11.3 Optional Low Voltage Terminal Package Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
12.0 HEAT REJECTION—LIEBERT MC™ CONDENSER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
12.1 Liebert MC Selections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
12.2 Condenser and Options Net Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
12.3 Sound Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
12.4 Electrical Data—Liebert MC™ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
12.5 Liebert MC™ Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
12.6 Piping Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
12.7 Electrical Field Connections—Liebert MC™. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
13.0 HEAT REJECTION—LIEBERT FIN/TUBE CONDENSERS . . . . . . . . . . . . . . . . . . . . . . . . . . . 134
13.1 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135
13.2 Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
13.2.1 Electrical Data—Fin/Tube Condensers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
13.2.2 Electrical Field Connections—Liebert Fin/Tube Condensers . . . . . . . . . . . . . . . . . . . . . . . . 138
13.3 Piping Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
14.0 HEAT REJECTION—LIEBERT PIGGYBACK CONDENSERS, AIR-COOLED . . . . . . . . . . . . . . . 143
14.1 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144
14.2 Electrical Field Connections—Liebert Piggyback Condensers . . . . . . . . . . . . . . . . . . . . . . 146
14.3 Connection Locations—Liebert Piggyback Condensers . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147
15.0 HEAT REJECTION—LIEBERT FIN/TUBE DRYCOOLERS AND PUMPS . . . . . . . . . . . . . . . . . . 148
15.1 Drycooler Selection—Prop Fan Drycoolers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148
15.2 Liebert Drycooler Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148
15.3 Dimensional Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149
15.3.1 Dimensions—Prop Fan Drycoolers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149
15.4 Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151
15.4.1 Electrical Data—Prop Fan Drycoolers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151
15.5 Piping Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 155
16.0 HEAT REJECTION—PIGGYBACK DRYCOOLERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 158
16.1 Drycooler Selection—Indoor Piggyback Drycoolers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 158
16.2 Electrical Data—Piggyback Drycoolers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 158
16.3 Dimensions—Indoor Piggyback Drycoolers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 159
16.4 Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 160
17.0 PUMP PACKAGES AND EXPANSION TANK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 161
ii
Liebert DS Model Number
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
D S 0 3 5 A U A 0 E I * * * *
Air Distribution
DS = Downflow Standard
VS = Upflow Standard
Factory Configuration
Nominal kW
Number
028, 035, 042, 053, 070, 077, 105
(8, 10, 12, 15, 20, 22, 30 tons) Humidification
Cooling Type 0 - None
A = Air-Cooled I - Infrared
D = Dual-Cool, Air-Cooled S - Steam Generating
H = Dual-Cool, Water-Cooled Canister
K = GLYCOOL (Liebert Economizer Coil)
W = Water/Glycol Reheat Type
0 - None
Compressor E - 3-Stage Electric
D - Digital Scroll, R-407C S - SCR
S - Scroll, R-407C
Voltage Fan Type
U - Semi-Hermetic with Four-Step, R-407C
A - 460/3/60 0 = Forward-Curved
V- Semi-Hermetic with Four-Step, R407C
B - 575/3/60 Blowers
(DS105 water/glycol/GLYCOOL only)
C - 208/3/60 1 = Electronically
D - 230/3/60 Commutated (EC)
2 - 380/3/60 Fans
1 Liebert® DS™
Liebert DS Configurations
NOTE
All field-installed piping must comply with applicable local, state and federal codes.
AIR-COOLED GLYCOL-COOLED
Air-cooled unit piping is spun closed from the Glycol-cooled units are factory-charged and
actory and contains a nitrogen holding charge. tested. Field-supplied and field-installed piping is
ach installation requires field-supplied required from the unit to the drycooler and pump
efrigerant and piping to a condenser. package.
DUAL-COOL
This system has all of the features of a compressorized
system, but adds a second cooling coil that is connected
to a source of chilled water. Cooling is provided by
circulating chilled water, when available, through this
second coil and reducing compressor operation.
Liebert® DS™ 2
Liebert DS Configurations
Front Front
Coil Coil
Supply
Blower
Air
Blower Raised Supply
Floor Air
Raised
Floor
Figure 2 Blower configurations—Downflow, bottom supply and under-floor supply models, EC fans
Return Air Return Air
Filter Filter
Front Front
Coil Coil
Blower
Raised Blower Raised
Floor Floor Floor Stand
(optional )
3 Liebert® DS™
Liebert DS Configurations
EC Fan EC Fan
Front Front
Coil Coil
Filter
Filter
Return Air
Return
Air Ductwork
Upflow, Front Return, EC Fan in Plenum Upflow, Rear Return, Ducted, EC Fan in Plenum
Blower Blower
Front Front
Coil Coil
Filter Filter
Return Return
Air Air
Top Supply, Front Throw Forward-Curved Blowers Top Supply, Rear Throw Forward-Curved Blowers
Liebert® DS™ 4
Liebert DS Configurations
Blower Blower
Front Front
Coil Coil
Filter Filter
Return Return
Air Air
Ductwork Ductwork
Top Supply, Front Throw, Forward-Curved Blowers Top Supply, Rear Throw, Forward-Curved Blowers
5 Liebert® DS™
Liebert DS Configurations
17
16
15
3
14
13 5
12
11 10
9
8
7
6 18
18
1. Condenser Cleanout Plugs, 10. Infrared Humidifier, optional
fluid-cooled units only 11. Econ-O-Coil Valve, GLYCOOL/Dual Cooling
2. Filters 12. Evaporator Coil
3. Liebert iCOM 13. Condenser Drain Plugs, fluid-cooled units only
4. Smoke Sensor, optional 14. Compressor Section
5. Fan Pulley 15. Electric Box
6. Motor 16. Disconnect, optional
7. Motor Sheave and Belts 17. Variable Frequency Drive (optional on
8. Blower digital scroll units only) DPN000958
9. Condensate Pump, optional 18. EC Fans, optional Rev. 4
Liebert® DS™ 6
Liebert DS Configurations
18
1
2
17 4
16
6
15
7
14
13
9
12 11 10
7 Liebert® DS™
Liebert DS Air-Cooled System Data
Liebert® DS™ 8
Liebert DS Air-Cooled System Data
9 Liebert® DS™
Liebert DS Air-Cooled System Data
Liebert® DS™ 10
Liebert DS Water-Cooled System Data
11 Liebert® DS™
Liebert DS Water-Cooled System Data
1
Table 5 Application data—Water-cooled units with forward-curved blowers
Model Size 28 35 42 053 070 077 105U 105V
APPLICATION DATA WITH FORWARD-CURVED BLOWERS
Net Application Data, BTUH (kW), Standard Air Volume and Evaporator Fan Motor
Semi-Hermetic Compressors (Four-Step Cooling) with Forward-Curved Blowers
85°F DB, 64.5°F WB, 52.3°F DP (29.4°C DB, 18.1°C WB) 32.4% RH
141.6 144.7 165.2 211.9 262.5 289.9 376.4 348.9
Total kBTUH (kW)
(41.5) (42.4) (48.4) (62.1) (76.9) (85.0) (110.3) (102.2)
132.8 141.9 161.7 194.6 248.4 274.4 348.7 338.8
Sensible kBTUH (kW)
(38.9) (41.6) (47.4) (57) (72.8) (80.4) (102.2) (99.3)
80°F DB, 62.9°F WB, 52.3°F DP (26.7°C DB, 17.1°C WB) 38.2% RH
135.9 137.9 157.4 205.2 251.6 278.1 361.8 332.8
Total kBTUH (kW)
(39.8) (40.4) (46.1) (59.7) (73.7) (81.5) (106) (97.5)
120.2 128.3 146.1 180.6 225.5 248.8 315.9 311.7
Sensible kBTUH (kW)
(35.2) (37.6) (42.8) (51.9) (66.1) (72.9) (92.6) (91.3)
75°F DB, 61.1°F WB, 52.3°F DP (23.9°C DB, 16.2°C WB) 45.1% RH
130.5 131.9 150.7 196.9 240.8 266.7 346.9 321.1
Total kBTUH (kW)
(38.3) (38.6) (44.2) (57.2) (70.6) (78.2) (101.7) (94.1)
107.1 113.8 129.3 162.1 200.3 220.8 279.8 277.9
Sensible kBTUH (kW)
(31.4) (33.3) (37.9) (46.4) (58.7) (64.7) (82) (81.4)
Net Application Data BTUH (kW), Standard Air Volume and Evaporator Fan Motor
Scroll Compressors Only
Scroll or Digital Scroll Compressors with Forward-Curved Blowers (not available after 12/31/15)
85°F DB, 64.5°F WB, 52.3°F DP (29.4°C DB, 18.1°C WB) 32.4% RH
117.8 139.7 156.3 219.6 269.6 295.1 374
Total kBTUH (kW) —
(34.5) (40.9) (45.8) (64.9) (79.0) (86.5) (109.6)
117.7 138.5 155.5 207.9 252.5 277.3 347.5
Sensible kBTUH (kW) —
(34.5) (40.6) (45.6) (62.0) (74.0) (81.3) (101.8)
80°F DB, 62.9°F WB, 52.3°F DP (26.7°C DB, 17.1°C WB) 38.2% RH
113.9 133.2 148.8 212.1 259.1 283.6 360
Total kBTUH (kW) —
(33.4) (39.0) (43.6) (62.2) (75.9) (83.1) (105.5)
108.8 125.8 141.6 192.6 229.3 251.5 315.2
Sensible kBTUH (kW) —
(31.9) (36.9) (41.5) (56.4) (67.2) (73.7) (92.4)
75°F DB, 61.1°F WB, 52.3°F DP (23.9°C DB, 16.2°C WB) 45% RH
109.6 127.5 142.3 202.9 248.5 272.9 346.3
Total kBTUH (kW) —
(32.1) (37.4) (41.7) (59.5) (72.8) (80) (101.5)
97 111.7 125.5 171.5 203.9 223.7 280
Sensible kBTUH (kW) —
(28.4) (32.7) (36.8) (50.3) (59.8) (65.5) (82.1)
FAN SECTION - Downflow Models - Fixed Pitch, Two Belts
3 3
Standard Air Volume f /m (m /h) 4,400 5,200 6200 7,500 9,000 10,400 13,700 13,700
0.2" External Static (7,476) (8,835) (10534) (12,743) (15,291) (17,670) (23,276) (23,276)
Standard Fan Motor, hp (kW) 2 (1.5) 3 (2.2) 5 (3.7) 3 (2.2) 5 (3.7) 7.5 (5.6) 10 (7.5) 10 (7.5)
Optional Fan Motor, hp (kW) 3 (2.2) 5 (3.7) 7.5 (5.6) 5 (3.7) 7.5 (5.6) 10 (7.5) 15 (11.2) 15 (11.2)
Number of Fans 1 1 1 2 2 2 3 3
1. Refer to Appendix A for U.S. Department of Energy Performance Data.
2. Application data is rated and factory certified per ASHRAE 127-2012 with a 5% tolerance.
3. Some options or combinations of options may result in reduced air flow—Contact factory for recommendations.
4. Digital scroll not available on 077 and 105 models; units available with semi-hermetic and standard scroll compressors only
Liebert® DS™ 12
Liebert DS Water-Cooled System Data
Capacity, kBTUH (kW), Standard Selection 51.2 51.2 51.2 85.3 85.3 85.3 102.4 102.4
(15.0) (15.0) (15.0) (25.0) (25.0) (25.0) (30.0) (30.0)
Capacity, kBTUH (kW), Optional Selection 34.1 (10.0) 34.1 (10.0) 34.1 (10.0) 15.0 (51.2) 15.0 (51.2) 15.0 (51.2) 20.0 (68.3) 20.0 (68.3)
Electric Reheat - SCR Control, Stainless Steel Fin Tubular (optional selection)
Capacity, kBTUH (kW) 51.2 51.2 51.2 85.3 85.3 85.3 102.4 102.4
(15.0) (15.0) (15.0) (25.0) (25.0) (25.0) (30.0) (30.0)
HUMIDIFIER SECTION
Infrared Humidifier
Capacity, lb./hr. (kg/h) 11.0 (5.0) 11.0 (5.0) 11.0 (5.0) 22.0 (10.0) 22.0 (10.0) 22.0 (10.0) 22.0 (10.0) 22.0 (10.0)
FILTER SECTION
Disposable Type - Nominal Sizes and Quantities, Standard MERV 8 or Optional MERV 11 (Filter types cannot be mixed, must be all MERV 8 or all
MERV 11.)
Downflow Models
Quantity 3 3 3 4 4 4 4 4
Nominal Size, inches 2 @ 25x20 2 @ 25x20 2 @ 25x20 4 @ 25x20 4 @ 25x20 4 @ 25x20 4 @ 25x20 4 @ 25x20
1 @ 25x16 1 @ 25x16 1 @ 25x16
Nominal Size, inches 25x20 25x20 25x20 25x20 25x20 25x20 25x20 25x20
Upflow Models (Front and Rear Return)—Filters located in separate filter box on rear return, located on lower unit panel on front return
Quantity 4 4 4 6 6 6 8 8
WATER COOLED SYSTEM
Semi-Hermetic Compressors, based on 75°F/45% room conditions with EC Fans
Condenser Flow Requirements - Maximum design water pressure 150psi (1034kPa), 350psi (2413kPa) available as option
THR, kBTUH (kW) 167.7 172.3 204.3 255 316.5 360.4 475.5 475.5
(49.2) (50.5) (59.9) (74.7) (92.7) (105.6) (139.3) (139.3)
83°F (28.3°C) EWT, GPM (l/m) 28 29 (109.7) 34 (128.7) 43 (162.7) 53 (200.6) 60 (227.1) 79 (299.0) 79 (299.0)
(105.90)
Pressure Drop, ft. of water (kPa), with valve 8.9 (26.70) 9.5 (28.4) 12.8 (38.3) 11.2 (33.5) 16.6 (49.6) 20.9 (62.5) 31.3 (93.6) 31.3 (93.6)
Standard Scroll Compressors Only
WATER COOLED SYSTEM - Digital Scroll Compressors, based on 75°F/45% room conditions (not available after 12/31/15)
Condenser Flow Requirements - Maximum design water pressure 150psi (1034kPa), 350psi (2413kPa) available as option; with EC Fans
THR, kBTUH (kW) 141.8 169.8 194.5 258.5 325.3 365.6 459.6 —
(41.6) (49.8) (57) (75.8) (95.3) (107.2) (134.7)
28.5 55.5 236.6 295.3
83°F (28.3°C) EWT, GPM (l/m) 24 (90.85) (107.9) 32.5 (123) 44 (166) (210.1) (62.5) (78) —
Pressure Drop, ft. of water (kPa), valve 19.7 (6.6) 27.5 (9.2) 35.3 (11.8) 35 (11.7) 54.1 (18.1) 67.5 (22.6) 91.4 (30.6) —
PIPING CONNECTION SIZES -Water-Cooled Liebert DS Indoor Unit
Water Supply, O.D. Copper 1-5/8" (41) 1-5/8" (41) 2-1/8" (54) 2-1/8" (54) 2-1/8" (54) 2-1/8" (54) 2-1/8" (54) 2-1/8" (54)
Water Return, O.D. Copper 1-5/8 1-5/8" (41) 2-1/8" (54) 2-1/8" (54) 2-1/8" (54) 2-1/8" (54) 2-1/8" (54) 2-1/8" (54)
Infrared Humidifier, O.D. Copper 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4
Condensate Drain, FPT 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4
Condensate Drain w/Optional Condensate 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2
Pump, OD
Hot Water Reheat, O.D. Copper 5/8 5/8 5/8 5/8 5/8 5/8 5/8 5/8
DUAL-COOL UNITS APPLICATION DATA, Water (0% Glycol), Net Application Data kBTUH (kW)
CAUTION: CuNi coil option must be specified when Econ-O-Coil is applied to open water tower.
75°F DB, 62.57 WB (23.9°C DB, 16.9°C WB) 45% RH, 45°F EWT, 55°F LWT; with EC Fans
Total Capacity, kBTUH (kW) 89.2 101.6 109.8 170.4 198.1 196.8 280.1 280.1
(26.2) (29.8) (32.2) (49.9) (58) (57.7) (82.1) (82.1)
Sensible Capacity, kBTUH (kW) 85 98.2 107.8 157.1 181.4 185.4 63.7 63.7
(24.9) (28.8) (31.6) (46) (53.2) (54.3) (4) (4)
19 22.4 25.5 36.4 47.2 46.1 54.9 54.9
Flow Rate, GPM (I/m) @ 10°F Rise (1.2) (1.4) (1.6) (2.3) (3.0) (2.9) (3.5) (3.5)
Pressure Drop, ft. (kPa), valve, coil 6.1 (18.23) 8.3 (24.81) 10.50 10.40 17.2 15.9 (47.6) 18 (53.80) 18 (53.80)
(31.39) (31.09) (51.41)
FLUID VOLUMES
Econ-O-Coil Fluid Volume, gal (l) 5 (19.0) 5 (19.0) 5 (19.0) 8 (30.4) 8 (30.4) 8 (30.4) 10 (38.0) 10 (38.0)
Unit Volume, Without Econ-O-Coil, gal, (l) 4 (15.2) 4 (15.2) 4 (15.2) 7 (26.6) 7 (26.6) 7 (26.6) 8 (30.4) 8 (30.4)
13 Liebert® DS™
Liebert DS Glycol-Cooled System Data
Liebert® DS™ 14
Liebert DS Glycol-Cooled System Data
15 Liebert® DS™
Liebert DS Glycol-Cooled System Data
Liebert® DS™ 16
Liebert DS GLYCOOL™ System Data
™
5.0 LIEBERT DS GLYCOOL SYSTEM DATA
Table 10 Application data—GLYCOOL units with EC fans 1
Model Size 028 035 042 053 070 077 105U 105V
APPLICATION DATA with EC Fans
Net Application Data BTUH (kW), Standard Air Volume and Evaporator Fan Motor,
17 Liebert® DS™
Liebert DS GLYCOOL™ System Data
Liebert® DS™ 18
Liebert DS GLYCOOL™ System Data
Upflow Models (Front & Rear Return) Filters located in separate filter box on rear return, located on lower unit panel on front return
Quantity 4 4 4 6 6 6 8 8
Nominal Size, inches 25x20 25x20 25x20 25x20 25x20 25x20 25x20 25x20
OUTDOOR DRYCOOLERS - Standard 95°F Ambient Selection; See Table 72 for other selections
Model Number D-174 D-174 D-225 D-260 D-310 D-350 D-466 D-466
Number of Fans 2 2 2 3 3 3 4 4
CONDENSER FLOW REQUIREMENTS—40% Ethylene Glycol
GLYCOOL SYSTEM - Semi-Hermetic Compressors, Based on 75°F/45% Room Conditions with EC Fans
THR, kBTUH (kW) 154.9 (45.4) 159 (46.6) 189.2 (55.5) 240.8 (70.6) 297.7 (87.2) 339.3 (99.4) 455.9 (133.6) 455.9 (133.6)
104°F (40°C) EGT, GPM (l/m) 32 (121) 33 (125) 40 (151) 49 (185) 62 (235) 71 (269) 95 (360) 95 (360)
Pressure Drop, ft. of water (kPa), 12.9 (38.50) 13.6 (40.60) 19.6 (58.59) 16.0 (47.83) 25.0 (74.73) 32.2 (96.25) 49.6 (148.30) 49.6 (148.30)
GLYCOOL SYSTEM - Digital Scroll Compressors, Based on 75°F/45% Room Conditions with EC Scroll Compressors Only
Fans (not available after 12/31/15)
THR, kBTUH (kW) 134.5 (39.4) 162.4 (47.6) 186.8 (54.7) 248 (72.7) 311.1 (91.2) 351.1 (102.9) 439.1 (128.7) —
104°F (40°C) EGT, GPM (l/m) 28 (98.4) 33.5 (127) 39 (148) 51 (193) 64 (242) 72 (273) 89 (337) —
Pressure Drop, ft. of water (kPa) 10.0 (29.89) 14.0 (41.85) 18.6 (55.60) 17.2 (51.41) 26.6 (79.51) 33.1 (98.84) 43.8 (130.92) —
PIPING CONNECTION SIZES - Glycol-Cooled Liebert DS Indoor Unit
Glycol Supply, O.D. Copper 1-5/8" (41) 1-5/8" (41) 2-1/8" (54) 2-1/8" (54) 2-1/8" (54) 2-1/8" (54) 2-1/8" (54) 2-1/8" (54)
Glycol Return, O.D. Copper 1-5/8" (41) 1-5/8" (41) 2-1/8" (54) 2-1/8" (54) 2-1/8" (54) 2-1/8" (54) 2-1/8" (54) 2-1/8" (54)
Infrared Humidifier, O.D. Copper 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4
Condensate Drain, FPT 3/4 3/4 3/4 3/4 3/4 3/4 3/4 3/4
Condensate Drain w/Optional
1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2
Condensate Pump, OD
Hot Water Reheat, O.D. Copper 5/8 5/8 5/8 5/8 5/8 5/8 5/8 5/8
ECON-O-COIL APPLICATION DATA (GLYCOOL Units), 40% Ethylene Glycol, Net Application Data, kBTUH (kW)
75°F DB, 62.57°FWB (23.9°C, 16.9°C) 45% RH, 45°F EGT Room Conditions with EC Fans
Total capacity kBTUH (kW) 82.8 (24.3) 93.9 (27.5) 103.9 (30.4) 156.8 (45.9) 182.3 (53.4) 182.3 (57.2) 243.3 (71.3) 243.3 (71.3)
Sensible Capacity 82.4 (24.1) 93.9 (27.5) 103.9 (30.4) 152.6 (44.7) 176.9 (51.8) 176.9 (55.3) 238.2 (69.8) 238.2 (69.8)
Flow rate, GPM (l/m) 28 (106) 33.5 (127) 39 (148) 51 (193) 64 (242) 72 (273) 89 (337) 89 (337)
Pressure Drop, ft. of water (kPa) 18.4 (55.0) 25.7 (76.82) 33.8 (101.03) 38.9 (116.27) 59.1 (176.65) 73.5 (219.70) 75.2 (224.78) 75.2 (224.78)
FLUID VOLUMES
Unit Volume Without Econ-O-Coil,
4 (15.2) 4 (15.2) 4 (15.2) 7 (26.6) 7 (26.6) 7 (26.6) 8 (30.4) 8 (30.4)
gal (l)
Unit Volume w/Econ-O-Coil, gal (l) 9 (34.2) 9 (34.2) 9 (34.2) 14 (53.2) 14 (53.2) 14 (53.2) 17 (64.6) 17 (64.6)
19 Liebert® DS™
Electrical Data
Humidifier
Options Infrared Infrared None None Humidifier No Humidifier
Model
# Volts 208 230 460 575 208 230 460 575 208 230 460 575 208 230 460 575 208 230 460 575 208 230 460 575
FLA 67.3 64.8 32.1 25.5 56.3 54.1 26.9 24.2 67.3 64.8 32.1 25 43 43 21.1 16.8 56.3 54.1 26.9 24.2 53.5 51.9 25.6 19.9
DS028 WSA 82 78.9 39.2 31.9 60.6 58.4 29.1 25.9 82 78.9 39.2 30.5 47.3 47.3 23.3 18.5 64.8 62.8 31.1 25.9 64.8 62.8 31.1 24.1
OPD 80 80 40 30 70 70 35 30 80 80 40 30 60 60 30 25 70 70 35 30 70 70 35 25
FLA 70.7 68.2 33.4 25.5 63.1 60.9 29.5 25.2 70.7 68.2 33.4 25.5 49.8 49.8 23.7 17.8 63.1 60.9 29.5 25.2 56.9 55.3 26.9 20.4
DS035 WSA 86.3 83.2 40.8 31.9 68.3 66.1 32 27.1 86.3 83.2 40.8 31.1 55 55 26.2 19.7 69 67 32.7 27.1 69 67 32.7 24.8
OPD 90 90 45 30 80 80 40 30 90 90 45 30 70 70 35 25 80 80 40 30 80 80 35 25
FLA 78.2 75.9 37.7 33 78.1 75.9 37.7 33 78.2 75.7 37.5 29.4 64.8 64.8 31.9 25.6 78.1 75.9 37.7 33 64.8 64.8 31.9 25.6
DS042 WSA 95.7 92.5 46 36 85.2 83 41.2 35.8 95.7 92.5 46 36 71.9 71.9 35.4 28.4 85.2 83 41.2 35.8 78.4 76.4 37.8 29.6
OPD 110 110 50 45 110 110 50 45 110 110 50 40 100 100 45 35 110 110 50 45 100 100 45 35
FLA 119.9 116 57.1 43.5 109.2 104.8 52.4 42 119.9 116 57.1 43.5 82.6 82.6 40.8 30.4 109.2 104.8 52.4 42 92.1 89.6 44.1 33.5
DS053 WSA 145.3 140.4 69.4 53.9 117.2 112.8 56.5 45 145.3 140.4 69.4 52.8 90.6 90.62 44.9 33.4 117.2 112.8 56.5 45 110.52 107.4 53.1 40.3
OPD 150 150 70 50 125 125 70 50 150 150 70 50 110 110 60 45 125 125 70 50 125 125 60 45
FLA 129.2 125.3 59.9 46.4 127.8 123.4 58 46.4 129.2 125.3 59.9 45.7 101.2 101.2 46.4 34.8 127.8 123.4 58 46.4 101.4 101.2 46.9 35.7
DS070 WSA 156.9 152 72.9 55.5 138.2 133.8 62.8 50 156.9 152.0 72.9 55.5 111.6 111.6 51.2 38.4 138.2 133.8 62.8 50 122.15 119.02 56.6 43
OPD 175 175 80 60 175 175 80 60 175 175 80 60 150 150 70 50 175 175 80 60 150 150 70 50
FLA 139.2 134.8 61.4 50 139.2 134.8 61 50 134.9 131 61.4 47.5 112.6 112.6 49.4 38.4 139.2 134.8 61 50 112.6 112.6 49.4 38.4
DS077 WSA 164 159.2 74.8 57.8 151. 146.6 66.2 54 164.0 159.2 74.8 57.8 124.37 124.4 54.6 42.4 151 146.6 66.2 54 129.27 126.15 58.5 45.3
OPD 175 175 80 70 175 175 80 70 175 175 80 60 150 150 70 50 175 175 80 70 150 150 70 50
FLA 171.5 167.1 83.7 69.1 171.5 167.1 83.7 69.1 164 163.5 79.8 62.6 144.9 144.9 72.1 57.5 171.5 167.1 83.7 69.1 144.9 144.9 72.1 57.5
DS105 WSA 198.8 198.2 97.4 76.4 186.5 182.1 91.6 75.4 198.8 198.2 97.4 76.4 159.9 159.9 80 63.8 186.5 182.1 91.6 75.4 169.3 165.5 81.3 63.9
OPD 225 225 110 100 225 225 110 100 225 225 110 90 200 200 110 80 225 225 110 100 200 200 110 80
1. Reduced reheat for 028, 035, and 042 models is 10kW.
2. Reduced reheat for 053, 070, and 077 models is 15kW.
3. Consult local representative for SCR reheat values.
4. Reduced reheat for 105 kW models is 20kW.
5. SCCR - Short Circuit Current Rating 65,000 amps rms symmetrical maximum.
6. Steam canister humidifiers not available on models with EC fans.
Liebert® DS™ 20
Electrical Data
21 Liebert® DS™
Electrical Data
Liebert® DS™ 22
Electrical Data
Humidifier
Options Infrared Infrared None None Humidifier None
Model# Volts 208 230 460 575 208 230 460 575 208 230 460 575 208 230 460 575 208 230 460 575 208 230 460 575
FLA 67.3 64.8 32.1 25.5 56.3 54.1 26.9 24.2 67.3 64.8 32.1 25 43 43 21.1 16.8 56.3 54.1 26.9 24.2 53.5 51.9 25.6 19.9
028 WSA 82 78.9 39.2 31.9 60.6 58.4 29.1 25.9 82 78.9 39.2 30.5 47.3 47.3 23.3 18.5 64.8 62.8 31.1 25.9 64.8 62.8 31.1 24.1
OPD 80 80 40 30 70 70 35 30 80 80 40 30 60 60 30 25 70 70 35 30 70 70 35 25
FLA 70.7 68.2 33.4 25.5 63.1 60.9 29.5 25.2 70.7 68.2 33.4 25.5 49.8 49.8 23.7 17.8 63.1 60.9 29.5 25.2 56.9 55.3 26.9 20.4
035 WSA 86.3 83.2 40.8 31.9 68.3 66.1 32 27.1 86.3 83.2 40.8 31.1 55 55 26.2 19.7 69 67 32.7 27.1 69 67 32.7 24.8
OPD 90 90 45 30 80 80 40 30 90 90 45 30 70 70 35 25 80 80 40 30 80 80 35 25
FLA 78.2 75.9 37.7 33 78.1 75.9 37.7 33 78.2 75.7 37.5 29.4 64.8 64.8 31.9 25.6 78.1 75.9 37.7 33 64.8 64.8 31.9 25.6
042 WSA 95.7 92.5 46 36 85.2 83 41.2 35.8 95.7 92.5 46 36 71.9 71.9 35.4 28.4 85.2 83 41.2 35.8 78.4 76.4 37.8 29.6
OPD 110 110 50 45 110 110 50 45 110 110 50 40 100 100 45 35 110 110 50 45 100 100 45 35
FLA 119.9 116 57.1 43.5 109.2 104.8 52.4 42 119.9 116 57.1 43.5 82.6 82.6 40.8 30.4 109.2 104.8 52.4 42 92.1 89.6 44.1 33.5
053 WSA 145.3 140.4 69.4 53.9 117.2 112.8 56.5 45 145.3 140.4 69.4 52.8 90.6 90.62 44.9 33.4 117.2 112.8 56.5 45 110.5 107.4 53.1 40.3
OPD 150 150 70 50 125 125 70 50 150 150 70 50 110 110 60 45 125 125 70 50 125 125 60 45
FLA 129.2 125.3 59.9 46.4 127.8 123.4 58 46.4 129.2 125.3 59.9 45.7 101.2 101.2 46.4 34.8 127.8 123.4 58 46.4 101.4 101.2 46.9 35.7
070 WSA 156.9 152 72.9 55.5 138.2 133.8 62.8 50 156.9 152.0 72.9 55.5 111.6 111.6 51.2 38.4 138.2 133.8 62.8 50 122.2 119.02 56.6 43
OPD 175 175 80 60 175 175 80 60 175 175 80 60 150 150 70 50 175 175 80 60 150 150 70 50
FLA 139.2 134.8 61.4 50 139.2 134.8 61 50 134.9 131 61.4 47.5 112.6 112.6 49.4 38.4 139.2 134.8 61 50 112.6 112.6 49.4 38.4
077 WSA 164 159.2 74.8 57.8 151. 146.6 66.2 54 164.0 159.2 74.8 57.8 124.4 124.4 54.6 42.4 151 146.6 66.2 54 129.3 126.15 58.5 45.3
OPD 175 175 80 70 175 175 80 70 175 175 80 60 150 150 70 50 175 175 80 70 150 150 70 50
FLA 171.5 167.1 83.7 69.1 171.5 167.1 83.7 69.1 164 163.5 79.8 62.6 144.9 144.9 72.1 57.5 171.5 167.1 83.7 69.1 144.9 144.9 72.1 57.5
105U WSA 198.8 198.2 97.4 76.4 186.5 182.1 91.6 75.4 198.8 198.2 97.4 76.4 159.9 159.9 80 63.8 186.5 182.1 91.6 75.4 169.3 165.5 81.3 63.9
OPD 225 225 110 100 225 225 110 100 225 225 110 90 200 200 110 80 225 225 110 100 200 200 110 80
FLA 164 163.5 82.5 64.7 158.6 154.2 75.7 62.2 164 163.5 82.5 64.7 132 132 64.1 50.6 158.6 154.2 75.7 62.2 140.4 137.4 69.6 54.7
105V WSA 198.8 198.2 100.1 78.5 173.6 169.2 83.6 68.5 198.8 198.2 100.1 78.5 147 147 72 56.9 173.6 169.2 84 68.5 169.3 165.5 84 66
OPD 225 225 110 90 225 225 110 90 225 225 110 90 200 200 100 80 225 225 110 90 200 200 100 80
1. Reduced reheat for 028, 035, and 042 models is 10kW.
2. Reduced reheat for 053, 070, and 077 models is 15kW.
3. Consult local representative for SCR reheat values.
4. Reduced reheat for 105 kW models is 20kW.
5. SCCR - Short Circuit Current Rating 65,000 amps rms symmetrical maximum.
6. Steam canister humidifiers not available on models with EC fans.
23 Liebert® DS™
Electrical Data
Liebert® DS™ 24
Electrical Data
25 Liebert® DS™
Weights and Dimensions
Liebert® DS™ 26
Weights and Dimensions
27 Liebert® DS™
Weights and Dimensions
Figure 8 Cabinet and floor planning dimensions—Downflow, air-cooled, 28-42kW (8-12 tons), scroll or
digital scroll compressors with EC fans
Secondary Refrigerant
Piping Entrance
56-7/8" (1445mm) Filters are accessible
Opening through top of unit only.
Downflow electrical
connections can be made
from top or bottom of unit.
33"
(838mm) 24-3/8"
AIR INLET OPENING (619mm)
35"
(889mm) Opening
1-3/4" (44mm)
Handle
5/16"
Bezel
(8mm)
5"
(127mm)
76"
(1930mm)
34" (864mm)
Shaded area indicates a
recommended minimum
clearance from floor to top
of unit and plenum for
component access.
2" 72" (1829mm) DPN003131
(51mm)
FRONT VIEW Rev. 1
Liebert® DS™ 28
Weights and Dimensions
Figure 9 Primary connection locations—Downflow, air-cooled, 28-42kW (8-12 tons), EC fans, scroll or
digital scroll compressor models
Y
R
L1 L2 G1 G2
4" (102mm) 35"
(889mm)
11.19" BLOWER
(284mm) ECS OUTLET
LV1
HUM LV2
CD LV3
E1 E2 ECR B
4.5"
73" (1854mm)
(114mm)
FRONT OF UNIT DPN003239
Rev. 0
Table 18 Piping data—Downflow, air-cooled, 28-42kW (8-12 tons), with EC fans, scroll or digital scroll
compressor models
Point Description X Y Connection Size / Opening
R Refrigerant Access 59-5/16 (1507) 14-3/4 (375) 11-3/16 x 4 (284 x 102)
L1 Liquid Line System 1 69-15/16 (1776) 16-13/16 (411) 1/2" Cu Sweat
L2 Liquid Line System 2 67-5/8 (1718) 16-13/16 (411) 1/2" Cu Sweat
G1 Hot Gas Discharge 1 65-1/2 (1664) 16-13/16 (411) 5/8" Cu Sweat
G2 Hot Gas Discharge 2 62-7/16 (1586) 16-13/16 (411) 5/8" Cu Sweat
Condensate Drain 1
46 (1168) 29-1/2 (749) 3/4" FPT
(Infrared Humidifier or No Humidifier)
CD Condensate Drain 1
46 (1168) 29-1/2 (749) 1-1/4" FPT
(Steam Generating Humidifier)
w/Optional Pump 46 (1168) 29-1/2 (749) 1/2" Cu Sweat
HUM Humidifier Supply Line 53-1/2 (1359) 29 (737) 1/4" Cu Sweat
ECS Econ-O-Coil Supply 54-7/8 (1394) 22-9/16 (573) 1-5/8" Cu Sweat
ECR Econ-O-Coil Return 49-3/8 (1254) 30-3/4 (781) 1-5/8" Cu Sweat
HS Hot Water Reheat Supply Consult Factory
HR Hot Water Reheat Return Consult Factory
E1 Electrical Connection (High-Voltage) 55-1/2 (1410) 31-1/4 (794) 2-1/2"
E2 Electrical Connection (High-Voltage) 52-7/16 (1332) 31-1/4 (794) 2-1/2"
LV1 Electrical Connection (Low-Voltage) 2-1/4 (57) 27 (686) 7/8"
LV2 Electrical Connection (Low-Voltage) 2-1/4 (57) 29 (737) 7/8"
LV3 Electrical Connection (Low-Voltage) 2-1/4 (57) 31 (787) 7/8"
B Blower Outlet 4-1/2 (114) 33 (838) 31 x 31 (787 x 787)
1. Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Source: DPN003239, Rev. 0
29 Liebert® DS™
Weights and Dimensions
Figure 10 Cabinet and floor planning dimensions—Downflow, air-cooled, 28-42kW (8-12 tons),
semi-hermetic compressors with EC fans
Secondary Refrigerant
Piping Entrance
56-7/8"
Opening
(1445mm)
5"
(127mm)
76"
(1930mm)
34"
(864mm)
Shaded area indicates a
recommended minimum
clearance from floor
to top of unit and plenum DPN003130
2" 85" (2159mm) for component access. Rev. 1
(51mm)
FRONT VIEW
Liebert® DS™ 30
Weights and Dimensions
Y
R
L1 L2 G1 G2
4" (102mm) BLOWER 35"
OUTLET (889mm)
16-7/16"
ECS
(418mm) LV1
HUM
LV2
CD
E1 E2 ECR B LV3
SECTION A-A
4.5"
FRONT OF UNIT 86" (114mm)
(2184mm)
DPN003598
Rev. 0
31 Liebert® DS™
Weights and Dimensions
Figure 12 Cabinet and floor planning dimensions—Downflow, air-cooled, 53-77kW (15-22 tons), scroll or
digital scroll compressors with EC fans
76"
(1930mm)
34"
(864mm)
Shaded area indicates a
recommended minimum
clearance from floor to top
2" 97" (2464mm) DPN003138
of unit and plenum
(51mm)
FRONT VIEW for component access. Rev. 2
Liebert® DS™ 32
Weights and Dimensions
Figure 13 Primary connection locations—Downflow, air-cooled, 53-77kW (15-22 tons), scroll or digital
scroll compressors, EC fans
Digital scroll compressors not
available on 077 models.
R Y
4" (102mm)
L1 L2 G1 G2 BLOWER
OUTLET 35"
12-3/16" (889mm)
(310mm)
ECS ECR LV1
CD B1 LV2
LV3
E1 E2 HUM
98" (2489mm)
DPN002182
FRONT OF UNIT Rev. 3
Table 19 Piping details—Downflow, air-cooled, 53-77kW (15-22 tons), EC fans, scroll or digital scroll
compressors 3
X Y Connection Size / Opening
Point Description in. (mm) in. (mm) in. (mm)
R Refrigerant Access 81-3/4 (2076) 14-3/4 (374) 12-3/16x4 (310x102)
53kW (15 tons)/ 70 & 77kW (20 & 22 tons)
L1 Liquid Line System 1 94-11/16 (2405) 16-3/4 (425) 1/2 / 5/8 Cu Sweat
L2 Liquid Line System 2 91-7/8 (2334) 16-3/4 (425) 1/2 / 5/8 Cu Sweat
G1 Hot Gas Discharge 1 88-3/4 (2254) 16-3/8 (416) 7/8 / 1-1/8 Cu Sweat
G2 Hot Gas Discharge 2 85-9/16 (2173) 16-3/8 (416) 7/8 / 1-1/8 Cu Sweat
Condensate Drain
68-3/8 (1737) 31-3/8 (797) 3/4 FPT
CD 1 (Infrared Humidifier or No Humidifier)
W/ Optional Pump 68-3/8 (1737) 31-3/8 (797) 1/2 Cu Sweat
HUM Humidifier Supply Line 76-1/2 (1943) 29 (736) 1/4 Cu Sweat
ECS 2 Econ-O-Coil Supply 78-5/8 (1997) 22-1/4 (565) 2-1/8 Cu Sweat
2
ECR Econ-O-Coil Return 73-15/16 (1862) 26-9/16 (675) 2-1/8 Cu Sweat
E1 Electrical Conn. (High-Voltage) 78-1/2 (1994) 31-1/8 (790) 2-1/2
E2 Electrical Conn. (High-Voltage) 75-3/8 (1915) 31-1/8 (790) 2-1/2
LV1 Electrical Conn. (Low-Voltage) 2 (51) 29 (737) 7/8
LV2 Electrical Conn. (Low-Voltage) 2 (51) 30-7/8 (784) 7/8
LV3 Electrical Conn. (Low-Voltage) 2 (51) 32 (813) 7/8
B1 Blower Outlet 4-1/2 (114) 33 (838) 58-3/8x30 (1483x762)
1. Field-pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on dual-cool systems only (four-pipe system).
3. Digital scroll compressors not available on 077 models.
4. Piping dimensions shown are connection sizes; field piping sizes may be different, depending on distance. Refer to user manual,
SL-18825.
5. Source: DPN002182, Rev. 3
33 Liebert® DS™
Weights and Dimensions
Figure 14 Cabinet and floor planning dimensions—Downflow, air-cooled, 53-77kW (15-22 tons),
semi-hermetic compressors with EC fans
Second Refrigerant
Piping Entrance
80" (2032mm)
Opening
Filters are accessible
33" 24-5/8" through top of unit only.
(838mm) AIR INLET OPENING (625mm)
35" Opening Downflow electrical
(889mm) connections can be made
from top or bottom of unit.
5/16"
(8mm)
1-3/4" Bezel
Secondary Entrance (44mm) Handle Secondary Entrance
High-Voltage Connection(s) TOP VIEW Low-Voltage Connections
Minimum required
109" (2769mm) for filter replacement
5"
(125mm)
76"
(1930mm)
34"
(864mm)
108" (2743mm) Shaded area indicates a
2" recommended minimum
(51mm) FRONT VIEW clearance be provided for DPN003137
component access. Rev. 2
Liebert® DS™ 34
Weights and Dimensions
R Y
L1 L2 G1 G2
4" (102mm) BLOWER 35"
OUTLET (889mm)
16-7/16"
(418mm)
ECS ECR LV1
CD B1 LV2
LV3
E1 HUM
109" (2769mm)
DPN002179
FRONT OF UNIT
Rev. 1
35 Liebert® DS™
Weights and Dimensions
Figure 16 Cabinet and floor planning dimensions—Downflow, air-cooled, 105kW (30 tons), standard
scroll and semi-hermetic compressors with EC fans
Secondary Refrigerant Digital scroll compressors
Piping Entrance
102-13/16" not available on 105 models.
(2611mm) Opening
33"
(838mm) 24-3/8"
AIR INLET OPENING (619mm)
35"
(889mm) Opening
5/16"
(8mm)
1-3/4" TOP VIEW Bezels
Secondary Entrance (44mm) Handle Secondary Entrance
High-Voltage Connection(s) Low-Voltage Connections
Minimum required
132" (3353mm) for filter replacement
5"
(127mm)
76"
(1930mm)
34" (864mm)
Shaded area indicates the
minimum clearance
131" (3327mm) required from floor to
FRONT VIEW top of unit and plenum for DPN0003145
Filters are accessible through top of unit only. component access. Rev. 2
Downflow electrical connections can be made
from top or bottom of unit.
Liebert® DS™ 36
Weights and Dimensions
Figure 17 Primary connection locations—Downflow, air-cooled, 105kW (30 tons), standard scroll and
semi-hermetic compressors with EC fans
Y
G1 G2 R 35"
4" (102mm) BLOWER (889mm)
L1 L2 OUTLET
16-7/16"
(418mm) ECS ECR LV1
CD LV2
B1
LV3
E1 E2 HUM
132" (3353mm)
FRONT VIEW DPN002154
Rev. 1
Table 21 Piping data—Downflow, air-cooled 105kW (30 tons) with EC fans, standard scroll 3 and
semi-hermetic compressors
X Y Connection Size / Opening
Point Description in. (mm) in. (mm) in. (mm)
R Refrigerant Access 109 (2769) 15-3/4 (400) 16-7/16 x 4 (418 x 102)
L1 Liquid Line System 1 121-3/4 (3092) 16-3/4 (425) 5/8 Cu Sweat
L2 Liquid Line System 2 118-1/8 (3000) 16-3/4 (425) 5/8 Cu Sweat
G1 Hot Gas Discharge 1 118-1/4 (3004) 14-1/4 (362) 1-1/8 Cu Sweat
G2 Hot Gas Discharge 2 115-5/8 (2937) 14-1/4 (362) 1-1/8 Cu Sweat
Condensate Drain
87-3/8 (2220) 31 (787) 3/4 FPT
CD 1 (Infrared Humidifier or No Humidifier)
W/ Optional Pump 83-13/16 (2129) 30 (762) 1/2 Cu Sweat
HUM Humidifier Supply Line 85-5/16 (2167) 32-1/2 (825) 1/4 Cu Sweat
2
ECS Econ-O-Coil Supply 101-7/8 (2588) 29 (737) 2-5/8 Cu Sweat
ECR 2 Econ-O-Coil Return 94-9/16 (2402) 29 (737) 2-5/8 Cu Sweat
E1 Electrical Connection (High-Voltage) 98-1/8 (2492) 31 (788) 2-1/2
E2 Electrical Connection (High-Voltage) 91 (2311) 31 (788) 2-1/2
LV1 Electrical Connection (Low-Voltage) 2 (51) 29 (737) 7/8
LV2 Electrical Connection (Low-Voltage) 2 (51) 30-7/8 (784) 7/8
LV3 Electrical Connection (Low-Voltage) 2 (51) 32 (813) 7/8
B1 Blower Outlet 4-1/2 (114) 33 (838) 77-3/8 x 30 (1965 x 762)
1. Field-pitch condensate drain line a minimum of 1/8" (3.2mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on dual-cool systems only (four-pipe system)
3. Digital scroll compressors not available on DS 105
4. Piping dimensions shown are connection sizes; field piping sizes may be different, depending on distance. Refer to user manual,
SL-18825.
5. Source: DPN002154, Rev. 1
37 Liebert® DS™
Weights and Dimensions
35" 24-3/8"
(889mm) AIR INLET OPENING (619mm)
33"
Opening
(838mm) 1-3/4"
(44mm) Handle
5/16 Filters are accessible
(8mm) through top of unit only.
Secondary Condenser Fluid Bezel Downflow electrical
Piping Entrance TOP VIEW Secondary Entrance connections can be made
Low-Voltage Connections from top or bottom of unit.
Secondary Entrance
High-Voltage Connection(s)
86" (2184mm) Required for
condenser cleanout
24"
(610mm)
Minimum required
for filter replacement
15"
(381mm)
76"
(1930mm)
34"
Shaded area indicates a (864mm)
2" 85" (2159mm)
(51mm) recommended minimum
FRONT VIEW clearance from floor to top DPN003135
of unit and plenum for
component access.
Rev. 2
Liebert® DS™ 38
Weights and Dimensions
NOTE
1. Drawing not to scale.
2. Tolerance on all All dimensions from
piping dimensions rear corner of unit
is ±1/2" (13mm). A A including panels
FRONT VIEW
SECTION A-A X O
Y
8"
(203mm) 35"
BLOWER (889mm)
OUTLET
ECS
3-1/2"
(89mm) HUM LV1
LV2
CD LV3
E1 E2 ECR B
4-1/2" DPN003530
86" (2184mm) (114mm)
Rev. 0
FRONT
Table 22 Piping data—Downflow, water/glycol/GLYCOOL, 28-42kW, all compressors
Connection Size / Opening
in. (mm)
X Y
Point Description in. (mm) in. (mm) 28-35kW (8-10 tons) / 42kW (12 tons)
W Water/Glycol/GLYCOOL Access 79-15/16 (2030) 9-1/16 (230) 3-1/2 x 8 (89 x 203)
WS Water/Glycol/GLYCOOL Supply 82-15/16 (2107) 10-15/16 (278) 1-5/8 / 2-1/8 Cu Sweat
WR Water/Glycol/GLYCOOL Return 82-15/16 (2107) 14-1/16 (357) 1-5/8 / 2-1/8 Cu Sweat
2
ECS Econ-O-Coil Supply 54-7/8 (1394) 22-9/16 (573) 1-5/8 / 2-1/8 Cu Sweat
2
ECR Econ-O-Coil Return 49-13/16 (1265) 28-1/2 (724) 1-5/8 / 2-1/8 Cu Sweat
1
Condensate Drain 46 (1168) 29-1/2 (749) 3/4 FPT
(Infrared Humidifier Or No Humidifier)
CD Condensate Drain 1
46 (1168) 29-1/2 (749) 1-1/4 FPT
(Steam Generating Humidifier)
W/ Optional Pump 46 (1168) 29-1/2 (749) 1/2 Cu Sweat
HUM Humidifier Supply Line 53-1/2 (1359) 29 (737) 1/4 Cu Sweat
HS Hot Water Reheat Supply Consult Factory
HR Hot Water Reheat Return Consult Factory
E1 Electrical Connection (High-Voltage) 55-1/2 (1410) 31-1/4 (794) 2-1/2
E2 Electrical Connection (High-Voltage) 52-7/16 (1332) 31-1/4 (794) 2-1/2
LV1 Electrical Connection (Low-Voltage) 2-1/4 (57) 27 (686) 7/8
LV2 Electrical Connection (Low-Voltage) 2-1/4 (57) 29 (737) 7/8
LV3 Electrical Connection (Low-Voltage) 2-1/4 (57) 31 (787) 7/8
B Blower Outlet 4-1/2 (114) 33 (838) 31 x 31 (787 x 787)
1. Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on dual cool systems only (four-pipe systems).
3. Source: DPN003530, Rev. 0
39 Liebert® DS™
Weights and Dimensions
76"
(1930mm)
34"
Shaded area indicates a
(864mm)
recommended minimum
2" 108" (2743mm) clearance from floor to top
of unit and plenum DPN003142
(51mm) Rev. 2
FRONT VIEW for component access.
Liebert® DS™ 40
Weights and Dimensions
3-1/2"
(89mm)
W Y
8" WS
(203mm) WR 35"
(889mm)
41 Liebert® DS™
Weights and Dimensions
5"
(127mm)
76"
(1930mm)
34" (864mm)
Liebert® DS™ 42
Weights and Dimensions
NOTES
Drawing not to scale. All dimensions from
Tolerance on
A A Rear corner of unit
all piping dimensions FRONT VIEW Including panels
is ± 1/2" (13mm). X
SECTION A-A O
W
8" WS
(203mm) WR Y
35"
3-1/2" BLOWER (889mm)
(89mm) OUTLET
ECS ECR
CD LV1
B1 LV2
LV3
E1 E2 HUM
132" (3353mm)
FRONT OF UNIT DPN002153
Rev. 1
Table 24 Piping data—Downflow, water/glycol/GLYCOOL 105kW (30 tons), EC fans, semi-hermetic or
standard scroll compressors 3
X Y Connection Size / Opening
Point Description in. (mm) in. (mm) in. (mm)
W Water/Glycol/GLYCOOL Access 125-15/16 (3199) 9 (229) 3-1/2 x 8 (89x203)
WS Water/Glycol/GLYCOOL Supply 127-7/8 (3248) 10-1/16 (256) 2-1/8 Cu Sweat
WR Water/Glycol/GLYCOOL Return 127-7/8 (3248) 13-1/4 (337) 2-1/8 Cu Sweat
Condensate Drain
87-3/8 (2220) 31 (787) 3/4 FPT
CD (Infrared Humidifier or No Humidifier) 1
W/ Optional Pump 83-13/16 (2129) 30 (762) 1/2 Cu Sweat
HUM Humidifier Supply Line 85-5/16 (2167) 32-1/2 (825) 1/4 Cu Sweat
ECS 2 Econ-O-Coil Supply 101-7/8 (2588) 29 (737) 2-5/8 Cu Sweat
ECR 2 Econ-O-Coil Return 94-9/16 (2402) 29 (737) 2-5/8 Cu Sweat
E1 Electrical Connection (High-Voltage) 98-1/8 (2492) 31 (788) 2-1/2
E2 Electrical Connection (High-Voltage) 91 (2311) 31 (788) 2-1/2
LV1 Electrical Connection (Low-Voltage) 2 (51) 29 (737) 7/8
LV2 Electrical Connection (Low-Voltage) 2 (51) 30-7/8 (784) 7/8
LV3 Electrical Connection (Low-Voltage) 2 (51) 32 (813) 7/8
B1 Blower Outlet 4-1/2 (114) 33 (838) 77-3/8 x 30 (1965x762)
1. Field-pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on dual-cool systems only (four-pipe system)
3. Digital scroll compressors not available on 105 models
4. Piping dimensions shown are connection sizes; field piping sizes may be different, depending on distance. Refer to user manual,
SL-18825.
5. Source: DPN002153, Rev. 1
43 Liebert® DS™
Weights and Dimensions
5/16"
Secondary Entrance (8mm) Bezels
High-Voltage Connection(s) Secondary Entrance
TOP VIEW
Low-Voltage Connections
A
Shaded area indicates a
recommended minimum
clearance from floor to top 34"
of unit and plenum (864mm)
for component access.
76"
(1930mm)
33-1/2"
(851mm)
19"
(483mm) Air Outlet
Opening
3"
3-1/4" 33-3/8"
2" (76mm)
(81mm) 19" (848mm)
(51mm) 3"
B (483mm) Air Outlet
(77mm) Opening
FRONT VIEW
3-1/4"
Filters are accessible only through top of unit. (81mm)
Customer Piping and Wiring Connections
1. For primary connection locations see standard submittals.
A floor stand at least 9" high is recommended if primary
connections locations are to be used.
DPN003180
2. Contact the factory to relocate connection locations. Rev. 1
Liebert® DS™ 44
Weights and Dimensions
Figure 25 Cabinet and floor planning dimensions—Downflow, 53-77kW (15-22 tons), front and/or rear
discharge models with EC fans
Secondary Refrigerant Required for Condenser
Piping Entrance 24" (610mm) cleanout on Water/Glycol or
80" (2032mm) GLYCOOL/Dual Cool.
Opening
Minimum required
for filter replacement.
35" AIR INLET OPENING 25-5/8" 5"
(889mm) (619mm) (127mm)
1-34" Opening
33"
(44mm) Handle
(838mm)
5/16"
Secondary Entrance TOP VIEW (619mm) Bezel
High-Voltage Connection(s) Secondary Entrance
Low-Voltage Connections
A Shaded area indicates
a recommended minimum
34"
clearance from floor to top
(864mm)
of unit and plenum for
component access.
76"
(1930mm)
15-1/8" 15-1/8"
(384mm) (384mm)
29-1/4" 29-5/8"
(743mm) (752mm) 3-1/8"
Air Outlet Air Outlet 15-1/8" 15-1/8"
Opening Opening (79mm) (384mm) (384mm)
29-5/8" 29-1/4"
2" FRONT VIEW 3-1/4" (752mm) (743mm)
Air Outlet Air Outlet
(83mm)
(51mm) B
Opening Opening
45 Liebert® DS™
Weights and Dimensions
Figure 26 Cabinet and floor planning dimensions—Downflow, air-cooled, 105kW (30 tons), front
discharge models with EC fans
Secondary Refrigerant
Piping Entrance
102-7/8" (2611mm)
Opening
33" 24-3/8"
(838mm) AIR INLET OPENING
(619mm)
35" Opening
(889mm)
5/16"
1-34" (619mm)
Secondary Entrance (44mm) TOP VIEW Secondary Entrance Bezel
High-Voltage Connection(s) Handle Low-Voltage Connections
5"
76" (127mm)
(1930mm)
30-7/8" 3/4"
(783mm) (19mm)
57-1/2"
(1459mm) 34"
131" (3326mm) Shaded area indicates a (864mm)
FRONT VIEW recommended minimum
clearance from floor to top of unit
Filters are accessible through top of unit only. and plenum for component access.
Downflow electrical connections can be made
from top or bottom of unit.
Customer Piping and Wiring Connections
1. For primary connection locations see standard submittals. DPN003182
A floor stand at least 9" high is recommended if primary Rev. 1
connections locations are to be used.
2. Contact the factory to relocate connection locations.
Liebert® DS™ 46
Weights and Dimensions
39"
(991mm)
76"
(1930mm)
Blower & Coil Assembled
Compressor Assembly Assembly Height
76"
59-7/16"
(1930mm)
(1509mm)
37"
(940mm)
47 Liebert® DS™
Weights and Dimensions
39"
(991mm)
76"
Compressor Assembly Blower & Coil (1930mm)
Assembly Assembled
Height
76" 59-7/16"
(1930mm) (1509mm)
37"
(940mm)
Drawing views are simplified with panels removed to show overall dimensions. DPN003132
See disassembly and handling instructions in installation manual. Rev. 1
Liebert® DS™ 48
Weights and Dimensions
Figure 29 Disassembly dimensions—Downflow, air-cooled, 53-77kW (15-22 tons), scroll or digital scroll 1
compressors
39"
(991mm)
76"
(1930mm)
59-7/16"
(1509mm)
37"
(940mm)
DS053-DS077 =
33" 15" (381mm) 82" (2083mm)
(838mm) Assembled Length
DS053-DS077 = 97" (2464mm) DPN003140
Drawing views are simplified with panels removed to show over all dimensions. Rev. 1
See disassembly and handling instructions in installation manual.
49 Liebert® DS™
Weights and Dimensions
39"
(991mm)
76"
(1930mm)
59-3/8"
(1507mm)
37"
(940mm)
Liebert® DS™ 50
Weights and Dimensions
39"
(991mm)
41-11/16"
(1059mm)
Compressor Assembly
76"
(1930mm)
Blower & Coil Assembled Height
Assembly
76"
(1930mm)
59-7/16"
(1510mm)
37"
(940mm)
51 Liebert® DS™
Weights and Dimensions
39"
(991mm)
41-11/16"
(1059mm)
Compressor
76"
Assembly
(1930mm)
Assembled
Blower and Coil Assembly Height
76"
(1930mm)
59 7/16"
(1510mm)
37"
(940mm)
Liebert® DS™ 52
Weights and Dimensions
39"
(991mm)
76"
(1930mm) 59-7/16"
(1509mm)
37"
(940mm)
53 Liebert® DS™
Weights and Dimensions
39"
(991mm)
76"
Compressor Assembly (1930mm)
Assembled
Blower & Coil Height
Assembly
76"
(1930mm)
59-7/16"
(1509mm)
37"
(940mm)
Liebert® DS™ 54
Weights and Dimensions
39"
(991mm)
41-11/16"
(1059mm)
Compressor Assembly
76" (1930mm)
Blower & Coil Assembled
Assembly Height
76"
(1930mm)
59-7/16"
(1510mm)
37"
(940mm)
55 Liebert® DS™
Weights and Dimensions
33"
(838mm)
34-3/4"
(883mm) 5/16"
(8mm)
Bezel Space required for EC fan
plenum (shipped separately)
dependent on height of plenum
High-Voltage ordered.
1-3/4"
Connection(s)
(44mm) TOP VIEW
Low-Voltage
Handle Connection(s)
3-1/24"
73-1/16" 1856mm)
(90mm)
75"
(1924mm)
36"
(914mm)
Shaded area indicates a
required minimum clearance from floor
to top of unit and plenum for component
access.
72" (1829mm)
1-3/4"
(44mm) FRONT VIEW
Notes:
1. Front air return unit shown. For rear return unit, in addition to front service
area shown, also include 25" (635mm) on one side of unit for access to rear
return filter box. See DPN001196.
2. EC fan plenum is not shown. EC fans and plenum are shipped separately. DPN003495
See DPN002747 for unit dimensions with EC fans plenum mounted Rev. 0
Liebert® DS™ 56
Weights and Dimensions
Figure 37 Primary connection locations—Upflow, air-cooled, 28-42kW (8-12 tons), scroll or digital scroll
compressors with EC fans
All dimensions from
rear corner of unit
10-1/8"
including panels X O
(257mm)
ECR
NOTES 4-1/8" (105mm) 3. R1 ECS
1. Drawing not to scale. HUM
2. Tolerance on all piping dimensions CPD
is ± 1/2" (13mm). R2 4.
4" L1 L2 G1 G2
3. Field-routed alternatives for refrigerant
gas and liquid line connection points. (102mm) Y
35"
4. See submittal page DPN002747 (889mm) 11-13/16"
for plenum dimensional data. 3. (300mm)
LV1
E1 E2 LV2 LV3
73" (1854mm)
TOP VIEW OF UNIT Front of Unit
6"
(152mm) R3
17-3/16" 3. 17-1/16" L1 L2 G1 G2
(437mm) (434mm)
CGD*
57 Liebert® DS™
Weights and Dimensions
Figure 38 Cabinet and floor planning dimensions—Upflow, air-cooled, 28-42kW (8-12 tons),
semi-hermetic compressor models with EC fans
Alternate refrigerant
piping entrance
33"
(838mm) Space required for EC fan
34-3/4" 5/16" plenum (shipped separately)
(883mm) (8mm) dependent on height of plenum
Bezel ordered.
76"
(1930mm)
36"
Shaded area indicates a (914mm)
required minimum clearance
from floor to top of unit and
plenum for component access.
Liebert® DS™ 58
Weights and Dimensions
6"
(152mm) R3
G1 G2
20-1/16" L1 L2
17-3/16" 3.
(509mm)
(437mm)
CGD*
14-1/4" CGD*
3-7/8"
(362mm) Factory Location
(98mm)
15-7/8" FRONT SECTION VIEW OF UNIT DPN002739
(403mm) (Left Front Panel Not Shown) Rev. 0
LEFT SIDE SECTION VIEW OF UNIT
Table 26 Piping data—Upflow, air-cooled, 28-42kW, EC fans, semi-hermetic compressor models
X Y Connection Size / Opening
Point Description in. (mm) in. (mm) in. (mm)
R1 3 Refrigerant Access (Top) 60-11/16 (1542) 1-7/8 (48) 22-1/2 x 15-3/16 (572 x 386)
R2 3 Refrigerant Access (Bottom) 63 (1600) 13-13/16 (351) 16-7/16 x 4 (102 x 418)
L1 Liquid Line System 1 79-3/16 (2011) 16-3/4 (425) 1/2 Cu Sweat
L2 Liquid Line System 2 76-1/2 (1943) 16-3/4 (425) 1/2 Cu Sweat
G1 Hot Gas Discharge 1 73-7/8 (1876) 16-3/4 (425) 5/8 Cu Sweat
G2 Hot Gas Discharge 2 70-1/8 (1780) 16-3/4 (425) 5/8 Cu Sweat
R3 3 Refrigerant Access (Side) — — 6 x 17-3/16 (152 x 437)
CGD 1 Condensate Gravity Drain — — 3/4 FPT
CPD Condensate Pump Discharge (Opt) 56-1/4 (1429) 11-1/8 (283) 1/2 Cu Sweat
HUM Humidifier Supply Line 56-1/4 (1429) 9-1/8 (233) 1/4 Cu Sweat
ECS 2 Econ-O-coil Supply 56 (1423) 7-5/16 (186) 1-5/8 Cu Sweat
ECR** Econ-O-coil Return 56 (1423) 4-1/2 (114) 1-5/8 Cu Sweat
E1 Electrical Connection (High-Voltage) 52-3/8 (1331) 29-15/16 (760) 2-1/2
E2 Electrical Connection (High-Voltage) 47-3/8 (1204) 29-15/16 (760) 2-1/2
LV1 Electrical Connection (Low-Voltage) 8-1/8 (207) 29-9/16 (751) 7/8
LV2 Electrical Connection (Low-Voltage) 8-1/8 (207) 31 (787) 7/8
LV3 Electrical Conn. (Low Volt) 8-1/8 (207) 32-7/16 (824) 7/8
1. Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on dual cool systems only.
3. Source: DPN002739, Rev. 0
59 Liebert® DS™
Weights and Dimensions
Figure 40 Cabinet and floor planning dimensions—Upflow, air-cooled, 53-77kW (15-22 tons), scroll or
digital scroll compressor models with EC fans
High-Voltage 1-3/4"
Connection(s) (44mm) TOP VIEW
Low-Voltage
Handle
Connection(s)
3-1/4"
(83mm) 98" (2489mm)
76"
(1930mm)
36"
(914mm)
Shaded area indicates a
required minimum clearance
from floor to top of unit and
2" 96-15/16" (2462mm) plenum for component access.
(50mm) FRONT VIEW
Notes:
1. Front air return unit shown. For rear return unit, in addition to front service
area shown, also include 25" (635mm) on one side of unit for access to rear
return filter box. See DPN001196.
DPN003498
2. EC fan plenum is not shown. EC fans and plenum are shipped separately.
Rev. 0
See DPN002748 for unit dimensions with EC fans plenum mounted
Liebert® DS™ 60
Weights and Dimensions
Figure 41 Primary connection locations—Upflow, air cooled, 53-77kW (15-22 tons) with EC fans, scroll or
digital scroll compressor models with EC fans
All dimensions from
Digital scroll compressors 12" rear corner of unit
not available on 105 models. X O
(305mm) including panels
NOTES ECR
4" (102mm) 3. R1 ECS
1. Drawing not to scale. HUM
2. Tolerance on all piping CPD
R2
dimensions is ±1/2" (13mm). 4" L1 L2G1G2 4
35" (102mm)
3. Field-routed alternatives for (889mm)
refrigerant gas and liquid
LV1
Y
3.
line connections. 12-13/16" E1 LV2
4. See submittal page DPN002748 for (325mm) E2 LV3
plenums dimensions.
98" (2489mm)
TOP VIEW OF UNIT Front of Unit
6" (152mm)
R3
* Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed
condensate trap. Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system
materials. The drain line must comply with all local codes.
** Supplied on dual cool systems only
Table 27 Piping data—Upflow, air cooled with EC fans, 53-77kWw (15-22 tons) scroll compressor models
X Y Connection Size / Opening
Point Description in. (mm) in. (mm) in. (mm)
R1 3 Refrigerant Access (Top) 83-5/8 (2124) 2 (51) 12 x 4 (305 x 102)
R2 3 Refrigerant Access (Bottom) 82-3/4 (2102) 14-3/4 (374) 12-3/16 x 4 (310 x 102)
53kW (15 Tons) / 70 and 77kW (20 and 22 Tons)
L1 Liquid Line System 1 94-11/16 (2405) 16-3/4 (425) 1/2 / 5/8 Cu Sweat
L2 Liquid Line System 2 91-7/8 (2334) 16-3/4 (425) 1/2 / 5/8 Cu Sweat
G1 Hot Gas Discharge 1 88-3/4 (2254) 16-3/8 (416) 7/8 / 1-1/8 Cu Sweat
G2 Hot Gas Discharge 2 85-9/16 (2173) 16-3/8 (416) 7/8 / 1-1/8 Cu Sweat
R3 3 Refrigerant Access (Side) — — 6 x 17-3/16 (152 x 437)
CGD 1 Condensate Gravity Drain — — 3/4 FPT
CPD Condensate Pump Discharge (Optional) 79-5/16 (2015) 11-7/8 (302) 1/2 Cu Sweat
HUM Humidifier Supply Line 79-5-16 (2015) 9-7/8 (251) 1/4 Cu Sweat
ECS 1 Econ-O-Coil Supply 78-5/8 (1998) 7-7/8 (200) 2-1/8 Cu Sweat
ECR 1 Econ-O-Coil Return 78-5/8 (1998) 4-5/8 (117) 2-1/8 Cu Sweat
E1 Electrical Connection (High-Voltage) 78-1/8 (1984) 30 (762) 2-1/2
E2 Electrical Connection (High-Voltage) 74-3/8 (1889) 30 (762) 2-1/2
LV1 Electrical Connection (Low-Voltage) 2-5/8 (66) 28-9/16 (726) 7/8
LV2 Electrical Connection (Low-Voltage) 2-5/8 (66) 30 (762) 7/8
LV3 Electrical Connection (Low-Voltage) 2-5/8 (66) 31-7/16 (799) 7/8
1. Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on dual cooling systems only
3. Source: DPN002743, Rev. 0
61 Liebert® DS™
Weights and Dimensions
Figure 42 Cabinet and floor planning dimensions—Upflow, air-cooled 53-77kW (15-22 tons),
semi-hermetic compressor models with EC fans
Alternate Refrigerant
Piping Entrance
33"
(838mm)
34-3/4"
(883mm) 5/16"
(8mm)
Bezel
High-Voltage 1-3/4" TOP VIEW
Connection(s) (44mm) Low-Voltage Space required for EC fan
Handle Connection(s) plenum (shipped separately)
dependent on height of plenum
3-1/4" ordered.
(83mm) 109" (2769mm)
76"
(1930mm)
36"
(914mm)
108" (2743mm)
2"
Shaded area indicates a
(50mm) FRONT VIEW required minimum clearance from floor
Notes: to top of unit and plenum for component
1. Front air return unit shown. For rear return unit, in addition to front service access.
area shown, also include 25" (635mm) on one side of unit for access to rear
return filter box. See DPN001196.
2. EC fan plenum is not shown. EC fans and plenum are shipped separately. DPN003497
See DPN002748 for unit dimensions with EC fans plenum mounted Rev. 0
Liebert® DS™ 62
Weights and Dimensions
109" 2760mm)
6" Front of Unit
(152mm)
TOP VIEW OF UNIT
R3
17-3/16" 3.
(437mm) G1 G2
CGD* 20-1/16" LV1 LV2
(509mm)
3-7/8" 14-1/4"
(98mm) (362mm)
15-7/8" CGD*
(403mm) FACTORYLOCATION
DPN002742
LEFT SIDE SECTION VIEW OF UNIT FRONT SECTION VIEW OF UNIT
(Left Front Panel Not Shown) Rev. 0
63 Liebert® DS™
Weights and Dimensions
Figure 44 Cabinet and floor planning dimensions—Upflow, air-cooled, 105kW (30 tons), all compressor
models with EC fans
Alternate Refrigerant Digital scroll compressors
Piping Entrance not available on 105 models.
33"
(838mm) Space required for EC fan plenum
34-3/4" (shipped separately) dependent on
(882mm) height of plenum ordered.
High-Voltage
Connection(s) 1-3/4" TOP VIEW 5/16"
(44mm) (8mm)
3-3/16" Low-Voltage
Handle Bezel
(81mm) Connection(s)
Typical
132-1/16" (3354mm)
76"
(1931mm)
2"
(51mm) 36"
Shaded area indicates a (914mm)
recommended minimum
130-15/16" (3325mm) clearance from floor to
ceiling for component access.
FRONT VIEW
Note:
1. Front air return unit shown. For rear return unit, in addition to front
service area shown, also include 25" (635mm) on one side of unit
for access to rear return filter box. See DPN001196.
2. EC fans plenum is not shown. EC fans and plenum are shipped
separately. See DPN002749 for unit dimensions with EC fans DPN003500
plenum mounted Rev. 0
Liebert® DS™ 64
Weights and Dimensions
Figure 45 Primary connection locations—Upflow, air-cooled 105kW (30 tons), all compressor models
with EC fans
6" (152mm)
R3
G1G2
17-3/16" 20-1/16" L1L2
3. (509mm)
(437mm)
CGD*
65 Liebert® DS™
Weights and Dimensions
33"
(838mm)
34-3/4" Space required for EC fan
(883mm) 5/16" plenum (shipped separately)
(8mm) dependent on height of plenum
Bezel ordered.
Required for
24" Condenser Cleanout
Alternate Condenser Fluid 1-3/4" TOP VIEW (610mm)
Piping Entrance (44mm) Low-Voltage
High-Voltage Handle Connection(s)
Connection(s)
3-1/4" 86-1/16" (2186mm)
(83mm)
76"
(1930mm)
36"
(914mm)
Liebert® DS™ 66
Weights and Dimensions
3-7/8" 14-1/4"
(98mm) (362mm)
15-7/8"
(403mm)
CGD* FRONT SECTION VIEW OF UNIT DPN002741
LEFT SIDE SECTION VIEW OF UNIT (Left Front Panel Not Shown) Rev. 1
Table 30 Piping data—Upflow, water/glycol/GLYCOOL, 28-42kW, EC fans, all compressor models
Connection Size / Opening
in. (mm)
X Y 28-35kW (8-10 Tons) /
Point Description in. (mm) in. (mm) 42kW (12 Tons)
W1 Water/Glycol/GLYCOOL Access (Bottom) 79-15/16 (2030) 9 (229) 3-1/2 x 8 (89 x 203)
W2 3 Water/Glycol/GLYCOOL Access (Top) 79-15/16 (2030) 9 (229) 3-1/2 x 8 (89 x 203)
W3 3 Water/Glycol/GLYCOOL Access (Side) — — 6 x 17-3/16 (152 x 437)
WS 3 Water/Glycol/GLYCOOL Supply — — 1-5/8 / 2-1/8 Cu Sweat
WR 3 Water/Glycol/GLYCOOL Return — — 1-5/8 / 2-1/8 Cu Sweat
2
ECS Econ-O-Coil Supply 56 (1423) 7-5/16 (186) 1-5/8 / 2-1/8 Cu Sweat
ECR 2 Econ-O-Coil Return 56 (1423) 4-1/2 (114) 1-5/8 / 2-1/8 Cu Sweat
CGD 1 Condensate Gravity Drain — — 3/4 FPT
CPD Condensate Pump Discharge (Optional) 56-1/4 (1429) 11-1/8 (282) 1/2 Cu Sweat
HUM Humidifier Supply Line 56-1/4 (1429) 9-1/8 (232) 1/4 Cu Sweat
E1 Electrical Connection (High-Voltage) 52-3/8 (1331) 29-15/16 (760) 2-1/2
E2 Electrical Connection (High-Voltage) 47-3/8 (1204) 29-15/16 (760) 2-1/2
LV1 Electrical Connection (Low-Voltage) 8-1/8 (207) 29-9/16 (751) 7/8
LV2 Electrical Connection (Low-Voltage) 8-1/8 (207) 31 (787) 7/8
LV3 Electrical Connection (Low-Voltage) 8-1/8 (207) 32-7/16 (824) 7/8
1. Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on dual cool systems only (four-pipe system).
3. Source: DPN002741, Rev. 1
67 Liebert® DS™
Weights and Dimensions
76"
(1930mm)
36"
Shaded area indicates a (914mm)
recommended minimum
clearance from floor to top
of unit for component access.
Liebert® DS™ 68
Weights and Dimensions
ECR
ECS
W1, W2 HUM
8" CPD
NOTES (203mm) 3.
35" 4.
1. Drawing not to scale.
2. Tolerance on all piping (889mm) 2-7/8"
dimensions
Y
(73mm)
is ±1/2" (13mm). E1 E2 LV1
3-1/2" LV2
3. Field-routed alternatives for (89mm) LV3
water/glycol connections.
4. See submittal page DPN002748 109" (2769mm)
TOP VIEW OF UNIT Front of Unit
for plenum dimensions.
6" (152mm)
W3
WS
17-3/16" WR
(437mm) 3. CGD*
69 Liebert® DS™
Weights and Dimensions
Figure 50 Cabinet and floor planning dimensions—Upflow, water/glycol/GLYCOOL™,105kW (30 tons), all
compressor models, with EC fans
76"
(1931mm)
34"
(864mm)
Liebert® DS™ 70
Weights and Dimensions
W3
17-3/16" WS
WR
(437mm) 3.
CGD*
3-7/8" 14-1/4"
CGD* FRONT SECTION VIEW OF UNIT DPN002746
(98mm) (362mm)
15-7/8" (Left Front Panel Not Shown) Rev. 0
(403mm)
71 Liebert® DS™
Weights and Dimensions
Alternate Refrigerant
Piping Entrance
33"
(838mm) 5/16"
35" (8mm)
(889mm) Bezel
Minimum required
for blower replacement
1-3/4"
High-Voltage (44mm) TOP Low-Voltage
Connection(s) Handle VIEW Connection(s)
1-1/2" 73" (1854mm) 24"
(38mm) (610mm)
76"
(1930mm)
34"
(864mm)
72" (1829mm)
2"
(51mm) FRONT VIEW
Front air return unit shown. For rear return unit, in addition to front service
area shown, also include 25" (635mm) on one side of unit for access to rear DPN003154
return filter box. See DPN001196. Rev. 1
Liebert® DS™ 72
Weights and Dimensions
Figure 53 Primary connection locations—Upflow air-cooled 28-42kW (8-12 tons) scroll compressor
models with foward-curved blowers
All dimensions from rear corner
10-1/8"
of unit including panels X O
(257mm)
73" (1854mm)
6" TOP VIEW Front
(152mm) R3
17-3/16" 3.
(437mm) 17-1/16" L1 L2 G1 G2
CGD* (434mm)
3-7/8" 14-1/4"
(98mm) (362mm)
15-7/8" CGD* Factory Location
(403mm)
FRONT SECTION DPN001119
LEFT SIDE SECTION (Left Front Panel Not Shown) Rev. 3
Table 33 Piping data—Upflow, air-cooled 28-42kW (8-12 tons) scroll compressors
X Y Connection Size / Opening
Point Description in. (mm) in. (mm) in. (mm)
R1 3 Refrigerant Access (Top) 60-5/8 (1539) 2-13/16 (71) 10-1/8 x 4-1/8 (257 105)
R2 3 Refrigerant Access (Bottom) 63 (1600) 13-13/16 (351) 16-7/16 x 4 (418 x 102)
L1 Liquid Line System 1 79-3/16 (2011) 16-3/4 (425) 1/2" Cu Sweat
L2 Liquid Line System 2 76-1/2 (1943) 16-3/4 (425) 1/2" Cu Sweat
G1 Hot Gas Discharge 1 73-7/8 (1876) 16-5/8 (422) 5/8" Cu Sweat
G2 Hot Gas Discharge 2 70-1/8 (1780) 16-5/8 (422) 5/8" Cu Sweat
R3 3 Refrigerant Access (Side) — — 6 x 17-3/16 (152 x 437)
CGD* Condensate Gravity Drain — — 3/4" FPT
CPD Condensate Pump Discharge (Optional) 56-1/4 (1429) 11-1/8 (283) 1/2" Cu Sweat
HUM Humidifier Supply Line 56-1/4 (1429) 9-1/8 (233) 1/4" Cu Sweat
2
ECS * Econ-O-Coil Supply 56 (1423) 7-5/16 (186) 1-5/8" Cu Sweat
ECR 2* Econ-O-Coil Return 56 (1423) 4-1/2 (114) 1-5/8" Cu Sweat
E1 Electrical Connection (High Voltage) 52-3/8 (1330) 30 (762) 2-1/2"
E2 Electrical Connection (High Voltage) 46-7/8 (1191) 30 (762) 2-1/2"
LV1 Electrical Connection (Low Voltage) 19-1/2 (495) 29-1/16 (738) 7/8"
LV2 Electrical Connection (Low Voltage) 19-1/2 (495) 30-1/2 (775) 7/8"
LV3 Electrical Connection (Low Voltage) 19-1/2 (495) 31-15/16 (811) 7/8"
1. Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on dual cool systems only.
3. Source: DPN001119, Rev. 3
73 Liebert® DS™
Weights and Dimensions
Figure 54 Cabinet and floor planning dimensions—Upflow, air-cooled 28-42kW (8-12 tons) semi-hermetic
compressor models with forward-curved blowers
Alternate Refrigerant
Piping Entrance
33"
(838mm)
5/16"
35" (8mm)
(889mm) Minimum required
Bezel
for blower replacement
1-3/4"
High-Voltage
TOP (44mm) Low-Voltage
Connection(s)
VIEW Handle Connection(s)
76"
(1930mm)
34"
(864mm)
85" (2159mm)
2" FRONT VIEW
(51mm) DPN003153
Front air return unit shown. For rear return unit, in addition to front service Rev. 1
area shown, also include 25" (635mm) on one side of unit for access to rear
return filter box. See DPN001196.
Liebert® DS™ 74
Weights and Dimensions
86" (2184mm)
TOP VIEW Front of Unit
6"
(152mm)
R3
17-3/16" 3 G1 G2
(437mm) 20-1/16" L1 L2
(509mm)
CGD *
14-1/4"
3-7/8" (362mm)
(98mm) CGD *
15-7/8" Factory Location
DPN001114
(403mm) FRONT SECTION VIEW Rev. 3
LEFT SIDE SECTION VIEW (Left Front Panel Not Shown)
Table 34 Piping data—Upflow, air-cooled, 28-42kW (8-12 tons), semi-hermetic compressors
X Y Connection Size / Opening
Point Description in. (mm) in. (mm) in. (mm)
R1 3 Refrigerant Access (Top) 60-11/16 (1542) 1-7/8 (48) 22-1/2 x 15-3/16 (572 x 386)
R2 3 Refrigerant Access (Bottom) 63 (1600) 13-13/16 (351) 16-7/16 x 4 (418 x 102)
L1 Liquid Line System 1 79-3/16 (2011) 16-3/4 (425) 1/2" Cu Sweat
L2 Liquid Line System 2 76-1/2 (1943) 16-3/4 (425) 1/2" Cu Sweat
G1 Hot Gas Discharge 1 73-7/8 (1876) 16-3/4 (425) 5/8" Cu Sweat
G2 Hot Gas Discharge 2 70-1/8 (1780) 16-3/4 (425) 5/8" Cu Sweat
R3 3 Refrigerant Access (Side) — — 6 x 17-3/16 (152 x 437)
CGD 1 Condensate Gravity Drain — — 3/4" FPT
CPD Condensate Pump Discharge (Opt) 56-1/4 (1429) 11-1/8 (283) 1/2" Cu Sweat
HUM Humidifier Supply Line 56-1/4 (1429) 9-1/8 (233) 1/4" Cu Sweat
ECS 2 Econ-O-Coil Supply 56 (1423) 7-5/16 (186) 1-5/8" Cu Sweat
ECR 2 Econ-O-Coil Return 56 (1423) 4-1/2 (114) 1-5/8" Cu Sweat
E1 Electrical Conn. (High-Voltage) 52-3/8 (1330) 30 (762mm) 2-1/2"
E2 Electrical Conn. (High-Voltage) 46-7/8 (1191) 30 (762mm) 2-1/2"
LV1 Electrical Conn. (Low-Voltage) 19-1/2 (495) 29-1/16 (738) 7/8"
LV2 Electrical Conn. (Low-Voltage) 19-1/2 (495) 30-1/2 (775) 7/8"
LV3 Electrical Conn. (Low-Voltage) 19-1/2 (495) 31-15/16 (811) 7/8"
1. Field-pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on Dual-Cool systems only (four-pipe system).
3. Piping dimensions shown are connection sizes; field piping sizes may be different, depending on distance. Refer to user manual,
SL-18825.
4. Source: DPN001114, Rev. 3
75 Liebert® DS™
Weights and Dimensions
Figure 56 Cabinet and floor planning dimensions—Upflow, air-cooled, 53-77kW (15-22 tons), scroll or
digital scroll compressors with forward-curved blowers
Alternate Refrigerant
Piping Entrance
Digital scroll compressors
not available on 077 models.
33"
(838mm) 5/16"
35" (8mm)
(889mm) Bezel Minimum required
for blower replacement
1-3/4"
High-Voltage (44mm) Low-Voltage
Connection(s) Handle Connection(s)
TOP VIEW
1-1/2" 98" (2489mm)
(38mm) 24"
(610mm)
76"
(1930mm)
34"
(864mm)
Liebert® DS™ 76
Weights and Dimensions
Figure 57 Primary connection locations—Upflow, air-cooled, 53-77kW (15-22 tons), scroll compressor
models with forward-curved blowers
Digital scroll compressors not
available on VS 077. All dimensions from
NOTES: rear corner of unit
12" (305mm)
1. Drawing not to scale. including panels
2. Tolerance on all piping dimensions
is ± 1/2" (13mm). Blower Blower
4" Outlet Outlet
3. Field-routed alternatives for refrigerant (102mm)
gas and liquid line connection points.
35" 4"
4. Forward-curved blowers shown. See (102mm)
submittal page DPN001191 for (889mm)
blower outlet and deck dimensions.
12-13/16"
(325mm)
6" (152mm) 98" (2489mm)
Front of Unit
TOP VIEW OF UNIT
17-3/16"
(437mm)
CGD *
Table 35 Piping data—Upflow, air-cooled, 53-77kw (15-22 tons), scroll compressor models 3
X Y Connection Size / Opening
Point Description in. (mm) in. (mm) in. (mm)
R1 3 Refrigerant Access (Top) 83-5/8 (2124) 2 (51) 12 x 4 (305 x 102)
R2 3 Refrigerant Access (Bottom) 82-3/4 (2102) 14-3/4 (374) 12-3/16 x 4 (310 x 102)
53kW (15 tons) / 70 & 77kW (20 & 22 tons)
L1 Liquid Line System 1 94-11/16 (2405) 16-3/4 (425) 1/2 / 5/8 Cu Sweat
L2 Liquid Line System 2 91-7/8 (2334) 16-3/4 (425) 1/2 / 5/8 Cu Sweat
G1 Hot Gas Discharge 1 88-3/4 (2254) 16-3/8 (416) 7/8 / 1-1/8 Cu Sweat
G2 Hot Gas Discharge 2 85-9/16 (2173) 16-3/8 (416) 7/8 / 1-1/8 Cu Sweat
R3 3 Refrigerant Access (Side) — — 6 x 17-3/16 (152 x 437)
1
CGD Condensate Gravity Drain — — 3/4 FPT
CPD Condensate Pump Discharge (Opt) 79-5/16 (2015) 11-7/8 (302) 1/2 Cu Sweat
HUM Humidifier Supply Line 79-5-16 (2015) 9-7/8 (251) 1/4 Cu Sweat
2
ECS Econ-O-Coil Supply 78-5/8 (1998) 7-7/8 (200) 2-1/8 Cu Sweat
2
ECR Econ-O-Coil Return 78-5/8 (1998) 4-5/8 (117) 2-1/8 Cu Sweat
E1 Electrical Connection (High-Voltage) 75-3/8 (1915) 30 (762) 2-1/2
E2 Electrical Connection (High-Voltage) 69-7/8 (1775) 30 (762) 2-1/2
LV1 Electrical Connection (Low-Voltage) 19-1/2 (495) 29-1/16 (738) 7/8
LV2 Electrical Connection (Low-Voltage) 19-1/2 (495) 30-1/2 (775) 7/8
LV3 Electrical Connection (Low-Voltage) 19-1/2 (495) 31-15/16 (811) 7/8
1. Field-pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on dual-cool systems only.
3. Digital scroll compressors not available on 077 models.
4. Piping dimensions shown are connection sizes; field piping sizes may be different depending, on distance. Refer to user manual,
SL-18825.
5. Source: DPN001213, Rev. 2
77 Liebert® DS™
Weights and Dimensions
Figure 58 Cabinet and floor plannning dimensions—Upflow air-cooled 53-77kw (15-22 tons)
semi-hermetic compressor models with forward curved blowers
Alternate Refrigerant
Piping Entrance
33"
(838mm) 5/16"
(8mm)
35"
Bezel
(889mm)
Minimum required
High-Voltage 1-3/4" for blower replacement
Connection(s) (44mm) TOP Low-Voltage
Handle VIEW Connection(s)
24"
(610mm)
76"
(1930mm)
34"
(864mm)
Liebert® DS™ 78
Weights and Dimensions
17-3/16"
(437mm)
20-1/16"
14-1/4" (509mm)
3-7/8"
(362mm)
(98mm)
15-7/8"
(403mm) CGD * Factory Location
LEFT SIDE SECTION VIEW OF UNIT FRONT SECTION VIEW OF UNIT DPN001212
(Left Front Panel Not Shown) Rev. 3
Table 36 Piping data—Upflow, air-cooled, 53-77kW (15-22 tons), semi-hermetic compressors
X Y Connection Size / Opening
Point Description in. (mm) in. (mm) in. (mm)
R1 3 Refrigerant Access (Top) 83-3/4 (2127) 1-7/8 (48) 22-1/2 x 15-3/16 (572 x 386)
R2 3 Refrigerant Access (Bottom) 86 (2184) 13-7/8 (352) 16-7/16 x4 (418 x102)
53kW (15 tons) / 70 & 77kW (20 & 22 tons)
L1 Liquid Line System 1 97 (2464) 16-3/4 (425) 1/2" / 5/8 Cu Sweat
L2 Liquid Line System 2 93-5/16 (2370) 16-3/4 (425) 1/2" / 5/8" Cu Sweat
G1 Hot Gas Discharge 1 90-5/8 (2302) 16-5/8 (422) 7/8" / 1-1/8" Cu Sweat
G2 Hot Gas Discharge 2 88 (2235) 16-5/8 (422) 7/8" / 1-1/8" Cu Sweat
R3 3 Refrigerant Access (Side) — — 6 x 17-3/16 (152 x 437)
CGD 1 Condensate Gravity Drain — — 3/4" FPT
CPD Condensate Pump Discharge (Opt) 79-5/16 (2015) 11-7/8 (302) 1/2" Cu Sweat
HUM Humidifier Supply Line 79-5/16 (2015) 9-7/8 (251) 1/4" Cu Sweat
ECS 2 Econ-O-Coil Supply 78-5/8 (1998) 7-7/8 (200) 2-1/8" Cu Sweat
ECR 2 Econ-O-Coil Return 78-5/8 (1998) 4-5/8 (117) 2-1/8" Cu Sweat
E1 Electrical Connection (High-Voltage) 75-3/8 (1915) 30 (762) 2-1/2"
E2 Electrical Connection (High-Voltage) 69-7/8 (1775) 30 (762) 2-1/2"
LV1 Electrical Connection (Low-Voltage) 19-1/2 (495) 29-1/16 (738) 7/8"
LV2 Electrical Connection (Low-Voltage) 19-1/2 (495) 30-1/2 (775) 7/8"
LV3 Electrical Conn. (Low-Voltage) 19-1/2 (495) 31-15/16 (811) 7/8"
1. Field-pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on dual-cool systems only.
3. Piping dimensions shown are connection sizes; field piping sizes may be different, depending on distance. Refer to user manual,
SL-18825.
4. Source: DPN001212, Rev. 3
79 Liebert® DS™
Weights and Dimensions
Figure 60 Cabinet and floor planning dimensions—Upflow, air-cooled, 105kW (30 tons), all compressor
models with forward-curved blowers
Alternate Refrigerant
Piping Entrance
33"
(838mm)
35"
(889mm) 5/16"
(8mm)
1-3/4" Bezel Minimum required
High-Voltage (44mm) Low-Voltage for blower replacement
Connection(s) TOP VIEW Handle Connection(s)
24"
(610mm)
76"
(1930mm)
34"
(864mm)
2" 131" (3327mm)
Shaded area indicates a
(51mm) FRONT VIEW required minimum clearance from floor
to top of unit and plenum for component
Front air return unit shown. For rear return unit, in addition to front service access.
area shown, also include 25" (635mm) on one side of unit for access to rear
DPN003159
return filter box. See DPN001196.
Rev. 1
Liebert® DS™ 80
Weights and Dimensions
Figure 61 Primary connection locations—Upflow, air-cooled, 105kW (30 tons), semi-hermetic and scroll
compressor models with forward-curved blowers
Digital scroll compressors not All dimensions from
available on 105 models. 22-1/2" rear corner of unit
X O
(572mm) including panels
ECR
15-3/16" ECS Blower Blower Blower
R2 HUM Outlet
(386mm) CPD Outlet Outlet
35"
(889mm)
R3
G2
17-3/16" 20-1/16" L1 L2G1
(437mm) (509mm)
CGD*
3-7/8" 14-1/4"
(98mm) CGD*
(362mm)
Factory Location
15-7/8"
(403mm) FRONT SECTION VIEW DPN001257
LEFT SIDE SECTION VIEW (Left Front Panel Not Shown)
Rev. 1
Table 37 Piping data—Upflow, air-cooled 105kW (30 tons), semi-hermetic and scroll compressors 3
Point Description X, in. (mm) Y, in. (mm) Connection Size / Opening
R1 3 Refrigerant Access (Top) 106-7/8 (2715) 1-7/8 (48) 22-1/2 x 15-3/16 (572 x 386)
R2 3 Refrigerant Access (Bottom) 109-1/8 (2772) 13-7/8 (352) 16-7/16 x 4 (418 x 102)
L1 Liquid Line System 1 121-3/4 (3092) 16-3/4 (425) 5/8" Cu Sweat
L2 Liquid Line System 2 118-1/8 (3000) 16-3/4 (425) 5/8" Cu Sweat
G1 Hot Gas Discharge 1 118-1/4 (3004) 14-1/4 (362) 1-1/8" Cu Sweat
G2 Hot Gas Discharge 2 115-5/8 (2937) 14-1/4 (362) 1-1/8" Cu Sweat
R3 3 Refrigerant Access (Side) — — 6 x 17-3/16 (152 x 437)
CGD* Condensate Gravity Drain — — 3/4" FPT
CPD Condensate Pump Discharge (Opt) 102-3/8 (2600) 13-5/8 (346) 1/2" Cu Sweat
HUM Humidifier Supply Line 101-1/8 (2569) 13-1/8 (333) 1/4" Cu Sweat
ECS 2 Econ-O-Coil Supply 101-1/8 (2569) 10-1/4 (260) 2-5/8" Cu Sweat
ECR 2 Econ-O-Coil Return 101-1/8 (2569) 5-1/4 (133) 2-5/8" Cu Sweat
E1 Electrical Connection (High-Voltage) 98-1/2 (2502) 30 (762) 2-1/2"
E2 Electrical Connection (High-Voltage) 93 (2362) 30 (762) 2-1/2"
LV1 Electrical Connection (Low-Voltage) 41-1/8 (1045) 30-3/8 (772) 7/8"
LV2 Electrical Connection (Low-Voltage) 38-7/8 (987) 30-3/8 (772) 7/8"
LV3 Electrical Connection (Low-Voltage) 35-1/8 (892) 30-3/8 (772) 7/8"
LV4 Electrical Connection (Low-Voltage) 31-5/8 (803) 30-3/8 (772) 7/8"
1. Field-pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on dual-cool systems only.
3. Digital scroll compressors not available on VS105
4. Piping dimensions shown are connection sizes; field piping sizes may be different, depending on distance. Refer to user manual,
SL-18825.
5. Source: DPN001257, Rev. 1
81 Liebert® DS™
Weights and Dimensions
33"
(838mm) 5/16"
(8mm)
35" Bezel Required for
(889mm) condenser cleanout
Minimum required
for blower replacement
Alternate Condenser Fluid 1-3/4"
Piping Entra (44mm) Low-Voltage
High-Voltage Handle Connection(s)
Connection(s) TOP VIEW
1-1/2" 86" (2184mm) 24"
(38mm) (610mm)
76"
(1930mm)
34"
(864mm)
85" (2159mm)
2"
(51mm) FRONT VIEW
Front air return unit shown. For rear return unit, in addition to front service DPN003155
area shown, also include 25" (635mm) on one side of unit for access to rear Rev. 1
return filter box. See DPN001196.
Liebert® DS™ 82
Weights and Dimensions
3-7/8"
14-1/4"
(98mm)
(362mm)
DPN001179
15-7/8"
(403mm) Rev. 6
CGD* FRONT SECTION VIEW OF UNIT
LEFT SIDE SECTION VIEW OF UNIT (Left Front Panel Not Shown)
Table 38 Piping data—Water/glycol/GLYCOOL, 28-42kW (8-12 tons), upflow, all compressors
Connection Size / Opening
in. (mm)
X Y 28-35kW (8-10 Ton) /
Point Description in. (mm) in. (mm) 42kW (12 Ton)
W1 3 Water/Glycol/GLYCOOL Access (Bottom) 79-15/16 (2030) 9 (229) 3-1/2 x 8 (89 x 203)
W2 3 Water/Glycol/GLYCOOL Access (Top) 79-15/16 (2030) 9 (229) 3-1/2 x 8 (89 x 203)
W3 3 Water/Glycol/GLYCOOL Access (Side) — — 6 x 17-3/16 (152 x 437)
WS 3 Water/Glycol/GLYCOOL Supply — — 1-5/8" / 2-18" Cu Sweat
WR 3 Water/Glycol/GLYCOOL Return — — 1-5/8" / 2-18" Cu Sweat
ECS 2 Econ-O-Coil Supply 56 (1423) 7-5/16 (186) 1-5/8" / 2-18" Cu Sweat
2
ECR Econ-O-Coil Return 56 (1423) 4-1/2 (114) 1-5/8" / 2-18" Cu Sweat
CGD 1 Condensate Gravity Drain — — 3/4" FPT
CPD Condensate Pump Discharge (Opt) 56-1/4 (1429) 11-1/8 (282) 1/2" Cu Sweat
HUM Humidifier Supply Line 56-1/4 (1429) 9-1/8 (232) 1/4" Cu Sweat
E1 Electrical Connection (High-Voltage) 52-3/8 (1330) 30 (762) 2-1/2"
E2 Electrical Connection (High-Voltage) 46-7/8 (1191) 30 (762) 2-1/2"
LV1 Electrical Connection (Low-Voltage) 19-1/2 (495) 29-1/16 (738) 7/8"
LV2 Electrical Connection (Low-Voltage) 19-1/2 (495) 30-1/2 (775) 7/8"
LV3 Electrical Connection (Low-Voltage) 19-1/2 (495) 31-15/16 (811) 7/8"
1. Field-pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on dual-cool systems only (four-pipe system).
3. Piping dimensions shown are connection sizes; field piping sizes may be different, depending on distance. Refer to user manual,
SL-18825.
4. Source: DPN001179, Rev. 6
83 Liebert® DS™
Weights and Dimensions
Figure 64 Cabinet and floor planning dimensions—Upflow, water/glycol-cooled, 53-77kW (15-22 tons), all
compressor models with forward-curved blowers
33"
(838mm) 5/16"
(8mm) Required for
35" Bezel condenser cleanout
(889mm)
Minimum required
Alternate Condenser Fluid 1-3/4" for blower replacement
(44mm) Low-Voltage
Piping Entra
High-Voltage Handle Connection(s)
Connection(s) TOP VIEW
1-1/2" 109" (2769mm)
(38mm)
24"
(610mm)
76"
(1930mm)
34"
(864mm)
Shaded area indicates a
required minimum clearance from floor
to top of unit and plenum for component
2" 108" (2743mm) access.
(51mm)
FRONT VIEW
Front air return unit shown. For rear return unit, in addition to front service
area shown, also include 25" (635mm) on one side of unit for access to rear DPN003158
return filter box. See DPN001196. Rev. 1
Liebert® DS™ 84
Weights and Dimensions
109" (2769mm)
Front
6"
(152mm)
TOP VIEW
W3
WS
17-3/16" WR
(437mm) 3.
CGD*
3-7/8" 14-1/4"
(98mm) (362mm)
15-7/8"
(403mm)
FRONT SECTION VIEW
CGD*
Left Front Panel Not Shown DPN001214
LEFT SIDE SECTION VIEW
Rev. 2
Table 39 Piping data—Water/glycol/GLYCOOL, 53-77kW (15-22 tons), all compressor models
X Y Connection Size / Opening
Point Description in. (mm) in. (mm) in. (mm)
W1 3 Water/Glycol/GLYCOOL Access (Bottom) 102-15/16 (2615) 9 (229) 3-1/2 x 8 (89 x 203)
W2 3 Water/Glycol/GLYCOOL Access (Top) 102-15/16 (2615) 9 (229) 3-1/2 x 8 (89 x 203)
W3 3 Water/Glycol/GLYCOOL Access (Side) — — 6 x 17-3/16 (152 x 437)
WS 3 Water/Glycol/GLYCOOL Supply — — 2-1/8" Cu Sweat
WR 3 Water/Glycol/GLYCOOL Return — — 2-1/8" Cu Sweat
1
CGD Condensate Gravity Drain — — 3/4" FPT
CPD Condensate Pump Discharge (Opt) 78-5/8 (1998) 11-1/8 (282) 1/2" Cu Sweat
HUM Humidifier Supply Line 78-5/8 (1998) 9-7/8 (251) 1/4" Cu Sweat
ECS 2 Econ-O-Coil Supply 79-5/16 (2015) 7-7/8 (200) 2-1/8" Cu Sweat
2
ECR Econ-O-Coil Return 79-5/16 (2015) 4-5/8 (117) 2-1/8" Cu Sweat
E1 Electrical Connection (High-Voltage) 75-3/8 (1915) 30 (762) 2-1/2"
E2 Electrical Connection (High-Voltage) 69-7/8 (1775) 30 (762) 2-1/2"
LV1 Electrical Connection (Low-Voltage) 19-1/2 (495) 29-1/16 (738) 7/8"
LV2 Electrical Connection (Low-Voltage) 19-1/2 (495) 30-1/2 (775) 7/8"
LV3 Electrical Connection (Low-Voltage) 19-1/2 (495) 31-15/16 (811) 7/8"
1. Field-pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate
trap. Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain
line must comply with all local codes.
2. Supplied on dual-cool systems only.
3. Source: DPN001214, Rev. 2
85 Liebert® DS™
Weights and Dimensions
Figure 66 Cabinet and floor planning dimensions—Upflow, water/glycol-cooled, 105kW (30 tons), all
compressor models with forward-curved blowers
Alternate Refrigerant
Piping Entrance
33"
(838mm)
35"
(889mm) 5/16"
Required for
(8mm)
condenser cleanout
Bezel
Alternate Condenser Fluid 1-3/4" Minimum required
Piping Entrance (44mm) Low-Voltage for blower replacement
High-Voltage TOP VIEW Handle Connection(s)
Connection(s)
132" (3353mm)
1-1/2"
(38mm)
24"
(610mm)
76"
(1930mm)
34"
(864mm)
2" 131" (3327mm) Shaded area indicates a
(51mm)
FRONT VIEW required minimum clearance from floor
to top of unit and plenum for component
access.
Front air return unit shown. For rear return unit, in addition to front service
DPN003160
area shown, also include 25" (635mm) on one side of unit for access to rear
Rev. 1
return filter box. See DPN001196.
Liebert® DS™ 86
Weights and Dimensions
W3
WS
17-3/16" WR
(437mm)
CGD*
3-7/8" CGD*
(98mm) 14-1/4"
(362mm) FRONT SECTION VIEW OF UNIT
15-7/8" (Left Front Panel Not Shown)
(403mm) DPN001258
Rev. 1
LEFT SIDE SECTION VIEW OF UNIT
Table 40 Piping data—Upflow water/glycol/GLYCOOL, 105kW (30 tons), all compressor models
X Y Connection Size / Opening
Point Description in. (mm) in. (mm) in. (mm)
W1 3 Water/Glycol/GLYCOOL Access (Bottom) 126-1/8 (3204) 9 (229) 3-1/2 x 8 (89 x 203)
W2 3 Water/Glycol/GLYCOOL Access (Top) 126-1/8 (3204) 9 (229) 3-1/2 x 8 (89 x 203)
W3 3 Water/Glycol/GLYCOOL Access (Side) — — 6 x 17-3/16 (152 x 437)
WS 3 Water/Glycol/GLYCOOL Supply — — 2-1/8" Cu Sweat
WR 3 Water/Glycol/GLYCOOL Return — — 2-1/8" Cu Sweat
1
CGD Condensate Gravity Drain — — 3/4" FPT
CPD Condensate Pump Discharge (Opt) 102-3/8 (2600) 13-5/8 (346) 1/2" Cu Sweat
HUM Humidifier Supply Line 101-1/8 (2569) 13-1/8 (333) 1/4" Cu Sweat
ECS 2 Econ-O-Coil Supply 101-1/8 (2569) 10-1/4 (260 2-5/8" Cu Sweat
2
ECR Econ-O-Coil Return 101-1/8 (2569) 5-1/4 (133) 2-5/8" Cu Sweat
E1 Electrical Connection (High-Voltage) 98-1/2 (2502) 30 (762) 2-1/2"
E2 Electrical Connection (High-Voltage) 93 (2362) 30 (762) 2-1/2"
LV1 Electrical Connection (Low-Voltage) 41-1/8 (1045) 30-3/8 (772) 7/8"
LV2 Electrical Connection (Low-Voltage) 38-7/8 (987) 30-3/8 (772) 7/8"
LV3 Electrical Connection (Low-Voltage) 35-1/8 (892) 30-3/8 (772) 7/8"
LV4 Electrical Connection (Low-Voltage) 31-5/8 (803) 30-3/8 (772) 7/8"
1. Field-pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate
trap. Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain
line must comply with all local codes.
2. Supplied on dual-cool systems only.
3. Source: DPN001258, Rev. 1
87 Liebert® DS™
Blower Outlet and Deck Dimensions
Figure 68 Blower outlet and deck dimensions—Upflow, 28-42kW (8-12 tons) with forward-curved blowers
A
35"
(889mm)
B Ref
Front of Unit
Blower Outlet Location - Top View
* Duct flange not provided
Top of Unit
Blower Deck
D 1-1/2"
(38mm)
76"
(1930mm)
Ref
DPN001120
Front or Rear Throw Air Supply Rev. 3
Liebert® DS™ 88
Blower Outlet and Deck Dimensions
Figure 69 Blower outlet and deck dimensions—Upflow, 53-77kW (15-22 tons) with forward-curved
blowers
98" (2449mm) or 109" (2769mm)
F
E
Blower Outlets * C
A A
35"
(889mm)
Ref
B B
76"
(1930mm)
Ref.
DPN001191
Front or Rear Air Throw Supply Rev. 6
Dimensional Data, in. (mm)
Models Blower Supply A B C D E F
Front Throw 15-7/8 (404) 18-5/8 (472) 2-1/8 (54) 25-5/8 (651) 27-3/4 (705) 55-1/2 (1410)
15 x 15
53-77kW Rear Throw 15-7/8 (404) 18-5/8 (472) 11-5/8 (295) 25-5/8 (651) 27-3/4 (705) 55-1/2 (1410)
(15-22
tons) Front Throw 15-7/8 (404) 14-11/16 (373) 2-1/8 (54) 25-5/8 (651) 31-3/8 (797) 58-7/16 (1484)
15 x 11
Rear Throw 15-7/8 (404) 14-11/16 (373) 11-5/8 (295) 25-5/8 (651) 31-3/8 (797) 58-7/16 (1484)
Source: DPN001191, Rev. 6
89 Liebert® DS™
Blower Outlet and Deck Dimensions
Figure 70 Blower outlet and deck dimensions—Upflow, 105kW (30 tons), forward-curved blowers
132" (3353mm)
G
Blower Outlets * F
E C
A A A
35"
(889mm)
B B B
Ref
76"
(1930mm)
Ref
DPN001192
Front or Rear Throw Air Supply Rev. 1
Liebert® DS™ 90
Blower Outlet and Deck Dimensions
31-1/4"
(794mm)
Compressor Assembly
76" (1930mm)
Assembled
Filter & Coil Height
Assembly
76"
(1930mm)
45-13/16"
(1163mm)
91 Liebert® DS™
Blower Outlet and Deck Dimensions
31-1/4"
(794mm)
Compressor Assembly
76"
(1930mm)
Assembled
Filter & Coil Height
Assembly
76"
(1930mm)
45-13/16"
(1163mm)
Liebert® DS™ 92
Blower Outlet and Deck Dimensions
Figure 73 Disassembly dimensions—Upflow, air-cooled, 53-77kw (15-22 tons), scroll or digital scroll
compressors
31-1/4"
Compressor Assembly (794mm)
76"
(1930mm)
Filter & Coil Assembled
Assembly Height
76"
(1930mm)
45-13/16"
(1163mm)
93 Liebert® DS™
Blower Outlet and Deck Dimensions
31-1/4"
(794mm)
Compressor Assembly
76" (1930mm)
Filter & Coil Assembled Height
Assembly
76"
(1930mm)
45-13/16"
(1163mm)
Liebert® DS™ 94
Blower Outlet and Deck Dimensions
Figure 75 Disassembly dimensions—Upflow, air-cooled, 105kW (30 tons), standard scroll compressors
31-1/4"
(794mm)
Compressor
Assembly 76"
(1930mm)
Assembled
Height
Filter & Coil Assembly
76"
(1930mm)
45-13/16"
(1164mm)
95 Liebert® DS™
Blower Outlet and Deck Dimensions
31-1/4"
(794mm)
Compressor
Assembly
76"
(1930mm)
Assembled
Filter & Coil Height
Assembly
76"
(1930mm)
45-13/16"
(1164mm)
33" 26"
(660mm) 105" (2667mm)
(838mm)
131" (3327mm
Assembled Length
Drawing views are simplified with panels removed to show overall dimensions. DPN003168
See disassembly and handling instructions in installation manual. Rev. 1
Liebert® DS™ 96
Blower Outlet and Deck Dimensions
31-1/4"
(794mm)
Compressor Assembly
76" (1930mm)
Assembled
Filter & Coil Height
Assembly
76"
(1930mm)
45-13/16"
(1163mm)
97 Liebert® DS™
Blower Outlet and Deck Dimensions
31-1/4"
(794mm)
Compressor Assembly
76"
(1930mm)
Assembled
Height
Filter & Coil
Assembly
76"
(1930mm)
45-13/16"
(1163mm)
33" 26"
(838mm) (660mm) 82" (2083mm)
108" (2743mm)
Assembled Length
DPN003167
Drawing views are simplified with panels removed to show overall dimensions.
See disassembly and handling instructions in installation manual.
Rev. 1
Liebert® DS™ 98
Blower Outlet and Deck Dimensions
31-1/4"
(794mm)
Compressor Assembly
76"
(1930mm)
45-13/16"
(1164mm)
33" 26"
(838mm) (660mm) 105" (2667mm)
131" (3327mm)
Assembled Length
Drawing views are simplified with panels removed to show overall dimensions. DPN003170
See disassembly and handling instructions in installation manual. Rev. 1
99 Liebert® DS™
Ancillary Items
33"
(838mm)
34-1/2"
876mm
(With Feet) 1"
(35mm)
Typical
Right side of paneled unit is flush with right side of floor stand.
All other paneled sides overhang floor stand 1" (25mm).
* Leveling feet are provided with ± 1-1/2" (38mm) adjustment
from nominal height C.
C*
7/8" 8"
(23mm) (203mm)
Figure 81 Floor stand dimensions, downflow, 53-77kW (15-22 tons) models with EC fans
A
B
3/4" Piping Access Area
(19mm)
31-1/2" 32"
(800mm) (813mm)
Center Feet
32-3/4"
3/4" C (832mm)
(19mm) Support Feet Centers See Note 4
7/8"
(23mm) F*
G
3"
(76mm)
E 35" (889mm)
Notes Overall Depth
1. This floor stand should be used when EC fans are intended to be lowered under
a raised floor. The standard Liebert DS floor stand can be used if the fans are to
remain in their original raised position.
2. Right side of paneled unit is flush with right side of floor stand. All other paneled sides
overhang floor stand 1" (25mm).
3) The floor stand used with EC units is not symmetrical, and its orientation to the
Liebert DSE is critical for lowering the EC fans. The blowers will not lower into the
floor stand unless the floor stand is installed in the correct position.
4. Jack and jack support are shipped loose and are intended to be placed into position
under each fan and utilized to lower or raise that fan as needed.
DPN003173
* Leveling feet are provided with ±1-1/2" (38mm) adjustment from nominal height F. Rev. 1
Figure 82 Floor stand dimensions—Downflow, 105kW (30 tons) models with EC fans, standard scroll and
semi-hermetic compressors
132-1/2" (3366mm)
(with feet)
131" (3327mm)
25"
(635mm)
34-1/2"
33" 35" (889mm)
(876mm)
(with feet) (838mm) (with feet)
Typ. Both Ends Typ. (2) Places
19-1/4"
(489mm)
A See
Note 4
35"
7/8" (889mm)
3" (76mm) (23mm) Overall Depth Height - A
Notes in. (mm)
1. This floor stand should be used when EC fans are intended to be lowered
under a raised floor. The standard Liebert DS floor stand can be used 24 (610)
if the fans are to remain in their original raised position. 30 (762)
2. Right side of paneled unit is flush with right side of floor stand. All other paneled 36 (914)
sides overhang floor stand 1" (25mm).
3. The floor stand used with EC units is not symmetrical and its orientation to the
42 (1067)
Liebert DS is critical for lowering the EC fans. The blowers will not lower into the floor stand 48 (1219)
unless the floor stand is installed in the correct position.
4. Jack and jack support are shipped loose and are intended to be placed into
position under each fan and utilized to lower or raise that fan as needed.
5. Not applicable to 24' (610mm) x 30" (762) tall floor stands. DPN003174
*Leveling feet are provided with ± 1-1/2" (38mm) adjustment from nominal height “A.” Rev. 2
9.2 Plenums
Figure 83 Plenum dimensions—Upflow VS028-VS042 with EC fans
Top duct flanges on plenum
1 Shaded area indicates a recommended top for supply air ducting when
minimum clearance of 36" (914mm) for solid panel plenum is used.
component access from the bottom of the unit mm) 32.1"
63 0.88"
(815mm)
to the top of the plenum. (14 (2.2mm)
.6"
2 Must have access to remove front grille 57
or panel to remove EC fans.
19.7"
(500mm)
Plenum
Height
4.3" (109mm)
0.88" 1.3"
Both top duct opening
(2.2mm) (33mm)
and grilles shown. See
specification sheet m)
4 0m
for specific application. (14 2
.7"
56
mm)
5 05
" " (1
1.3 m) 9.2
5
m 5
33.75" (33
(857mm)
DPN002747
Height
In. (mm)
Rev. 1
Plenum Type
Grille & Top Discharge 24 (610)
Top Discharge Only 30 (762)
Top Discharge Only 36 (914)
4" (102mm)
1"
Plenum (25mm)
Height
2
Both top duct opening 0.88"
and grilles shown. See (2.2mm)
mm)
specification sheet 0 32
for specific application. " (2
80
)
3 mm
08
" (2
82
1"
(25mm)
34"
(864mm)
1
DPN002748
Rev. 3
Height
Plenum Type In. (mm)
Grille & Top Discharge 24 (610)
Top Discharge Only 30 (762)
Top Discharge Only 36 (914)
4" (102mm)
1"
m)
m
(51 m)
(25mm)
2" 9m
5 2
Plenum " (5
22
Height
0.88"
(2.2mm)
m)
32m
" (20 m)
80 73m
(26
5"
10
34" 1"
(864mm) (25mm)
1
DPN002749
Rev. 1
Height
Plenum Type In. (mm)
Grille & Top Discharge 24 (610)
Top Discharge Only 30 (762)
Top Discharge Only 36 (914)
7-15/16"
(202mm)
76"
(1930mm)
40"
(1016mm)
38-1/4"
(971mm)
Duct Size
3-1/2" (89mm)
D Duct Size
A B C
NOTES
1. Filters can be accessed from either side.
2. 25" (635mm) minimum clearance provided on one side for filter access. DPN001196
3. Filter boxes are shipped flat and must be field assembled. Rev. 1
A B C D
Model # in. (mm) in. (mm) in. (mm) in. (mm) # Filters
DS28-42kW (8-12 Tons) Air-Cooled Scroll
4-1/4 (108) 50-3/4 (1289) 18 (457) 47-5/8 (1210) 4
and Air-Cooled Digital Scroll Models
DS28-42kW (8-12 Tons) Semi-Hermetic and All
4-1/4 (108) 50-3/4 (1289) 31 (787) 47-5/8 (1210) 4
Water/Glycol/GLYCOOL Models
DS53-77kW (15-22 Tons) Air-Cooled Scroll
3-1/4 (83) 75-1/2 (1918) 19-1/4 (489) 72-3/8 (1838) 6
and Air-Cooled Digital Scroll Models
DS53-77kW (15-22 Tons) Semi-Hermetic and
3-1/4 (83) 75-1/2 (1918) 30-1/4 (768) 72-3/8 (1838) 6
All Water/Glycol/GLYCOOL Models
DS105kW (30 Tons), All Models 2-1/4 (57) 100-1/4 (2546) 29-1/2 (749) 97-1/8 (2467) 8
Source: DPN001196, Rev. 1
10.0 PIPING
Table 41 Recommended refrigerant line sizes - OD copper (inches)
Standard Scroll Models (Non-Digital Scroll)
Model 028 035 042 053 070 077 105
Hot Hot Hot Hot Hot Hot Hot
Equivalent Gas Liquid Gas Liquid Gas Liquid Gas Liquid Gas Liquid Gas Liquid Gas Liquid
Length Line Line Line Line Line Line Line Line Line Line Line Line Line Line
50 ft (15m) 7/8 1/2 7/8 1/2 7/8 1/2 7/8 5/8 1-1/8 7/8 1-1/8 7/8 1-3/8 7/8
100 ft (30m) 7/8 5/8 7/8 5/8 7/8 5/8 1-1/8 7/8 1-1/8 7/8 1-1/8 7/8 1-3/8 7/8
150 ft (45 m) 7/8 5/8 7/8 5/8 7/8 5/8 1-1/8 7/8 1-1/8 7/8 1-1/8 7/8 1-3/8 1-1/8
4-Step Semi-Hermetic and Digital Scroll Models
Model 028 035 042 053 070 077 2 105 2
Hot Hot Hot Hot Hot Hot Hot
Equivalent Gas Liquid Gas Liquid Gas Liquid Gas Liquid Gas Liquid Gas Liquid Gas Liquid
Length Line Line Line Line Line Line Line Line Line Line Line Line Line Line
50 ft (15m) 3/4 1/2 3/4 1/2 7/8 5/8 7/8 7/8 1-1/81 7/8 1-1/8 7/8 1-3/8 7/8
1
100 ft (30m) 3/4 5/8 7/8 5/8 7/8 5/8 1-1/8 7/8 1-1/81 7/8 1-1/8 7/8 1-3/8 7/8
1 1 1
150 ft (45 m) 7/8 5/8 7/8 5/8 1-1/8 5/8 1-1/8 7/8 1-1/8 7/8 1-1/8 7/8 1-3/8 1-1/8
1. Downsize vertical riser one trade size (1-1/8" to 7/8")
2. Digital scroll not available on 077 and 105 models.
3. Source: DPN000788, Rev 1
Condenser Condenser
Optional Field-Installed
Coil Coil
Fusible Plug
Liebert Lee-Temp
Internal
Inverted Trap
Liquid
For rises over 25ft. (7.6m),
Sensing
Evaporator trap every 20ft. (6m) or at
Coil evenly divided distances*
Bulb
Service
Valve Suction
NOTES
Single refrigeration circuit shown for clarity. DPN002188
Schematic representation shown. Do not use for specific connection locations. Rev. 3
Figure 89 Piping schematic, air-cooled with semi-hermetic compressor with fin/tube condenser
Liquid Return
Check Relief Valve Service
Valve Valve Optional
Subcooling
Coil Optional
Head Pressure Inverted trap on discharge
Sub-Cooling
Control Valve and liquid lines to extend above
Coil
Liebert Lee-Temp Receiver base of coil by a minimum of
7-1/2" (190mm).
CONDENSER CONDENSER
COIL COIL Optional Field-Installed
(Liebert Lee-Temp) (FAN SPEED or VFD) Fusible Plug
LIEBERT LEE-TEMP
Muffler
Field-installed relief valve(s)
COMPRESSOR Service External required for 50Hz EU CE units
Valve Equalizer rated maximum 480 PSIG (33 Bar).
Check Valve
*Isolation
Valve
**Muffler
Figure 90 Piping schematic, air-cooled with scroll or digital scroll compressor with fin/tube condenser
Inverted Trap on discharge Relief
and liquid lines to extend above Check Valve Service
base of coil by a minimum of Valve Valve Liquid Return Optional
7-1/2" (190mm).
Sub-Cooling
Head Pressure Coil
Optional
Liebert Lee-Temp Receiver Control Valve
Subcooling
Coil
Service
Valve Field-installed relief valve(s) required
for 50Hz EU CE units rated maximum
Check External
Service 480 PSIG (33 Bar).
Valve Equalizer
COMPRESSOR Valve
*Isolation
Valve
Hot Gas Discharge
Flow Switch
Supplied with Dual
Pump Systems
* Shutoff Valve * Flow-Regulating
RETURN SUPPLY Valve
RETURN SUPPLY
LIEBERT DS
RETURN
(and associated piping) SUPPLY
Muffler
COMPRESSOR Two-Way
Service External Regulating
Check
Valve Equalizer Valve
Valve
DISCHARGE
Flow Switch
Supplied with Dual
Pump Systems
RETURN SUPPLY
LIEBERT DS
(and associated piping) RETURN SUPPLY
Service
Valve
Service External Two-Way
CheckCOMPRESSOR Valve
Equalizer Regulating
Valve Valve
DISCHARGE
Flow Switch
Supplied with Dual
Pump Systems
RETURN SUPPLY
To
Expansion Solenoid Sight Filter Drier Liebert
Valve Valve Glass Pressure iCOM
Relief valve(s) supplied Transducer Control
with 50 Hz EU CE units rated To Second
maximum 480 PSIG (33 Bar). Refrigeration
Circuit
Flow Switch
Supplied with Dual
Pump Systems
Flow-Regulating
Shutoff Valve*
Valve*
RETURN SUPPLY
External
Equalizer
Muffler
COMPRESSOR
Service
Check Valve Valve Service
DISCHARGE Valve
® 3-Way
PARADENSER
CONDENSER Regulating
Valve
RETURN SUPPLY
Check Service
Valve Valve External
COMPRESSOR Equalizer
DISCHARGE
3-Way
Paradenser® Regulating
Condenser Valve
Flow Switch
Supplied with Dual
Pump Systems
Flow-Regulating
Shutoff Valve* Valve*
RETURN SUPPLY
Service
Valve
Check External
3-Way
Valve COMPRESSOR Equalizer
Motorized From
Ball Valve Liebert
DISCHARGE iCOM
Control
PARADENSER®
CONDENSER
Return Return
Supply Supply
Econ-O-Coil Econ-O-Coil
Factory Piping *Supplied with 10 feet (3m) extra thermistor wire for installation
Field Piping on field suppy line.
DPN000805
1. Place thermistor in location where flow is always present.
Rev.
2
2. Thermistor must be located out of the supply air stream.
3. On downflow units the sensor is coiled in the bottom of the
unit on the left side. On upflow units it is coiled on top of unit on the left side.
Figure 98 Electrical field connections—Upflow and downflow models, single molded case switch
disconnect with main fuses
P64
6 CONTACTORS
P67
60Hz
Downflow 3
1 5 6 Typical orientation of components shown. DOWNFLOW LOW-VOLTAGE SECTION
Component location varies by option and unit size.
17 18 9 22 16 19
NOTICE
UPFLOW Risk of broken or shorted low-voltage
82 83 88 89 75 76 94 95 96 97 91 92 93 80 81 11 12 wiring. Field-installed low-voltage wiring
3 must be routed with loop as shown
A B to allow electric box to swing.
24 23 21 7 8 10 20
C D
C D
11
SH
49-1
49-3
12
E E
Item 12 Installation Conditions
1. Follow all local installation codes. Point of Hinged Low-Voltage
DPN000807 2. Do not run CAN cables in same conduit, raceway, or Electric Box
chase as high voltage wires (120-600V). LIEBERT DS UPFLOW LOW-VOLT SECTION
Pg. 3, Rev. 13
3. Separate high volt wires from CAN wires by 12 inches.
4. For runs greater than 350ft(107m), contact Liebert factory.
Figure 99 Electrical field connections—Upflow and downflow models, dual-fused disconnect switches
See 11.1 - Standard Electrical Field Connections, 11.2 -
Optional Electrical Connections, 11.2 - Optional Electrical
Connections and 11.3 - Optional Low Voltage Terminal Liebert
2 Package Connections for keys to numbered components. IntelliSlot
4 Housing
A B
OVERCURRENT PROTECTION DEVICES
15 C D
60Hz 14
6
Alternate
15 Alternate
Location
Location
P64
CONTACTORS P67
PRIMARY SECONDARY
13
CONTACTORS, RELAYS and
OVERLOAD PROTECTORS
C D
C D
11
SH
49-1
49-3
12
E E
Item 12 Installation Conditions
1. Follow all local installation codes.
Point of Hinged Low-Voltage
2. Do not run CAN cables in same conduit, raceway or
chase as high-voltage wires (120-600V).
Electric Box
3. Separate high-voltage wires from CAN wires by 12” (305mm) DS UPFLOW LOW-VOLTAGE SECTION
4. Contact factory for runs greater than 350ft. (107m).
DPN000807
Pg. 4, Rev. 13
Table 47 85°F/33RH return air conditions for Hot Aisle/Cold Aisle applications
Outdoor Design Ambient Temperature
Model # 95°F (35°C) 100°F (38°C) 105°F (41°C) 110°F (43°C) 115°F (46°C) 120°F (49°C)
DS/VS028A MCM056_8 MCM080_8 MCL110_8 MCL110_8 MCL110_8 MCM160_8
DS/VS035A MCM056_8 MCM080_8 MCL110_8 MCL110_8 MCM160_8 MCM160_8
DS/VS042A MCM080_8 MCL110_8 MCL110_8 MCM160_8 MCM160_8 MCM160_8
DS/VS053A MCL110_8 MCL110_8 MCM160_8 MCL220_8 MCL220_8 MCL220_8
DS/VS070A MCL110_8 MCM160_8 MCM160_8 MCL220_8 MCL220_8 MCL220_8
DS/VS077A MCL110_8 MCM160_8 MCM160_8 MCL220_8 MCL220_8 MCL220_8
DS/VS105A MCM160_8 MCL220_8 MCL220_8 MCL220_8 MCL220_8 —
™
Table 48 T75°F/45RH return air conditions Liebert QuietLine for lower sound levels
Outdoor Design Ambient Temperature
Liebert DS
Model # 95°F (35°C) 100°F (38°C) 105°F (41°C) 110°F (43°C) 115°F (46°C)
DS/VS028A MCM080E8 MCM080E8 MCL110E8 MCL110E8 MCL110E8
DS/VS035A MCM080E8 MCL110E8 MCL110E8 MCM160E8 MCM160E8
DS/VS042A MCM080E8 MCL110E8 MCL110E8 MCM160E8 MCM160E8
DS/VS053A MCL110E8 MCL110E8 MCM160E8 MCL220E8 MCL220E8
DS/VS070A MCL110E8 MCM160E8 MCL220E8 MCL220E8 MCL220E8
DS/VS077A MCL110E8 MCM160E8 MCL220E8 MCL220E8 MCL220E8
DS/VS105A MCM160E8 MCL220E8 Consult Factory
H
Top of
Fan Guard
G
A F
A*
Liebert Lee-Temp
Entering Hot Gas
C and Leaving
D Liquid Piping
Anchor
A Plan
Main
Full height leg Electric
M L K
supplied for each Box
Liebert Lee-Temp End
Receiver Required 6-1/2"
(165mm) Ref
6-1/2"
Dual Circuit Only
(165mm) Ref
15-1/4" K 15-1/4"
(387mm) (387mm)
J Dual Circuit Only
Left Side of Unit Liebert Lee-Temp Only
3-5/8"
(93mm) FRONT VIEW
13/16" Emerson recommends a clearance of
Typical (Liebert Lee-Temp Shown)
(21mm) 36" (915mm) on each side for proper
Typical operation and component access.
1-7/8" (48mm)
7" Typical
(178mm)
Typical
1/2" x 1"
(13mm x 25mm)
Obround Typical DPN003437
DETAIL A
Typical of all Legs
Rev. 1
A* J
Liebert A (575V Only) C D Liebert Lee-Temp K L M
Model No. in. (mm) in. (mm) in. (mm) in. (mm) Only in. (mm) in. (mm) in. (mm)
94-7/8 103-1/8 88-3/8 86-3/4 42-1/2 42-1/2 40-7/8 35-7/8
MCS056
(2411) (2619) (2245) (2203) (1079) (1080) (1038) (910)
105-1/4 113-7/16 96-1/16 94-7/16 46-5/16 46 44-3/8 39-5/16
MCM080
(2674) (2882) (2440) (2398) (1177) (1168) (1127) (999)
124-1/8 133-1/8 112-1/8 110-1/2 54-3/8 55-1/2 53-7/8 48-3/4
MCL110
(3152) (3381) (2848) (2806) (1381) (1410) (1368) (1238)
Source: DPN003437, Rev. 1
B
Lifting Eyebolts
Typ. (4) Places
F
H
A* Top of
A Fan Guard
G
Liebert Lee-Temp
Receiver
Entering Hot Gas
C and Leaving
E D Liquid Piping 54-3/16
(1376mm)
A Typical
7"
(178mm) 1-7/8"
Typical (48mm)
Typical
1/2" x 1"
(13mm x 25mm) DPN003439
DETAIL A Obround Typical
Rev. 1
Typical of all Legs
A* J
Liebert A (575V Only) B C D E Liebert Lee-Temp K L M
Model No. in. (mm) in. (mm) in. (mm) in. (mm) in. (mm) in. (mm) Receivers Only in. (mm) in. (mm) in. (mm)
202-7/16 210-5/8 113-1/2 192-1/4 94-7/16 96-3/16 46-5/16 46 44-3/8 39-5/16
MCM160
(5142) (5350) (2883) (4883) (2398) (2444) (1177) (1168) (1127) (999)
236-5/16 245-5/16 129-9/16 224-3/8 110-1/2 112-1/4 54-3/8 55-1/2 53-7/8 48-3/4
MCL220
(6003) (6231) (3291) (5699) (2806) (2851) (1381) (1410) (1368) (1238)
Source: DPN003439, Rev. 1
* Cover
Vertical
Inverted traps
are factory provided
inside condenser
Leaving Liquid
Field Piping
Line
Horizontal
Entering Hot
Gas Line
DETAIL A
Circuit #1 Circuit #2
Table 54 Liebert MC piping connection sizes—Liebert MC dual-circuit, two-fan and four-fan units
Connection Sizes, OD, in
# of
Model # Fans Hot Gas Line Liquid Line
MCS056 2 7/8 5/8
MCM080 2 7/8 5/8
MCL110 2 1-1/8 7/8
MCM160 4 1-1/8 7/8
MCL220 4 1-3/8 1-1/8
Source: DPN002425, Rev. 5
Figure 103 Piping dimensions—Liebert MC™ dual-circuit condensers with Liebert Lee-Temp™
Hot Gas Line
To Condenser
Entering Hot
Gas Line
C View
B View
* Cover
* Shipping cover is not necessary for proper
condenser operation and may be recycled if field
piping interferes with proper reattachment
Position elbow to
direct relief valve
B View Fasten hot gas line to cabinet
using flat surface clamps with
downward isolators (field-supplied)
See Detail A A
Leaving Metal Clamp
Liquid Line Hot Gas Line Isolator
Liquid Line Detail AA
To Condenser
From Condenser
GENERAL ARRANGEMENT
Electrical connection
Fan 1 box; cover removed
for clarity
Without Liebert
Lee-Temp Electrical service connection.
With Liebert
Pigtails in electric handy box
are factory-wired to Liebert Lee-Temp Lee-Temp
heater pads for field-connection
of separate continuous electric
source; wire not by Emerson.
+
5A
5B
+
6
xxxxxxxxxxxxxxxxxxxxxx
4
xxxxxxxxxxxxxxxxxxxxxx
+
+ 2
xxxxxxx
xxxxxxxxxxxxxx
xxxxxxx
xxxxxxx
xxxxxxx xxxxxxx
xxxxxxx
xxxxxxx
xxxxxxx
ALARM RELAY CARD xxxxxxxxxxxxxx
xxxxxxx xxxxxxx
xxxxxxx
xxxxxxx xxxxxxx
xxxxxxx
7
XX
XX
5C xxxxxxx
xxxxxxx
xxxxxxx
xxxxxxx
xxxxxxx
xxxxxxx
xxxxxxx xxxxxxx
xxxxxxx
xxxxxxx
xxxxxxx
xxxxxxx
xxxxxxx
+
3
11 Right Two
8 Left Knockout Knockouts
10 Item appears only with
12
13
Liebert Lee-Temp board
9 70
71
See on page 132 for key to numbered
230
components
NOTICE!
THIS HOLE FOR FIELD
SUPPLIED EXTRA LOW
VOLTAGE CONTROL WIRING DPN002169 DPN002374
Pg. 1, Rev. 7 Pg. 1, Rev. 6
Notes
1. Refer to specification sheet for unit voltage rating, full load amp, and wire size amp ratings.
2. The CANbus wiring is field supplied and must be:
• Conductors 22-18AWG stranded tinned copper
• Twisted pair (minimum 4 twists per foot)
• Braided shield or foil shield with drain wire
• Shield must be wired to ground at indoor unit
• Low Capacitance (15pf/ft or less)
• UL approved temperature rated to 75°C
• UL approved voltage rated to 300V
• UV-resistant and moisture-resistant if not run in conduit
• Examples: Belden part number 89207(plenum rated) or Alpha Wire part number 6454 (UV
resistant outdoor rated) Category 5, 5e or higher. Do not run the CANbus cable in the same
conduit, raceway or chase as high voltage.
3. Do not run the CANbus cable in the same conduit, raceway or chase as high voltage.
4. No special considerations are required when the total external cable connection between the
indoor unit and outdoor unit(s) is less than 450ft. (137m). For total external cable connections
greater than 450ft. (137m) but less than 800ft. (243m), a CANbus isolator is required.
5. All wiring must be sized and selected for insulation case per NEC and other local codes.
6. Do not bend cables to less than four times the diameter of the cable.
7. Do not deform cables when securing in bundles or when hanging them.
8. Avoid running the cables by devices that may introduce noise, such as machines, fluorescent
lights and electronics.
9. Avoid stretching cables.
10. Separate high volt wires and other high voltage sources from CAN wires by 12 inches.
11. The electrically commutated (EC) motors included in the Liebert MC™ Condenser are suitable for
connection to power supplies with a solidly grounded neutral. (Some platforms can accept power
supplies listed under Item b below. Contact the factory for more information.)
a. Acceptable power supplies for 208 to 575V nominal units
• 208V wye with solidly grounded neutral and 120V line to ground;
• 380V wye with solidly grounded neutral and 220V line to ground;
• 480V wye with solidly grounded neutral and 277V line to ground.
• 575V wye with solidly grounded neutral and 332V line to ground. (uses step-down
transformer)
b. Non-acceptable power supplies for 208V to 575V nominal units
• wye with high resistance (or impedance) ground;
• delta without ground or with floating ground;
• delta with corner ground; or
• delta with grounded center tap.
Table 57 Fin/tube condenser physical data and R-407C refrigerant required per condenser circuit
Connection Size, Dual-Circuit
OD, In. lb/circuit (kg/circuit)
Number Number Net Weight Liebert Lee-Temp™
Model # of Fans of Circuits Hot Gas Liquid lb (kg) FSC or VFD (includes receiver)
Standard Models
TCDV/CD*205 2 2 1-1/8 7/8 495 (225) 7 (3.2) 54 (24.4)
TCDV/CD*251 3 2 1-1/8 7/8 500 (227) 10 (4.6) 36 (16.3)
TCDV/CD*308 3 2 1-3/8 1-1/8 670 (304) 11 (5.0) 55 (24.9)
TCDV/CD*415 4 2 1-3/8 1-1/8 840 (381) 24 (10.9) 102 (46.2)
TCDV/CD*616 6 2 1-5/8 1-1/8 1380 (626) 26 (11.8) 108 (49.0)
Quiet-Line Models
TCDV/DCD*214 3 2 1-1/8 7/8 840 (381) N/A 77 (34.9)
TCDV/DCD*286 4 2 1-1/8 7/8 1105 (501) N/A 119 (54.0)
TCDV/DCD*409 6 2 1-5/8 1-1/8 1380 (626) N/A 148 (67.2)
TCDV/DCD*572 8 2 2-1/8 1-1/8 2430 (1102) N/A 186 (84.4)
13.1 Dimensions
Figure 105 Fin/tube condenser dimensions, 2-fan model
Emerson recommends a
clearance of 36" (915mm) on
43-9/16" each side for proper operation
(1106mm) and component access.
91-1/2"
(2324mm)
37-7/8"
(962mm)
18"
(457mm)
84"
(2134mm)
43-3/16"
(1097mm)
171-1/2"
(4356mm)
18" 70"
(457mm)
(1778mm) 37-7/8"
(962mm)
124"
Eyebolts
(3150mm)
for Lifting
43-3/16"
18"
(1097mm) (457mm)
Note:
Overall height to the top of fan guard 164"
43-1/8" (1095mm) (4166mm)
43-3/16"
(1097mm)
59"
(1499mm)
18"
(457mm)
18"
(457mm)
124"
86-3/4" (3150mm) 70" (1778mm)
(2203mm) 164"
1-1/2" (38mm) (4166mm)
diameter hole for
rigging (typ.4)
Overalll height to the top
of the fan guard is 43-1/8” (1095mm). 86-3/4"
(2203mm)
™ ™
Table 60 Fin/tube condenser data, Liebert Quiet-Line (Liebert Lee-Temp controlled/fan-cycling), 60Hz
Model # ph 214 286 409 572
3 Fans 4 Fans 6 Fans 8 Fans
Input
Voltage ph FLA WSA OPD FLA WSA OPD FLA WSA OPD FLA WSA OPD
208/230 5.4 5.9 15 7.2 7.7 15 10.8 11.3 15 14.4 14.9 20
460 3 2.7 2.9 15 3.6 3.8 15 5.4 5.6 15 7.2 7.4 15
575 2.1 2.3 15 2.8 3.0 15 4.2 4.4 15 5.6 5.8 15
FLA = Full Load Amps; WSA = Wire Size Amps; OPD = Maximum Overcurrent Protection Device
Factory-wired to 24V
control circuit.
Heat Rjection
Connection 70, 71 Electric Service Connection
Field-supplied terminals when factory
Class 2 wiring to disconnect is NOT supplied
interlock condenser 24V
controls to Liebert indoor
unit (70, 71). Refer to the 70
71 Electric Service Connection
condenser and indoor unit terminals when factory
electrical schematics for disconnect is supplied.
termination. 7/8 in (22.2mm)
diameter hole provided in
bottom of electric box.
Factory-installed disconnect
switch (optional).
Factory-wired to components on
electric panel.
Earth Ground Bar (optional on 50Hz only). Electric Service Entrance.
Connection terminals with factory A 7/8 in. (22.2mm) diameter hole in
ground from each high-voltage a 1-1/18 in. (28.6mm) knockout
component for field-supplied provided in bottom of electric box.
earth grounding wire.
Figure 109 Electrical field connections for VFD control fin/tube condensers
Factory-wired to 24V
control circuit.
Heat Rjection
Factory installed fuse block on
Connection 70, 71 60Hz units. Circuit breaker supplied
Field-supplied in lieu of fuse block on 50Hz units.
Class 1 wiring to
interlock condenser 24V Electric Service Connection
controls to Liebert indoor terminals with factory
unit (70, 71). Reference the supplied disconnect.
condenser and indoor unit
electrical schematics for
termination. 7/8" (22.2mm)
70
71
V
diameter hole provided in
11
12
13
14
F
bottom of electric box. D SPD Factory-installed
disconnect switch
Special Alarm Connections
Field- supplied 24V Class 1
wiring to remote alarm circuits
Surge Protection Device (SPD) Electric Service Entrance.
normally open alarm contact connections (11, 12). A 7/8" (22.2mm) diameter hole in
a 1-1/18" (28.6mm) knockout
Variable Frequency Drive (VFD)
provided in bottom of electric.
normally closed alarm contact connections (13, 14).
Reference the indoor unit electric
diagram (RAD1-4) for termination.
Factory-wired to components
Electric service,
on electric panel. not by Emerson
Earth Ground BAR (optional
on 50Hz only).
Connection terminals with factory
ground from each high-voltage DPN001051
component for field-supplied Rev. 2
Refer to specification sheet earth grounding wire.
for full load amp and wire size amp ratings Earth Ground Connection (60Hz)
Connection terminal for field-
supplied earth grounding wire
when factory disconnect is supplied.
Figure 110 Electrical field connections for Liebert Lee-Temp™ control fin/tube condensers
Figure 112 Liebert Lee-Temp™ head pressure control condenser piping—Fin/tube condensers
Metal
Clamp
Isolator
Detail A-A
Table 66 Separate electrical supply requirements for Liebert Lee-Temp™ receivers, 60Hz, 1 ph
Voltage 120 120 208/230 208/230
Watts/Receiver 150 300 150 300
FLA 2.5 5.0 1.4 2.8
WSA 3.1 6.2 1.8 3.6
OPD 15 15 15 15
Only one independent input power supply is needed per piggyback unit; connect to Terminals 90 & 91.
14.1 Dimensions
Figure 113 Piggyback condenser planning dimensions
E
H D
1-1/8" K J B
R Overa
ll Dim
(29mm) sions
Dimen ensio
Overall ns
K Optional Fan
Discharge
S Disconnect
H Switch (optional)
J 72"
35-1/8" R (1829mm)
(892mm) Fan Discharge
Shaded areas
indicate a recommended
clearance of 34" (864mm)
for component access.
5"
(127mm)
1"
G A (25.4mm)
C Unit Base
Condenser Coil Inlet
10" (254mm) Unit Base
And Duct Connection
Drain Outlet
C Opening UNIT DIMENSIONAL DATA
NOTE: A 1" (25.4mm) flange is provided on all units
F for duct connection to coil duct opening and
Floor Level fan air discharge opening.
A
DPN000695
Rev. 1
FLOOR CUTOUT DIMENSIONS
Table 67 Piggyback condenser dimensions, in. (mm)
Model A B C D E F G H J K R S
72 74 31 32 1-1/8 33 60 8-5/8 50-3/16 16-1/16 13-3/16 14-11/16
PB-350A
(1829) (1880) (787) (813) (29) (838) (1524) (219) (1275) (408) (335) (373)
72 74 31 32 1-1/8 33 60 8-5/8 50-3/16 16-1/16 13-3/16 14-11/16
PB-550A
(1829) (1880) (787) (813) (29) (838) (1564) (219) (1275) (408) (335) (373)
72 74 31 32 1-1/8 33 60 8-5/8 50-3/16 16-1/16 13-3/16 14-11/16
PB-675A
(1829) (1880) (787) (813) (29) (838) (1564) (219) (1275) (408) (335) (373)
97 99 33 34 3-1/8 45-1/2 85 23-5/16 50-3/16 16-1/16 23-1/2 14-11/16
PB-925A
(2464) (2515) (838) (864) (79) (1156) (2159) (592) (1275) (408) (597) (373)
97 99 33 34 3-1/8 45-1/2 85 23-5/16 50-3/16 16-1/16 23-1/2 14-11/16
PB-1100A
(2464) (2515) (838) (864) (79) (1156) (2159) (592) (1275) (408) (597) (373)
97 99 33 34 3-1/8 45-1/2 85 16-5/16 63-7/8 19-1/8 16-13/16 11-5/8
PB-1350A
(2464) (2515) (838) (864) (79) (1156) (2159) (421) (1622) (486) (427) (295)
Source: DPN000695, Rev. 1
Figure 114 Floor stand dimensions, piggyback condensers with forward-curved blowers
C
B
A
1"
(25.4mm) * H ± 1-1/2" (38mm)
For height selection
refer to chart.
Center Leg Provided
See Table 69 for on 99" Cabinets
height selection
Leg Support on Models DPN000727
18, 21 & 24" High Rev. 0
Factory-installed unit
disconnect switch (optional)
Field-supplied disconnect
switch when factory-installed
unit disconnect switch is not provided.
1" (25mm)
Panel 1" (25mm)
Panel
See Note 2 3" (76mm)
See Note 2 3" (76mm)
See Note 1 3" (76mm)
See Note 1 3" (76mm)
E See Note 3
E See Note 3
12-5/8"
(321mm) 12-5/8"
(321mm)
3"
Drain Outlet (76mm)
Location 8"
1-1/4" (32mm) F.P.T. 6" (203mm)
See Note 3
(152mm)
3"
ALL MODELS 1-1/2"
(76mm)
(38mm)
DPN00696
1. Multiple knockouts of 1-3/8" (35mm), 1-3/4" (45mm) and 2-1/2" (64mm) for main power supply (typical).
2. 7/8" (22.2mm) knockouts for Liebert Lee-Temp power supply (typical). Rev. 1
3. Cover plate for access of liquid line and hot gas line.
43-9/16"
(1106mm)
91-1/2"
(2324mm)
37-7/8"
(962mm)
18"
(457mm)
43-9/16"
(1106mm)
131-1/2"
(3340mm)
37-7/8" 43-9/16"
(962mm) (1106mm)
171-1/2"
(4356mm)
18" 70"
(457mm)
(1778mm) 37-7/8"
(962mm)
124"
Eyebolts
(3150mm)
for Lifting
43-3/16"
18"
(1097mm) (457mm)
Note:
Overall height to the top of fan guard 164"
43-1/8" (1095mm) (4166mm)
Emerson recommends a
43-3/16" clearance of 36" (915mm) on
(1097mm) each side for proper operation
and component access.
87-1/8"
131-1/2" (2213mm)
(3340mm) 87-1/8"
(2213mm)
171-1/2"
37-7/8" (4356mm)
(962mm)
37-7/8"
(962mm)
59"
(1499mm)
18"
(457mm)
18"
(457mm)
124"
86-3/4" (3150mm) 70" (1778mm)
(2203mm) 164"
1-1/2" (38mm) (4166mm)
diameter hole for
rigging (typ.4)
Overalll height to the top
of the fan guard is 43-1/8” (1095mm). 86-3/4" Emerson recommends a
clearance of 36" (915mm) on
(2203mm)
each side for proper
operation and component
Table 76 60Hz electrical values—Prop fan drycoolers without pump controls, Liebert Quiet-Line™
models
Drycooler Model
Electrical 173, 178 205, 248 347, 356 453
Voltage Phase Value 3 Fans 4 Fans 6 Fans 8 Fans
3 FLA 5.4 7.2 10.8 14.4
208/230 3 WSA 5.9 7.7 11.3 14.9
3 OPD 15 15 15 20
3 FLA 2.7 3.6 5.4 7.2
460 3 WSA 2.9 3.8 5.6 7.4
3 OPD 15 15 15 15
3 FLA 2.1 2.8 4.2 5.6
575 3 WSA 2.3 3.0 4.4 5.8
3 OPD 15 15 15 15
Table 77 60Hz electrical values—Standard prop fan drycoolers with integral pump controls
Number of Fans
2 3 4 6 8
Model # 174, 225 260, 310, 350 419, 466, 491 620, 650 880
Pump HP FLA WSA OPD FLA WSA OPD FLA WSA OPD FLA WSA OPD FLA WSA OPD
208/230/3/60
0.75 10.5 11.4 15 14.0 14.9 20 17.5 18.4 25 24.5 25.4 30 31.5 32.4 40
1.5 13.6 15.3 20 17.1 18.8 25 20.6 22.3 25 27.6 29.3 35 34.6 36.3 40
2.0 14.5 16.4 20 18.0 19.9 25 21.5 23.4 30 28.5 30.4 35 35.5 37.4 45
3.0 17.6 20.3 30 21.1 23.8 30 24.6 27.3 35 31.6 34.3 40 38.6 41.3 50
5.0 23.7 27.9 40 27.2 31.4 45 30.7 34.9 50 37.7 41.9 50 44.7 48.9 60
7.5 31.2 37.3 60 34.7 40.8 60 38.2 44.3 60 45.2 51.3 70 52.2 58.3 80
10.0 37.8 45.5 70 41.3 49.0 70 44.8 52.5 80 51.8 59.5 90 58.8 66.5 90
15 53.2 64.8 110 56.7 68.3 110 60.2 71.8 110 67.2 78.8 110 74.2 85.8 125
460/3/60
0.75 5.0 5.4 15 6.7 7.1 15 8.4 8.8 15 11.8 12.2 15 15.2 15.6 20
1.5 6.4 7.2 15 8.1 8.9 15 9.8 10.6 15 13.2 14.0 20 16.6 17.4 20
2.0 6.8 7.7 15 8.5 9.4 15 10.2 11.1 15 13.6 14.5 20 17.0 17.9 20
3.0 8.2 9.4 15 9.9 11.1 15 11.6 12.8 15 15.0 16.2 20 18.4 19.6 25
5.0 11.0 12.9 20 12.7 14.6 20 14.4 16.3 20 17.8 19.7 25 21.2 23.1 30
7.5 14.4 17.2 25 16.1 18.9 25 17.8 20.6 30 21.2 24.0 30 24.6 27.4 35
10.0 17.4 20.9 30 19.1 22.6 35 20.8 24.3 35 24.2 27.7 40 27.6 31.1 45
15 24.4 29.7 50 26.1 31.4 50 27.8 33.1 50 31.2 36.5 50 34.6 39.9 60
575/3/60
0.75 4.1 4.5 15 5.5 5.9 15 6.9 7.3 15 9.7 10.1 15 12.5 12.9 15
1.5 5.2 5.8 15 6.6 7.2 15 8.0 8.6 15 10.8 11.4 15 13.6 14.2 20
2.0 5.5 6.2 15 6.9 7.6 15 8.3 9.0 15 11.1 11.8 15 13.9 14.6 20
3.0 6.7 7.7 15 8.1 9.1 15 9.5 10.5 15 12.3 13.3 15 15.1 16.1 20
5.0 8.9 10.4 15 10.3 11.8 15 11.7 13.2 15 14.5 16.0 20 17.3 18.8 20
7.5 11.8 14.1 20 13.2 15.5 20 14.6 16.9 25 17.4 19.7 25 20.2 22.5 30
10.0 13.8 16.6 25 15.2 18.0 25 16.6 19.4 30 19.4 22.2 30 22.2 25.0 35
15 19.8 24.1 40 21.2 25.5 40 22.6 26.9 40 25.4 29.7 45 28.2 32.5 45
Table 78 60Hz electrical values—Liebert Quiet-Line™ drycoolers with integral pump controls
Number of Fans
3 4 6 8
Model # 173, 178 205, 248 347, 356 453
Pump H.P. FLA WSA OPD FLA WSA OPD FLA WSA OPD FLA WSA OPD
208/230/3/60
0.75 8.9 9.8 15.0 10.7 11.6 15.0 14.3 15.2 20.0 17.9 18.8 25.0
1.5 12.0 13.7 20.0 13.8 15.5 20.0 17.4 19.1 25.0 21.0 22.7 25.0
2.0 12.9 14.8 20.0 14.7 16.6 20.0 18.3 20.2 25.0 21.9 23.8 30.0
3.0 16.0 18.7 25.0 17.8 20.5 30.0 21.4 24.1 30.0 25.0 27.7 35.0
5.0 22.1 26.3 40.0 23.9 28.1 40.0 27.5 31.7 45.0 31.1 35.3 50.0
7.5 * 29.6 35.7 50.0 31.4 37.5 60.0 35.0 41.1 60.0 38.6 44.7 60.0
10.0 2 36.2 43.9 70.0 38.0 45.7 70.0 41.6 49.3 80.0 45.2 52.9 80.0
15 2 51.6 63.2 100.0 53.4 65.0 110.0 57.0 68.6 110.0 60.6 72.2 110.0
460/3/60
0.75 4.3 4.7 15.0 5.2 5.6 15.0 7.0 7.4 15.0 8.8 9.2 15.0
1.5 5.7 6.5 15.0 6.6 7.4 15.0 8.4 9.2 15.0 10.2 11.0 15.0
2.0 6.1 7.0 15.0 7.0 7.9 15.0 8.8 9.7 15.0 10.6 11.5 15.0
3.0 7.5 8.7 15.0 8.4 9.6 15.0 10.2 11.4 15.0 12.0 13.2 15.0
5.0 10.3 12.2 15.0 11.2 13.1 20.0 13.0 14.9 20.0 14.8 16.7 20.0
7.5 * 13.7 16.5 25.0 14.6 17.4 25.0 16.4 19.2 30.0 18.2 21.0 30.0
10.0 2 16.7 20.2 30.0 17.6 21.1 35.0 19.4 22.9 35.0 21.2 24.7 35.0
15 2 23.7 29.0 45.0 24.6 29.9 50.0 26.4 31.7 50.0 28.2 33.5 50.0
575/3/60
0.75 3.4 3.7 15.0 4.1 4.4 15.0 5.5 5.8 15.0 6.9 7.2 15.0
1.5 4.5 5.1 15.0 5.2 5.8 15.0 6.6 7.2 15.0 8.0 8.6 15.0
2.0 4.8 5.5 15.0 5.5 6.2 15.0 6.9 7.6 15.0 8.3 9.0 15.0
3.0 6.0 7.0 15.0 6.7 7.7 15.0 8.1 9.1 15.0 9.5 10.5 15.0
5.0 8.2 9.7 15.0 8.9 10.4 15.0 10.3 11.8 15.0 11.7 13.2 15.0
7.5 2 11.1 13.4 20.0 11.8 14.1 20.0 13.2 15.5 20.0 14.6 16.9 25.0
10.0 2 13.1 15.9 25.0 13.8 16.6 25.0 15.2 18.0 25.0 16.6 19.4 30.0
15 2 19.1 23.4 40.0 19.8 24.1 40.0 21.2 25.5 40.0 22.6 26.9 40.0
1. Values are calculated per UL 1995. Pump FLA values used are based on NEC tables for motor horsepower. OPD values may be
adjusted higher than calculations to compensate for maximum anticipated application temperatures.
2. May require electrical component(s) with higher capacity in the drycooler. Consult factory representatives for assistance before
ordering.
Figure 120 Electrical field connections for fluid temperature control, direct-drive Drycoolers
Factory-installed
Unit Alarm Connection disconnect switch
Field-supplied 24V. (optional).
Class 2 wiring to
Terminals "24 & 50"
to indicate "Standby Glycol
Pump On". (Supplied
with dual pump controls
only.)
Control interlock
Field-supplied
Class 2 wiring to
interlock drycooler
24V controls to
Liebert room unit
(Not required on
CSU 3000). 7/8" Pump fuses & overload
(22.2mm) diameter heaters (shipped with
hole provided in standard pump packages)
bottom of electric box. are to be field-installed in
pump fuse block(s) and
Flow switch connection starter(s).
(Dual pump controls only)
Earth ground bar (50Hz).
Field-supplied 24V Class 2
Connection terminals with factory
wiring from terminals 74 +
ground from each high voltage
77 to field mounted flow
component for field-supplied
switch.
earth grounding wire. Electric service entrance. Electric service.
Electric service connection A 7/8" (22.2mm) diameter hole not by Emerson.
terminals for power supply to in a 1-1/8" (28.6mm) knockout (Field-wired to Liebert
pumps when pump controls Earth ground connection (60 HZ). provided in bottom of electric CSU 3000.
are factory-supplied. Dual Connection terminal for field- box. Interconnecting wiring
pump connection shown. 7/8" supplied earth grounding wire. not by Emerson).
(22.2mm) diameter knockouts
provided in bottom DPN000276
of electric box. Refer to specification sheet for full load amp and wire size amp ratings.
Rev. 1
Inlet Connection
(Upper Header)
Outlet Connection
(Lower Header)
DPN000275
1/2" FPT Connections Rev. 3
EXPANSION TANK
(GLYCOOL CSU 3000
Units Supplied with
Compression Tank)
Inlet
Connections
(4 Inlet, 4 Outlet
Connections Shown)
See table for actual DPN002429
number provided. Rev. 0
Outlet Connections
Figure 123 Typical piping arrangement, multiple prop fan drycoolers and multiple indoor units
Expansion Tank
Gal. (L)
Total
FS GPM
(L/s):
Drycooler No. 1 Model Cooling Unit # Pipe
GPM (L/s) P: Ft (kPA) Model Diam.: In. (mm)
P: Ft. (kPa)
GPM (L/s)
Cooling Unit #
P Ft (kPa):
Model
Cooling Unit # GPM (L/s)
Model P Ft (kPa):
GPM (L/s)
Cooling Unit #
P Ft (kPa):
See Note 3 Model
Cooling Unit # GPM (L/s)
Model P Ft (kPa):
GPM (L/s)
Cooling Unit #
P Ft (kPa):
Model
Cooling Unit # GPM (L/s)
Model P Ft (kPa):
Drycooler No. 2 Model
GPM (L/s) P: Ft (kPA) GPM (L/s)
Cooling Unit #
P Ft (kPa):
LEGEND Model
Gate Valve Cooling Unit # GPM (L/s)
Model P Ft (kPa):
Check Valve
GPM (L/s)
Butterfly Valve P Ft (kPa):
Cooling Unit #
Model
Relief Valve
Cooling Unit # GPM (L/s)
Union P Ft (kPa):
Model
Ball Or Flow Control Valve GPM (L/s)
Cooling Unit #
P Ft (kPa):
FS Flow Switch Model
P:Pressure Drop GPM (L/s)
P Ft (kPa):
Strainer Filter
Notes:
1. Pressure and temperature gauges (or ports for same) are recommended to monitor
component pressure drops and performance.
2. Flow measuring devices, drain and balancing valves to be supplied by others and
located as required.
3. See product literature for installation guidelines and clearance dimensions.
4. Drawing shows dual pump package. Alternate pump packages with more pumps may be DPN000991
considered, consult supplier Rev. 0
G 1"
A (25.4mm)
Condenser Coil Inlet 10" C Unit Base
and Duct Connection (254mm) Unit Base
16.4 Piping
Figure 125 Piping—Indoor piggyback drycooler models
See
See Note 4
Note 4
See
See Note 1
Note 1
See Note 2 D
1-13/16" E
A (46mm) A
E
C
C
B B
1-13/16"
(46mm) See Note 2
D 3" (76mm) 3" (76mm)
12-5/8"
12-5/8"
(321mm)
(321mm)
4-1/2"
9-11/16" (114mm) 9-11/16" 4-1/2"
(246mm) 7-7/8" (246mm) (114mm)
(200mm) 7-7/8"
(200mm)
MODELS PD-102 THRU PD-290
MODEL PD-333
5-1/2" (140mm) See Note 1
3-1/4" (85mm)
See Note 4
Drain Outlet
Location 3"
1-1/4" (32mm) F.P.T. (76mm)
8"
See 6" (1
52m (203mm)
Note 2 m)
3" (7
NOTES 6mm
1-1/2 )
1. Multiple knockouts of 1-3/8" (35mm), 1-3/4" (45mm) and " (38
mm)
2-1/2" (64mm) for main power supply (typical).
2. Cover plate for access of glycol piping inlet and outlet. ALL MODELS
3. Piggyback drycooler connection sizes for supply and return
glycol lines are the same as room unit supply and return lines.
FE/FH 110G 1-5/8" (41mm); FE/FH116G - 2-1/8" (54mm).
Note applies to PD-133. DPN000711
4. 7/8" (22.2mm) knockout provided. Rev. 1
17-1/4"
SINGLE PACKAGE 0.75 - 7.5 HP (438.2mm)
1
3
19"
(482.6mm)
2-7/8"
15-7/8" (72.9mm)
(403.2mm)
1-3/4"
6-3/8"
(44.4mm)
(161.9mm)
8-3/4"
(222.3mm)
12-1/4"
(311.1mm) 30"
(762mm)
17"
(431.8mm)
PUMP PACKAGE MOUNTING ANGLES
(Angles are inside, bottom
of pump package. View used for
1 3" (76.2mm) diameter pump suction mounting reference.)
connection knockouts 4
3/4"
(19mm)
C
A DPN000278
Rev. 0
B
3
4-1/8"
6-3/8" (104.8mm)
15-7/8" (161.9mm) "
2-7/8" 19"
(403.2mm) (482.6mm)
(73mm)
23-3/4" 30"
(603.2mm) (762mm)
27-1/4" 1 3" (76.2mm) diameter pump suction
(692.1mm) connection knockouts
32" 2 3" (76.2mm) diameter pump discharge
(812.8mm) connection knockouts
3 7/8" (22.2mm) diameter electrical knockouts
5 5" (127mm) diameter pump discharge
connection hole
6 5" (127mm) diameter pump suction
connection hole
32-3/8"
DUAL PACKAGE 7.5 HP 3 41-1/4"
(822.3mm)
5 (1047.8mm)
6
5
6
19-15/16
(506.4mm)
11-7/8
(301.6mm)
15-7/8
(403.2mm)
33-3/16" 16-3/8"
(843mm) (415.9mm)
29-3/16"
(741.4mm)
6-1/2" DPN000328
41"
(165.1mm)
(1041.4mm) Rev. 0
2-3/4" 2-1/2"
(69.9mm) (63.5mm) 7"
(177.8mm)
140 D 2
F E 3
F 5
120 E
G 7.5
D
100 G
C
80 B
A
60
40
20
0 10 20 30 40 50 60 70 80 120 160 200 250 300 400
Flow Rate, GPM
Capacity data is rated and factory-certified per ASHRAE 127-2007 with a 0% tolerance.
Table 89 U.S. DOE performance table—Liebert DS upflow and downflow, air-cooled (continued)
Total Cooling Capacity Sensible Cooling Capacity
Basic Model Airflow
Number Configuration Btu/hr kW Btu/hr kW CFM SCOP
DS070AU*0* Downflow 216853 63.56 193460 56.70 8613 2.27
DS070AU*1* Downflow 221634 64.96 202332 59.30 9277 2.43
DS070DD*0* Downflow 224707 65.86 195849 57.40 8613 2.1
DS070DD*1* Downflow 228805 67.06 204720 60.00 9277 2.21
DS070DU*0* Downflow 214462 62.86 190731 55.90 8613 2.18
DS070DU*1* Downflow 218902 64.16 199943 58.60 9277 2.32
DS077AS*1* Downflow 252710 74.07 226216 66.30 10644 2.1
DS077AU*1* Downflow 243490 71.36 221780 65.00 10644 2.15
DS077DU*1* Downflow 241099 70.66 215638 63.20 10063 2.1
DS105AS*1* Downflow 328182 96.18 276372 81.00 13111 1.92
DS105AU*1* Downflow 326474 95.68 283878 83.20 13111 1.9
DS105DU*1* Downflow 322035 94.38 270572 79.30 13087 1.9
VS028AD*0* Upflow 105524 30.93 95195 27.90 4210 2.35
VS028AD*1* Upflow 106548 31.23 96218 28.20 4210 2.45
VS028AS*0* Upflow 104499 30.63 94854 27.80 4210 2.52
VS028AS*1* Upflow 105865 31.03 95877 28.10 4210 2.63
VS028AU*0* Upflow 125672 36.83 105090 30.80 4210 2.31
VS028AU*1* Upflow 126697 37.13 106113 31.10 4210 2.4
VS028DD*0* Upflow 104841 30.73 94854 27.80 4210 2.32
VS028DD*1* Upflow 106207 31.13 95877 28.10 4210 2.42
VS028DU*0* Upflow 125331 36.73 104748 30.70 4210 2.29
VS028DU*1* Upflow 126355 37.03 105772 31.00 4210 2.37
VS035AD*0* Upflow 120550 35.33 108843 31.90 4976 2.21
VS035AD*1* Upflow 122599 35.93 110890 32.50 4976 2.35
VS035AS*0* Upflow 127721 37.43 103042 30.20 4976 2.17
VS035AS*1* Upflow 126697 37.13 112937 33.10 4976 2.49
VS035AU*0* Upflow 126697 37.13 111914 32.80 4976 2.3
VS035AU*1* Upflow 128746 37.73 113961 33.40 4976 2.44
VS035DD*0* Upflow 119867 35.13 110208 32.30 5263 2.16
VS035DD*1* Upflow 121916 35.73 110208 32.30 4976 2.31
VS035DU*0* Upflow 126014 36.93 113278 33.20 5263 2.24
VS035DU*1* Upflow 128063 37.53 113278 33.20 4976 2.4
VS042AD*0* Upflow 135234 39.63 122491 35.90 5933 2.01
VS042AD*1* Upflow 138649 40.64 125903 36.90 5933 2.19
VS042AS*0* Upflow 135917 39.83 122832 36.00 5933 2.13
VS042AS*1* Upflow 139332 40.84 126244 37.00 5933 2.33
VS042AU*0* Upflow 143430 42.04 126585 37.10 5933 2.05
VS042AU*1* Upflow 146845 43.04 129997 38.10 5933 2.23
VS042DD*0* Upflow 130795 38.33 121808 35.70 6029 1.99
VS042DD*1* Upflow 137625 40.34 125220 36.70 5933 2.15
VS042DU*0* Upflow 142747 41.84 125903 36.90 5933 2.01
VS042DU*1* Upflow 145821 42.74 129315 37.90 5933 2.18
Table 89 U.S. DOE performance table—Liebert DS upflow and downflow, air-cooled (continued)
Total Cooling Capacity Sensible Cooling Capacity
Basic Model Airflow
Number Configuration Btu/hr kW Btu/hr kW CFM SCOP
VS053AD*0* Upflow 186118 54.55 172988 50.70 7656 2.45
VS053AD*1* Upflow 186801 54.75 173671 50.90 7656 2.47
VS053AS*0* Upflow 192606 56.45 176400 51.70 7656 2.45
VS053AS*1* Upflow 193289 56.65 177083 51.90 7656 2.48
VS053AU*0* Upflow 184410 54.05 171965 50.40 7656 2.49
VS053AU*1* Upflow 184752 54.15 172647 50.60 7656 2.52
VS053DD*0* Upflow 184752 54.15 171624 50.30 7656 2.37
VS053DD*1* Upflow 185776 54.45 171624 50.30 7656 2.47
VS053DU*0* Upflow 182703 53.55 170600 50.00 7656 2.41
VS053DU*1* Upflow 184069 53.95 172647 50.60 7656 2.43
VS070AD*0* Upflow 230513 67.56 207450 60.80 9187 2.16
VS070AD*1* Upflow 231537 67.86 208473 61.10 9187 2.2
VS070AS*0* Upflow 235635 69.06 209838 61.50 9187 2.18
VS070AS*1* Upflow 236660 69.36 210862 61.80 9187 2.21
VS070AU*0* Upflow 220609 64.66 202332 59.30 9187 2.26
VS070AU*1* Upflow 221634 64.96 203355 59.60 9187 2.3
VS070DD*0* Upflow 229147 67.16 205744 60.30 9187 2.11
VS070DD*1* Upflow 230171 67.46 206767 60.60 9187 2.15
VS070DU*0* Upflow 219243 64.26 200967 58.90 9187 2.21
VS070DU*1* Upflow 220268 64.56 201990 59.20 9187 2.25
VS077AS*0* Upflow 253052 74.17 223486 65.50 9953 1.99
VS077AS*1* Upflow 254076 74.47 224510 65.80 9953 2.02
VS077AU*0* Upflow 243490 71.36 219050 64.20 9953 2.05
VS077AU*1* Upflow 244514 71.66 220210 64.54 9953 2.08
VS077DU*0* Upflow 241441 70.76 217003 63.60 9953 2
VS077DU*1* Upflow 243148 71.26 215980 63.30 9570 2.05
VS105AS*0* Upflow 328865 96.38 277054 81.20 13111 1.84
VS105AS*1* Upflow 329548 96.58 275007 80.60 12633 1.87
VS105AU*0* Upflow 326474 95.68 276031 80.90 13111 1.81
VS105AU*1* Upflow 324425 95.08 273984 80.30 12633 1.84
VS105DU*0* Upflow 322376 94.48 272278 79.80 13111 1.79
VS105DU*1* Upflow 325108 95.28 269548 79.00 12250 1.81
Table 90 U.S. DOE performance table—Liebert DS upflow and downflow, water-cooled (continued)
Total Cooling Capacity Sensible Cooling Capacity
Basic Model Airflow
Number Configuration Btu/hr kW Btu/hr kW CFM SCOP
VS035WD*1* Upflow 129087 37.83 114643.2 33.60 5078 2.72
VS035WS*0* Upflow 122940 36.03 110548.8 32.40 5078 2.85
VS035WS*1* Upflow 124989 36.63 112596 33.00 5078 2.94
VS035WU*0* Upflow 130794.5 38.33 114643.2 33.60 5078 2.75
VS035WU*1* Upflow 132843.5 38.93 116349.2 34.10 5078 2.93
VS042WD*0* Upflow 142747 41.84 127267.6 37.30 6054 2.386
VS042WD*1* Upflow 146162 42.84 130679.6 38.30 6054 2.62
VS042WS*0* Upflow 126696.5 37.13 126585.2 37.10 6054 2.526
VS042WS*1* Upflow 144796 42.44 129656 38.00 6054 2.78
VS042WU*0* Upflow 150260 44.04 130679.6 38.30 6054 2.41
VS042WU*1* Upflow 153675 45.04 134091.6 39.30 6054 2.64
VS053WD*0* Upflow 202851 59.45 177082.8 51.90 7812 3.07
VS053WD*1* Upflow 203534 59.65 177424 52.00 7812 3.11
VS053WS*0* Upflow 204558.5 59.95 177765.2 52.10 7812 3.066
VS053WS*1* Upflow 205241.5 60.15 178106.4 52.20 7812 3.1
VS053WU*0* Upflow 197728.5 57.95 174353.2 51.10 7812 3.05
VS053WU*1* Upflow 198411.5 58.15 174694.4 51.20 7812 3.09
VS070WD*0* Upflow 249295 73.06 211544 62.00 9374 2.69
VS070WD*1* Upflow 250319.5 73.36 212226.4 62.20 9374 2.73
VS070WS*0* Upflow 252368.5 73.96 213250 62.50 9374 2.7
VS070WS*1* Upflow 253734.5 74.37 213932.4 62.70 9374 2.74
VS070WU*0* Upflow 240416 70.46 207108.4 60.70 9374 2.71
VS070WU*1* Upflow 241440.5 70.76 207790.8 60.90 9374 2.76
VS077WS*0* Upflow 274566 80.47 228945.2 67.10 10156 2.51
VS077WS*1* Upflow 276273.5 80.97 229968.8 67.40 10156 2.56
VS077WU*0* Upflow 267394.5 78.37 225533.2 66.10 10156 2.49
VS077WU*1* Upflow 268760.5 78.77 226215.6 66.30 10156 2.53
VS105WS*0* Upflow 348330 102.09 286266.8 83.90 12890 2.29
VS105WS*1* Upflow 349013 102.29 283537.2 83.10 12890 2.32
VS105WU*0* Upflow 345256.5 101.19 285925.6 83.80 12500 2.29
VS105WU*1* Upflow 345256.5 101.19 282854.8 82.90 12500 2.29
Table 91 U.S. DOE performance table—Liebert DS upflow and downflow, water-cooled with a fluid
economizer
Total Cooling Capacity Sensible Cooling Capacity
Basic Model Airflow
Number Configuration Btu/hr kW Btu/hr kW CFM SCOP
VS028*U*1* Upflow 130111.5 38.13 108160.4 31.70 4297 2.86
VS028*U*0* Upflow 128745.5 37.73 107136.8 31.40 4297 2.75
VS028*D*1* Upflow 109280 32.03 97924.4 28.70 4297 2.94
VS028*D*0* Upflow 108255.5 31.73 96900.8 28.40 4297 2.82
VS035*U*1* Upflow 132160.5 38.73 116008 34.00 5078 2.88
VS035*U*0* Upflow 130111.5 38.13 114302 33.50 5078 2.71
VS035*D*1* Upflow 129087 37.83 113960.8 33.40 5078 2.67
VS035*D*0* Upflow 126355 37.03 112254.8 32.90 5078 2.52
VS042*U*1* Upflow 152650.5 44.74 133068 39.00 6054 2.56
VS042*U*0* Upflow 149577 43.84 129997.2 38.10 6054 2.37
VS042*D*1* Upflow 145137.5 42.54 129314.8 37.90 6054 2.54
VS042*D*0* Upflow 142064 41.64 126585.2 37.10 6054 2.34
VS053*U*1* Upflow 197728.5 57.95 174012 51.00 7812 3.02
VS053*U*0* Upflow 195679.5 57.35 172306 50.50 7812 2.91
VS053*D*1* Upflow 202509.5 59.35 176400.4 51.70 7812 3.05
VS053*D*0* Upflow 200802 58.85 175035.6 51.30 7812 2.93
VS070*U*1* Upflow 240074.5 70.36 206426 60.50 9374 2.68
VS070*U*0* Upflow 238708.5 69.96 205743.6 60.30 9374 2.64
VS070*D*1* Upflow 248953.5 72.96 210861.6 61.80 9374 2.66
VS070*D*0* Upflow 247587.5 72.56 210179.2 61.60 9374 2.62
VS077*U*1* Upflow 266370 78.07 222121.2 65.10 9765 2.49
VS077*U*0* Upflow 265345.5 77.77 223486 65.50 9765 2.42
VS105*U*1* Upflow 345256.5 101.19 278419.2 81.60 12500 2.24
DS028*U*1* Downflow 130794.5 38.33 109184 32.00 4210 3.06
DS028*U*0* Downflow 128404 37.63 106795.6 31.30 4210 2.82
DS028*D*1* Downflow 110646 32.43 99289.2 29.10 4210 3.2
DS028*D*0* Downflow 108255.5 31.73 96900.8 28.40 4210 2.92
DS035*U*1* Downflow 133185 39.03 117031.6 34.30 4976 3.09
DS035*U*0* Downflow 129428.5 37.93 113278.4 33.20 4976 2.74
DS035*D*1* Downflow 129428.5 37.93 115325.6 33.80 4976 2.86
DS035*D*0* Downflow 126013.5 36.93 111572.4 32.70 4976 2.55
DS042*U*1* Downflow 153675 45.04 134774 39.50 5957 2.72
DS042*D*1* Downflow 146162 42.84 131362 38.50 5957 2.7
DS053*U*1* Downflow 198753 58.25 175376.8 51.40 7714 3.23
DS053*U*0* Downflow 195338 57.25 168552.8 49.40 7177 3.06
DS053*D*1* Downflow 203534 59.65 177765.2 52.10 7714 3.25
DS053*D*0* Downflow 200119 58.65 170941.2 50.10 7177 3.07
DS070*U*1* Downflow 240416 70.46 207449.6 60.80 9277 2.82
DS070*U*0* Downflow 235635 69.06 198578.4 58.20 8613 2.65
DS070*D*1* Downflow 249295 73.06 211544 62.00 9277 2.79
DS070*D*0* Downflow 244514 71.66 203014 59.50 8613 2.62
DS077*U*1* Downflow 266711.5 78.17 224850.8 65.90 9998 2.56
1.0 General
1.1 SUMMARY
These specifications describe requirements for a Thermal Management system. The system shall be
designed to control temperature and humidity conditions in rooms containing electronic equipment,
with good insulation and vapor barrier. The manufacturer shall design and furnish all equipment to
be fully compatible with heat-dissipation requirements of the room.
1.3 SUBMITTALS
Submittals shall be provided with the proposal and shall include: Single-Line Diagrams;
Dimensional, Electrical, and Capacity Data; Piping and Electrical Connection Drawings.
2.0 Product
2.1 FRAME
The frame shall be MIG welded, formed sheet metal. It shall be protected against corrosion using the
autophoretic coating process. The frame shall be capable of being separated into three parts in the
field to accommodate rigging through small spaces.
2.1.1 Downflow Air-flow Configurations
2.1.1.1 Downflow Air Supply
The supply air shall exit from the bottom of the unit.
2.2 FILTERS
For Downflow units, the filter chamber shall be located within the cabinet, and filters shall be
removable from the top of the unit. Filters shall be arranged in a flat bank configuration.
For Upflow units, the filter chamber shall be located within the cabinet, and filters shall be removable
from the front or rear of the unit. Filters shall be arranged in a horizontal bank configuration.
2.2.1 Filters, 4-in. MERV8 or MERV11
Filters shall be deep pleated 4-in. filters with an ASHRAE 52.2 MERV8 rating (45% ASHRAE 52.1) or
ASHRAE 52.2 MERV11 rating (60-65% ASHRAE 52.1).
2.2.1 Filters, 2-in. MERV8 Pre-Filter With 2-in. Filter MERV11
Filters shall be 2-in. ASHRAE 52.2 MERV8 (45% ASHRAE 52.1) pre-filter, with 2-in. ASHRAE 52.2
MERV11 (60-65% ASHRAE 52.1) efficiency filter.
2.2.2 Extra Filter Set
____ extra set(s) of filters shall be provided per system.
2.4.1.1 Motor
The fan motor shall be ____ hp (kW) at 1750 rpm @ 60Hz (1450 rpm @50Hz), mounted to an
automatic, spring-tensioning base. The motor shall be removable from the front of the cabinet.
2.5 HUMIDIFIER
A humidifier shall be factory-installed inside the unit. Bypass air slots shall be included to enable
moisture to be absorbed into the air stream. The humidifier capacity shall be ____lb./hr (kg/hr). The
humidifier shall be removable from the front of the cabinet.
2.5.1 Infrared Humidifier—Optional
The humidifier shall be of the infrared type, consisting of high-intensity quartz lamps mounted above
and out-of the water supply. The humidifier pan shall be stainless steel and arranged to be removable
without disconnecting high-voltage electrical connections. The complete humidifier section shall be
pre-piped, ready for field connection to the water supply. The humidifier shall be equipped with an
automatic water-supply system and shall have an adjustable water-overfeed to prevent mineral
precipitation. A high-water detector shall shut-down the humidifier to prevent overflowing. A 1 in.
(24 mm) air-gap shall prevent back-flow of the humidifier supply water.
2.5.1 Steam Generating Canister Humidifier—Optional
A canister-type steam canister shall be factory-installed in the cooling unit and shall be controlled by
®
the Liebert iCOM control system. It shall be complete with disposable canister, all supply and drain
valves, steam distributor and electronic controls. The need to change the canister shall be indicated
on the Liebert iCOM display. System shall automatically fill and drain as well as maintain the
required water level based on conductivity The humidifier shall be designed to operate with water
conductivity from 200 to 500 micro-ohms. An air-gap within the humidifier assembly shall prevent
back-flow of the humidifier supply water.
2.6 REHEAT
The environmental control unit shall include a factory-installed reheat to control temperature during
dehumidification.
2.6.1 Three-Stage Electric Reheat—Optional
The electric reheat coils shall be low watt density, 304/304 stainless steel fin tubular construction,
protected by thermal safety switches, shall be ____ kW (____ BTUH) controlled in three stages. The
reheat elements shall be removable from the front of the cabinet.
2.6.1 SCR Electric Reheat—Optional
The electric reheat coils shall be low watt density, 304/304 stainless steel fin tubular construction,
protected by thermal safety switches, ____ kW (____ BTUH) controlled by multiple pulses to achieve
tight temperature control. The reheat elements shall be removable from the front of the cabinet.
2.6.1 Hot Water Reheat
The hot water reheat coil shall have copper tubes and aluminum fins with a capacity of ____ BTUH
(kW) when supplied with ____ °F (°C) entering water temperature at ____ GPM (l/s) flow rate.
Maximum pressure drop shall be ____ psi (kPa). The hot water reheat control system shall be factory
pre-piped with a two-way modulating control valve and cleanable Y-strainer.
3.0 CONTROLS
3.1 LIEBERT ICOM®
MICROPROCESSOR CONTROL WITH 9-INCH COLOR TOUCHSCREEN
The Liebert iCOM shall be microprocessor-based with a 9-in. color touchscreen display and shall be
mounted in an ergonomic, aesthetically pleasing housing. The display and housing shall be viewable
while the front panel is open or closed. The controls shall be menu-driven. The system shall display
user menus for active alarms, event log, graphic data, unit view/status overview (including the
monitoring of room conditions, operational status in percentage of each function, date and time), total
run hours, various sensors, display setup and service contacts. A password shall be required to make
system changes. Service menus shall include setpoints, standby settings (lead/lag), timers/sleep
mode, alarm setup, sensor calibration, maintenance/wellness settings, options setup, system/network
setup, auxiliary boards and diagnostics/service mode.
• Password Protection - The Liebert iCOM shall contain two unique passwords to protect against
unauthorized changes. An auto hide/show feature shall allow the user to see applicable
information based on the login used.
• Unit Backup/Restore - The Backup function saves a copy of the settings in a file based on the
system name assigned during startup. The backup can be used to restore only the unit where it
was created and serve as a recovery if a display fails. The backup file includes network settings,
the unit name, panel configuration and other details specific to the Liebert iCOM display. The
Restore function copies the backup settings file to a Liebert iCOM/display so that it functions
exactly as it did before the unwanted change or as it did on the Liebert iCOM that was replaced.
• Unit Export/Import - The Export function makes a copy of the settings from the Liebert iCOM
display that may be stored on a local disk or USB drive. The settings may be imported to a second
Liebert iCOM, resulting in two systems with identical display properties. The Liebert iCOM will
automatically recognize USB drives and display them in the relevant screens. Multiple backup
files may be put on the same USB drive as long as each system name is unique. The Import
function allows previously exported settings files to be loaded to a second Liebert iCOM. This
allows display settings, including panel configurations and custom labels, to be copied from one
display to another.
• Parameter Download - The Liebert iCOM shall enable the user to download a report that lists
parameter names, factory default settings and user programmed settings in .csv format for
remote reference.
• Parameter Search - The Liebert iCOM shall have search fields for efficient navigation and
parameter lookup.
• Parameter Directory - The Liebert iCOM shall provide a directory that lists all parameters in
the control. The list shall provide Line ID numbers, parameter labels, and current parameter
values.
• Setup Wizards - The Liebert iCOM shall contain step-by-step tutorials or wizards to provide
easy setup of the control.
• Context-Sensitive Help - The Liebert iCOM shall have an on-board help database. The
database shall provide context-sensitive help to assist with setup and navigation of the menus.
• Display Setup - The user shall be able to configure the display information based on the specific
user’s preference. Language, units of measure, screen contrast, home screen layout, back-light
timer and the hide/show of certain readouts shall be configurable through the display.
• Additional Readouts - The display shall enable the user to configure custom widgets on the
main screen. Widget options will include items such as fan speed, call for cooling, call for free-
cooling, maintenance status, call for hot water reheat, call for electric reheat, call for
dehumidification, call for humidification, airflow, static pressure, fluid flow rate and cooling
capacity.
• Status LED’s - The Liebert iCOM shall show the unit’s operating status using an integral LED.
The LED shall indicate if the unit has an active alarm; if the unit has an active alarm that has
been acknowledged; or if the unit is On, Off or in standby status.
• Event Log - The Liebert iCOM shall automatically store the last 400 unit-only events (messages,
warnings, and alarms).
• Service Contact Information - The Liebert iCOM shall be able to store the local service or
sales contact information.
• Upgradeable - Liebert iCOM upgrades shall be performed through a USB connection.
• Timers/Sleep Mode – The menus shall allow various customer settings for turning the unit On
or Off.
• Menu Layout - The menus shall be divided into two main menus: User and Service. The User
screen shall contain the menus to access parameters required for basic unit control and setup.
The Service screen shall be designed for service personnel and shall provide access to advanced
control setup features and diagnostic information.
• Sensor Calibration - The menus shall allow unit sensors to be calibrated with external sensors.
• Maintenance/Wellness Settings - The menus shall allow reporting of potential component
problems before they occur.
• Options Setup - The menus shall provide operation settings for the installed components.
• Auxiliary Boards - The menus shall allow setup of optional expansion boards.
• Various Sensors: The menus shall allow setup and display of optional custom sensors. The
control shall include four customer accessible analog inputs for field-supplied sensors. The analog
inputs shall accept a 4 to 20mA signal. The user shall be able to change the input to 0 to 5VDC or
0 to 10VDC. The gains for each analog input shall be programmable from the front display. The
analog inputs shall be able to be monitored from the front display.
• Diagnostics/Service Mode - The Liebert iCOM control shall be provided with self-diagnostics to
aid in troubleshooting. The microcontroller board shall be diagnosed and reported as pass/not
pass. Control inputs shall be indicated as On or Off at the front display. Control outputs shall be
able to be turned On or Off from the front display without using jumpers or a service terminal.
Each control output shall be indicated by an LED on a circuit board.
3.2 ALARMS
All unit alarms shall be annunciated through both audio and visual cues, clearly displayed on the
screen, automatically recorded in the event log and communicated to the customers Building
Management System/Building Automation System. The Liebert iCOM control shall activate an
audible and visual alarm in event of any of the following conditions:
• High Temperature
• Low Temperature
• High Humidity
• Low Humidity
• EC Fan Fault
• Change Filters
• Loss of Air Flow
• Loss of Power
• Compressor Overload (Optional)
• Humidifier Problem
• High Head Pressure
• Low Suction Pressure
• Custom Alarms
Custom alarm inputs shall be provided to indicate facility-specific events. Custom alarms can be
identified with programmable labels. Frequently used alarm inputs include:
• Leak Under Floor
• Smoke Detected
• Standby Unit On
Each alarm (unit and custom) shall be separately enabled or disabled, selected to activate the
common alarm and programmed for a time delay of 0 to 255 seconds.
6.0 Execution
6.1 INSTALLATION OF THERMAL MANAGEMENT UNITS
6.1.1 General
Install Thermal Management units in accordance with manufacturer’s installation instructions.
Install units plumb and level, firmly anchored in locations indicated and maintain manufacturer’s
recommended clearances.
6.1.2 Electrical Wiring
Install and connect electrical devices furnished by manufacturer but not specified to be factory-
mounted. Furnish copy of manufacturer’s electrical connection diagram submittal to electrical
contractor.
6.1.3 Piping Connections
Install and connect devices furnished by manufacturer but not specified to be factory-mounted.
Furnish copy of manufacturer’s piping connection diagram submittal to piping contractor.
6.1.4 Supply and Drain Water Piping
Connect water supply and drains to air-conditioning unit. Provide pitch and trap as manufacturer's
instructions and local codes require.