7/8
B1 Blower Outlet 4-1/2 (114) 33 (838) 58-3/8 x 30 (1483x762)
1. Field-pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on dual-cool systems only (four-pipe system).
3. Piping dimensions shown are connection sizes; field piping sizes may be different, depending on distance. Refer to user manual,
SL-18825.
4. Source: DPN002179, Rev. 1

35 Liebert® DS™
Weights and Dimensions

Figure 16 Cabinet and floor planning dimensions—Downflow, air-cooled, 105kW (30 tons), standard
scroll and semi-hermetic compressors with EC fans
Secondary Refrigerant Digital scroll compressors
Piping Entrance
102-13/16" not available on 105 models.
(2611mm) Opening

33"
(838mm) 24-3/8"
AIR INLET OPENING (619mm)
35"
(889mm) Opening

5/16"
(8mm)
1-3/4" TOP VIEW Bezels
Secondary Entrance (44mm) Handle Secondary Entrance
High-Voltage Connection(s) Low-Voltage Connections
Minimum required
132" (3353mm) for filter replacement

5"
(127mm)

76"
(1930mm)

34" (864mm)
Shaded area indicates the
minimum clearance
131" (3327mm) required from floor to
FRONT VIEW top of unit and plenum for DPN0003145
Filters are accessible through top of unit only. component access. Rev. 2
Downflow electrical connections can be made
from top or bottom of unit.

Liebert® DS™ 36
Weights and Dimensions

Figure 17 Primary connection locations—Downflow, air-cooled, 105kW (30 tons), standard scroll and
semi-hermetic compressors with EC fans

Digital scroll compressors not


available on 105 models.
NOTE A All dimensions from
Drawing not to scale. A
rear corner of unit
Tolerance on all piping FRONT OF UNIT including panels
dimensions is ± 1/2" (13mm).
SECTION A-A X O

Y
G1 G2 R 35"
4" (102mm) BLOWER (889mm)
L1 L2 OUTLET
16-7/16"
(418mm) ECS ECR LV1
CD LV2
B1
LV3
E1 E2 HUM
132" (3353mm)
FRONT VIEW DPN002154
Rev. 1
Table 21 Piping data—Downflow, air-cooled 105kW (30 tons) with EC fans, standard scroll 3 and
semi-hermetic compressors
X Y Connection Size / Opening
Point Description in. (mm) in. (mm) in. (mm)
R Refrigerant Access 109 (2769) 15-3/4 (400) 16-7/16 x 4 (418 x 102)
L1 Liquid Line System 1 121-3/4 (3092) 16-3/4 (425) 5/8 Cu Sweat
L2 Liquid Line System 2 118-1/8 (3000) 16-3/4 (425) 5/8 Cu Sweat
G1 Hot Gas Discharge 1 118-1/4 (3004) 14-1/4 (362) 1-1/8 Cu Sweat
G2 Hot Gas Discharge 2 115-5/8 (2937) 14-1/4 (362) 1-1/8 Cu Sweat
Condensate Drain
87-3/8 (2220) 31 (787) 3/4 FPT
CD 1 (Infrared Humidifier or No Humidifier)
W/ Optional Pump 83-13/16 (2129) 30 (762) 1/2 Cu Sweat
HUM Humidifier Supply Line 85-5/16 (2167) 32-1/2 (825) 1/4 Cu Sweat
2
ECS Econ-O-Coil Supply 101-7/8 (2588) 29 (737) 2-5/8 Cu Sweat
ECR 2 Econ-O-Coil Return 94-9/16 (2402) 29 (737) 2-5/8 Cu Sweat
E1 Electrical Connection (High-Voltage) 98-1/8 (2492) 31 (788) 2-1/2
E2 Electrical Connection (High-Voltage) 91 (2311) 31 (788) 2-1/2
LV1 Electrical Connection (Low-Voltage) 2 (51) 29 (737) 7/8
LV2 Electrical Connection (Low-Voltage) 2 (51) 30-7/8 (784) 7/8
LV3 Electrical Connection (Low-Voltage) 2 (51) 32 (813) 7/8
B1 Blower Outlet 4-1/2 (114) 33 (838) 77-3/8 x 30 (1965 x 762)
1. Field-pitch condensate drain line a minimum of 1/8" (3.2mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on dual-cool systems only (four-pipe system)
3. Digital scroll compressors not available on DS 105
4. Piping dimensions shown are connection sizes; field piping sizes may be different, depending on distance. Refer to user manual,
SL-18825.
5. Source: DPN002154, Rev. 1

37 Liebert® DS™
Weights and Dimensions

7.1 Downflow Model Dimensions and Primary Connections—


Water/Glycol/GLYCOOL™ Systems
Figure 18 Cabinet and floor planning dimensions—Downflow, water/glycol/GLYCOOL, 28-42kW
(8-12 tons), all compressors with EC fans
Condenser
Cleanout
Access
56-7/8" (1445mm)
Opening

35" 24-3/8"
(889mm) AIR INLET OPENING (619mm)
33"
Opening
(838mm) 1-3/4"
(44mm) Handle
5/16 Filters are accessible
(8mm) through top of unit only.
Secondary Condenser Fluid Bezel Downflow electrical
Piping Entrance TOP VIEW Secondary Entrance connections can be made
Low-Voltage Connections from top or bottom of unit.
Secondary Entrance
High-Voltage Connection(s)
86" (2184mm) Required for
condenser cleanout
24"
(610mm)
Minimum required
for filter replacement

15"
(381mm)

76"
(1930mm)

34"
Shaded area indicates a (864mm)
2" 85" (2159mm)
(51mm) recommended minimum
FRONT VIEW clearance from floor to top DPN003135
of unit and plenum for
component access.
Rev. 2

Liebert® DS™ 38
Weights and Dimensions

Figure 19 Primary connection locations—Downflow, water/glycol/GLYCOOL™, 28-42kW, EC fans, all


compressor models

NOTE
1. Drawing not to scale.
2. Tolerance on all All dimensions from
piping dimensions rear corner of unit
is ±1/2" (13mm). A A including panels
FRONT VIEW
SECTION A-A X O

Y
8"
(203mm) 35"
BLOWER (889mm)
OUTLET
ECS
3-1/2"
(89mm) HUM LV1
LV2
CD LV3
E1 E2 ECR B

4-1/2" DPN003530
86" (2184mm) (114mm)
Rev. 0
FRONT
Table 22 Piping data—Downflow, water/glycol/GLYCOOL, 28-42kW, all compressors
Connection Size / Opening
in. (mm)
X Y
Point Description in. (mm) in. (mm) 28-35kW (8-10 tons) / 42kW (12 tons)
W Water/Glycol/GLYCOOL Access 79-15/16 (2030) 9-1/16 (230) 3-1/2 x 8 (89 x 203)
WS Water/Glycol/GLYCOOL Supply 82-15/16 (2107) 10-15/16 (278) 1-5/8 / 2-1/8 Cu Sweat
WR Water/Glycol/GLYCOOL Return 82-15/16 (2107) 14-1/16 (357) 1-5/8 / 2-1/8 Cu Sweat
2
ECS Econ-O-Coil Supply 54-7/8 (1394) 22-9/16 (573) 1-5/8 / 2-1/8 Cu Sweat
2
ECR Econ-O-Coil Return 49-13/16 (1265) 28-1/2 (724) 1-5/8 / 2-1/8 Cu Sweat
1
Condensate Drain 46 (1168) 29-1/2 (749) 3/4 FPT
(Infrared Humidifier Or No Humidifier)
CD Condensate Drain 1
46 (1168) 29-1/2 (749) 1-1/4 FPT
(Steam Generating Humidifier)
W/ Optional Pump 46 (1168) 29-1/2 (749) 1/2 Cu Sweat
HUM Humidifier Supply Line 53-1/2 (1359) 29 (737) 1/4 Cu Sweat
HS Hot Water Reheat Supply Consult Factory
HR Hot Water Reheat Return Consult Factory
E1 Electrical Connection (High-Voltage) 55-1/2 (1410) 31-1/4 (794) 2-1/2
E2 Electrical Connection (High-Voltage) 52-7/16 (1332) 31-1/4 (794) 2-1/2
LV1 Electrical Connection (Low-Voltage) 2-1/4 (57) 27 (686) 7/8
LV2 Electrical Connection (Low-Voltage) 2-1/4 (57) 29 (737) 7/8
LV3 Electrical Connection (Low-Voltage) 2-1/4 (57) 31 (787) 7/8
B Blower Outlet 4-1/2 (114) 33 (838) 31 x 31 (787 x 787)
1. Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on dual cool systems only (four-pipe systems).
3. Source: DPN003530, Rev. 0

39 Liebert® DS™
Weights and Dimensions

Figure 20 Cabinet and floor planning dimensions—Downflow, water/glycol/GLYCOOL™, 53-77kW (15-22


tons), all compressors with EC fans
Condenser Cleanout Access Digital scroll compressors
not available on 077 models.
80" (2032mm)
Opening
Filters are accessible
through top of unit only.
33" 24-5/8" Downflow electrical
(838mm) AIR INLET OPENING (625mm) connections can be made
Opening from top or bottom of unit.
35"
(889mm
5/16"
(8mm)
1-3/4" Bezel
Secondary Condenser (44mm) Handle Secondary Entrance
Fluid Piping Entrance Low-Voltage Connections Required for
Secondary Entrance TOP VIEW condenser cleanout
High-Voltage Connection(s)
24"
(610mm) Minimum
required
for filter
109" replacement
(2769mm)
5"
(127mm)

76"
(1930mm)

34"
Shaded area indicates a
(864mm)
recommended minimum
2" 108" (2743mm) clearance from floor to top
of unit and plenum DPN003142
(51mm) Rev. 2
FRONT VIEW for component access.

Liebert® DS™ 40
Weights and Dimensions

Figure 21 Primary connection locations—Downflow, water/glycol/GLYCOOL™, 53-77kW, all compressors


with EC fans

Digital scroll compressors


not available on 077 models.
NOTE: Drawing not to scale.
Tolerance on All dimensions from
all piping dimensions rear corner of unit
is ± 1/2" (13mm). A A including panels
FRONT VIEW
X
SECTION A-A O

3-1/2"
(89mm)
W Y
8" WS
(203mm) WR 35"
(889mm)

ECS ECR LV1


CD B1 LV2
LV3
E1 E2 HUM
109" (2769mm)
FRONT OF UNIT DPN002183
Rev. 1
Table 23 Piping data—Downflow, water/glycol/GLYCOOL, 53-77kW, all compressors
X Y Connection Size / Opening
Point Description in. (mm) in. (mm) in. (mm)
W Water/Glycol/GLYCOOL Access 103 (2616) 9 (229) 3-1/2 x 8 (89 x 203)
WS Water/Glycol/GLYCOOL Supply 104-3/4 (2661) 11 (279) 2-1/8 Cu Sweat
WR Water/Glycol/GLYCOOL Return 104-3/4 (2661) 15 (381) 2-1/8 Cu Sweat
Condensate Drain
69-1/4 (1759) 30 (762) 3/4 FPT
CD (Infrared Humidifier or No Humidifier)*
W/ Optional Pump 69-1/4 (1759) 30 (762) 1/2 Cu Sweat
HUM Humidifier Supply Line 76-1/2 (1943) 29 (736) 1/4 Cu Sweat
2
ECS Econ-O-Coil Supply 78-5/8 (1997) 22-1/4 (565) 2-1/8 Cu Sweat
ECR 2 Econ-O-Coil Return 73-15/16 (1862) 26-9/16 (675) 2-1/8 Cu Sweat
E1 Electrical Connection (High-Voltage) 78-1/2 (1994) 31-1/8 (790) 2-1/2
E2 Electrical Connection (High-Voltage) 75-3/8 (1915) 31-1/8 (790) 2-1/2
LV1 Electrical Connection (Low-Voltage) 2 (51) 28-1/2 (724) 7/8
LV2 Electrical Connection (Low-Voltage) 2 (51) 30-1/4 (768) 7/8
LV3 Electrical Connection (Low-Voltage) 2 (51) 32 (813) 7/8
B1 Blower Outlet 4-1/28 (114) 133 (838) 58-3/8 x 30 (1483 x 762)
1. Field-pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on dual-cool systems only (four-pipe system).
3. Source: DPN002183, Rev. 0

41 Liebert® DS™
Weights and Dimensions

Figure 22 Cabinet and floor planning dimensions—Downflow, water/glycol/GLYCOOL™, 105kW (30


tons), all compressors with EC fans

Condenser Cleanout Access Digital scroll compressors not


available on 105 models.
102-13/16"
(2611mm) Opening Filters are accessible
through top of unit only.
33" Downflow electrical
24-3/8"
(838mm) AIR INLET OPENING connections can be made
(619mm)
from top or bottom of unit.
35" Opening
(889mm)
5/16"
(8mm Bezel
Secondary Condenser 1-3/4"
Fluid Entrance (44mm) Handle Secondary Entrance
Secondary Entrance TOP VIEW Low-Voltage Connections
High-Voltage Connection(s) Required for
condenser
24"
cleanout
(610mm)
132" (3353mm) Minimum required
for filter replacement

5"
(127mm)

76"
(1930mm)

34" (864mm)

Shaded area indicates a


131" (3327mm) recommended minimum
FRONT VIEW clearance from floor
to top of unit and plenum DPN003146
for component access. Rev. 2

Liebert® DS™ 42
Weights and Dimensions

Figure 23 Primary connection locations—Downflow, water/glycol/GLYCOOL™ 105kW (30 tons), EC fans,


semi-hermetic or standard scroll compressors
Digital scroll compressors
not available on 105 models

NOTES
Drawing not to scale. All dimensions from
Tolerance on
A A Rear corner of unit
all piping dimensions FRONT VIEW Including panels
is ± 1/2" (13mm). X
SECTION A-A O

W
8" WS
(203mm) WR Y

35"
3-1/2" BLOWER (889mm)
(89mm) OUTLET
ECS ECR
CD LV1
B1 LV2
LV3
E1 E2 HUM
132" (3353mm)
FRONT OF UNIT DPN002153
Rev. 1
Table 24 Piping data—Downflow, water/glycol/GLYCOOL 105kW (30 tons), EC fans, semi-hermetic or
standard scroll compressors 3
X Y Connection Size / Opening
Point Description in. (mm) in. (mm) in. (mm)
W Water/Glycol/GLYCOOL Access 125-15/16 (3199) 9 (229) 3-1/2 x 8 (89x203)
WS Water/Glycol/GLYCOOL Supply 127-7/8 (3248) 10-1/16 (256) 2-1/8 Cu Sweat
WR Water/Glycol/GLYCOOL Return 127-7/8 (3248) 13-1/4 (337) 2-1/8 Cu Sweat
Condensate Drain
87-3/8 (2220) 31 (787) 3/4 FPT
CD (Infrared Humidifier or No Humidifier) 1
W/ Optional Pump 83-13/16 (2129) 30 (762) 1/2 Cu Sweat
HUM Humidifier Supply Line 85-5/16 (2167) 32-1/2 (825) 1/4 Cu Sweat
ECS 2 Econ-O-Coil Supply 101-7/8 (2588) 29 (737) 2-5/8 Cu Sweat
ECR 2 Econ-O-Coil Return 94-9/16 (2402) 29 (737) 2-5/8 Cu Sweat
E1 Electrical Connection (High-Voltage) 98-1/8 (2492) 31 (788) 2-1/2
E2 Electrical Connection (High-Voltage) 91 (2311) 31 (788) 2-1/2
LV1 Electrical Connection (Low-Voltage) 2 (51) 29 (737) 7/8
LV2 Electrical Connection (Low-Voltage) 2 (51) 30-7/8 (784) 7/8
LV3 Electrical Connection (Low-Voltage) 2 (51) 32 (813) 7/8
B1 Blower Outlet 4-1/2 (114) 33 (838) 77-3/8 x 30 (1965x762)
1. Field-pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on dual-cool systems only (four-pipe system)
3. Digital scroll compressors not available on 105 models
4. Piping dimensions shown are connection sizes; field piping sizes may be different, depending on distance. Refer to user manual,
SL-18825.
5. Source: DPN002153, Rev. 1

43 Liebert® DS™
Weights and Dimensions

7.2 Downflow Models with Front and/or Rear Discharge


Figure 24 Cabinet and floor planning dimensions—Downflow, 28-42kW (8-12 tons), front and/or rear
discharge models with EC fans
Secondary Refrigerant
Piping Entrance
24" (610mm) Minimum required
56-7/8" (1445mm)
for filter replacement.
Opening
Required for Condenser
cleanout on Water/Glycol
33" AIR INLET OPENING or GLYCOOL/Dual cool 5"
24-3/8"
(838mm) (127mm)
(619mm)
1-3/4" Opening
35"
(889mm) (44mm) Handle

5/16"
Secondary Entrance (8mm) Bezels
High-Voltage Connection(s) Secondary Entrance
TOP VIEW
Low-Voltage Connections
A
Shaded area indicates a
recommended minimum
clearance from floor to top 34"
of unit and plenum (864mm)
for component access.

76"
(1930mm)

33-1/2"
(851mm)
19"
(483mm) Air Outlet
Opening
3"
3-1/4" 33-3/8"
2" (76mm)
(81mm) 19" (848mm)
(51mm) 3"
B (483mm) Air Outlet
(77mm) Opening
FRONT VIEW

3-1/4"
Filters are accessible only through top of unit. (81mm)
Customer Piping and Wiring Connections
1. For primary connection locations see standard submittals.
A floor stand at least 9" high is recommended if primary
connections locations are to be used.
DPN003180
2. Contact the factory to relocate connection locations. Rev. 1

Liebert® DS™ 44
Weights and Dimensions

Figure 25 Cabinet and floor planning dimensions—Downflow, 53-77kW (15-22 tons), front and/or rear
discharge models with EC fans
Secondary Refrigerant Required for Condenser
Piping Entrance 24" (610mm) cleanout on Water/Glycol or
80" (2032mm) GLYCOOL/Dual Cool.
Opening
Minimum required
for filter replacement.
35" AIR INLET OPENING 25-5/8" 5"
(889mm) (619mm) (127mm)
1-34" Opening
33"
(44mm) Handle
(838mm)

5/16"
Secondary Entrance TOP VIEW (619mm) Bezel
High-Voltage Connection(s) Secondary Entrance
Low-Voltage Connections
A Shaded area indicates
a recommended minimum
34"
clearance from floor to top
(864mm)
of unit and plenum for
component access.

76"
(1930mm)

15-1/8" 15-1/8"
(384mm) (384mm)
29-1/4" 29-5/8"
(743mm) (752mm) 3-1/8"
Air Outlet Air Outlet 15-1/8" 15-1/8"
Opening Opening (79mm) (384mm) (384mm)
29-5/8" 29-1/4"
2" FRONT VIEW 3-1/4" (752mm) (743mm)
Air Outlet Air Outlet
(83mm)
(51mm) B
Opening Opening

Filters are accessible through top of unit only. 3" 3-1/4"


Customer Piping and Wiring Connections (76mm) (83mm) REAR VIEW
1. For primary connection locations see standard submittals.
A floor stand at least 9" high is recommended if primary
connections locations are to be used. DPN003181
2. Contact the factory to relocate connection locations. Rev. 1

45 Liebert® DS™
Weights and Dimensions

Figure 26 Cabinet and floor planning dimensions—Downflow, air-cooled, 105kW (30 tons), front
discharge models with EC fans
Secondary Refrigerant
Piping Entrance
102-7/8" (2611mm)
Opening

33" 24-3/8"
(838mm) AIR INLET OPENING
(619mm)
35" Opening
(889mm)

5/16"
1-34" (619mm)
Secondary Entrance (44mm) TOP VIEW Secondary Entrance Bezel
High-Voltage Connection(s) Handle Low-Voltage Connections

Required for Condenser cleanout


132" (3353mm) on Water/Glycol or GLYCOOL/Dual Cool.

24" Minimum required


(610mm) for filter replacement.

5"
76" (127mm)
(1930mm)

16-1/8" 16-1/8" 16-1/8"


(410mm) (410mm) (410mm)
25-5/8" 24-7/8" 28-1/4"
(649mm) (649mm) (718mm)
Air Outlet Air Outlet Air Outlet
Opening Opening Opening

30-7/8" 3/4"
(783mm) (19mm)
57-1/2"
(1459mm) 34"
131" (3326mm) Shaded area indicates a (864mm)
FRONT VIEW recommended minimum
clearance from floor to top of unit
Filters are accessible through top of unit only. and plenum for component access.
Downflow electrical connections can be made
from top or bottom of unit.
Customer Piping and Wiring Connections
1. For primary connection locations see standard submittals. DPN003182
A floor stand at least 9" high is recommended if primary Rev. 1
connections locations are to be used.
2. Contact the factory to relocate connection locations.

Liebert® DS™ 46
Weights and Dimensions

7.3 Disassembly Dimensions—Downflow Air-Cooled Systems


Figure 27 Disassembly dimensions—Downflow, air-cooled, 28-42kW (8-12 tons), scroll or digital scroll
compressors with EC fans

Filter & Electric


Box Assembly

39"
(991mm)

76"
(1930mm)
Blower & Coil Assembled
Compressor Assembly Assembly Height

76"
59-7/16"
(1930mm)
(1509mm)

37"
(940mm)

33" 13" 59" (1499mm)


(838mm) (330mm)
72" (1829mm)
Assembled Length
Drawing views are simplified with panels removed to show overall dimensions. DPN003133
See disassembly and handling instructions in installation manual. Rev. 1

Dry Weight, Approximate, lb. (kg)


Component Air-Cooled Dual-Cool
Compressor Assembly 490 (223) 490 (223)
Filter and Electric Box Assembly 210 (96) 210 (96)
Blower and Coil Assembly 770 (350) 920 (418)
Source: DPN000802, Rev. 2

47 Liebert® DS™
Weights and Dimensions

Figure 28 Disassembly dimensions—Downflow, air-cooled, 28-42kW (8-12 tons), semi-hermetic


compressors with EC fans

Filter & Electric


Box Assembly

39"
(991mm)

76"
Compressor Assembly Blower & Coil (1930mm)
Assembly Assembled
Height

76" 59-7/16"
(1930mm) (1509mm)

37"
(940mm)

33" 26" 59" (1499mm)


(838mm) (660mm)
85" (2159mm)
Assembled Length

Drawing views are simplified with panels removed to show overall dimensions. DPN003132
See disassembly and handling instructions in installation manual. Rev. 1

Dry Weight, Approximate, Including Panels, lb (kg)


Component Air-Cooled Dual-Cooled
Compressor Assembly 800 (364) 800 (364)
Filter and Electric Box Assembly 210 (96) 210 (96)
Blower and Coil Assembly 770 (350) 920 (418)
Source: DPN003132, Rev. 1

Liebert® DS™ 48
Weights and Dimensions

Figure 29 Disassembly dimensions—Downflow, air-cooled, 53-77kW (15-22 tons), scroll or digital scroll 1
compressors

Digital scroll compressors


not available on DS 077.

Filter & Electric Box Assembly

39"
(991mm)

Compressor Assembly 76"


(1930mm)
Blower & Coil Assembly
Assembled
Height

76"
(1930mm)
59-7/16"
(1509mm)

37"
(940mm)

DS053-DS077 =
33" 15" (381mm) 82" (2083mm)
(838mm) Assembled Length
DS053-DS077 = 97" (2464mm) DPN003140
Drawing views are simplified with panels removed to show over all dimensions. Rev. 1
See disassembly and handling instructions in installation manual.

Dry Weight, Approximate, Including Panels, lb (kg)


Component Air-Cooled Dual-Cool
Compressor Assembly 540 (246) 540 (246)
Filter and Electric Box Assembly 250 (114) 250 (114)
Blower and Coil Assembly 1230 (560) 1410 (641)
1. Digital scroll compressors not available on 077 models.
2. Source: DPN003140, Rev. 1

49 Liebert® DS™
Weights and Dimensions

Figure 30 Disassembly dimensions—Downflow, air-cooled, 53-77kW (15-22 tons), semi-hermetic


compressors

Filter & Electric


Box Assembly

39"
(991mm)

Compressor Assembly 76"


(1930mm)
Assembled
Blower & Coil
Height
Assembly

76"
(1930mm)
59-3/8"
(1507mm)

37"
(940mm)

33" 26" 82" (2083mm)


(838mm) (660mm)
108" (2743mm)
Assembled Length
Drawing views are simplified with panels removed to show overall dimensions.
DPN003139
See disassembly and handling instructions in installation manual. Rev. 1

Dry Weight, Approximate, Including Panels, lb (kg)


Component Air-Cooled Dual-Cool
Compressor Assembly 970 (441) 970 (441)
Filter and Electric Box Assembly 250 (114) 250 (114)
Blower and Coil Assembly 1230 (560) 1410 (641)
Source: DPN003139, Rev. 1

Liebert® DS™ 50
Weights and Dimensions

Figure 31 Disassembly dimensions—Downflow, air-cooled, 105kW (30 tons), standard scroll


compressors

Digital scroll compressors not


available on 105 models.

Filter & Electric Box Assembly

39"
(991mm)

41-11/16"
(1059mm)

Compressor Assembly
76"
(1930mm)
Blower & Coil Assembled Height
Assembly

76"
(1930mm)
59-7/16"
(1510mm)
37"
(940mm)

33" 26" 105" (2667mm)


(838mm) (660mm)
131" (3327mm)
Assembled Length
Drawing views are simplified with panels removed to show overall dimensions. DPN003148
See disassembly and handling instructions in installation manual. Rev. 2

Dry Weight, Approximate Including Panels, lb (kg)


EC Fans
Component Air-Cooled Dual-Cool
Compressor Assembly 830 (377) 830 (377)
Filter and Electric Box Assembly 270 (123) 270 (123)
Blower and Coil Assembly 1560 (708) 1915 (870)
1. Digital scroll compressors not available on DS 105 models.
2. Source: DPN003148, Rev. 2

51 Liebert® DS™
Weights and Dimensions

Figure 32 Disassembly dimensions—Downflow, air-cooled, 105kW (30 tons), semi-hermetic


compressors

Filter and Electric Box Assembly

39"
(991mm)

41-11/16"
(1059mm)

Compressor
76"
Assembly
(1930mm)
Assembled
Blower and Coil Assembly Height

76"
(1930mm)
59 7/16"
(1510mm)

37"
(940mm)

33" 26" 105" (2667mm)


(838mm) (660mm) DPN003147
131" (3327mm) Rev. 1
Assembled Length

Dry Weight, Approximate, Including Panels, lb (kg)


EC Fans
Component Air-Cooled Dual-Cool
Compressor Assembly 950 (432) 950 (432)
Filter and Electric Box Assembly 270 (123) 270 (123)
Blower and Coil Assembly 1560 (708) 1915 (870)
Source: DPN003147, Rev. 1

Liebert® DS™ 52
Weights and Dimensions

7.4 Disassembly Dimensions—Downflow, Water/Glycol/GLYCOOL™ Systems


Figure 33 Disassembly dimensions—Downflow, water/glycol/GLYCOOL, 28-42kW (8-12 tons), all
compressors

Filter & Electric


Box Assembly

39"
(991mm)

Compressor Assembly Blower & Coil 76"


Assembly (1930mm)
Assembled
Height

76"
(1930mm) 59-7/16"
(1509mm)

37"
(940mm)

33" 26" 59" (1499mm)


(838mm) (660mm)
85" (2159mm)
Assembled Length DPN003136
Drawing views are simplified with panels removed to show overall dimensions. Rev. 1
See disassembly and handling instructions in installation manual.

Dry Weight, Approximate, Including Panels, lb (kg)


Semi-Hermetic Compressor Scroll or Digital Scroll Compressor
Component Water/Glycol GLYCOOL/Dual-Cool Water/Glycol GLYCOOL/Dual-Cool
Compressor Assembly 950 (432) 950 (432) 800 (364) 800 (364)
Filter and Electric Box Assembly 210 (96) 210 (96) 210 (96) 210 (96)
Blower and Coil Assembly 770 (350) 920 (418) 770 (350) 920 (418)
Source: DPN003136, Rev. 1

53 Liebert® DS™
Weights and Dimensions

Figure 34 Disassembly dimensions—Downflow, water/glycol/GLYCOOL™, 53-77kW (15-22 tons), all


compressors

Digital scroll compressors


not available on 077 models

Filter & Electric Box Assembly

39"
(991mm)

76"
Compressor Assembly (1930mm)
Assembled
Blower & Coil Height
Assembly

76"
(1930mm)
59-7/16"
(1509mm)
37"
(940mm)

33" 26" 82" (2083mm)


(838mm) (660mm)
108" (2743mm)
Assembled Length
Drawing views are simplified with panels removed to show overall dimensions. DPN003143
See disassembly and handling instructions in installation manual. Rev. 1
Dry Weight, Approximate, Including Panels, lb (kg)
Semi-Hermetic Compressor Scroll or Digital Scroll Compressor 1
Component Water/Glycol GLYCOOL/Dual-Cool Water/Glycol GLYCOOL/Dual-Cool
Compressor Assembly 1270 (578) 1270 (578) 840 (382) 840 (382)
Filter and Electric Box Assembly 250 (114) 250 (114) 250 (114) 250 (114)
Blower and Coil Assembly 1230 (560) 1410 (641) 1230 (560) 1410 (641)
1. Digital scroll compressors not available on 077 models
2. Source: DPN003143, Rev. 1

Liebert® DS™ 54
Weights and Dimensions

Figure 35 Disassembly dimensions—Downflow, water/glycol/GLYCOOL™ 105kW (30 tons), semi-


hermetic or standard scroll compressors
Digital scroll compressors
not available on 105 models

Filter & Electric Box Assembly

39"
(991mm)
41-11/16"
(1059mm)

Compressor Assembly
76" (1930mm)
Blower & Coil Assembled
Assembly Height

76"
(1930mm)
59-7/16"
(1510mm)
37"
(940mm)

33" 26" 105" (2667mm)


(838mm) (660mm)
131" Assembled Length
(3327mm)
Drawing views are simplified with panels removed to show overall dimensions. DPN003150
See disassembly and handling instructions in installation manual. Rev. 1

Dry Weight, Approximate, Including Panels, lb (kg)


Semi-Hermetic Compressor Standard Scroll Compressor 1
Component Water/Glycol GLYCOOL/Dual-Cool Water/Glycol GLYCOOL/Dual-Cool
Compressor Assembly 1320 (600) 1320 (600) 1200 (545) 1200 (545)
Filter and Electric Box Assembly 270 (123) 270 (123) 270 (123) 270 (123)
Blower and Coil Assembly 1560 (708) 1915 (870) 1560 (708) 1915 (870)
1. Digital scroll compressors not available on 105 models.
2. Source: DPN003150, Rev. 2

55 Liebert® DS™
Weights and Dimensions

7.5 Upflow Model Dimensions and Primary Connections—Air-Cooled Systems with


EC Fans
Figure 36 Cabinet and floor planning dimensions—Upflow, air-cooled, 28-42kW (8-12 tons), scroll or
digital scroll compressors with EC fans
Alternate refrigerant
piping entrance

33"
(838mm)
34-3/4"
(883mm) 5/16"
(8mm)
Bezel Space required for EC fan
plenum (shipped separately)
dependent on height of plenum
High-Voltage ordered.
1-3/4"
Connection(s)
(44mm) TOP VIEW
Low-Voltage
Handle Connection(s)
3-1/24"
73-1/16" 1856mm)
(90mm)

75"
(1924mm)
36"
(914mm)
Shaded area indicates a
required minimum clearance from floor
to top of unit and plenum for component
access.

72" (1829mm)
1-3/4"
(44mm) FRONT VIEW
Notes:
1. Front air return unit shown. For rear return unit, in addition to front service
area shown, also include 25" (635mm) on one side of unit for access to rear
return filter box. See DPN001196.
2. EC fan plenum is not shown. EC fans and plenum are shipped separately. DPN003495
See DPN002747 for unit dimensions with EC fans plenum mounted Rev. 0

Liebert® DS™ 56
Weights and Dimensions

Figure 37 Primary connection locations—Upflow, air-cooled, 28-42kW (8-12 tons), scroll or digital scroll
compressors with EC fans
All dimensions from
rear corner of unit
10-1/8"
including panels X O
(257mm)
ECR
NOTES 4-1/8" (105mm) 3. R1 ECS
1. Drawing not to scale. HUM
2. Tolerance on all piping dimensions CPD
is ± 1/2" (13mm). R2 4.
4" L1 L2 G1 G2
3. Field-routed alternatives for refrigerant
gas and liquid line connection points. (102mm) Y
35"
4. See submittal page DPN002747 (889mm) 11-13/16"
for plenum dimensional data. 3. (300mm)
LV1
E1 E2 LV2 LV3

73" (1854mm)
TOP VIEW OF UNIT Front of Unit

6"
(152mm) R3

17-3/16" 3. 17-1/16" L1 L2 G1 G2
(437mm) (434mm)
CGD*

3-7/8" 14-1/4" CGD*


(362mm) Factory Location
(98mm)
15-7/8" FRONT SECTION VIEW OF UNIT DPN002740
(403mm) (Left Front Panel Not Shown) Rev. 0
LEFT SIDE SECTION VIEW OF UNIT
Table 25 Piping data—Upflow, air-cooled, 28-42kW (8-12 tons), scroll compressor models
X Y Connection Size / Opening
Point Description in. (mm) in. (mm) in. (mm)
R1 3 Refrigerant Access (Top) 60-5/8 (1539) 2-13/16 (71) 10-1/8 x 4-1/8 (257 x 105)
R2 3 Refrigerant Access (Bottom) 63 (1600) 13-13/16 (351) 16-7/16 x 4 (418 x 102)
L1 Liquid Line System 1 79-3/16 (2011) 16-3/4 (425) 1/2 Cu Sweat
L2 Liquid Line System 2 76-1/2 (1943) 16-3/4 (425) 1/2 Cu Sweat
G1 Hot Gas Discharge 1 73-7/8 (1876) 16-5/8 (422) 5/8 Cu Sweat
G2 Hot Gas Discharge 2 70-1/8 (1780) 16-5/8 (422) 5/8 Cu Sweat
R3 3 Refrigerant Access (Side) — — 6 x 17-3/16 (152 x 437)
1
CGD Condensate Gravity Drain — — 3/4 FPT
CPD Condensate Pump Discharge (Optional) 56-1/4 (1429) 11-1/8 (283) 1/2 Cu Sweat
HUM Humidifier Supply Line 56-1/4 (1429) 9-1/8 (233) 1/4 Cu Sweat
ECS 2 Econ-O-Coil Supply 56 (1423) 7-5/16 (186) 1-5/8 Cu Sweat
ECR 2 Econ-O-Coil Return 56 (1423) 4-1/2 (114) 1-5/8 Cu Sweat
E1 Electrical Connection (High-Voltage) 52-3/8 (1331) 29-15/16 (760) 2-1/2
E2 Electrical Connection (High-Voltage) 47-3/8 (1204) 29-15/16 (760) 2-1/2
LV1 Electrical Connection (Low-Voltage) 8-1/8 (207) 29-9/16 (751) 7/8
LV2 Electrical Connection (Low-Voltage) 8-1/8 (207) 31 (787) 7/8
LV3 Electrical Connection (Low-Voltage) 8-1/8 (207) 32-7/16 (824) 7/8
1. Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap.
Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must
comply with all local codes.
2. Supplied on dual cool systems only.
3. Source: DPN002740, Rev. 0

57 Liebert® DS™
Weights and Dimensions

Figure 38 Cabinet and floor planning dimensions—Upflow, air-cooled, 28-42kW (8-12 tons),
semi-hermetic compressor models with EC fans

Alternate refrigerant
piping entrance

33"
(838mm) Space required for EC fan
34-3/4" 5/16" plenum (shipped separately)
(883mm) (8mm) dependent on height of plenum
Bezel ordered.

High-Voltage 1-9/16" TOP VIEW


Connection(s) (40mm) Low-Voltage
Handle Connection(s)
3-1/4"
(83mm)
86-1/16" (2186mm)

76"
(1930mm)
36"
Shaded area indicates a (914mm)
required minimum clearance
from floor to top of unit and
plenum for component access.

2" 84-15/16" (2158mm)


(50mm) FRONT VIEW
Notes:
1. Front air return unit shown. For rear return unit, in addition to front service
area shown, also include 25" (635mm) on one side of unit for access to rear
return filter box. See DPN001196.
2. EC fan plenum is not shown. EC fans and plenum are shipped separately. DPN003494
See DPN002747 for unit dimensions with EC fans plenum mounted Rev. 0

Liebert® DS™ 58
Weights and Dimensions

Figure 39 Primary connection locations—Upflow air-cooled, 28-42kW, semi-hermetic compressor


models with EC fans
All dimensions from
22-1/2" rear corner of unit
(572mm) including panels
X O
R1 ECR
ECS
15-3/16" 3. HUM
R2
(386mm) CPD
NOTES: 35"
1. Drawing not to scale. (889mm) 4.
2. Tolerance on all piping dimensions 4" L1 L2 G1 G2
is ± 1/2" (13mm). (102mm) 16-7/16" Y
3. Field-routed alternatives for refrigerant (418mm)
3.
gas and liquid line connection points.
LV1
E1 E2 LV2 LV3
4. See submittal page DPN002747
for plenum dimensional data.
86" (2184mm)
TOP VIEW OF UNIT Front of Unit

6"
(152mm) R3
G1 G2
20-1/16" L1 L2
17-3/16" 3.
(509mm)
(437mm)
CGD*

14-1/4" CGD*
3-7/8"
(362mm) Factory Location
(98mm)
15-7/8" FRONT SECTION VIEW OF UNIT DPN002739
(403mm) (Left Front Panel Not Shown) Rev. 0
LEFT SIDE SECTION VIEW OF UNIT
Table 26 Piping data—Upflow, air-cooled, 28-42kW, EC fans, semi-hermetic compressor models
X Y Connection Size / Opening
Point Description in. (mm) in. (mm) in. (mm)
R1 3 Refrigerant Access (Top) 60-11/16 (1542) 1-7/8 (48) 22-1/2 x 15-3/16 (572 x 386)
R2 3 Refrigerant Access (Bottom) 63 (1600) 13-13/16 (351) 16-7/16 x 4 (102 x 418)
L1 Liquid Line System 1 79-3/16 (2011) 16-3/4 (425) 1/2 Cu Sweat
L2 Liquid Line System 2 76-1/2 (1943) 16-3/4 (425) 1/2 Cu Sweat
G1 Hot Gas Discharge 1 73-7/8 (1876) 16-3/4 (425) 5/8 Cu Sweat
G2 Hot Gas Discharge 2 70-1/8 (1780) 16-3/4 (425) 5/8 Cu Sweat
R3 3 Refrigerant Access (Side) — — 6 x 17-3/16 (152 x 437)
CGD 1 Condensate Gravity Drain — — 3/4 FPT
CPD Condensate Pump Discharge (Opt) 56-1/4 (1429) 11-1/8 (283) 1/2 Cu Sweat
HUM Humidifier Supply Line 56-1/4 (1429) 9-1/8 (233) 1/4 Cu Sweat
ECS 2 Econ-O-coil Supply 56 (1423) 7-5/16 (186) 1-5/8 Cu Sweat
ECR** Econ-O-coil Return 56 (1423) 4-1/2 (114) 1-5/8 Cu Sweat
E1 Electrical Connection (High-Voltage) 52-3/8 (1331) 29-15/16 (760) 2-1/2
E2 Electrical Connection (High-Voltage) 47-3/8 (1204) 29-15/16 (760) 2-1/2
LV1 Electrical Connection (Low-Voltage) 8-1/8 (207) 29-9/16 (751) 7/8
LV2 Electrical Connection (Low-Voltage) 8-1/8 (207) 31 (787) 7/8
LV3 Electrical Conn. (Low Volt) 8-1/8 (207) 32-7/16 (824) 7/8
1. Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on dual cool systems only.
3. Source: DPN002739, Rev. 0

59 Liebert® DS™
Weights and Dimensions

Figure 40 Cabinet and floor planning dimensions—Upflow, air-cooled, 53-77kW (15-22 tons), scroll or
digital scroll compressor models with EC fans

Alternate Refrigerant Digital scroll compressors not


available on 077 models.
Piping Entrance

33" Space required for EC fan


(838mm) 5/16" plenum (shipped separately)
(8mm) dependent on height of plenum
34-3/4"
Bezel ordered.
(883mm)

High-Voltage 1-3/4"
Connection(s) (44mm) TOP VIEW
Low-Voltage
Handle
Connection(s)
3-1/4"
(83mm) 98" (2489mm)

76"
(1930mm)

36"
(914mm)
Shaded area indicates a
required minimum clearance
from floor to top of unit and
2" 96-15/16" (2462mm) plenum for component access.
(50mm) FRONT VIEW
Notes:
1. Front air return unit shown. For rear return unit, in addition to front service
area shown, also include 25" (635mm) on one side of unit for access to rear
return filter box. See DPN001196.
DPN003498
2. EC fan plenum is not shown. EC fans and plenum are shipped separately.
Rev. 0
See DPN002748 for unit dimensions with EC fans plenum mounted

Liebert® DS™ 60
Weights and Dimensions

Figure 41 Primary connection locations—Upflow, air cooled, 53-77kW (15-22 tons) with EC fans, scroll or
digital scroll compressor models with EC fans
All dimensions from
Digital scroll compressors 12" rear corner of unit
not available on 105 models. X O
(305mm) including panels

NOTES ECR
4" (102mm) 3. R1 ECS
1. Drawing not to scale. HUM
2. Tolerance on all piping CPD
R2
dimensions is ±1/2" (13mm). 4" L1 L2G1G2 4
35" (102mm)
3. Field-routed alternatives for (889mm)
refrigerant gas and liquid
LV1
Y
3.
line connections. 12-13/16" E1 LV2
4. See submittal page DPN002748 for (325mm) E2 LV3
plenums dimensions.
98" (2489mm)
TOP VIEW OF UNIT Front of Unit
6" (152mm)

R3

17-3/16" 3. 17-1/16" L1 L2G1G2


(437mm) (433mm)
CGD*

3-7/8" 14-1/4" Factory Location


(98mm) (362mm) CGD*
15-7/8" DPN002743
(403mm) FRONT SECTION VIEW OF UNIT Rev. 0
LEFT SIDE SECTION VIEW OF UNIT (Left Front Panel Not Shown)

* Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed
condensate trap. Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system
materials. The drain line must comply with all local codes.
** Supplied on dual cool systems only
Table 27 Piping data—Upflow, air cooled with EC fans, 53-77kWw (15-22 tons) scroll compressor models
X Y Connection Size / Opening
Point Description in. (mm) in. (mm) in. (mm)
R1 3 Refrigerant Access (Top) 83-5/8 (2124) 2 (51) 12 x 4 (305 x 102)
R2 3 Refrigerant Access (Bottom) 82-3/4 (2102) 14-3/4 (374) 12-3/16 x 4 (310 x 102)
53kW (15 Tons) / 70 and 77kW (20 and 22 Tons)
L1 Liquid Line System 1 94-11/16 (2405) 16-3/4 (425) 1/2 / 5/8 Cu Sweat
L2 Liquid Line System 2 91-7/8 (2334) 16-3/4 (425) 1/2 / 5/8 Cu Sweat
G1 Hot Gas Discharge 1 88-3/4 (2254) 16-3/8 (416) 7/8 / 1-1/8 Cu Sweat
G2 Hot Gas Discharge 2 85-9/16 (2173) 16-3/8 (416) 7/8 / 1-1/8 Cu Sweat
R3 3 Refrigerant Access (Side) — — 6 x 17-3/16 (152 x 437)
CGD 1 Condensate Gravity Drain — — 3/4 FPT
CPD Condensate Pump Discharge (Optional) 79-5/16 (2015) 11-7/8 (302) 1/2 Cu Sweat
HUM Humidifier Supply Line 79-5-16 (2015) 9-7/8 (251) 1/4 Cu Sweat
ECS 1 Econ-O-Coil Supply 78-5/8 (1998) 7-7/8 (200) 2-1/8 Cu Sweat
ECR 1 Econ-O-Coil Return 78-5/8 (1998) 4-5/8 (117) 2-1/8 Cu Sweat
E1 Electrical Connection (High-Voltage) 78-1/8 (1984) 30 (762) 2-1/2
E2 Electrical Connection (High-Voltage) 74-3/8 (1889) 30 (762) 2-1/2
LV1 Electrical Connection (Low-Voltage) 2-5/8 (66) 28-9/16 (726) 7/8
LV2 Electrical Connection (Low-Voltage) 2-5/8 (66) 30 (762) 7/8
LV3 Electrical Connection (Low-Voltage) 2-5/8 (66) 31-7/16 (799) 7/8
1. Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on dual cooling systems only
3. Source: DPN002743, Rev. 0

61 Liebert® DS™
Weights and Dimensions

Figure 42 Cabinet and floor planning dimensions—Upflow, air-cooled 53-77kW (15-22 tons),
semi-hermetic compressor models with EC fans
Alternate Refrigerant
Piping Entrance

33"
(838mm)

34-3/4"
(883mm) 5/16"
(8mm)
Bezel
High-Voltage 1-3/4" TOP VIEW
Connection(s) (44mm) Low-Voltage Space required for EC fan
Handle Connection(s) plenum (shipped separately)
dependent on height of plenum
3-1/4" ordered.
(83mm) 109" (2769mm)

76"
(1930mm)

36"
(914mm)
108" (2743mm)
2"
Shaded area indicates a
(50mm) FRONT VIEW required minimum clearance from floor
Notes: to top of unit and plenum for component
1. Front air return unit shown. For rear return unit, in addition to front service access.
area shown, also include 25" (635mm) on one side of unit for access to rear
return filter box. See DPN001196.
2. EC fan plenum is not shown. EC fans and plenum are shipped separately. DPN003497
See DPN002748 for unit dimensions with EC fans plenum mounted Rev. 0

Liebert® DS™ 62
Weights and Dimensions

Figure 43 Primary connection locations—Upflow, air-cooled, 53-77kW, semi-hermetic compressor


models with EC fans
All dimensions from
22-1/2" rear corner of unit X O
(572mm) including panels
NOTES:
1. Drawing not to scale. R1 ECR
2. Tolerance on all piping dimensions 15-3/16" R2 ECS
35" 3. HUM
is ± 1/2" (13mm). (386mm)
(889mm) CPD
3. Field-routed alternatives for 4.
L1 L2 G1 G2
refrigerant gas and liquid 4"
line connections. (102mm) 3. 16-7/16" Y
(418mm)
E1 E2
4. See submittal page DPN002748 LV1
LV2
for plenum dimension. LV3

109" 2760mm)
6" Front of Unit
(152mm)
TOP VIEW OF UNIT
R3

17-3/16" 3.
(437mm) G1 G2
CGD* 20-1/16" LV1 LV2

(509mm)
3-7/8" 14-1/4"
(98mm) (362mm)
15-7/8" CGD*
(403mm) FACTORYLOCATION
DPN002742
LEFT SIDE SECTION VIEW OF UNIT FRONT SECTION VIEW OF UNIT
(Left Front Panel Not Shown) Rev. 0

Table 28 Piping data—Air-cooled, upflow, 53-77kW, EC fans, semi-hermetic compressor models


X Y Connection Size / Opening
Point Description in. (mm) in. (mm) in. (mm)
R1 3 Refrigerant Access (Top) 83-3/4 (2127) 1-7/8 (48) 22-1/2 x 15-3/16 (572 x 386)
R2 3 Refrigerant Access (Bottom) 86 (2184) 13-7/8 (352) 16-7/16 x 4 (418 x 102)
53kW (15 Tons) / 70 and 77kW (20 and 22 Tons)
L1 Liquid Line System 1 97 (2464) 16-3/4 (425) 1/2 / 5/8 Cu Sweat
L2 Liquid Line System 2 93-5/16 (2370) 16-3/4 (425) 1/2 / 5/8 Cu Sweat
G1 Hot Gas Discharge 1 90-5/8 (2302) 16-5/8 (422) 7/8 / 1-1/8 Cu Sweat
G2 Hot Gas Discharge 2 88 (2235) 16-5/8 (422) 7/8 / 1-1/8 Cu Sweat
R3 3 Refrigerant Access (Side) — — 6 x 17-3/16 (152 x 437)
CGD 1 Condensate Gravity Drain — — 3/4 FPT
CPD Condensate Pump Discharge (Optional) 79-5/16 (2015) 11-7/8 (302) 1/2 Cu Sweat
HUM Humidifier Supply Line 79-5/16 (2015) 9-7/8 (251) 1/4 Cu Sweat
2
ECS Econ-O-Coil Supply 78-5/8 (1998) 7-7/8 (200) 2-1/8 Cu Sweat
2
ECR Econ-O-Coil Return 78-5/8 (1998) 4-5/8 (117) 2-1/8 Cu Sweat
E1 Electrical Connection (High-Voltage) 78-1/8 (1984) 30 (762) 2-1/2
E2 Electrical Connection (High-Voltage) 74-3/8 (1889) 30 (762) 2-1/2
LV1 Electrical Connection (Low-Voltage) 2-5/8 (66) 28-9/16 (726) 7/8
LV2 Electrical Connection (Low-Voltage) 2-5/8 (66) 30 (762) 7/8
LV3 Electrical Connection (Low-Voltage) 2-5/8 (66) 31-7/16 (799) 7/8
1. Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on dual cool systems only.
3. Source: DPN002742, Rev. 0

63 Liebert® DS™
Weights and Dimensions

Figure 44 Cabinet and floor planning dimensions—Upflow, air-cooled, 105kW (30 tons), all compressor
models with EC fans
Alternate Refrigerant Digital scroll compressors
Piping Entrance not available on 105 models.

33"
(838mm) Space required for EC fan plenum
34-3/4" (shipped separately) dependent on
(882mm) height of plenum ordered.

High-Voltage
Connection(s) 1-3/4" TOP VIEW 5/16"
(44mm) (8mm)
3-3/16" Low-Voltage
Handle Bezel
(81mm) Connection(s)
Typical
132-1/16" (3354mm)

76"
(1931mm)

2"
(51mm) 36"
Shaded area indicates a (914mm)
recommended minimum
130-15/16" (3325mm) clearance from floor to
ceiling for component access.
FRONT VIEW
Note:
1. Front air return unit shown. For rear return unit, in addition to front
service area shown, also include 25" (635mm) on one side of unit
for access to rear return filter box. See DPN001196.
2. EC fans plenum is not shown. EC fans and plenum are shipped
separately. See DPN002749 for unit dimensions with EC fans DPN003500
plenum mounted Rev. 0

Liebert® DS™ 64
Weights and Dimensions

Figure 45 Primary connection locations—Upflow, air-cooled 105kW (30 tons), all compressor models
with EC fans

All dimensions from


22-1/2" rear corner of unit
including panels
X O
(572mm)
R1 ECR
15-3/16" 3. R2
ECS
HUM
NOTES (386mm) CPD
35"
1. Drawing not to scale. 4.
(889mm) L1L2 G1G2
2. Tolerance on all piping 16-7/16"
dimensions is ±1/2" (13mm). 4" (418mm)
3. Field-routed alternatives for (102mm) E1 Y
3. E2 LV1 LV3
refrigerant gas and liquid LV2 LV3
line connections.
4. See submittal page DPN002749 for 132" (3353mm)
plenums dimensions. Front of Unit
TOP VIEW OF UNIT

6" (152mm)

R3
G1G2
17-3/16" 20-1/16" L1L2
3. (509mm)
(437mm)
CGD*

3-7/8" 14-1/4" CGD*


(98mm) (362mm) Factory Location
15-7/8" FRONT SECTION VIEW OF UNIT
(403mm) (Left Front Panel Not Shown) DPN002745
LEFT SIDE SECTION VIEW OF UNIT Rev. 0
Table 29 Piping data—Upflow, air-cooled 105kW (30 tons), EC fans, all compressor models
X Y Connection Size / Opening
Point Description in. (mm) in. (mm) in. (mm)
R1 3 Refrigerant Access (Top) 106-7/8 (2715) 1-7/8 (48) 22-1/2 x 15-3/16 (572mm x 386mm)
R2 3 Refrigerant Access (Bottom) 109-1/8 (2772) 13-7/8 (352) 16-7/16 x 4 (418mm x 102mm)
L1 Liquid Line System 1 121-3/4 (3092) 16-3/4 (425) 5/8 Cu Sweat
L2 Liquid Line System 2 118-1/8 (3000) 16-3/4 (425) 5/8 Cu Sweat
G1 Hot Gas Discharge 1 118-1/4 (3004) 14-1/4 (362) 1-1/8 Cu Sweat
G2 Hot Gas Discharge 2 115-5/8 (2937) 14-1/4 (362) 1-1/8 Cu Sweat
R3 3 Refrigerant Access (Side) — — 6 x 17-3/16 (152 x 437mm)
CGD 1 Condensate Gravity Drain — — 3/4 FPT
CPD Condensate Pump Discharge (Optional) 102-3/8 (2600) 13-5/8 (346) 1/2 Cu Sweat
HUM Humidifier Supply Line 101-1/8 (2569) 13-1/8 (333) 1/4 Cu Sweat
ECS 2 Econ-O-Coil Supply 101-1/8 (2569) 10-1/4 (260) 2-5/8 Cu Sweat
ECR 2 Econ-O-Coil Return 101-1/8 (2569) 5-1/4 (133) 2-5/8 Cu Sweat
E1 Electrical Connection (High-Voltage) 101-5/8 (2581) 30 (762) 2-1/2
E2 Electrical Connection (High-Voltage) 97-7/8 (2486) 30 (762) 2-1/2
LV1 Electrical Connection (Low-Voltage) 34-1/8 (867) 30-1/4 (769) 7/8
LV2 Electrical Connection (Low-Voltage) 34-1/8 (867) 31-3/4 (807) 7/8
LV3 Electrical Connection (Low-Voltage) 32-5/8 (829) 28-15/16 (734) 7/8
LV4 Electrical Connection (Low-Voltage) 32-5/8 (829) 30-7/16 (772) 7/8
1. Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on dual cool systems only.
3. Source: DPN002745, Rev. 0

65 Liebert® DS™
Weights and Dimensions

7.6 Upflow Model Dimensions and Primary Connections—Water/Glycol/GLYCOOL™


Cooled Systems
Figure 46 Cabinet and floor planning dimensions—Upflow, water/glycol/GLYCOOL, 28-42kW (8-12 tons),
all compressor models with EC fans

Condenser Cleanout Access

33"
(838mm)
34-3/4" Space required for EC fan
(883mm) 5/16" plenum (shipped separately)
(8mm) dependent on height of plenum
Bezel ordered.
Required for
24" Condenser Cleanout
Alternate Condenser Fluid 1-3/4" TOP VIEW (610mm)
Piping Entrance (44mm) Low-Voltage
High-Voltage Handle Connection(s)
Connection(s)
3-1/4" 86-1/16" (2186mm)
(83mm)

76"
(1930mm)

36"
(914mm)

Shaded area indicates a


required minimum clearance from floor
to top of unit and plenum for component
access.
2" 84-15/16" (2158mm)
(50mm)
Notes:
FRONT VIEW
1. Front air return unit shown. For rear return unit, in addition to front service
area shown, also include 25" (635mm) on one side of unit for access to rear
return filter box. See DPN001196.
2. EC fan plenum is not shown. EC fans and plenum are shipped separately. DPN003496
See DPN002747 for unit dimensions with EC fans plenum mounted Rev. 0

Liebert® DS™ 66
Weights and Dimensions

Figure 47 Primary connection locations—Upflow, water/glycol/GLYCOOL™, 28-42kW, all compressor


models with EC fans
All dimensions from rear corner
of unit including panels X O
ECR
1. Drawing not to scale. ECS
2. Tolerance on all piping dimensions W1, W2 3. HUM
is ± 1/2" (13mm). 8" CPD
3. Field-routed alternatives for (203mm)
water/glycol connections. 4
4. See submittal page DPN002747
2-7/8" Y
for plenum dimension.
35" (73mm)
3-1/2"
(889mm) LV1
(89mm) LV2
E1 E2 LV3
6" Front of Unit
(152mm) 86" 2184mm)
W3 TOP VIEW OF UNIT
WS
17-3/16" WR
(437mm) 3.
CGD*

3-7/8" 14-1/4"
(98mm) (362mm)
15-7/8"
(403mm)
CGD* FRONT SECTION VIEW OF UNIT DPN002741
LEFT SIDE SECTION VIEW OF UNIT (Left Front Panel Not Shown) Rev. 1
Table 30 Piping data—Upflow, water/glycol/GLYCOOL, 28-42kW, EC fans, all compressor models
Connection Size / Opening
in. (mm)
X Y 28-35kW (8-10 Tons) /
Point Description in. (mm) in. (mm) 42kW (12 Tons)
W1 Water/Glycol/GLYCOOL Access (Bottom) 79-15/16 (2030) 9 (229) 3-1/2 x 8 (89 x 203)
W2 3 Water/Glycol/GLYCOOL Access (Top) 79-15/16 (2030) 9 (229) 3-1/2 x 8 (89 x 203)
W3 3 Water/Glycol/GLYCOOL Access (Side) — — 6 x 17-3/16 (152 x 437)
WS 3 Water/Glycol/GLYCOOL Supply — — 1-5/8 / 2-1/8 Cu Sweat
WR 3 Water/Glycol/GLYCOOL Return — — 1-5/8 / 2-1/8 Cu Sweat
2
ECS Econ-O-Coil Supply 56 (1423) 7-5/16 (186) 1-5/8 / 2-1/8 Cu Sweat
ECR 2 Econ-O-Coil Return 56 (1423) 4-1/2 (114) 1-5/8 / 2-1/8 Cu Sweat
CGD 1 Condensate Gravity Drain — — 3/4 FPT
CPD Condensate Pump Discharge (Optional) 56-1/4 (1429) 11-1/8 (282) 1/2 Cu Sweat
HUM Humidifier Supply Line 56-1/4 (1429) 9-1/8 (232) 1/4 Cu Sweat
E1 Electrical Connection (High-Voltage) 52-3/8 (1331) 29-15/16 (760) 2-1/2
E2 Electrical Connection (High-Voltage) 47-3/8 (1204) 29-15/16 (760) 2-1/2
LV1 Electrical Connection (Low-Voltage) 8-1/8 (207) 29-9/16 (751) 7/8
LV2 Electrical Connection (Low-Voltage) 8-1/8 (207) 31 (787) 7/8
LV3 Electrical Connection (Low-Voltage) 8-1/8 (207) 32-7/16 (824) 7/8
1. Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on dual cool systems only (four-pipe system).
3. Source: DPN002741, Rev. 1

67 Liebert® DS™
Weights and Dimensions

Figure 48 Dimensions—Upflow, water/glycol/GLYCOOL™, 53-77kW (15-22 tons), all compressor models


with EC fans
Digital scroll compressors
not available on 077 models.

Condenser Cleanout Access Space required for EC fan plenum


(shipped separately) dependent on
height of plenum ordered
33"
(838mm) 5/16" Required for
(8mm) condenser cleanout
35" Bezels
(889mm) 24"
(610mm)

1-3/4" TOP VIEW


Alternate Refrigerant
Piping Entrance Low-Voltage
(44mm)
High-Voltage Connection(s) Handle Connection(s)
3-1/4"
(83mm) 109" (2769mm)

76"
(1930mm)
36"
Shaded area indicates a (914mm)
recommended minimum
clearance from floor to top
of unit for component access.

2" 108" (2743mm)


(50mm)
FRONT VIEW
NOTES
1. Front air return unit shown. For rear return unit, in addition to front service
area shown, also include 25" (635mm) on one side of unit for access to rear
return filter box. See DPN001196.
2. EC fans plenum is not shown. EC fans and plenum are shipped separately. DPN003499
See DPN002748 for unit dimensions with EC fans plenum mounted Rev. 0

Liebert® DS™ 68
Weights and Dimensions

Figure 49 Primary connection locations—Upflow, water/glycol/GLYCOOL™, 53-77kW (15-22 tons), all


compressor models with EC fans
All dimensions from
rear corner of unit X O
including panels

ECR
ECS
W1, W2 HUM
8" CPD
NOTES (203mm) 3.
35" 4.
1. Drawing not to scale.
2. Tolerance on all piping (889mm) 2-7/8"
dimensions
Y
(73mm)
is ±1/2" (13mm). E1 E2 LV1
3-1/2" LV2
3. Field-routed alternatives for (89mm) LV3
water/glycol connections.
4. See submittal page DPN002748 109" (2769mm)
TOP VIEW OF UNIT Front of Unit
for plenum dimensions.

6" (152mm)

W3
WS
17-3/16" WR
(437mm) 3. CGD*

3-7/8" 14-1/4" CGD*


(98mm) (362mm) FRONT SECTION VIEW OF UNIT
(Left Front Panel Not Shown)
15-7/8"
(403mm) DPN002744
LEFT SIDE SECTION VIEW OF UNIT
Rev. 0
* Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed
condensate trap. Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system
materials. The drain line must comply with all local codes. Supplied on dual cool systems only.
** Supplied on dual cool systems only.
Table 31 Piping data—Upflow, water/glycol/GLYCOOL, 53-77kW (15-22 tons), EC fans, all compressor
models
X Y Connection Size / Opening
Point Description in. (mm) in. (mm) in. (mm)
W1 3 Water/Glycol/GLYCOOL Access (Bottom) 102-15/16 (2615) 9 (229) 3-1/2 x 8 (89 x 203)
W2 3 Water/Glycol/GLYCOOL Access (Top) 102-15/16 (2615) 9 (229) 3-1/2 x 8 (89 x 203)
W3 3 Water/Glycol/GLYCOOL Access (Side) — — 6 X 17-3/16 (152 x 437)
WS 3 Water/Glycol/GLYCOOL Supply — — 2-1/8 Cu Sweat
WR 3 Water/Glycol/GLYCOOL Return — — 2-1/8 Cu Sweat
1
CGD Condensate Gravity Drain — — 3/4 Fpt
CPD Condensate Pump Discharge (Optional) 79-5/16 (2015) 11-7/8 (302) 1/2 Cu Sweat
HUM Humidifier Supply Line 79-5/16 (2015) 9-7/8 (251) 1/4 Cu Sweat
ECS 2 Econ-O-Coil Supply 78-5/8 (1998) 7-7/8 (200) 2-1/8 Cu Sweat
2
ECR Econ-O-Coil Return 78-5/8 (1998) 4-5/8 (117) 2-1/8 Cu Sweat
E1 Electrical Connection (High-Voltage) 78-1/8 (1984) 30 (762) 2-1/2
E2 Electrical Connection (High-Voltage) 74-3/8 (1889) 30 (762) 2-1/2
LV1 Electrical Connection (Low-Voltage) 2-5/8 (66) 28-9/16 (726) 7/8
LV2 Electrical Connection (Low-Voltage) 2-5/8 (66) 30 (762) 7/8
LV3 Electrical Connection (Low-Voltage) 2-5/8 (66) 31-7/16 (799) 7/8
1. Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on dual cool systems only.
3. Source: DPN002744, Rev. 0

69 Liebert® DS™
Weights and Dimensions

Figure 50 Cabinet and floor planning dimensions—Upflow, water/glycol/GLYCOOL™,105kW (30 tons), all
compressor models, with EC fans

Alternate Refrigeration Digital scroll compressors


Piping Entrance not available on 105 models.

Space required for EC Fan Plenum


33" 5/16" (shipped separately) dependent on
(838mm) (8mm) height of plenum ordered
34-3/4" Bezel
(883mm) Required for
24" condenser cleanout
Alternate Condenser Low-Voltage (610mm)
1-3/4" TOP VIEW
Fluid Piping Entrance Connection(s)
(44mm)
High-Voltage
Handle
Connection(s)
3-3/16"
(81mm) 132-1/16" (3354mm)
Typical

76"
(1931mm)

34"
(864mm)

Shaded area indicates a


130-15/16" (3325mm) recommended minimum
1-15/16" clearance from floor to top
(50mm) FRONT VIEW
of unit and plenum for component
NOTES access.
1. Front air return unit shown. For rear return unit, in addition to front
service area shown, also include 25" (635mm) on one side of unit
for access to rear return filter box. See DPN001196. DPN003501
2. EC fans plenum not shown. EC fans and plenum shipped separately.
See DPN002749 for plenum dimensions. Rev. 0

Liebert® DS™ 70
Weights and Dimensions

Figure 51 Primary connection locations—Upflow, water/glycol/GLYCOOL™, 105kW (30 tons), all


compressor models with EC fans
All dimensions from
rear corner of unit
including panels X O
ECR
W1, W2 3. ECS
8" HUM
35" (203mm) CPD
NOTES (889mm) 4.
1. Drawing not to scale. 2-7/8"
2. Tolerance on all piping (73mm) E1
dimensions is ±1/2" (13mm). 3-1/2" LV1 LV3
Y
E2 LV2
(89mm) LV4
3. Field-routed alternatives for
water/glycol connections. 132" (3353mm)
4. See submittal page DPN002746 for Front of Unit
plenums dimensions. TOP VIEW OF UNIT
6" (152mm)

W3
17-3/16" WS
WR
(437mm) 3.
CGD*

3-7/8" 14-1/4"
CGD* FRONT SECTION VIEW OF UNIT DPN002746
(98mm) (362mm)
15-7/8" (Left Front Panel Not Shown) Rev. 0
(403mm)

LEFT SIDE SECTION VIEW OF UNIT


Table 32 Piping data—Upflow, water/glycol/GLYCOOL, 105kW (30 tons), EC fans, all compressor models
Point Description X Y Connection Size / Opening
W1 3 Water/Glycol/GLYCOOL Access (Bottom) 126-1/8 (3204) 9 (229) 3-1/2 x 8 (89 x 203)
W2 3 Water/Glycol/GLYCOOL Access (Top) 126-1/8 (3204) 9 (229) 3-1/2 x 8 (89 x 203)
W3 3 Water/Glycol/GLYCOOL Access (Side) — — 6 x 17-3/16 (152 x 437)
WS 3 Water/Glycol/GLYCOOL Supply — — 2-1/8 Cu Sweat
WR 3 Water/Glycol/GLYCOOL Return — — 2-1/8 Cu Sweat
CGD 1 Condensate Gravity Drain — — 3/4 FPT
CPD Condensate Pump Discharge (Opt) 102-3/8 (2600) 13-5/8 (346) 1/2 Cu Sweat
HUM Humidifier Supply Line 101-1/8 (2569) 13-1/8 (333) 1/4 Cu Sweat
2
ECS Econ-O-Coil Supply 101-1/8 (2569) 10-1/4 (260) 2-5/8 Cu Sweat
ECR 2 Econ-O-Coil Return 101-1/8 (2569) 5-1/4 (133) 2-5/8 Cu Sweat
E1 Electrical Connection (High-Voltage) 101-5/8 (2581) 30 (762) 2-1/2
E2 Electrical Connection (High-Voltage) 97-7/8 (2486) 30 (762) 2-1/2
LV1 Electrical Connection (Low-Voltage) 34-1/8 (867) 30-1/4 (769) 7/8
LV2 Electrical Connection (Low-Voltage) 34-1/8 (867) 31-3/4 (807) 7/8
LV3 Electrical Connection (Low-Voltage) 32-5/8 (829) 28-15/16 (734) 7/8
LV4 Electrical Connection (Low-Voltage) 32-5/8 (829) 30-7/16 (772) 7/8
1. Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on dual cool systems only.
3. Source: DPN002746, Rev. 0

71 Liebert® DS™
Weights and Dimensions

7.7 Upflow Model Dimensions and Primary Connections—Air-Cooled Systems with


Forward-Curved Blowers
Figure 52 Dimensions—Upflow, air-cooled, 28-42kW (8-12 tons), scroll or digital scroll compressor
models with forward-curved blowers

Alternate Refrigerant
Piping Entrance

33"
(838mm) 5/16"
35" (8mm)
(889mm) Bezel
Minimum required
for blower replacement

1-3/4"
High-Voltage (44mm) TOP Low-Voltage
Connection(s) Handle VIEW Connection(s)
1-1/2" 73" (1854mm) 24"
(38mm) (610mm)

76"
(1930mm)
34"
(864mm)

Shaded area indicates a


required minimum clearance from floor
to top of unit and plenum for component
access.

72" (1829mm)
2"
(51mm) FRONT VIEW
Front air return unit shown. For rear return unit, in addition to front service
area shown, also include 25" (635mm) on one side of unit for access to rear DPN003154
return filter box. See DPN001196. Rev. 1

Liebert® DS™ 72
Weights and Dimensions

Figure 53 Primary connection locations—Upflow air-cooled 28-42kW (8-12 tons) scroll compressor
models with foward-curved blowers
All dimensions from rear corner
10-1/8"
of unit including panels X O
(257mm)

1. Drawing not to scale. R1 ECR


4-1/8" (105mm) 3.
2. Tolerance on all piping dimensions ECS
BLOWER
HUM
is ± 1/2" (13mm). CPD OUTLET
3. Field-routed alternatives for refrigerant R2
4.
gas and liquid line connection points. L1 L2 G1 G2
4" (102mm)
4. Unit with forward-curved blower shown. Y
See submittal page DPN001120 for 35"
11-1/8"
blower outlet and deck dimensions. (889mm)
3. (283mm)
LV1
LV2
E1 E2 LV3

73" (1854mm)
6" TOP VIEW Front
(152mm) R3

17-3/16" 3.
(437mm) 17-1/16" L1 L2 G1 G2
CGD* (434mm)

3-7/8" 14-1/4"
(98mm) (362mm)
15-7/8" CGD* Factory Location
(403mm)
FRONT SECTION DPN001119
LEFT SIDE SECTION (Left Front Panel Not Shown) Rev. 3
Table 33 Piping data—Upflow, air-cooled 28-42kW (8-12 tons) scroll compressors
X Y Connection Size / Opening
Point Description in. (mm) in. (mm) in. (mm)
R1 3 Refrigerant Access (Top) 60-5/8 (1539) 2-13/16 (71) 10-1/8 x 4-1/8 (257 105)
R2 3 Refrigerant Access (Bottom) 63 (1600) 13-13/16 (351) 16-7/16 x 4 (418 x 102)
L1 Liquid Line System 1 79-3/16 (2011) 16-3/4 (425) 1/2" Cu Sweat
L2 Liquid Line System 2 76-1/2 (1943) 16-3/4 (425) 1/2" Cu Sweat
G1 Hot Gas Discharge 1 73-7/8 (1876) 16-5/8 (422) 5/8" Cu Sweat
G2 Hot Gas Discharge 2 70-1/8 (1780) 16-5/8 (422) 5/8" Cu Sweat
R3 3 Refrigerant Access (Side) — — 6 x 17-3/16 (152 x 437)
CGD* Condensate Gravity Drain — — 3/4" FPT
CPD Condensate Pump Discharge (Optional) 56-1/4 (1429) 11-1/8 (283) 1/2" Cu Sweat
HUM Humidifier Supply Line 56-1/4 (1429) 9-1/8 (233) 1/4" Cu Sweat
2
ECS * Econ-O-Coil Supply 56 (1423) 7-5/16 (186) 1-5/8" Cu Sweat
ECR 2* Econ-O-Coil Return 56 (1423) 4-1/2 (114) 1-5/8" Cu Sweat
E1 Electrical Connection (High Voltage) 52-3/8 (1330) 30 (762) 2-1/2"
E2 Electrical Connection (High Voltage) 46-7/8 (1191) 30 (762) 2-1/2"
LV1 Electrical Connection (Low Voltage) 19-1/2 (495) 29-1/16 (738) 7/8"
LV2 Electrical Connection (Low Voltage) 19-1/2 (495) 30-1/2 (775) 7/8"
LV3 Electrical Connection (Low Voltage) 19-1/2 (495) 31-15/16 (811) 7/8"
1. Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on dual cool systems only.
3. Source: DPN001119, Rev. 3

73 Liebert® DS™
Weights and Dimensions

Figure 54 Cabinet and floor planning dimensions—Upflow, air-cooled 28-42kW (8-12 tons) semi-hermetic
compressor models with forward-curved blowers

Alternate Refrigerant
Piping Entrance

33"
(838mm)
5/16"
35" (8mm)
(889mm) Minimum required
Bezel
for blower replacement

1-3/4"
High-Voltage
TOP (44mm) Low-Voltage
Connection(s)
VIEW Handle Connection(s)

1-1/2" 86" (2184mm) 24"


(38mm) (610mm)

76"
(1930mm)
34"
(864mm)

Shaded area indicates a


required minimum clearance from floor
to top of unit and plenum for component
access.

85" (2159mm)
2" FRONT VIEW
(51mm) DPN003153
Front air return unit shown. For rear return unit, in addition to front service Rev. 1
area shown, also include 25" (635mm) on one side of unit for access to rear
return filter box. See DPN001196.

Liebert® DS™ 74
Weights and Dimensions

Figure 55 Primary connection locations—Upflow, air-cooled, 28-42kW (8-12 tons), semi-hermetic


compressor models with forward-curved blowers

All dimensions from


NOTES: 22-1/2" rear corner of unit
1. Drawing not to scale. (572mm) including panels X
0
2. Tolerance on all piping dimensions ECR
is ± 1/2" (13mm). ECS Blower
15-3/16" 3 R2 HUM Outlet
3 Field-routed alternatives for refrigerant 35" (386mm) CPD
gas and liquid line connection points. 4
(889mm)
4 Forwad-curved blower shown. See L1 L2 G1 G2
submittal page DPN001120 for 4"
blower outlet and deck dimensions. (102mm) 16-7/16" Y
3
(418mm)
LV1
LV2
E1 E2 LV3

86" (2184mm)
TOP VIEW Front of Unit

6"
(152mm)
R3

17-3/16" 3 G1 G2
(437mm) 20-1/16" L1 L2
(509mm)
CGD *

14-1/4"
3-7/8" (362mm)
(98mm) CGD *
15-7/8" Factory Location
DPN001114
(403mm) FRONT SECTION VIEW Rev. 3
LEFT SIDE SECTION VIEW (Left Front Panel Not Shown)
Table 34 Piping data—Upflow, air-cooled, 28-42kW (8-12 tons), semi-hermetic compressors
X Y Connection Size / Opening
Point Description in. (mm) in. (mm) in. (mm)
R1 3 Refrigerant Access (Top) 60-11/16 (1542) 1-7/8 (48) 22-1/2 x 15-3/16 (572 x 386)
R2 3 Refrigerant Access (Bottom) 63 (1600) 13-13/16 (351) 16-7/16 x 4 (418 x 102)
L1 Liquid Line System 1 79-3/16 (2011) 16-3/4 (425) 1/2" Cu Sweat
L2 Liquid Line System 2 76-1/2 (1943) 16-3/4 (425) 1/2" Cu Sweat
G1 Hot Gas Discharge 1 73-7/8 (1876) 16-3/4 (425) 5/8" Cu Sweat
G2 Hot Gas Discharge 2 70-1/8 (1780) 16-3/4 (425) 5/8" Cu Sweat
R3 3 Refrigerant Access (Side) — — 6 x 17-3/16 (152 x 437)
CGD 1 Condensate Gravity Drain — — 3/4" FPT
CPD Condensate Pump Discharge (Opt) 56-1/4 (1429) 11-1/8 (283) 1/2" Cu Sweat
HUM Humidifier Supply Line 56-1/4 (1429) 9-1/8 (233) 1/4" Cu Sweat
ECS 2 Econ-O-Coil Supply 56 (1423) 7-5/16 (186) 1-5/8" Cu Sweat
ECR 2 Econ-O-Coil Return 56 (1423) 4-1/2 (114) 1-5/8" Cu Sweat
E1 Electrical Conn. (High-Voltage) 52-3/8 (1330) 30 (762mm) 2-1/2"
E2 Electrical Conn. (High-Voltage) 46-7/8 (1191) 30 (762mm) 2-1/2"
LV1 Electrical Conn. (Low-Voltage) 19-1/2 (495) 29-1/16 (738) 7/8"
LV2 Electrical Conn. (Low-Voltage) 19-1/2 (495) 30-1/2 (775) 7/8"
LV3 Electrical Conn. (Low-Voltage) 19-1/2 (495) 31-15/16 (811) 7/8"
1. Field-pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on Dual-Cool systems only (four-pipe system).
3. Piping dimensions shown are connection sizes; field piping sizes may be different, depending on distance. Refer to user manual,
SL-18825.
4. Source: DPN001114, Rev. 3

75 Liebert® DS™
Weights and Dimensions

Figure 56 Cabinet and floor planning dimensions—Upflow, air-cooled, 53-77kW (15-22 tons), scroll or
digital scroll compressors with forward-curved blowers
Alternate Refrigerant
Piping Entrance
Digital scroll compressors
not available on 077 models.
33"
(838mm) 5/16"
35" (8mm)
(889mm) Bezel Minimum required
for blower replacement
1-3/4"
High-Voltage (44mm) Low-Voltage
Connection(s) Handle Connection(s)
TOP VIEW
1-1/2" 98" (2489mm)
(38mm) 24"
(610mm)

76"
(1930mm)

34"
(864mm)

Shaded area indicates a


required minimum clearance from floor
to top of unit and plenum for component
access.
2" 97" (2464mm)
(51mm)
FRONT VIEW
Front air return unit shown. For rear return unit, in addition to front service
area shown, also include 25" (635mm) on one side of unit for access to rear DPN003157
return filter box. See DPN001196. Rev. 1

Liebert® DS™ 76
Weights and Dimensions

Figure 57 Primary connection locations—Upflow, air-cooled, 53-77kW (15-22 tons), scroll compressor
models with forward-curved blowers
Digital scroll compressors not
available on VS 077. All dimensions from
NOTES: rear corner of unit
12" (305mm)
1. Drawing not to scale. including panels
2. Tolerance on all piping dimensions
is ± 1/2" (13mm). Blower Blower
4" Outlet Outlet
3. Field-routed alternatives for refrigerant (102mm)
gas and liquid line connection points.
35" 4"
4. Forward-curved blowers shown. See (102mm)
submittal page DPN001191 for (889mm)
blower outlet and deck dimensions.
12-13/16"
(325mm)
6" (152mm) 98" (2489mm)
Front of Unit
TOP VIEW OF UNIT

17-3/16"
(437mm)
CGD *

3-7/8" 14-1/4" 17-1/16"


(98mm) (362mm) (433mm)
15-7/8"
(403mm)
Factory FRONT SECTION VIEW OF UNIT DPN001213
LEFT SIDE SECTION VIEW OF UNIT CGD * Location Rev. 2
(Left Front Panel Not Shown)

Table 35 Piping data—Upflow, air-cooled, 53-77kw (15-22 tons), scroll compressor models 3
X Y Connection Size / Opening
Point Description in. (mm) in. (mm) in. (mm)
R1 3 Refrigerant Access (Top) 83-5/8 (2124) 2 (51) 12 x 4 (305 x 102)
R2 3 Refrigerant Access (Bottom) 82-3/4 (2102) 14-3/4 (374) 12-3/16 x 4 (310 x 102)
53kW (15 tons) / 70 & 77kW (20 & 22 tons)
L1 Liquid Line System 1 94-11/16 (2405) 16-3/4 (425) 1/2 / 5/8 Cu Sweat
L2 Liquid Line System 2 91-7/8 (2334) 16-3/4 (425) 1/2 / 5/8 Cu Sweat
G1 Hot Gas Discharge 1 88-3/4 (2254) 16-3/8 (416) 7/8 / 1-1/8 Cu Sweat
G2 Hot Gas Discharge 2 85-9/16 (2173) 16-3/8 (416) 7/8 / 1-1/8 Cu Sweat
R3 3 Refrigerant Access (Side) — — 6 x 17-3/16 (152 x 437)
1
CGD Condensate Gravity Drain — — 3/4 FPT
CPD Condensate Pump Discharge (Opt) 79-5/16 (2015) 11-7/8 (302) 1/2 Cu Sweat
HUM Humidifier Supply Line 79-5-16 (2015) 9-7/8 (251) 1/4 Cu Sweat
2
ECS Econ-O-Coil Supply 78-5/8 (1998) 7-7/8 (200) 2-1/8 Cu Sweat
2
ECR Econ-O-Coil Return 78-5/8 (1998) 4-5/8 (117) 2-1/8 Cu Sweat
E1 Electrical Connection (High-Voltage) 75-3/8 (1915) 30 (762) 2-1/2
E2 Electrical Connection (High-Voltage) 69-7/8 (1775) 30 (762) 2-1/2
LV1 Electrical Connection (Low-Voltage) 19-1/2 (495) 29-1/16 (738) 7/8
LV2 Electrical Connection (Low-Voltage) 19-1/2 (495) 30-1/2 (775) 7/8
LV3 Electrical Connection (Low-Voltage) 19-1/2 (495) 31-15/16 (811) 7/8
1. Field-pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on dual-cool systems only.
3. Digital scroll compressors not available on 077 models.
4. Piping dimensions shown are connection sizes; field piping sizes may be different depending, on distance. Refer to user manual,
SL-18825.
5. Source: DPN001213, Rev. 2

77 Liebert® DS™
Weights and Dimensions

Figure 58 Cabinet and floor plannning dimensions—Upflow air-cooled 53-77kw (15-22 tons)
semi-hermetic compressor models with forward curved blowers

Alternate Refrigerant
Piping Entrance

33"
(838mm) 5/16"
(8mm)
35"
Bezel
(889mm)
Minimum required
High-Voltage 1-3/4" for blower replacement
Connection(s) (44mm) TOP Low-Voltage
Handle VIEW Connection(s)

1-1/2" 109" (2769mm)


(38mm)

24"
(610mm)

76"
(1930mm)

34"
(864mm)

Shaded area indicates a


2" 108" (2743mm) required minimum clearance from floor
(51mm) to top of unit and plenum for component
FRONT VIEW access.
Front air return unit shown. For rear return unit, in addition to front service
DPN003156
area shown, also include 25" (635mm) on one side of unit for access to rear
Rev. 1
return filter box. See DPN001196.

Liebert® DS™ 78
Weights and Dimensions

Figure 59 Primary connection locations—Upflow, air-cooled 53-77kW (15-22 tons), semi-hermetic


compressor models with forward-curved blowers
All dimensions from
22-1/2"
NOTES: rear corner of unit X O
(572mm)
1. Drawing not to scale. including panels
2. Tolerance on all piping dimensions Blower Blower
is ± 1/2" (13mm). 15-3/16" Outlet Outlet
3. Field-routed alternatives for refrigerant 35" (386mm)
gas and liquid line connection points. (889mm)
4. Forward-curved fans shown. See 4"
(102mm) 16-7/16"
submittal page DPN001191 for Y
(418mm)
blower outlet and deck dimensions.

6" 109" (2769mm)


(152mm) TOP VIEW OF UNIT Front of Unit

17-3/16"
(437mm)
20-1/16"
14-1/4" (509mm)
3-7/8"
(362mm)
(98mm)
15-7/8"
(403mm) CGD * Factory Location
LEFT SIDE SECTION VIEW OF UNIT FRONT SECTION VIEW OF UNIT DPN001212
(Left Front Panel Not Shown) Rev. 3
Table 36 Piping data—Upflow, air-cooled, 53-77kW (15-22 tons), semi-hermetic compressors
X Y Connection Size / Opening
Point Description in. (mm) in. (mm) in. (mm)
R1 3 Refrigerant Access (Top) 83-3/4 (2127) 1-7/8 (48) 22-1/2 x 15-3/16 (572 x 386)
R2 3 Refrigerant Access (Bottom) 86 (2184) 13-7/8 (352) 16-7/16 x4 (418 x102)
53kW (15 tons) / 70 & 77kW (20 & 22 tons)
L1 Liquid Line System 1 97 (2464) 16-3/4 (425) 1/2" / 5/8 Cu Sweat
L2 Liquid Line System 2 93-5/16 (2370) 16-3/4 (425) 1/2" / 5/8" Cu Sweat
G1 Hot Gas Discharge 1 90-5/8 (2302) 16-5/8 (422) 7/8" / 1-1/8" Cu Sweat
G2 Hot Gas Discharge 2 88 (2235) 16-5/8 (422) 7/8" / 1-1/8" Cu Sweat
R3 3 Refrigerant Access (Side) — — 6 x 17-3/16 (152 x 437)
CGD 1 Condensate Gravity Drain — — 3/4" FPT
CPD Condensate Pump Discharge (Opt) 79-5/16 (2015) 11-7/8 (302) 1/2" Cu Sweat
HUM Humidifier Supply Line 79-5/16 (2015) 9-7/8 (251) 1/4" Cu Sweat
ECS 2 Econ-O-Coil Supply 78-5/8 (1998) 7-7/8 (200) 2-1/8" Cu Sweat
ECR 2 Econ-O-Coil Return 78-5/8 (1998) 4-5/8 (117) 2-1/8" Cu Sweat
E1 Electrical Connection (High-Voltage) 75-3/8 (1915) 30 (762) 2-1/2"
E2 Electrical Connection (High-Voltage) 69-7/8 (1775) 30 (762) 2-1/2"
LV1 Electrical Connection (Low-Voltage) 19-1/2 (495) 29-1/16 (738) 7/8"
LV2 Electrical Connection (Low-Voltage) 19-1/2 (495) 30-1/2 (775) 7/8"
LV3 Electrical Conn. (Low-Voltage) 19-1/2 (495) 31-15/16 (811) 7/8"
1. Field-pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on dual-cool systems only.
3. Piping dimensions shown are connection sizes; field piping sizes may be different, depending on distance. Refer to user manual,
SL-18825.
4. Source: DPN001212, Rev. 3

79 Liebert® DS™
Weights and Dimensions

Figure 60 Cabinet and floor planning dimensions—Upflow, air-cooled, 105kW (30 tons), all compressor
models with forward-curved blowers

Alternate Refrigerant
Piping Entrance

33"
(838mm)
35"
(889mm) 5/16"
(8mm)
1-3/4" Bezel Minimum required
High-Voltage (44mm) Low-Voltage for blower replacement
Connection(s) TOP VIEW Handle Connection(s)

1-1/2" 132" (3353mm)


(38mm)

24"
(610mm)

76"
(1930mm)

34"
(864mm)
2" 131" (3327mm)
Shaded area indicates a
(51mm) FRONT VIEW required minimum clearance from floor
to top of unit and plenum for component
Front air return unit shown. For rear return unit, in addition to front service access.
area shown, also include 25" (635mm) on one side of unit for access to rear
DPN003159
return filter box. See DPN001196.
Rev. 1

Liebert® DS™ 80
Weights and Dimensions

Figure 61 Primary connection locations—Upflow, air-cooled, 105kW (30 tons), semi-hermetic and scroll
compressor models with forward-curved blowers
Digital scroll compressors not All dimensions from
available on 105 models. 22-1/2" rear corner of unit
X O
(572mm) including panels

ECR
15-3/16" ECS Blower Blower Blower
R2 HUM Outlet
(386mm) CPD Outlet Outlet
35"
(889mm)

NOTES: 4" 16-7/16"


1. Drawing not to scale. (102mm) (418mm) LV1 LV3 Y
2. Tolerance on all piping dimensions E1 E2 LV2 LV4
is ± 1/2" (13mm).
3. Field-routed alternatives for refrigerant 132" (3353mm)
gas and liquid line connection points. Front Of Unit
4. Forward-curved fans shown. See submittal TOP VIEW
page DPN001192 for blower outlet and
deck dimensions.
5. EC fans are field-installed in plenum.
6"
(152mm)

R3
G2
17-3/16" 20-1/16" L1 L2G1
(437mm) (509mm)
CGD*

3-7/8" 14-1/4"
(98mm) CGD*
(362mm)
Factory Location
15-7/8"
(403mm) FRONT SECTION VIEW DPN001257
LEFT SIDE SECTION VIEW (Left Front Panel Not Shown)
Rev. 1

Table 37 Piping data—Upflow, air-cooled 105kW (30 tons), semi-hermetic and scroll compressors 3
Point Description X, in. (mm) Y, in. (mm) Connection Size / Opening
R1 3 Refrigerant Access (Top) 106-7/8 (2715) 1-7/8 (48) 22-1/2 x 15-3/16 (572 x 386)
R2 3 Refrigerant Access (Bottom) 109-1/8 (2772) 13-7/8 (352) 16-7/16 x 4 (418 x 102)
L1 Liquid Line System 1 121-3/4 (3092) 16-3/4 (425) 5/8" Cu Sweat
L2 Liquid Line System 2 118-1/8 (3000) 16-3/4 (425) 5/8" Cu Sweat
G1 Hot Gas Discharge 1 118-1/4 (3004) 14-1/4 (362) 1-1/8" Cu Sweat
G2 Hot Gas Discharge 2 115-5/8 (2937) 14-1/4 (362) 1-1/8" Cu Sweat
R3 3 Refrigerant Access (Side) — — 6 x 17-3/16 (152 x 437)
CGD* Condensate Gravity Drain — — 3/4" FPT
CPD Condensate Pump Discharge (Opt) 102-3/8 (2600) 13-5/8 (346) 1/2" Cu Sweat
HUM Humidifier Supply Line 101-1/8 (2569) 13-1/8 (333) 1/4" Cu Sweat
ECS 2 Econ-O-Coil Supply 101-1/8 (2569) 10-1/4 (260) 2-5/8" Cu Sweat
ECR 2 Econ-O-Coil Return 101-1/8 (2569) 5-1/4 (133) 2-5/8" Cu Sweat
E1 Electrical Connection (High-Voltage) 98-1/2 (2502) 30 (762) 2-1/2"
E2 Electrical Connection (High-Voltage) 93 (2362) 30 (762) 2-1/2"
LV1 Electrical Connection (Low-Voltage) 41-1/8 (1045) 30-3/8 (772) 7/8"
LV2 Electrical Connection (Low-Voltage) 38-7/8 (987) 30-3/8 (772) 7/8"
LV3 Electrical Connection (Low-Voltage) 35-1/8 (892) 30-3/8 (772) 7/8"
LV4 Electrical Connection (Low-Voltage) 31-5/8 (803) 30-3/8 (772) 7/8"
1. Field-pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on dual-cool systems only.
3. Digital scroll compressors not available on VS105
4. Piping dimensions shown are connection sizes; field piping sizes may be different, depending on distance. Refer to user manual,
SL-18825.
5. Source: DPN001257, Rev. 1

81 Liebert® DS™
Weights and Dimensions

7.8 Upflow Model Dimensions and Primary Connections—Water/Glycol/GLYCOOL™


Systems
Figure 62 Cabinet and floor planning dimensions—Upflow, water/glycol/GLYCOOL, 28-42kW (8-12 tons),
all compressor models with forward-curved blowers

Condenser Cleanout Access

33"
(838mm) 5/16"
(8mm)
35" Bezel Required for
(889mm) condenser cleanout
Minimum required
for blower replacement
Alternate Condenser Fluid 1-3/4"
Piping Entra (44mm) Low-Voltage
High-Voltage Handle Connection(s)
Connection(s) TOP VIEW
1-1/2" 86" (2184mm) 24"
(38mm) (610mm)

76"
(1930mm)
34"
(864mm)

Shaded area indicates a


required minimum clearance from floor
to top of unit and plenum for component
access.

85" (2159mm)
2"
(51mm) FRONT VIEW
Front air return unit shown. For rear return unit, in addition to front service DPN003155
area shown, also include 25" (635mm) on one side of unit for access to rear Rev. 1
return filter box. See DPN001196.

Liebert® DS™ 82
Weights and Dimensions

Figure 63 Primary connection locations—Upflow water/glycol/GLYCOOL™ 28-42kW (8-12 tons) all


compressor models with forward-curved blowers
1. Drawing not to scale.
2. Tolerance on all piping dimensions is ± 1/2" (13mm). All dimensions from rear corner
of unit including panels
3. Field routed alternatives for water/glycol connections.
X O
4. Unit with forward-curved fan
shown.See submittal page
ECS
ECR
Blower
DPN001120 for blower
W1, W2 3 HUM
CPD
Outlet
outlet and deck dimensions. 8" 4
(203mm)
35"
(889mm)
Y
2-7/8"
LV1
(73mm) 3-1/2"
LV2
(89mm) E1 LV3
E2

6" 86" (2184mm)


(152mm) TOP VIEW OF UNIT Front
W3
WS
17-3/16" WR
(437mm) 3
CGD*

3-7/8"
14-1/4"
(98mm)
(362mm)
DPN001179
15-7/8"
(403mm) Rev. 6
CGD* FRONT SECTION VIEW OF UNIT
LEFT SIDE SECTION VIEW OF UNIT (Left Front Panel Not Shown)
Table 38 Piping data—Water/glycol/GLYCOOL, 28-42kW (8-12 tons), upflow, all compressors
Connection Size / Opening
in. (mm)
X Y 28-35kW (8-10 Ton) /
Point Description in. (mm) in. (mm) 42kW (12 Ton)
W1 3 Water/Glycol/GLYCOOL Access (Bottom) 79-15/16 (2030) 9 (229) 3-1/2 x 8 (89 x 203)
W2 3 Water/Glycol/GLYCOOL Access (Top) 79-15/16 (2030) 9 (229) 3-1/2 x 8 (89 x 203)
W3 3 Water/Glycol/GLYCOOL Access (Side) — — 6 x 17-3/16 (152 x 437)
WS 3 Water/Glycol/GLYCOOL Supply — — 1-5/8" / 2-18" Cu Sweat
WR 3 Water/Glycol/GLYCOOL Return — — 1-5/8" / 2-18" Cu Sweat
ECS 2 Econ-O-Coil Supply 56 (1423) 7-5/16 (186) 1-5/8" / 2-18" Cu Sweat
2
ECR Econ-O-Coil Return 56 (1423) 4-1/2 (114) 1-5/8" / 2-18" Cu Sweat
CGD 1 Condensate Gravity Drain — — 3/4" FPT
CPD Condensate Pump Discharge (Opt) 56-1/4 (1429) 11-1/8 (282) 1/2" Cu Sweat
HUM Humidifier Supply Line 56-1/4 (1429) 9-1/8 (232) 1/4" Cu Sweat
E1 Electrical Connection (High-Voltage) 52-3/8 (1330) 30 (762) 2-1/2"
E2 Electrical Connection (High-Voltage) 46-7/8 (1191) 30 (762) 2-1/2"
LV1 Electrical Connection (Low-Voltage) 19-1/2 (495) 29-1/16 (738) 7/8"
LV2 Electrical Connection (Low-Voltage) 19-1/2 (495) 30-1/2 (775) 7/8"
LV3 Electrical Connection (Low-Voltage) 19-1/2 (495) 31-15/16 (811) 7/8"
1. Field-pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on dual-cool systems only (four-pipe system).
3. Piping dimensions shown are connection sizes; field piping sizes may be different, depending on distance. Refer to user manual,
SL-18825.
4. Source: DPN001179, Rev. 6

83 Liebert® DS™
Weights and Dimensions

Figure 64 Cabinet and floor planning dimensions—Upflow, water/glycol-cooled, 53-77kW (15-22 tons), all
compressor models with forward-curved blowers

Condenser Cleanout Access

33"
(838mm) 5/16"
(8mm) Required for
35" Bezel condenser cleanout
(889mm)
Minimum required
Alternate Condenser Fluid 1-3/4" for blower replacement
(44mm) Low-Voltage
Piping Entra
High-Voltage Handle Connection(s)
Connection(s) TOP VIEW
1-1/2" 109" (2769mm)
(38mm)
24"
(610mm)

76"
(1930mm)

34"
(864mm)
Shaded area indicates a
required minimum clearance from floor
to top of unit and plenum for component
2" 108" (2743mm) access.
(51mm)
FRONT VIEW
Front air return unit shown. For rear return unit, in addition to front service
area shown, also include 25" (635mm) on one side of unit for access to rear DPN003158
return filter box. See DPN001196. Rev. 1

Liebert® DS™ 84
Weights and Dimensions

Figure 65 Primary connection locations—Upflow water/glycol/GLYCOOL™ 53-77kW (15-22 tons) all


compressor models with forward-curved blowers

1. Drawing not to scale.


2. Tolerance on all piping dimensions is ± 1/2" (13mm).
3. Field-routed alternatives for GLYCOOL connections.
4. See submittal page DPN001191 for blower outlet and deck
dimensional data. All dimensions from
rear corner of unit X O
including panels
ECR
W1, W2 ECS
BLOWER BLOWER
8" HUM OUTLET OUTLET
CPD
(203mm) 3. 4. 4.
35"
(889mm) 2-7/8" Y
(73mm)
3-1/2" LV1
LV2
(89mm) E1 E2 LV3

109" (2769mm)
Front
6"
(152mm)
TOP VIEW
W3
WS
17-3/16" WR
(437mm) 3.
CGD*

3-7/8" 14-1/4"
(98mm) (362mm)
15-7/8"
(403mm)
FRONT SECTION VIEW
CGD*
Left Front Panel Not Shown DPN001214
LEFT SIDE SECTION VIEW
Rev. 2
Table 39 Piping data—Water/glycol/GLYCOOL, 53-77kW (15-22 tons), all compressor models
X Y Connection Size / Opening
Point Description in. (mm) in. (mm) in. (mm)
W1 3 Water/Glycol/GLYCOOL Access (Bottom) 102-15/16 (2615) 9 (229) 3-1/2 x 8 (89 x 203)
W2 3 Water/Glycol/GLYCOOL Access (Top) 102-15/16 (2615) 9 (229) 3-1/2 x 8 (89 x 203)
W3 3 Water/Glycol/GLYCOOL Access (Side) — — 6 x 17-3/16 (152 x 437)
WS 3 Water/Glycol/GLYCOOL Supply — — 2-1/8" Cu Sweat
WR 3 Water/Glycol/GLYCOOL Return — — 2-1/8" Cu Sweat
1
CGD Condensate Gravity Drain — — 3/4" FPT
CPD Condensate Pump Discharge (Opt) 78-5/8 (1998) 11-1/8 (282) 1/2" Cu Sweat
HUM Humidifier Supply Line 78-5/8 (1998) 9-7/8 (251) 1/4" Cu Sweat
ECS 2 Econ-O-Coil Supply 79-5/16 (2015) 7-7/8 (200) 2-1/8" Cu Sweat
2
ECR Econ-O-Coil Return 79-5/16 (2015) 4-5/8 (117) 2-1/8" Cu Sweat
E1 Electrical Connection (High-Voltage) 75-3/8 (1915) 30 (762) 2-1/2"
E2 Electrical Connection (High-Voltage) 69-7/8 (1775) 30 (762) 2-1/2"
LV1 Electrical Connection (Low-Voltage) 19-1/2 (495) 29-1/16 (738) 7/8"
LV2 Electrical Connection (Low-Voltage) 19-1/2 (495) 30-1/2 (775) 7/8"
LV3 Electrical Connection (Low-Voltage) 19-1/2 (495) 31-15/16 (811) 7/8"
1. Field-pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate
trap. Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain
line must comply with all local codes.
2. Supplied on dual-cool systems only.
3. Source: DPN001214, Rev. 2

85 Liebert® DS™
Weights and Dimensions

Figure 66 Cabinet and floor planning dimensions—Upflow, water/glycol-cooled, 105kW (30 tons), all
compressor models with forward-curved blowers
Alternate Refrigerant
Piping Entrance

33"
(838mm)
35"
(889mm) 5/16"
Required for
(8mm)
condenser cleanout
Bezel
Alternate Condenser Fluid 1-3/4" Minimum required
Piping Entrance (44mm) Low-Voltage for blower replacement
High-Voltage TOP VIEW Handle Connection(s)
Connection(s)
132" (3353mm)
1-1/2"
(38mm)

24"
(610mm)

76"
(1930mm)

34"
(864mm)
2" 131" (3327mm) Shaded area indicates a
(51mm)
FRONT VIEW required minimum clearance from floor
to top of unit and plenum for component
access.
Front air return unit shown. For rear return unit, in addition to front service
DPN003160
area shown, also include 25" (635mm) on one side of unit for access to rear
Rev. 1
return filter box. See DPN001196.

Liebert® DS™ 86
Weights and Dimensions

Figure 67 Primary connection locations—Upflow water/glycol/GLYCOOL™ 105kW (30 tons) all


compressor models with forward-curved blowers
All dimensions from
rear corner of unit
including panels

Blower Blower Blower


Outlet Outlet Outlet
8"
35" (203mm)
(889mm)
2-7/8"
NOTES: (73mm)
1. Drawing not to scale. LV1 LV3
3-1/2"
2. Tolerance on all piping dimensions (89mm) LV2 LV4
is ± 1/2" (13mm).
3. Field routed alternatives for water/glycol 132"
connections. (3353mm)
Front Of Unit
4. Forward-curved blowers shown.
See submittal page DPN001192 for
blower outlet and deck dimensional data.

TOP VIEW OF UNIT


6"
(152mm)

W3
WS
17-3/16" WR
(437mm)
CGD*

3-7/8" CGD*
(98mm) 14-1/4"
(362mm) FRONT SECTION VIEW OF UNIT
15-7/8" (Left Front Panel Not Shown)
(403mm) DPN001258
Rev. 1
LEFT SIDE SECTION VIEW OF UNIT
Table 40 Piping data—Upflow water/glycol/GLYCOOL, 105kW (30 tons), all compressor models
X Y Connection Size / Opening
Point Description in. (mm) in. (mm) in. (mm)
W1 3 Water/Glycol/GLYCOOL Access (Bottom) 126-1/8 (3204) 9 (229) 3-1/2 x 8 (89 x 203)
W2 3 Water/Glycol/GLYCOOL Access (Top) 126-1/8 (3204) 9 (229) 3-1/2 x 8 (89 x 203)
W3 3 Water/Glycol/GLYCOOL Access (Side) — — 6 x 17-3/16 (152 x 437)
WS 3 Water/Glycol/GLYCOOL Supply — — 2-1/8" Cu Sweat
WR 3 Water/Glycol/GLYCOOL Return — — 2-1/8" Cu Sweat
1
CGD Condensate Gravity Drain — — 3/4" FPT
CPD Condensate Pump Discharge (Opt) 102-3/8 (2600) 13-5/8 (346) 1/2" Cu Sweat
HUM Humidifier Supply Line 101-1/8 (2569) 13-1/8 (333) 1/4" Cu Sweat
ECS 2 Econ-O-Coil Supply 101-1/8 (2569) 10-1/4 (260 2-5/8" Cu Sweat
2
ECR Econ-O-Coil Return 101-1/8 (2569) 5-1/4 (133) 2-5/8" Cu Sweat
E1 Electrical Connection (High-Voltage) 98-1/2 (2502) 30 (762) 2-1/2"
E2 Electrical Connection (High-Voltage) 93 (2362) 30 (762) 2-1/2"
LV1 Electrical Connection (Low-Voltage) 41-1/8 (1045) 30-3/8 (772) 7/8"
LV2 Electrical Connection (Low-Voltage) 38-7/8 (987) 30-3/8 (772) 7/8"
LV3 Electrical Connection (Low-Voltage) 35-1/8 (892) 30-3/8 (772) 7/8"
LV4 Electrical Connection (Low-Voltage) 31-5/8 (803) 30-3/8 (772) 7/8"
1. Field-pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate
trap. Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain
line must comply with all local codes.
2. Supplied on dual-cool systems only.
3. Source: DPN001258, Rev. 1

87 Liebert® DS™
Blower Outlet and Deck Dimensions

8.0 BLOWER OUTLET AND DECK DIMENSIONS

Figure 68 Blower outlet and deck dimensions—Upflow, 28-42kW (8-12 tons) with forward-curved blowers

73" (1854mm) or 86" (2184mm) Ref


Blower Outlet * E C

A
35"
(889mm)
B Ref

Front of Unit
Blower Outlet Location - Top View
* Duct flange not provided
Top of Unit
Blower Deck
D 1-1/2"
(38mm)

76"
(1930mm)
Ref

DPN001120
Front or Rear Throw Air Supply Rev. 3

Dimensional Data in. (mm)


Models Blower Supply A B C D E
Front Throw 15-7/8 (404) 18-5/8 (472) 2-1/8 (54) 25-5/8 (651) 25 (635)
15 x 15
28-42kW Rear Throw 15-7/8 (404) 18-5/8 (472) 11-5/8 (295) 25-5/8 (651) 25 (635)
(8-12 Tons) Front Throw 15-7/8 (404) 14-1/2 (368) 2-1/8 (54) 25-5/8 (651) 25 (635)
15 x 15
Rear Throw 15-7/8 (404) 14-1/2 (368) 11-5/8 (295) 25-5/8 (651) 25 (635)
Source: DPN001120, Rev. 3

Liebert® DS™ 88
Blower Outlet and Deck Dimensions

Figure 69 Blower outlet and deck dimensions—Upflow, 53-77kW (15-22 tons) with forward-curved
blowers
98" (2449mm) or 109" (2769mm)
F
E
Blower Outlets * C

A A
35"
(889mm)
Ref
B B

Blower Outlet Location - Top View


Front of Unit
* Duct flanges not provided.
Top of Unit
Blower Deck
D 1-1/2"
(38mm)

76"
(1930mm)
Ref.

DPN001191
Front or Rear Air Throw Supply Rev. 6
Dimensional Data, in. (mm)
Models Blower Supply A B C D E F
Front Throw 15-7/8 (404) 18-5/8 (472) 2-1/8 (54) 25-5/8 (651) 27-3/4 (705) 55-1/2 (1410)
15 x 15
53-77kW Rear Throw 15-7/8 (404) 18-5/8 (472) 11-5/8 (295) 25-5/8 (651) 27-3/4 (705) 55-1/2 (1410)
(15-22
tons) Front Throw 15-7/8 (404) 14-11/16 (373) 2-1/8 (54) 25-5/8 (651) 31-3/8 (797) 58-7/16 (1484)
15 x 11
Rear Throw 15-7/8 (404) 14-11/16 (373) 11-5/8 (295) 25-5/8 (651) 31-3/8 (797) 58-7/16 (1484)
Source: DPN001191, Rev. 6

89 Liebert® DS™
Blower Outlet and Deck Dimensions

Figure 70 Blower outlet and deck dimensions—Upflow, 105kW (30 tons), forward-curved blowers

132" (3353mm)
G
Blower Outlets * F
E C

A A A
35"
(889mm)
B B B
Ref

BLOWER OUTLET LOCATION - TOP VIEW Front of Unit


* Duct flanges not provided
TOP OF UNIT
Blower Deck
1-1/2"
(38mm)

76"
(1930mm)
Ref

DPN001192
Front or Rear Throw Air Supply Rev. 1

Dimensional Data, in. (mm)


Blower SUPPLY A B C D E F G
Front Throw 15-7/8 (404) 14-11/16 (373) 2-1/8 (54) 25-5/8 (651) 30-3/4 (781) 54-1/2 (1384) 78-1/8 (1984)
15 x 11
Rear Throw 15-7/8 (404) 14-11/16 (373) 11-5/8 (295) 25-5/8 (651) 30-3/4 (781) 54-1/2 (1384) 78-1/8 (1984)
Source: DPN001192, Rev. 1

Liebert® DS™ 90
Blower Outlet and Deck Dimensions

8.1 Disassembly Dimensions—Upflow Air-Cooled Systems


Figure 71 Disassembly dimensions—Upflow, air-cooled, 28-42kW (8-12 tons), scroll compressor models

Blower & Electric


Box Assembly

31-1/4"
(794mm)

Compressor Assembly

76" (1930mm)
Assembled
Filter & Coil Height
Assembly

76"
(1930mm)

45-13/16"
(1163mm)

33" 13" 59" (1499mm)


(838mm) (330mm)
72" (1829mm)
Assembled Length
Drawing views are simplified with panels removed to show overall dimensions. DPN003162
See disassembly and handling instructions in installation manual. Rev. 1

Dry Weight, Approximate, Including Panels, lb (kg)


Component Air-Cooled Dual-Cool
Compressor Assembly 490 (223) 490 (223)
Blower and Electric Box Assembly
510 (231) 510 (231)
Forward-Curved Blowers
EC Fan 1 360 (163) 360 (163)
Filter and Coil Assembly 520 (236) 670 (304)
1. Fan weight not included in this weight. Fan is installed in plenum. See 313221 for plenum weight.
2. Source: DPN003162, Rev. 2

91 Liebert® DS™
Blower Outlet and Deck Dimensions

Figure 72 Disassembly dimensions—Upflow, air-cooled, 28-42kW (8-12 tons), semi-hermetic


compressors

Blower & Electric


Box Assembly

31-1/4"
(794mm)

Compressor Assembly

76"
(1930mm)
Assembled
Filter & Coil Height
Assembly

76"
(1930mm)

45-13/16"
(1163mm)

33" 26" 59"


(838mm) (660mm) (1499mm)
85" (2159mm)
Assembled Length
Drawing views are simplified with panels removed to show overall dimensions. DPN003161
See disassembly and handling instructions in installation manual. Rev. 1

Dry Weight, Approximate, Including Panels, lb. (kg)


Component Air-Cooled Dual-Cool
Compressor Assembly 800 (364) 800 (364)
Blower and Electric Box Assembly (Forward-Curved Fans) 510 (231) 510 (231)
1
Blower and Electric Box Assembly (EC Fans ) 360 (163) 360 (163)
Filter and Coil Assembly 520 (236) 670 (304)
1. Fan weight not included in this weight. Fan is installed in plenum. See 313221 for plenum weight.
2. Source: DPN003161, Rev. 1

Liebert® DS™ 92
Blower Outlet and Deck Dimensions

Figure 73 Disassembly dimensions—Upflow, air-cooled, 53-77kw (15-22 tons), scroll or digital scroll
compressors

Digital scroll compressors not


available on 077 models.

Blower & Electric


Box Assembly

31-1/4"
Compressor Assembly (794mm)

76"
(1930mm)
Filter & Coil Assembled
Assembly Height

76"
(1930mm)

45-13/16"
(1163mm)

33" 15" 82" (2083mm)


(838mm) (381mm)
97" (2464mm)
Assembled Length
Drawing views are simplified with panels removed to show overall dimensions. DPN003166
See disassembly and handling instructions in installation manual. Rev. 1

Dry Weight, Approximate, Including Panels, lb. (kg)


Model # 053, 070, 077
Compressor Scroll/Digital Scroll 1
Component Air-Cooled Dual-Cool
Compressor Assembly 540 (246) 540 (246)
Blower and Electric Box Assembly
600 (272) 600 (272)
EC Fans 2
Blower and Electic Box Assembly
770 (349) 770 (349)
(Forward-Curved Blowers)
Filter and Coil Assembly 760 (345) 940 (426)
1. Digital scroll compressors not available on 077 models.
2. Fan weight not included in this weight. Fans are installed in plenum. See 313221 for plenum weight.
3. Source: DPN003166, Rev. 1

93 Liebert® DS™
Blower Outlet and Deck Dimensions

Figure 74 Disassembly dimensions—Upflow, air-cooled, 53-77kW (15-22 tons), semi-hermetic


compressor models

Blower & Electric


Box Assembly

31-1/4"
(794mm)

Compressor Assembly

76" (1930mm)
Filter & Coil Assembled Height
Assembly

76"
(1930mm)

45-13/16"
(1163mm)

33" 26" 82" (2083mm)


(838mm) (660mm)
108" (2743mm)
Assembled Length
Drawing views are simplified with panels removed to show overall dimensions. DPN003165
See disassembly and handling instructions in installation manual. Rev. 2

Dry Weight, Approximate Including Panels, lb. (kg)


Component Air-Cooled Dual-Cool
Compressor Assembly 970 (441) 970 (441)
Blower and Electric Box Assembly
770 (349) 770 (349)
(Forward-Curved Blowers)
EC Fans 1 600 (231) 600 (231)
Filter and Coil Assembly 760 (345) 940 (426)
1. Fan weight not included in this weight. Fans are installed in plenum. See 313221 for plenum weight.
2. Source: DPN003165, Rev. 2

Liebert® DS™ 94
Blower Outlet and Deck Dimensions

Figure 75 Disassembly dimensions—Upflow, air-cooled, 105kW (30 tons), standard scroll compressors

Digital scroll compressors


not available on VS 105.

Blower & Electric


Box Assembly

31-1/4"
(794mm)

Compressor
Assembly 76"
(1930mm)
Assembled
Height
Filter & Coil Assembly

76"
(1930mm)
45-13/16"
(1164mm)

33" 26" 105" (2667mm)


(838mm) (660mm)
131" (3327mm
Assembled Length
Drawing views are simplified with panels removed to show overall dimensions. DPN003169
Seee disassembly and handling instructions in installation manual. Rev. 1

Dry Weight, Approximate, Including Panels, lb (kg)


Component Air-Cooled Dual-Cool
Compressor Assembly 830 (376) 830 (376)
Blower and Electric Box Assembly
1080 (490) 1080 (490)
(Forward-Curved Blowers)
EC Fans 2 840 (381) 840 (381)
Filter and Coil Assembly 970 (440) 1300 (590)
1. Digital scroll compressors not available on DS105 models.
2. Fan weight not included in this weight. Fans are installed in plenum. See 313221 for plenum weight.
3. Source: DPN003169, Rev. 1

95 Liebert® DS™
Blower Outlet and Deck Dimensions

Figure 76 Disassembly dimensions—Upflow, air-cooled, 105kW (30 tons), semi-hermetic compressors

Blower & Electric


Box Assembly

31-1/4"
(794mm)

Compressor
Assembly
76"
(1930mm)
Assembled
Filter & Coil Height
Assembly
76"
(1930mm)

45-13/16"
(1164mm)

33" 26"
(660mm) 105" (2667mm)
(838mm)
131" (3327mm
Assembled Length
Drawing views are simplified with panels removed to show overall dimensions. DPN003168
See disassembly and handling instructions in installation manual. Rev. 1

Dry Weight, Approximate, Including Panels, lb (kg)


Component Air-Cooled Dual-Cool
Compressor Assembly 950 (431) 950 (431)
Blower and Electric Box Assembly
1080 (490) 1080 (490)
(Forward-Curved Blowers)
EC Fans 1 840 (381) 840 (381)
Filter and Coil Assembly 970 (440) 1300 (590)
1. Fan weight not included in this weight. Fans are installed in plenum. See 313221 for plenum weight.
2. Source: DPN001254, Rev. 1

Liebert® DS™ 96
Blower Outlet and Deck Dimensions

8.2 Disassembly Dimensions—Upflow, Water/Glycol/GLYCOOL™ Systems


Figure 77 Disassembly dimensions—Upflow, water/glycol/GLYCOOL, 28-42kW (8-12 tons), all
compressors

Digital scroll compressors not


available on 077 models.

Blower & Electric


Box Assembly

31-1/4"
(794mm)

Compressor Assembly

76" (1930mm)
Assembled
Filter & Coil Height
Assembly

76"
(1930mm)

45-13/16"
(1163mm)

33" 26" 59" (1499mm)


(838mm) (660mm)
85" (2159mm)
Assembled Length
Drawing views are simplified with panels removed to show overall dimensions. DPN003163
See disassembly and handling instructions in installation manual. Rev. 1

Dry Weight, Approximate, Including Panels, lb (kg)


Semi-Hermetic Compressor Scroll/Digital Scroll Compressor 1
Component Water/Glycol GLYCOOL/Dual-Cool Water/Glycol GLYCOOL/Dual-Cool
Compressor Assembly 950 (432) 950 (432) 800 (364) 800 (364)
Blower and Electric Box Assembly
510 (231) 510 (231) 510 (231) 510 (231)
(Forward-Curved Blower)
Blower and Electric Box Assembly
360 (163) 360 (163) 360 (163) 360 (163)
EC Fans 2
Filter and Coil Assembly 520 (236) 670 (304) 520 (236) 670 (304)
1. Digital scroll compressors not available on 077 models.
2. Fan weight not included in this weight; fans are installed in plenum. See 313221 for plenum weight.
3. Source: DPN003163, Rev. 1

97 Liebert® DS™
Blower Outlet and Deck Dimensions

Figure 78 Disassembly dimensions—Upflow, water/glycol/GLYCOOL™, 53-77kW (15-22 tons), all


compressors

Digital scroll compressors


not available on 077 models.

Blower & Electric


Box Assembly

31-1/4"
(794mm)

Compressor Assembly
76"
(1930mm)
Assembled
Height
Filter & Coil
Assembly

76"
(1930mm)

45-13/16"
(1163mm)

33" 26"
(838mm) (660mm) 82" (2083mm)
108" (2743mm)
Assembled Length
DPN003167
Drawing views are simplified with panels removed to show overall dimensions.
See disassembly and handling instructions in installation manual.
Rev. 1

Dry Weight, Approximate, Including Panels, lb (kg)


Semi-Hermetic Compressor Scroll or Digital Scroll Compressor 1
Component Water/Glycol GLYCOOL/Dual-cool Water/Glycol GLYCOOL/Dual-Cool
Compressor Assembly 1270 (578) 1270 (578) 840 (382) 840 (382)
Blower and Electric Box Assembly
770 (349) 770 (349) 770 (349) 770 (349)
Forward-Curved Fans
Blower and Electric Box Assembly
600 (272) 600 (272) 600 (272) 600 (272)
EC Fans 2
Filter and Coil Assembly 760 (345) 940 (426) 760 (345) 940 (426)
1. Digital scroll compressors not available on 077 models
2. Fan weight not included in this weight; fans are installed in plenum. See 313221 for plenum weight.
3. Source: DPN003167, Rev. 2

Liebert® DS™ 98
Blower Outlet and Deck Dimensions

Figure 79 Disassembly dimensions—Upflow, water/glycol/GLYCOOL™, 105kW (30 Tons) all compressor


models

Blower and Electric Box


Assembly

31-1/4"
(794mm)

Compressor Assembly

Filter and Coil 76" (1930mm)


Assembled Height
Assembly

76"
(1930mm)

45-13/16"
(1164mm)

33" 26"
(838mm) (660mm) 105" (2667mm)
131" (3327mm)
Assembled Length

Drawing views are simplified with panels removed to show overall dimensions. DPN003170
See disassembly and handling instructions in installation manual. Rev. 1

Dry Weight, Approximate, Including Panels, lb (kg)


Semi-Hermetic Compressor Scroll or Digital Scroll Compressor
Component Water/Glycol GLYCOOL/Dual-cool Water/Glycol GLYCOOL/Dual-Cool
Compressor Assembly 1320 (599) 1320 (599) 1200 (544) 1200 (544)
Blower and Electric Box Assembly
1080 (490) 1080 (490) 1080 (490) 1080 (490)
Forward-Curved Fans
Blower and Electric Box Assembly
840 (381) 840 (381) 840 (381) 840 (381)
EC Fans
Filter and Coil Assembly 970 (440) 1300 (590) 970 (440) 1300 (590)
1. Fan weight not included in this weight; fans are installed in plenum. See 313221 for plenum weight.
2. Source: DPN003170, Rev. 1

99 Liebert® DS™
Ancillary Items

9.0 ANCILLARY ITEMS

9.1 Floor Stands


Figure 80 Floor stand dimensions, downflow, 28-42kW (8-12 tons) models with EC fans

A + 1-1/2" (38mm) (with feet)


A
B

33"
(838mm)

34-1/2"
876mm
(With Feet) 1"
(35mm)
Typical

Right side of paneled unit is flush with right side of floor stand.
All other paneled sides overhang floor stand 1" (25mm).
* Leveling feet are provided with ± 1-1/2" (38mm) adjustment
from nominal height C.

Gussets supplied on floor stands


12" (305 mm) tall and greater

C*

7/8" 8"
(23mm) (203mm)

3" Applies to 36", 42" and 48" floor stand. DPN003240


1
(76mm) Rev. 1

Dimensions, in. (mm) Floor Stand


Height C*
Model A B in. (mm)
DS028-042 Air-Cooled Semi-Hermetic and all Water/Glycol/GLYCOOL
85 (2159) 27 (686) 24 (610)
Models
DS028-042 Air-Cooled Scroll and Air-Cooled Digital Scroll Models 72 (1829) 14 (356) 30 (762)
36 (914)
Source: DPN003240, Rev. 1 42 (1069)
48 (1219)

Liebert® DS™ 100


Ancillary Items

Figure 81 Floor stand dimensions, downflow, 53-77kW (15-22 tons) models with EC fans

A
B
3/4" Piping Access Area
(19mm)

31-1/2" 32"
(800mm) (813mm)
Center Feet

32-3/4"
3/4" C (832mm)
(19mm) Support Feet Centers See Note 4

D 24" FLOOR STAND SHOWN


3/4"
(19mm) 1" 33"
(25mm) (838mm)

7/8"
(23mm) F*

G
3"
(76mm)
E 35" (889mm)
Notes Overall Depth
1. This floor stand should be used when EC fans are intended to be lowered under
a raised floor. The standard Liebert DS floor stand can be used if the fans are to
remain in their original raised position.
2. Right side of paneled unit is flush with right side of floor stand. All other paneled sides
overhang floor stand 1" (25mm).
3) The floor stand used with EC units is not symmetrical, and its orientation to the
Liebert DSE is critical for lowering the EC fans. The blowers will not lower into the
floor stand unless the floor stand is installed in the correct position.
4. Jack and jack support are shipped loose and are intended to be placed into position
under each fan and utilized to lower or raise that fan as needed.
DPN003173
* Leveling feet are provided with ±1-1/2" (38mm) adjustment from nominal height F. Rev. 1

Dimension, in. (mm) Leg


Height Height
F, in. G, in.
Liebert DS Model A B C D E (mm) (mm)
DS053-077, Air-Cooled Semi-Hermetic 108 26 106.5 108 109.5
24 (610) —
and all Water/Glycol/ GLYCOOL Models (2743) (660) (2705) (2743) (2781)
DS053-077, Air-Cooled Scroll and 97 15 95.5 97 98.5
30 (762) —
Air-Cooled Digital Scroll Models (2464) (381) (2426) (2464) (2502)
Source: DPN003173, Rev. 1 36 (914) 5
42 (1067) 11
48 (1219) 17

101 Liebert® DS™


Ancillary Items

Figure 82 Floor stand dimensions—Downflow, 105kW (30 tons) models with EC fans, standard scroll and
semi-hermetic compressors

Digital scroll compressors


not available on 105 models.

132-1/2" (3366mm)
(with feet)
131" (3327mm)
25"
(635mm)

34-1/2"
33" 35" (889mm)
(876mm)
(with feet) (838mm) (with feet)
Typ. Both Ends Typ. (2) Places

74" (1880mm) 1"


(25mm Typ.)
5

19-1/4"
(489mm)
A See
Note 4

35"
7/8" (889mm)
3" (76mm) (23mm) Overall Depth Height - A
Notes in. (mm)
1. This floor stand should be used when EC fans are intended to be lowered
under a raised floor. The standard Liebert DS floor stand can be used 24 (610)
if the fans are to remain in their original raised position. 30 (762)
2. Right side of paneled unit is flush with right side of floor stand. All other paneled 36 (914)
sides overhang floor stand 1" (25mm).
3. The floor stand used with EC units is not symmetrical and its orientation to the
42 (1067)
Liebert DS is critical for lowering the EC fans. The blowers will not lower into the floor stand 48 (1219)
unless the floor stand is installed in the correct position.
4. Jack and jack support are shipped loose and are intended to be placed into
position under each fan and utilized to lower or raise that fan as needed.
5. Not applicable to 24' (610mm) x 30" (762) tall floor stands. DPN003174
*Leveling feet are provided with ± 1-1/2" (38mm) adjustment from nominal height “A.” Rev. 2

Liebert® DS™ 102


Ancillary Items

9.2 Plenums
Figure 83 Plenum dimensions—Upflow VS028-VS042 with EC fans
Top duct flanges on plenum
1 Shaded area indicates a recommended top for supply air ducting when
minimum clearance of 36" (914mm) for solid panel plenum is used.
component access from the bottom of the unit mm) 32.1"
63 0.88"
(815mm)
to the top of the plenum. (14 (2.2mm)
.6"
2 Must have access to remove front grille 57
or panel to remove EC fans.
19.7"
(500mm)

Plenum
Height
4.3" (109mm)
0.88" 1.3"
Both top duct opening
(2.2mm) (33mm)
and grilles shown. See
specification sheet m)
4 0m
for specific application. (14 2
.7"
56

mm)
5 05
" " (1
1.3 m) 9.2
5
m 5
33.75" (33
(857mm)

DPN002747
Height
In. (mm)
Rev. 1
Plenum Type
Grille & Top Discharge 24 (610)
Top Discharge Only 30 (762)
Top Discharge Only 36 (914)

103 Liebert® DS™


Ancillary Items

Figure 84 Plenum dimensions—Upflow 53-77kW (15-22 tons) with EC fans

Top duct flanges on plenum


top for supply air ducting when
solid panel plenum is used.
1 Shaded area indicates a recommended 32"
minimum clearance of 36" (914mm) for 0.88"
(813mm)
(2.2mm)
component access from the bottom of the unit m)
to the top of the plenum. 57m
" (20
2 Must have access to remove front grille 81 20"
or panel to remove EC fans. (508mm)

4" (102mm)
1"
Plenum (25mm)
Height
2
Both top duct opening 0.88"
and grilles shown. See (2.2mm)
mm)
specification sheet 0 32
for specific application. " (2
80
)
3 mm
08
" (2
82
1"
(25mm)
34"
(864mm)
1

DPN002748
Rev. 3
Height
Plenum Type In. (mm)
Grille & Top Discharge 24 (610)
Top Discharge Only 30 (762)
Top Discharge Only 36 (914)

Liebert® DS™ 104


Ancillary Items

Figure 85 Plenum dimensions—Upflow 105kW (30 tons) with EC fans

1 Shaded area indicates a recommended 32" Top duct flanges on plenum


minimum clearance of 36" (914mm) for (813mm)
component access from the bottom of the unit top for supply air ducting when
to the top of the plenum. solid panel plenum is used.

2 Must have access to remove front grille ) 0.88"


(2.2mm)
or panel to remove EC fans. mm
6 41
(2
4"
10
Both top duct opening 20"
and grilles shown. See (508mm)
specification sheet
for specific application.

4" (102mm)
1"
m)
m
(51 m)
(25mm)
2" 9m
5 2
Plenum " (5
22
Height

0.88"
(2.2mm)
m)
32m
" (20 m)
80 73m
(26
5"
10

34" 1"
(864mm) (25mm)
1

DPN002749
Rev. 1

Height
Plenum Type In. (mm)
Grille & Top Discharge 24 (610)
Top Discharge Only 30 (762)
Top Discharge Only 36 (914)

105 Liebert® DS™


Ancillary Items

Figure 86 Plenum dimensions—28-105kW (8-30 tons), upflow with forward-curved blowers

FRONT VIEWS - CHECK ONE REAR VIEWS - CHECK ONE

With Front Grille With Rear Grille


Panel removable
for condenser clean
out access
(Water/Glycol/GLYCOOL
Without Grille models only) Without Grille
34"
(864mm) B A Right Side Views -
Left Side Views -
Check One:
Check One:
1" H
(25mm)

With Grille With


Grille
76"
(1930mm)

Without Without Grille


Grille SIDE VIEW - UNIT WITH PLENUM
FRONT VIEW - UNIT WITH PLENUM
NOTES
1. Typical 53-77kW (15-20 Tons) unit orientation shown with grille plenum.
View varies by unit size and plenum selection.
2. Optional grille plenum kits must include front or rear grille.
3. Non-grille plenums are open on the top and not designed with duct flange. DPN003164
4. All plenums are shipped flat and must be field assembled. Rev. 1

Dimensions, in. (mm) Grille Size, in. (mm) - Nominal


A B Front/Rear
Model in. (mm) in. (mm) Grilles Side Grille
28-42kW (8-12 tons) Air-Cooled Scroll and 59-1/4 13-3/4 18 x 55 18 x 20
Air-Cooled Digital Scroll Models (1505) (349) (457 x 1397) (457 x 508)
28-42kW (8-12 tons) Semi-Hermetic and 59-1/4 26-3/4 18 x 55 18 x 20
all Water/Glycol/GLYCOOL Models (1505) (679) (457 x 1397) (457 x 508)
53-77kW (15-22 tons) Air-Cooled Scroll and Air-Cooled 82-1/4 15-3/4 18 x 78 18 x 20
Digital Scroll Models (2089) (400) (457 x 1981) (457 x 508)
53-77kW (15-22 tons) Semi-Hermetic and 82-1/4 26-3/4 18 x 78 18 x 20
all Water/Glycol/GLYCOOL Models (2089) (679) (457 x 1981) (457 x 508)
(1) 18 x 20
105-1/4 26-3/4 (457 x 508) 18 x 20
105kW (30 tons)—All Models
(2673) (679) (1) 18 x 78 (457 x 508)
(457 x 1981)
Source: DPN001187, Rev. 3

Height H, in. (mm) Plenum Configuration


20 (508) Non-grilled
24 (610) Non-grilled, front discharge or rear discharge
36 (914) Non-grilled
Source: DPN 001187, Rev. 3

Liebert® DS™ 106


Ancillary Items

9.3 Rear Return Filter Box


Figure 87 Rear return filter box dimensions—Upflow, air cooled 28-105kW (8-30 tons), all compressors
Filter Access Filter Access
Door Door

7-15/16"
(202mm)
76"
(1930mm)
40"
(1016mm)
38-1/4"
(971mm)
Duct Size

3-1/2" (89mm)
D Duct Size

A B C
NOTES
1. Filters can be accessed from either side.
2. 25" (635mm) minimum clearance provided on one side for filter access. DPN001196
3. Filter boxes are shipped flat and must be field assembled. Rev. 1

A B C D
Model # in. (mm) in. (mm) in. (mm) in. (mm) # Filters
DS28-42kW (8-12 Tons) Air-Cooled Scroll
4-1/4 (108) 50-3/4 (1289) 18 (457) 47-5/8 (1210) 4
and Air-Cooled Digital Scroll Models
DS28-42kW (8-12 Tons) Semi-Hermetic and All
4-1/4 (108) 50-3/4 (1289) 31 (787) 47-5/8 (1210) 4
Water/Glycol/GLYCOOL Models
DS53-77kW (15-22 Tons) Air-Cooled Scroll
3-1/4 (83) 75-1/2 (1918) 19-1/4 (489) 72-3/8 (1838) 6
and Air-Cooled Digital Scroll Models
DS53-77kW (15-22 Tons) Semi-Hermetic and
3-1/4 (83) 75-1/2 (1918) 30-1/4 (768) 72-3/8 (1838) 6
All Water/Glycol/GLYCOOL Models
DS105kW (30 Tons), All Models 2-1/4 (57) 100-1/4 (2546) 29-1/2 (749) 97-1/8 (2467) 8
Source: DPN001196, Rev. 1

107 Liebert® DS™


Piping

10.0 PIPING
Table 41 Recommended refrigerant line sizes - OD copper (inches)
Standard Scroll Models (Non-Digital Scroll)
Model 028 035 042 053 070 077 105
Hot Hot Hot Hot Hot Hot Hot
Equivalent Gas Liquid Gas Liquid Gas Liquid Gas Liquid Gas Liquid Gas Liquid Gas Liquid
Length Line Line Line Line Line Line Line Line Line Line Line Line Line Line
50 ft (15m) 7/8 1/2 7/8 1/2 7/8 1/2 7/8 5/8 1-1/8 7/8 1-1/8 7/8 1-3/8 7/8
100 ft (30m) 7/8 5/8 7/8 5/8 7/8 5/8 1-1/8 7/8 1-1/8 7/8 1-1/8 7/8 1-3/8 7/8
150 ft (45 m) 7/8 5/8 7/8 5/8 7/8 5/8 1-1/8 7/8 1-1/8 7/8 1-1/8 7/8 1-3/8 1-1/8
4-Step Semi-Hermetic and Digital Scroll Models
Model 028 035 042 053 070 077 2 105 2
Hot Hot Hot Hot Hot Hot Hot
Equivalent Gas Liquid Gas Liquid Gas Liquid Gas Liquid Gas Liquid Gas Liquid Gas Liquid
Length Line Line Line Line Line Line Line Line Line Line Line Line Line Line
50 ft (15m) 3/4 1/2 3/4 1/2 7/8 5/8 7/8 7/8 1-1/81 7/8 1-1/8 7/8 1-3/8 7/8
1
100 ft (30m) 3/4 5/8 7/8 5/8 7/8 5/8 1-1/8 7/8 1-1/81 7/8 1-1/8 7/8 1-3/8 7/8
1 1 1
150 ft (45 m) 7/8 5/8 7/8 5/8 1-1/8 5/8 1-1/8 7/8 1-1/8 7/8 1-1/8 7/8 1-3/8 1-1/8
1. Downsize vertical riser one trade size (1-1/8" to 7/8")
2. Digital scroll not available on 077 and 105 models.
3. Source: DPN000788, Rev 1

Table 42 Indoor unit approximate refrigerant charge for R-407C


R-407C Charge
System Type Model per Circuit, lb. (kg)
028, 035, 042 5.5 (2.5)
Air-Cooled 053, 070, 077 8.0 (3.6)
105 9.5 (4.3)

Table 43 Interconnecting piping refrigerant charge


R-407C, lb/100 ft. (kg/30m)
Line Size,
O.D., in. Liquid Line Hot Gas Line
1/2 6.7 (3.0) —
5/8 10.8 (4.8) 0.8 (0.4)
3/4 16.1 (7.2) 1.2 (0.5)
7/8 22.3 (10.0) 1.7 (0.8)
1-1/8 38.0 (17.0) 2.9 (1.3)
1-3/8 57.9 (25.9) 4.4 (2.0)
Source: DPN003099, Rev. 0

Liebert® DS™ 108


Piping

Table 44 Liebert MC Condenser—Refrigerant required, R-407C, approximate


Dual-Circuit, lb/circuit (kg/circuit)
Condenser Condensers without Condensers with
Models Liebert Lee-Temp Liebert Lee-Temp
Approximate R-407C Refrigerant Needed
MCS056 2.2 (1.0) 21.0 (9.5)
MCM080 3.0 (1.4) 21.8 (9.9)
MCM160 7.5 (3.4) 44.5 (20.2)
MCL110 5.1 (2.3) 26.0 (11.8)
MCL220 12.2 (5.6) 53.8 (24.4)
Source: DPN002411, Rev. 7

Table 45 Liebert Fin/Tube condenser—Refrigerant required, R-407C, approximate


Approximate R-407C Refrigerant Needed
Dual-Circuit lb/circuit (kg/circuit)
Standard
Condenser Lee-Temp
Models FSC or VFD (includes receiver)
CD*/TCDV205 7 (3.2) 54 (24.4)
CD*/TCDV251 10 (4.6) 36 (16.3)
CD*/TCDV308 11 (5.0) 55 (24.9)
CD*/TCDV415 24 (10.9) 102 (46.2)
CD*/TCDV616 26 (11.8) 108 (49.0)
Quiet-Line Condenser Models
DCD*214 N/A 77 (34.9)
DCD*286 N/A 119 (54.0)
DCD*409 N/A 148 (67.2)
DCD*572 N/A 186 (84.4)

109 Liebert® DS™


Piping

10.1 Piping Schematics



10.1.1 Typical System Configurations—LIEBERT MC CONDENSERS
Figure 88 shows a single refrigeration circuit diagram, displaying the indoor air conditioning unit,
the outdoor condenser (with or without Liebert Lee-Temp™) and field-supplied interconnection piping.

Figure 88 Liebert MC piping schematic with and without Liebert Lee-Temp

Check Valve Service


Relief Valve Valve Liquid Return
Head Pressure
Control Valve Check
Liebert Lee-Temp Receiver
Valve

Condenser Condenser
Optional Field-Installed
Coil Coil
Fusible Plug

Hot Gas Discharge

Liebert Lee-Temp
Internal
Inverted Trap
Liquid
For rises over 25ft. (7.6m),
Sensing
Evaporator trap every 20ft. (6m) or at
Coil evenly divided distances*
Bulb
Service
Valve Suction

Field installed relief valve(s) required


Check Service for 50Hz EU CE units
External
Valve Valve
Equalizer
Compressor *Isolation
Valve

Hot Gas Discharge

Expansion Solenoid Sight Filter Drier Liquid Line Trap at base


*Isolation of risers
Valve Valve Glass
Valve over 5ft. (1.5m)*
Refrigerant Piping
* Components are not supplied by
Field Piping Liebert but are required for
Service/Schrader (Access) Connection No Valve Core proper circuit operation and
Service/Schrader (Access) Connection With Valve Core maintenance

NOTES
Single refrigeration circuit shown for clarity. DPN002188
Schematic representation shown. Do not use for specific connection locations. Rev. 3

Liebert® DS™ 110


Piping

10.1.2 Typical System Configurations—Fin/Tube


Figure 90 shows a single refrigeration circuit diagram, displaying the indoor air conditioning unit,
the outdoor condenser (VFD, Fan Speed Control or Liebert Lee-Temp™) and field-supplied
interconnection piping.

Figure 89 Piping schematic, air-cooled with semi-hermetic compressor with fin/tube condenser

Liquid Return
Check Relief Valve Service
Valve Valve Optional
Subcooling
Coil Optional
Head Pressure Inverted trap on discharge
Sub-Cooling
Control Valve and liquid lines to extend above
Coil
Liebert Lee-Temp Receiver base of coil by a minimum of
7-1/2" (190mm).

CONDENSER CONDENSER
COIL COIL Optional Field-Installed
(Liebert Lee-Temp) (FAN SPEED or VFD) Fusible Plug

Hot Gas Discharge

LIEBERT LEE-TEMP

For rises over


LIQUID 25ft. (7.6m),
EVAPORATOR trap every 20ft. (6m) or
Sensing evenly divided*
Cylinder COIL
Service Bulb
Valve Unloader(s)
SUCTION

Muffler
Field-installed relief valve(s)
COMPRESSOR Service External required for 50Hz EU CE units
Valve Equalizer rated maximum 480 PSIG (33 Bar).
Check Valve
*Isolation
Valve
**Muffler

Hot Gas Discharge

Expansion Solenoid Sight Filter Drier Liquid Return


Valve *Isolation Trap at base of risers
Valve Glass Valve over 5ft. (1.5m)*
NOTES: Two refrigeration circuits provided.
* Components are not supplied by
Single refrigeration circuit shown for clarity.
Emerson but are required for
Schematic representation shown. proper circuit operation and
Do not use for specific connection locations. maintenance.

REFRIGERANT PIPING ** Components supplied by Emerson


FIELD PIPING and must be field-installed (70kW,
77 kW & 105kW models only).
Service / Schrader (Access) Connection No Valve Core
DPN000797
Service / Schrader (Access) Connection With Valve Core Rev. 7

111 Liebert® DS™


Piping

Figure 90 Piping schematic, air-cooled with scroll or digital scroll compressor with fin/tube condenser
Inverted Trap on discharge Relief
and liquid lines to extend above Check Valve Service
base of coil by a minimum of Valve Valve Liquid Return Optional
7-1/2" (190mm).
Sub-Cooling
Head Pressure Coil
Optional
Liebert Lee-Temp Receiver Control Valve
Subcooling
Coil

CONDENSER Optional CONDENSER


COIL Field-Installed COIL
Fusible Plug
(Fanspeed or VFD) (Liebert Lee-Temp)

Hot Gas Discharge Hot Gas Discharge


LIEBERT LEE-TEMP
(Liebert Lee-Temp or VFD condenser
FANSPEED/VFD
is required with digital scroll)
(Liebert Lee-Temp or VFD condenser
is required with Digital Scroll) LIQUID For rises over
25ft. (7.6m),
28-42kW Digital Solenoid Valve Sensing EVAPORATOR trap every 20ft.
Bulb COIL (6m) or evenly
53-70kW Digital
Solenoid Valve
divided*
SUCTION

Service
Valve Field-installed relief valve(s) required
for 50Hz EU CE units rated maximum
Check External
Service 480 PSIG (33 Bar).
Valve Equalizer
COMPRESSOR Valve
*Isolation
Valve
Hot Gas Discharge

Expansion Solenoid Sight Filter Drier Liquid Return *Isolation


Valve Valve Glass Valve Trap at base of risers
NOTES: Two refrigeration circuits provided. over 5ft. (1.5m)*
* Components are not supplied by
Single refrigeration circuit shown for clarity. Emerson but are required for
Schematic representation shown. proper circuit operation and
Do not use for specific connection locations. maintenance.
REFRIGERANT PIPING
DPN000798
FIELD PIPING
Rev. 7
Service / Schrader (Access) Connection No Valve Core
Service / Schrader (Access) Connection With Valve Core

Liebert® DS™ 112


Piping

Figure 91 Piping schematic—Water/glycol semi-hermetic compressor models

Optional Dual Pump System Shown


** EXPANSION
LIEBERT
CUSTOMER TANK GLYCOL
HEAT REJECTION
HEAT REJECTION PUMPS
* Check Valves
(on Dual Pump
DRYCOOLER Systems only)
(Glycol) * Pressure
COOLING TOWER
Port * Gate Valves
AND PUMP Aquastat
SYSTEM Sensing
BY OTHERS Bulbs
*** Air Vents
* Hose * Pressure Port
Bib * Shutoff Valve (typical)

Flow Switch
Supplied with Dual
Pump Systems
* Shutoff Valve * Flow-Regulating
RETURN SUPPLY Valve

RETURN SUPPLY

LIEBERT DS
RETURN
(and associated piping) SUPPLY

LIQUID * Shutoff Valve


Optional
* Shutoff Valve
3-Way
Sensing Bulb EVAPORATOR Regulating * Hose
Cylinder COIL Valve Bib * Hose
Service Unloader(s) Bib
SUCTION
Valve

Muffler
COMPRESSOR Two-Way
Service External Regulating
Check
Valve Equalizer Valve
Valve
DISCHARGE

PARADENSER® Bypass Valve


CONDENSER

Expansion Solenoid Sight Filter Drier


Valve Valve Glass Sensor
Relief valve(s) supplied
with 50 Hz EU CE units rated TO SECOND
maximum 480 PSIG (33 Bar). REFRIGERATION
CIRCUIT

FACTORY PIPING * Components are not supplied by Emerson


FIELD PIPING but are required for proper circuit operation and
OPTIONAL FACTORY PIPING maintenance
Service / Schrader (Access) Connection No Valve Core ** Field-installed at highest point in system on return
line to pumps
Service / Schrader (Access) Connection With Valve Core
*** Locate at tops of all risers and any intermediate
NOTES: Two refrigeration circuits provided. system high points
Single refrigeration circuit shown for clarity. DPN000895
Schematic representation shown. Rev. 5
Do not use for specific connection locations.

113 Liebert® DS™


Piping

Figure 92 Piping schematic—Water/glycol scroll compressor models

Optional Dual Pump System Shown


LIEBERT ** EXPANSION
HEAT REJECTION TANK GLYCOL * Check Valves
CUSTOMER PUMPS (on Dual Pump
HEAT REJECTION Systems only)

DRYCOOLER * Gate Valves


(Glycol) * Pressure
COOLING TOWER Port
AND PUMP Aquastat
SYSTEM Sensing
BY OTHERS Bulbs
* Hose
*** Air Vents
Bib
* Shutoff Valve (typical) * Pressure Port

Flow Switch
Supplied with Dual
Pump Systems

* Shutoff Valve * Flow-Regulating


RETURN SUPPLY Valve

RETURN SUPPLY

LIEBERT DS
(and associated piping) RETURN SUPPLY

LIQUID * Shutoff Valve * Shutoff Valve


Optional
Sensing Bulb 3-Way
EVAPORATOR * Hose
Regulating * Hose
COIL Valve Bib
Bib
SUCTION

Service
Valve
Service External Two-Way
CheckCOMPRESSOR Valve
Equalizer Regulating
Valve Valve
DISCHARGE

PARADENSER® Bypass Valve


CONDENSER

Expansion Solenoid Sight Filter Drier


Valve Valve Glass Sensor
Relief valve(s) supplied
with 50 Hz EU CE units rated
maximum 480 PSIG (33 Bar). To Second
Refrigeration
Circuit

FACTORY PIPING * Components are not supplied by


FIELD PIPING Emerson but are required for
OPTIONAL FACTORY PIPING proper circuit operation and maintenance
** Field-installed at highest point in system
Service / Schrader (Access) Connection No Valve Core
on return line to pumps
Service / Schrader (Access) Connection With Valve Core *** Locate at tops of all risers and
NOTES: Two refrigeration circuits provided. any intermediate system high points
Single refrigeration circuit shown for clarity.
DPN000896
Schematic representation shown.
Rev. 5
This schematic does not imply or define elevations and
component location, unless specifically noted.

Liebert® DS™ 114


Piping

Figure 93 Piping schematic—Water/glycol with digital scroll compressor models

Optional Dual Pump System shown


CUSTOMER LIEBERT EXPANSION
TANK**
GLYCOL
HEAT REJECTION HEAT REJECTION PUMPS
Check Valves*
(on Dual Pump
Systems only)
DRYCOOLER Pressure
COOLING TOWER (Glycol) Port*
AND PUMP Aquastat Gate Valves*
SYSTEM Sensing
BY OTHERS Bulbs
Hose Air Vents
Pressure Port*
Bib* Shut-Off Valve* (typical)***

Flow Switch
Supplied with Dual
Pump Systems

Shut-Off Valve* Flow-Regulating


RETURN SUPPLY Valve*

RETURN SUPPLY

LIEBERT DS HOT GAS REHEAT RETURN SUPPLY


(and associated piping) Optional 3-Way
LIQUID Motorized Ball Shut-Off Valve* Shut-Off Valve*
Valve
28-42kW Digital Solenoid Valve Sensing Bulb
Hose Hose
EVAPORATOR
53-70kW Digital Bib* Bib*
COIL
Solenoid Valve SUCTION

Hot Gas Reheat


Service Valve
Valve Service 2-Way
Valve Check Valve
Check External Motorized
COMPRESSOR From
Valve Equalizer Ball Valve
Liebert
DISCHARGE iCOM
Control
PARADENSER®
CONDENSER

To
Expansion Solenoid Sight Filter Drier Liebert
Valve Valve Glass Pressure iCOM
Relief valve(s) supplied Transducer Control
with 50 Hz EU CE units rated To Second
maximum 480 PSIG (33 Bar). Refrigeration
Circuit

FACTORY PIPING * Components are not supplied by


Emerson, but are required for
FIELD PIPING proper circuit operation and
OPTIONAL FACTORY PIPING maintenance
SERVICE / SCHRADER (ACCESS) CONNECTION NO VALVE CORE ** Field-installed at highest point in
system on return line to pumps
SERVICE / SCHRADER (ACCESS) CONNECTION WITH VALVE CORE *** Locate at tops of all risers and
DPN001430
any intermediate system high points
NOTE: Two refrigeration circuits provided. Single refrigeration circuit shown for clarity Rev. 1
Schematic representation shown. This schematic does not imply or define elevations and
component location, unless specifically noted.

115 Liebert® DS™


Piping

Figure 94 Piping schematic—GLYCOOL™ semi-hermetic compressor models

LIEBERT Optional Dual Pump System shown


EXPANSION
HEAT REJECTION TANK**
GLYCOL
PUMPS
Check Valves*
DRYCOOLER Pressure (on Dual Pump
(Glycol) Port* Systems only)

Aquastat Gate Valves*


Sensing
Bulbs
Hose Air Vents
Bib* Shutoff Valve* (typical)*** Pressure Port*

Flow Switch
Supplied with Dual
Pump Systems

Flow-Regulating
Shutoff Valve*
Valve*

RETURN SUPPLY

LIEBERT DS ECON-O-COIL RETURN SUPPLY


(and associated piping) Shutoff Valve* Shutoff Valve*
LIQUID 3-Way
Chilled Glycol
Sensing Bulb EVAPORATOR Valve
Thermistor Hose Hose
Service Cylinder COIL Bib* Bib*
Valve Unloader(s) SUCTION

External
Equalizer
Muffler
COMPRESSOR
Service
Check Valve Valve Service
DISCHARGE Valve
® 3-Way
PARADENSER
CONDENSER Regulating
Valve

Expansion Solenoid Sight Filter


Valve Valve Glass Dryer Sensor
Relief valve(s) supplied
with 50Hz EU CE units rated To Second
maximum 480 PSIG (33 Bar). Refrigeration
Circuit

Factory Piping * Components are not supplied by


Field Piping Emeron but are required for
proper circuit operation and
Service/Schrader (Access) Connection No Valve Core maintenance
** Field-installed at highest point in
Service/Schrader (Access) Connections With Valve Core
system on return line to pumps
*** Locate at tops of all risers and
Notes: Schematic representation shown. This schematic does not imply or define elevations and any intermediate system high points
component location unless specifically noted.
Two refrigeration circuits provided. Single refrigeration circuit shown for clarity. DPN000897
Rev. 4

Liebert® DS™ 116


Piping

Figure 95 Piping schematic—GLYCOOL™ with scroll compressor models

EXPANSION Optional Dual Pump System shown


LIEBERT
TANK**
HEAT REJECTION GLYCOL PUMPS
Check Valves*
(on Dual Pump
DRYCOOLER Systems only)
Pressure
(Glycol) Gate Valves*
Aquastat Port*
Sensing
Bulbs
Air Vents
Hose Pressure Port*
Shutoff Valve* (typical)***
Bib*
Flow Switch
Supplied with Dual
Pump Systems

Shutoff Valve* Flow-Regulating


Valve*

RETURN SUPPLY

LIEBERT DS UNIT ECON-O-COIL RETURN SUPPLY


(and associated piping) Shutoff Valve*
3-Way Shutoff Valve*
LIQUID
Chilled Glycol
Sensing Bulb Valve Thermistor Hose Hose
EVAPORATOR
Service Bib* Bib*
SUCTION
COIL
Valve

Check Service
Valve Valve External
COMPRESSOR Equalizer
DISCHARGE
3-Way
Paradenser® Regulating
Condenser Valve

Expansion Solenoid Sight Filter Dryer


Valve Valve Glass Sensor
Relief valve(s) supplied
with 50 Hz EU CE units rated To Second
maximum 480 PSIG (33 Bar). Refrigeration
Circuit

FIELD PIPING * Components are not supplied


FACTORY PIPING by Liebert but are required for
SERVICE / SCHRADER (ACCESS) CONNECTION NO VALVE CORE proper circuit operation and
maintenance
SERVICE / SCHRADER (ACCESS) CONNECTION WITH VALVE CORE ** Field installed at highest point in
NOTES: Two refrigeration circuits provided. Single refrigeration circuit shown for clarity. system on return line to pumps
Schematic representation shown. This schematic does not imply or define elevations and *** Locate at tops of all risers and
component location, unless specifically noted. any intermediate system high points
DPN000898
Rev. 4

117 Liebert® DS™


Piping

Figure 96 Piping schematic—GLYCOOL™ with digital scroll compressor models


Optional Dual Pump System shown
LIEBERT EXPANSION
TANK**
HEAT REJECTION GLYCOL
PUMPS
Check Valves*
(on Dual Pimp
DRYCOOLER Pressure Systems only)
(Glycol) Port* Gate Valves*
Aquastat
Sensing
Bulb
Hose Air Vents Pressure Port*
Bib* Shutoff Valve* (typical)***

Flow Switch
Supplied with Dual
Pump Systems
Flow-Regulating
Shutoff Valve* Valve*

RETURN SUPPLY

LIEBERT DS RETURN SUPPLY


ECON-O-COIL
(and associated piping) Shutoff Valve* Shutoff Valve*
LIQUID 3-Way
Chilled Glycol
28-42kW Digital Solenoid Valve Hose
Sensing Bulb EVAPORATOR Valve Hose
Thermistor Bib*
53-70kW Digital Bib*
COIL
Solenoid Valve
SUCTION

Service
Valve
Check External
3-Way
Valve COMPRESSOR Equalizer
Motorized From
Ball Valve Liebert
DISCHARGE iCOM
Control
PARADENSER®
CONDENSER

Expansion Solenoid Sight To


Filter Drier
Valve Liebert
Valve Glass Pressure
iCOM
Relief valve(s) supplied Transducer Control
with 50Hz EU CE units rated To Second
maximum 480 PSIG (33 Bar). Refrigeration
Circuit

FACTORY PIPING * Components are not supplied by


Emerson, but are required for
FIELD PIPING
proper circuit operation and
SERVICE / SCHRADER (ACCESS) CONNECTION NO VALVE CORE
maintenance
SERVICE / SCHRADER (ACCESS) CONNECTION WITH VALVE CORE ** Field installed at highest point in
system on return line to pumps
NOTE: Two refrigeration circuits provided. Single refrigeration circuit shown for clarity. *** Locate at tops of all risers and DPN001432
Schematic representation shown. This schematic does not imply or define elevations and any intermediate system high points Rev. 1
Component location, unless specifically noted.

Liebert® DS™ 118


Piping

Figure 97 Piping schematic—Optional Econ-O-Coil

Return Supply Return Supply

Thermistor* Thermistor* Actuator


Actuator

Return Return

Supply Supply
Econ-O-Coil Econ-O-Coil

Optional Econ-O-Coil (2-Way Valve) Optional Econ-O-Coil (3-Way Valve)

Factory Piping *Supplied with 10 feet (3m) extra thermistor wire for installation
Field Piping on field suppy line.
DPN000805
1. Place thermistor in location where flow is always present.
Rev.
2
2. Thermistor must be located out of the supply air stream.
3. On downflow units the sensor is coiled in the bottom of the
unit on the left side. On upflow units it is coiled on top of unit on the left side.

119 Liebert® DS™


Electrical Field Connections

11.0 ELECTRICAL FIELD CONNECTIONS

Figure 98 Electrical field connections—Upflow and downflow models, single molded case switch
disconnect with main fuses

See 11.1 - Standard Electrical Field Connections, 11.2 -


Optional Electrical Connections, 11.2 - Optional Electrical
Connections and 11.3 - Optional Low Voltage Terminal
2 Package Connections for keys to numbered components. 4 Liebert
IntelliSlot
Housing
A B
OVERCURRENT PROTECTION DEVICES
C D
15
Alternate
Location

P64
6 CONTACTORS
P67
60Hz

CONTACTORS, RELAYS, &


13 OVERLOAD PROTECTORS

Downflow 3
1 5 6 Typical orientation of components shown. DOWNFLOW LOW-VOLTAGE SECTION
Component location varies by option and unit size.

17 18 9 22 16 19
NOTICE
UPFLOW Risk of broken or shorted low-voltage
82 83 88 89 75 76 94 95 96 97 91 92 93 80 81 11 12 wiring. Field-installed low-voltage wiring
3 must be routed with loop as shown
A B to allow electric box to swing.
24 23 21 7 8 10 20

58 59 84 85 37C38C 37B 38B 37 38 24 50 51 55 56 70 71 230 72 73 A B

C D
C D
11
SH
49-1
49-3

12

E E
Item 12 Installation Conditions
1. Follow all local installation codes. Point of Hinged Low-Voltage
DPN000807 2. Do not run CAN cables in same conduit, raceway, or Electric Box
chase as high voltage wires (120-600V). LIEBERT DS UPFLOW LOW-VOLT SECTION
Pg. 3, Rev. 13
3. Separate high volt wires from CAN wires by 12 inches.
4. For runs greater than 350ft(107m), contact Liebert factory.

Liebert® DS™ 120


Electrical Field Connections

Figure 99 Electrical field connections—Upflow and downflow models, dual-fused disconnect switches
See 11.1 - Standard Electrical Field Connections, 11.2 -
Optional Electrical Connections, 11.2 - Optional Electrical
Connections and 11.3 - Optional Low Voltage Terminal Liebert
2 Package Connections for keys to numbered components. IntelliSlot
4 Housing

A B
OVERCURRENT PROTECTION DEVICES
15 C D
60Hz 14
6
Alternate
15 Alternate
Location
Location

P64
CONTACTORS P67
PRIMARY SECONDARY

13
CONTACTORS, RELAYS and
OVERLOAD PROTECTORS

Typical orientation of components shown. DOWNFLOW 3


1 6 Component location varies by option and unit size.
DOWNFLOW LOW VOLTAGE SECTION
17 18 9 22 16 19
NOTICE
82 83 88 89 75 76 94 95 96 97 91 92 93 80 81 11 12 Risk of broken or shorted low-voltage
UPFLOW wiring. Field-installed low-voltage wiring
A B 3 must be routed with loop as shown
to allow electric box to swing.
24 23 21 7 8 10 20

58 59 84 85 37C 38C 37B38B 37 38 24 50 51 55 56 70 71 230 72 73


A B

C D
C D
11
SH
49-1
49-3

12

E E
Item 12 Installation Conditions
1. Follow all local installation codes.
Point of Hinged Low-Voltage
2. Do not run CAN cables in same conduit, raceway or
chase as high-voltage wires (120-600V).
Electric Box
3. Separate high-voltage wires from CAN wires by 12” (305mm) DS UPFLOW LOW-VOLTAGE SECTION
4. Contact factory for runs greater than 350ft. (107m).
DPN000807
Pg. 4, Rev. 13

121 Liebert® DS™


Electrical Field Connections

11.1 Standard Electrical Field Connections


Source: DPN000807, Rev. 13
1. Primary high-voltage entrance—2.50" (64mm); 1.75" (44mm); 1.375" (35mm) diameter
concentric knockouts in bottom of box.
2. Secondary high-voltage entrance—2.50" (64mm); 1.75" (44mm); 1.375" (35mm) diameter
concentric knockouts in top of box.
3. Primary low-voltage entrance—Three knockouts, each 1.375" (35mm) diameter in bottom of
unit.
4. Secondary low-voltage entrance—Three knockouts, each 1.375" (35mm) diameter in top of
box.
5. Three-phase electrical service—Terminals are on main fuse block (disregard if unit has
optional disconnect switch). Three-phase service not by Emerson.
6. Earth ground—Terminal for field-supplied earth grounding wire. Earth grounding required for
Liebert units.
7. Remote unit shutdown—Replace existing jumper between Terminals 37 and 38 with
field-supplied normally closed switch having a minimum 75VA, 24VAC rating. Use field-supplied
Class 1 wiring.
8. Customer alarm inputs—Terminals for field-supplied, normally open contacts, having a
minimum 75VA, 24VAC rating, between Terminals 24 and 50, 51, 55, 56. Use field-supplied Class
1 wiring. Terminal availability varies by unit options.
9. Common alarm—On any alarm, normally open dry contact is closed across Terminals 75 and 76
for remote indication. 1A, 24VAC maximum load. Use field-supplied Class 1 wiring.
10. Heat rejection interlock—On any call for compressor operation, normally open dry contact is
closed across Terminals 70 and 71 (Circuit 1), 230 (Circuit 2) to heat rejection equipment. 1A,
24VAC maximum load. Use field-supplied Class 1 wiring. When Liebert DS is paired with a
Liebert MC™ series condenser, remove jumper between Terminal 71 and Terminal 230. Three
wires must connect Terminals 70, 71 and 230 of the indoor unit to Terminals 70, 71 and 230 of the
Liebert MC.

CANbus Electrical Connections


11. CANbus Connector– Terminal block with Terminals 49-1 (CAN-H) and 49-3 (CAN-L) + SH
(shield connection). The terminals are used to connect the CANbus communication cable
(provided by others) from the indoor unit to the Liebert MC - Premium Model and optional Liebert
PRE™.
12. CANbus Cable—CANbus cable provided by others to connect to the outdoor condenser and
optional Liebert PRE. No special considerations are required when the total external cable
connection between the indoor unit and outdoor unit(s) is less than 450 ft. (137m). A CANbus
isolator is required for total external cable connections greater than 450 ft. (137m) but less than
800 ft. (243m). Cable must meet the following specifications:
• Conductors 22-18AWG stranded tinned copper
• Twisted pair (minimum 4 twists per foot)
• Braided shield or foil shield with drain wire
• Low Capacitance (15pF/FT or less)
• UL approved temperature rated to 75°C
• UL approved-voltage rated to 300V
• UV-resistant and moisture-resistant if not run in conduit
• Plenum-rated NEC type CMP, if required by national or local codes
Examples: Belden 89207 (plenum-rated), or Alpha Wire 6454 Category 5, 5e, or higher

Liebert® DS™ 122


Electrical Field Connections

11.2 Optional Electrical Connections


Source: DPN000807, Rev. 13
13. Unit factory-installed disconnect switch, fuse block and main fuses—Two types of
disconnect switches are available: Non-Locking and Locking. The Non-Locking switch consists of
a non-automatic molded case switch operational from the outside of the unit. Access to the
high-voltage electric panel compartment can be obtained with the switch in either the On or Off
position. The Locking switch is identical except access to the high-voltage electric panel
compartment can be obtained only with the switch in the Off position. Units with fused
disconnects are provided with a defeater button that allows access to the electrical panel when
power is On. The molded case switch disconnect models contain separate main fuses. Units with
fused disconnects have main fuses within disconnect. Only fused disconnects are used on dual
disconnect options.
14. Secondary disconnect switch and earth ground
15. Three-phase electrical service—Terminals are on top of disconnect switch. Three-phase
service not by Emerson.
16. Smoke sensor alarm—Factory-wired dry contacts from smoke sensor are 91-common, 92-NO
and 93-NC. Supervised contacts, 80 and 81, open on sensor trouble indication. This smoke sensor
is not intended to function as, or replace, any room smoke detection system that may be required
by local or national codes. 1A, 24VAC maximum load. Use field-supplied Class 1 wiring.
17. Reheat and humidifier lockout—Remote 24VAC required at Terminals 82 and 83 for lockout
of reheat and humidifier.
18. Condensate alarm (with condensate pump option)—On pump high water indication,
normally open dry contact is closed across Terminals 88 and 89 for remote indication. 1A, 24VAC
maximum load. Use field-supplied Class 1 wiring.
19. Remote humidifier—On any call for humidification, normally open dry contact is closed across
Terminals 11 and 12 to signal field-supplied remote humidifier. 1A, 24VAC maximum load. Use
field-supplied Class 1 wiring.
20. Auxiliary cool contact—On any call for Liebert Econ-O-Coil™ operation, normally open dry
contact is closed across Terminals 72 and 73 on dual cool units only. 1A, 24VAC maximum load.
Use field-supplied Class 1 wiring.

11.3 Optional Low Voltage Terminal Package Connections


21. Remote unit shutdown—Two additional contact pairs available for unit shutdown (labeled as
37B and 38B, 37C and 38C). Replace jumpers with field-supplied normally closed switch having a
minimum 75VA, 24VAC rating. Use field-supplied Class 1 wiring.
22. Common alarm—On any alarm, two additional normally open dry contacts are closed across
Terminals 94 and 95 and 96 and 97 for remote indication. 1A, 24VAC maximum load. Use
field-supplied Class 1 wiring.
23. Main fan auxiliary switch—On closure of main fan contactor, normally open dry contact is
closed across Terminals 84 and 85 for remote indication. 1A, 24VAC maximum load. Use
field-supplied Class 1 wiring.
24. Liebert Liqui-tect® shutdown and dry contact—On Liebert Liqui-tect activation, normally
open dry contact is closed across Terminals 58 and 59 for remote indication (Liebert Liqui-tect
sensor ordered separately). 1A, 24VAC maximum load. Use field-supplied Class 1 wiring.
Refer to specification sheet for total unit full load amps, wire size amps and maximum
overcurrent protective device size.

123 Liebert® DS™


Heat Rejection—Liebert MC™ Condenser

12.0 HEAT REJECTION—LIEBERT MC™ CONDENSER

12.1 Liebert MC Selections


Table 46 75°F/45RH return air conditions for traditional rooms
Outdoor Design Ambient Temperature
Model # 95°F (35°C) 100°F (38°C) 105°F (41°C) 110°F (43°C) 115°F (46°C) 120°F (49°C)
DS/VS028A MCM056_8 MCM056_8 MCM080_8 MCL110_8 MCL110_8 MCL110_8
DS/VS035A MCM056_8 MCM080_8 MCM080_8 MCL110_8 MCL110_8 MCL110_8
DS/VS042A MCM056_8 MCM080_8 MCL110_8 MCL110_8 MCL110_8 MCL110_8
DS/VS053A MCM056_8 MCM080_8 MCL110_8 MCM160_8 MCM160_8 MCL220_8
DS/VS070A MCM080_8 MCL110_8 MCL110_8 MCM160_8 MCM160_8 MCL220_8
DS/VS077A MCM080_8 MCL110_8 MCL110_8 MCM160_8 MCM160_8 MCL220_8
DS/VS105A MCL110_8 MCM160_8 MCM160_8 MCL220_8 MCL220_8 MCL220_8

Table 47 85°F/33RH return air conditions for Hot Aisle/Cold Aisle applications
Outdoor Design Ambient Temperature
Model # 95°F (35°C) 100°F (38°C) 105°F (41°C) 110°F (43°C) 115°F (46°C) 120°F (49°C)
DS/VS028A MCM056_8 MCM080_8 MCL110_8 MCL110_8 MCL110_8 MCM160_8
DS/VS035A MCM056_8 MCM080_8 MCL110_8 MCL110_8 MCM160_8 MCM160_8
DS/VS042A MCM080_8 MCL110_8 MCL110_8 MCM160_8 MCM160_8 MCM160_8
DS/VS053A MCL110_8 MCL110_8 MCM160_8 MCL220_8 MCL220_8 MCL220_8
DS/VS070A MCL110_8 MCM160_8 MCM160_8 MCL220_8 MCL220_8 MCL220_8
DS/VS077A MCL110_8 MCM160_8 MCM160_8 MCL220_8 MCL220_8 MCL220_8
DS/VS105A MCM160_8 MCL220_8 MCL220_8 MCL220_8 MCL220_8 —

Table 48 T75°F/45RH return air conditions Liebert QuietLine for lower sound levels
Outdoor Design Ambient Temperature
Liebert DS
Model # 95°F (35°C) 100°F (38°C) 105°F (41°C) 110°F (43°C) 115°F (46°C)
DS/VS028A MCM080E8 MCM080E8 MCL110E8 MCL110E8 MCL110E8
DS/VS035A MCM080E8 MCL110E8 MCL110E8 MCM160E8 MCM160E8
DS/VS042A MCM080E8 MCL110E8 MCL110E8 MCM160E8 MCM160E8
DS/VS053A MCL110E8 MCL110E8 MCM160E8 MCL220E8 MCL220E8
DS/VS070A MCL110E8 MCM160E8 MCL220E8 MCL220E8 MCL220E8
DS/VS077A MCL110E8 MCM160E8 MCL220E8 MCL220E8 MCL220E8
DS/VS105A MCM160E8 MCL220E8 Consult Factory

Liebert® DS™ 124


Heat Rejection—Liebert MC™ Condenser

12.2 Condenser and Options Net Weights


Total unit weight is the sum of the condenser weight with the selected legs plus the weight of any
option.
Source: DPN003034, Rev. 1
Table 49 Condenser and option net weights—Small condensers
Condenser Model MCS056
Refrigeration Circuits 2
18" Leg 270 (122)
Condenser Dry 36" Leg 419 (190)
Weight, lb (kg) 48" Leg 451 (205)
60" Leg 482 (219)
Additional Weight for Options, lb (kg)
Liebert Lee-Temp 110 (50)
Coated Coil 8 (4)
575 Transformer 63 (29)

Table 50 Condenser and option net weights—Medium condensers


Condenser Model MCM080 MCM160
Refrigeration Circuits 2 2
18" Leg 441 (200) 860 (390)
Condenser Dry 36" Leg 590 (268) 1066 (484)
Weight, lb (kg) 48" Leg 622 (282) 1114 (505)
60" Leg 653 (296) 1160 (526)
Additional Weight for Options, lb (kg)
Liebert Lee-Temp 110 (50) 220 (100)
Coated Coil 10 (5) 20 (9)
575 Transformer 63 (29) 76 (34)

Table 51 Condenser and option net weights—Large condensers


Condenser Model MCL110 MCL220
Refrigeration Circuits 2 2
18" Leg 602 (273) 1186 (538)
Condenser Dry 36" Leg 766 (347) 1453 (659)
Weight, lb (kg) 48" Leg 798 (362) 1501 (681)
60" Leg 829 (376) 1547 (702)
Additional Weight for Options, lb (kg)
Liebert Lee-Temp 120 (54) 240 (109)
Coated Coil 16 (7) 32 (15)
90 (41) 134 (61)

125 Liebert® DS™


Heat Rejection—Liebert MC™ Condenser

12.3 Sound Data


Table 52 Premium version (EC control)
100% Speed - A-Weighted Sound Power, dBA
Frequency - Hz
Maximum Sound Power 63 125 250 500 1000 2000 4000 8000 Total
MCS 56 53 73 69 73 76 74 67 61 81
80 52 70 76 79 81 79 72 65 85
MCM
160 55 73 79 82 84 82 75 68 89
110 65 74 78 83 85 83 76 69 89
MCL
220 68 77 81 86 88 86 79 72 92

12.4 Electrical Data—Liebert MC™


Table 53 Liebert MC electrical data, three-phase, 60Hz condenser, Premium Version (EC control)
Power Requirements
FLA WSA OPD
Number
Model # of Fans 208/230V 460V 575V 208/230V 460V 575V 208/230V 460V 575V
MCS056 2 6.0 2.8 2.3 6.8 3.3 2.8 15 15 15
MCM080 2 4.6 2.8 2.3 5.5 3.3 2.8 15 15 15
MCM160 4 9.2 5.6 4.7 9.8 6.0 5.0 15 15 15
MCL110 2 11.4 5.6 4.7 12.8 6.3 5.3 15 15 15
MCL220 4 22.8 11.2 9.3 24.2 11.9 9.9 25 15 15
1. FLA = Full Load Amps; WSA = Wire Size Amps; OPD = Maximum Overcurrent Protection Device.
2. 208V–460V premium models must be connected to Wye 3-phase systems.

Liebert® DS™ 126


Heat Rejection—Liebert MC™ Condenser

12.5 Liebert MC™ Dimensions



Figure 100 Condenser planning dimensions—MCM080, MCL110 with/without Liebert Lee-Temp
575V 575V
Option Option

H
Top of
Fan Guard
G

A F
A*

Liebert Lee-Temp
Entering Hot Gas
C and Leaving
D Liquid Piping

Anchor
A Plan

Main
Full height leg Electric
M L K
supplied for each Box
Liebert Lee-Temp End
Receiver Required 6-1/2"
(165mm) Ref
6-1/2"
Dual Circuit Only
(165mm) Ref
15-1/4" K 15-1/4"
(387mm) (387mm)
J Dual Circuit Only
Left Side of Unit Liebert Lee-Temp Only
3-5/8"
(93mm) FRONT VIEW
13/16" Emerson recommends a clearance of
Typical (Liebert Lee-Temp Shown)
(21mm) 36" (915mm) on each side for proper
Typical operation and component access.

1-7/8" (48mm)
7" Typical
(178mm)
Typical
1/2" x 1"
(13mm x 25mm)
Obround Typical DPN003437
DETAIL A
Typical of all Legs
Rev. 1

A* J
Liebert A (575V Only) C D Liebert Lee-Temp K L M
Model No. in. (mm) in. (mm) in. (mm) in. (mm) Only in. (mm) in. (mm) in. (mm)
94-7/8 103-1/8 88-3/8 86-3/4 42-1/2 42-1/2 40-7/8 35-7/8
MCS056
(2411) (2619) (2245) (2203) (1079) (1080) (1038) (910)
105-1/4 113-7/16 96-1/16 94-7/16 46-5/16 46 44-3/8 39-5/16
MCM080
(2674) (2882) (2440) (2398) (1177) (1168) (1127) (999)
124-1/8 133-1/8 112-1/8 110-1/2 54-3/8 55-1/2 53-7/8 48-3/4
MCL110
(3152) (3381) (2848) (2806) (1381) (1410) (1368) (1238)
Source: DPN003437, Rev. 1

Liebert Model No. F 1 (Leg Height Dimensions) , in. (mm)


MCS 056 18 (457) 36 (914) 48 (1219) 60 (1524)
Dimension G, in. (mm) 31-5/8 (803) 49-5/8 (1260) 61-5/8 (1565) 73-5/8 (1870)
Dimension H, in. (mm) 39-5/8 (1006) 57-5/8 (1464) 69-5/8 (1768) 81-5/8 (2073)
MCM080 18 (457) 36 (914) 48 (1219) 60 (1524)
Dimension G, in. (mm) 31-5/8 (803) 49-5/8 (1260) 61-5/8 (1565) 73-5/8 (1870)
Dimension H, in. (mm) 39-5/8 (1006) 57-5/8 (1464) 69-5/8 (1768) 81-5/8 (2073)
MCL110
Dimension G, in. (mm) 35-7/8 (911) 53-7/8 (1368) 65-7/8 (1673) 77-7/8 (1978)
Dimension H, in. (mm) 43-5/8 (1108) 61-5/8 (1565) 73-5/8 (1870) 85-5/8 (2175)
1. Cross-bracing required for legs longer than 18". Number of legs varies per model and options.
2. Source: DPN003437, Rev. 1

127 Liebert® DS™


Heat Rejection—Liebert MC™ Condenser

Figure 101 Condenser planning dimensions—MCM160, MCL220 with/without Liebert Lee-Temp™


575V
Option 575V
Option

B
Lifting Eyebolts
Typ. (4) Places
F

H
A* Top of
A Fan Guard
G

Liebert Lee-Temp
Receiver
Entering Hot Gas
C and Leaving
E D Liquid Piping 54-3/16
(1376mm)
A Typical

Full height leg Main


Anchor
supplied for each Electric
Plan Liebert Lee-Temp M L K
Box
Receiver Required End
6-1/2"
(165mm) Ref
J 6-1/2"
Left Side of Unit 15-1/4" (165mm) Ref.
3-5/8" Liebert Lee-Temp Dual Circuit Only
(387mm) 15-1/4"
13/16" (93mm) Only K
Typical (387mm)
(21mm) FRONT VIEW
Typical Emerson recommends a clearance of (Liebert Lee-Temp Shown)
36" (915mm) on each side for proper
operation and component access.

7"
(178mm) 1-7/8"
Typical (48mm)
Typical

1/2" x 1"
(13mm x 25mm) DPN003439
DETAIL A Obround Typical
Rev. 1
Typical of all Legs

A* J
Liebert A (575V Only) B C D E Liebert Lee-Temp K L M
Model No. in. (mm) in. (mm) in. (mm) in. (mm) in. (mm) in. (mm) Receivers Only in. (mm) in. (mm) in. (mm)
202-7/16 210-5/8 113-1/2 192-1/4 94-7/16 96-3/16 46-5/16 46 44-3/8 39-5/16
MCM160
(5142) (5350) (2883) (4883) (2398) (2444) (1177) (1168) (1127) (999)
236-5/16 245-5/16 129-9/16 224-3/8 110-1/2 112-1/4 54-3/8 55-1/2 53-7/8 48-3/4
MCL220
(6003) (6231) (3291) (5699) (2806) (2851) (1381) (1410) (1368) (1238)
Source: DPN003439, Rev. 1

Liebert Model No. F 1 (Leg Height Dimensions) , in. (mm)


MCM160 18 (457) 36 (914) 48 (1219) 60 (1524)
Dimension G, in. (mm) 31-5/8 (803) 49-5/8 (1260) 61-5/8 (1565) 73-5/8 (1870)
Dimension H, in. (mm) 39-5/8 (1006 57-5/8 (1464) 69-5/8 1768) 81-5/8 (2073)
MCL220
Dimension G, in. (mm) 35-7/8 (911) 53-7/8 (1368) 65-7/8 (1673) 77-7/8 (1978)
Dimension H, in. (mm) 43-5/8 (1108) 61-5/8 (1565) 73-5/8 (1870) 85-5/8 (2175)
1. Cross-bracing required for legs longer than 18". Number of legs varies per model and options.
2. Source: DPN003439, Rev. 1

Liebert® DS™ 128


Heat Rejection—Liebert MC™ Condenser

12.6 Piping Connections



Figure 102 Piping connections—Liebert MC dual-circuit, two-fan and four-fan units

* Cover

Vertical

Inverted traps
are factory provided
inside condenser

Leaving Liquid
Field Piping
Line

Horizontal

Entering Hot
Gas Line
DETAIL A
Circuit #1 Circuit #2

Optional fusible plug service kit to


be brazed into the liquid line(s) in
either the vertical or horizontal A
position (where required).
(Vertical position is suggested,
horizontal position is optional.)
For two circuit systems, one * Shipping cover is not necessary
fusible plug kit must be for proper condenser operation and
installed in each circuit. may be recycled if field piping
DPN002425 interferes with proper reattachment.
Rev. 5

Table 54 Liebert MC piping connection sizes—Liebert MC dual-circuit, two-fan and four-fan units
Connection Sizes, OD, in
# of
Model # Fans Hot Gas Line Liquid Line
MCS056 2 7/8 5/8
MCM080 2 7/8 5/8
MCL110 2 1-1/8 7/8
MCM160 4 1-1/8 7/8
MCL220 4 1-3/8 1-1/8
Source: DPN002425, Rev. 5

129 Liebert® DS™


Heat Rejection—Liebert MC™ Condenser

Figure 103 Piping dimensions—Liebert MC™ dual-circuit condensers with Liebert Lee-Temp™
Hot Gas Line
To Condenser
Entering Hot
Gas Line

C View

B View
* Cover
* Shipping cover is not necessary for proper
condenser operation and may be recycled if field
piping interferes with proper reattachment

Position elbow to
direct relief valve
B View Fasten hot gas line to cabinet
using flat surface clamps with
downward isolators (field-supplied)
See Detail A A
Leaving Metal Clamp
Liquid Line Hot Gas Line Isolator
Liquid Line Detail AA
To Condenser
From Condenser

GENERAL ARRANGEMENT

Liebert-supplied piping assembly Entering Hot


will include one or two valve and check Gas Line
Liquid Line
valves, depending on condenser
From Condenser Position elbow to
capacity and refrigerant
Leaving
C View direct relief valve
Field Piping downward
Liquid Line
Note:
1. The following materials are supplied by Emerson for each circuit (shipped loose with condenser)
for field installation: insulated Liebert Lee-Temp receiver tank with sight glasses, piping assembly
with head pressure control valve, check valve, rotalock valve and pressure relief valve. All other piping
and electrical wiring to be supplied and installed by others. An additional condenser leg per circuit
to be shipped with the condenser. DPN002426
2. Consult factory for proper line sizing for runs longer than 150ft. (45.7m) equivalent length. Rev. 6

Table 55 Piping dimensions—Liebert MC dual-circuit condensers with Liebert Lee-Temp
Condenser Connections
ODS, in. Liebert Lee-Temp Connections
Liquid Line Receiver Out
Hot Gas Tee to Liebert Lee-Temp Rotalock
Model # Circuit No. Hot Gas Liquid IDS, in. Valve ODS, In. IDS, in.
MCS056 2 7/8 5/8 7/8 5/8 5/8
MCM080 2 7/8 5/8 7/8 5/8 5/8
MCL110 2 1-1/8 7/8 1-1/8 7/8 7/8
MCM160 2 1-1/8 7/8 1-1/8 7/8 1-1/8
MCL220 2 1-3/8 1-1/8 1-3/8 1-1/8 1-1/8
Source: DPN002426, Rev. 6

Liebert® DS™ 130


Heat Rejection—Liebert MC™ Condenser

12.7 Electrical Field Connections—Liebert MC™


Figure 104 Electrical field connections—Liebert MC premium efficiency control, with and without Liebert

Lee-Temp
Fan 2 Fan 2
Liebert Lee-Temp receiver tank 1 per circuit). Fan 1
NOTE: Heater pad voltage available for
120V/1ph/60Hz or 230V/1ph/60Hz
150 or 300 watt, varies by condenser.

Electrical connection
Fan 1 box; cover removed
for clarity
Without Liebert
Lee-Temp Electrical service connection.
With Liebert
Pigtails in electric handy box
are factory-wired to Liebert Lee-Temp Lee-Temp
heater pads for field-connection
of separate continuous electric
source; wire not by Emerson.

+
5A

5B
+
6
xxxxxxxxxxxxxxxxxxxxxx

4
xxxxxxxxxxxxxxxxxxxxxx

+
+ 2
xxxxxxx
xxxxxxxxxxxxxx
xxxxxxx
xxxxxxx
xxxxxxx xxxxxxx
xxxxxxx
xxxxxxx
xxxxxxx
ALARM RELAY CARD xxxxxxxxxxxxxx
xxxxxxx xxxxxxx
xxxxxxx
xxxxxxx xxxxxxx
xxxxxxx

7
XX
XX
5C xxxxxxx
xxxxxxx
xxxxxxx
xxxxxxx
xxxxxxx
xxxxxxx
xxxxxxx xxxxxxx
xxxxxxx
xxxxxxx
xxxxxxx
xxxxxxx
xxxxxxx
+

3
11 Right Two
8 Left Knockout Knockouts
10 Item appears only with
12
13
Liebert Lee-Temp board
9 70
71
See on page 132 for key to numbered
230
components
NOTICE!
THIS HOLE FOR FIELD
SUPPLIED EXTRA LOW
VOLTAGE CONTROL WIRING DPN002169 DPN002374
Pg. 1, Rev. 7 Pg. 1, Rev. 6

131 Liebert® DS™


Heat Rejection—Liebert MC™ Condenser

Key Electrical Details; Source: DPN002169, Rev. 7 and DPN002374 Rev. 6


1. Three-phase electrical service—Terminals are on top of disconnect switch for one-fan and
two-fan units. Terminals are on bottom of disconnect switch for three-fan and four-fan units.
Three-phase service not by Emerson. See Note 5.
2. Earth ground—Field lug terminal for earth ground connection. Ground terminal strip for fan
motor ground connection.
3. Primary high-voltage entrance—Two knockouts, each 7/8" (22.2mm) diameter, at the bottom
of the enclosure.
4. SPD field connection terminals—High-voltage surge protection device (SPD) terminals. SPD
is an optional device.
5. CANbus terminal connections—Field terminals for CANbus cable connection.
• 5A is the CANbus connectors
• TB49-1 is the input terminal for CANbus high
• TB49-3 is the input terminal for CANbus low
• TB50-1 is output terminal for CANbus high
• TB50-3 is the output terminal for CANbus low
• Each CANbus cable shield is connected to terminal “SH”, Item 9.
• 5B is the “End of Line” jumper.
• 5C is the CANbus “Device Address DIP Switch.” CANbus cable not by Emerson. See Note 2.
6. Remote unit shutdown—Replace exiting jumper between terminals TB38-1 and TB38-2 with
field-supplied normally closed switch having a minimum 75VA 24VAC rating. Use field-supplied
Class 1 wiring. (This is an optional feature that may be owner specified.)
7. Alarm terminal connections
a. Common Alarm Relay indicates when any type of alarm occurs. TB74-1 is common; TB74-2 is
normally open; and TB74-3 is normally closed. 1 Amp 24VAC is the maximum load. Use
field-supplied Class 1 wiring.
b. Shutdown Alarm Relay indicates when condenser loses power or when a critical alarm has
occurred that shuts down the condenser unit. TB74-4 is common; TB74-5 is normally open;
and TB74-6 is normally closed. 1A 24VAC is the maximum load. Use field-supplied Class 1
wiring.
8. Indoor unit interlock and SPD alarm terminals
a. On any call for compressor operation, normally open contact is closed across Terminals 70 and
71 for Circuit 1, and normally open contact is closed across Terminals 70 and 230 for Circuit 2
from indoor room unit.
b. During SPD alarm, normally open contact is closed across Terminals 12 and13. SPD is an
optional device.
9. CANbus shield terminal—Terminal for field connection of the field-supplied CANbus cables.
Shield of field-supplied CANbus cables must not be connected to ground at the condenser.
10. Primary low voltage entrance—One knockout, 7/8" (22.2mm) diameter, that is free for
customer low-voltage wiring.
11. SPD entrance—One knockout, 7/8" (22.2mm) diameter, at the bottom of the enclosure.
High-voltage surge protective device (SPD) is optional.

Liebert® DS™ 132


Heat Rejection—Liebert MC™ Condenser

Notes
1. Refer to specification sheet for unit voltage rating, full load amp, and wire size amp ratings.
2. The CANbus wiring is field supplied and must be:
• Conductors 22-18AWG stranded tinned copper
• Twisted pair (minimum 4 twists per foot)
• Braided shield or foil shield with drain wire
• Shield must be wired to ground at indoor unit
• Low Capacitance (15pf/ft or less)
• UL approved temperature rated to 75°C
• UL approved voltage rated to 300V
• UV-resistant and moisture-resistant if not run in conduit
• Examples: Belden part number 89207(plenum rated) or Alpha Wire part number 6454 (UV
resistant outdoor rated) Category 5, 5e or higher. Do not run the CANbus cable in the same
conduit, raceway or chase as high voltage.
3. Do not run the CANbus cable in the same conduit, raceway or chase as high voltage.
4. No special considerations are required when the total external cable connection between the
indoor unit and outdoor unit(s) is less than 450ft. (137m). For total external cable connections
greater than 450ft. (137m) but less than 800ft. (243m), a CANbus isolator is required.
5. All wiring must be sized and selected for insulation case per NEC and other local codes.
6. Do not bend cables to less than four times the diameter of the cable.
7. Do not deform cables when securing in bundles or when hanging them.
8. Avoid running the cables by devices that may introduce noise, such as machines, fluorescent
lights and electronics.
9. Avoid stretching cables.
10. Separate high volt wires and other high voltage sources from CAN wires by 12 inches.
11. The electrically commutated (EC) motors included in the Liebert MC™ Condenser are suitable for
connection to power supplies with a solidly grounded neutral. (Some platforms can accept power
supplies listed under Item b below. Contact the factory for more information.)
a. Acceptable power supplies for 208 to 575V nominal units
• 208V wye with solidly grounded neutral and 120V line to ground;
• 380V wye with solidly grounded neutral and 220V line to ground;
• 480V wye with solidly grounded neutral and 277V line to ground.
• 575V wye with solidly grounded neutral and 332V line to ground. (uses step-down
transformer)
b. Non-acceptable power supplies for 208V to 575V nominal units
• wye with high resistance (or impedance) ground;
• delta without ground or with floating ground;
• delta with corner ground; or
• delta with grounded center tap.

133 Liebert® DS™


Heat Rejection—Liebert Fin/Tube Condensers

13.0 HEAT REJECTION—LIEBERT FIN/TUBE CONDENSERS

Table 56 Liebert DS air-cooled condenser selection, finned-tubular design, R-407C


Ambient Temperature, °F (°C)
Outdoor Condenser Outdoor Quiet-Line Condenser
Liebert DS
Model 95 (35) 100 (38) 105 (41) 95 (35) 100 (38) 105 (41)
028 TCDV/CD*-205 TCDV/CD*-205 TCDV/CD*-251 TCDV/CD*-214 TCDV/CD*-214 TCDV/CD*-286
035 TCDV/CD*-205 TCDV/CD*-205 TCDV/CD*-251 TCDV/CD*-214 TCDV/CD*-214 TCDV/CD*-286
042 TCDV/CD*-205 TCDV/CD*-251 TCDV/CD*-308 TCDV/CD*-286 TCDV/CD*-286 TCDV/CD*-409
053 TCDV/CD*-251 TCDV/CD*-308 TCDV/CD*-415 TCDV/CD*-286 TCDV/CD*-409 TCDV/CD*-409
070 TCDV/CD*-308 TCDV/CD*-415 TCDV/CD*-415 TCDV/CD*-409 TCDV/CD*-572 TCDV/CD*-572
077 TCDV/CD*-308 TCDV/CD*-415 TCDV/CD*-616 TCDV/CD*-409 TCDV/CD*-572 TCDV/CD*-572
105 TCDV/CD*-415 TCDV/CD*-616 TCDV/CD*-616 TCDV/CD*-572 N/A N/A

Table 57 Fin/tube condenser physical data and R-407C refrigerant required per condenser circuit
Connection Size, Dual-Circuit
OD, In. lb/circuit (kg/circuit)
Number Number Net Weight Liebert Lee-Temp™
Model # of Fans of Circuits Hot Gas Liquid lb (kg) FSC or VFD (includes receiver)
Standard Models
TCDV/CD*205 2 2 1-1/8 7/8 495 (225) 7 (3.2) 54 (24.4)
TCDV/CD*251 3 2 1-1/8 7/8 500 (227) 10 (4.6) 36 (16.3)
TCDV/CD*308 3 2 1-3/8 1-1/8 670 (304) 11 (5.0) 55 (24.9)
TCDV/CD*415 4 2 1-3/8 1-1/8 840 (381) 24 (10.9) 102 (46.2)
TCDV/CD*616 6 2 1-5/8 1-1/8 1380 (626) 26 (11.8) 108 (49.0)
Quiet-Line Models
TCDV/DCD*214 3 2 1-1/8 7/8 840 (381) N/A 77 (34.9)
TCDV/DCD*286 4 2 1-1/8 7/8 1105 (501) N/A 119 (54.0)
TCDV/DCD*409 6 2 1-5/8 1-1/8 1380 (626) N/A 148 (67.2)
TCDV/DCD*572 8 2 2-1/8 1-1/8 2430 (1102) N/A 186 (84.4)

Table 58 DS fin/tube condenser cfm and sound data


Number Sound Power Sound Pressure
Model # of Fans Horsepower CFM LwA dBA 3
Standard Models
205 2 3/4 10300 91.0 75.5
251 3 3/4 17950 94.0 77.3
308 3 3/4 16650 93.8 77.3
415 4 3/4 20650 94.4 78.5
616 6 3/4 33300 96.8 80.3
Quiet-Line Models
214 3 1/4 6400 74.8 61.3
286 4 1/4 8275 76.2 62.5
409 6 1/4 13750 78.4 64.3
572 8 1/4 17050 79.9 65.5

Liebert® DS™ 134


Heat Rejection—Liebert Fin/Tube Condensers

13.1 Dimensions
Figure 105 Fin/tube condenser dimensions, 2-fan model
Emerson recommends a
clearance of 36" (915mm) on
43-9/16" each side for proper operation
(1106mm) and component access.
91-1/2"
(2324mm)

37-7/8"
(962mm)

18"
(457mm)

84"
(2134mm)
43-3/16"
(1097mm)

Figure 106 Fin/tube condenser dimensions, 3-fan and 4-fan models

43-9/16" Emerson recommends a clearance of 36" (915mm)


(1106mm) on each side for proper operation and component
access.
131-1/2"
(3340mm)
37-7/8" 43-9/16"
(962mm) (1106mm)

171-1/2"
(4356mm)
18" 70"
(457mm)
(1778mm) 37-7/8"
(962mm)
124"
Eyebolts
(3150mm)
for Lifting
43-3/16"
18"
(1097mm) (457mm)

Note:
Overall height to the top of fan guard 164"
43-1/8" (1095mm) (4166mm)

43-3/16"
(1097mm)

135 Liebert® DS™


Heat Rejection—Liebert Fin/Tube Condensers

Figure 107 Fin/tube condenser dimensions, 6-fan and 8-fan models


Emerson recommends a clearance of 36" (915mm) on
each side for proper operation and component access.
87-1/8"
131-1/2" (2213mm)
(3340mm) 87-1/8"
(2213mm)
171-1/2"
37-7/8" (4356mm)
(962mm)
37-7/8"
(962mm)

59"
(1499mm)
18"
(457mm)
18"
(457mm)
124"
86-3/4" (3150mm) 70" (1778mm)
(2203mm) 164"
1-1/2" (38mm) (4166mm)
diameter hole for
rigging (typ.4)
Overalll height to the top
of the fan guard is 43-1/8” (1095mm). 86-3/4"
(2203mm)

Liebert® DS™ 136


Heat Rejection—Liebert Fin/Tube Condensers

13.2 Electrical Data


13.2.1 Electrical Data—Fin/Tube Condensers
Table 59 Fin/tube condenser data, 60Hz
Model # 205 251, 308 415 616
2 Fans 3 Fans 4 Fans 6 Fans
Input
Voltage ph FLA WSA OPD FLA WSA OPD FLA WSA OPD FLA WSA OPD
Fan Speed Controlled
208/230 8.3 9.5 15 11.8 13.0 15 15.3 16.5 20 23.6 24.8 30
460 3 4.2 4.8 15 5.9 6.5 15 7.6 8.2 15 11.8 12.4 15
575 3.3 3.8 15 4.7 5.2 15 6.1 6.6 15 9.4 9.9 15
VFD Controlled
208/230 7.2 8.1 15 10.7 11.6 15 14.2 15.1 20 N/A N/A N/A
3
460 3.5 4.0 15 5.2 5.7 15 6.9 7.4 15 N/A N/A N/A
Lee-Temp Controlled/Fan-Cycling
208/230 7.0 7.9 15 10.5 11.4 15 14.0 14.9 20 21.0 21.9 25
460 3 3.4 3.8 15 5.1 5.5 15 6.8 7.2 15 10.2 10.6 15
575 2.8 3.2 15 4.2 4.6 15 5.6 6.0 15 8.4 8.8 15
FLA = Full Load Amps; WSA = Wire Size Amps; OPD = Maximum Overcurrent Protection Device

™ ™
Table 60 Fin/tube condenser data, Liebert Quiet-Line (Liebert Lee-Temp controlled/fan-cycling), 60Hz
Model # ph 214 286 409 572
3 Fans 4 Fans 6 Fans 8 Fans
Input
Voltage ph FLA WSA OPD FLA WSA OPD FLA WSA OPD FLA WSA OPD
208/230 5.4 5.9 15 7.2 7.7 15 10.8 11.3 15 14.4 14.9 20
460 3 2.7 2.9 15 3.6 3.8 15 5.4 5.6 15 7.2 7.4 15
575 2.1 2.3 15 2.8 3.0 15 4.2 4.4 15 5.6 5.8 15
FLA = Full Load Amps; WSA = Wire Size Amps; OPD = Maximum Overcurrent Protection Device

Table 61 Liebert Lee-Temp receiver electrical data, fin/tube condensers


Rated Voltage - Single Phase 120 200/208/230
Watts/Receiver 150 300 150 300
Full Load Amps 1.25 2.5 0.7 1.4
Wire Size Amps 1.56 3.1 0.9 1.8
Maximum Overcurrent
15 15 15 15
Protection Device, Amps
The Liebert Lee-Temp receiver requires a separate power feed for heaters. The
condenser is not designed to supply power to the receiver.

137 Liebert® DS™


Heat Rejection—Liebert Fin/Tube Condensers

13.2.2 Electrical Field Connections—Liebert Fin/Tube Condensers


Figure 108 Electrical field connections for Fan Speed Control fin/tube condensers

Electric service connection


and fuse block

Factory-wired to 24V
control circuit.

Heat Rjection
Connection 70, 71 Electric Service Connection
Field-supplied terminals when factory
Class 2 wiring to disconnect is NOT supplied
interlock condenser 24V
controls to Liebert indoor
unit (70, 71). Refer to the 70
71 Electric Service Connection
condenser and indoor unit terminals when factory
electrical schematics for disconnect is supplied.
termination. 7/8 in (22.2mm)
diameter hole provided in
bottom of electric box.
Factory-installed disconnect
switch (optional).

Factory-wired to components on
electric panel.
Earth Ground Bar (optional on 50Hz only). Electric Service Entrance.
Connection terminals with factory A 7/8 in. (22.2mm) diameter hole in
ground from each high-voltage a 1-1/18 in. (28.6mm) knockout
component for field-supplied provided in bottom of electric box.
earth grounding wire.

Earth ground connection (60Hz)


Connection terminal for field- Electric Service, not by Emerson.
supplied earth grounding wire Single phase for condenser
when factory disconnect is NOT models CSF, CDF with single
supplied. fan motor. Three phase for
all other condenser models.
Refer to specification sheet for full load
Earth ground connection (60Hz) amp and wire size amp ratings.
Connection terminal for field- DPN000666
supplied earth grounding wire Rev. 1
when factory disconnect is supplied.

Liebert® DS™ 138


Heat Rejection—Liebert Fin/Tube Condensers

Figure 109 Electrical field connections for VFD control fin/tube condensers

Factory-wired to 24V
control circuit.

Heat Rjection
Factory installed fuse block on
Connection 70, 71 60Hz units. Circuit breaker supplied
Field-supplied in lieu of fuse block on 50Hz units.
Class 1 wiring to
interlock condenser 24V Electric Service Connection
controls to Liebert indoor terminals with factory
unit (70, 71). Reference the supplied disconnect.
condenser and indoor unit
electrical schematics for
termination. 7/8" (22.2mm)
70
71
V
diameter hole provided in
11
12
13
14
F
bottom of electric box. D SPD Factory-installed
disconnect switch
Special Alarm Connections
Field- supplied 24V Class 1
wiring to remote alarm circuits
Surge Protection Device (SPD) Electric Service Entrance.
normally open alarm contact connections (11, 12). A 7/8" (22.2mm) diameter hole in
a 1-1/18" (28.6mm) knockout
Variable Frequency Drive (VFD)
provided in bottom of electric.
normally closed alarm contact connections (13, 14).
Reference the indoor unit electric
diagram (RAD1-4) for termination.
Factory-wired to components
Electric service,
on electric panel. not by Emerson
Earth Ground BAR (optional
on 50Hz only).
Connection terminals with factory
ground from each high-voltage DPN001051
component for field-supplied Rev. 2
Refer to specification sheet earth grounding wire.
for full load amp and wire size amp ratings Earth Ground Connection (60Hz)
Connection terminal for field-
supplied earth grounding wire
when factory disconnect is supplied.

139 Liebert® DS™


Heat Rejection—Liebert Fin/Tube Condensers

Figure 110 Electrical field connections for Liebert Lee-Temp™ control fin/tube condensers

Liebert Lee-Temp receiver tank


(1 per circuit).
NOTE: Standard heater pads
are 150 Watts each. (Optional
300 Watts heater pads are
available.) Standard heater
pad voltage is 230V. (120V
heater pad voltage is optional.)
Electric connection box
with cover

Electrical service connection.


Pigtails in electric handy
box are factory-wired to
Electric service connection Liebert Lee-Temp
and fuse block heater pads for field
connection of separate
continuous electric source,
Factory-wired to 24V wiring not by Emerson.
Class 2 control circuit.
Heat Rjection
Connection 70, 71
Field-supplied
Class 2 wiring to Electric service connection
interlock condenser 24V terminals when factory
controls to Liebert indoor 70 disconnect is NOT supplied.
71
unit (70, 71). Refer to the
condenser and indoor unit
Electric service connection
electrical schematics for
terminals when factory
termination. 7/8 in (22.2mm)
disconnect is supplied.
diameter hole provided in
bottom of electric box.

Factory-wired to components on Factory-installed disconnect


electric panel switch (optional).

Earth ground bar (optional on 50Hz only). Electric Service Entrance.


Connection terminals with factory A 7/8 in. (22.2mm) diameter hole in
groubd from each high-voltage a 1-1/18 in. (28.6mm) knockout
component for field-supplied provided in bottom of electric box.
earth grounding wire.

Earth ground connection (60Hz) Earth ground connection (60Hz)


Connection terminal for field- Connection terminal for field-supplied
supplied earth grounding wire earth grounding wire when factory
when factory disconnect is NOT disconnect is supplied
supplied.
Electric Service,
not by Emerson.
Refer to specification sheet for full DPN000683
load amp and wire size amp ratings. Rev. 1

Liebert® DS™ 140


Heat Rejection—Liebert Fin/Tube Condensers

13.3 Piping Connections


Figure 111 VFD and Fan Speed Control condenser piping—Fin/tube condensers

Optional fusible plug service kit to


be brazed into the liquid line(s) in
either the vertical or horizontal
position (where required).
(Vertical position is preferable,
horizontal position is optional.)
For two-circuit systems, one
Inverted Traps (field-supplied)
fusible plug kit must to
to extend a minimum of
be installed in each circuit.
Entering Hot Leaving 7-1/2" (190mm) above coil base
Gas Line Liquid Line
Vertical Metal
Clamp
See Isolator
Detail
Horizontal A-A Detail A-A

Fasten liquid and hot gas lines to leg using


flat surface clamps with isolators (field-supplied). DPN001065
Support field piping separately to avoid coil damage Rev. 1
and loss of charge.

141 Liebert® DS™


Heat Rejection—Liebert Fin/Tube Condensers

Figure 112 Liebert Lee-Temp™ head pressure control condenser piping—Fin/tube condensers

Metal
Clamp
Isolator
Detail A-A

This view is shown


with header cover
removed.
Discharge Line Discharge Line
from Unit (field-supplied) Liquid return line to
from Unit
unit (field supplied
(field-supplied)
Inverted Traps (field-supplied) Position elbow to direct
Position elbow to direct to extend at least 7-1/2" (190mm) relief valve downward
relief valve downward above coil base
Liquid Return
The following materials are supplied by Emerson
Line to Unit
for each circuit (shipped loose with condenser)
(field-supplied) Fasten liquid and hot gas lines
for field installation: insulated Liebert Lee-Temp
to leg using flat surface clamps
storage tank with two sight glasses, head
Hot Gas Line with isolators (field-supplied).
pressure control valve, check valve, rotalock
(field-supplied) Support field piping separately
valve and pressure relief valve. All other
to avoid coil damage and loss
piping to be supplied and installed by others.
Liquid Line of charge. See Detail A-A.
(field-supplied) DPN000669
Rev. 4

Liebert® DS™ 142


Heat Rejection—Liebert Piggyback Condensers, Air-Cooled

14.0 HEAT REJECTION—LIEBERT PIGGYBACK CONDENSERS, AIR-COOLED


Table 62 Liebert DS piggyback condenser selection
Air-Cooled Condenser Selection Liebert DS Size
Condenser Ambient
Type Temp. °F (°C) 028 035 042 053 070 077 105
95 (35) PB-925 PB-925 PB-1100 PB-1350 N/A N/A N/A
Piggyback 100 (38) PB-1100 PB-1100 PB-1350 N/A N/A N/A N/A
105 (41) PB-1100 PB-1350 N/A N/A N/A N/A N/A

Table 63 Piggyback condenser physical data, 60Hz


Connection Size, OD, In.
Number Condenser Charge Per Circuit
Model of Circuits Hot Gas Liquid R-407C, lb (kg)
PB-350 2 5/8 1/2 18 8.2)
PB-550 2 5/8 1/2 17 (7.8)
PB-675 2 7/8 1/2 25 (11.2)
PB-925 2 7/8 1/2 22 (9.9)
PB-1100 2 1-1/8 5/8 34 (15.5)
PB-1350 2 1-1/8 5/8 34 (15.5)

Table 64 Piggyback condenser airflow, and static pressure data


HP/RPM
Ext. Static Pressure - in. (Pa)
No. 3
Model of Fans CFM / m / hr 0.25 (62.3) 0.50 (125) 0.75 (187) 1.0 (249)
PB-350A 2 7600/12,920 2/580 3/650 3/720 3/790
PB-550A 2 6600/11,200 2/575 3/650 3/725 3/800
PB-675A 2 6900/11,730 2/605 3/680 3/750 3/820
PB-925A 2 12,500/21,250 7.5/760 7.5/810 7.5/870 7.5/920
PB-1100A 2 12,300/20,910 7.5/780 7.5/830 7.5/890 7.5/940
PB-1350A 2 16,500/28,050 10/640 10/695 10/740 15/790
Values are without filter box. External Static Pressure = filter pressure drop + other static drops.
Source: DPN000695, Rev. 1

Table 65 Piggyback condenser electrical data, 60 Hz, 3 phase 1


208 230 460 575
hp FLA LRA FLA LRA FLA LRA FLA LRA
2.0 7.5 55 6.8 50 3.4 25 2.7 20
3.0 10.6 71 9.6 64.0 4.8 32.0 3.9 25.6
5.0 16.7 102 15.2 92 7.6 46 6.1 36.8
7.5 24.2 140 22.0 127 11.0 63.5 9.0 50.8
10.0 30.8 179 28.0 162.0 14.0 81 11.0 64.8
15.0 46.2 257 42.0 232 21.0 116.0 17.0 93.0
1. See Table 66 for separate power feed needed for Lee-Temp receiver heaters.
2. FLA: Full Load Amps; LRA: Lock Rotor Amps
3. Source: DPN000695, Rev. 1

Table 66 Separate electrical supply requirements for Liebert Lee-Temp™ receivers, 60Hz, 1 ph
Voltage 120 120 208/230 208/230
Watts/Receiver 150 300 150 300
FLA 2.5 5.0 1.4 2.8
WSA 3.1 6.2 1.8 3.6
OPD 15 15 15 15
Only one independent input power supply is needed per piggyback unit; connect to Terminals 90 & 91.

143 Liebert® DS™


Heat Rejection—Liebert Piggyback Condensers, Air-Cooled

14.1 Dimensions
Figure 113 Piggyback condenser planning dimensions

E
H D
1-1/8" K J B
R Overa
ll Dim
(29mm) sions
Dimen ensio
Overall ns
K Optional Fan
Discharge
S Disconnect
H Switch (optional)
J 72"
35-1/8" R (1829mm)
(892mm) Fan Discharge
Shaded areas
indicate a recommended
clearance of 34" (864mm)
for component access.

5"
(127mm)
1"
G A (25.4mm)
C Unit Base
Condenser Coil Inlet
10" (254mm) Unit Base
And Duct Connection
Drain Outlet
C Opening UNIT DIMENSIONAL DATA
NOTE: A 1" (25.4mm) flange is provided on all units
F for duct connection to coil duct opening and
Floor Level fan air discharge opening.
A
DPN000695
Rev. 1
FLOOR CUTOUT DIMENSIONS
Table 67 Piggyback condenser dimensions, in. (mm)
Model A B C D E F G H J K R S
72 74 31 32 1-1/8 33 60 8-5/8 50-3/16 16-1/16 13-3/16 14-11/16
PB-350A
(1829) (1880) (787) (813) (29) (838) (1524) (219) (1275) (408) (335) (373)
72 74 31 32 1-1/8 33 60 8-5/8 50-3/16 16-1/16 13-3/16 14-11/16
PB-550A
(1829) (1880) (787) (813) (29) (838) (1564) (219) (1275) (408) (335) (373)
72 74 31 32 1-1/8 33 60 8-5/8 50-3/16 16-1/16 13-3/16 14-11/16
PB-675A
(1829) (1880) (787) (813) (29) (838) (1564) (219) (1275) (408) (335) (373)
97 99 33 34 3-1/8 45-1/2 85 23-5/16 50-3/16 16-1/16 23-1/2 14-11/16
PB-925A
(2464) (2515) (838) (864) (79) (1156) (2159) (592) (1275) (408) (597) (373)
97 99 33 34 3-1/8 45-1/2 85 23-5/16 50-3/16 16-1/16 23-1/2 14-11/16
PB-1100A
(2464) (2515) (838) (864) (79) (1156) (2159) (592) (1275) (408) (597) (373)
97 99 33 34 3-1/8 45-1/2 85 16-5/16 63-7/8 19-1/8 16-13/16 11-5/8
PB-1350A
(2464) (2515) (838) (864) (79) (1156) (2159) (421) (1622) (486) (427) (295)
Source: DPN000695, Rev. 1

Liebert® DS™ 144


Heat Rejection—Liebert Piggyback Condensers, Air-Cooled

Figure 114 Floor stand dimensions, piggyback condensers with forward-curved blowers

C
B
A

1"
(25.4mm) * H ± 1-1/2" (38mm)
For height selection
refer to chart.
Center Leg Provided
See Table 69 for on 99" Cabinets
height selection
Leg Support on Models DPN000727
18, 21 & 24" High Rev. 0

Table 68 Floor stand dimensions, in. (mm)


Model A B C
PB-350A, PB-550A PB-675A 72 (1829) 36 (914) 31 (787)
PB-925A, PB-1100A PB-1350A 97 (2464) 48-1/2 (1232) 33 (838)
Source: DPN000727, Rev. 0

Table 69 Floor stand height selection, in. (mm)


Nominal Range (Nominal ±1-1/2 *)
9 (229) 7-1/2 to 10-1/2 (191 to 267)
12 (305) 10-1/2 to 13-1/2 (267 to 343)
15 (381) 13-1/2 to 16-1/2 (343 to 419)
18 (458) 16-1/2 to 19-1/2 (419 to 495)
21 (553) 19-1/2 to 22-1/2 (495 to 572)
24 (610) 22-1/2 to 25-1/2 (572 to 648)
1. Leveling feet are provided with ±1-1/2" (38mm) adjustment from nominal height “H”.
2. Source: DPN000727, Rev. 0

145 Liebert® DS™


Heat Rejection—Liebert Piggyback Condensers, Air-Cooled

14.2 Electrical Field Connections—Liebert Piggyback Condensers


Figure 115 Electrical field connections for Liebert piggyback condensers

Factory-installed unit
disconnect switch (optional)

Field-supplied disconnect
switch when factory-installed
unit disconnect switch is not provided.

Three phase electric


service not by
Emerson

Three-phase connection. Electric


service connection terminals
Three-phase connection. when factory disconnect switch
Electric service is supplied
connection terminals Factory-installed disconnect
when factory disconnect switch (optional)
switch is not supplied
Electric conduit knockouts
on bottom of wire raceway
Knockout sizes 1-3/8"
(34.9mm) or 1-3/4" (44.5mm)
or 2 1/2" (63.5mm)
Three-phase electric
service not by Emerson
Factory-wired to Earth ground connection (60Hz).
components 71 Connection terminal for field-supplied
on electric panel. 70

earth grounding wire.


Liebert Lee-Temp electric 90
91

service connection to Factory-wired to components


terminals supplied from on electric panel
factory-wired Liebert Control interlock Field-supplied, Class 2 wiring to
Lee-Temp heater pads Terminals 70 & 71 to interlock condenser 24V
for field connection of separate controls to Liebert room unit; 7/8 in. (22.2mm)
continuous electrical source, diameter knockout provided in bottom of box
not supplied by Emerson. DPN000697
Refer to specification sheet for full load amp and wire size amp ratings. Rev. 0

Liebert® DS™ 146


Heat Rejection—Liebert Piggyback Condensers, Air-Cooled

14.3 Connection Locations—Liebert Piggyback Condensers


Figure 116 Piggyback condenser piping and electrical connection locations

See See Note 2


Note 2 See Note 1
See
Note 1
A
1-13/16" B
C (46mm)
G C
1-13
/16"
(46m
m)
E E
D D
See Note 3 3" (76mm) See Note 2
F 3" (76mm)

1" (25mm)
Panel 1" (25mm)
Panel
See Note 2 3" (76mm)
See Note 2 3" (76mm)
See Note 1 3" (76mm)
See Note 1 3" (76mm)
E See Note 3
E See Note 3

12-5/8"
(321mm) 12-5/8"
(321mm)

9-11/16" 4-1/2" (114mm)


(246mm) 9-11/16" 4-1/2"
(246mm) (114mm)
7-7/8"
7-7/8"
(200mm)
(200mm)
MODELS PB-350A THRU PB-1100A
MODEL PB-1350A

5-1/2" (140mm) See Note 1


3-1/4" (85mm) See Note 2

3"
Drain Outlet (76mm)
Location 8"
1-1/4" (32mm) F.P.T. 6" (203mm)
See Note 3
(152mm)
3"
ALL MODELS 1-1/2"
(76mm)

(38mm)
DPN00696
1. Multiple knockouts of 1-3/8" (35mm), 1-3/4" (45mm) and 2-1/2" (64mm) for main power supply (typical).
2. 7/8" (22.2mm) knockouts for Liebert Lee-Temp power supply (typical). Rev. 1
3. Cover plate for access of liquid line and hot gas line.

Table 70 Dimensions—Piggyback condensers, in. (mm)


Model A B C D E F G
PB-350A — — 27-1/4 (692) 2-1/2 (64) 6 (152) 10-1/8 (267) 28-3/4 (730)
PB-550A — — 27-1/4 (692) 2-1/2 (64) 6 (152) 10-1/8 (267) 28-3/4 (730)
PB-675A — — 27-1/4 (692) 2-1/2 (64) 6 (152) 10-1/8 (267) 28-3/4 (730)
PB-925A — — 27-1/4 (692) 2-1/2 (64) 6 (152) 10-1/8 (267) 28-3/4 (730)
PB-1100A — — 27-1/4 (692) 2-1/2 (64) 6 (152) 10-1/8 (267) 28-3/4 (730)
PB-1350A 11-1/4 (286) 24 (610) 26-1/2 (673) 7 (178) 6 (152) — —
Table 71 Piping connection sizes, ODS, in. (mm)
Model Liquid Line Hot Gas Line Drain
PB-350A 2 @ 1/2 (13) 2 @ 5/8 (16) 1-1/4 (32)
PB-550A 2 @ 1/2 (13) 2 @ 5/8 (16) 1-1/4 (32)
PB-675A 2 @ 1/2 (13) 2 @ 7/8 (22) 1-1/4 (32)
PB-925A 2 @ 1/2 (13) 2 @ 7/8 (22) 1-1/4 (32)
PB-1100A 2 @ 5/8 (16) 2 @ 1-1/8 (29) 1-1/4 (32)
PB-1350A 2 @ 5/8 (16) 2 @ 1-1/8 (29) 1-1/4 (32)

See Figures 89 and 90 for piggyback condenser piping schematic with Liebert Lee-Temp .

147 Liebert® DS™


Heat Rejection—Liebert Fin/Tube Drycoolers and Pumps

15.0 HEAT REJECTION—LIEBERT FIN/TUBE DRYCOOLERS AND PUMPS

15.1 Drycooler Selection—Prop Fan Drycoolers


Table 72 Liebert DS drycooler selection
Drycooler Type
Outdoor Drycooler Outdoor Quiet-Line Drycooler
Liebert DS
Model 95°F (35°C) 100°F (38°C) 105°F (41°C) 95°F (35°C) 100°F (38°C) 105°F (41°C)
028 D-174 D-225-16 D-310-16 D-173-16 D-205-16 D-356-32
035 D-174 D-225-16 D-350-16 D-178-16 D-205-16 D-356-32
042 D-225-16 D-310 D-419 D-205 D-347-32 D-453-32
053 D-260 D-350 D-491-32 DD-248 D-347-32 D-453-32
070 D-310 D-419 D-620-32 D-347-32 D-453-32 D-453-32
077 D-350 D-466 D-650-40 D-347-32 D-453-32 N/A
105 D-466 D-620-32 D-880-52 D-453 N/A N/A

15.2 Liebert Drycooler Data


Table 73 Liebert standard drycooler performance data, 60Hz
Internal Sound
Number Volume, Dry Weight CFM, (l/s) Sound Power Pressure
Model # of Fans gal. (L) lb. (kg) 60Hz LwA dBA
-174 6.9 (26.2) 540 (245) 13265 (6261) 91.0 75.5
2
-225 11.1 (42.1) 620 (281) 12177 (5748) 91.1 75.5
-260 10.0 (37.8) 735 (333) 19898 (9392) 94.0 77.3
-310 3 13.1 (50.0) 795 (361) 18965 (8951) 94.0 77.3
-350 19.4 (73.3) 855 (388 17398 (8212) 94.0 77.3
-419 17.4 (65.9) 1020 (463) 23650 (11163) 94.4 78.5
-466 4 22.0 (83.3) 1050 (476) 22770 (10747) 94.4 78.5
-491 26.3 (99.6) 1100 (499) 21700 (10242) 94.4 78.5
-620 27.0 (102.2) 1780 (808) 37930 (17901) 96.8 80.3
6
-650 33.0 (124.9) 1780 (808) 36531 (17241) 96.8 80.3
-880 8 44.0 (166.5) 2330 (1058) 45500 (21474) 97.4 81.5
All drycooler fan motors are 3/4 hp.

Table 74 Liebert Quiet-Line™ drycooler performance data, 60Hz


Internal Sound
Number Volume, Dry Weight CFM, l/s Sound Power Pressure
Model # of Fans gal. (L) lb. (kg) 60Hz LwA dBA
-173 13.1 (50.0) 795 (361) 8520 (14477) 74.8 61.3
3
-178 19.4 (73.3) 855 (388) 7440 (12642) 74.8 61.3
-205 13.1 (50.0) 940 (426) 11680 (19847) 76.2 62.5
4
-248 17.4 (65.9) 1020 (463) 11360 (19303) 76.2 62.5
-347 27.0 (102.2) 1780 (808) 17040 (8042) 78.4 64.3
6
-356 39.3 (148.8) 1880 (854) 14880 (7023) 78.4 64.3
-453 8 35.0 (132.5) 2250 (1022) 22720 (10723) 79.9 65.5

Liebert® DS™ 148


Heat Rejection—Liebert Fin/Tube Drycoolers and Pumps

15.3 Dimensional Information


15.3.1 Dimensions—Prop Fan Drycoolers
Figure 117 Dimensions—2-fan fin/tube drycooler models

43-9/16"
(1106mm)
91-1/2"
(2324mm)

37-7/8"
(962mm)

18"
(457mm)

84" Emerson recommends a


(2134mm) clearance of 36" (915mm) on
43-3/16" each side for proper operation
(1097mm) and component access.

Figure 118 Dimensions—3- and 4-fan fin/tube drycooler models

43-9/16"
(1106mm)
131-1/2"
(3340mm)
37-7/8" 43-9/16"
(962mm) (1106mm)

171-1/2"
(4356mm)
18" 70"
(457mm)
(1778mm) 37-7/8"
(962mm)
124"
Eyebolts
(3150mm)
for Lifting
43-3/16"
18"
(1097mm) (457mm)

Note:
Overall height to the top of fan guard 164"
43-1/8" (1095mm) (4166mm)

Emerson recommends a
43-3/16" clearance of 36" (915mm) on
(1097mm) each side for proper operation
and component access.

149 Liebert® DS™


Heat Rejection—Liebert Fin/Tube Drycoolers and Pumps

Figure 119 Dimensions—6- and 8-fan fin/tube drycooler models

87-1/8"
131-1/2" (2213mm)
(3340mm) 87-1/8"
(2213mm)
171-1/2"
37-7/8" (4356mm)
(962mm)
37-7/8"
(962mm)

59"
(1499mm)
18"
(457mm)
18"
(457mm)
124"
86-3/4" (3150mm) 70" (1778mm)
(2203mm) 164"
1-1/2" (38mm) (4166mm)
diameter hole for
rigging (typ.4)
Overalll height to the top
of the fan guard is 43-1/8” (1095mm). 86-3/4" Emerson recommends a
clearance of 36" (915mm) on
(2203mm)
each side for proper
operation and component

Liebert® DS™ 150


Heat Rejection—Liebert Fin/Tube Drycoolers and Pumps

15.4 Electrical Data


15.4.1 Electrical Data—Prop Fan Drycoolers
Table 75 60Hz electrical values—Prop fan drycoolers without pump controls, standard models
Drycooler Model
Electrical 174, 225 260, 310, 350 419, 466, 491 620, 650 880
Voltage Phase Value 2 Fans 3 Fans 4 Fans 6 Fan 8 Fans
FLA 7.0 10.5 14.0 21.0 28.0
208/230 3 WSA 7.9 11.4 14.9 21.9 28.9
OPD 15 15 20 25 35
FLA 3.4 5.1 6.8 10.2 13.6
460 3 WSA 3.8 5.5 7.2 10.6 14.0
OPD 15 15 15 15 20
FLA 2.8 4.2 5.6 8.4 11.2
575 3 WSA 3.2 4.6 6.0 8.8 11.6
OPD 15 15 15 15 15

Table 76 60Hz electrical values—Prop fan drycoolers without pump controls, Liebert Quiet-Line™
models
Drycooler Model
Electrical 173, 178 205, 248 347, 356 453
Voltage Phase Value 3 Fans 4 Fans 6 Fans 8 Fans
3 FLA 5.4 7.2 10.8 14.4
208/230 3 WSA 5.9 7.7 11.3 14.9
3 OPD 15 15 15 20
3 FLA 2.7 3.6 5.4 7.2
460 3 WSA 2.9 3.8 5.6 7.4
3 OPD 15 15 15 15
3 FLA 2.1 2.8 4.2 5.6
575 3 WSA 2.3 3.0 4.4 5.8
3 OPD 15 15 15 15

151 Liebert® DS™


Heat Rejection—Liebert Fin/Tube Drycoolers and Pumps

Table 77 60Hz electrical values—Standard prop fan drycoolers with integral pump controls
Number of Fans
2 3 4 6 8
Model # 174, 225 260, 310, 350 419, 466, 491 620, 650 880
Pump HP FLA WSA OPD FLA WSA OPD FLA WSA OPD FLA WSA OPD FLA WSA OPD
208/230/3/60
0.75 10.5 11.4 15 14.0 14.9 20 17.5 18.4 25 24.5 25.4 30 31.5 32.4 40
1.5 13.6 15.3 20 17.1 18.8 25 20.6 22.3 25 27.6 29.3 35 34.6 36.3 40
2.0 14.5 16.4 20 18.0 19.9 25 21.5 23.4 30 28.5 30.4 35 35.5 37.4 45
3.0 17.6 20.3 30 21.1 23.8 30 24.6 27.3 35 31.6 34.3 40 38.6 41.3 50
5.0 23.7 27.9 40 27.2 31.4 45 30.7 34.9 50 37.7 41.9 50 44.7 48.9 60
7.5 31.2 37.3 60 34.7 40.8 60 38.2 44.3 60 45.2 51.3 70 52.2 58.3 80
10.0 37.8 45.5 70 41.3 49.0 70 44.8 52.5 80 51.8 59.5 90 58.8 66.5 90
15 53.2 64.8 110 56.7 68.3 110 60.2 71.8 110 67.2 78.8 110 74.2 85.8 125
460/3/60
0.75 5.0 5.4 15 6.7 7.1 15 8.4 8.8 15 11.8 12.2 15 15.2 15.6 20
1.5 6.4 7.2 15 8.1 8.9 15 9.8 10.6 15 13.2 14.0 20 16.6 17.4 20
2.0 6.8 7.7 15 8.5 9.4 15 10.2 11.1 15 13.6 14.5 20 17.0 17.9 20
3.0 8.2 9.4 15 9.9 11.1 15 11.6 12.8 15 15.0 16.2 20 18.4 19.6 25
5.0 11.0 12.9 20 12.7 14.6 20 14.4 16.3 20 17.8 19.7 25 21.2 23.1 30
7.5 14.4 17.2 25 16.1 18.9 25 17.8 20.6 30 21.2 24.0 30 24.6 27.4 35
10.0 17.4 20.9 30 19.1 22.6 35 20.8 24.3 35 24.2 27.7 40 27.6 31.1 45
15 24.4 29.7 50 26.1 31.4 50 27.8 33.1 50 31.2 36.5 50 34.6 39.9 60
575/3/60
0.75 4.1 4.5 15 5.5 5.9 15 6.9 7.3 15 9.7 10.1 15 12.5 12.9 15
1.5 5.2 5.8 15 6.6 7.2 15 8.0 8.6 15 10.8 11.4 15 13.6 14.2 20
2.0 5.5 6.2 15 6.9 7.6 15 8.3 9.0 15 11.1 11.8 15 13.9 14.6 20
3.0 6.7 7.7 15 8.1 9.1 15 9.5 10.5 15 12.3 13.3 15 15.1 16.1 20
5.0 8.9 10.4 15 10.3 11.8 15 11.7 13.2 15 14.5 16.0 20 17.3 18.8 20
7.5 11.8 14.1 20 13.2 15.5 20 14.6 16.9 25 17.4 19.7 25 20.2 22.5 30
10.0 13.8 16.6 25 15.2 18.0 25 16.6 19.4 30 19.4 22.2 30 22.2 25.0 35
15 19.8 24.1 40 21.2 25.5 40 22.6 26.9 40 25.4 29.7 45 28.2 32.5 45

Liebert® DS™ 152


Heat Rejection—Liebert Fin/Tube Drycoolers and Pumps

Table 78 60Hz electrical values—Liebert Quiet-Line™ drycoolers with integral pump controls
Number of Fans
3 4 6 8
Model # 173, 178 205, 248 347, 356 453
Pump H.P. FLA WSA OPD FLA WSA OPD FLA WSA OPD FLA WSA OPD
208/230/3/60
0.75 8.9 9.8 15.0 10.7 11.6 15.0 14.3 15.2 20.0 17.9 18.8 25.0
1.5 12.0 13.7 20.0 13.8 15.5 20.0 17.4 19.1 25.0 21.0 22.7 25.0
2.0 12.9 14.8 20.0 14.7 16.6 20.0 18.3 20.2 25.0 21.9 23.8 30.0
3.0 16.0 18.7 25.0 17.8 20.5 30.0 21.4 24.1 30.0 25.0 27.7 35.0
5.0 22.1 26.3 40.0 23.9 28.1 40.0 27.5 31.7 45.0 31.1 35.3 50.0
7.5 * 29.6 35.7 50.0 31.4 37.5 60.0 35.0 41.1 60.0 38.6 44.7 60.0
10.0 2 36.2 43.9 70.0 38.0 45.7 70.0 41.6 49.3 80.0 45.2 52.9 80.0
15 2 51.6 63.2 100.0 53.4 65.0 110.0 57.0 68.6 110.0 60.6 72.2 110.0
460/3/60
0.75 4.3 4.7 15.0 5.2 5.6 15.0 7.0 7.4 15.0 8.8 9.2 15.0
1.5 5.7 6.5 15.0 6.6 7.4 15.0 8.4 9.2 15.0 10.2 11.0 15.0
2.0 6.1 7.0 15.0 7.0 7.9 15.0 8.8 9.7 15.0 10.6 11.5 15.0
3.0 7.5 8.7 15.0 8.4 9.6 15.0 10.2 11.4 15.0 12.0 13.2 15.0
5.0 10.3 12.2 15.0 11.2 13.1 20.0 13.0 14.9 20.0 14.8 16.7 20.0
7.5 * 13.7 16.5 25.0 14.6 17.4 25.0 16.4 19.2 30.0 18.2 21.0 30.0
10.0 2 16.7 20.2 30.0 17.6 21.1 35.0 19.4 22.9 35.0 21.2 24.7 35.0
15 2 23.7 29.0 45.0 24.6 29.9 50.0 26.4 31.7 50.0 28.2 33.5 50.0
575/3/60
0.75 3.4 3.7 15.0 4.1 4.4 15.0 5.5 5.8 15.0 6.9 7.2 15.0
1.5 4.5 5.1 15.0 5.2 5.8 15.0 6.6 7.2 15.0 8.0 8.6 15.0
2.0 4.8 5.5 15.0 5.5 6.2 15.0 6.9 7.6 15.0 8.3 9.0 15.0
3.0 6.0 7.0 15.0 6.7 7.7 15.0 8.1 9.1 15.0 9.5 10.5 15.0
5.0 8.2 9.7 15.0 8.9 10.4 15.0 10.3 11.8 15.0 11.7 13.2 15.0
7.5 2 11.1 13.4 20.0 11.8 14.1 20.0 13.2 15.5 20.0 14.6 16.9 25.0
10.0 2 13.1 15.9 25.0 13.8 16.6 25.0 15.2 18.0 25.0 16.6 19.4 30.0
15 2 19.1 23.4 40.0 19.8 24.1 40.0 21.2 25.5 40.0 22.6 26.9 40.0
1. Values are calculated per UL 1995. Pump FLA values used are based on NEC tables for motor horsepower. OPD values may be
adjusted higher than calculations to compensate for maximum anticipated application temperatures.
2. May require electrical component(s) with higher capacity in the drycooler. Consult factory representatives for assistance before
ordering.

153 Liebert® DS™


Heat Rejection—Liebert Fin/Tube Drycoolers and Pumps

Figure 120 Electrical field connections for fluid temperature control, direct-drive Drycoolers

Electrical service connection


Factory-wired to 24V terminals when factory
Class 2 control circuit disconnect is not supplied.
Factory-wired to components Electric service connection
Fuse block supplied on terminals when factory
on electric panel
DNT drycoolers. disconnect is supplied.

Factory-installed
Unit Alarm Connection disconnect switch
Field-supplied 24V. (optional).
Class 2 wiring to
Terminals "24 & 50"
to indicate "Standby Glycol
Pump On". (Supplied
with dual pump controls
only.)

Control interlock
Field-supplied
Class 2 wiring to
interlock drycooler
24V controls to
Liebert room unit
(Not required on
CSU 3000). 7/8" Pump fuses & overload
(22.2mm) diameter heaters (shipped with
hole provided in standard pump packages)
bottom of electric box. are to be field-installed in
pump fuse block(s) and
Flow switch connection starter(s).
(Dual pump controls only)
Earth ground bar (50Hz).
Field-supplied 24V Class 2
Connection terminals with factory
wiring from terminals 74 +
ground from each high voltage
77 to field mounted flow
component for field-supplied
switch.
earth grounding wire. Electric service entrance. Electric service.
Electric service connection A 7/8" (22.2mm) diameter hole not by Emerson.
terminals for power supply to in a 1-1/8" (28.6mm) knockout (Field-wired to Liebert
pumps when pump controls Earth ground connection (60 HZ). provided in bottom of electric CSU 3000.
are factory-supplied. Dual Connection terminal for field- box. Interconnecting wiring
pump connection shown. 7/8" supplied earth grounding wire. not by Emerson).
(22.2mm) diameter knockouts
provided in bottom DPN000276
of electric box. Refer to specification sheet for full load amp and wire size amp ratings.
Rev. 1

Liebert® DS™ 154


Heat Rejection—Liebert Fin/Tube Drycoolers and Pumps

15.5 Piping Connections


Table 79 Standard drycooler piping connection sizes and internal volume
Inlet & Outlet Connection Size
Drycooler No. of Internal No. of Internal Volume, No. of
Model # Coil Circuits Fans gal. (L) Inlets/Outlets OD Copper, in. ID Sweat, in.
174 16* 6.9 (26.2) 1/1 2-1/8 —
2
225 16 11.1 (42.1) 1/1 2-1/8 —
260 24* 10.0 (37.8) 1/1 2-1/8 —
310 16 3 13.1 (50.0) 1/1 2-1/8 —
350 16 19.4 (73.3) 1/1 2-1/8 —
419 32* 17.4 (65.9) 1/1 2-1/8 —
466 40* 4 22.0 (83.3) 1/1 2-5/8 —
491 32 26.3 (99.6) 1/1 2-1/8 —
620 32 27.0 (102.2) 2/2 — 2-1/8
6
650 40 33.0 (124.9) 2/2 — 2-1/8
880 52 8 44.0 (166.5) 2/2 — 2-1/8
* = Standard Circuiting

Table 80 Liebert Quiet-Line drycooler piping connection sizes and internal volume
Inlet & Outlet Connection Size
Drycooler No. of Internal No. of Internal Volume No. of
Model # Coil Circuits Fans gal. (L) Inlets/Outlets OD Copper, in. ID Sweat, in.
173 16, 32* 3 13.1 (50.0) 1/1 2-1/8 —
178 16, 32* 19.4 (73.3) 1/1 2-1/8 —
205 16 13.1 (50.0) 1/1 2-1/8 —
4
248 32* 17.4 (65.9) 1/1 2-1/8 —
347 32 27.0 (102.2) 2/2 — 2-1/8
6
356 32 39.3 (148.8) 2/2 — 2-1/8
453 32 8 35.0 (132.5) 2/2 — 2-1/8
* = Standard circuiting

155 Liebert® DS™


Heat Rejection—Liebert Fin/Tube Drycoolers and Pumps

Figure 121 Piping—Direct-drive drycoolers

Inlet Connection
(Upper Header)
Outlet Connection
(Lower Header)

DPN000275
1/2" FPT Connections Rev. 3
EXPANSION TANK
(GLYCOOL CSU 3000
Units Supplied with
Compression Tank)

Figure 122 Piping—6 and 8 fan drycoolers

Inlet
Connections

(4 Inlet, 4 Outlet
Connections Shown)
See table for actual DPN002429
number provided. Rev. 0
Outlet Connections

Liebert® DS™ 156


Heat Rejection—Liebert Fin/Tube Drycoolers and Pumps

Figure 123 Typical piping arrangement, multiple prop fan drycoolers and multiple indoor units

Expansion Tank
Gal. (L)

Total
FS GPM
(L/s):
Drycooler No. 1 Model Cooling Unit # Pipe
GPM (L/s) P: Ft (kPA) Model Diam.: In. (mm)
P: Ft. (kPa)
GPM (L/s)
Cooling Unit #
P Ft (kPa):
Model
Cooling Unit # GPM (L/s)
Model P Ft (kPa):
GPM (L/s)
Cooling Unit #
P Ft (kPa):
See Note 3 Model
Cooling Unit # GPM (L/s)
Model P Ft (kPa):
GPM (L/s)
Cooling Unit #
P Ft (kPa):
Model
Cooling Unit # GPM (L/s)
Model P Ft (kPa):
Drycooler No. 2 Model
GPM (L/s) P: Ft (kPA) GPM (L/s)
Cooling Unit #
P Ft (kPa):
LEGEND Model
Gate Valve Cooling Unit # GPM (L/s)
Model P Ft (kPa):
Check Valve
GPM (L/s)
Butterfly Valve P Ft (kPa):
Cooling Unit #
Model
Relief Valve
Cooling Unit # GPM (L/s)
Union P Ft (kPa):
Model
Ball Or Flow Control Valve GPM (L/s)
Cooling Unit #
P Ft (kPa):
FS Flow Switch Model
P:Pressure Drop GPM (L/s)
P Ft (kPa):
Strainer Filter
Notes:
1. Pressure and temperature gauges (or ports for same) are recommended to monitor
component pressure drops and performance.
2. Flow measuring devices, drain and balancing valves to be supplied by others and
located as required.
3. See product literature for installation guidelines and clearance dimensions.
4. Drawing shows dual pump package. Alternate pump packages with more pumps may be DPN000991
considered, consult supplier Rev. 0

157 Liebert® DS™


Heat Rejection—Piggyback Drycoolers

16.0 HEAT REJECTION—PIGGYBACK DRYCOOLERS

16.1 Drycooler Selection—Indoor Piggyback Drycoolers


Table 81 Liebert indoor piggyback drycooler/DS matchup data
Drycooler Selections Liebert DS Model
Drycooler Type Ambient Temp. °F (°C) 028 035 042 053 070 077
95 (35) PD-133/150 PD-150 PD-223 PD-290 PD-333 PD-333
Piggyback
100 (38) PD-223 PD-223 PD-333 N/A N/A N/A
Drycooler
105 (41) PD-333 PD-333 PD-333 N/A N/A N/A
Table 82 Indoor piggyback airflow and static pressure data
Horsepower/rpm
Ext. Static Pressure - in. (Pa)
Model No. of Fans CFM (m3/hr) 0.25 (62.3) 0.50 (125) 0.75 (187) 1.0 (249)
PD-133
2 6900 (11,730 2/605 3/680 3/750 3/820
PD-150
PD-223 2 12,500 (21,250 7.5/760 7.5/810 7.5/870 7.5/920
PD-290 2 12,300 (20,910 7.5/780 7.5/830 7.5/890 7.5/940
PD-333 2 16,500 (28,050 10/640 10/695 10/740 15/790
1. Values are without filter box. External Static Pressure = filter pressure drop + other static drops.
2. Source: DPN000695, Rev. 0

16.2 Electrical Data—Piggyback Drycoolers


Table 83 Electrical data, piggyback drycoolers, 60Hz, 3 phase
Drycooler Drycooler Drycooler - Optional
No Pumps Standard Pump Package Pump Package
Pump
Total Unit Pump Only Total Unit Only Total Unit
Blower
Model Voltage Motor hp FLA WSA OPD hp FLA FLA WSA OPD hp FLA WSA OPD
208 3 10.6 13.3 20 1.5 6.6 17.2 19.9 30 2 18.1 20.8 30
230 3 9.6 12.0 20 1.5 6.0 15.6 18 25 2 16.4 18.8 25
PD-133
460 3 4.8 6.0 15 1.5 3.0 7.8 9 15 2 8.2 9.4 15
575 3 3.9 4.9 15 1.5 2.4 6.3 7.3 15 2 6.6 7.6 15
208 3 10.6 13.3 20 2 7.5 18.1 20.8 30 3 21.2 23.9 30
230 3 9.6 12.0 20 2 6.8 16.4 18.8 25 3 19.2 21.6 30
PD-150
460 3 4.8 6.0 15 2 3.4 8.2 9.4 15 3 9.6 10.8 15
575 3 3.9 4.9 15 2 2.7 6.6 7.6 15 3 7.8 8.8 15
208 7.5 24.2 30.3 50 3 10.6 34.8 40.9 60 5 40.9 47 70
230 7.5 22.0 27.5 45 3 9.6 31.6 37.1 50 5 37.2 42.7 60
PD-223
460 7.5 11.0 13.8 20 3 4.8 15.8 18.6 25 5 18.6 21.4 30
575 7.5 9.0 11.3 20 3 3.9 12.9 15.2 20 5 15.1 17.4 25
208 7.5 24.2 30.3 50 5 10.6 40.9 47 60 3 34.8 40.9 60
230 7.5 22.0 27.5 45 5 9.6 37.2 42.7 30 3 31.6 37.1 50
PD-290
460 7.5 11.0 13.8 20 5 4.8 18.6 21.4 25 3 15.8 18.6 25
575 7.5 9.0 11.3 20 5 3.9 15.1 17.4 20 3 12.9 15.2 20
208 10 30.8 38.5 60 5 10.6 47.5 55.2 80 3 41.4 49.1 70
230 10 28.0 35.0 60 5 9.6 43.2 50.2 70 3 37.6 44.6 70
PD-333
460 10 14.0 17.5 30 5 4.8 21.6 25.1 35 3 18.8 22.3 35
575 10 11.0 13.8 20 5 3.9 17.1 19.9 30 3 14.9 17.7 25
ph = phase; FLA = Full Load Amps; WSA = Wire Size Amp; OPD = Maximum Overcurrent Protection Device
Source: DPN000710, Rev. 0

Liebert® DS™ 158


Heat Rejection—Piggyback Drycoolers

16.3 Dimensions—Indoor Piggyback Drycoolers


Figure 124 Dimensions—Indoor piggyback drycoolers
1-1/8"
(29mm) E
H
K J D
R B
Over
sions all Dim
Dimen ensio
K Overall ns
Optional Fan
Discharge
S
Disconnect
H
Switch
J
35-1/8" R
72"
(892mm) Fan Discharge (1829mm)

Shaded areas indicate


a recommended
clearance of 34" (864mm)
for component access.
5"
(127mm)

G 1"
A (25.4mm)
Condenser Coil Inlet 10" C Unit Base
and Duct Connection (254mm) Unit Base

Drain Outlet UNIT DIMENSIONS


C Opening FAN DISCHARGE DATA
15-7/16" REAR DISCHARGE
(392mm)
OPTIONAL TOP DISCHARGE
Floor Level
PUMP PACKAGE SELECTION
A F
SINGLE PUMP PACKAGE
Rear of DUAL PUMP PACKAGE
Cabinet DPN000710
FLOOR CUTOUT DIMENSIONS Rev. 2

Table 84 Dimensions—Indoor piggyback drycoolers, in (mm)


Model A B C D E F G H J K R S
72 74 31 32 1-1/8 33 60 8-5/8 50-3/16 16-1/16 13-3/16 14-11/16
PD-133
(1829) (1880) (787) (813) (29) (838) (1524) (219) (1275) (408) (335) (373)
72 74 31 32 1-1/8 33 60 8-5/8 50-3/16 16-1/16 13-3/16 14-11/16
PD-150
(1829) (1880) (787) (813) (29) (838) (1524) (219) (1275) (408) (335) (373)
97 99 33 34 3-1/8 46-1/2 85 23-5/16 50-3/16 16-1/16 23-1/2 14-11/16
PD-223
(2464) (2515) (838) (864) (79) (1181) (2159) (592) (1275) (408) (597) (373)
97 99 33 34 3-1/8 46-1/2 85 23-5/16 50-3/16 16-1/16 23-1/2 14-11/16
PD-290
(2464) (2515) (838) (864) (79) (1181) (2159) (592) (1275) (408) (597) (373)
97 99 33 34 3-1/8 46-1/2 85 16-5/16 63-7/8 19-1/8 16-13/16 11-5/8
PD-333
(2464) (2515) (838) (864) (79) (1181) (2159) (421) (1622) (486) (427) (295)
1. A 1" (25.4mm) flange is provided on all units for duct connection to coil duct opening and fan air discharge opening.
2. Source: DPN000710, Rev. 1

159 Liebert® DS™


Heat Rejection—Piggyback Drycoolers

16.4 Piping
Figure 125 Piping—Indoor piggyback drycooler models

See
See Note 4
Note 4
See
See Note 1
Note 1
See Note 2 D

1-13/16" E
A (46mm) A
E

C
C
B B
1-13/16"
(46mm) See Note 2
D 3" (76mm) 3" (76mm)

1" (25mm) 1" (25mm)


Panel Panel
3" (76mm) See Note 1 3" (76mm)
See Note 1 3" (76mm)
See Note 4 See Note 4 3" (76mm)
C See Note 2
C
See Note 2

12-5/8"
12-5/8"
(321mm)
(321mm)

4-1/2"
9-11/16" (114mm) 9-11/16" 4-1/2"
(246mm) 7-7/8" (246mm) (114mm)
(200mm) 7-7/8"
(200mm)
MODELS PD-102 THRU PD-290
MODEL PD-333
5-1/2" (140mm) See Note 1
3-1/4" (85mm)
See Note 4

Drain Outlet
Location 3"
1-1/4" (32mm) F.P.T. (76mm)
8"
See 6" (1
52m (203mm)
Note 2 m)
3" (7
NOTES 6mm
1-1/2 )
1. Multiple knockouts of 1-3/8" (35mm), 1-3/4" (45mm) and " (38
mm)
2-1/2" (64mm) for main power supply (typical).
2. Cover plate for access of glycol piping inlet and outlet. ALL MODELS
3. Piggyback drycooler connection sizes for supply and return
glycol lines are the same as room unit supply and return lines.
FE/FH 110G 1-5/8" (41mm); FE/FH116G - 2-1/8" (54mm).
Note applies to PD-133. DPN000711
4. 7/8" (22.2mm) knockout provided. Rev. 1

Table 85 Dimensions—Indoor piggyback drycoolers Table 86 Pipe connection sizes, ODS


Model # A B C D E Model # Glycol Supply Glycol Ret. Drain
PD-133 27-1/4 (692) 2-1/2 (64) 6 (152) 9-1/8 (232) 28-3/4 (730) PD-133 See Note 3 See Note 3 1-1/4 (32)
PD-150 27-1/4 (692) 2-1/2 (64) 6 (152) 9-1/8 (232) 28-3/4 (730) PD-150 2-1/8 (54) 2-1/8 (54) 1-1/4 (32)
PD-223 27-1/4 (692) 2-1/2 (64) 6 (152) 9-1/8 (232) 28-3/4 (730) PD-223 2-1/8 (54) 2-1/8 (54) 1-1/4 (32)
PD-290 27-1/4 (692) 2-1/2 (64) 6 (152) 9-1/8 (232) 28-3/4 (730) PD-290 2-1/8 (54) 2-1/8 (54) 1-1/4 (32)
PD-333 26-1/2 (673 6 (152) 7 (178) 11-1/4 (286) 24 (610) PD-333 2-1/8 (54) 2-1/8 (54) 1-1/4 (32)
Source: DPN000711, Rev. 1 Source: DPN000711, Rev. 1

Liebert® DS™ 160


Pump Packages and Expansion Tank

17.0 PUMP PACKAGES AND EXPANSION TANK

Figure 126 Single pump package piping connections and dimension

17-1/4"
SINGLE PACKAGE 0.75 - 7.5 HP (438.2mm)

1
3
19"
(482.6mm)

2-7/8"
15-7/8" (72.9mm)
(403.2mm)

1-3/4"
6-3/8"
(44.4mm)
(161.9mm)

8-3/4"
(222.3mm)

12-1/4"
(311.1mm) 30"
(762mm)
17"
(431.8mm)
PUMP PACKAGE MOUNTING ANGLES
(Angles are inside, bottom
of pump package. View used for
1 3" (76.2mm) diameter pump suction mounting reference.)
connection knockouts 4

2 3" (76.2mm) diameter pump discharge


connection knockouts
3 7/8" (22.2mm) diameter electrical knockouts
4
4 1/2" (12.7mm) diameter holes for mounting

3/4"
(19mm)

C
A DPN000278
Rev. 0
B

Table 87 Mounting hole dimensions, in. (mm)


Pump Package A B C
Single (0.75 - 7.5hp) 15-1/4 (387.4) 2-1/2 (63.5) 22-1/2 (571.5)
Dual (0.75 - 5hp) 30-1/4 (768.4) 2-1/2 (63.5) 22-1/2 (571.5)
Dual (7.5hp) 39-5/16 (998.5) 1-3/4 (44.5) 26-7/8 (682.6)
Source: DPN000278, Rev. 0

161 Liebert® DS™


Pump Packages and Expansion Tank

Figure 127 Dual pump package piping connections and dimensions


DUAL PACKAGE 0.75 - 5 HP
See Figure 126 and Table 87 for
2 mounting angles and dimensions
1 32-1/4"
(819.2mm)
2
3
1

3
4-1/8"
6-3/8" (104.8mm)
15-7/8" (161.9mm) "
2-7/8" 19"
(403.2mm) (482.6mm)
(73mm)

8-3/4" (222.2mm) 1-3/4"


(44.4mm)
12-1/4"
(311.1mm)

23-3/4" 30"
(603.2mm) (762mm)
27-1/4" 1 3" (76.2mm) diameter pump suction
(692.1mm) connection knockouts
32" 2 3" (76.2mm) diameter pump discharge
(812.8mm) connection knockouts
3 7/8" (22.2mm) diameter electrical knockouts
5 5" (127mm) diameter pump discharge
connection hole
6 5" (127mm) diameter pump suction
connection hole
32-3/8"
DUAL PACKAGE 7.5 HP 3 41-1/4"
(822.3mm)
5 (1047.8mm)
6
5
6

19-15/16
(506.4mm)

11-7/8
(301.6mm)
15-7/8
(403.2mm)

33-3/16" 16-3/8"
(843mm) (415.9mm)
29-3/16"
(741.4mm)

6-1/2" DPN000328
41"
(165.1mm)
(1041.4mm) Rev. 0

Liebert® DS™ 162


Pump Packages and Expansion Tank

Figure 128 Pump package expansion tank


30-1/2"
(774.7mm)
6-13/16" 17-1/4"
1/2" F.P.T. Ø 9" 1/2" F.P.T.
(173mm) (438.2mm)
Fitting (228.6mm) Fitting

2-3/4" 2-1/2"
(69.9mm) (63.5mm) 7"
(177.8mm)

4" Ø 1/2" (12.7mm)


1"
1" (101.6mm) 8 Holes
(25.4mm)
(25.4mm)
1-1/2" 1-1/2"
(38.1mm) 6-1/8" (38.1mm) DPN000329
8.8 gal. (33.3 L)
(155.6mm) 3" Expansion Tank Rev. 0
(76.2mm)

Expansion Tank (P/N 1C16717P1)


This tank, included in a standard pump package, has an internal volume of 8.8 gal. (33 l) and a
maximum pressure of 100 psi (690 kPa).
This tank is sized for a typical “open” system with a fluid volume of less than 75 gal. (280l). When
used in a “closed” system, volumes of up to 140 gal. (910l) can be accommodated. The use of a safety
relief valve, field-supplied, is recommended for systems “closed” to atmospheric venting. Other piping
accessories for filling, venting, or adjusting the fluid in the system, are recommended, but not
included.
Table 88 Glycol pump data
Connections Electric @ 60Hz
Female
Pump NPT Suction Discharge
HP Connection Connection ph 208 FLA 230 FLA 460 FLA 575 FLA
3/4 1-1/4" 3/4" 1 7.6 6.9 N/A N/A
3/4 1-1/4" 3/4" 3 3.5 3.2 1.6 1.3
1-1/2 1-1/4" 3/4" 3 6.6 6.0 3.0 2.4
2 1-1/4" 3/4" 3 7.5 6.8 3.4 2.7
3 1-1/2" 1" 3 10.6 9.6 4.8 3.9
5 1-1/2" 1-1/4" 3 16.7 15.2 7.6 6.1
7-1/2 * 3" 3" 3 24.2 22.0 11.0 9.0
* May require electrical component(s) with higher capacity in the drycooler. Consult factory representative
for assistance before ordering.

• To Calculate Total Pump and Drycooler Full Load Amps (FLA):


Total FLA = Pump FLA + Drycooler FLA
• To Calculate Total Pump and Drycooler Wire Size Amps (WSA):
Total WSA = Largest Motor FLA x 1.25 + Sum of other Motor FLA values
• To Calculate Total Pump and Drycooler Maximum Overcurrent Protective Device (OPD):
Total OPD = Largest Motor FLA x 2.25 + Sum of other Motor FLA values
Select standard fuse size (15A, 20A, 25A, 30A, etc.)

163 Liebert® DS™


Pump Packages and Expansion Tank

Figure 129 Pump curve, 60 Hz


180
Curve HP
A 3/4 (1-ph)
160 B 3/4 (3-ph)
C 1.5
Total Head, Feet/Water

140 D 2
F E 3
F 5
120 E
G 7.5
D
100 G
C

80 B

A
60

40

20
0 10 20 30 40 50 60 70 80 120 160 200 250 300 400
Flow Rate, GPM
Capacity data is rated and factory-certified per ASHRAE 127-2007 with a 0% tolerance.

Liebert® DS™ 164


U.S. Department of Energy (DOE) Performance Data

APPENDIX A - U.S. DEPARTMENT OF ENERGY (DOE) PERFORMANCE DATA

Table 89 U.S. DOE performance table—Liebert DS upflow and downflow, air-cooled


Total Cooling Capacity Sensible Cooling Capacity
Basic Model Airflow
Number Configuration Btu/hr kW Btu/hr kW CFM SCOP
DS028AD*0* Downflow 104499 30.63 94171 27.60 4210 2.42
DS028AD*1* Downflow 106548 31.23 96218 28.20 4199 2.62
DS028AS*0* Downflow 104158 30.53 93830 27.50 4210 2.6
DS028AS*1* Downflow 106207 31.13 95877 28.10 4199 2.83
DS028AU*0* Downflow 124306 36.43 103725 30.40 4210 2.37
DS028AU*1* Downflow 126697 37.13 106113 31.10 4199 2.54
DS028DD*0* Downflow 103816 30.43 93489 27.40 4210 2.36
DS028DD*1* Downflow 105865 31.03 95536 28.00 4199 2.56
DS028DU*0* Downflow 123623 36.23 103384 30.30 4210 2.32
DS028DU*1* Downflow 126014 36.93 105431 30.90 4199 2.48
DS035AD*0* Downflow 119184 34.93 107137 31.40 4976 2.24
DS035AD*1* Downflow 122940 36.03 110549 32.40 4976 2.5
DS035AS*0* Downflow 123623 36.23 109184 32.00 4976 2.38
DS035AS*1* Downflow 127038 37.23 112596 33.00 4976 2.66
DS035AU*0* Downflow 124989 36.63 109866 32.20 4976 2.33
DS035AU*1* Downflow 128746 37.73 113620 33.30 4976 2.59
DS035DD*0* Downflow 118501 34.73 106113 31.10 4976 2.18
DS035DD*1* Downflow 121916 35.73 109525 32.10 4976 2.42
DS035DU*0* Downflow 123965 36.33 108843 31.90 4976 2.26
DS035DU*1* Downflow 127721 37.43 112596 33.00 4976 2.51
DS042AD*1* Downflow 138649 40.64 125220 36.70 5957 2.32
DS042AS*0* Downflow 133185 39.03 120102 35.20 6029 2.1
DS042AS*1* Downflow 139674 40.94 125903 36.90 5957 2.46
DS042AU*1* Downflow 146504 42.94 129315 37.90 5957 2.35
DS042DD*1* Downflow 136942 40.14 124538 36.50 6053 2.22
DS042DU*1* Downflow 145138 42.54 128632 37.70 6053 2.26
DS053AD*0* Downflow 184069 53.95 166506 48.80 7177 2.49
DS053AD*1* Downflow 187484 54.95 173671 50.90 7714 2.63
DS053AS*0* Downflow 190557 55.85 169918 49.80 7177 2.5
DS053AS*1* Downflow 193972 56.85 177083 51.90 7714 2.63
DS053AU*0* Downflow 182020 53.35 165482 48.50 7177 2.54
DS053AU*1* Downflow 185435 54.35 172306 50.50 7714 2.68
DS053DD*0* Downflow 182361 53.45 164800 48.30 7177 2.41
DS053DD*1* Downflow 185776 54.45 171965 50.40 7714 2.54
DS053DU*0* Downflow 180312 52.85 163776 48.00 7177 2.46
DS053DU*1* Downflow 183727 53.85 170600 50.00 7714 2.59
DS070AD*0* Downflow 227098 66.56 198237 58.10 8613 2.16
DS070AD*1* Downflow 231537 67.86 207450 60.80 9277 2.3
DS070AS*0* Downflow 231879 67.96 200626 58.80 8613 2.18
DS070AS*1* Downflow 236318 69.26 209497 61.40 9277 2.32

165 Liebert® DS™


U.S. Department of Energy (DOE) Performance Data

Table 89 U.S. DOE performance table—Liebert DS upflow and downflow, air-cooled (continued)
Total Cooling Capacity Sensible Cooling Capacity
Basic Model Airflow
Number Configuration Btu/hr kW Btu/hr kW CFM SCOP
DS070AU*0* Downflow 216853 63.56 193460 56.70 8613 2.27
DS070AU*1* Downflow 221634 64.96 202332 59.30 9277 2.43
DS070DD*0* Downflow 224707 65.86 195849 57.40 8613 2.1
DS070DD*1* Downflow 228805 67.06 204720 60.00 9277 2.21
DS070DU*0* Downflow 214462 62.86 190731 55.90 8613 2.18
DS070DU*1* Downflow 218902 64.16 199943 58.60 9277 2.32
DS077AS*1* Downflow 252710 74.07 226216 66.30 10644 2.1
DS077AU*1* Downflow 243490 71.36 221780 65.00 10644 2.15
DS077DU*1* Downflow 241099 70.66 215638 63.20 10063 2.1
DS105AS*1* Downflow 328182 96.18 276372 81.00 13111 1.92
DS105AU*1* Downflow 326474 95.68 283878 83.20 13111 1.9
DS105DU*1* Downflow 322035 94.38 270572 79.30 13087 1.9
VS028AD*0* Upflow 105524 30.93 95195 27.90 4210 2.35
VS028AD*1* Upflow 106548 31.23 96218 28.20 4210 2.45
VS028AS*0* Upflow 104499 30.63 94854 27.80 4210 2.52
VS028AS*1* Upflow 105865 31.03 95877 28.10 4210 2.63
VS028AU*0* Upflow 125672 36.83 105090 30.80 4210 2.31
VS028AU*1* Upflow 126697 37.13 106113 31.10 4210 2.4
VS028DD*0* Upflow 104841 30.73 94854 27.80 4210 2.32
VS028DD*1* Upflow 106207 31.13 95877 28.10 4210 2.42
VS028DU*0* Upflow 125331 36.73 104748 30.70 4210 2.29
VS028DU*1* Upflow 126355 37.03 105772 31.00 4210 2.37
VS035AD*0* Upflow 120550 35.33 108843 31.90 4976 2.21
VS035AD*1* Upflow 122599 35.93 110890 32.50 4976 2.35
VS035AS*0* Upflow 127721 37.43 103042 30.20 4976 2.17
VS035AS*1* Upflow 126697 37.13 112937 33.10 4976 2.49
VS035AU*0* Upflow 126697 37.13 111914 32.80 4976 2.3
VS035AU*1* Upflow 128746 37.73 113961 33.40 4976 2.44
VS035DD*0* Upflow 119867 35.13 110208 32.30 5263 2.16
VS035DD*1* Upflow 121916 35.73 110208 32.30 4976 2.31
VS035DU*0* Upflow 126014 36.93 113278 33.20 5263 2.24
VS035DU*1* Upflow 128063 37.53 113278 33.20 4976 2.4
VS042AD*0* Upflow 135234 39.63 122491 35.90 5933 2.01
VS042AD*1* Upflow 138649 40.64 125903 36.90 5933 2.19
VS042AS*0* Upflow 135917 39.83 122832 36.00 5933 2.13
VS042AS*1* Upflow 139332 40.84 126244 37.00 5933 2.33
VS042AU*0* Upflow 143430 42.04 126585 37.10 5933 2.05
VS042AU*1* Upflow 146845 43.04 129997 38.10 5933 2.23
VS042DD*0* Upflow 130795 38.33 121808 35.70 6029 1.99
VS042DD*1* Upflow 137625 40.34 125220 36.70 5933 2.15
VS042DU*0* Upflow 142747 41.84 125903 36.90 5933 2.01
VS042DU*1* Upflow 145821 42.74 129315 37.90 5933 2.18

Liebert® DS™ 166


U.S. Department of Energy (DOE) Performance Data

Table 89 U.S. DOE performance table—Liebert DS upflow and downflow, air-cooled (continued)
Total Cooling Capacity Sensible Cooling Capacity
Basic Model Airflow
Number Configuration Btu/hr kW Btu/hr kW CFM SCOP
VS053AD*0* Upflow 186118 54.55 172988 50.70 7656 2.45
VS053AD*1* Upflow 186801 54.75 173671 50.90 7656 2.47
VS053AS*0* Upflow 192606 56.45 176400 51.70 7656 2.45
VS053AS*1* Upflow 193289 56.65 177083 51.90 7656 2.48
VS053AU*0* Upflow 184410 54.05 171965 50.40 7656 2.49
VS053AU*1* Upflow 184752 54.15 172647 50.60 7656 2.52
VS053DD*0* Upflow 184752 54.15 171624 50.30 7656 2.37
VS053DD*1* Upflow 185776 54.45 171624 50.30 7656 2.47
VS053DU*0* Upflow 182703 53.55 170600 50.00 7656 2.41
VS053DU*1* Upflow 184069 53.95 172647 50.60 7656 2.43
VS070AD*0* Upflow 230513 67.56 207450 60.80 9187 2.16
VS070AD*1* Upflow 231537 67.86 208473 61.10 9187 2.2
VS070AS*0* Upflow 235635 69.06 209838 61.50 9187 2.18
VS070AS*1* Upflow 236660 69.36 210862 61.80 9187 2.21
VS070AU*0* Upflow 220609 64.66 202332 59.30 9187 2.26
VS070AU*1* Upflow 221634 64.96 203355 59.60 9187 2.3
VS070DD*0* Upflow 229147 67.16 205744 60.30 9187 2.11
VS070DD*1* Upflow 230171 67.46 206767 60.60 9187 2.15
VS070DU*0* Upflow 219243 64.26 200967 58.90 9187 2.21
VS070DU*1* Upflow 220268 64.56 201990 59.20 9187 2.25
VS077AS*0* Upflow 253052 74.17 223486 65.50 9953 1.99
VS077AS*1* Upflow 254076 74.47 224510 65.80 9953 2.02
VS077AU*0* Upflow 243490 71.36 219050 64.20 9953 2.05
VS077AU*1* Upflow 244514 71.66 220210 64.54 9953 2.08
VS077DU*0* Upflow 241441 70.76 217003 63.60 9953 2
VS077DU*1* Upflow 243148 71.26 215980 63.30 9570 2.05
VS105AS*0* Upflow 328865 96.38 277054 81.20 13111 1.84
VS105AS*1* Upflow 329548 96.58 275007 80.60 12633 1.87
VS105AU*0* Upflow 326474 95.68 276031 80.90 13111 1.81
VS105AU*1* Upflow 324425 95.08 273984 80.30 12633 1.84
VS105DU*0* Upflow 322376 94.48 272278 79.80 13111 1.79
VS105DU*1* Upflow 325108 95.28 269548 79.00 12250 1.81

167 Liebert® DS™


U.S. Department of Energy (DOE) Performance Data

Table 90 U.S. DOE performance table—Liebert DS upflow and downflow, water-cooled


Total Cooling Capacity Sensible Cooling Capacity
Basic Model Airflow
Number Configuration Btu/hr kW Btu/hr kW CFM SCOP
DS028WD*0* Downflow 107914 31.63 97583.2 28.60 4210 3
DS028WD*1* Downflow 111329 32.63 99971.6 29.30 4210 3.29
DS028WS*0* Downflow 106889.5 31.33 96559.6 28.30 4210 3.25
DS028WS*1* Downflow 108938.5 31.93 98948 29.00 4210 3.59
DS028WU*0* Downflow 129087 37.83 107478 31.50 4210 2.89
DS028WU*1* Downflow 131477.5 38.53 109866.4 32.20 4210 3.14
DS035WD*0* Downflow 127038 37.23 112596 33.00 4926 2.63
DS035WD*1* Downflow 130453 38.23 116008 34.00 4926 2.96
DS035WS*0* Downflow 122940 36.03 110548.8 32.40 4926 2.83
DS035WS*1* Downflow 126355 37.03 113960.8 33.40 4926 3.22
DS035WU*0* Downflow 130453 38.23 114302 33.50 4926 2.83
DS035WU*1* Downflow 134209.5 39.33 118055.2 34.60 4926 3.2
DS042WD*1* Downflow 147869.5 43.34 132044.4 38.70 5850 2.83
DS042WS*0* Downflow 140015 41.04 125902.8 36.90 5950 2.52
DS042WS*1* Downflow 131477.5 38.53 131362 38.50 5850 3.02
DS042WU*0* Downflow 150943 44.24 129997.2 38.10 6054 2.5
DS042WU*1* Downflow 155041 45.44 135456.4 39.70 5850 2.84
DS053WD*0* Downflow 201826.5 59.15 172647.2 50.60 7177 3.19
DS053WD*1* Downflow 205241.5 60.15 179471.2 52.60 7714 3.38
DS053WS*0* Downflow 203875.5 59.75 173670.8 50.90 7177 3.19
DS053WS*1* Downflow 207290.5 60.75 180494.8 52.90 7714 3.38
DS053WU*0* Downflow 196704 57.65 170258.8 49.90 7177 3.18
DS053WU*1* Downflow 200460.5 58.75 177082.8 51.90 7714 3.37
DS070WD*0* Downflow 246904.5 72.36 205402.4 60.20 8613 2.74
DS070WD*1* Downflow 252027 73.86 214273.6 62.80 9277 2.92
DS070WS*0* Downflow 250319.5 73.36 207108.4 60.70 8613 2.75
DS070WS*1* Downflow 255442 74.87 215979.6 63.30 9277 2.94
DS070WU*0* Downflow 238025.5 69.76 201308 59.00 8613 2.77
DS070WU*1* Downflow 243148 71.26 209838 61.50 9277 2.96
DS077WS*0* Downflow 273883 80.27 225192 66.00 10500 2.5
DS077WS*1* Downflow 263638 77.27 235428 69.00 10644 2.67
DS077WU*0* Downflow 266711.5 78.17 221780 65.00 10500 2.5
DS077WU*1* Downflow 270126.5 79.17 232016 68.00 10644 2.65
DS105WS*1* Downflow 349013 102.29 288314 84.50 12890 2.43
DS105WU*1* Downflow 353111 103.49 287972.8 84.40 13000 2.4
VS028WD*0* Upflow 108597 31.83 97242 28.50 4297 2.856
VS028WD*1* Upflow 109621.5 32.13 98265.6 28.80 4297 2.99
VS028WS*0* Upflow 106206.5 31.13 96218.4 28.20 4297 3.092
VS028WS*1* Upflow 107572.5 31.53 97242 28.50 4297 3.24
VS028WU*0* Upflow 129087 37.83 107478 31.50 4297 2.78
VS028WU*1* Upflow 130453 38.23 108501.6 31.80 4297 2.89
VS035WD*0* Upflow 127038 37.23 112937.2 33.10 5078 2.556

Liebert® DS™ 168


U.S. Department of Energy (DOE) Performance Data

Table 90 U.S. DOE performance table—Liebert DS upflow and downflow, water-cooled (continued)
Total Cooling Capacity Sensible Cooling Capacity
Basic Model Airflow
Number Configuration Btu/hr kW Btu/hr kW CFM SCOP
VS035WD*1* Upflow 129087 37.83 114643.2 33.60 5078 2.72
VS035WS*0* Upflow 122940 36.03 110548.8 32.40 5078 2.85
VS035WS*1* Upflow 124989 36.63 112596 33.00 5078 2.94
VS035WU*0* Upflow 130794.5 38.33 114643.2 33.60 5078 2.75
VS035WU*1* Upflow 132843.5 38.93 116349.2 34.10 5078 2.93
VS042WD*0* Upflow 142747 41.84 127267.6 37.30 6054 2.386
VS042WD*1* Upflow 146162 42.84 130679.6 38.30 6054 2.62
VS042WS*0* Upflow 126696.5 37.13 126585.2 37.10 6054 2.526
VS042WS*1* Upflow 144796 42.44 129656 38.00 6054 2.78
VS042WU*0* Upflow 150260 44.04 130679.6 38.30 6054 2.41
VS042WU*1* Upflow 153675 45.04 134091.6 39.30 6054 2.64
VS053WD*0* Upflow 202851 59.45 177082.8 51.90 7812 3.07
VS053WD*1* Upflow 203534 59.65 177424 52.00 7812 3.11
VS053WS*0* Upflow 204558.5 59.95 177765.2 52.10 7812 3.066
VS053WS*1* Upflow 205241.5 60.15 178106.4 52.20 7812 3.1
VS053WU*0* Upflow 197728.5 57.95 174353.2 51.10 7812 3.05
VS053WU*1* Upflow 198411.5 58.15 174694.4 51.20 7812 3.09
VS070WD*0* Upflow 249295 73.06 211544 62.00 9374 2.69
VS070WD*1* Upflow 250319.5 73.36 212226.4 62.20 9374 2.73
VS070WS*0* Upflow 252368.5 73.96 213250 62.50 9374 2.7
VS070WS*1* Upflow 253734.5 74.37 213932.4 62.70 9374 2.74
VS070WU*0* Upflow 240416 70.46 207108.4 60.70 9374 2.71
VS070WU*1* Upflow 241440.5 70.76 207790.8 60.90 9374 2.76
VS077WS*0* Upflow 274566 80.47 228945.2 67.10 10156 2.51
VS077WS*1* Upflow 276273.5 80.97 229968.8 67.40 10156 2.56
VS077WU*0* Upflow 267394.5 78.37 225533.2 66.10 10156 2.49
VS077WU*1* Upflow 268760.5 78.77 226215.6 66.30 10156 2.53
VS105WS*0* Upflow 348330 102.09 286266.8 83.90 12890 2.29
VS105WS*1* Upflow 349013 102.29 283537.2 83.10 12890 2.32
VS105WU*0* Upflow 345256.5 101.19 285925.6 83.80 12500 2.29
VS105WU*1* Upflow 345256.5 101.19 282854.8 82.90 12500 2.29

169 Liebert® DS™


U.S. Department of Energy (DOE) Performance Data

Table 91 U.S. DOE performance table—Liebert DS upflow and downflow, water-cooled with a fluid
economizer
Total Cooling Capacity Sensible Cooling Capacity
Basic Model Airflow
Number Configuration Btu/hr kW Btu/hr kW CFM SCOP
VS028*U*1* Upflow 130111.5 38.13 108160.4 31.70 4297 2.86
VS028*U*0* Upflow 128745.5 37.73 107136.8 31.40 4297 2.75
VS028*D*1* Upflow 109280 32.03 97924.4 28.70 4297 2.94
VS028*D*0* Upflow 108255.5 31.73 96900.8 28.40 4297 2.82
VS035*U*1* Upflow 132160.5 38.73 116008 34.00 5078 2.88
VS035*U*0* Upflow 130111.5 38.13 114302 33.50 5078 2.71
VS035*D*1* Upflow 129087 37.83 113960.8 33.40 5078 2.67
VS035*D*0* Upflow 126355 37.03 112254.8 32.90 5078 2.52
VS042*U*1* Upflow 152650.5 44.74 133068 39.00 6054 2.56
VS042*U*0* Upflow 149577 43.84 129997.2 38.10 6054 2.37
VS042*D*1* Upflow 145137.5 42.54 129314.8 37.90 6054 2.54
VS042*D*0* Upflow 142064 41.64 126585.2 37.10 6054 2.34
VS053*U*1* Upflow 197728.5 57.95 174012 51.00 7812 3.02
VS053*U*0* Upflow 195679.5 57.35 172306 50.50 7812 2.91
VS053*D*1* Upflow 202509.5 59.35 176400.4 51.70 7812 3.05
VS053*D*0* Upflow 200802 58.85 175035.6 51.30 7812 2.93
VS070*U*1* Upflow 240074.5 70.36 206426 60.50 9374 2.68
VS070*U*0* Upflow 238708.5 69.96 205743.6 60.30 9374 2.64
VS070*D*1* Upflow 248953.5 72.96 210861.6 61.80 9374 2.66
VS070*D*0* Upflow 247587.5 72.56 210179.2 61.60 9374 2.62
VS077*U*1* Upflow 266370 78.07 222121.2 65.10 9765 2.49
VS077*U*0* Upflow 265345.5 77.77 223486 65.50 9765 2.42
VS105*U*1* Upflow 345256.5 101.19 278419.2 81.60 12500 2.24
DS028*U*1* Downflow 130794.5 38.33 109184 32.00 4210 3.06
DS028*U*0* Downflow 128404 37.63 106795.6 31.30 4210 2.82
DS028*D*1* Downflow 110646 32.43 99289.2 29.10 4210 3.2
DS028*D*0* Downflow 108255.5 31.73 96900.8 28.40 4210 2.92
DS035*U*1* Downflow 133185 39.03 117031.6 34.30 4976 3.09
DS035*U*0* Downflow 129428.5 37.93 113278.4 33.20 4976 2.74
DS035*D*1* Downflow 129428.5 37.93 115325.6 33.80 4976 2.86
DS035*D*0* Downflow 126013.5 36.93 111572.4 32.70 4976 2.55
DS042*U*1* Downflow 153675 45.04 134774 39.50 5957 2.72
DS042*D*1* Downflow 146162 42.84 131362 38.50 5957 2.7
DS053*U*1* Downflow 198753 58.25 175376.8 51.40 7714 3.23
DS053*U*0* Downflow 195338 57.25 168552.8 49.40 7177 3.06
DS053*D*1* Downflow 203534 59.65 177765.2 52.10 7714 3.25
DS053*D*0* Downflow 200119 58.65 170941.2 50.10 7177 3.07
DS070*U*1* Downflow 240416 70.46 207449.6 60.80 9277 2.82
DS070*U*0* Downflow 235635 69.06 198578.4 58.20 8613 2.65
DS070*D*1* Downflow 249295 73.06 211544 62.00 9277 2.79
DS070*D*0* Downflow 244514 71.66 203014 59.50 8613 2.62
DS077*U*1* Downflow 266711.5 78.17 224850.8 65.90 9998 2.56

Liebert® DS™ 170


Guide Specifications

APPENDIX B - GUIDE SPECIFICATIONS

1.0 General
1.1 SUMMARY
These specifications describe requirements for a Thermal Management system. The system shall be
designed to control temperature and humidity conditions in rooms containing electronic equipment,
with good insulation and vapor barrier. The manufacturer shall design and furnish all equipment to
be fully compatible with heat-dissipation requirements of the room.

1.2 DESIGN REQUIREMENTS


The Thermal Management system shall be a Liebert self-contained, factory-assembled unit. Standard
60 Hz units shall be CSA-certified to the harmonized U.S. and Canadian product safety standard,
"CSA C22.2 No 236/UL 1995 for Heating and Cooling Equipment" and are marked with the CSA c-us
logo.
The system shall be AHRI Certified™, the trusted mark of performance assurance for heating,
ventilation, air conditioning and commercial refrigeration equipment, using AHRI Standard 1360.

1.3 SUBMITTALS
Submittals shall be provided with the proposal and shall include: Single-Line Diagrams;
Dimensional, Electrical, and Capacity Data; Piping and Electrical Connection Drawings.

1.4 SERVICEABILITY/ ACCESS


The cabinet shall be designed so that all components are easily accessible for service and maintenance
through the unit's side and front [CW026-084], front [CW089-181].

1.5 ACCEPTABLE ALTERNATIVES


With prior engineer's approval only. Contractor to submit a detailed summary form listing all
variations to include size deviations, electrical load differences, functional and component changes
and savings to end user.

1.6 QUALITY ASSURANCE


The specified system shall be factory-tested before shipment. Testing shall include, but shall not be
limited to: Quality Control Checks, “Hi-Pot.” The system shall be designed and manufactured
according to world-class quality standards. The manufacturer shall be ISO 9001 certified.

171 Liebert® DS™


Guide Specifications

2.0 Product
2.1 FRAME
The frame shall be MIG welded, formed sheet metal. It shall be protected against corrosion using the
autophoretic coating process. The frame shall be capable of being separated into three parts in the
field to accommodate rigging through small spaces.
2.1.1 Downflow Air-flow Configurations
2.1.1.1 Downflow Air Supply
The supply air shall exit from the bottom of the unit.

2.1.1.2 Downflow Air, Under-floor discharge


The supply air shall exit from the bottom of the unit.

2.1.1.3 Downflow Air, EC Fans Lowered into Floor Stand


The supply air shall exit from all sides of the floor stand.

2.1.1.4 Downflow Air, Front Discharge


The supply air shall exit from the front of the unit.

2.1.1.5 Downflow Air, Rear discharge


The supply air shall exit from the rear of the unit.

2.1.1.6 Downflow Air Return


The return air shall enter the unit from the top.
2.1.2 Upflow Air-flow Configurations
2.1.2.1 Upflow Air Supply
The supply air shall exit from the top of the unit.

2.1.2.2 Upflow Top Air Supply, Front Throw


The supply air shall exit from the top of the cabinet (or plenum) with the air throw toward the front.

2.1.2.3 Upflow Top Air Supply, Rear Throw


The supply air shall exit from the top of the cabinet (or plenum) with the air throw toward the back.

2.1.2.4 Upflow Rear Air Supply


The supply air shall exit from the back of the cabinet.

2.1.2.5 Upflow Air Return, Front


The return air shall enter the unit from the front of the cabinet through factory-installed grilles.
Grilles shall be painted black.

2.1.2.6 Upflow Air Return, Rear


The return air shall enter the unit from the back of the cabinet.
2.1.3 Exterior Panels
The exterior panels shall be insulated with a minimum 1 in. (25 mm), 1.5 lb. (0.68 kg) density fiber
insulation. The main front panel shall have captive quarter-turn fasteners. The main unit color shall
be ______. The accent color shall be _________.

2.1.3.1 Double-Skin Panels—Optional


The exterior panels shall be internally lined with 20-gauge sheet metal, sandwiching the insulation
between the panels, for easy cleaning. The accent color shall be _________.

Liebert® DS™ 172


Guide Specifications

2.2 FILTERS
For Downflow units, the filter chamber shall be located within the cabinet, and filters shall be
removable from the top of the unit. Filters shall be arranged in a flat bank configuration.
For Upflow units, the filter chamber shall be located within the cabinet, and filters shall be removable
from the front or rear of the unit. Filters shall be arranged in a horizontal bank configuration.
2.2.1 Filters, 4-in. MERV8 or MERV11
Filters shall be deep pleated 4-in. filters with an ASHRAE 52.2 MERV8 rating (45% ASHRAE 52.1) or
ASHRAE 52.2 MERV11 rating (60-65% ASHRAE 52.1).
2.2.1 Filters, 2-in. MERV8 Pre-Filter With 2-in. Filter MERV11
Filters shall be 2-in. ASHRAE 52.2 MERV8 (45% ASHRAE 52.1) pre-filter, with 2-in. ASHRAE 52.2
MERV11 (60-65% ASHRAE 52.1) efficiency filter.
2.2.2 Extra Filter Set
____ extra set(s) of filters shall be provided per system.

2.3 LOCKING DISCONNECT SWITCH


The manual disconnect switch shall be mounted in the high-voltage section of the electrical panel.
The switch shall be accessible from the outside of the unit with the door closed, and shall prevent
access to the high-voltage electrical components until switched to the Off position.

2.4 FAN SECTION


2.4.1 Electronically Commutated (EC) Fan
The fans shall be plug/plenum type, single inlet and shall be dynamically balanced. The drive package
shall be direct drive, electronically commutated and variable speed. The fans shall be located to draw
air over the A-frame coil to ensure even air distribution and maximum coil performance. EC fans
shall be available on downflow models, and fans may be lowered into a raised floor with a minimum
height of 24 in. (610 mm). EC fans may operate within the Liebert DS cabinet, instead of under the
floor. EC fans shall be available on upflow models and fans shall operate outside the unit in a factory-
provided plenum with a minimum height of 24 in. (610 mm).
• DS028, DS035 and DS042 fan motor(s) shall be nominal 3.7 hp (2.8 kW) each with a maximum
operating speed of 1230 rpm; quantity, 1. Liebert Econ-O-Coil gets a 5.4 hp (4.0 kW) fan for
380-480V (maximum 1370 rpm).
• DS053, DS070 and DS077 fan motors shall be nominal 4.0 hp (3.0 kW) each with a maximum
operating speed of 1520 rpm; quantity, 2.
• DS105 fan motors shall be nominal 3.4 hp (2.5 kW) each, with a maximum operating speed of
1700 rpm; quantity, 3. (Power rating for 380-480V is 3.4 hp (2.5 kW); for 200-240V power
is 3.6 hp [2.7kW].)

173 Liebert® DS™


Guide Specifications

2.4.1 Forward Curved Blower


The blower section shall be designed for ___ CFM (CMH) at an external static pressure
of ___ in. wg. (Pa).
The fans shall be the centrifugal type, double-width and double-inlet, and shall be dynamically
balanced as a completed assembly. The shaft shall be heavy-duty steel with self-aligning,
permanently-sealed, pillow-block bearings with a minimum L3 life of 200,000 hours. The fans shall
draw air through the coil to ensure even air distribution and maximum coil performance. The fan
motor shall be ____ hp (kW) at 1750 rpm @ 60 Hz (1450 rpm @50 Hz), mounted to an automatic,
spring tensioning base. The motor shall be removable from the front of the cabinet. The drive package
shall be two-belt, variable speed, sized for 200% of the fan-motor horsepower. An auto-tension system
shall provide constant tension on the belts. Belts, shaft, blower bearings, sheave, and pulley shall be
warranted for 5 years (parts only).

2.4.1.1 Motor
The fan motor shall be ____ hp (kW) at 1750 rpm @ 60Hz (1450 rpm @50Hz), mounted to an
automatic, spring-tensioning base. The motor shall be removable from the front of the cabinet.

2.4.1.1.1 Premium Efficiency Motor


The fan motor shall be Open Drip-Proof, Premium efficiency and shall meet NEMA Premium
standard. Motor efficiency shall be ____%.
2.4.1.1.1 TEFC Motor-Optional
The motor shall be Totally Enclosed Fan Cooled for protection in harsh environments.

2.4.1.2 Drive Package


The motor sheave and fan pulley shall be double-width fixed pitch. Two belts, sized for 200% of the
fan motor horsepower shall be provided with the drive package. An auto-tension system shall provide
constant tension on the belts. Belts, shaft, blower bearings, sheave and pulley shall be warranted for
five years (parts only).

2.5 HUMIDIFIER
A humidifier shall be factory-installed inside the unit. Bypass air slots shall be included to enable
moisture to be absorbed into the air stream. The humidifier capacity shall be ____lb./hr (kg/hr). The
humidifier shall be removable from the front of the cabinet.
2.5.1 Infrared Humidifier—Optional
The humidifier shall be of the infrared type, consisting of high-intensity quartz lamps mounted above
and out-of the water supply. The humidifier pan shall be stainless steel and arranged to be removable
without disconnecting high-voltage electrical connections. The complete humidifier section shall be
pre-piped, ready for field connection to the water supply. The humidifier shall be equipped with an
automatic water-supply system and shall have an adjustable water-overfeed to prevent mineral
precipitation. A high-water detector shall shut-down the humidifier to prevent overflowing. A 1 in.
(24 mm) air-gap shall prevent back-flow of the humidifier supply water.
2.5.1 Steam Generating Canister Humidifier—Optional
A canister-type steam canister shall be factory-installed in the cooling unit and shall be controlled by
®
the Liebert iCOM control system. It shall be complete with disposable canister, all supply and drain
valves, steam distributor and electronic controls. The need to change the canister shall be indicated
on the Liebert iCOM display. System shall automatically fill and drain as well as maintain the
required water level based on conductivity The humidifier shall be designed to operate with water
conductivity from 200 to 500 micro-ohms. An air-gap within the humidifier assembly shall prevent
back-flow of the humidifier supply water.

Liebert® DS™ 174


Guide Specifications

2.6 REHEAT
The environmental control unit shall include a factory-installed reheat to control temperature during
dehumidification.
2.6.1 Three-Stage Electric Reheat—Optional
The electric reheat coils shall be low watt density, 304/304 stainless steel fin tubular construction,
protected by thermal safety switches, shall be ____ kW (____ BTUH) controlled in three stages. The
reheat elements shall be removable from the front of the cabinet.
2.6.1 SCR Electric Reheat—Optional
The electric reheat coils shall be low watt density, 304/304 stainless steel fin tubular construction,
protected by thermal safety switches, ____ kW (____ BTUH) controlled by multiple pulses to achieve
tight temperature control. The reheat elements shall be removable from the front of the cabinet.
2.6.1 Hot Water Reheat
The hot water reheat coil shall have copper tubes and aluminum fins with a capacity of ____ BTUH
(kW) when supplied with ____ °F (°C) entering water temperature at ____ GPM (l/s) flow rate.
Maximum pressure drop shall be ____ psi (kPa). The hot water reheat control system shall be factory
pre-piped with a two-way modulating control valve and cleanable Y-strainer.

2.7 DUAL REFRIGERATION SYSTEM


Each unit shall include two (2) independent refrigeration circuits and shall include hot gas mufflers
(semi-hermetic compressors units only), liquid line filter dryers, refrigerant sight glasses with
moisture indicator, externally equalized expansion valves and liquid line solenoid valves.
Compressors shall be located outside the air stream and shall be removable and serviceable from the
front of the unit.
2.7.1 Semi-Hermetic Compressor with Four-Step Unloaders Control
The compressor shall be semi-hermetic with a suction gas cooled motor, vibration isolators, thermal
overloads, oil sight glass, automatic reset high pressure switch with control lockout after three
failures, pump-down low-pressure transducer, suction line strainer, service valves, reversible oil
pumps for forced feed lubrication, a maximum operating speed of 1750 rpm. The system shall include
cylinder unloaders on the semi-hermetic compressors. The unloaders shall be activated by solenoid
valves which are controlled from the microprocessor control. In response to the return air
temperature, the microprocessor control shall activate the unloader solenoids and the liquid line
solenoids such that four stages of refrigeration cooling are obtained. The stages shall be: 1) one
compressor, partially loaded, 2) two compressors partially loaded, 3) one compressor partially loaded,
one compressor fully loaded, 4) two compressors fully loaded. On a call for dehumidification, the
microprocessor control shall ensure that at least one compressor is on full for proper humidity control.
2.7.1 Digital Scroll Compressors
The compressor shall be scroll-type with a variable capacity operation capability. The compressor
solenoid valve shall unload the compressor and allow for variable capacity operation. The compressor
shall be suction gas cooled motor, vibration isolators, thermal overloads, automatic reset high-
pressure switch with lockout after three failures, rotalock service valves, pump down low pressure
transducer, suction line strainer and a maximum operating speed of 3500 rpm. Consult factory for
575V availability.
2.7.1 Scroll Compressors
The compressor shall be scroll-type. The compressor shall be suction gas cooled motor, vibration
isolators, thermal overloads, automatic reset high pressure switch with lockout after three failures,
rotalock service valves, pump down low pressure transducer, suction line strainer and a maximum
operating speed of 3500 RPM.

2.7.1.1 Crankcase Heaters


The compressors shall include crankcase heaters, powered from the indoor unit electric panel.

175 Liebert® DS™


Guide Specifications

2.7.2 Evaporator Coil


The evaporator coil shall be A-frame design on downflow units with offset orientation and have
2
____sq. ft. (m ) face area, ____ rows deep. It shall be constructed of rifled copper tubes and aluminum
3
fins and shall have a maximum face velocity of ____ ft. per minute (m/s) at ____ CFM (m ). A
stainless-steel condensate drain pan shall be provided.

2.7.2.1 Polymeric Coating—Optional


The coil shall be coated with a high performance polymeric coating process to provide corrosion
resistance within 2 to 12 pH range.
2.7.3 Dual-Cooling Source
The dual-cooling source system shall consist of an air-cooled or water-cooled compressorized system

with the addition of a chilled water coil (Liebert Econ-O-Coil ), a modulating control valve and a
comparative temperature sensor. The system shall be able to function either as a modulating chilled
water system or as a compressorized system, or a combination of both. The primary cooling mode
shall be chilled water. Switchover between the two cooling modes shall be performed automatically by
the microprocessor control. Four (4) pipes shall be included on water/glycol systems: Liebert Econ-O-
Coil supply, Liebert Econ-O-Coil return, condenser supply and condenser return.
2.7.4 Dual-Cooling Source Control Valve
The water circuit shall include a three-way modulating valve. The microprocessor positions the valve
in response to room conditions. Cooling capacity will be controlled by bypassing chilled water around
the coil. The modulating valve travel for dehumidification shall be proportional.
2.7.5 Cu-Ni Coil —Optional

A 70/30 Cu-Ni Liebert Econ-O-Coil shall be provided on dual-cooling units that are connected to a
cooling tower loop or other open water system. This option shall be required on open cooling tower
applications.

2.7.6 Polymeric Coating on Liebert Econ-O-Coil and DX Coil —Optional
The coil shall be coated with a high performance polymeric coating process to provide corrosion
resistance within 2 to 12 pH range.
2.7.7 R-407C Refrigerant
The system shall be designed for use with R-407C refrigerant, which meets the EPA clean air act for
phase-out of HCFC refrigerants.

2.8 OPTIONS—WATER/GLYCOL SYSTEMS


2.8.1 Paradenser™ Condenser
The water-cooled condensers for each circuit shall be cleanable, shell-and-tube, counter-flow type. The
heads shall be removable to allow for cleaning of the water tubes. Condensers shall be rated for a
maximum refrigerant pressure of 400 psi at 200°F (2758 kPa at 93.3°C). The condenser shall be
capable of operating with R-22 or R 407C refrigerant. The unit shall require ____ GPM (l/m) of ____ °F
(°C) water and have a maximum pressure drop of ____ psi (kPa).
2.8.2 Water/Glycol Regulating Valve, 2-way with Bypass
The condenser shall be pre-piped with a 2-way regulating valve. A gate-valve shall bypass the
regulating valve.
2.8.3 Water/Glycol Regulating Valve, 3-way
The condenser shall be pre-piped with a 3-way regulating valve.
2.8.4 Pressure Rating, 150 psi (1034 kPa)
The condenser water circuit shall be designed for a pressure of 150 psi (1034 kPa).
2.8.5 Pressure Rating, 350 psi (2413 kPa)
The condenser water circuit shall be designed for a pressure of 350 psi (2413 kPa).

Liebert® DS™ 176


Guide Specifications

2.9 OPTIONS—GLYCOOL SYSTEMS


2.9.1 GLYCOOL Coil
The GLYCOOL (Liebert Econ-O-Coil™) shall be constructed of copper tubes and aluminum fins. The
coil shall be A-frame or V-frame to minimize air-pressure drop and shall be nested with the DX coil.
The Liebert Econ-O-Coil shall be upstream of the DX coil to enable pre-cooling of the air.
The Liebert Econ-O-Coil shall have a net sensible cooling capacity of ____ BTUH (kW)
with 45°F (7.2°C) entering glycol solution temperature. The system shall require ____ GPM (l/s) and
the total unit pressure drop shall not exceed ____ feet of water (kPa), when in the Liebert Econ-O-Coil
mode of operation.
2.9.2 GLYCOOL 3-way Control Valve
The GLYCOOL coil shall be equipped with a fully-proportional 3-way control valve. This motorized
control valve shall control the amount of flow to the GLYCOOL (Econ-O-Coil) coil to control room
temperature and relative humidity.
2.9.3 High Pressure System, 350 psi (2413 kPa)
The GLYCOOL system shall be designed for a pressure of 350 psi (2413 kPa).
2.9.4 Cu-Ni Econ-O-Coil
A 70/30 Cu-Ni Econ-O-Coil shall be provided for when the Liebert Econ-O-Coil is cooling tower loop or
other open water system. This option shall be required on open cooling-tower applications.

177 Liebert® DS™


Guide Specifications

3.0 CONTROLS
3.1 LIEBERT ICOM®
MICROPROCESSOR CONTROL WITH 9-INCH COLOR TOUCHSCREEN
The Liebert iCOM shall be microprocessor-based with a 9-in. color touchscreen display and shall be
mounted in an ergonomic, aesthetically pleasing housing. The display and housing shall be viewable
while the front panel is open or closed. The controls shall be menu-driven. The system shall display
user menus for active alarms, event log, graphic data, unit view/status overview (including the
monitoring of room conditions, operational status in percentage of each function, date and time), total
run hours, various sensors, display setup and service contacts. A password shall be required to make
system changes. Service menus shall include setpoints, standby settings (lead/lag), timers/sleep
mode, alarm setup, sensor calibration, maintenance/wellness settings, options setup, system/network
setup, auxiliary boards and diagnostics/service mode.
• Password Protection - The Liebert iCOM shall contain two unique passwords to protect against
unauthorized changes. An auto hide/show feature shall allow the user to see applicable
information based on the login used.
• Unit Backup/Restore - The Backup function saves a copy of the settings in a file based on the
system name assigned during startup. The backup can be used to restore only the unit where it
was created and serve as a recovery if a display fails. The backup file includes network settings,
the unit name, panel configuration and other details specific to the Liebert iCOM display. The
Restore function copies the backup settings file to a Liebert iCOM/display so that it functions
exactly as it did before the unwanted change or as it did on the Liebert iCOM that was replaced.
• Unit Export/Import - The Export function makes a copy of the settings from the Liebert iCOM
display that may be stored on a local disk or USB drive. The settings may be imported to a second
Liebert iCOM, resulting in two systems with identical display properties. The Liebert iCOM will
automatically recognize USB drives and display them in the relevant screens. Multiple backup
files may be put on the same USB drive as long as each system name is unique. The Import
function allows previously exported settings files to be loaded to a second Liebert iCOM. This
allows display settings, including panel configurations and custom labels, to be copied from one
display to another.
• Parameter Download - The Liebert iCOM shall enable the user to download a report that lists
parameter names, factory default settings and user programmed settings in .csv format for
remote reference.
• Parameter Search - The Liebert iCOM shall have search fields for efficient navigation and
parameter lookup.
• Parameter Directory - The Liebert iCOM shall provide a directory that lists all parameters in
the control. The list shall provide Line ID numbers, parameter labels, and current parameter
values.
• Setup Wizards - The Liebert iCOM shall contain step-by-step tutorials or wizards to provide
easy setup of the control.
• Context-Sensitive Help - The Liebert iCOM shall have an on-board help database. The
database shall provide context-sensitive help to assist with setup and navigation of the menus.
• Display Setup - The user shall be able to configure the display information based on the specific
user’s preference. Language, units of measure, screen contrast, home screen layout, back-light
timer and the hide/show of certain readouts shall be configurable through the display.
• Additional Readouts - The display shall enable the user to configure custom widgets on the
main screen. Widget options will include items such as fan speed, call for cooling, call for free-
cooling, maintenance status, call for hot water reheat, call for electric reheat, call for
dehumidification, call for humidification, airflow, static pressure, fluid flow rate and cooling
capacity.

Liebert® DS™ 178


Guide Specifications

• Status LED’s - The Liebert iCOM shall show the unit’s operating status using an integral LED.
The LED shall indicate if the unit has an active alarm; if the unit has an active alarm that has
been acknowledged; or if the unit is On, Off or in standby status.
• Event Log - The Liebert iCOM shall automatically store the last 400 unit-only events (messages,
warnings, and alarms).
• Service Contact Information - The Liebert iCOM shall be able to store the local service or
sales contact information.
• Upgradeable - Liebert iCOM upgrades shall be performed through a USB connection.
• Timers/Sleep Mode – The menus shall allow various customer settings for turning the unit On
or Off.
• Menu Layout - The menus shall be divided into two main menus: User and Service. The User
screen shall contain the menus to access parameters required for basic unit control and setup.
The Service screen shall be designed for service personnel and shall provide access to advanced
control setup features and diagnostic information.
• Sensor Calibration - The menus shall allow unit sensors to be calibrated with external sensors.
• Maintenance/Wellness Settings - The menus shall allow reporting of potential component
problems before they occur.
• Options Setup - The menus shall provide operation settings for the installed components.
• Auxiliary Boards - The menus shall allow setup of optional expansion boards.
• Various Sensors: The menus shall allow setup and display of optional custom sensors. The
control shall include four customer accessible analog inputs for field-supplied sensors. The analog
inputs shall accept a 4 to 20mA signal. The user shall be able to change the input to 0 to 5VDC or
0 to 10VDC. The gains for each analog input shall be programmable from the front display. The
analog inputs shall be able to be monitored from the front display.
• Diagnostics/Service Mode - The Liebert iCOM control shall be provided with self-diagnostics to
aid in troubleshooting. The microcontroller board shall be diagnosed and reported as pass/not
pass. Control inputs shall be indicated as On or Off at the front display. Control outputs shall be
able to be turned On or Off from the front display without using jumpers or a service terminal.
Each control output shall be indicated by an LED on a circuit board.

3.2 ALARMS
All unit alarms shall be annunciated through both audio and visual cues, clearly displayed on the
screen, automatically recorded in the event log and communicated to the customers Building
Management System/Building Automation System. The Liebert iCOM control shall activate an
audible and visual alarm in event of any of the following conditions:
• High Temperature
• Low Temperature
• High Humidity
• Low Humidity
• EC Fan Fault
• Change Filters
• Loss of Air Flow
• Loss of Power
• Compressor Overload (Optional)
• Humidifier Problem
• High Head Pressure
• Low Suction Pressure

179 Liebert® DS™


Guide Specifications

• Custom Alarms
Custom alarm inputs shall be provided to indicate facility-specific events. Custom alarms can be
identified with programmable labels. Frequently used alarm inputs include:
• Leak Under Floor
• Smoke Detected
• Standby Unit On
Each alarm (unit and custom) shall be separately enabled or disabled, selected to activate the
common alarm and programmed for a time delay of 0 to 255 seconds.

3.3 LIEBERT ICOM® CONTROL METHODS AND OPTIONS


The Liebert iCOM shall be factory-set to allow precise monitoring and control of the condition of the
air entering and leaving the unit. This control shall include predictive methods to control air flow and
cooling capacity based control sensors installed. Proportional and Tunable PID shall also be user-
selectable options.
3.3.1 Controlling Sensor Options
Liebert iCOM shall be flexible in the sense that it shall allow for controlling the capacity and fan from
multiple different sensor selections. The sensor selections shall be:

3.3.1.1 Cooling Capacity


• Supply
• Remote
• Return

3.3.1.2 Fan Speed


• Supply
• Remote
• Return
• Manual (for diagnostic or to receive a signal from the BMS through the Liebert remote monitoring
devices or analog input)
• Static Pressure
3.3.2 Temperature Compensation
The Liebert iCOM shall be able to adjust the capacity output based on supply and return temperature
conditions to meet SLA guidelines while operating to highest efficiency.
3.3.3 Humidity Control
Dew point and relative humidity control methods shall be available (based on user preference) for
humidity control within the conditioned space.

Liebert® DS™ 180


Guide Specifications

3.4 MULTI-UNIT COORDINATION


Liebert iCOM teamwork shall save energy by preventing multiple units in an area from operating in
opposing modes. Teamwork allows the control to optimize a group of connected cooling units equipped
with Liebert iCOM using the U2U (Unit-to-Unit) network. There shall be three modes of teamwork
operation:
• Teamwork Mode 1 (Parallel): Is best in small rooms with balanced heat loads. The controlling
temperature and humidity sensor readings of all units in operation (fan On) are collected to be
used for an average or worst-case sensor reading (user-selectable). The master unit shall send the
operating requirements to all operating units in the group. The control band (temperature, fan
and humidity) is divided and shared among the units in the group. Each unit will receive
instructions on how to operate from the Master unit based on how far the system deviates from
the setpoints. Evaporator fans and cooling capacity are ramped in parallel.
• Teamwork Mode 2 (Independent): The Liebert iCOM calculates the worse-case demand for
heating, cooling humidification and dehumidification. Based on the greatest demand within the
group, each unit operates independently, meaning that the unit may respond to the thermal load
and humidity conditions based on the unit’s controlling sensors. All sensor readings are shared.
• Teamwork Mode 3 (Optimized Aisle): May be employed in large and small rooms with varying
heat loads. Optimized Aisle is the most efficient teamwork mode that allows the unit to match
cooling capacity with heat load. In the Optimized Aisle mode, the fans operate in parallel. Fans
can be controlled exclusively by remote temperature or using static pressure with a secondary
remote temperature sensor(s) as an override to ensure that the inlet rack temperature is being
met. Cooling (Compressors or Economizer) is controlled through unit supply air conditions.
Liebert iCOM calculates the average or worst-case sensor reading (user-selectable) for heating,
cooling humidification and dehumidification. Based on the demand within the group, units will be
allowed to operate within that mode until room conditions are satisfied. This is the best form of
control for a room with an unbalanced load.

3.5 STANDBY LEAD-LAG


The Liebert iCOM® shall allow scheduled rotation to keep equal run time on units and provide
automated emergency rotation of operating and standby units.

3.6 STANDBY UNIT CASCADING


The Liebert iCOM cascade option shall allow the units to turn On and Off based on heat load when
utilizing Teamwork Mode 1, Independent mode or Teamwork Mode 3, Optimized Aisle mode with
remote temperature sensors. In Teamwork Mode 1, Cascade mode will stage units On based on the
temperature and humidity readings and their deviation from setpoint. In Teamwork 3 Mode, Cascade
mode dynamically coordinates the fan speed to save energy and to meet the cooling demands. For
instance, with a Liebert iCOM group of six units and only 50% of the heat load, the Liebert iCOM
shall operate only four units at 80% fan speed and leave the other two units in standby. As the heat
load increases, the Liebert iCOM shall automatically respond to the additional load and bring on
another unit, increasing the units in operation to five. As the heat load shifts up or down, the control
shall meet the needs by cascading units On or putting them into standby.

3.7 WIRED SUPPLY SENSOR


Each Liebert iCOM shall have one factory-supplied and connected supply air sensor that may be used
as a controlling sensor or reference. When multiple sensors are applied for control purposes, the user
shall be able to control based on a maximum or average temperature reading.

181 Liebert® DS™


Guide Specifications

3.8 VIRTUAL MASTER


As part of the robust architecture of the Liebert iCOM control, it shall allow for a virtual master that
coordinates operation. The Virtual Master function shall provide smooth control operation if the
group’s communication is compromised. When the lead unit, which is in charge of component staging
in teamwork, unit staging and standby rotation, becomes disconnected from the network, the Liebert
iCOM shall automatically assign a virtual master. The virtual master shall assume the same
responsibilities as the master until communication is restored.

3.9 VIRTUAL BACK-DRAFT DAMPER


The Liebert iCOM shall allow the use of a virtual back-draft damper, eliminating the need for a
mechanical damper. This shall allow the fans to spin slower (15% or less) to act as a damper.

3.10 COMPRESSOR SHORT CYCLE CONTROL


To help maximize the life of the compressor(s), there shall be start-to-next start delay for each single
compressor. The control shall monitor the number of compressor starts in an hour. If the compressor
starts more than 10 times in 60 minutes, the local display and remote monitoring shall notify the user
through a Compressor 1 or 2 Short Cycle event.

3.11 LIEBERT MC™


Units may be matched to a premium-efficiency condenser control with enhanced monitoring,
alarming and diagnostics. The condenser control shall have an automated, low-noise mode and fan
reversal for cleaning mode.

3.12 SYSTEM AUTO RESTART


The auto restart feature shall automatically restart the system after a power failure. Time delay shall
be programmable. An optional capacitive buffer may be provided for continuous control operation
through a power failure.

3.13 SEQUENTIAL LOAD ACTIVATION


On initial startup or restart after power failure, each operational load shall be sequenced with a
minimum delay of one second to minimize total inrush current.

3.14 LOW-PRESSURE MONITORING


Units shall ship standard with low-pressure transducers for monitoring individual compressor
suction pressure. If the pressure falls due to loss of charge or other mechanical cause, the
corresponding circuit shall shut down to prevent equipment damage. The user shall be notified of the
low-pressure condition through the local display and remote monitoring.

3.15 WINTER START TIME DELAY—AIR-COOLED MODELS


An adjustable software timer shall be provided to assist with compressor starting during cold
weather. When the compressor starts, the low-pressure input shall be ignored for the period set in the
user-adjustable timer. Once the time period has elapsed after the compressor start, the low-pressure
input should remain in the normal state. If the low-pressure input does not remain in the normal
state when the time delay has elapsed, the circuit shall lock out on low pressure. The low-pressure
alarm shall be announced on the local display and communicated to remote monitoring systems.

Liebert® DS™ 182


Guide Specifications

3.16 ADVANCED FREEZE PROTECTION


Units shall ship standard with advanced freeze protection enabled. The advanced freeze protection
shall monitor the pressure of each circuit using a transducer. The control shall interact with the fan
and compressor to prevent the unit coil from freezing if circuit suction pressure drops. Applying fan
speed to direct expansion systems requires limitations to avoid freezing condensate on the coil when
the unit operates below 100% fan speed. Liebert iCOM's advanced freeze protection provides the
ability to predict freeze conditions and correct this condition automatically by adjusting fan speed and
compressor capacity. If a freeze condition is detected, the user shall be notified through the local
display and remote monitoring systems.

3.17 ADVANCED HIGH-PRESSURE PROTECTION—


WATER/GLYCOL-COOLED MODELS WITH DIGITAL SCROLL COMPRESSORS
When the compressor is initially activated, the system shall be monitored for high pressure. When
high pressure is detected, the control shall alter the compressor operation and the condenser fans
peed to reduce the system discharge pressure, preventing circuit shut down. If the unit is
unsuccessful in correcting the problem through this interaction, an alarm shall occur and the affected
compressor shall be immediately locked off. The control shall re-enable the compressor when the
pressure returns to a safe level. This feature is standard on units equipped with liquid line
transducers and these compressor types:
• 4-Step
• Digital Scroll
• Tandem Digital

3.18 REFRIGERANT PRESSURE TRANSDUCER FAILURE


The control shall monitor the high-side and low-side refrigerant pressure transducers. If the control
senses the transducer has failed, has been disconnected, has shorted or the reading has gone out of
range, the user shall be notified through an event on the local display and remote monitoring. The
corresponding circuit that the failure has occurred on shall be disabled to prevent unit damage.

3.19 OIL RETURN PROTECTION


The control shall monitor compressor operation and staging to ensure that liquid and hot gas velocity
are maintained for proper oil return to the compressor.

3.20 DIGITAL SCROLL HIGH-TEMPERATURE PROTECTION


The control shall monitor digital scroll temperature during unit operation. A compressor temperature
limit shall be imposed to help prevent damage to the compressor. If the temperature reaches the
maximum temperature limit, the compressor shall be locked out for 30 minutes and an alarm shall be
annunciated on the local display and through monitoring. After the initial lockout, the control shall
continue to monitor compressor temperature during the off-cycle and re-enable the circuit once a safe
operating temperature is reached and the 30 minutes has elapsed. The control shall store the number
of high-temperature trips. The number of trips shall be accessible through the local display.

3.21 DIGITAL SCROLL SENSOR FAILURE


The control shall monitor the status of the digital scroll sensor(s). If the control senses that the
thermistor is disconnected, shorted or the reading goes out of range, the user shall be notified through
an event on the local display and remote monitoring.

183 Liebert® DS™


Guide Specifications

3.22 COMPRESSOR SEQUENCING


A user-selectable compressor sequencing parameter shall be provided and shall be accessible through
the local display. This sequencing parameter shall present the user with three choices:
• Always use Compressor 1 as the lead compressor.
• Always use Compressor 2 as the lead compressor.
• Auto: The unit shall automatically stage compressors to keep each unit’s run time within 8 hours
of the other’s run time. NOTE: The Auto setting attempts to maintain equal run times between
compressors. However, the control will not turn Off a compressor to equalize run time when it is
needed to control the space.
First priority: If the safety timings are acceptable for only one compressor, then it is the next to
be started/stopped.
Second priority: If both compressors are Off: The compressor with fewer working hours is the
next to start.
Third priority: If both compressors are in operation: the compressor that has been operating
longer since the last start is the next to be stopped.

3.23 COMPRESSOR HIGH- AND LOW-TEMPERATURE LIMIT PROTECTION


The control shall monitor the return air to ensure that the compressor(s) are operated within the
manufacturer’s defined window of operation. If the return air temperature deviates from the
manufacturer’s window of operation, the Liebert iCOM shall automatically adjust to prevent damage
to the cooling unit or reduction in its reliability.

3.24 COMPRESSOR RUN TIME MONITORING


The control shall log these compressor statistics:
• Number of compressor starts
• Run hours
• Average run time
• Starts per day
• Starts per day worst
• Number of high-pressure alarms
• Operating phase in which the high-pressure alarm occurred
• Number of low-pressure alarms
• Operating phase in which the low-pressure alarm occurred
• Number of compressor overloads
• Number of high-temperature alarms (scroll compressors)
The user shall have the ability to monitor compressor operating temperature and pressure from the
local display to be used as a diagnostic tool.

3.25 MANUAL COMPRESSOR DISABLEMENT


The user shall have the ability to disable compressor operation using a set of either normally open or
normally closed dry contacts tied directly to the control or through remote monitoring. An additional
enable/disable feature shall be provided to allow the user to permanently disable an individual
compressor circuit for maintenance using the local display.

Liebert® DS™ 184


Guide Specifications

3.26 MANUAL COMPRESSOR OPERATION


The user shall be able to operate each compressor(s) manually from the local display. The user shall
be able to energize refrigeration components including liquid line solenoid valves, compressor
contactors, electronic expansion valves and adjust capacity for troubleshooting or repair. The control
shall monitor the compressor during manual operation and shall shut the compressor down if needed
to prevent electrical or mechanical damage.

3.27 FLOODED START PROTECTION


The control shall isolate each compressor through a dedicated circuit liquid line solenoid valve and/or
electronic expansion valve. These devices, combined with a spring-closed discharge check valve and
compressor crankcase heater (air-cooled models), shall help ensure refrigerant does not migrate/carry
oil out of the compressor case during the off cycle.

3.28 COMPRESSOR DEHUMIDIFICATION


The control shall permit the user to specify which compressor is used for dehumidification. The
choices shall be 1st compressor, 2nd compressor, 1 or 2, or BOTH.

185 Liebert® DS™


Guide Specifications

4.0 Miscellaneous Options


4.1 HIGH TEMPERATURE SENSOR—OPTIONAL
The high-temperature sensor shall immediately shut down the environmental control system when
activated. The high-temperature sensor shall be mounted in the electrical panel with the sensing
element in the return air.

4.2 SMOKE SENSOR—OPTIONAL


The smoke sensor shall immediately shut-down the environmental control system and activate the
alarm system when activated. The smoke sensor shall be mounted in the electrical panel with the
sensing element in the return-air compartment. The smoke sensor is not intended to function as or
replace any room smoke-detection system that may be required by local or national codes. The smoke
sensor shall include a supervision contact closure.

4.3 CONDENSATE PUMP, DUAL FLOAT—OPTIONAL


The condensate pump shall have a minimum capacity of 145 GPH (548 l/h) at 20 ft. (58 kPa) head. It
shall be complete with integral dual-float switches, pump-and-motor assembly and reservoir. The
secondary float shall send a signal to the local alarm and shall shut down the unit upon high water
condition.

4.4 LOW-VOLTAGE TERMINAL PACKAGE—OPTIONAL


Factory-installed and factory-wired terminals shall be provided.
• Remote Shutdown Terminals - Two additional pairs of terminals provide the customer with
additional locations to remotely shut down the unit by field-installed devices or controls.
• Extra Common Alarm Contacts - Two additional pairs of terminals provide the customer with
normally open contacts for remote indication of unit alarms.
• Main Fan Auxiliary Switch - One set of normally open contacts wired to the EC fan motor
contactor will close when EC fan operation is required. This set of dry contacts could also be used
to initiate air economizer operation. Air economizer and associated devices by others.
• Liqui-tect Shutdown - One pair of dry contacts for the Liqui-tect sensor signal will provide unit
shut down. (Liqui-tect sensor is not included)

4.5 REMOTE HUMIDIFIER CONTACT—OPTIONAL


Pair of N/O contacts provided for connection to a remote humidifier that allow the unit's humidity
controller to control a humidifier outside the unit. Power to operate the remote humidifier does not
come from the unit

4.6 MAIN FAN OVERLOAD—OPTIONAL


A pair of normally open contacts shall be factory-installed and wired to indicate Main Fan Overload.

4.7 COMPRESSOR OVERLOAD—OPTIONAL


A pair of normally open contacts shall be factory-installed and factory-wired to each compressor to
indicate Compressor Overload.

4.8 WIRED SUPPLY SENSOR(S)—OPTIONAL


Each Liebert iCOM shall have up to 10 optional supply air sensors connected and used as a
controlling sensors or reference. This shall be in addition to the standard factory-supplied supply air
sensor. When multiple sensors are applied for control purposes, the user shall be able to control based
on a maximum or average temperature reading.

Liebert® DS™ 186


Guide Specifications

4.9 WIRED REMOTE SENSOR(S)—OPTIONAL


Each Liebert iCOM shall have up to ten 2T sensors (20 sensor readings total) for control or reference.
As part of the U2U network, those sensors shall be shared and used to control the units and provide
greater flexibility, visibility and control using that to respond to changes in the data center. When the
sensors are used for control, the user may set the control to be based off a maximum or average of a
select highest temperature reading.

4.10 STATIC PRESSURE TRANSDUCER(S)—OPTIONAL


Each Liebert iCOM shall have up to four factory-installed and factory-programmed static pressure
transducer(s). The transducer(s) may be used for control of fan speed or reference of the supply
plenum pressure. When used for control, the Liebert iCOM shall be capable of:
• Sharing sensor data across multiple units in the U2U network to provide greater flexibility,
visibility and control. Only one transducer shall be required for a group of units however multiple
transducers may be applied per group and aggregated for redundancy.
• Offering the user selections to control fan from either the average or lowest pressure reading
collected in the U2U network.

4.11 AIR FLOW MONITORING—OPTIONAL


The Liebert iCOM shall monitor evaporator fan airflow for monitoring purpose.

4.12 REMOTE MONITORING—OPTIONAL


A factory-installed communication card shall be provided for monitoring and/or control. The
communication card shall be capable of connecting to Building Management System/Building
Automation System using the following protocols:
• BACnet IP—BACnet over Internet Protocol
• BACnet MSTP—BACnet Master-Slave/Token-Passing (MSTP) communications protocol over a
RS-485 serial network (also known as BACnet MSTP RS-485)
• Modbus RTU—Modbus Remote Terminal Unit (RTU) communication protocol over a RS-485
serial network (also known as Modbus RTU RS-485)
• Modbus TCP—Modbus Transmission Control Protocol over Internet Protocol (also known as
Modbus TCP/IP)
• SNMP
• YDN23 - YD-T-1363 specification protocol (also known as YD/T 1363)
The communications card shall be capable of connecting to two of these protocols at once.

4.13 POWER MONITORING—OPTIONAL


The unit shall be equipped with factory-programmed/installed power meters to monitor power
characteristics for either individual components or the total unit. These meters shall allow the user to
monitor meter connection status, input undervoltage, input RMS voltage leg-to-leg and leg-to-ground,
input current for each phase, energy consumption in kilowatt hours and instantaneous power in
watts. In multi-unit applications, a phase loss protection routine shall place a unit into standby mode
in the event.

4.14 LIEBERT LIQUI-TECT® SENSORS


Provide ____ (quantity) solid state water sensors under the raised floor.

4.19 FLOOR STAND


The floor stand shall be constructed of a welded steel frame. The floor stand shall have adjustable legs
with vibration isolation pads. The floor stand shall be ____ in. (mm) high.

187 Liebert® DS™


Guide Specifications

4.20 SEISMIC RATED FLOOR STAND—OPTIONAL


The floor stand shall be seismic rated and shall be bolted to the unit frame.
4.20.1 Floor Stand Turning Vane—Optional
A turning vane shall be supplied with the floor stand and shall be designed for the specified floor
stand height.

4.21 RETURN AIR PLENUM FOR DOWNFLOW UNITS—OPTIONAL


The air plenum shall be constructed of 20-gauge steel, powder-coated to match unit color. The plenum
shall be ___ in. (mm) high. A door shall be included in the front of the plenum to enable front filter
access. Air shall enter the plenum from the top.

4.22 DISCHARGE AIR PLENUM FOR UPFLOW UNITS,


WITH DISCHARGE GRILLE(S)—OPTIONAL
The air plenum shall be constructed of 20-gauge steel, powder-coated to match unit color. The plenum
shall be ___in. (mm) high. Discharge air grilles shall be painted black and shall be included on the
(front), (rear), (left side) or (right side) of the plenum.

4.22 DISCHARGE AIR PLENUM


FOR UPFLOW UNITS, WITHOUT DISCHARGE GRILLE(S)—OPTIONAL
The air plenum shall be constructed of 20-gauge steel, powder-coated to match unit color. The plenum
shall be ___ in. (mm) high. Air shall discharge from the top of the plenum.

5.0 HEAT REJECTION


5.1 OPTIONS—AIR-COOLED LIEBERT MC CONDENSER
The indoor evaporator unit shall include refrigerant piping, with a factory holding charge of nitrogen.
The hot-gas and liquid lines shall be spun shut and shall include a factory-installed Schrader valve.
Field-relief of the Schrader valve shall indicate a leak-free system.
5.1.1 Liebert MC Summary
These specifications describe requirements for a Liebert air-cooled condenser for a Liebert Thermal
Management system. The condenser shall be designed to reject waste heat to outdoor air and to
control refrigerant head pressure as indoor equipment loading and outdoor ambient conditions
change.
The manufacturer shall design and furnish all equipment in the quantities and configurations shown
on the project drawings.
Standard 60-Hz units shall be CSA-certified to the harmonized U.S. and Canadian product safety
standard “CSA C22.2 No 236/UL 1995 for Heating and Cooling Equipment” and shall be marked with
the CSA c-us logo.
5.1.2 Liebert MC Design Requirements
The air-cooled condenser shall be a factory-assembled unit, complete with integral electrical panel,
designed for outdoor installation. The condenser shall be a draw-through design.
5.1.3 Liebert MC Standard Features
Condenser shall consist of microchannel condenser coil(s), propeller fan(s) direct-driven by individual
fan motor(s), electrical controls, housing and mounting legs. The Liebert air-cooled condenser shall
provide positive refrigerant head pressure control to the indoor cooling unit by adjusting heat
rejection capacity. Microchannel coils shall provide superior heat transfer, reduce air-side pressure
drop, increase energy efficiency and significantly reduce the system refrigerant volume required. EC
fans and fan operating techniques shall reduce sound levels. Various methods shall be available to
match indoor unit type, maximum outdoor design ambient and maximum sound requirements.

Liebert® DS™ 188


Guide Specifications

5.1.4 Liebert MC Coil


Liebert MC coils shall be constructed of aluminum microchannel tubes, fins and manifolds. Tubes
shall be flat and contain multiple, parallel-flow microchannels and span between aluminum headers.
Full-depth louvered aluminum fins shall fill spaces between the tubes. Tubes, fins and aluminum
headers shall be oven-brazed to form a complete refrigerant-to-air heat exchanger coil. Copper stub
pipes shall be electric resistance-welded to aluminum coils and joints protected with polyolefin to seal
joints from corrosive environmental elements. Coil assemblies shall be factory leak tested at a
minimum of 300 psig (2068 kPag). Hot -gas and liquid lines shall be copper and shall be brazed using
nitrogen gas flow to the stub pipes with spun-closed ends for customer piping connections. Complete
coil/piping assembly shall be then filled and sealed with an inert gas holding charge for shipment.
Aluminum Microchannel Coil with E-Coat-Optional
Aluminum microchannel coil with E-coat shall provide a flexible epoxy coating to all coil surface areas
without material bridging between fins. E-coat shall increase coil corrosion protection and shall
reduce heat rejection capacity degradation to less than 10% after a severe 2000 hour 5% neutral salt-
spray test (ref. ASTM B117). The coating process shall ensure complete coil encapsulation, and the
color shall be black.
5.1.5 Liebert MC™ Fan Motor/Blade Assembly
The fan motor/blade assembly shall have an external rotor motor, fan blades and fan/finger guard.
Fan blades shall be constructed of cast aluminum or glass-reinforced polymeric material. Fan guards
shall be heavy gauge, close-meshed steel wire, coated with a black, corrosion-resistant finish. Fan
terminal blocks shall be in an IP54 enclosure on the top of the fan motor. Fan assemblies shall be
factory-balanced, tested before shipment, and mounted securely to the condenser structure.
Liebert MC Condenser EC Fan Motor
The EC-fan motors shall be electronically commutated for variable-speed operation and shall have
ball bearings. The EC fans shall provide internal overload protection through built-in electronics.
Each EC-fan motor shall have a built-in controller and communication module linked via RS485
communication wire to each fan and the Premium Control Board, allowing each fan to receive and
respond to precise fan speed inputs from the Premium Control Board.

189 Liebert® DS™


Guide Specifications

5.1.6 Liebert MC Electrical Controls


Electrical controls and service-connection terminals shall be provided and factory-wired inside the
attached control panel section. Only high-voltage supply wiring and low-voltage indoor-unit
communication/interlock wiring are required at condenser installation.
EC Fan Speed and Premium Control
The EC fan/Premium Control System shall include an electronic control board, EC-fan motor(s) with
internal overload protection, refrigerant and ambient temperature thermistors and refrigerant
pressure transducers. The Premium Control Board shall communicate directly with the indoor unit's
Liebert iCOM control via field-supplied CANbus communication wires and via field-supplied low-
voltage interlock wires. The control board shall use sensor and communication inputs to maintain
refrigerant pressure by controlling each EC fan on the same refrigerant circuit to the same speed. The
Premium control board shall be rated to a temperature of –30°F to 125°F. The premium control shall
be factory-set for (fan speed) (fan speed with Liebert Lee-Temp™) control.
Locking Disconnect Switch
A locking-type disconnect switch shall be factory-mounted and wired to the electrical panel and be
capable of disrupting the flow of power to the unit and controlled via an externally-mounted locking
and lockable door handle. The locking disconnect shall be lockable in support of lockout/tagout safety
programs.
Short Circuit Current Rating
The electrical panel shall provide at least 65,000 A SCCR.
Cabinet
The condenser cabinet shall be constructed of bright aluminum sheet and divided into individual fan
sections by full-width baffles. Internal structural support members, including coil support frame,
shall be galvanized steel for strength and corrosion resistance. Panel doors shall be provided on two
sides of each coil/fan section to permit coil cleaning. An electrical panel shall be contained inside a
factory-mounted NEMA 3R weatherproof electrical enclosure.
5.1.7 Liebert MC Mounting Legs Standard Aluminum Legs
Aluminum legs shall be provided to mount unit for vertical air discharge with rigging holes for
hoisting the unit into position. Standard height is 18 in. (457 mm).
Optional Galvanized-steel Legs with Bracing
Condensers shall be shipped with (36 in. [914 mm]) (48 in. [1219 mm]) (60 in. [1524 mm]) mounting
legs with stabilization bracing. Legs, bracing and hardware shall be galvanized steel.
5.1.8 Liebert MC Condenser Accessories
Liebert Lee-Temp™ System-Optional
Liebert Lee-Temp Receiver Kit shall contain an insulated, heated receiver tank with sight glasses,
mounting plate, mounting hardware, pressure-relief valve, rota-lock valve for refrigerant charge
isolation and piping assembly with head-pressure operated 3-way valve and check valve. Components
shall be field-assembled to the condenser. The 3-way valve shall sense refrigerant head pressure and
adjust the flooding charge in the condenser coil to adjust the condenser heat-rejection capacity. The
Liebert Lee-Temp heater shall be 150 W, shall include an integral thermostat to maintain refrigerant
temperature at a minimum of 85°F (29°C) and shall require a separate power supply
of (208/230V - 1 ph - 60 Hz) (120V - 1 ph - 60 Hz).
The Liebert Lee-Temp Kit shall function with Liebert MC variable-speed fan motors and electronic
controls that lower fan speed in lower outdoor ambient temperatures for maximum energy efficiency.
This system shall allow system start-up and positive head-pressure control with ambient
temperatures as low as –30°F (–34.4°C).
Liebert MC 575 Volt—Optional
The condenser cabinet shall include a secondary, factory-mounted, NEMA 3R weatherproof electrical
enclosure. The secondary enclosure shall contain a 575-V transformer and protective fuses. All wiring
between main and secondary electrical enclosures shall be factory-provided. All field electrical
connections shall be made in the main electrical enclosure.

Liebert® DS™ 190


Guide Specifications

5.1.9 Fusible Plug Kit—Optional


A fusible plug kit shall be field-installed on the liquid line for compliance with building codes
requiring refrigerant relief during high-temperature and building-fire conditions.
5.1.10 IBC/OSHPD Seismic Certification
and IBC Wind/Snow Load Compliant—Optional
IBC/OSHPD Seismic Certification and IBC Wind/Snow Load Compliant condensers shall be provided
with any applicable bracing and field-installation instructions. Condensers shall bear a label
certifying compliance with IBC/OSHPD requirements.

5.2 OPTIONS—AIR-COOLED LIEBERT FIN/TUBE CONDENSER


5.2.1 Liebert Fin/Tube Condenser Summary
These specifications describe requirements for a Liebert air-cooled fin/tube condenser for a Liebert
Thermal Management system. The condenser shall be designed to reject waste heat to outdoor air
and to control refrigerant head pressure as outdoor ambient conditions change.
The manufacturer shall design and furnish all equipment in the quantities and configurations shown
on the project drawings.
Standard 60-Hz units are CSA-certified to the harmonized U. S. and Canadian product safety
standard CSA C22.2 No 236/UL 1995 for “Heating and Cooling Equipment” and are marked with the
CSA c-us logo.
5.2.2 Standard Features-All Condensers
Condenser shall consist of condenser coil(s), housing, propeller fan(s) direct-driven by individual fan
motor(s), electrical controls and mounting legs. The Liebert air-cooled condenser shall provide
positive refrigerant head pressure control to the indoor cooling unit by adjusting heat-rejection
capacity. Various methods shall be available to match indoor unit type, minimum outdoor design
ambient and maximum sound requirements.
5.2.3 Condenser Coil
Liebert-manufactured coil shall be constructed of copper tubes in a staggered tube pattern. Tubes are
expanded into continuous, corrugated aluminum fins. The fins have full-depth fin collars completely
covering the copper tubes, which are connected to heavy wall Type “L” headers. Inlet-coil connector
tubes pass through relieved holes in the tube sheet for maximum resistance to piping strain and
vibration. Coil shall be [(single circuit) (dual circuit)]. The hot-gas and liquid lines shall be spun shut
and shall include a factory-installed Schrader valve. Coils shall be factory leak-tested at a minimum
of 300 psig (2068 kPag), dehydrated, then filled and sealed with a low-pressure inert gas holding
charge for shipment. Field relief of the Schrader valve shall indicate a leak-free system.
5.2.4 Housing
The condenser housing shall be constructed of bright aluminum sheet and divided into individual fan
sections by full-width baffles. Structural support members, including coil support frame, motor and
drive support, are galvanized steel for strength and corrosion resistance. Aluminum legs shall be
provided to mount unit for vertical air discharge and have rigging holes for hoisting the unit into
position. An electrical panel shall be inside an integral NEMA 3R weatherproof section of the
housing.
5.2.5 Propeller Fan
Propeller fan shall have aluminum blades secured to corrosion-protected steel hub. Fans shall be
secured to the fan motor shaft by means of the keyed hub and dual set screws. Fan diameter shall be
26 in. (660 mm) or less. Fans shall be factory-balanced and run before shipment. Fan guards shall be
heavy gauge, close-meshed steel wire with corrosion-resistant polyester paint finish that shall be
rated to pass a 1000-hour salt spray test.
5.2.6 Fan Motor
Fan motor shall be continuous air-over design and shall be equipped with rain shield and
permanently-sealed bearing. Motors shall be rigidly mounted on die-formed galvanized-steel
supports.

191 Liebert® DS™


Guide Specifications

5.2.7 Electrical Controls


Electrical controls, overload-protection devices and service-connection terminals shall be provided
and factory-wired inside the integral electrical-panel section of the housing. A locking disconnect
switch shall be factory-mounted and wired to the electrical panel and controlled via an externally-
mounted, locking door handle. An indoor-unit interlock circuit shall enable condenser operation
whenever indoor-unit compressors are active. Only supply wiring and indoor-unit interlock wiring are
required at condenser installation.
5.2.8 Variable Frequency Drive (VFD) Condenser (1 to 4 Fan)
The winter control system for the air-cooled condenser shall be Liebert Fan Speed Control. The VFD
condenser shall have a variable frequency drive controlling one inverter-duty, variable-speed motor
and On/Off fan motor(s) (for multiple-fan models only) to vary the air flow across the coil. The VFD
shall use one or more pressure transducers to sense refrigerant pressure to adjust fan speed to a
positive head-pressure control range. The inverter duty motor shall have permanently-lubricated,
ceramic ball bearings. The Liebert variable-frequency-drive control system shall provide overload
protection for the variable-speed motor. On/Off fan motor(s) shall have individual, internal overload
protection and shall be controlled by ambient-air thermostat(s) increasing/decreasing condenser
capacity in stepped increments. Motors shall have a TEAO enclosure and a full speed
of 1140 RPM @ 60 Hz (950 RPM @ 50 Hz). A disconnect switch shall be factory-mounted and wired to
the condenser control panel, accessible from the exterior. An internal Surge Protective Device (SPD)
shall protect the VFD from power surges. Alarm contacts for the SPD and VFD shall be provided for
monitoring of system components.
The VFD Control system shall provide positive start-up and operation in ambient temperature as low
as [0°F (–17.8°C)] [–20°F (–28.9°C) with optional, low-ambient, VFD heater kit]. The air-cooled
condenser shall have a ____ volt, 3 ph ____ Hz power supply.
5.2.9 Liebert Lee-Temp System -Optional (All Fan Quantities)
Liebert Lee-Temp condensers shall consist of fixed-speed fan motor(s), controlled by internal
contactor(s). Fans shall run full speed whenever compressors are running. The fixed-speed motors
shall be 3-phase and provide individual, internal overload protection. Fixed-speed motors shall have a
TEAO enclosure and a full speed of 1140 rpm @ 60Hz (950 rpm @ 50 Hz). An optional disconnect
switch shall be factory-mounted and wired to the condenser control panel, accessible from the
exterior.
Each refrigerant circuit shall have an insulated, heated receiver tank with sight glasses, pressure-
relief valve, rota-lock valve for refrigerant charge isolation, and piping assembly with head-pressure
operated 3-way valve and check valve. Components shall be field-assembled to the condenser. The
3-way valve shall sense refrigerant head pressure and adjust the flooding charge in the condenser coil
to adjust the condenser heat-rejection capacity. The Liebert Lee-Temp heater shall be [(150 W)
(300 W)], include an integral thermostat to maintain refrigerant temperature at a minimum
of 85°F (29°C) and requires a separate power supply of [(208/230-1-60) (120-1-60) (200/230-1-50)
(110-1-50)].
This system shall allow system start-up and positive head-pressure control with ambient
temperatures as low as –30°F (–34.4°C). The air-cooled condenser shall have a ____ volt, 3 ph ____ Hz
power supply.
5.2.10 Fan Speed Control (FSC) Condenser (2, 3 or 4 Fans)
The FSC condenser shall have a fan-speed controller sensing refrigerant pressure and varying the
speed of an FSC duty motor. Additional fan motors shall be fixed-speed, cycled On/Off by ambient-air
thermostats to further vary the airflow across the coil. The FSC motor shall be single-phase and
include built-in overload protection. FSC motor shall have an ODP enclosure and a full speed of
1100 RPM @ 60 Hz (920 RPM @ 50 Hz). The fixed-speed motors shall be 3-phase and have individual,
internal overload protection. Fixed-speed motors shall have a TEAO enclosure and a full speed of
1140 RPM @ 60 Hz (950 RPM @ 50 Hz). An optional disconnect switch shall be factory-mounted and
wired to the condenser control panel, accessible from the exterior. FSC Condenser shall only be
applied to standard-scroll or semi-hermetic compressor systems.
This system shall provide positive start-up and operation in ambient temperature as low as
–20°F (–28.9°C). The air-cooled condenser shall have a ____ volt, 3 ph, ____ Hz power supply.

Liebert® DS™ 192


Guide Specifications

5.2.11 Fan Speed Control (FSC) Condenser (6 and 8 Fans)


The FSC condenser shall have 2 fan-speed controllers, each sensing the refrigerant pressure of its
associated refrigerant circuit and independently varying the speed of the FSC duty motor. Additional
motors shall be fixed-speed, cycled On/Off by ambient-air thermostats to further vary the airflow
across the coil. The FSC motors shall be single-phase and include built-in overload protection. FSC
motors shall have an ODP enclosure and a full speed of 1100 RPM @ 60 Hz (920 RPM @ 50 Hz). The
fixed-speed motors shall be 3-phase and have individual, internal overload protection. Fixed-speed
motors shall have a TEAO enclosure and a full speed of 1140 RPM @ 60 Hz (950 RPM @ 50 Hz). An
optional disconnect switch shall be factory-mounted and wired to the condenser control panel,
accessible from the exterior. FSC Condenser shall only be applied to standard-scroll or semi-hermetic
compressor systems.
The fan-speed control system shall provide positive start-up and operation in ambient temperature as
low as –20°F (–28.9°C). The air-cooled condenser shall have a ____ volt, 3 ph, ____ Hz power supply.

5.3 OPTIONS—LIEBERT DRYCOOLER


5.3.1 Liebert Drycooler Summary
These specifications describe requirements for a Liebert air-cooled drycooler for a Liebert Thermal
Management system. The drycooler shall be designed to reject waste heat to outdoor air and to control
glycol temperature as pumped glycol rates and outdoor ambient conditions change.
The manufacturer shall design and furnish all equipment in the quantities and configurations shown
on the project drawings.
Standard 60-Hz units shall be CSA-certified to the harmonized U.S. and Canadian product safety
standard CSA C22.2 No 236/UL 1995 for Heating and Cooling Equipment and shall be marked with
the CSA c-us logo.
5.3.2 Liebert Design Requirements
The drycooler shall be a factory-assembled unit, complete with integral electrical panel, designed for
outdoor installation and vertical air flow only. The drycooler shall be a draw-through design.
5.3.3 Liebert Drycooler Standard Features—All Drycoolers
The drycooler shall consist of drycooler coil(s), housing, propeller fan(s) direct-driven by individual fan
motor(s), electrical controls, and mounting legs. The Liebert air-cooled drycooler shall provide glycol
temperature control to the indoor cooling unit by adjusting heat-rejection capacity. Various methods
shall be available to match indoor unit type, minimum outdoor design ambient and maximum sound
requirements.
5.3.4 Liebert Drycooler Coil
The Liebert-manufactured coil shall be constructed of copper tubes in a staggered tube pattern. Tubes
shall be expanded into continuous, corrugated aluminum fins. The fins shall have full-depth fin
collars completely covering the copper tubes, which shall connected to heavy wall Type “L” headers.
Inlet-coil connector tubes shall pass through relieved holes in the tube sheet for maximum resistance
to piping strain and vibration. Coil shall be split-flow into multiple coil circuits, combined to yield a
drycooler with ______ internal circuits. The supply and return lines shall be (spun shut [1 to 4 fan
models]), (brazed with a cap [6 or 8-fan models]) and shall include a factory-installed Schrader valve.
Coils shall be factory leak-tested at a minimum of 300 psig (2068 kPag), dehydrated, then filled and
sealed with an inert-gas holding charge for shipment. Field relief of the Schrader valve shall indicate
a leak-free coil.
5.3.5 Housing
The drycooler housing shall be constructed of bright aluminum sheet and divided into individual fan
sections by full-width baffles. Structural support members, including coil support frame, motor, and
drive support, shall be galvanized steel for strength and corrosion resistance. Aluminum legs shall be
provided to mount unit for vertical air discharge and shall have rigging holes for hoisting the unit into
position. An electrical panel shall be inside an integral NEMA 3R weatherproof section of the
housing.

193 Liebert® DS™


Guide Specifications

5.3.6 Propeller Fan


The propeller fan shall have aluminum blades secured to a corrosion-protected steel hub. Fans shall
be secured to the fan-motor shaft by means of a keyed hub and dual set screws. Fan diameter shall be
26 in. (660 mm) or less. Fans shall be factory-balanced and run before shipment. Fan guards shall be
heavy gauge, close-mesh steel wire with corrosion resistant PVC finish that shall be rated to pass a
675-hour salt spray test.
5.3.7 Fan Motor
The fan motor shall be continuous air-over design and shall be equipped with a rain shield and
permanently-sealed bearings. Motors shall be rigidly mounted on die-formed galvanized-steel
supports.
5.3.8 Electrical Controls
Electrical controls, overload-protection devices and service-connection terminals shall be provided
and factory-wired inside the integral electrical-panel section of the housing. A locking disconnect
switch shall be factory-mounted and wired to the electrical panel and controlled via an externally-
mounted, locking door handle. An indoor-unit interlock circuit shall enable drycooler operation
whenever indoor-unit compressors are active. Only supply wiring, indoor-unit interlock wiring and
high-voltage wiring to pumps when controlled by the drycooler shall be required at drycooler
installation.
5.3.9 Specific Features by Drycooler Type
5.3.9.1 Fan Cycling Control (DSO, DDO) Drycooler (All Fan Quantities)
with Integral Pump Control
The DSO/DDO drycooler shall sense the leaving glycol temperature and cycle fixed-speed fans to
maintain glycol temperatures. Aquastats shall have field-adjustable setpoints. The fixed-speed
motors shall be 3-phase and have individual, internal overload protection. Fixed-speed motors shall
have a TEAO enclosure. The DSO/DDO drycooler shall control operation of glycol pumps powered
from the electrical panel. The air-cooled drycooler shall have a ____ volt, 3 ph, ____ Hz power supply.

5.3.9.2 Fan Cycling Control (DDNT/DNT) Drycooler (All Fan Quantities)


The DDNT/DNT drycooler shall sense the leaving glycol temperature and cycle fixed-speed fans to
maintain glycol temperatures. Aquastats shall have field-adjustable setpoints. The fixed-speed
motors shall be 3-phase and have individual, internal overload protection. Fixed-speed motors shall
have a TEAO enclosure. The air-cooled drycooler shall have a ____ volt, 3 ph, ____ Hz power supply.

5.3.9.3 Main Fan Control (DDNL/DNL) Drycoolers (All Fan Quantities)


The [D]DNL/DNL drycooler shall control fixed-speed fans when an external contact closure completes
the internal 24-VAC circuit. The fixed-speed motors shall be 3-phase and have individual, internal
overload protection. Fixed-speed motors shall have a TEAO enclosure. The air-cooled drycooler shall
have a ____ volt, 3 ph, ____ Hz power supply.

5.3.9.4 No Fan Control (DDNC/DNC) Drycoolers (All Fan Quantities)


The [D]DNC/DNC drycooler shall activate all fixed-speed fans when supply power is applied to the
drycooler. The fixed-speed motors shall be 3-phase and have individual, internal overload protection.
Fixed-speed motors shall have a TEAO enclosure. The air-cooled drycooler shall have a ____ volt,
3 ph, ____ Hz power supply.

5.3.9.5 Liebert Quiet-Line™ Drycoolers (All Fan Quantities)


Liebert Quiet-Line drycoolers shall be available for DSO, DDO, DDNT, DDNL and DDNC control
types. The fan motor(s) shall have a TEAO enclosure and provide individual overload protection for
quiet operation.

Liebert® DS™ 194


Guide Specifications

5.3.10 PUMP CONTROLS WITHIN DRYCOOLER


5.3.10.1 Single Pump Option
Pump controls for a single glycol pump up to 7.5 hp (5.6 kW) shall be incorporated into the same
integral electrical panel as the drycooler fan controls and may include fuses or circuit breakers as
required for the pump motor. Pump voltage, phase and frequency shall be same as drycooler voltage,
phase and frequency.

5.3.10.2 Dual Pump Option


Pump controls for a dual glycol pump system up to 7.5 hp (5.6 kW) shall operate one pump as primary
and the second pump shall operate as a stand-by pump. Pump controls shall be incorporated into the
same integral electrical panel controlling drycooler fans. A factory-supplied, field-installed flow
switch shall sense loss of flow and switch to the stand-by pump for continuous system operation. An
internal switch shall allow manual selection of the primary (lead) pump.
5.3.11 PUMP PACKAGE
Single Pump Package
This system shall be provided with a centrifugal pump mounted in a weatherproof and vented
enclosure. The pump shall be rated for ___ GPM (___ l/m) at ___ ft. (___ kPa) of head and operate on
___ volt, 3-phase, ___ Hz and operate on ___ volt, 3-phase, ___ Hz.
Dual Pump Package
The dual pump package shall include pumps, enclosure, and field-mounted flow switch. The standby
pump shall automatically start up on failure of the lead pump by drycooler pump controls or by a
separate, factory-wired control box and shall include a lead/ lag switch for the pumps. Each pump
shall be rated for _______ GPM (___ l/s) at ___ ft. (___ kPa) of head and operate on ___ volt, 3-phase,
___ Hz.
5.3.12 ANCILLARY ITEMS
Expansion Tanks, Fluid Relief Valves, Air Management and Other Devices
An expansion tank shall be provided for expansion and contraction of the glycol fluid due to
temperature change in the closed system. The tank and air vents shall be field-installed at the
system’s highest elevation to allow venting of trapped air. A fluid-pressure relief valve shall be
provided for system safety. The system shall include (tank-steel [expansion, compression, diaphragm,
bladder], air separator, air vent, fluid-pressure relief valve, pressure gages, flow switches, tempering
valves, [primary, primary and stand-by] pumps, supply and return piping).

5.4 OPTIONS—LIEBERT PIGGYBACK CONDENSER /DRYCOOLER

195 Liebert® DS™


Guide Specifications

6.0 Execution
6.1 INSTALLATION OF THERMAL MANAGEMENT UNITS
6.1.1 General
Install Thermal Management units in accordance with manufacturer’s installation instructions.
Install units plumb and level, firmly anchored in locations indicated and maintain manufacturer’s
recommended clearances.
6.1.2 Electrical Wiring
Install and connect electrical devices furnished by manufacturer but not specified to be factory-
mounted. Furnish copy of manufacturer’s electrical connection diagram submittal to electrical
contractor.
6.1.3 Piping Connections
Install and connect devices furnished by manufacturer but not specified to be factory-mounted.
Furnish copy of manufacturer’s piping connection diagram submittal to piping contractor.
6.1.4 Supply and Drain Water Piping
Connect water supply and drains to air-conditioning unit. Provide pitch and trap as manufacturer's
instructions and local codes require.

6.2 FIELD QUALITY CONTROL


Start the system in accordance with manufacturer's start-up instructions. Test controls and
demonstrate compliance with requirements. These specifications describe requirements for a
computer-room environmental-control system. The system shall be designed to maintain temperature
and humidity conditions in the rooms containing electronic equipment.
The manufacturer shall design and furnish all equipment to be fully compatible with heat-dissipation
requirements.

6.3 WARRANTY START-UP AND CONTROL PROGRAMMING


Engage manufacturer's field service technician to provide warranty start-up supervision and assist in
programming of unit(s) controls and ancillary panels supplied by them.

Liebert® DS™ 196


Technical Support / Service
Web Site
www.liebert.com
Monitoring
liebert.monitoring@emerson.com
800-222-5877
Outside North America: +00800 1155 4499
Single-Phase UPS & Server Cabinets
liebert.upstech@emerson.com
800-222-5877
Outside North America: +00800 1155 4499
Three-Phase UPS & Power Systems
800-543-2378
Outside North America: 614-841-6598
Environmental Systems
800-543-2778
Outside the United States: 614-888-0246
Locations
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Europe
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD) Italy
+39 049 9719 111
While every precaution has been taken to ensure the accuracy Fax: +39 049 5841 257
and completeness of this literature, Liebert Corporation assumes no Asia
responsibility and disclaims all liability for damages resulting from use of
this information or for any errors or omissions.
29/F, The Orient Square Building
© 2014 Liebert Corporation F. Ortigas Jr. Road, Ortigas Center
All rights reserved throughout the world. Specifications subject to change Pasig City 1605
without notice. Philippines
® Liebert is a registered trademark of Liebert Corporation.
All names referred to are trademarks +63 2 687 6615
or registered trademarks of their respective owners. Fax: +63 2 730 9572
SL-18827_REV1_1-17

Emerson Network Power


Liebert
www.emerson.com

www.EmersonNetworkPower.com