Академический Документы
Профессиональный Документы
Культура Документы
\'
i .,),if'i:Jl::iH/1!'iri I
!,' : ! \ 'w ;~U :';g')'i 1 1 i"
I I; Th~!~ra(li~~offine aggregate, when determined by a test according to Clause 3 above, shall be within the limits of
; on~;q[i~e,{~r,~,ding zones given in Table 2, except that a total tolerance of up to 5 % may be applied to the
per~en,tages!gi~en in light type. This tolerance may be split up; for example, it could be 1 % on each of three
, Th~fin~!.a~regate shall be described as fine aggregate of the grading zone into which it falls, e.g. BS 882,
9rad\~8,'~~R;~J
. :;, ,.,
. ')';,~ ~'d
NOTE.:' [t' islintended that individual zones should not be specified in contract documents relating to concrete; the concrete
mixes should be modified to make the best use of the materials readily available.
~ . 'I
, ,) I Zone 1 Zone 2
Zone 3 Zone 4
,!,i'! i
mm 'I
i
i;,: ,
"
10.0 100 100 100 100 \.,../'
5.00 I :
I' il t': 96-100 90-100 90-100 95-100
2.36 i
60-95 75-100 85-100 95-100
I
, I "
i
:;~l,j!l!l!i!I~I
,150'ii>+r ir
15-34
5-20
,
35-59
8-30
~60-79
12-40
80-100
15-50
': I 0-10* 0-10*
0-10* 0-15*
" 'rd~':!~'~,f11t!!
" 1'~ ..
H.' !:i" '!
"I'
• For crushed stone sands, the permissible limit is increased to 20 %. The 5 % tolerance permitted by 5.2 may, in addition, be
':: i~j:Fiii':!
NOTE; The commonly used proportions of one part of fine aggregate to two parts of coarse aggregate, i.e. a fine aggregate
; percentage'of about 33 % by weight of the total aggregate, are not always the most suitable for making concrete of high strength
. andgooddui.,bility.
. ! To 'makci:co'ncreteof the best quality with the range of aggregates alJo,,"ed,the mix should be suitably designed and the
proportion 'of fine aggregate in the mix should be reduced as the fine aggregate grading becomes finer.
For example, in an investigation using an irregular shaped gravel of 20 mm 'maximum size and a natural sand, concrete mixes of
, , 1 : 6'proportion by weight were found to require the same water/cement ratio and to have the same workability and strength, when
- the sand was graded to lie in the middle of Grading Zones 1,2,3 and 4, if the sand contents were approximately 45, 35, 30 and
- 25"tiiweight respectively.- _ .
The most suitable proportion of fine aggregate to be used for a particular cement/aggregate ratio will, however, depend on the
actual grading,.the particle shape and the surface texture of both the fine and the coarse aggh:gates. In particular, the Correct design
. of the mix becomes increasingly important as the grading of the fine aggregate approaches the coarser limit of Grading Zone 1 or
the finer limit of Grading Zone 4. The suitability of a given fine aggregate for use with the available coarse aggregate should always
I
I
I
!t
I
I
!;
V"'"
6
2.064. Prescribed mix zuo». Suipruue ULLUU\.
~"
- When a prescribed mix is specified the Engineer will specify the mix
proportions and the Contractor shall undertake to provide a proper
For concrete in piles exposed to sulphate attack the requirei.i
Building Research Establishment Digest 174 shall be observcc
,
be not less than 400 kg/m',
The cement content in any mix shall not exceed 550 kg/tp.3~
;l~,
i"pl~" pm""
Table 2. Prescribed mixes for piling
-
Concrete
grade I
Nominal maximum
size of aggregate, mm . 40 20 ", iIi~:
Table 3. Prescribed mixes
. . ' , '... --'
·ror.."cast
,;, " " .'
using only gravel alii"
. . .
i 410 460
30 Cement, kg/rrr' 370 390 400 430 30 Cement, kg/rrr' I
Total aggregate, kg/m' 1750 1700 1700 I 1650 Total aggregate, kg/m' 1750 1680
- \
Sand/total aggregate: zone 1 35% 40% 40% 45% Sand/total aggregate: zone 1 40%
zone 2 30% 35% 35% 40% zone Z 35% 40%
I vone 3 I
I 30% 30% 30% 35% I
I
zone 3 32% 35%
Notes.
I. If the specific gravity of either the coarse or the fine aggregate differs significantly from 2,6, Votes.
I. This table is based on the use of gravel aggregates, and is not applicable to c'
the weight of each type of aggregate shall be adjusted in proportion to the specific gravity of the
materials. aggregates.
2. If the specitlc gravity of either the coarse or the fine aggregate differs signific?n·'
2. If a crushed stone sand or a crushed gravel sand is used instead of natural sand the weight of
the coarse aggregate shall be reduced by at least 90 kg without alteration to the weight of sand or the weight of each type of aggregate shall be adjusted in proportion to the specific ~
cement. materials.
3. The cement shall be ordinary Portland cement or sulphate-resisting Portland Co'
J. The cement shall be ordinary Portland cement or sulphate-resisting Portland cement. Where
other cements listed in clause 2.021 are used, special consideration shall be givento the design of other cements listed in clause 2.021 are used, special consideration shall be given tc
the mix. the mix.
4. The weights of cementand dry aggregates are those whichwill produce approxima
4. The weights of cement and dry aggregatesare those which will produce approximatelyone cubic
metre of compacted concrete, metre of compacted concrete.
64 , ~ ~
)
,
-s , ,
III !ilM'\'Ul!IIfJ
TABLE 7.8
:-ea5e of.strengllJ,with.tlme l< .. ,. 'i::
•• -c :
Coe fficient Po
.
'
~.<~ ,. ..
'. " , . .." :. ~
.... -..
.' , ...'
,',
3.6r-·--r--.......---r------,----.---..---r~'7"_.
,~,- "
60
I.
c
.'
.~ .k p'
.~
j
50
-.'~J;)
'. .~~~ ,
~~
..,;
.\
3Dt---'--'+ --+--- --t----"+---I----+--,,,e-:>'f---,,,e--1
40
G. &1 ,., »>
,.
Lb.()'./', ,
.. ..
",
,
2.01-'--+---+----\---+-h.£+::r--7'!'~"~t_'_~
30
.7 ] .: .i-> . ";" . .
,."
/~
, ';: <:;}~~< .. ~ ~
20, .7"~
~~
,....
"
.
~
<
'<r'
.t::: :5::<'-.
.'
r
.•
'
".
.,
,."
?
;
..
~
",
io
7 28 2 ~ 6 1
., Creep multiplier
~,'ri~ti~~ ormodJusor'el~~ti~t~; ';;t~'~t;~:1gth , :' ::CI.2ll
I II
'~ J~~sJ'Y,c~r con.~rtte.· _, , ••
~
I '"IV
'.', ~/" ". - .,;
0.22
i I /.,/.(
,
0,2' t
U
I /,
I i i/
0.2t I '~~
;,r.:
/,
D.2a , ~§,,- I I 1/
~''v/ ~j'
~ct'/; '/ 'L" ~1~ I i7
1/
/'' v . /1./1~
'c/> ,.
~."
1/ V '/
'tP, A1P_fI. .. I
. '. , .
'.
~~ I.o"V ".
.' ,....
-"':" III
"
."
" "'" -" ,I I,
;
"'~ 'i I
D.K"''''' of I<:od ,,~-;
'" 0
"
;u Concrete
Nom. max, agg. size (mm) 40 ~~
20 • 14 I 10.
hi~_~i~_
E grade
t Workability medium nigh medium
'O"~ .... ,' . .. ,.. ',' .'
:: . i;'; .':: ;~"otalaggregate';(kg), . '.' , -. )05, 2S5 220
265
35
240
40
45
t-40.:
(,:'35 .~,':
. 0.146
220
45
. .; 50';
::6'; ~
;0.130
195
50
f . 25 Zone 2 (%)
30 35 40
45
Co Zone 3 (%)
30 30 35
40
.
:: '
E
, Vol. or finished concrete (m J )
0.147 0.137 0.130 0,118
.t: .,,·Tolalaggregate(kg)
..
30
:.. "" -. Zone,3 (%)
1lo,:':V'ot.brlinished concrete (m J )
.
, .
Sand:.~~~: ~ ~:~ .
,0.134'
235
:~30 5
215 <'210190
:3°55
0.115
170
r05
0.106
Pr.rccntages are by weight or fine agg~cgate in weight or total dry:aggregates. Volumes cirfinished concrete are approximate only.
: ....
. -i'· .. '
\
-;\
"."-.;.'
\
\ .
~ .
Ijm~
.. - ;~~Ur':-:~~h;':'~
ul\zAv[3L. <S.f;N0 I IJ\JA~ 2 \":::l... i ) llA fo' r
\0 .,,""
2.0 ...... "'" I
I
L>T
I
.2- 5""0 S?-6 5"rt I
!
. 2-1::0
&i'-' s s, i
2lC'
v
ii
L.. -15" 2'f uz: Z. 0' [t c ')-gI I
\ _ b,,_IOC
! -1.}· S ~ '2. c cr;
. }\
'\ (, I..
'-130 7<l:J
I..i' ;)" Set
't ~r Fey! \lr'?f .... ; L""
.; '"'-:~
!
S' J '$ ::;:75
z: , 5 .. "'- -': z.
"'1 '~J'
'1)C
I fc
.'-H-J'"
i l'-
'-(/;<:; I 9 t-l'
I
--=..-\._. i
'7C>O '-(LfS- 8L 7 18/
-----_.
ti'-t. '15
P;n' .z;
---
z,,'L
C
.-
u,c;+ '2-}
?.!Jc; 7S')
.. I It 0,'
c - '10 '1 be
I
j ac . , f1 ' .;.,:
T be I He ..-'
'J" C f ::t v
I.)
c) 2(D
'...J I
i:)
).
\.J e-"
,
~7
'I
MONENCO
L
~Dear Sir;
Yours truly,
~. E. BITAR
Construction Manager
BDu/cb
Monenco RQra
1 8. N'j'l. 1995 l~i~~.iS~
Ra~ lanuf 01 all1 &as Processlng CompleX ErL..K;;; . jWI 3 .hA.;J1 (L:.;:t j,..~ I)"'ij ~
.- ~ ".':; v:-z:';": .: _",- .~,r. ~~. -•. ~I..-"';.: .(.:.. .--: :..--."7""...... ., ..... __ ~ - . --._. __ ._---- .
. ...
---'--- - - - - - -->-
~~~".~~:u_~~. . ~~_\l~{:'i\.":"m~~",.~-!!U!llIIIll""'-, ~tf.Ql~,:~~~.
--'--~'--
MAN
MAN Gutehoffnunqshutte AG 12M ....
~\ II ~:f>~~~f':" tJL
MONENCO AGRA copies to:
Ras Lanuf Oil and Gas Processing Complex MAN GHH Project Manager, Gustavsburg
Ras Lanuf, Libya RASCO Manager of Projects, Ras Lanuf
Office File
Construction Manager
Dear Sir,
'''-"' Please find attached copies of three laboratory Concrete Compression Test result sheets of
the nine cubes crushed on the morning of Thursday the 09th of November 1995. The tests
were witnessed by representatives of Rasco, ~J1onel;:':; i.~"'I\j and J~.c, I'lith all three recor o
sheets b:::irlJ d..', ::]:',:::::l t ; If',;~ ,:;",=:
The results ale preliminary, being seven day c':;--;';J~essi,e strslg~h results, as til'::
specificalion relates to twenty eight day characteristic strenqth re quirernents of 35N/ sq. rnrn.
Nevertheless, the results reveal.
1. AI! seven clay results exce e d t':enty eight clay Ch?-3::er~s:ic streng:h requirements, by an
average of 109 percent.
2. Tr>~ :~'~'C:;J c~-J/ (C:~'..l:~~ 2~:; j''''-: -:~1~··"::; r~ ~ '.':::'-I~'/ =":_1 _ J~ I r,-.,-.ir r c:. '3 ::: · .'~ s·re!:J~h va'ue s n r
approximately 48N/sq. rnrn.
Compliance Requirements
All results satisfy all compliance requirements of BS 5t,)} Para 7: 1978: Para 3.9.2.2 Testing
..... Plan A and Para 3.9.2.3 Testing Plan B; and BS 5320: Pari 4: 1990: Para 3.16.2 (a) and (b).
The latter standard being referenced as the compliance requirements of BS 8110: Part 1:
1985.
To allow us to proceed with the works your early written approval of the 35N/sq. mm. mix
design would be appreciated.
Yours Faithfully.
~~~~.-/\
K. KOZAK W.ALM
Site Representative Deputy Site Representative
B~(~~~\\f1;~'='
.. -. - ,- .
lilJ ~6~5 ~:VJ
:-";~
. :.f)J .3.:.'
MAN GHH, Marsa EI Brega - Libya/S.P.LA.J.
·C·I·J..J. C'( ':::J - ~)I .r:r ..... C .,:.L.
Telephor.e (0656) 260713501 • Telex ~544 BREGAl.Y 51 It} . J J J :.4:/. 0' I l.l :.,r-C!: • or 0 • 'In,. v ( .", ) :....;.....
--: .:.::-- ". .
- -~~- --------::--------:---:-------
JOANNOU & PAPASKEVAIDES (0) L I D.,
LIBYA BRANCH
C:;ONTRACT: The Installation of Utilities, Offsites and Inter connecting Facilities
inside Ras Lanuf Complex, Phase" Pacakage 'H'
CLIENT MAIN CONTRACTOR CONSULTANT SUB·CONTRACTOR
RAS·LANUF OIL &
GAS PROCESSING MNJ MONENCO J&P (0) L TO
CO. INC.
SC'URCE:
S~·}S'LE tJU:,IC:ER.
rc:O"~CR[TE CU\SS
1-:-, ',':Jl,E TYPF
- - --- -
[. . - (.,.,e
j LI. '_' D....
'"::)'''Ir: -.
TE ~
- --~--
I·"~-;;·_·; ~ I
I U:'" H\1 ..\ TE CCJ,\i?RESSI\/E
l::; TF:cJ1G TH t j'min' 'h (:'.1-- I '2,~, .;
\~'
0_ U " c:J TEST
i'J~r
80 80 \ 8'~
\
, "-c
/ r----.... 0, /)
) ~)(
C) !U)ljj5 is»:
~~
.e-: DGb(
f~, If
r'
C}) li',Gt;(· (\{ ( )
\.
'~- .
7'-:; I
(-',,
~;; , - ' - '
L / c-'
04TE ./Tt':S~EO 8( CHECKED 8.l Ei·~G. REPRESEN.~tATv.:·=
CLIENT USE:
~V~
-" -- .
bflS( Q '-'~'imrt{
DATE REVIEWC:D 8'( ENGINEER' rACEPTt REJECT
--: :::~-::::
i:~fi;i1i%tmifu~~'£imiN;;i._:'jl:;;<~~~"'·:::;---'~~-'~·"'_iiiiai2wi~:iv.:::kw~-?,~::
JOANNOU & PARASKEVAIDES (0) LTD.,
'.
LIBYA BRANCH
CONTRACT: The Installation of Utilities, Offsites and Inter c onne ctinq Facilities
inside Ras Lanuf Complex, Phase II Pacakage 'H'
I
CLIENT MAIN CONTRACTOR CONSULTANT I SUS - CONTRACTOR
RAS·LANUF OIL t:
GAS PROCESSING MAN MONENCO J&P (0) LTO
CO. INC.
U\80iV\ TORY No
-
;1\ 2
~
r,~.~ r> LE No. \~\,(:\S'"., (V-'~ \ ') 8(;/8 BcGu 8U~U I
co~
_.
::::RETE : CLASS
L- :r-) c.
_.1 r {; cz:: r- l=G-'-, --, r: :
' "
,- _,
_~~I..:::h--J~ _ _ _ _ --~--~--
SU.~?L1t!G Dl,TE '2- \\- (\5. .2-\\<,~S ')- \\- ~\5 -----
I--.j,".,,'~·Lt: "f\t.h
(' • I • '"'"\' r- .. -- ..
ri 1rn :' I" JI"C"'Jr)~)1
:I "2~-d~C)()\.l-::/ _.
I
r -":~r?SS~~.~l l_O'~ yrJ (-: fr,
l.. I ... _
, P (' r
_ '-- '-- I
9 L, (
_ • _
I
I
---- I
t=.~ . . .
-"',---'-.
UL TI~,'u,TE Cm:iPRESSIVE
r\ -: C:. \', G~':-:::". i
I
::;LU.\iP TEST ~JiM B7 B --1- 87
'\L11d'155
DATE
CLIENT USE:
DATE REVIEWED BY
.. ~_.~._---
LIBYA BRANCH ~-
-- I
GAS PROCESSING
MAN MONENCO
J&P (0) LTD
CO. INC.
I
L/,80Rf\ TOR'l' i h
__
.. ... 1\ 0 '\ 1
1
~!\MPLE r-Jo.
III f\ So,"'-, \y-'s. ·d 8c ,c.: I
I ~ l. ,,-. ) ~)Ul () ,(':'Ci 'S?:J
,TRUCTURE r:8 -r :r\r~L ~ j '-' ~
...
COi lCRETE . CLASS
~~
~
-
C"~ 0-,~,~ ~ -
Sr.r.1?LE TY;:::
------
_______ CU_t C __ ';..:_tL~) ["_L/ iJ r~ E I ----_.
'\-\'·-')~ls-\\·'J::,I~'J-\\·YS[
-
~~~I_l~_'-~I
,7 c.'i:.~J22c/) :,127 co oL__ . . .
1\ T Dp.yS i
,
,;:) ·\~.~?LE t-P::: :. r~. , "1 7 1
I ----- -
I ~~,C-
l_~__-,-------_
\;FISC <' .
~) <--~~'
<1 ~1'5-
REVIEWED BY ENGINEER'S ACCE I EJECT
•• ' ~ :i ~ _~.
, .
ACKnowledgement Copy
M~N
MAN GutehoffnungshOtle AG GH",
~I II L.;~~?:Jr:- 0~
Ras Lanuf Oil and Gas Processing Complex rv1AN GHH Project Manager. Gustavsburg
Dear Sir,
PI-::3:;e find 2~.t3::r,ej copy 0' co,'v::,c;l-:-: graje 35/i,~::,r;:~ ~!;\ p.oportio: 0 21d slump test re su't s
of trial mixes conducted on the morning of Thursday 2nj November 1Sg5
All slump test results are witbin the specification to.erance s. The r ssult sheet has be e n
signed by representatives of Rasco, Monenco, M~N and J&P.
The seven day compressive strength tests will be u .: '2 ita ke n on Tr..:rsday 9th November
r
1995 and subject to their achieving satisfactory values, we assume tne mix design will be an
approved [-;-,j Io: u se \'/it:1i:'1 the p::::m21en t• \'/8,\S
Yours Faithfully,
\J~,,~~
K. KOZAK W.ALM
Site Representative Deputy Site Representative
Attachment(s): As stated.
LE ,t\ r -T.
E i =4OO"t- 0 CY:--, c; -= ~ ~ } 0 0 .t> \'~ (~.... v' ., ~;
>
\
\ (.J"1-. \\. <..\ s~
_ ~fr-~~? __
,
.
(
~
1- L\l
~~
f
,f
,lr rr-:-;
~
, )
::
'-..J
2id- -r~\4C
.I
L
[
r
047 e R- 20 ()' l. (7 /,,/,r 0D> ') z:
t
r Si u (Llp ~ 6 7-rl~l r-,
,
!"
I Nu!VI iQrJ ~ cuJh 1( 1; y
) 1,/ Cr.( (~ {
r
~
-I ~~I ~_~_~~~_-~2
I 'N ~ 1 E:~ 2J'Ju L( 7/hJ) ~ r;)i5 ~ '>.: ""7- L ( T
(V)
I
f 1e,4i /J';i C UJt; 7 O~tVV7y) /_/~-.//,;.r~
, 'Nlot llJ.e.<.:: 4,600)', lJoQ.... o,,€ ' = \4-ooo(cc.) !,/
. 36800-46qO :::3.?~OO -= 2.-~ d:)Ch7~o;» ,/rr?
:- \ ~~~~
.. ~" "-'." 'i' :.,!.+-;{",
' " -: ,''...._.. .
'""::.<....:;._'"'.~.-._,~ ..-.: ...~ .- .
" '·-.A"'.·-·~,
. ",';'';'c'..w.i._ '.', . -. ~~~:: _.,_ ..~".: : .. ' •
;;. ..,..,,,,,-: '..' •. , ...~~?t¥...-'=.-,"; f:o,""'" -..... ,,,. .,,~~.":>.~.c;.(:.,. ';, ,~.: ." -".....
-'. ;~ ...-.•. _.. ~~~:2;~~-
V1 TABLE' 4-6. Typical Uses of Asphalt (after Asphalt Institute)
(j'I
ec
Asphalt Cements Liquid Asphalts
Viscosity Viscosity Rapid Medium Slo\" Emulsified
Graded Graded Penetration CUring Curing CUring
-Original -Residue Graded (RO (MO (SO Anionic Cationic
Type Baaaa
aaaaa o~g
of coo ~ \.00000 aa a_", N N~
, ...c:
-~'"7~~--;;
I __
Construction
":J"N-ltjN
00000
-C::O"'1"N
~~~~~
"'
I .....I - l aI aI a
aaa a
aaa a
aaa
I , V) V) , ,
I
Well-graded aggregate x x x x x x x x x x
*i H--H-f1 ~
Sand x x x x x x x x x
Sandy soil x x x x x x x x x x x x x x
Patching, immediate use x x ~ x x x x x x
~~
Patching, stockpile x x x x
.) )
~,..J.. CD"l4Jf'-
~'-L.L ;",;. L""1-L~A
I ~
Stage Item Reference or Values
calculation
---------------- - - -
l.
t.->
1.2 Standard deviation Fig 3 N/mm' or no data 8 N/mm'
1.3 Margin C1 x .. <if:> =I~~O'-N/mm'
1.4 Target mean strength C2 +/s l..f S N/mm'
1.5 Cement type Specified
1.6 Aggregate type: coarse
-----
Aggregate type: fine
1.7 Free water/cement ratio Table 2, Fig 4
L-.
2.1 Slump orV-B Specified SlumpJ ll. '-;.3 \::) mm orV-B s
2.2 Maximum aggregate size Specified mm.
3
2.3 Free-water content Table 3 kg/m
:luantities Cement (kg) Water (kg or I) Fine aggregate (kg) Coarse aggregate (kg)
3(to
ier m nearest 5 kg)
-----------------------------------------==--------~--.. ,
S
,8 days
per cent
~. Z ..-·,·· .,
~~~
~ .
2 2,1 Slump orV-B Specified .. . . . ..... s
2,2 Maximum aggregate size Specified 2..0 mm.
2.3 Free-water content Table 3 2. 2. r kg/m
3
3
3 3.1 Cement content C3 - kg/m
3
3.2 Maximwn cement cotent Specified kg/m
3
3.3 Minimum cement content Specified .'3~ kg/m ~~
Use if greater than Item 3.1
and calculate Item 3.4
Ouantities Cement (kg) Water (kg or I) Fine aggregate (kg) Coarse aggregate (kg)
3
per m (to nearest 5 kg)
3
per trial mix of m
1"'
1 1.1 Characteristic strength • Specified
-1 Proportion defective
N/mm'at days
per cent
Quantities Cement (kg) Water (kg or I) Fine aggregate (kg) Coarse aggregate (kg)
3(to
per m nearest 5 kg)
,
per trial mix of m
,
\
•
"
.
•• t{
;;".'(
'I~ :
. -~
.1'
..
',
'.
,.'
Concrete mix design form
\
.'
:
I
,
' •
i
1.1 Characteristic strength Specified N/mm'at .,. days
Proportion defective per cent
3
3.1 Cement content C3 kg/m
3
3.2 Maximum cement cotent Specified kg/m
3
3.3 Minimum cement content Specified kg/m Use if greater than Item 3.1
and calculate Item 3.4
Quantities Cement (kg) Water (kg or I) Fine aggregate (kg) Coarse aggregate (kg)
Reference or
calculation Values
----------------------------------------
Characteristic strength
!
Specified
Nlmm'at "'C"
days
1.2 Standard devi~tion
- ~>, .... ,
per cent
.. 1.3 t.1argi~\· .3:" '!'£ , - ~
; Fig 3";'("
,~.~~.- ... ~
1.4 C1
........... , ••••• ' , . , . , •• - ••••
. .. Nlmm' or no data
#
. ; . '."'"; I
Target mean strength k:::: . •.:;,......,....';Nlmm ..
1.5 C2 ......................
x . -; .~ ~ ::S :l ...
Cement type == ,.--Nlmrn
1.6 Specifie~ + ::
Aggregate type: coarse OPCfSRPCfRHPC N1mml
Aggregate type: fine
1.7
Free water/cement ratio
1.8 Table 2, Fig 4
Specified
1- Use the lOwer value 1.~
1.8
Slump orV.B
Specified
MaXimum aggregate size Slump
Specified rnm orV-B 2
Free-water content
s 2.1
Table 3
22 ~
2.3 FI,
~ment content
C3
faximum cementcotCIlt
Specified
'WmU1.ll cement Content
Specified
'" .... kg/m 3
I 3
3.1
Ceme
r
-:ontent 5.1
C5 percent Grading of fine aggre,
1 COntent x 5.2
kglm
3 ProPortion of fine aggn
5.3
3 Fine aggregate content
kglm 5.3
lment (kg) Coarse aggregate conten
Water (kg or I)
Fine aggregate (kg)
Coarse aggregate (kg) Quantities
3
Cement (,
per rn (to nearest 5 kg)
4. Quality of aggregates
Aggregates for 'concrete shall consist of any type of coarse aggregate to be combined with any type of
aggregate, or of ail-in aggregate, all as defined in Clause 2. When an aggregate is to be supplied as a mixture
different sizes or types, it shall be produced in such a way as to ensure thorough mixing of the various
component materials and care shall be taken that the proportions are as consistent as possible from consignme
to consignment. The aggregates shall be hard, durable and clean and shall not contain deleterious materials
such a form or in sufficient quantity to affect adversely the strength at any age or the durability of the con ere
including, where applicable, the resistance to frost and to corrosion of the reinforcement. Examples of su
materials are: clay, particularly as an adherent coating; flaky or elongated particles; mica, shale and 01I
laminated materials; coal and other organic impurities; iron pyrites and soluble sulphate salts such as those
calcium, magnesium and sodium. If there is any reason to suspect the presence of harmful impurities, and unl
evidence of general performance is offered which is satisfactory to the purchaser or his representative, any em
shall be determined by a test according to Clause 3 to compare the strength of concrete cubes made with t
aggregates in question with that of-concrete made with acceptable aggregates. The details of this concrete te
including mix proportions, type of cement, type and grading of reference aggregates, age at test and criterion f
. . , acceptance, shall be agreed between the supplier and the purchaser or between their representatives prior to tl
test.
-, NOTE. No simple tests for the durability and frost resistance of concrete or for corrosion of reinforcement can be applied,
experience of the properties of concrete made with the type of aggregates in question and a knowledge of their source are the
only reliable means of assessment.
Aggregates vary in their shrinkage properties and, when this may be excessive, account should be taken of this
factor. Aggregates also differ in their modulus of elasticity and, where applicable, this should be taken into
consideration. Furthermore, where the appearance of the finished concrete is important, care should be taken to
select a suitable aggregate, for which the only guide is a knowledge of the source and of similar work which has
been carried out with the aggregate in question.
4.2.1 '10 % fines' value. The '10% fines' value, when determined in accordance with BS 812, shall be not less
than 50 kN, Where the purchaser has specified aggregates for concrete wearing surfaces, the '10% fines' value
shall not be less than 100 kN.
4.2_2 Aggregate impact value. As an alternative to the '10 % fines' test, the aggregate impact test in accordance
'" with BS 812 may be carried out. The aggregate impact value shall not exceed 45 %. Where the purchaser has
specified aggregates for concrete wearing surfaces, the aggregate impact value shall not exceed 30 %.
5. Grading
The grading of coarse aggregate, when determined by a test according to Clause 3, shall be within the limits given
in Table I.
BS 410
test sieve
Nominal size of
graded aggregate
Nominal size of
single-sized aggrega tes .
40mm 20mm 14mm 63mm 40mm 20mm 14mm 10mm
to to to
5mm 5mm 5mm
mm
5.00 0-5 v
0-10 O-tO - - 0-5 0-10 0-25
2.36 - - - - - - - 0-5
..
REF NO ;- 2013/98
DATE :-19/05/2013
INFORMATION :- Aggregate testes were carried out for the company as requested by the
* Raslanof :
A- SIEVE ANALYSIS :
~
Passing (% )
]
Aggregate
Aggregate
I Sieve Size (mm) I (B)
( A)
50
37
t 100.0
100.0
-
- I
20 36.05 I
14
10
0.95
- =1 10~'
95.63
------~
4. 75 - I 1.56
2.36 0.79
B SPECIFIC GRAVITY
I~=-J-
Aggregate Aggregate
(A) ( B)
I
I
Test
ls~ ~=======~~~~~ _
Flakness (%)
Moisture content (%)
----l
L
23.57
12.23
1.14
-~-
12.23 -. J
;/l
({~t:)' '.; .
... . 'j~
Elmarkaz Company
<oj.!)
",,~
Concrete mix design for C40 Job title: Maintains of Sewage Water Treatment at Residential City
Refference
Stage Item Values
or Calculation
water/cement content
)PC- Ordinary Po 'ahd cement; SRPC· Sulphate resisting Portland cement; RHPC- Rapid hardening Portland cement
Note: .~,~.ter Content is 190kglm3, By adding Edecrete BVF Which Reduce water content from 10% to 15%
the f.~dative Per M Pentrone Admix CMB Fiber CMB Edecrete BVF
. fr t
; '. t: '<'.
f;:"n.
-}
Kg
9
Kg
0.9
Kg
9
.\
vn
...
' ,~~.
ermarxaz Company
""-I \ .... . S
Concrete mix design for C40 Job title: Maintains of Sewage Water Treatment at Residential City
-~;type
caWH... nt
1.5 Specified SRPC L
OPC· Ordinary Portlarid cement; SRPC· Sulphate resisting Portland cement; RHPC- Rapid hardening Portland cement
Note: f[~e 1I\Ia,ter Content is 190kg/m3, By adding Edecrete BVF Which Reduce water content from 10% to 15%
*
the weil~1'. .a..~.~t.',',',
.. ~rl.i
..
V.
.•' " " rif Pentrone Admix
K K K
CMB Fiber CMB Edecrete 8VF
~ ," '. g g g
_ "~, t; : 9 0.9 9
,(.... ,
~~ ~~1.::_. ~'fi
(~~,,,/~ ..~~\~.s f;.\;~~'
* Ajdabya :
, A- SIEVE ANALYSIS:
I
~ -~'
I
'--'._.
'.
Sample
Passing (% )
J "
t
Aggregate Sand
Sieve Size (mm)~~"""'---- ..
Aggregate
(B) I
(A)
I
50 100.0 I
37 100.0
20 28.91
14 0,16 100,0
10 98,63
4.75
2.36
5.08
I
~:::~~~=j
1.18
0.6 =r
------j
98.51
83.53
0.30 28.40
0.150 I 2.38
B. SPECIFIC GRAVITY
I
~~ Test
Aggregate
(A)
I
Aggregate
(B) l Sand
~~~
Aggregate Aggregate
Test (A) ., (B)
NOTE:
_The company carried out sampling and preparing the tested specimens. Therefore, the UNIVERSITY OF
BENGHAZI ENGINEERING CONSULTING OFFICE is merely responsible for the condition of the tests and for
Reported by ;
EI\G.KHAcED ELGEMBRI(Msc).
c:,:'::':"'::':,:,::.:',:,p.:::':::.::::":;:;;;;""'
BS 882 Part 2 1973
The grading of fine aggregate,when determined by a test according to Clause 3 above, shall be within the limits of
one of the grading zones given in Table 2, except that a total tolerance of up to 5 % may be applied to the
percentages given in light type. This tolerance may be split up; for example, it could be I % on each of three
sieves and 2 % on another, of 4 % on one sieve and I % on another.
The fine aggregate shall be described as fine aggregate of the grading zone into which it falls, e.g. BS 882,
Grading Zone 1.
NOTE. It is intended that individual zones should not be specified in contract documents relating to concrete; the concrete
mixes should be modified to make the best use of the materials readily available.
!
BS 410 Percen tage by weigh t passing BS sieves
test sieve
Grading Grading Grading Grading
Zone I Zone 2 Zone 3 Zone 4
mm
pm
* For crushed stone sands, the permissible limit is increased to 20 %. The 5 % tolerance permitted by 5.2 may, in addition, be
applied to the percentages in light type.
NOTE. The commonly used proportions of one part of fine aggregate to two parts of coarse aggregate, i.e, a fine aggregate
percentage of about 33 % by. weight of the total aggregate, are not always the most suitable for making concrete of high strength
and good durability.
To make concrete of the best quality with the range of aggregates allowed, the mix should be suitably designed and the
proportion of fine aggregate in the mix should be reduced as the fine aggregate grading becomes finer.
For example, in an investigation using an irregular shaped gravel of 20 mm maximum size and a natural sand. concrete mixes of
1 : 6 proportion by weight were found to require the same water/cement ratio and to have the same workability and strength, when
the sand was graded to lie in the middle of Grading Zones 1,2,3 and 4, if the sand contents were approximately 45,35,30 and
25 % by weight respectively.
The most suitable proportion of fine aggregate to be used for a particular cement/aggregate ratio will, however, depend on the
actual grading. the particle shape and the surface texture of both the fine and the coarse aggregates. In particular. the correct design
of the mix becomes increasingly important as the grading of the fine aggregate approaches the coarser limit of Grading Zone 1 or
the finer limit of Grading Zone 4. The suitability of a given fine aggregate for use with the available coarse aggregate should always
be ascertained, this being especially important in respect of reinforced concrete structures.
" )";:11<,~
' ,: •. i:i1if,J
iii\ j
('I COr.c,f'cte Mix DesisV\
ii'iiJti',;;~1
: r;,,+ill~''7i~,peslqll
J ,
(01' COI/1Fl/'csshy' sf"t::ngfh
, J;iJL;,~::I, d,1 . . . .
," : HI,::,.""
~""H '1
:~I 'efective I"ate k=1.64
;ii~ r
,"'l'r"l:'dihal"y Podlahd cemeht
/
:1
~t,!tkl" ~-,<
1,'1 1
!;i!ll~W"i)tljtltl : .
. :[l~i!L!'{'\~:;j!!Hr:i I
-~ L;, \(fHt~..:14r~hi: I
rt::J' A' ~ I~
2
kl Jd:our case no data 5 = 8 corresponding to 30 N/mm strength.
j'-i'itHt,l1 F'Ufij ! ~ ..}l\
·'~"~lm~:f1:'~I:--ri
f,"!' 1 3 ;VIQI .'g111
,nj;!!!"iifo-"~~m. . \ /1 --
Iv, I, - S
K;;' ~1
•.•••• L
~'4'l:';~i r-p ~ii
r~~iil[l~lt:i:!j!~hel"e
'
I
r ,~ '-,'
rf''' )
, /
/ CD
'\10,-,
, .
',S
,:
= stcH'\dw·d deviCltioVl
-,I'
In our lease M = I.G4 x 8 = 13 N/mm 2
- -
Fm-:-fc+M ., .. " C2
~qJ'.
~~Q_
~,
~
Where fm = tClrget stre':'9th
Fc = characteristic stren9th
M = M a r 9 in
~ 6.. Jtem, 1.6 A99re9ate type for coarse .1\99' And fihe A99' This can
" :!;~rv.shed
"'IL L,F·"'"
:
Or LAncrLAshed ClS per B5882/ Part 2
':0' c: 'V'
;;L:F"rt~:: i. ,---/"
" 'l.Inour case: Uncrushed coarse and Fine Aggregates are used.
a- from table 2 find the stre.n~tkvalLA~of m,ix made ,;Ih a free- /",
w"tulcement e"t;o of O.5,¥coed;ng iVspec;f;ed~ ---~~ 1.J·y
i,~ . ,:';6- plot the stren9th valLA'~"obtainedfro~ table 2 on -19 4 and ~raw Cl
,,' ,'I •
. ;:; F;iCLA~Vf parClllel to the printed CLArves LAntil it intercept~ a hori 40ntal line
;. pass,in9 throLA9h(ordinate representin9 the target mean st.. . en9th/ The
, '
.. correspondin9 vClIL-Ie for f,·e.e \\lIe ,'atio can then be 'i'-ecd from the
a6scissCl ,
" ;' ': j
c- compare the valLAe obtClined iVl b with the specified wlc max if any
.at:\d ,v.se the sm'aller vaiL-Ie,
In pur
case: From table 2 for OPC, uncrushed coarse Agg, And an
2
. age. of 28 days, the strc..ngth value IS 40 N/mm
. ,..;;--
\
<to:
~ On figure 4 the value 40 at POint a on the starting line IS found.thls
/ t;' comes exactly on a printed curve (No need for draWing a ne'w curve
~ as stated In b above), move to POint B where the printed (or
I ~draWn) curve corresponds to horizontal line of strength value
(target strength) of 43 N/mm 2 then move down to POint c where
you read a value of wlc = 0.47
Wlc = 0.47 < specified max 0.55 use 0.47
Jtem 1.8 Maximl-l-m fr'ee-water'/cement r'atio specified, see table 6&
Jtem 2.1 sll-l-mp Or' V _B this is the wOr'kability meas~re. see table 11
for different'de9ree'of workability relate:d to differeVlt ~se.
In our case Slump = )0-30'mm
Jtem 2.2 Maximl-l-m ..A99r'e9ate size specified vall-l-e it caVl be 10, 20,
Or' 40
,,
In our case 20mm.
i> I
In our case free water content = I GO kg/m 3
this completes stage 2
I'
:' 1' .
" ., ..
":~~
,,
~ \
I ~
.~ :i; ': !
'~:~t ! '~l~:":;;:~
iii!':
i;n ,I:.. I
"Total aggregate content
; !
= 2400-340-1 GO= 1900 kg/m 3
j:!i:ifLhis,sompletes stage 4
'liliT~! . <f.iji,!;:
': "\STi,\G\6 5 Selection of fine C\nd coorse C\ggresC\te contents
-." .: !
. l;{te;'7:'., 5. 1 G\rading of fine aS9regC\te C\ccordiVlg to BS882 see relC\te
'::t~bl~:2
; '" iJ,r:,8~r:case fin aggregate of Zone 3 IS used
.~ i' :Prt\~1gt!1:!;;!.
• I l- !' i ~ ~Ij· ii, i
Ii Jter"?2 Proportion of fine C\9sre9C\te taken from Fig. 6
, i i j, ,
,.,' .
"
;:It,er.5.3 FiV\c a881'c9L,tc
. ~ i I; ~
CClI\1clll
"pe"ceVltagc
.i iii lr 0Hf
, "I '1!\' i ~ . , .j
case frne aggregate content
I
1900xO.27 5 15 kglm 3
,
k0"m 3
,; o.
I i
. i.
i
TofiVl9 the gl-\aV\tity I"egl-\il"ed fol" a tl"ial mix of CI cel"taiI'1 voll-\me simply
I I
. !; ! Jf-.1?if,ign for indirecf fensile sfrengfh
: 1'~Il:'!~~~:~lete
I. ! 'j(1:'lq: vrr,iftH1!.,I
l-\sed iVl I"oads is I"egl-\il"ed to achieve CI cel"taiVl level of
I. " i ,ip~,i~~t-tensile stl"eV\sth
:::1'1' I' _
:Jh~,:~fsisn p ...ocess is the same CIS fol" compt'essive with the foilowiVl9
!;s.~b~titl-\tions:
,:Jt~~''1.2 StClnda.l'd deviatioV\
I: I' .; :, :
. J~s~r8: vall-\e N/mm
2
of 0.6
the sfCII'1dClt'd deviatioV\ wheV\ less thClVl 40
fol"
!'p'r~Yh::u""s t'esl-\Its co-e. aVClilClble/ aV\d CI vall-\e of 03 N/mm as the
watel"/cemeV\t I"atios CIS dictated by the dClta avai lable at the pl"eseV\t
T~p," of COC\"sc
,
ce~eYlt
····~vf:.28· 91
C( d L I (I n ~' c , •• , I .' I Cr"\'
;?~;:;t:Ut?E:;£('~3?;;·qg~:x,:·:··tfim} .
43.
47' 55
'·J:;~.~~0;~iig:
46 53
0-10 10-30
c
30-60 60-180
>12 6-12 3-6 0-3
======'"
3 7· '",28, 91
1.7 2.2 2.8 3.3
"," . ,
------------@J
<,
/ <,
/ 1/
t--... B: minimum s
for 40 or more
results
o ~
o 10 20 30 40 50
~
60 70
I ~
Characteristic strength (N/mm )
2
~~\ G-'A
~~Y.l
Figure 3 Relationship between standard dexiation and characteristic strength
, ; i: ';::j
.,:i,
l ,
!
...
Iii
rio
n iii I'
f' 11 H :1 :UfJ !
,; .J
9.0 \
.~.
"
...
,:'"
\ 1\ Startin~ line
,. '.,1:'
1\ using ala
: .... n " \ from liable 2
.. \ 1\
8.0,1\ 1\
.i: I
i
!\ , '!\
\.
, 1\ \
;: 1.0 \. \
\ 1\ \ \ ,
\ 1\
\ \ \. \
.- : :
\ I\.
\ \ I\.
; :~.,O: 1\
1\
NI
,, E .,
1\
\
1\
\
\.
I\.
1\
E
<,
,
1
\.
1\ '\ " '\
IZ '
-5.0 \ \ \. 1\ 1'\
I\. 1'\
" c'
,;
' :-. f"1\. 1\
Ii., ;I'l(:;::i
1\ s:
~ \
1\
1\
I\. '" 1'\
I'\.
,'\
'\
·~:,-~:nl1:-;.)'~1ii ,~ _\ i'. '\
;: :i';: QI'I" \
1'\
, I!'i,'.~ 40
." "lIli"
'-'
.\ \
:\
"\
r-, r-,
I'\...
r-,
"
l"jl~;li IIlHH'j "\ 1\ I\. r-,
'!!l!j~
\. \.
I'\. :-... '" <,
'I I. ,
':.:l~t'
d :i: t
III • ~
• I .
~
1\ \.
" '\. r-, " " r-,
K " r-,
I~~,
:rlt"H!Ir.:'i
l
0 i'.
r-,
I'\.
" r-, <,
\
I
I
,
I
'y
;'
~~d ,1 )
I" I
• ~ 11~ 1 1
"
r-,
.......
I'-.... .......
r- ...
! r-.....
' 'j
{I"I-"
1 i5I
1
flf.l::' I'
\~ . ~
',ll. \{\!'l
'" ....... ..... , r-, ....... <, r--. ....... t-.
...
: • < 1 t j'l
--; r-.... i
r---~ t' r-I-.. "'- "'
Ii:!:;'"ii/ll'r:i :- '-..
";!!';'~Ti:~:':
0.4 0.5
• 0.6 0.7 0.8 0.9
,", Free-Water/cement ratio
\ f\
1\ 1\
\ \
7.0 " 1\ f'\
1\
"1\ 1\, \ I\. \
I" I\..
1\ \ \ I\.
6.0 i\ 1\ \ 1\
~
I \ \ ~
E 1\ \
E '\
<,
z 5.0 \ \ -, "-, '\
s:
151 ~-
1\ 1\ \
+,,.,, ~ -p ..-
f\.
I-
" I'\.
~- - -
_. p, ,
C
~
.....
1\\ 1\ 1\ -e "" -, 1'\ '1- c-,
- -, ~
III
all:
4.0
' '\"1\
- -
\ \ I\;. ~g
, I'\. r-, ""
'111
III I\. 1\ 1\ 'I\.. I"\.. r-, r-,
f!
c.
\ t\. -,
rr-, <, r-,
1\ \ \ ~ ; r'\. r-,
E 1\" r-, r-,
8 l\ -,
\ q" r-, " t'-.
3.0 \ '\ '\
I\' :1'\.
I\' r-, I......
r-,
<,
"
I'-..
"
'\ \ ! r-, r-,
'"
I r-,
1\ I'\. '-l I":: -, i':
<,
r--... ".
'-.;,.
r-, "' ~ " .......
-, r-, r-; r-, <,
2.0 f'.....
r-,
r-,
r-,
I,' ..... " .........
" r-,
r-,
r-,
i'--..
r-, "' 'I-.. r-, ,....... t--- f-..
r-, <, <, t--.... -..... r- r-
......... ~ :--...! <, r---.. r--t- r- f-..
10 ....... r-,
...... 1'-.
t-- t-
r-
"
t--
f
"-
1--_
t--f-.
r-- I-
-
a0.3 0.4 __ 0.5 0.6 0.7 0.8 0.9
Free-Water I cement ratio
. 80
•.. --
.. ... - ......... '" .-..
-.~ ~.
.,- 'h-:
.. .._. .-.-......-t
-.~
~
-.-~-
~
......- r-r-:» ........ :;:;-:FE:rtl±
.... ,. ......
~ ~ ~-
L.
t = "":1Xtt:::-.:: rrr: -::-j:-::
-_.- ,
---,!- .a.,
"+,--
.ri;:r .. ~ !tr1~
m+ t+:--' TO . H~
4 . ~L ~,-tJ
TO
:::J+
..
;l!ili£ :g\~'Jf --1~j :± +H+
" :::m: it t +Ii ·ft :;-tl
-:--f
L J:I
-'
60
50 50 50
40 40 40
-
30 30 30
20 20 20
10 10 1o
0.4 0.6 0.8 0.2 0.4 0.6 0.8 0.2 0.4 0.6 0.8 0.2 0.4 0.6 0.8
Free-water/cement ratio
70 70 7D
60 60 60
50
40 40
30 30 30
20 20 20
10 10 10
0.6 0.8 0.2 0.4 0.6 0.8 0.2 0.4 0.6 0.8 0.2 0.4 0.6 0.8
Free-water/cement ratio
iure 6 (Continued)
1----··--,·,
L_''.' i ..
I
'j: : .
:
I · 'i
I TT-i'- -IH-i--r-i , I I
I
'i'
'::
2700
'~-I-~·~I -I I I
I
I . ,I··:·-i-i-~ -I~I
i I I -i-Ii
!i
I " I I I , ,.;
I
2600
f-"
;"--1-/- -iTT ~CT'- I I I I I .. - , ~~;
; ! "'I-- _ilL ,......
--H-C:: :--.... -.. -l-H
I I
Relative density of '
"
Lttf
combined aggre'gate-
~--fj-t- . :--....1
I I I ! I (on saturated and -
-----~
I I i 1--
-!-:::"..
--. f c:r J 1 surface-dry basis) : -
:
2500
I ' ,
~h:::+-+
f:="~--.L.
-- r-
-- :--....
r--..
r--.. -..
--.
....... <,
?'a
,I
r--- -- -- I--
;-.
-- -- As
~ 5IJrnert fOr --.
~ CilJshecJ a '
r--
r--.. 28 .
I
r-
--
-- -- r- -- I--
r- As· 1
r-!-U!!l!:CI for un~
~9regate
hi, ~ ? 7
"
,
'I:
.r .
i
2300
e--
-- - -- -- -- -~~ed aggreg~t I
...::::~
r--
- --
I--. ?fl
- -- I--- I--.
I--.
I---
;-. r--
- I
" " -".
--
,I
I--.
;":0
l - I--.
-- --
I
2200
-
"
I-
I--- 24
2100
100 120 140 160 180 200 21° 220 240 260
3
Free-water content (kg/m )
70
70
70 I,
~ 1
!\II,
50_
60
80
50
50
40
40
30
30
20
20
tf±1:±±±i±t1±J 10
10
10
0.8 0.2 0.4 0.6 O.B 0.2 0.4 0.6 0.8 0.2 0.4
z Free-water/cement ratio
~ecommended proportions of fine aggregate for 85882 grading zones 1,2,3 and 4
I I I I I I
J I I I I I I
Starting line using HI---t-t--+-++-+-+-f-+-i
data from Table 8
,L': r-....
'I
,i
f',
<,
r-,
<,
........
r-- .......
........
.....
....... ........
........ ~
........
" I-i';~:i':H-+--+--I-IH-t--f-t-I-t--t--t-I-t-t-+-H--+-t-H-t--t--f-H
\ >:';'P
"~,
! '
OJ. 0.5 0.6
Free-Water/cement ratio
E \. ~.
.A.; s for less ~ / ".
z "'1
"I ") ')
than 20
v; 6 results
c
c 1I
cc • I
0:
-c
R''1)lnlmllrT) S 1/- ')
T
for 20 or
"2
~
more results
o
L
co
(jj
.. _~,__ .-J
,
Figure 3 aS
UlI! ~
0 10 20 30 40 50 60 70 Relationship between standard deviation and
r~h~":1r'tPrlc;tfr ~l,.n('l'J'!'h IN ,'f)")n"'/ \ character.sue 5tltOll(jth
9°K I \
;S-t-Lo~:j~-:U !.~
".
E
5-3 >=
z ..-._---+-..._- ._
~
(f)
<ll
C.E I
I
C I
U 30r
l o,J
""
Maximum aggregate size: 20mm
70 70 70
60 60 60
50 50 50
40 40 40
30 30 30
20 20 20
10 10 10
0.4 0.6 0.8 0.2 0.4 0.6 0.8 0.2 0.4 0.6 0.8 0.2 0.4 0.6 0.8
Free-water/cement ratio
Figure 6 (Continued)
70 70 70
80 60 60
50 50 50
40 40 40
30 30 30
20 20 20
10 10 10
0.4 0.6 0.8 0.2 0.4
0.6 0.8 0.2 0.4 0.6 0.8 0.2 0.4 0.6 0.8
Free-water/cement ratio
Figure 6 (Continued)
2700
- I--
-
r--. .......
r-...
-I'---.
,
- - -- -
.......
I'---. -I""--- I
--I--- -
-
'e
2600
-
I
r--. r-...
r-...
Relative density of
-
~
-
OJ
-
(on saturated and -
~ -I""--- ....... r--. --..
-
I--..
-
I
"-'
--.. r-... surface-dry basis) -
-
.~ 2500 I
-...
E
-(J)
tI!
o
c r-
I--..
--.. r-..
-I-.... '.HI
....8
0
2400
- - -- - - :--
I
:--
r-
AsSUll'led fa
:-....
~CltJsh
I
~9'ega(,
....... r--...
- 28
~t/)
c(J)
- - r- I--..
I-
-
r-.. 1
~~ettbr.1
I
I ,I
1J~8h
I
.
~ ') '7
-
I r- r-.. r--:.~8d agg~ I
"C 2300
, r--
- - :-- t- I-. ~ates
~
-- -- - ---
:-:.:: ')fl
r-- :--
- :--
-r-..
I-
2200
,
-- - -- r-..
:--
r-..
t - 24
25
--
- i i
2100
"
3
Free-water content (kg/m )
80
80 80
10 10 10
eo 80 80
50 50 50
40 40 40
30 30 30
20 20 20
10 10 10
1.4 0.6 0.8 0.2 0.4 0.6 0.8 0.2 0.4 0.6 0.8 0.2 0.4 0.6 0.8
Free-water/cement ratio
Figure 6 Recommended proportions of fine aggregate for BS882 grading zones 1,2,3 and 4
t8, 18262· 1982
'0Q ....----..,----..,.--.--r--~T_--__,r__--...,..---...,
oa
F
E
N
soo
E D
...E
z C
j; 40·0
o B
z
UJ
...
CI:
Vl A
::' 30· 0
UJ
CI:
U
Z
0
u
;>- 20·0
<t
0 ,
CD
N
10·0
WATER-CEMENl RAllO
9.0
, \
I\. Startin~ line
1\ using ata
8.01\
, " 1\
from Table 2
I\.
I\.
\.
~
'I
\.
\.
,
7.0 ~ \.
I\. 'I \.
\ I\.
1\ \ 1\ "\
I\. !\ I\.
\. \ 1\
6.0 1\ 1\ \ I\. I\.
1'0' \. 1\
E !\ 1\
E 'I "'
"
z
-5.0 \ \ -, "\ "I'
s:
1Sl
c
i
,
1\ 1\
\
\.
I\.
I\. 1"-
I'\.
I"
1""-
f r\ f\. 1\ 5 "' r-, 1'\
1;i
GI
\ \ , i, ~
A
\
1'\
"
I\.
" <,
.~ 4.0
III
1\ ./\ I\. f\.. 1"\
"
'\.
\. I\...
I'\..
"" " .....
<,
"-
r-,
..... ,
I'. ..., -, '" ........
'"
\. ..... :--....
"- -, -, r-,
r-, I'\.. <, r-, ~
2.0 r-,
i"'-
~
r-,
." r-,
'",-
.......
.....
:-......
<,
I'-..
--,
....... r-, ....... ........ I"-
--
r-, t--... ........
r-, r-, r-, ....... ....... ~ r---.
-- --
.......
..... ....... ......
10
:-...... t-..... ....... " f-.. ~
!-
...... r-.
..... ""' ....... t--... I"---
-- l"-
~
I'-- '--
I"- t--
I'-- r-
- ""-
I
(: J
0.4 (-'.4]0.5.. 0.6 0.7 0.8 0.9
Free-Water/cement ratio