GENERAL NOTES: PIPING GENERAL NOTES: PLUMBING SYMBOL AND ABBREVIATION SCHEDULE

1. THE DRAWINGS ARE DIAGRAMMATIC AND SHOW ONLY THE GENERAL ARRANGEMENTS OF ALL PIPING 1. ALL WATER LINES IN EXTERIOR WALLS SHALL BE INSULATED AND LOCATED WITHIN THE INSULATION SANITARY SEWER LINE (SAN) WH WALL HYDRANT
AND EQUIPMENT. BECAUSE OF THE SMALL SCALE OF THE DRAWINGS, IT IS NOT POSSIBLE TO SHOW ENVELOPE OF THE BUILDING EXTERIOR WALL.
OR INDICATE ALL OFFSETS, FITTINGS, AND ACCESSORIES WHICH MAY BE REQUIRED TO AVOID STORM SEWER LINE (STM) HB HOSE BIBB
STRUCTURAL FEATURES. 2. SET ALL FLOOR AND FUNNEL DRAINS OVER P-TRAPS. KIT W KITCHEN WASTE LINE
COMBINATION HOSE BIBB
2. DO NOT SCALE DRAWINGS - ALL DIMENSIONS AND EXISTING CONDITIONS SHALL BE CHECKED AND 3. PROVIDE SHUT-OFF COCK AT EACH CONNECTION TO GAS EQUIPMENT. CDL CONDENSATE DRAIN LINE
FUNNEL DRAIN
VERIFIED BY THE CONTRACTOR AT THE SITE. NOTIFY ENGINEER OF ANY DEVIATIONS FROM THE
SR CONDENSATE OVER FLOW DRAIN LINE (OF)
DRAWINGS. 4. PROVIDE DIRT LEG AT BOTTOM OF ALL VERTICAL RISERS AND DROPS IN GAS LINES. FD FLOOR DRAIN
W WATER SERVICE LINE
3. REPORT ANY DISCREPANCIES FOUND IN THE DRAWINGS AND/OR IN THE SPECIFICATIONS DURING 5. INSTALL WALL HYDRANTS AT A MINIMUM OF 2'-0" ABOVE FINISHED GRADE, UNLESS OTHERWISE RD ROOF DRAIN
THE BIDDING PROCESS FOR CLARIFICATION BY THE ENGINEER AND/OR ARCHITECT G GAS LINE (G)
INDICATED.
SUPERVISED VALVE
BRANCH VENT LINE (V)
4. ALL WORK PERFORMED ON THIS BUILDING SHALL BE IN COMPLIANCE WITH ALL PERTINENT CODES, 6. EXTEND ALL CLEANOUTS ON SANITARY SEWER, KITCHEN WASTE AND RAIN WATER CONDUCTOR
RULES, ORDINANCES, AND REGULATIONS OF THE LOCAL GOVERNING AUTHORITIES, STATE LINES BELOW SLAB ON GRADE TO FINISHED FLOOR LEVEL. COLD WATER LINE (C) PRESSURE GAUGES
GOVERNING AUTHORITIES AND NATIONAL GOVERNING AUTHORITIES.
HOT WATER LINE (H) RECIRCULATING PUMP
7. COORDINATE LOCATIONS OF ALL LINES, EQUIPMENT AND WORK WITH OTHER CONTRACTORS.
5. ALL WORK PERFORMED UNDER AND IN CONNECTION WITH THESE DRAWINGS AND SPECIFICATIONS HOT WATER RETURN LINE (R)
SHALL BE IN STRICT COMPLIANCE WITH THE LATEST OSHA SAFETY AND HEALTH STANDARDS. INDICATES NOTE LOCATED ELSEWHERE
8. THE CONTRACTOR SHALL REFER TO APPLICABLE CODES FOR ACCEPTABLE DRAINAGE SYSTEM XX
ON DRAWING AND NOTE NUMBER
FITTINGS.
6. THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATION WITH ALL UTILITY AUTHORITIES
DETAIL/PLAN REFERENCE SYMBOL
FOR INSTALLATION REQUIREMENTS, REGULATIONS, FEES, PERMITS AND APPROVALS AS 9. DIELECTRIC UNIONS AND FLANGES SHALL BE USED ON ALL CONNECTIONS BETWEEN DISSIMILAR XXX
NECESSARY TO COMPLETE THE INSTALLATION. METALS. T TEMPERED HOT WATER LINE (TEMP H) INDICATES DETAIL/PLAN NUMBER
YYYYY
INDICATES DRAWING No FOR WHICH
PD PUMP DISCHARGE
7. ALL PIPE PENETRATIONS THROUGH CHASE, WALLS OR FLOORS WHICH ARE FIRE-RATED, SHALL BE 10. WHERE DOMESTIC COLD WATER, DOMESTIC HOT WATER, DOMESTIC HOT WATER RETURN WATER THE DETAIL/PLAN IS LOCATED
PROPERLY SEALED TO MAINTAIN FIRE PROTECTION. CONTRACTOR SHALL SUBMIT PROPOSED UL AND NATURAL GAS SUPPLY LINES ARE NOTED TO BE RUN AT CEILING AND/OR ABOVE CEILING, RUN TP TRAP PRIMER LINE
LISTED SYSTEM FOR REVIEW.. LINES AS HIGH AS POSSIBLE. COORDINATE WITH ARCHITECTURAL, HVAC, FIRE PROTECTION, AND SQUARE FOOT
SW SAFE WASTE
ELECTRICAL DRAWINGS - REFER TO DETAIL ON DRAWING P5.4.
ABV ABOVE
8. ALL PIPING SHALL BE INSTALLED AS HIGH AS POSSIBLE UNLESS NOTED OTHERWISE. BALL VALVE
11. ALL PIPING NOTED ABOVE OR AT CEILING, SHALL BE TIGHT TO UNDERSIDE OF FLOOR SLAB WITH BLW BELOW
9. ALL PIPING, CONDUIT, DUCTWORK, ETC., SHALL BE INSTALLED IN A MANNER WHICH WILL NOT SPACE FOR INSULATION AND HANGERS AS REQUIRED. GATE OR GLOBE VALVE
DEFACE OR ALTER ANY AREAS. ROUTING OF THE ABOVE EQUIPMENT SHALL BE APPROVED BY THE CB CATCH BASIN
GAS, AIR, VACUUM COCK
ARCHITECT/ENGINEER PRIOR TO INSTALLATION. 12. WHERE RAIN WATER CONDUCTORS, SANITARY SEWER, SANITARY VENT, CONDENSATE DRAIN AND CLG CEILING
TRAP PRIMER LINES ARE NOTED TO BE RUN AT CEILING, ABOVE CEILING AND/OR BELOW FLOOR RUN FLOW CONTROL VALVE
10. ALL PIPING TO BE LOCATED AND COORDINATED WITH ARCHITECTURAL PLANS. ALL PIPING SHALL BE LINES AS HIGH AS POSSIBLE, UNLESS LINES ARE RUN BELOW SLAB ON GRADE. EC ELECTRICAL CONTRACTOR
CONCEALED IN FINISHED AREAS. NEW COMBINATION BALANCING/
SHUT-OFF VALVE FLR FLOOR
13. MEANS OF ACCESS SHALL BE PROVIDED TO CONCEALED TRAPS, VALVES, CLEANOUTS, DRAIN
11. THE CONTRACTOR SHALL COORDINATE THE LOCATION OF PIPING AND EQUIPMENT WITH ALL NEW POINTS OR SIMILAR ITEMS. THE CONTRACTORS SHALL COORDINATE THE LOCATIONS AND LOCKING VALVE W/IDENTIFICATION FNL DR FUNNEL DRAIN
HVAC PIPING, DUCTWORK, HVAC EQUIPMENT, ELECTRICAL CONDUIT AND ELECTRICAL EQUIPMENT QUANTITIES OF ALL ACCESS PANELS DURING BIDDING PHASE. ACCESS PANELS WILL BE FURNISHED
THAT IS TO BE INSTALLED WITH THE OTHER CONTRACTORS. STRAINER GC GENERAL CONTRACTOR
AND INSTALLED BY OTHERS.
CHECK VALVE HC HEATING CONTRACTOR
12. ALL PIPING IN FINISHED ROOMS OR SPACES SHALL BE CONCEALED IN FURRED CHASES OR ABOVE 14. PROVIDE CLEANOUTS IN SANITARY AND STORM PIPING SYSTEMS AT ENDS OF RUNS, AT CHANGES IN
SUSPENDED CEILING. DIRECTION, AT BASE OF STACKS AND AT 50 FOOT INTERVALS IN HORIZONTAL PIPING, AND CHECK VALVE INV ELEV INVERT ELEVATION
ELSEWHERE AS INDICATED. CLEANOUTS SHALL INSTALLED IN NON PUBLIC PLACES WHENEVER BP REDUCED PRESSURE TYPE MH MANHOLE
13. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE REMOVAL AND CLEANUP OF ALL DEBRIS POSSIBLE. BACK FLOW PREVENTER
ASSOCIATED WITH THE INSTALLATION OF PLUMBING ITEMS COMPLETE. FSEC FOOD SERVICE EQUIPMENT CONTRACTOR
15. ALL INTERIOR STORM WATER PIPING, 4" AND LARGER, SHALL BE SLOPED AT 1/8" PER FOOT, UNLESS PRESSURE REDUCING VALVE
14. ALL FLOOR AND FUNNEL DRAINS TO BE INSTALLED WITH TRAP PRIMER CONNECTION AND TRAP PC PLUMBING CONTRACTOR
NOTED OTHERWISE. ALL INTERIOR STORM WATER PIPING, 3" AND SMALLER, SHALL BE SLOPED AT
PRIMER VALVES. PROVIDE 1/8" PER FOOT SLOPE ON ALL TRAP PRIMER LINE SUPPLYING DRAINS. UNION
1/4" PER FOOT, UNLESS NOTED OTHERWISE. ATC AUTOMATIC TEMPETURE CONTROL CONTRACTOR
PROVIDE PIPE SLEEVES FOR ALL TRAP PRIMER LINES INSTALLED BELOW SLAB ON GRADE.
WATER HAMMER ARRESTER RWC RAIN WATER CONDUCTOR
16. ALL INTERIOR, ABOVEGROUND, HORIZONTAL STORM DRAINAGE SYSTEMS SHALL BE INSULATED AS
SPECIFIED. SPC SPRINKLER CONTRACTOR
PIPE ANCHOR
17. ALL KITCHEN EQUIPMENT IN THE KITCHEN AREA SHALL BE FURNISHED AND INSTALLED BY (OWNER) SS SOIL STACK
PIPE GUIDE
FOOD SERVICE EQUIPMENT CONTRACTOR. PLUMBING CONTRACTOR TO PROVIDE ROUGH-INS AND VS VENT STACK
FINAL CONNECTIONS INCLUDING BUT NOT LIMITED TO WATER LINES, DRAINS, AND FAUCETS UNLESS CAP OR PLUG
SPECIFIED OTHERWISE. VTR VENT THROUGH ROOF
CO CLEANOUT EXTENDED UP TO FLOOR/GRADE
WR WATER RISER
18. REFER TO FOOD SERVICE EQUIPMENT DRAWINGS FOR MOUNTING HEIGHTS, ROUGH-IN CO CLEANOUT END OF LINE
CONNECTIONS AND LOCATIONS. WS WASTE STACK
TP TRAP PRIMER
19. PROVIDE FLOW CONTROL VALVES ON THE WASTE OUTLETS OF THE DISHWASHING SINKS ENTERING CFH CUBIC FOOT PER HOUR
M GAS METER (SEE SPECIFICATIONS)
THE KITCHEN WASTE PIPING SYSTEM. (REFER TO SPECIFICATIONS). GPM GALLONS PER MINUTE
R GAS REGULATOR
20. EXPOSED PIPING, FITTINGS AND VALVES IN THE KITCHEN AREA SHALL HAVE A CHROME (PLATTED DFU DRAINAGE FIXTURE UNIT
PEX MANIFOLD
BRASS) FINISH UNLESS SPECIFIED OTHERWISE.
WSFU WATER SUPPLY FIXTURE UNIT
21. COORDINATE THE LOCATIONS OF WATER, GAS AND VENT PIPING ABOVE CEILING WITH HEATING
CONTRACTOR IN AREAS WHERE KITCHEN VENTILATOR HOODS ARE LOCATED TO AVOID
INTERFERENCE WITH DUCT, ETC. .

22. ALL DOMESTIC WATER PIPING IN THE WATER HEATER ROOM TO BE TYPE 'L' COPPER.

23. ALL SANITARY PIPING ABOVE PUBLIC AREAS TO BE CAST IRON AND INSULATED.

24. SANITARY WASTE PIPING INDICATED IN THE KITCHEN AREA AND WATER HEATER ROOM TO BE CAST
IRON.

25. ALL INTERIOR SANITARY PIPING, 4" AND LARGER, SHALL BE SLOPED AT 1/8" PER FOOT, UNLESS
NOTED OTHERWISE. ALL INTERIOR SANITARY PIPING, 3" AND SMALLER, SHALL BE SLOPED AT 1/4"
PER FOOT, UNLESS NOTED OTHERWISE. ALL SANITARY PIPING BELOW SLAB 4" MINIMUM.

SYMBOLS, ABBREVIATIONS
AND GENERAL NOTES
PLUMBING

P0.01
KEYNOTES
1 PROVIDE 4" WASTE CONNECTION TO POOL TRENCH DRAINS. PLUMBING CONTRACTOR
SHALL COORDINATE 4" WASTE OUTLET WITH OTHER CONTRACTORS. (TYPICAL)

2 PROVIDE ELEVATOR SUMP PUMP (SP-1) FOR ELEVATOR SUMP MAINTENANCE. FOR
MORE INFORMATION REFER TO DETAIL ON DRAWING P5.02.

3 CONNECT 1 1/4" CONDENSATE DRAIN LINE TO OUTLET CONNECTION OF HVAC UNIT.


HVAC UNIT PROVIDED BY THE HEATING CONTRACTOR. PLUMBING CONTRACTOR
SHALL COORDINATE EXACT CONNECTION POINT OF DRAIN LINE TO HVAC UNIT WITH
HEATING CONTRACTOR.

4 PROVIDE 2" CONDENSATE DRAIN RISER FROM ABOVE, EXTEND 2" CONDENSATE DRAIN
LINE THROUGH EXTERIOR WALL, TERMINATE CONDENSATE DRAIN LINE 0'-6" ABOVE

FINAL LOCATION WITH OTHERS.

5 CONNECT 1 1/4" CONDENSATE OVER FLOW DRAIN LINE TO OUTLET CONNECTION OF


HVAC UNIT OVER FLOW DRAIN CONNECTION. HVAC UNIT PROVIDED BY THE HEATING
CONTRACTOR. PLUMBING CONTRACTOR SHALL COORDINATE EXACT CONNECTION
POINT OF DRAIN LINE TO HVAC UNIT WITH HEATING CONTRACT

6 FOR CONTINUATION OF PIPING - REFER TO SITE UTILITY PLAN.

7 2" CONDENSATE DRAIN RISER FROM ABOVE.

8 CONNECT 1 1/4" CONDENSATE OVER FLOW DRAIN LINE TO OUTLET CONNECTION OF


NOTE: HVAC UNIT OVER FLOW DRAIN CONNECTION. HVAC UNIT PROVIDED BY THE HEATING
ALL SANITARY, CONDENSATE DRAIN, AND CONTRACTOR. PLUMBING CONTRACTOR SHALL COORDINATE EXACT CONNECTION
SECONDARY CONDENSATE DRAIN LINES POINT OF DRAIN LINE TO HVAC UNIT WITH HEATING CONTRACT
OVER PUBLIC SPACES TO BE INSULATED.
9 TERMINATE CONDENSATE DRAIN OR CONDENSATE OVER FLOW LINE LINE OVER
FLOOR DRAIN AND/OR FUNNEL DRAIN W/APPROVED AIR GAP.

10 ALL WASTE, VENT, STORM, AND CONDENSATE PIPING IN POOL AND POOL EQUIPMENT
AREA TO BE PVC.

11 TERMINATE CONDENSATE LINE OVER MOP SINK W/APPROVED AIR GAP.

12 PROVIDE CONDENSATE DRAIN OVER FLOW, EXTEND CONDENSATE DRAIN OVER FLOW
LINE THROUGH EXTERIOR WALL, TERMINATE CONDENSATE DRAIN LINE 0'-6" ABOVE

FINAL LOCATION WITH OTHERS.

13
REMOVABLE INSECT SCREEN. COORDINATE FINAL LOCATION WITH OTHERS.

14
CHANGE IN DIRECTION.

15 TERMINATE CONDENSATE DRAIN LINE OVER FLOW, OVER LAUNDRY SINK W/


APPROVED AIR GAP.

FOR PIPING AND EQUIPMENT


IN THIS AREA - REFER TO
9 ENLARGED PLAN ON DRAWING
P4.05

AS HIGH AS POSSIBLE MECHANICAL/ELECTRICAL


020

4"RWC-FRM ABV
(1014 SQ/FT)

6"RWC-FRM ABV
(2186 SQ/FT)
CO

AT CLG

7 SITE STORAGE
019
BLW SLAB KITCHEN DESIGN TO FOLLOW
AS SEPERATE SUBMISSION

3"V-UP 3"RD-FRM ABV


3"VTR (380 SQ/FT)

MATCHLINE
6

4"RD-FRM ABV BLW GRADE


(910 SQ/FT) 4
7
12 10" (13,967 SQ/FT)

DEN
6 10" 6"RWC-DOWN CO 010
HOUSE TRAP - ACCORDING TO (6981 SQ/FT)
BLW SLAB CO
ALLEGHENY COUNTY REQUIREMENTS BLW SLAB

SW
6"RWC-FRM ABV KITCHEN
BLW SLAB (4354 SQ/FT) 017
AS HIGH AS POSSIBLE ABV CLG
COR. 6"RWC-FRM ABV
(2627 SQ/FT)
7 016 ABV CLG
MENS 6"
6" 8"RWC-DOWN
014 (5466 SQ/FT)
ABV CLG

1 1/4"
3 (TYPICAL)
4"
1 1/4" CO
BUFFET
6 BLW SLAB
STORAGE 009
HOUSE TRAP - ACCORDING TO
017a SW
CO
CO
ALLEGHENY COUNTY REQUIREMENTS
WOMENS CO
14 BLW SLAB
015 CO CO SOCIAL SEATING AREA
BLW SLAB 8 (TYPICAL) BLW SLAB 008
CO
FOR PIPING AND EQUIPMENT
CO
IN THIS AREA - REFER TO ABV CLG
ENLARGED PLAN ON DRAWING P4.05 4" COMMUNAL AREA
BILLIARDS 011
CDL

013
4"RWC-DOWN
(940 SQ/FT)
AS HIGH AS POSSIBLE
ALONG WALL
4"
ABV CLG 2"
2" DINING AREA 2"
ABV CLG 012 ABV CLG
CO CDL
3" 4" 2" 2" 2" 2"
CO
CO CDL CDL CO
CO

3"RD-FRM ABV
7

MATCHLINE
(940 SQ/FT) 7
7 7
7 7 7

3"RD-FRM ABV
(332 SQ/FT)

PARTIAL GROUND FLOOR


WASTE, VENT AND STORM
PLUMBING
PARTIAL GROUND FLOOR PLAN
WASTE, VENT, AND STORM - PLUMBING
01 SCALE: 1/8" = 1'-0"

P1.01A
KEYNOTES
1 PROVIDE 4" WASTE CONNECTION TO POOL TRENCH DRAINS. PLUMBING CONTRACTOR
SHALL COORDINATE 4" WASTE OUTLET WITH OTHER CONTRACTORS. (TYPICAL)

2 PROVIDE ELEVATOR SUMP PUMP (SP-1) FOR ELEVATOR SUMP MAINTENANCE. FOR
MORE INFORMATION REFER TO DETAIL ON DRAWING P5.02.

3 CONNECT 1 1/4" CONDENSATE DRAIN LINE TO OUTLET CONNECTION OF HVAC UNIT.


HVAC UNIT PROVIDED BY THE HEATING CONTRACTOR. PLUMBING CONTRACTOR
SHALL COORDINATE EXACT CONNECTION POINT OF DRAIN LINE TO HVAC UNIT WITH
HEATING CONTRACTOR.

4 PROVIDE 2" CONDENSATE DRAIN RISER FROM ABOVE, EXTEND 2" CONDENSATE DRAIN
LINE THROUGH EXTERIOR WALL, TERMINATE CONDENSATE DRAIN LINE 0'-6" ABOVE

FINAL LOCATION WITH OTHERS.

5 CONNECT 1 1/4" CONDENSATE OVER FLOW DRAIN LINE TO OUTLET CONNECTION OF


HVAC UNIT OVER FLOW DRAIN CONNECTION. HVAC UNIT PROVIDED BY THE HEATING
CONTRACTOR. PLUMBING CONTRACTOR SHALL COORDINATE EXACT CONNECTION
POINT OF DRAIN LINE TO HVAC UNIT WITH HEATING CONTRACT

6 FOR CONTINUATION OF PIPING - REFER TO SITE UTILITY PLAN.

7 2" CONDENSATE DRAIN RISER FROM ABOVE.


NOTE:
ALL SANITARY, CONDENSATE DRAIN, AND 8 CONNECT 1 1/4" CONDENSATE OVER FLOW DRAIN LINE TO OUTLET CONNECTION OF
SECONDARY CONDENSATE DRAIN LINES HVAC UNIT OVER FLOW DRAIN CONNECTION. HVAC UNIT PROVIDED BY THE HEATING
OVER PUBLIC SPACES TO BE INSULATED. CONTRACTOR. PLUMBING CONTRACTOR SHALL COORDINATE EXACT CONNECTION
POINT OF DRAIN LINE TO HVAC UNIT WITH HEATING CONTRACT

9 TERMINATE CONDENSATE DRAIN OR CONDENSATE OVER FLOW LINE LINE OVER


FLOOR DRAIN AND/OR FUNNEL DRAIN W/APPROVED AIR GAP.

10 ALL WASTE, VENT, STORM, AND CONDENSATE PIPING IN POOL AND POOL EQUIPMENT
AREA TO BE PVC.

11 TERMINATE CONDENSATE LINE OVER MOP SINK W/APPROVED AIR GAP.

12 PROVIDE CONDENSATE DRAIN OVER FLOW, EXTEND CONDENSATE DRAIN OVER FLOW
LINE THROUGH EXTERIOR WALL, TERMINATE CONDENSATE DRAIN LINE 0'-6" ABOVE

FINAL LOCATION WITH OTHERS.

13
REMOVABLE INSECT SCREEN. COORDINATE FINAL LOCATION WITH OTHERS.

14
CHANGE IN DIRECTION.
REFUSE/
RECYCLE 15 TERMINATE CONDENSATE DRAIN LINE OVER FLOW, OVER LAUNDRY SINK W/
052 APPROVED AIR GAP.

4"RD-FRM ABV
SH-3
(1025 SQ/FT)
4"FD-1

ABV CLG BLW SLAB

ABV CLG
6"
3"V-UP
3"VTR INDOOR POOL
10
049 3"

ABV CLG
12 ABV CLG
3" 6" 6"RWC-FRM ABV
FOR PIPING AND EQUIPMENT 4"RD-FRM ABV
3"RD-FRM ABV IN THIS AREA - REFER TO (1170 SQ/FT) CORRIDOR (2098 SQ/FT)
(380 SQ/FT) ENLARGED PLAN ON DRAWING P4.05 051
MATCHLINE

6 8" STAIR 2
8"RWC-DOWN
8"RWC-DOWN (10,988 SQ/FT) 054
(5846 SQ/FT) 7 4"
BLW GRADE 1 1/4" TRENCH DRAIN (TD-1)

L
9 7 7

D
ABV CLG

C
10" (17,166 SQ/FT) 9 (TYPICAL)
ABV CLG BLW SLAB
CORRIDOR
2" 1 1/4" 2" 8" 2" 048
CO CDL 14
ABV CLG CDL
WORK AREA EMPLOYEE
CO CO 10" CO
3" 022 8" LOUNGE
ABV CLG 047 BLW SLAB
8" L-4
BLW SLAB COMPUTER
6"RWC-FRM ABV CO
023 6"
(2665 SQ/FT)
1 1/4"CDL RISER
CO PD
CO W-4
LAUNDRY 3 (TYPICAL) POOL TOILET
8"RWC-DOWN ABV CLG 2 11
045 050
CO
(5466 SQ/FT) 8" 15 ABV CLG
BLW SLAB
ELEVATOR FITNESS 2"
LOBBY CDL ABV CLG BLW SLAB 040
4"FD-6 LINEN 7
025 CORRIDOR BLW SLAB
STORAGE MEETING ROOM ABV CLG
CO 8 (TYPICAL)
STORAGE 038 CO
043 OFFICE
BLW SLAB CDL 042 044 6"
SW

BLW SLAB STORAGE


CDL

024
CO MARKET 2"V-UP BLW SLAB
CO
CO
004CDL SW CO
PRE-FUNCTION
BLW SLAB CORRIDOR 1 1/4"
2" SW 030 ABV CLG 2" 1 1/4"
4" 026
POOL EQUIPMENT
1 1/4" 2" CO
ABV CLG
3"RWC-DOWN 039 7
(332 SQ/FT) ABV CLG
CO BLW SLAB 2"
CO
CDL

CO ABV CLG 4"VS-UP ABV CLG


CO
SW

GM OFFICE 2" 6"RWC-FRM ABV


027 (2606 SQ/FT) CO
CORRIDOR
CORR. 035 CDL
028 TERMINATE 1 1/4" CONDENSATE DRAIN
CDL

(TYPICAL) 8 OVER FLOW DOWN ALONG WALL 1'-0" AFF


ABV CLG
SW

3"
SALES OFFICE
2" ABV CLG 029 ABV CLG
FOR PIPING AND EQUIPMENT
ABV CLG
2" 2" IN THIS AREA - REFER TO
2" ENLARGED PLAN ON DRAWING
CO CDL CDL ABV CLG P4.05
CO CO CDL STORAGE
CO 034
CO

7
MATCHLINE

7 7 7 7
7 7
3 (TYPICAL)

3"RD-FRM ABV
(332 SQ/FT)

PARTIAL GROUND FLOOR


WASTE, VENT AND STORM
PLUMBING
PARTIAL GROUND FLOOR PLAN
WASTE, VENT, AND STORM - PLUMBING
01 SCALE: 1/8" = 1'-0"
P1.01B
KEYNOTES
1 EXPANSION LOOP (REFER TO DETAIL ON DRAWING P5.02)

2 PROVIDE 1 1/4" ELECTRIC GAS SOLENOID VALVE (NORMALLY CLOSED). INTERFACE


ELECTRIC GAS SOLENOID WITH WITH EMERGENCY PANIC SHUT-OFF STATION. (REFER
TO SPECIFICATIONS)

3 FOR DOMESTIC WATER PIPING SIZES - REFER TO DOMESTIC WATER RISER DIAGRAM

4 PROVIDE TRAP PRIMER DISTRIBUTION VALVE AT CEILING (FOR MORE INFORMATION


ON TRAP PRIMER DISTRIBUTION VALVE REFER TO DETAIL ON DRAWING P5.1 AND
SPECIFICATION).

5 PROVIDE 1/2" TRAP PRIMER LINE DOWN IN CHASE, EXTEND 1/2" TRAP PRIMER LINE IN
PIPE SLEEVE BELOW SLAB ON GRADE AND CONNECT 1/2" TRAP PRIMER LINE TO TRAP
PRIMER CONNECTION OF FLOOR DRAIN. INSTALL TRAP PRIMER LINES WITH A 1/8" PER
FOOT SLOPE TO FLOOR DRAIN CONNECTION POINT.

6 PROVIDE 1 1/2" COLD WATER LINE, 3/4" HOT WATER LINE, AND 3/4" HOT WATER RETURN
LINE DOWN IN CHASE. PROVIDE 1" COLD WATER TO (W-4) WATER CLOSET AND RUN
1/2" COLD WATER HEADER TO (L-4) SINK. PROVIDE 1/2" HOT WATER TO (L-4)
LAVATORY.

7 PROVIDE 1/2" COLD WATER AND 1/2" HOT WATER DOWN TO THERMOSTATIC MIXING
VALVE. FOR MORE INFORMATION REFER TO DETAIL ON DRAWING P5.01

8 PROVIDE 1/2" TRAP PRIMER LINE DOWN IN WALL, EXTEND 1/2" TRAP PRIMER LINE IN
PIPE SLEEVE BELOW SLAB ON GRADE AND CONNECT 1/2" TRAP PRIMER LINE TO TRAP
PRIMER CONNECTION OF FLOOR DRAIN. INSTALL TRAP PRIMER LINES WITH A 1/8" PER
FOOT SLOPE TO FLOOR DRAIN CONNECTION POINT.

FOR PIPING AND EQUIPMENT


IN THIS AREA - REFER TO
ENLARGED PLAN ON DRAWING
P4.05

MECHANICAL/ELECTRICAL
020

4
2 1/2" GAS RISER 2 1/2"

1"HWR RETURN
A RISER
8
(TYPICAL) 3
SITE STORAGE
019 1/2"C-TO FIRE PIT

3 (TYPICAL) 3/4"G-UP TO FIRE PIT


W/GAS COCK ABOVE GRADE
G
3/4"

MATCHLINE
BLW GRADE

G
1"G-UP TO GRILL
1/2" W/GAS COCK ABOVE GRADE
4"
ABV CLG 1 1/4"G-DOWN
EMERGENCY SHUT-OFF
1 1/4"
(SEE SPECIFICATIONS)

G
B S
KITCHEN DESIGN TO FOLLOW DEN
AS SEPERATE SUBMISSION
FOR PIPING AND EQUIPMENT 2 010
IN THIS AREA - REFER TO ABV CLG 1/2"-DOWN
ENLARGED PLAN ON DRAWING P4.05 1/2" IN WALL
KITCHEN
017
COR.
016
MENS
014 D D

WH-1 C

BUFFET 3 (TYPICAL)
STORAGE C 1 1/2" 009 C 3/4"
1
017a G

WOMENS
015 G
SOCIAL SEATING AREA
008
B B 3"
C 3"
B
COMMUNAL AREA
BILLIARDS 011
013

DINING AREA BAR DESIGN TO FOLLOW


012 AS SEPERATE SUBMISSION

MATCHLINE
WH-1

PARTIAL GROUND FLOOR


DOMESTIC WATER AND GAS
PLUMBING
PARTIAL GROUND FLOOR PLAN
DOMESTIC WATER AND GAS - PLUMBING
01 SCALE: 1/8" = 1'-0"

P1.02A
KEYNOTES
1 EXPANSION LOOP (REFER TO DETAIL ON DRAWING P5.02)

2 PROVIDE 1 1/4" ELECTRIC GAS SOLENOID VALVE (NORMALLY CLOSED). INTERFACE


ELECTRIC GAS SOLENOID WITH WITH EMERGENCY PANIC SHUT-OFF STATION. (REFER
TO SPECIFICATIONS)

3 FOR DOMESTIC WATER PIPING SIZES - REFER TO DOMESTIC WATER RISER DIAGRAM

4 PROVIDE TRAP PRIMER DISTRIBUTION VALVE AT CEILING (FOR MORE INFORMATION


ON TRAP PRIMER DISTRIBUTION VALVE REFER TO DETAIL ON DRAWING P5.1 AND
SPECIFICATION).

5 PROVIDE 1/2" TRAP PRIMER LINE DOWN IN CHASE, EXTEND 1/2" TRAP PRIMER LINE IN
PIPE SLEEVE BELOW SLAB ON GRADE AND CONNECT 1/2" TRAP PRIMER LINE TO TRAP
PRIMER CONNECTION OF FLOOR DRAIN. INSTALL TRAP PRIMER LINES WITH A 1/8" PER
FOOT SLOPE TO FLOOR DRAIN CONNECTION POINT.

6 PROVIDE 1 1/2" COLD WATER LINE, 3/4" HOT WATER LINE, AND 3/4" HOT WATER RETURN
LINE DOWN IN CHASE. PROVIDE 1" COLD WATER TO (W-4) WATER CLOSET AND RUN
1/2" COLD WATER HEADER TO (L-4) SINK. PROVIDE 1/2" HOT WATER TO (L-4)
LAVATORY.

7 PROVIDE 1/2" COLD WATER AND 1/2" HOT WATER DOWN TO THERMOSTATIC MIXING
VALVE. FOR MORE INFORMATION REFER TO DETAIL ON DRAWING P5.01

8 PROVIDE 1/2" TRAP PRIMER LINE DOWN IN WALL, EXTEND 1/2" TRAP PRIMER LINE IN
PIPE SLEEVE BELOW SLAB ON GRADE AND CONNECT 1/2" TRAP PRIMER LINE TO TRAP
PRIMER CONNECTION OF FLOOR DRAIN. INSTALL TRAP PRIMER LINES WITH A 1/8" PER
FOOT SLOPE TO FLOOR DRAIN CONNECTION POINT.

REFUSE/
RECYCLE
052

WH-1

INDOOR POOL
049

WH-1
CORRIDOR
051 A (TYPICAL)
3
MATCHLINE

STAIR 2
FOR PIPING AND EQUIPMENT
IN THIS AREA - REFER TO
054
ENLARGED PLAN ON DRAWING
P4.05
WH-1
CORRIDOR
048

6
WORK AREA EMPLOYEE
022 LOUNGE
047 L-4
COMPUTER
023
5
W-4
B POOL TOILET
1/2"C-UP LAUNDRY 4
045 050
8
D
4 ELEVATOR D FITNESS
3 (TYPICAL)
LOBBY 040
TP 025 LINEN CORRIDOR
STORAGE MEETING ROOM E
STORAGE 038
043 OFFICE
C STORAGE 042 044
3/4"
G
024
MARKET 3"
004
PRE-FUNCTION CORRIDOR
G 026 030 G
1 1/2"
POOL EQUIPMENT
B B 039
3" B
B
3 (TYPICAL)
GM OFFICE
027
CORRIDOR
CORR. 035
028

SALES OFFICE
029
FOR PIPING AND EQUIPMENT
IN THIS AREA - REFER TO
ENLARGED PLAN ON DRAWING
P4.05
STORAGE
034
WH-1
MATCHLINE

WH-1

PARTIAL GROUND FLOOR


DOMESTIC WATER AND GAS
PLUMBING
PARTIAL GROUND FLOOR PLAN
DOMESTIC WATER AND GAS - PLUMBING
01 SCALE: 1/8" = 1'-0"
P1.02B
KEYNOTES:
1 FOR FIXTURES IN SUITE TOILET ROOMS AND KITCHEN - REFER TO 1/4" SCALE GUEST
ROOM FLOOR PLANS ON DRAWING P4.01, P4.02, AND P4.03. FOR PIPING - REFER TO
RISER DIAGRAMS.

2 FOR RISER SIZES - REFER TO DOMESTIC WATER RISER DIAGRAM

3 FOR STACK SIZES - REFER TO SANITARY WASTE AND VENT RISER DIAGRAM.

4 EXTEND 3/4" CONDENSATE DRAIN FROM AIR CONDITIONING UNIT AND CONNECT TO
RISER. REFER TO VERTICAL PACKAGED TERMINAL AIR CONDITIONING UNIT DETAIL ON
DRAWING P6.02.

5 PROVIDE 2" CONDENSATE DRAIN RISER FROM ABOVE, AFTER DRAIN LINE
CONNECTION ON THIS FLOOR EXTEND 2" CONDENSATE DRAIN LINE THROUGH

ELBOW AND REMOVABLE INSECT SCREEN. COORDINATE FINAL LOCATION WITH


OTHERS.

6 PROVIDE TRAP PRIMER DISTRIBUTION VALVE AT CEILING (FOR MORE INFORMATION


ON TRAP PRIMER DISTRIBUTION VALVE REFER TO DETAIL ON DRAWING P6.01 AND
SPECIFICATION).

7 PROVIDE 1/2" TRAP PRIMER LINE DOWN IN WALL, EXTEND 1/2" TRAP PRIMER LINE TO
TRAP PRIMER CONNECTION OF FLOOR DRAIN. INSTALL TRAP PRIMER LINES WITH A
1/8" PER FOOT SLOPE TO FLOOR DRAIN CONNECTION POINT.

8 TERMINATE 1 1/4" CONDENSATE DRAIN OVERFLOW LINE OVER FLOOR DRAIN


NOTE: W/APPROVED AIR GAP.
ALL SANITARY, CONDENSATE DRAIN, AND
SECONDARY CONDENSATE DRAIN LINES
OVER PUBLIC SPACES TO BE INSULATED.

5 4 (TYPICAL)
4"RD-1
(703 SQ/FT)

1 5

4"RD-1
(408 SQ/FT)

QQ
TYPE 1 CO
202 CO
4"RD-1 1
(1014 SQ/FT)

2 1/2" GAS RISER 4"V

QQ
TYPE 1
201 4"RD-1
A CO
(825 SQ/FT)
2 3 (TYPICAL)
CO
5 1"HWR RETURN
RISER
6"RWC-DOWN
CO (2186 SQ/FT)
3"V
1
(TYPICAL) 3"RD-1
(380 SQ/FT)

MATCHLINE
4"RD-1
(910 SQ/FT)
STAIR 1 5
253 2"CDL-DN
5 5

CO CO

B CO CDL
2"

1 BLW FLR
4"VS
CORRIDOR 6"RWC-DOWN 2 3 (TYPICAL)
240 (4354 SQ/FT) (TYPICAL) 8"RWC-DOWN
KDL
(5466 SQ/FT)
CO
212
(TYPICAL) 4 3 KD
CO 4"WS-FRM ABV KD 6"RWC-DOWN QQ TYPE 2
CO
QQA TYPE 2
TYPE 1 (2627 SQ/FT) 216
CO 208 D 5 214 D 5
1 1 4"WS-DN 210 CO CO
STORAGE
CO
237
C
C 4
4
CO CO CO
C
K
TYPE 1 CO
205
CORRIDOR
CO CO
241
C B 2 B CO B

ELECTRICAL CO
ROOM CO CO CO CO
5 2 5
236 5
3 4"VS

K
TYPE 2
206 KS KS KS
(TYPICAL)
KS 2 3 (TYPICAL) KS 211 213 215 217
207 209

3"RD-1
(940 SQ/FT)
CO

MATCHLINE
1
(TYPICAL) 4
3"RD-1
(332 SQ/FT)

PARTIAL SECOND FLOOR


PLUMBING

PARTIAL SECOND FLOOR PLAN


PLUMBING
01 SCALE: 1/8" = 1'-0"

P1.03A
KEYNOTES:
1 FOR FIXTURES IN SUITE TOILET ROOMS AND KITCHEN - REFER TO 1/4" SCALE GUEST
ROOM FLOOR PLANS ON DRAWING P4.01, P4.02, AND P4.03. FOR PIPING - REFER TO
RISER DIAGRAMS.

2 FOR RISER SIZES - REFER TO DOMESTIC WATER RISER DIAGRAM

3 FOR STACK SIZES - REFER TO SANITARY WASTE AND VENT RISER DIAGRAM.

4 EXTEND 3/4" CONDENSATE DRAIN FROM AIR CONDITIONING UNIT AND CONNECT TO
RISER. REFER TO VERTICAL PACKAGED TERMINAL AIR CONDITIONING UNIT DETAIL ON
DRAWING P6.02.

5 PROVIDE 2" CONDENSATE DRAIN RISER FROM ABOVE, AFTER DRAIN LINE
CONNECTION ON THIS FLOOR EXTEND 2" CONDENSATE DRAIN LINE THROUGH

ELBOW AND REMOVABLE INSECT SCREEN. COORDINATE FINAL LOCATION WITH


OTHERS.

6 PROVIDE TRAP PRIMER DISTRIBUTION VALVE AT CEILING (FOR MORE INFORMATION


ON TRAP PRIMER DISTRIBUTION VALVE REFER TO DETAIL ON DRAWING P6.01 AND
SPECIFICATION).

7 PROVIDE 1/2" TRAP PRIMER LINE DOWN IN WALL, EXTEND 1/2" TRAP PRIMER LINE TO
TRAP PRIMER CONNECTION OF FLOOR DRAIN. INSTALL TRAP PRIMER LINES WITH A
1/8" PER FOOT SLOPE TO FLOOR DRAIN CONNECTION POINT.
NOTE:
8 TERMINATE 1 1/4" CONDENSATE DRAIN OVERFLOW LINE OVER FLOOR DRAIN
ALL SANITARY, CONDENSATE DRAIN, AND
W/APPROVED AIR GAP.
SECONDARY CONDENSATE DRAIN LINES
OVER PUBLIC SPACES TO BE INSULATED.

4 (TYPICAL)
4"RD-1
(1025 SQ/FT)

1
CO 5

1
CO

4"RD-1 (TYPICAL)
(1170 SQ/FT)
A

3"RD-1 CO
(380 SQ/FT) 5
MATCHLINE

(TYPICAL)
STAIR 2
5 4
5 254
CO CORRIDOR
2"CDL-DN 1 1/4"CDL RISER 2"CDL-DN 2"CDL-DN 1 243
CO 1 AHU-1 BY OTHERS
2"
CO CO
BLW FLR 2" 2"
CO BLW FLR BLW FLR CO
6
3"FD-7

SW 4"RD-1
TP (TYPICAL) (1014 SQ/FT)
2 3 B
8"RWC-DOWN CO
(5466 SQ/FT) 6"RWC-DOWN
HOUSE (2665 SQ/FT) KDA 5
KD KD 7 ELEV KEEPING
TYPE 2 TYPE 2 QQ 1 KD 5 KD 228
(TYPICAL) TYPE 2 1 1/4"SW RISER 235 TYPE 1 TYPE 1
216 D 5 218 CO
CO 220 224 226
ELEVATOR CO
CO 2 3 (TYPICAL) LOBBY D
4 234 4"FD-1
ELEV
2 E 2 3 (TYPICAL)
CO
CO
4 1
CO
C CO
CORRIDOR 6"RWC-DOWN
2 (2606 SQ/FT)
B 2 CO B CO 2 B CO
CO
4"VS-UP B

3"VS-UP
CO CO CO
5 5 CO CO
5 5
1
4"VS
KS
CORNER
229
KS KS KS KS KS (TYPICAL)
217 219 221 223 225
MATCHLINE

3"RD-1 4 (TYPICAL)
(332 SQ/FT)

PARTIAL SECOND FLOOR


PLUMBING

PARTIAL SECOND LEVEL FLOOR PLAN


PLUMBING
01 SCALE: 1/8" = 1'-0"

P1.03B
4 (TYPICAL)

QQ
TYPE 1
302
1

2 1/2" GAS RISER

QQ
TYPE 1
301
A
2 3 (TYPICAL)

5 1"HWR RETURN
RISER
6"RWC-DOWN
(2186 SQ/FT)

1
(TYPICAL)

MATCHLINE
STAIR 1
353
5

1
4"VS
2 3 (TYPICAL)
6"RWC-DOWN
(4354 SQ/FT) (TYPICAL) KDL 8"RWC-DOWN
CORRIDOR
(5466 SQ/FT)
340 312
(TYPICAL) 4 3 KD
4"WS KD 6"RWC-DOWN QQ TYPE 2
QQA TYPE 2
TYPE 1 (2627 SQ/FT) 316
308 D 5 314 D 5
1 STORAGE 1 310
337
C
C 4
4
ICE C
K 344
TYPE 1
305
REFER TO ICE MACHINE DETAIL CORRIDOR
ON DRAWING P6.02 341
C B 2 5 B 2 B

STORAGE
ROOM
5
336 5
3 4"VS

K
TYPE 2
306 KS KS KS
(TYPICAL)
KS 2 3 (TYPICAL) KS 311 313 315 317
307 309

MATCHLINE
1
(TYPICAL) 4

PARTIAL THIRD FLOOR


PLUMBING

PARTIAL THIRD FLOOR PLAN


PLUMBING
01 SCALE: 1/8" = 1'-0"

P1.04A
4 (TYPICAL)

(TYPICAL)

5
MATCHLINE

4 (TYPICAL) STAIR 2
354 CORRIDOR 6"RWC-DOWN
SSAHU-2 BY OTHERS 1 343 (2098 SQ/FT)
1

1 1/4"CDL RISER
5
MAINTENANCE
333 (TYPICAL)
6
2 3 B 2 3 (TYPICAL)
8"RWC-DOWN
(5466 SQ/FT) 6"RWC-DOWN
HOUSE (2665 SQ/FT) KDA 5
KD KD 1 1/4"SW RISER ELEV KEEPING
TYPE 2 TYPE 2 QQ 1 KD KD 328
(TYPICAL) TYPE 2 335 TYPE 1 TYPE 1 STORAGE
316 D 5 318
320 324 5 326 338
ELEVATOR
2 3 (TYPICAL) LOBBY D
4 4"FD-1
334 ELEV
2 E

4 1

C 6"RWC-DOWN
CORRIDOR
(2606 SQ/FT)
B 2 B 2 B 2
4"VS-UP B

3"VS-UP

5 5 5 5
1
4"VS
KS
CORNER
329
KS KS KS KS KS KSA (TYPICAL)
317 319 321 323 325 TYPE 1
327
MATCHLINE

4 (TYPICAL)

PARTIAL THIRD FLOOR


PLUMBING

PARTIAL THIRD FLOOR PLAN


PLUMBING
01 SCALE: 1/8" = 1'-0"

P1.04B
4 (TYPICAL)

QQ
TYPE 1 1
402

2 1/2" GAS RISER

QQ
TYPE 1
401
A
2 3 (TYPICAL)

5 ___"HWR RETURN
RISER
6"RWC-DOWN
(2186 SQ/FT)

1
(TYPICAL)

MATCHLINE
STAIR 1
453
5

B
LINT INTERCEPTOR
(LI-2) 1
4"VS
2 3 (TYPICAL)
6"RWC-DOWN
(4354 SQ/FT) (TYPICAL) KDL 8"RWC-DOWN
CORRIDOR
(5466 SQ/FT)
440 412
(TYPICAL) 4 3 QQS KD
4"WS TYPE 3 KD 6"RWC-DOWN QQ TYPE 2
2"W-FRM ABV TYPE 2
408 TYPE 1 (2627 SQ/FT) 416
D 5 414 D 5
1 1 410
STORAGE
C 437
C 4
4
C
K
TYPE 1
405
CORRIDOR
5 B 441
C B 2 2 B

STORAGE
ROOM 5
436 5
3 4"VS

K
TYPE 2
406 KS KS KS
(TYPICAL)
KS 2 3 (TYPICAL) KS 411 413 415 417
407 409

MATCHLINE
1
(TYPICAL) 4

PARTIAL FOURTH FLOOR


PLUMBING

PARTIAL FOURTH FLOOR PLAN


PLUMBING
01 SCALE: 1/8" = 1'-0"

P1.05A
4 (TYPICAL)

(TYPICAL)

5
MATCHLINE

4 (TYPICAL) STAIR 2
454 CORRIDOR 6"RWC-DOWN
1 443 (2098 SQ/FT)
1 SSAHU-2 BY OTHERS

1 1/4"CDL RISER
5
CATV/
PBX
433 2 3 (TYPICAL)
6
B 2 3 (TYPICAL)
8"RWC-DOWN
(5466 SQ/FT) 6"RWC-DOWN KD
HOUSE TYPE 3 5
KD KD 1 1/4"SW RISER ELEV KEEPING
(2665 SQ/FT)
TYPE 2 TYPE 2 QQ 1 KD 5 KD 428
(TYPICAL) TYPE 2 435 TYPE 1 TYPE 1 STORAGE
416 D 5 418
420 424 426 438
ELEVATOR
2 3 (TYPICAL) LOBBY D
4 434 ELEV
2 E

4 1

C 6"RWC-DOWN
CORRIDOR
(2606 SQ/FT)
B 2 B 2 B 2
4"VS-UP B

3"VS-UP

5 5 5 5
1
4"VS
KS
CORNER
429
KS KS KS KS KS KSA (TYPICAL)
417 419 421 423 425 TYPE 1
427
MATCHLINE

4 (TYPICAL)

PARTIAL FOURTH FLOOR


PLUMBING

PARTIAL FOURTH FLOOR PLAN


PLUMBING
01 SCALE: 1/8" = 1'-0"

P1.05B
1

4 (TYPICAL)

1 3"V-UP
3"VTR

3"V-UP
3"V-UP
QQ
TYPE 1
ABV CLG
502 1
6"RWC-DOWN
(2186 SQ/FT)
4"V-UP
2 1/2" GAS RISER 4"VTR

QQ
TYPE 1
501
A (TYPICAL)
2 3

___"HWR-DOWN
5

1 ABV CLG
(TYPICAL)

MATCHLINE
4"V-UP
4"VTR
STAIR 1 3"V-UP
5 553 3"VTR

4"V-UP 1
2"W-DN FRM BLW
2 3 (TYPICAL)
6"RWC-DOWN (TYPICAL) KDL 8"RWC-DOWN
CORRIDOR (4354 SQ/FT) (5466 SQ/FT)
540 512
(TYPICAL) 4 3 6"V-UP KD 6"V-UP
QQS KD 6"RWC-DOWN QQ TYPE 2 6"VTR
6"VTR
ABV CLG TYPE 1 (2627 SQ/FT) TYPE 2
4"WS-DOWN508 510
D 5 514
516
D 5
1 1 4"V-UP
GUEST
LAUNDRY/ 4"VTR
3"V-UP
3"VTR C ICE BLW FLR
537CO C C 4
REFER TO ICE MACHINE DETAIL 3/4"C-UP 4
WATER HAMMER
ON DRAWING P5.02 TO RH-1 ARRESTER SIZE 'A'
K CO (TYPICAL FOR 2)
TYPE 1
5
505
CORRIDOR
541
C
ABV CLG B 2 B B

ELECTRICAL
ROOM 5 2 5
536 6"V-UP
3 6"VTR 5 ABV CLG ABV CLG

K
TYPE 2 4"VS
6"V-UP 6"V-UP
506 KS 6"VTR KS KS
(TYPICAL) 6"VTR
KS 2 3 (TYPICAL) KS 511 513 515 517
507 509

3"V-UP

MATCHLINE
3"VTR 1
(TYPICAL) 4

PARTIAL FIFTH FLOOR


PLUMBING

PARTIAL FIFTH FLOOR PLAN


PLUMBING
01 SCALE: 1/8" = 1'-0"

P1.06A
1

4 (TYPICAL)

ABV CLG

ABV CLG (TYPICAL)

4"V-UP
A 4"VTR

ABV CLG
5
MATCHLINE

4 (TYPICAL) STAIR 2
554
CORRIDOR 6"RWC-DOWN
1 543
3"V-UP (2098 SQ/FT)
1 3"VTR

2 3 (TYPICAL)
B 2 3 (TYPICAL)
8"RWC-DOWN
(5466 SQ/FT) ABV CLG 6"RWC-DOWN KD
HOUSE (2665 SQ/FT) TYPE 3 5
KD 6"V-UP KD ELEV KEEPING
QQ KD KD 528
TYPE 2 6"VTR TYPE 2 (TYPICAL) 1 535
TYPE 2 TYPE 1 TYPE 1 STORAGE 6"V-UP
516 518 5 6"VTR
D 5 520 524 526 538
ELEVATOR
ABV CLG
2 3 (TYPICAL) LOBBY D
4 534 ELEV 6"V-UP E
2 6"VTR
ABV CLG
4 1

C 5
CORRIDOR
2 B 6"RWC-DOWN
B 2 B ABV CLG 2 B (2606 SQ/FT)

4"V-UP 3"V-UP
5 5 5 4"VTR 5 3"V-UP 3"VTR
ABV CLG ABV CLG 3"VTR
ABV CLG

KS 1
4"VS
CORNER
6"V-UP 6"V-UP 6"V-UP 529
6"VTR KS KS 6"VTR KS KS 6"VTR KS (TYPICAL)
KSA
517 519 521 523 525 TYPE 2
527
MATCHLINE

4 (TYPICAL)

PARTIAL FIFTH FLOOR


PLUMBING

PARTIAL FIFTH FLOOR PLAN


PLUMBING
01 SCALE: 1/8" = 1'-0"

P1.06B
3"V-UP
3"VTR

2 1/2" GAS RISER


6"RD-1
(2186 SQ/FT)

4"V

6"RWC-DOWN
(2186 SQ/FT)

MATCHLINE
ON ROOF
2 1/2"

G
4"V 3"V

4"V
6"RWC-DOWN
(4354 SQ/FT)

6"RWC-DOWN 8"RWC-DOWN
(2627 SQ/FT) (5466 SQ/FT)

6"V
3"V-UP 6"RD-1 BLW ROOF 6"V
8"
3"VTR (4354 SQ/FT) 6" 6"RD-1
6"RD-1 BLW ROOF (2741 SQ/FT) BLW ROOF
(2627 SQ/FT)
6" 6"

ON ROOF
G G

2" 2"
RTU-1 BY OTHERS 6"V 6"V

6"V

MATCHLINE
PARTIAL ROOF PLAN
PLUMBING

PARTIAL ROOF PLAN


PLUMBING
01 SCALE: 1/8" = 1'-0"

P1.07A
4"V

6"RD-1
(2098 SQ/FT)
MATCHLINE

BLW ROOF
6"

6"RWC-DOWN
(2098 SQ/FT)

3"V

8"RWC-DOWN 6"RWC-DOWN 6"V


(5466 SQ/FT) (2665 SQ/FT)

6"V
6"V
RH-1
8"
BLW ROOF RTU-2 BY OTHERS
BLW ROOF BLW ROOF
6"
6" 6"

6"RD-1
6"RD-1 6"RD-1 (2606 SQ/FT)
(2725 SQ/FT) (2665 SQ/FT) BLW ROOF
ON ROOF 6"
G G
3"V 3"V
2"
6"RWC-DOWN
6"V (2606 SQ/FT)
6"V 6"V

4"V
MATCHLINE

PARTIAL ROOF PLAN


PLUMBING

PARTIAL ROOF PLAN


PLUMBING
01 SCALE: 1/8" = 1'-0"

P1.07B
KEYNOTES
PROVIDE CPVC TO PEX MANIFOLD ABOVE CEILING. COORDINATE LOCATION, SIZE AND
ACCESS OF PEX MANIFOLD WITH GENERAL CONTRACTOR.

MAIN COLD AND HOT WATER RISERS. FOR SIZES REFER TO RISER DIAGRAMS.

PROVIDE 1/2" (PEX) HOT AND COLD WATER TO SHOWER CONTROL VALVE. PROVIDE 1/2"
(PEX) SHOWER SUPPLY LINES TO SHOWER HEAD FROM CONTROL VALVE. REFER TO
ARCHTECTURAL DRAWINGS FOR LOCATIONS.

MAIN SOIL STACK. FOR SOIL AND VENT STACK SIZES REFER TO RISER DIAGRAM.

NOTES:
1. WATER CLOSET FLUSH HANDLES IN ADA GUESTROOM BATHS TO BE
PLACED ON THE SIDE OF THE TANK THAT FACES THE OPEN SIDE OF THE
ROOM.

2. THE CONTRACTOR SHALL COORDINATE FLOOR, WALL AND ROOF


PENETRATIONS WITH GENERAL CONTRACTOR.

3. FOR CONTROL VALVE AND SHOWER HEAD LOCATIONS REFER TO


ARCHITECTURAL DRAWINGS. (UNIT PLANS)

SH-1
L-1
4
4
4 W-1 2

4
1
L-1 W-1
S-1
S-1
DISHWASHER
1 SH-1

DISHWASHER

REFRIGERATOR

W-1 L-1

DISHWASHER
4

S-1
2

SH-1

GUEST ROOM PLAN


CUSTOM 2
01 SCALE: 1/4" = 1'-0"
GUEST ROOM PLAN
CUSTOM 3
02 SCALE: 1/4" = 1'-0"

GUEST ROOM PLAN


K - TYPE 1
03 SCALE: 1/4" = 1'-0"

4
4

S-1
BT-1

DISHWASHER 1

W-1
L-1

NOTE:
1. ROUTING OF WASTE AND VENT PIPING NOT SHOWN ON SUITE PLANS.
FOR WASTE AND VENT PIPING SIZES - REFER TO RISER DIAGRAM ON
DRAWING P5.03 THROUGH P5.07, AND PIPING SCHEDULE ON DRAWING
P7.01. (REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR
CEILING HEIGHTS AND BULKHEADS)

2. TYPICAL SUITE LAYOUT ON THIS SHEET. SANITARY SEWER WILL BE


DIFFERENT AT BOTTOM FLOOR (BOTTOM OF STACK) - REFER TO
GROUND FLOOR PLAN, SECOND LEVEL PLAN AND SANITARY SEWER
RISER DIAGRAM TO COORDINATE WHERE THIS OCCURS.

3. ROUTING OF PEX TUBING NOT SHOWN ON SUITE PLANS. REFER TO


SPECIFICATIONS AND REFER TO SCHEMATIC DIAGRAM ON DRAWING
P6.03. CHROME TO PEX TRANSITION FITTINGS SHALL BE PROVIDED AT
ALL ROUGH-IN'S AT LOCATIONS WHERE FIXTURES ARE SUPPLIED BY
PEX TUBING. FOR PIPING SIZES - REFER TO DOMESTIC WATER RISER
* SIMILAR TO K-TYPE 1 DIAGRAM ON DRAWING P5.01 THROUGH P5.02 .

4. WHERE SUITES ARE BACK TO BACK AND ONE (1) SET OF WATER RISERS
FEED TWO (2) SUITES, ONE (1) PEX MANIFOLD WILL SUPPLY BOTH
SUITES PER FLOOR. REFER TO FLOOR PLANS AND RISER DIAGRAM
GUEST ROOM PLAN GUEST ROOM PLAN FOR LOCATIONS WHERE THIS OCCURS. GUESTROOM TYPES
K - TYPE 3 FLOOR PLANS
04 K - TYPE 2
SCALE: 1/4" = 1'-0" 05 SCALE: 1/4" = 1'-0"
PLUMBING

P4.01
KEYNOTES
PROVIDE CPVC TO PEX MANIFOLD ABOVE CEILING. COORDINATE LOCATION, SIZE AND
ACCESS OF PEX MANIFOLD WITH GENERAL CONTRACTOR.

MAIN COLD AND HOT WATER RISERS. FOR SIZES REFER TO RISER DIAGRAMS.

PROVIDE 1/2" (PEX) HOT AND COLD WATER TO SHOWER CONTROL VALVE. PROVIDE 1/2"
(PEX) SHOWER SUPPLY LINES TO SHOWER HEAD FROM CONTROL VALVE. REFER TO
ARCHTECTURAL DRAWINGS FOR LOCATIONS.

MAIN SOIL STACK. FOR SOIL AND VENT STACK SIZES REFER TO RISER DIAGRAM.

NOTES:
1. WATER CLOSET FLUSH HANDLES IN ADA GUESTROOM BATHS TO BE
PLACED ON THE SIDE OF THE TANK THAT FACES THE OPEN SIDE OF THE
ROOM.

2. THE CONTRACTOR SHALL COORDINATE FLOOR, WALL AND ROOF


PENETRATIONS WITH GENERAL CONTRACTOR.

3. FOR CONTROL VALVE AND SHOWER HEAD LOCATIONS REFER TO


ARCHITECTURAL DRAWINGS. (UNIT PLANS)

2
4

W-1 SH-1 SH-1


L-1

L-1
W-1

* SIMILAR TO KD-TYPE 1 * SIMILAR TO KD-TYPE 1 * SIMILAR TO KDA

GUEST ROOM PLAN GUEST ROOM PLAN GUEST ROOM PLAN GUEST ROOM PLAN
KD - SIM KD - TYPE 1 KD - TYPE 2 KD - TYPE 3
01 SCALE: 1/4" = 1'-0" 02 SCALE: 1/4" = 1'-0" 03 SCALE: 1/4" = 1'-0" 04 SCALE: 1/4" = 1'-0"

NOTE:
1. ROUTING OF WASTE AND VENT PIPING NOT SHOWN ON SUITE PLANS.
FOR WASTE AND VENT PIPING SIZES - REFER TO RISER DIAGRAM ON
DRAWING P5.03 THROUGH P5.07, AND PIPING SCHEDULE ON DRAWING
P7.01. (REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR
CEILING HEIGHTS AND BULKHEADS)

2. TYPICAL SUITE LAYOUT ON THIS SHEET. SANITARY SEWER WILL BE


SH-2 DIFFERENT AT BOTTOM FLOOR (BOTTOM OF STACK) - REFER TO
GROUND FLOOR PLAN, SECOND LEVEL PLAN AND SANITARY SEWER
RISER DIAGRAM TO COORDINATE WHERE THIS OCCURS.
4"FD-1
3. ROUTING OF PEX TUBING NOT SHOWN ON SUITE PLANS. REFER TO
SPECIFICATIONS AND REFER TO SCHEMATIC DIAGRAM ON DRAWING
P6.03. CHROME TO PEX TRANSITION FITTINGS SHALL BE PROVIDED AT
ALL ROUGH-IN'S AT LOCATIONS WHERE FIXTURES ARE SUPPLIED BY
L-2 PEX TUBING. FOR PIPING SIZES - REFER TO DOMESTIC WATER RISER
W-2 DIAGRAM ON DRAWING P5.01 THROUGH P5.02 .
* SIMILAR TO KD-TYPE 1 * SIMILAR TO KD-TYPE 1
4. WHERE SUITES ARE BACK TO BACK AND ONE (1) SET OF WATER RISERS
FEED TWO (2) SUITES, ONE (1) PEX MANIFOLD WILL SUPPLY BOTH
SUITES PER FLOOR. REFER TO FLOOR PLANS AND RISER DIAGRAM
1 4 2 FOR LOCATIONS WHERE THIS OCCURS. GUESTROOM TYPES
FLOOR PLANS
PLUMBING
GUEST ROOM PLAN GUEST ROOM PLAN GUEST ROOM PLAN
KD KD - L KDA
05 SCALE: 1/4" = 1'-0" 06 SCALE: 1/4" = 1'-0" 07 SCALE: 1/4" = 1'-0"
P4.02
KEYNOTES
PROVIDE CPVC TO PEX MANIFOLD ABOVE CEILING. COORDINATE LOCATION, SIZE AND
ACCESS OF PEX MANIFOLD WITH GENERAL CONTRACTOR.

MAIN COLD AND HOT WATER RISERS. FOR SIZES REFER TO RISER DIAGRAMS.

PROVIDE 1/2" (PEX) HOT AND COLD WATER TO SHOWER CONTROL VALVE. PROVIDE 1/2"
(PEX) SHOWER SUPPLY LINES TO SHOWER HEAD FROM CONTROL VALVE. REFER TO
ARCHTECTURAL DRAWINGS FOR LOCATIONS.

MAIN SOIL STACK. FOR SOIL AND VENT STACK SIZES REFER TO RISER DIAGRAM.

NOTES:
1. WATER CLOSET FLUSH HANDLES IN ADA GUESTROOM BATHS TO BE
PLACED ON THE SIDE OF THE TANK THAT FACES THE OPEN SIDE OF THE
ROOM.

2. THE CONTRACTOR SHALL COORDINATE FLOOR, WALL AND ROOF


PENETRATIONS WITH GENERAL CONTRACTOR.

3. FOR CONTROL VALVE AND SHOWER HEAD LOCATIONS REFER TO


ARCHITECTURAL DRAWINGS. (UNIT PLANS)

DISHWASHER

GUEST ROOM PLAN GUEST ROOM PLAN


KS KSA - TYPE 1
02 SCALE: 1/4" = 1'-0" 03 SCALE: 1/4" = 1'-0"

GUEST ROOM PLAN


KS - CORNER
01 SCALE: 1/4" = 1'-0"

NOTE:
1. ROUTING OF WASTE AND VENT PIPING NOT SHOWN ON SUITE PLANS.
FOR WASTE AND VENT PIPING SIZES - REFER TO RISER DIAGRAM ON
DRAWING P5.03 THROUGH P5.07, AND PIPING SCHEDULE ON DRAWING
P7.01. (REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR
CEILING HEIGHTS AND BULKHEADS)

2. TYPICAL SUITE LAYOUT ON THIS SHEET. SANITARY SEWER WILL BE


DIFFERENT AT BOTTOM FLOOR (BOTTOM OF STACK) - REFER TO
GROUND FLOOR PLAN, SECOND LEVEL PLAN AND SANITARY SEWER
RISER DIAGRAM TO COORDINATE WHERE THIS OCCURS.

3. ROUTING OF PEX TUBING NOT SHOWN ON SUITE PLANS. REFER TO


SPECIFICATIONS AND REFER TO SCHEMATIC DIAGRAM ON DRAWING
P6.03. CHROME TO PEX TRANSITION FITTINGS SHALL BE PROVIDED AT
ALL ROUGH-IN'S AT LOCATIONS WHERE FIXTURES ARE SUPPLIED BY
PEX TUBING. FOR PIPING SIZES - REFER TO DOMESTIC WATER RISER
DIAGRAM ON DRAWING P5.01 THROUGH P5.02 .
* SIMILAR TO KSA - TYPE 1 * SIMILAR TO KSA - TYPE 1
4. WHERE SUITES ARE BACK TO BACK AND ONE (1) SET OF WATER RISERS
FEED TWO (2) SUITES, ONE (1) PEX MANIFOLD WILL SUPPLY BOTH
SUITES PER FLOOR. REFER TO FLOOR PLANS AND RISER DIAGRAM
FOR LOCATIONS WHERE THIS OCCURS. GUESTROOM TYPES
FLOOR PLANS
GUEST ROOM PLAN GUEST ROOM PLAN PLUMBING
KSA - TYPE 2 KSA
04 SCALE: 1/4" = 1'-0" 05 SCALE: 1/4" = 1'-0"

P4.03
KEYNOTES
PROVIDE CPVC TO PEX MANIFOLD ABOVE CEILING. COORDINATE LOCATION, SIZE AND
ACCESS OF PEX MANIFOLD WITH GENERAL CONTRACTOR.

MAIN COLD AND HOT WATER RISERS. FOR SIZES REFER TO RISER DIAGRAMS.

PROVIDE 1/2" (PEX) HOT AND COLD WATER TO SHOWER CONTROL VALVE. PROVIDE 1/2"
(PEX) SHOWER SUPPLY LINES TO SHOWER HEAD FROM CONTROL VALVE. REFER TO
ARCHTECTURAL DRAWINGS FOR LOCATIONS.

MAIN SOIL STACK. FOR SOIL AND VENT STACK SIZES REFER TO RISER DIAGRAM.

NOTES:
1. WATER CLOSET FLUSH HANDLES IN ADA GUESTROOM BATHS TO BE
PLACED ON THE SIDE OF THE TANK THAT FACES THE OPEN SIDE OF THE
ROOM.

2. THE CONTRACTOR SHALL COORDINATE FLOOR, WALL AND ROOF


PENETRATIONS WITH GENERAL CONTRACTOR.

3. FOR CONTROL VALVE AND SHOWER HEAD LOCATIONS REFER TO


ARCHITECTURAL DRAWINGS. (UNIT PLANS)

REFRIGERATOR

S-1

DISHWASHER

REFRIGERATOR

W-1

L-1 1

4 BT-1

* SIMILAR TO QQ - TYPE 1 * SIMILAR TO QQ - TYPE 1 GUEST ROOM PLAN


QQ - TYPE 3
04 SCALE: 1/4" = 1'-0"

GUEST ROOM PLAN GUEST ROOM PLAN GUEST ROOM PLAN


QQ - CUSTOM QQ - TYPE 1 QQ - TYPE 2
01 SCALE: 1/4" = 1'-0" 02 SCALE: 1/4" = 1'-0" 03 SCALE: 1/4" = 1'-0"

NOTE:
1. ROUTING OF WASTE AND VENT PIPING NOT SHOWN ON SUITE PLANS.
FOR WASTE AND VENT PIPING SIZES - REFER TO RISER DIAGRAM ON
DRAWING P5.03 THROUGH P5.07, AND PIPING SCHEDULE ON DRAWING
P7.01. (REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR
CEILING HEIGHTS AND BULKHEADS)

2. TYPICAL SUITE LAYOUT ON THIS SHEET. SANITARY SEWER WILL BE


DIFFERENT AT BOTTOM FLOOR (BOTTOM OF STACK) - REFER TO
GROUND FLOOR PLAN, SECOND LEVEL PLAN AND SANITARY SEWER
RISER DIAGRAM TO COORDINATE WHERE THIS OCCURS.

3. ROUTING OF PEX TUBING NOT SHOWN ON SUITE PLANS. REFER TO


SPECIFICATIONS AND REFER TO SCHEMATIC DIAGRAM ON DRAWING
P6.03. CHROME TO PEX TRANSITION FITTINGS SHALL BE PROVIDED AT
ALL ROUGH-IN'S AT LOCATIONS WHERE FIXTURES ARE SUPPLIED BY
PEX TUBING. FOR PIPING SIZES - REFER TO DOMESTIC WATER RISER
DIAGRAM ON DRAWING P5.01 THROUGH P5.02 .

4. WHERE SUITES ARE BACK TO BACK AND ONE (1) SET OF WATER RISERS
FEED TWO (2) SUITES, ONE (1) PEX MANIFOLD WILL SUPPLY BOTH
* SIMILAR TO QQ - TYPE 1 * SIMILAR TO QQ - TYPE 3
SUITES PER FLOOR. REFER TO FLOOR PLANS AND RISER DIAGRAM
* SIMILAR TO QQ - TYPE 3
FOR LOCATIONS WHERE THIS OCCURS. GUESTROOM TYPES
FLOOR PLANS
PLUMBING
GUEST ROOM PLAN GUEST ROOM PLAN GUEST ROOM PLAN
QQ QQA QQS
05 SCALE: 1/4" = 1'-0" 06 SCALE: 1/4" = 1'-0" 07 SCALE: 1/4" = 1'-0"

P4.04
KEY NOTES:
1 PROVIDE 1 1/2" GAS LINE DOWN AND CONNECT TO POOL HEATER GAS TRAIN. POOL HEATER AND GAS TRAIN TO BE
PROVIDED BY OTHERS. PLUMBING CONTRACTOR SHALL COORDINATE EXACT CONNECTION POINT OF GAS LINE TO POOL
HEATER WITH OTHER CONTRACTORS.

2 PROVIDE A 3" POOL WATER MAKE-UP WATER CONNECTION WITH 3" BALL VALVE, 3" STRAINER. 3" DOUBLE CHECK VALVE
TYPE BACKFLOW PREVENTER AND REMOVABLE END CAP. COORDINATE EXACT LOCATION OF POOL WATER MAKE-UP
CONNECTION WITH OTHER CONTRACTORS.

3 LINT INTERCEPTOR, IN FLOOR (FOR MORE INFORMATION REFER TO SPECIFICATIONS)

4 PROVIDE LOCKABLE BALL VALVES WITH IDENTIFICATION ON HOT AND COLD WATER MAINS SUPPLYING EMERGENCY
EYEWASH UNIT.

5 PROVIDE 1/2" TEMPERED WATER LINE, 2" WASTE LINE DOWN IN WALL AND 2" VENT PIPING UP IN WALL TO SERVE
EMERGENCY EYEWASH (EF-1). FOR MORE INFORMATION REFER TO FIXTURE SCHEDULES ON DRAWING P7.01,AND DETAIL
ON DRAWING P6.01 AND SPECIFICATION.
GAS METER, GAS REGULATOR AND RELATED VALVING 22 2 1/2" 2"
PER GAS COMPANY STANDARDS. TOTAL CONNECTED DOMESTIC HOT WATER HEATERS 2"W-DN
4"RD-FRM ABV 1 1/2" 6 PROVIDE 1/2" COLD WATER AND 1/2" HOT WATER DOWN TO THERMOSTATIC MIXING VALVE. FOR MORE INFORMATION REFER
GAS LOAD 4038 CFH 14"WC (MINIMUM) 27 BLW GRADE REFER TO DETAIL ON DRAWING P5.03 TO DETAIL ON DRAWING P6.01
(703 SQ/FT) HB-2
4"
22 4"SS CO 7 PROVIDE A 1" CAPPED COLD WATER CONNECTION WITH REDUCED PRESSURE ZONE BACKFLOW PREVENTER, AND
4" 4"VS-UP
STRAINER FOR HVAC SYSTEM WATER MAKE-UP. FOUNTAIN SYSTEM TO BE FURNISHED AND INSTALLED BY OTHERS
13 4"
8 PROVIDE TRAP PRIMER DISTRIBUTION VALVE AT CEILING (FOR MORE INFORMATION ON TRAP PRIMER DISTRIBUTION VALVE
6" 6" 3" 2" 1 1/2" 3/4" CO L-3 L-3 COR.
3/4" REFER TO DETAIL ON DRAWING P6.01 AND SPECIFICATION).
G G 4"RD-FRM ABV
(TYPICAL)
(408 SQ/FT) 4" 016
GAS METER, GAS REGULATOR AND RELATED VALVING 2" 9 PROVIDE TRAP PRIMER DISTRIBUTION VALVE ABOVE CEILING (FOR MORE INFORMATION ON TRAP PRIMER DISTRIBUTION
4" 4"
PER GAS COMPANY STANDARDS. TOTAL CONNECTED 4"WS VALVE REFER TO DETAIL ON DRAWING P6.01 AND SPECIFICATION).
GAS LOAD 1200 CFH 14"WC (MINIMUM) 4" 3"
4" CO
WH-1 10 PROVIDE 1/2" TRAP PRIMER LINE EXPOSED DOWN ALONG WALL, EXTEND 1/2" TRAP PRIMER LINE IN PIPE SLEEVE BELOW
CO MENS SLAB ON GRADE AND CONNECT 1/2" TRAP PRIMER LINE TO TRAP PRIMER CONNECTION OF FLOOR DRAIN. INSTALL TRAP
33 G G 2"
24 CO 014 4" PRIMER LINES WITH A 1/8" PER FOOT SLOPE TO FLOOR DRAIN CONNECTION POINT.
4"FD-2 3" 4"FD-2 4"FD-1 CO
AT CLG
22 4"FD-2 9 4" 11 PROVIDE 1/2" TRAP PRIMER LINE DOWN IN WALL, EXTEND 1/2" TRAP PRIMER LINE IN PIPE SLEEVE BELOW SLAB ON GRADE
AND CONNECT 1/2" TRAP PRIMER LINE TO TRAP PRIMER CONNECTION OF FLOOR DRAIN. INSTALL TRAP PRIMER LINES WITH
2" 4"
4" A 1/8" PER FOOT SLOPE TO FLOOR DRAIN CONNECTION POINT.
BLW GRADE 28 11
3/4" CO 12 PROVIDE A WATER HAMMER ARRESTER SIZE "C".
22 W AT CLG W-3 TP
35 4"FD-2 4"
HB-1 25 3" 13 PROVIDE 3/4" COLD WATER AND 3/4" HOT WATER DOWN IN CHASE. RUN A 3/4" COLD AND 3/4" HOT WATER HEADER, ABOVE
WH-1 BLW SLAB U-1 2"V-UP 4" FLOOD RIM OF THE HIGHEST MOUNTED FIXTURE.
4" 3/4"
CO 15 3/4"
4"V-UP
14 PROVIDE 3/4" HOT WATER DOWN IN CHASE. RUN A 3/4" HOT WATER HEADER, ABOVE FLOOD RIM OF THE HIGHEST MOUNTED
3/4" 4"VTR 4"W-DN
(HOTEL) DOMESTIC WATER 4"FD-6 4" ABV CLG FIXTURE.
SERVICE REFER TO
6" 12 CDL 15 PROVIDE 2" COLD WATER DOWN IN CHASE. RUN A 2" COLD AND HEADER, ABOVE FLOOD RIM OF THE HIGHEST MOUNTED
DETAIL ON DRAWING P5.01 6"FD-2 CO 4" 2" 4" 4"SS FIXTURE. FOR WATERLESS URINAL PROVIDE 3/4" CAPPED CONNECTION FOR FUTURE.
4" 4"

G
3/4" 4" BLW SLAB 30 2"
4" 16 PROVIDE 2" GAS LINE DOWN AND CONNECT TO COMMERCIAL DRYER. COMMERCIAL DRYER TO BE PROVIDED BY OTHERS.
BLW GRADE BP 21 PLUMBING CONTRACTOR SHALL COORDINATE EXACT CONNECTION POINT OF GAS LINE TO COMMERCIAL DRYER WITH
G

8" W-4 W-3 4" 8"


BP 26 MECHANICAL/ELECTRICAL 1 1/2" 3" 32
4" OTHER CONTRACTORS.
CO
6" TP 10 4"FD-2 7 020 4"RD-FRM
3" 1 1/2" 17 PROVIDE 1 1/2" COLD WATER AND 1 1/2" HOT WATER DOWN ALONG WALL. PROVIDE 1 1/2" BY 1" TEE'S, RUN 1" COLD WATER
ABV AND 1" HOT WATER LINE'S HORIZONTALLY ALONG WALL WITH BALL VALVES IN THE HORIZONTAL TO EACH HOSE BIBB
22 3/4" 2"V-UP
(825 SQ/FT) SUPPLYING THE WASHING MACHINES. WASHING MACHINES TO BE PROVIDED BY OTHERS. COORDINATE WATER HOSE BIBB
4" 4"FD-1 INSTALLATION WITH OTHER CONTRACTORS.
4"SS-FRM ABV CO 4" ABV CLG
AND DOWN 18 PROVIDE 1" HOT AND COLD WATER HOSE BIBB'S FOR EACH WASHING MACHINES. WASHING MACHINES TO BE PROVIDED BY
3" WOMENS 4" 3/4" OTHERS. COORDINATE WATER HOSE BIBB INSTALLATION WITH OTHER CONTRACTORS.
3"V-UP AT CLG
015 3/4" L-3 L-3
22 W
19 PROVIDE A WATER HAMMER ARRESTER SIZE "A".
6"
6" 1 1/2" 2"
BLW GRADE 20 PROVIDE A WATER HAMMER ARRESTER SIZE "B".
8 CO
3"
21 PROVIDE A 1" CAPPED COLD WATER CONNECTION WITH REDUCED PRESSURE ZONE BACKFLOW PREVENTER, AND
(TENANT) DOMESTIC WATER STRAINER FOR IRRIGATION SYSTEM WATER MAKE-UP. SITE IRRIGATION TO BE FURNISHED AND INSTALLED BY OTHERS.
SERVICE REFER TO 2"
13
DETAIL ON DRAWING P5.04 22 FOR CONTINUATION OF PIPING - REFER TO SITE UTILITY PLAN.
2"W-DN
23 PROVIDE 1 1/2" GAS LINE DOWN AND CONNECT TO DOMESTIC WATER HEATER. TYPICAL FOR (8) EIGHT DOMESTIC WATER
HEATERS.

24 PROVIDE DOMESTIC WATER THERMAL EXPANSION TANK. FOR PIPING SCHEMATIC REFER TO DETAIL ON DRAWING P6.03
PARTIAL GROUND FLOOR MECHANICAL ROOM PLAN PARTIAL GROUND FLOOR TOILET ROOM PLANS
PLUMBING
01 SCALE: 1/4" = 1'-0"
02 PLUMBING
SCALE: 1/4" = 1'-0"
25 ALL DOMESTIC WATER PIPING IN THE WATER HEATER ROOM TO BE COPPER TYPE L.

26 SANITARY WASTE PIPING INDICATED (BELOW SLAB IN WATER HEATER ROOM AND FROM COMMERCIAL WASHERS) TO BE
CAST IRON.

27 3" GAS LINE W/ SHUT-OFF VALVE. VALVE TO BE LABELED "SUPPLYING AN EMERGENCY GENERATOR".

28 PROVIDE WASTE LINE IN CHASE.

29 PROVIDE 2" TOP CONNECTION RELIEF VENT. PROVIDE 2" VENT PIPING BELOW SLAB ON GRADE, SLOPING VENT PIPING
UPWARDS AT 1/8" PER FOOT TO WALL, SO VENT PIPING CAN RISE VERTICALLY, CONCEALED, UP IN WALL TO ABOVE CEILING.
S-2 PLUMBING CONTRACTOR SHALL COORDINATE CONCEALED VENT PIPING RISE UP IN WALL WITH OTHER CONTRACTORS.

30 PROVIDE VENT HEADER IN CHASE. RUN HEADER ABOVE FLOOD RIM OF THE HIGHEST MOUNTED FIXTURE.
4"
31 PROVIDE SUMP PUMP (SP-2) REFER TO DETAIL ON DRAWING P6.03

32 PROVIDE FIXED AIR GAP FITTING IN CHASE - REFER TO DETAIL ON DRAWING P6.04
3"V-UP 2
33 PROVIDE 3/4" COLD WATER DOWN TO HOSE BIBB OR WALL HYDRANT W/BALL VALVE IN VERTICAL.
3" CO
1/2" 34 CENTRAL BUILDING MIXING VALVE - REFER TO DETAIL ON DRAWING P6.01

3/4" BP
3/4" 4" D-1 35 DOMESTIC WATER BOOSTER PUMP - REFER TO DETAIL ON DRAWING P6.04
18 3" 6"
2" 1/2"C
17 18 1 1/4"W & V 36 TERMINATE 4" SAFE WASTE LINE OVER TRENCH DRAIN W/APPROVED AIR GAP.
36
4
4" 2" G 4"FD-6
EMPLOYEE 1 1/2" 1/2" EF-1 1 1/4"
SH-3
LOUNGE 6 T POOL EQUIPMENT
CO 29 047 6"

16 1 1/2" 4"
039 4"
1 1/2" 4"
1 1/2" CO
CO SW CO
2" 1" 1 1/4"
3 L-4 BLW SLAB 35
5 8 4"

TP
D-1 3"
16 1/2" 2"
4"FD-1 CO 2" 2 1/2"
20 3/4" 4"FD-2
3/4" 2" G
29 3/4" TP 1 1/2"-DN 8" x 6" FUNNEL AT CLG
4"FD-1 1" POOL HEATER
4" CO BLW SLAB DRAIN
3/4" HB-1 BY OTHERS
4"
SW

4" 3/4" 4" 3"V-UP 2"


1/2" 9
AT CLG 1/2"
4" 11 15 10
CORRIDOR ABV CLG
035 11 BLW SLAB
G

9 2"V-UP
PD 26 W-2 4"
11 ABV CLG CO 1
2"
1 1/2" CO 2"V-UP 4" 4"FD-1
9 2" 4"-DN
LAUNDRY ABV CLG __" TP
4"FD-1
TP
045 3"
26 W-3
1/2" BLW SLAB
4" 4" CO 4"
4" __" ABV CLG 30
CO 2"V-UP
4" W-4
EF-1 4"VS
1 1/2"
3/4" 14 2"
2" 3" L-3
19 28
(TYP FOR 4) U-1
SS-1 2"
LT-1 3/4" HB-2
G

5 ABV CLG 4"


4"
LINEN 6 4"FD-1
BLW SLAB CO
3/4" STORAGE MEETING ROOM 12
ABV CLG 043 STORAGE
W-4
3/4" 042 OFFICE
1 1/2"
2"V-UP 044 STORAGE
4"
4" 4 034
4"SS CO
4"

4"
BLW SLAB

PARTIAL GROUND FLOOR TOILET ROOM PLANS


PLUMBING

03
PARTIAL GROUND FLOOR LAUNDRY AND TOILET ROOM PLANS
PLUMBING
SCALE: 1/4" = 1'-0"
04 SCALE: 1/4" = 1'-0"

ENLARGED PARTIAL
GROUND FLOOR PLANS
PLUMBING

P4.05
DOMESTIC WATER
RISER DIAGRAMS
PLUMBING

P5.01
DOMESTIC WATER
RISER DIAGRAMS
PLUMBING

P5.02
SANITARY SEWER AND
VENT - RISER DIAGRAM
PLUMBING

P5.03
SANITARY SEWER AND
VENT - RISER DIAGRAM
PLUMBING

P5.04
SANITARY SEWER AND
VENT - RISER DIAGRAM
PLUMBING

P5.05
SANITARY SEWER AND
VENT - RISER DIAGRAM
PLUMBING

P5.06
SANITARY SEWER AND
VENT - RISER DIAGRAM
PLUMBING

P5.07
HEAVY DUTY TRAFFIC CLEANOUT
"CO" TO BE CAST IN COVER WITH COVER AND PLUG POLISHED NICKEL BRONZE

CLEANOUT WITH COVER AND VARIES


3" DIA (MIN) SIZE 6" THICK BY 18" SQUARE
PLUG FOR DUTY REQUIRED. FINISHED GRADE PIPE INSULATION PIPE THRU FLOOR CONSTRUCTION.
REFER TO PLAN CONCRETE PAD
GRADE OR TERMINATE AT SLEEVE (TYP) SIZE AS NOTED ON PLAN
PAVING
PIPE SLEEVE SHALL BE SIZED ONE
VENT PIPE PACK W/FIRESTOPPING MATERIAL WALL CONSTRUCTION BY GC
DIAMETER LARGER THAN PIPE OR
AS REQUIRED TO ACCOMMODATE PIPE SLEEVE SHALL BE SIZED ONE
WATER CUT-OFF PIPE SLEEVE PROVIDED, DIAMETER LARGER THAN PIPE OR
4" IN MECHANICAL EQUIPMENT PIPE WITH SPACE FOR
MASTIC LOCATED AND SET BY PC AS REQUIRED TO ACCOMMODATE PIPE
AREAS AND UNFINISHED SPACES FIRESTOPPING MATERIAL.

2'-0" (MIN)
ONLY. SLEEVE FLUSH W/FLOOR WITH SPACE FOR FIRESTOPPING MATERIAL.
CLAMPING RING EXTENSION SAME SIZE AS

AS REQUIRED
SEWER UP TO 4"DIA (FOR IN FINISHED AREAS
SLIP-ON FLANGE - WELD TO SLEEVE
SEWER SIZES 6"DIA AND 4"
MOLDED PIPE FLASH LONG SWEEP 1/4" BEND OR PIPE THRU WALL CONSTRUCTION.
MEMBRANE ROOFING UP USE 4"DIA EXTENSION).
COMB "Y" & 1/8" BEND SIZE AS NOTED ON PLAN
LAP SEALANT (USE REDUCING TYPE VARIES
RIGID INSULATION
WHERE REQUIRED).
PIPE INSULATION
TERMINATE AT SLEEVE (TYP) PACK W/ FIRESTOPPING MATERIAL
FLOOR CONSTRUCTION BY GC 1/4" PLATE FLANGE WELDED ALL
AROUND TO SLEEVE. FLANGE DOWELS 3/8" DIAMETER.
PIPE SLEEVE PROVIDED, NOTE:
SHALL BE TWICE DIAMETER OF PIPE LENGTH EQUAL TO 1/2
LOCATED AND SET BY HC SIZE SLEEVE DIAMETER. OMIT DOWELS WHEN SLEEVE IS
BUILDING DRAIN OR SEWER DIRECTION OF FLOW INSTALLED IN AN EXISTING WALL.
ROOF STRUCTURE NOTE: (4 PER SLEEVE)
MATERIAL SIZE AS SPECIFIED OMIT 1/4" PLATE FRAME WHEN SLEEVE IS
INSTALLED IN AN EXISTING FLOOR.
EXTERIOR CLEANOUT INTERIOR FLOOR CLEANOUT INTERIOR WALLS
PIPE SLEEVE THRU WALL DETAIL
TYPICAL VENT THRU ROOF DETAIL
01
NOTE: PIPE SLEEVE THRU FLOOR DETAIL
FOR MATERIAL TYPE SEE SPECIFICATIONS. NOTE:
NOT TO SCALE
CONTRACTOR TO VERIFY THAT FIRE STOP IS COMPATIBLE
WITH CPVC PIPING USED. VERIFY WITH MANUFACTURES

DETAIL OF CLEAN OUT 03 FLOOR SLEEVE DETAIL - (PIPE)


NOT TO SCALE
RECOMMENDATIONS.

02 NOT TO SCALE
04 WALL SLEEVE DETAIL - (PIPE)
NOT TO SCALE

4" DOMESTIC WATER SUPPLY TO


BUILDING, FOR CONTINUATION
REFER TO DRAWING P4.05

BUILDING WALL FLANGE


NOTE:
FINISHED GRADE 1. ALL FLOOR AND FUNNEL DRAINS TO BE
PIPE SLEEVE THRU
FLOOR INSTALLED WITH TRAP PRIMER
METER PROVIDED BY P.C. CONNECTION AND TRAP PRIMER
PRESSURE INSTALLED BY PWSA VALVES.
FINISHED FLOOR 4" REDUCED PRESSURE
GAUGE BACKFLOW PREVENTER
2. PROVIDE 1/8" PER FOOT SLOPE ON ALL
TRAP PRIMER LINE SUPPLYING DRAINS.

4" 3. PROVIDE PIPE SLEEVES FOR ALL TRAP


4" STRAINER PRIMER LINES INSTALLED BELOW SLAB
COVER

4'-6" MINIMUM 4" ON GRADE.


3/4" DIAMETER PODS TRAP PRIMER VALVE
1/2"CW
WHEN THIS PIECE EXCEEDS HALF
A LENGTH, STRAPS MAY BE RUN 4"
ONLY TO FIRST OUTSIDE JOINT DUCTILE IRON PIPE FLOOR OR FUNNEL DRAIN
3/4" HOSE END DRAIN PIPE SLEEVE FLOOR
VALVE WITH VACUUM 4" BALL VALVE (TYPICAL) THRU FLOOR
BREAKER 4"
RESTRAINING LUGS PIPE SUPPORTS (TYPICAL) FINISHED
FLOOR

SEWER GASES

1" TO 3" WATERPROOF MASTIC


FROM MAIN DISTRIBUTION SYSTEM CONNECT AND EXTEND REFLIEF VENT DRAIN AND
NOTE:
ALLOW THE PIPE TO PASS THRU WALL WITHOUT RESTRAINT. TERMINATE OVER FLOOR/FUNNEL DRAIN WITH
UNGROUTED PIPE ANTICIPATE POSSIBLE SETTLEMENT OF WALL BY PROVIDING APPROVED AIR GAP FITTING. WATER TRAP
SUFFICIENT CLEARANCE AROUND PIPE. 4" WATER SERVICE SUPPLY, FOR
CONTINUATION REFER TO DRAWING P6.05

05 WATER SERVICE SUPPLY PIPING ENTERING THE BUILDING


NOT TO SCALE
06 DOMESTIC WATER SERVICE DIAGRAM (HOTEL)
NOT TO SCALE
07 TRAP PRIMER DETAIL (FOR FLOOR AND FUNNEL DRAINS)
NOT TO SCALE

FLASHING
(AS REQUIRED)
ROOF DRAIN
(AS SPECIFIED)
ROOF

4" HIGH CONCRETE HOUSEKEEPING PAD


SIZE LENGTH AND WIDTH TO SUIT EQUIPMENT

EXPANSION JOINT CLAMPING RING


EMERGENCY EYEWASH 1/2" PUBLIC FIXTURE(S) 1/2"
CEILING THERMOSTATIC MIXING VALVE THERMOSTATIC MIXING VALVE
3/4" CHAMFER 2" 6x6 - W4.0xW4.0
WELDED WIRE FABRIC T 2 GPM @ 5 PSI DROP T 4 GPM @ 5 PSI DROP
3 GPM @ 10 PSI DROP 6 GPM @ 10 PSI DROP
FOR CONTINUATION OF PIPING FOR CONTINUATION OF PIPING
RWC (AS SPECIFIED) REFER TO FLOOR PLANS REFER TO FLOOR PLANS
OFFSET RWC WHERE LINE SHALL BE A MAXIMUM OF LINE SHALL BE A MAXIMUM OF
SHOWN ON PLAN 10'-0' IN LENGTH FROM THE 10'-0' IN LENGTH FROM THE
4" CIRCULATED HOT WATER MAIN SEE FLOOR PLAN CIRCULATED HOT WATER MAIN SEE FLOOR PLAN
FOR CONTINUATION FOR CONTINUATION

1/2" LOCKING VALVE 1/2" LOCKING VALVE


WALL WITH IDENTIFICATION WITH IDENTIFICATION
(TYPICAL) (TYPICAL)
CO
STAINLESS STEEL IN PUBLIC AREAS
PAINT TO MACH IN SUITE AREAS FLOOR NOTE: 1/2" 1/2"
INSTALL TO MANUFACTURE'S NOTE:
RECOMMENDATIONS INSTALL TO MANUFACTURE'S
FLOOR SLAB RECOMMENDATIONS

EMERGENCY EYEWASH MIXING VALVE DETAIL PUBLIC FIXTURE MIXING VALVE DETAIL
10 NOT TO SCALE 11 NOT TO SCALE

08 TYPICAL DETAIL OF ROOF DRAIN AND RAIN WATER CONDUCTOR


NOT TO SCALE
09 TYPICAL HOUSEKEEPING PAD DETAIL
NOT TO SCALE

SEE FLOOR PLAN FOR CONTINUATION


1/2"
SEE FLOOR PLAN FOR CONTINUATION (2) 'S 3"x 3"x 1/4"x 12" LG MASONRY
4" (OR AS REQUIRED
SURFACE MOUNTED CABINET CONCRETE SLAB TO VARY HEIGHT)

NOTE:
THERMOSTATIC MIXING VALVE
T

ADDITIONAL OULET CONTROLS 6 GPM @ 5 PSI DROP


SHOULD BE USED 10 GPM @ 10 PSI DROP THERMOSTATIC MIXING VALVE
78 GPM @ 5 PSI DROP U-BOLT - 3/8" FOR
0.5 GPM MINIMUM FLOW
113 GPM @ 10 PSI DROP 2" DIA & OVER 1/4"
1 GPM MINIMUM FLOW FOR PIPE LESS THAN 2"

HWR
ANCHOR BOLT
HANGER ROD FOR GUIDE COUPLING W/STOP HW
SEE FLOOR PLAN SOLDER FITTING TO
1/2" CLEVIS HANGER
FOR CONTINUATION PIPE FOR ANCHOR
3/4" PIPE
SEE FLOOR PLAN
FOR CONTINUATION
2" DETAILS
2"
SEE FLOOR PLAN
PLUMBING
1/2"
FOR CONTINUATION
3/4"
3"
NOTE: 1" PIPE HANGER DETAIL COUPLING WITHOUT STOP
INSTALL TO MANUFACTURE'S
RECOMMENDATIONS
CHECK VALVE (TYPICAL) NOTE:
INSTALL TO MANUFACTURE'S CHECK VALVE (TYPICAL)
14 NOT TO SCALE
SOLDER FITTING TO PIPE

12 POOL SHOWER MIXING VALVE DETAIL


RECOMMENDATIONS

CENTRAL BUILDING MIXING VALVES DETAIL 15 TYPICAL DETAILS OF ANCHORS AND GUIDES P6.01
13
NOT TO SCALE NOT TO SCALE
NOT TO SCALE
REMOVEABLE LAUNDRY TRENCH GRATE -
AS PER MARRIOTT'S REQUIREMENTS.
REMOVABLE LAUNDRY TRENCH GRATE WITH
HOLES FOR WASHER DISCHARGE LINES -
ELECTRICAL AS PER MARRIOTT'S REQUIREMENTS.
NO SCALE
RECEPTACLE
(REFER TO BALL VALVE SEE FLOOR PLAN FOR CONTINUATION
4" OVERFLOW DRAIN
ELECTRICAL
CHECK ROOF
DRAWINGS) FINISHED FLOOR
VALVE
(2) 1x2x3/16x 3" WITH 4" 3/4" SECONDARY
1 1/2" DISCHARGE PIPE VTAC
CLEAR BETWEEN, ANCHORED CONDENSATE DRAIN
INTO CONCRETE. (TYPICAL)

ELEVATOR PIT FLOOR


FOURTH FLR.

1x2x3/16 ON EACH SIDE OF VTAC


TRENCH ANCHORED INTO CONCRETE.

2"
THIRD FLR.
3/4" SECONDARY
FOR CONTINUATION REFER CONDENSATE DRAIN VTAC
ELEVATOR SUMP PIT
TO FLOOR PLAN (TYPICAL)
24"L x 24"W x 24"D (REFER
TO ARCHITECTURAL DRAWINGS)
POWER CABLE SECOND FLR.

PUMP
RUN VTAC

REMOVABLE LAUNDRY TRENCH


PUMP STOP/OFF LEVEL
GRATE - TYPE AS PER
PER-MANUFACTURER'S 4" OVERFLOW DRAIN WITHOUT STRAINER. PROVIDE
MARRIOTT'S REQUIREMENTS. FIRST FLR.
REQUIREMENTS ELBOW AT TOP WITH INVERT ELEVATION 3" BELOW
2" CONDENSATE RISER WEEP TO LANDSCAPE, LOW
TOP OF TROUGH. HAND TIGHTEN ELBOW.
SUPPORT ANGLE 3x3x3/16x2'-0" REFER TO FLOOR PLANS ROOF AREAS OR FLOOR INSULATE RISER WITH 1/2"
LONG ON EACH SIDE OF TRENCH DRAINS ON FIRST FLOOR FIBERGLASS PIPE INSULATION
SUBMERSIBLE SUMP PUMP ADJUSTABLE LEVEL CONTROL FLOAT
ANCHORED INTO CONCRETE. INSIDE EQUIPMENT ROOMS.
(REFER TO SPECIFICATIONS)
SUCTION
CONCRETE BASIN SLOPED TO DRAIN-BY OTHERS 3/4" SECONDARY CONDENSATE DRAIN EXTEND
SEAT ANGLE 1x3x3/16x6" GROUND FLR.
3/4" PRIMARY CONDENSATE DRAIN TO EXTERNAL. CONDENSATE LINES BY
SECTION LONG AT 3'-6"O.C. WELDED LINE, EXTEND TO RISER, CONDENSATE PLUMBING CONTRACTOR
TO SUPPORT ANGLE. LINES BY PLUMBING CONTRACTOR TONS PIPE SIZE
0-5 1"
WASHER/EXTRACTOR-
PERMANENT ELEVATOR SUMP PUMP (SP-1) SYSTEM DETAIL
01 NOT TO SCALE
BY OTHERS
FINISHED FLOOR
6-30 1 1/4"

VTAC CONDENSATE RISER DETAIL


FLOOR DRAIN WITH REMOVABLE 03 VERTICAL PACKAGE TERMINAL AIR CONDITIONING UNIT DETAIL
NOT TO SCALE
04 NOT TO SCALE

DOMED STRAINER (4"FD-5)


4"
4"

FOR CONTINUATION REFER


TO FLOOR PLAN NOTE:
1. PROVIDE TRAP PRIMER TO OVERFLOW DRAIN.
2. COORDINATE WITH STRUCTURAL DRAWINGS.

WASHING MACHINE DRAINAGE BASIN DETAIL


02 NOT TO SCALE

GAS PIPE SUPPORT BLOCKS. FOR MORE 1'-6"

ELBOWS TO COMPENSATE FOR PIPE INFORMATION REFER TO NATURAL GAS PIPING


EXPANSION. SUPPORT ON ROOF DETAIL ON THIS DRAWING.

FLASHING AND COUNTER FLASHING IS BY


GAS PIPE SUPPORT BLOCKS BASE. FOR MORE

1'-6"
GENERAL CONTRACTOR. PLUMBING

4"
INFORMATION REFER TO NATURAL GAS PIPING COUNTERTOP
CONTRACTOR TO COORDINATE INSTALLATION
SUPPORT ON ROOF DETAIL ON THIS DRAWING. DISHWASHER WASTE HOSE SHALL BE
OF PIPING WITH GENERAL CONTRACTOR.
GROUND JOINT LOOPED HIGH AS POSSIBLE AND SECURELY HOT WATER RETURN
PIPE UNION. FASTENED TO COUNTERTOP OR WALL IN BRANCH
ONE HOLE PIPE STRAP (GALVANIZED) KITCHEN SINK (S-1 OR S-2) BASE CABINET
ROOFING SYSTEM BY GC PIPE SIZE AS SHOWN ON PLANS
TOP VIEW BALANCING VALVE

12" CHECK VALVE


TWO 4" X 4" X 12" CCA ROT-PROOF TREATED DISHWASHER- BY OWNER
18"SQ. X 3/16" ROOF WALKWAY TIMBERS SUPPORT BOCKS. TOE NAIL BLOCKS
MATERIAL FOR BASE, MATERIAL TOGETHER TO PROVIDE MINIMUM 7" CLEARANCE (L-3, L-4) LAVATORY END LAVATORY
ANCHOR PIPE TO ROOF DECK OR JOISTS. MUST BE COMPATIBLE WITH ROOF UNDER PIPES. CONNECT PIPES TO SUPPORT (ON HOT WATER HEADER)
ROOF PENETRATION BY GC. MEMBRANE. WITH GALVANIZED PIPE CLAMP LOOSELY
CLAMPED. FINISH FLOOR
ROOF-BY GC
NOTES:
1. REFER TO PLANS FOR PIPE SIZE(S) AND
LOCATION(S). USE WELDED OR SCREWED MIXING VALVE
FITTINGS AS SPECIFIED FOR PIPE SIZE. DISHWASHER WASTE HOSE -
PROVIDE DISHWASHER WASTE HOSE, (PER DISHWASHER MANUFACTURES
LOCATE PENETRATION MINIMUM 18" FROM END VIEW (3/4" MINIMUM SIZE)
RECOMMENDATIONS). CONNECT DISHWASHER WASTE HOSE TO
ADJACENT WALLS, EQUIPMENT CURBS, 1. REFER TO PLANS FOR PIPE SIZE(S) AND LOCATION(S). USE WELDED OR SCREWED FITTINGS AS SPECIFIED FOR DISHWASHER, EXTEND AND CONNECT TO TAIL PIECE OF KITCHEN SINK.
PARAPETS, EXPANSION JOINTS, PIPE SIZE. LOCATE PENETRATION MINIMUM 18" FROM ADJACENT WALLS, EQUIPMENT CURBS, PARAPETS, CONNECT DISHWASHER WASTE
DISHWASHER TO BE PROVIDED BY OTHERS. PLUMBING CONTRACTOR TO
ETCETERA. EXPANSION JOINTS, ETCETERA. TO THE DISPOSER HEAD/DISHWASHER
MAKE FINAL WATER AND WASTE CONNECTION. COORINATE FINAL
DRAIN CONNECTION
CONNECTION WITH GENERAL CONTRACTOR.
2. LOCATE SUPPORTS AT THE FOLLOWING SPACING: 2"=10' 1-1/2"=9', 1-1/4"=8', 1"=7' & 3/4"=6'. PROVIDE SUPPORTS AS FINISHED FLOOR
CLOSE AS POSSIBLE TO EACH ELBOW AND TEE.

NATURAL GAS PIPING ROOF PENETRATION


05 NOT TO SCALE
06 NATURAL GAS PIPING SUPPORT ON ROOF
NOT TO SCALE 07 DISHWASHER WASTE CONNECTION DETAIL
NOT TO SCALE 08 PUBLIC TOILET ROOM HOT WATER RETURN SCHEMATIC DETAIL
NOT TO SCALE

ANCHOR

100'
FOR CONTINUATION REFER TO FLOOR PLAN
FOR CONTINUATION REFER TO FLOOR PLAN
3/4" COLD WATER RISER 1/4 L
1/5 L
1/2" COLD WATER LINE 2" VENT STACK PROVIDE TRAP PRIMER DISTRIBUTION VALVE ABOVE CEILING (FOR MORE
PROVIDE TRAP PRIMER DISTRIBUTION VALVE ABOVE CEILING (FOR MORE 4" WASTE STACK INFORMATION ON TRAP PRIMER DISTRIBUTION VALVE REFER TO DETAIL ON
2" VENT
INFORMATION ON TRAP PRIMER DISTRIBUTION VALVE REFER TO DETAIL ON DRAWING P6.01 AND SPECIFICATION).
DRAWING P6.01 AND SPECIFICATION). TP TP SUSPENDED CEILING
TP TP SUSPENDED CEILING
1/2" TRAP PRIMER PROVIDE 1/2" TRAP PRIMER LINE DOWN IN WALL, 2/5 L 1/2 L L
CONCEAL STACKS AND RISERS IN LINE ABOVE CEILING EXTEND 1/2" TRAP PRIMER LINE BELOW FLOOR AND
1/2" TRAP PRIMER PROVIDE 1/2" TRAP PRIMER LINE DOWN IN WALL, WALL CONSTRUCTION CONNECT 1/2" TRAP PRIMER LINE TO TRAP PRIMER
CONCEAL PIPING IN
TP

LINE ABOVE CEILING EXTEND 1/2" TRAP PRIMER LINE IN PIPE SLEEVE
WALL CONSTRUCTION BELOW SLAB ON GRADE AND CONNECT 1/2" TRAP CONNECTION OF FLOOR DRAIN. INSTALL TRAP
TP

PRIMER LINE TO TRAP PRIMER CONNECTION OF PRIMER LINES WITH A 1/8" PER FOOT SLOPE TO
FLOOR DRAIN. INSTALL TRAP PRIMER LINES WITH A FLOOR DRAIN CONNECTION POINT.
1/8" PER FOOT SLOPE TO FLOOR DRAIN CONNECTION 6" MIN 1/4 L HANGER OR PIPE GUIDE
POINT. 1/2" DUAL CHECK VALVE
(TYPICAL)
1/2" DUAL CHECK VALVE BACKFLOW PREVENTER
PLUMBING CONTRACTOR SHALL INSTALL BALL VALVES, STRAINER, DUAL CHECK VALVE AND BUILDING WALL
BACKFLOW PREVENTER 1/2" STRAINER WATER FILTER ALONG WALL BESIDE ICE MACHINE FOR EASY MAINTENANCE.
1/2" STRAINER
PLUMBING CONTRACTOR SHALL INSTALL BALL VALVES, STRAINER, DUAL CHECK VALVE AND
WATER FILTER ALONG WALL BESIDE ICE MACHINE FOR EASY MAINTENANCE. 1/2" BALL VALVE PROVIDE WATER FILTER, COORDINATE WITH OTHERS. CPVC HOT WATER PIPING
1/2" BALL VALVE PROVIDE WATER FILTER, COORDINATE WITH OTHERS.
1/2" COLD WATER LINE THROUGH 1/2" BALL
ICE MACHINE PROVIDE BY OTHERS.
PLUMBING CONTRACTOR TO MAKE EYEWASH
EXPANSION LOOP CHART
ICE MACHINE PROVIDE BY OTHERS. WALL WITH CHROME PLATED VALVE
1/2" COLD WATER LINE THROUGH 1/2" BALL FINAL WATER AND WASTE (EF-1)
PLUMBING CONTRACTOR TO MAKE ESCUTCHEON PLATE
WALL WITH CHROME PLATED VALVE CONNECTION. PC SHALL COORDINATE SIZE INDICATED AND EXPANSION LOOP AT MIDPOINT, 100' BETWEEN ANCHORS
FINAL WATER AND WASTE
ESCUTCHEON PLATE CONNECTION. PC SHALL COORDINATE FINAL CONNECTION OF UTILITIES AND ON DRAWING DEVOLOPED LENGTH (L) OF EXPANSION LOOP (SHOWN IN INCHES)
F
FINAL CONNECTION OF UTILITIES AND LOCATION OF ICE MACHINE WITH
F UNION. OTHERS.
LOCATION OF ICE MACHINE WITH PIPE SIZE
TP

3/4" COLD WATER RISER


UNION. OTHERS. 4'-0" AFF
TP

4'-0" AFF BLW FLR 1" 40" 44" 46" 52"


FINISHED
2" FLOOR FINISHED FLOOR
BLW SLAB FINISHED 1 1/4" 45" 49" 52" 58"
2" FLOOR 4"FS-1, FLOOR SINK WITH 1/2 GRATE,
4"FS-1, FLOOR SINK WITH 1/2 GRATE, 4" OUTLET, FUNNEL ASSEMBLY AND TRAP
PRIMER CONNECTION. 1 1/2" 49" 53" 56" 62"
4" OUTLET, FUNNEL ASSEMBLY AND TRAP 4"
FOR CONTINUATION REFER 4" PRIMER CONNECTION. 2" TOP CONNECTION RELIEF VENT 2" 54" 59" 62" 69"
2" VENT STACK
TO FLOOR PLAN 3/4" COLD WATER RISER
2" TOP CONNECTION RELIEF VENT 4" WASTE STACK
2 1/2" 60" 65" 68" 76" DETAILS
FOR CONTINUATION REFER
TO FLOOR PLAN 3" 66" 71" 75" 84"
PLUMBING
EMERGENCY EYEWASH DETAIL
ICE MACHINE PIPING DETAIL
11 NOT TO SCALE
4" 75" 81" 85" 96"

09 NOT TO SCALE

10 VENDING AREA ICE MACHINE PIPING DETAIL


NOT TO SCALE
P6.02
CPVC HOT WATER PIPING EXPANSION LOOP DETAIL
12 NOT TO SCALE
PROVIDE 4" INTAKE AND 4" EXHAUST FOR DOMESTIC WATER HEATER PER
MANUFACTURE'S, LOCAL, AND NATIONAL CODES RECOMMENDATIONS.
(COORDINATE LOCATION W/HVAC DUCTWORK)
EXHAUST
REFER TO 1/2" PEX TUBING IN WALL
ENLARGED PLANS (HOT AND/OR COLD)
FOR LOCATION
(CP-2) CIRC PUMP
CHECK VALVE REFER TO SCHEDULE ON
(TYPICAL) INTERIOR WALL SUPPLY RISER TO
AQUASTAT DRAWING P7.01 FIXTURE

FLOW
INTAKE 3"
1 1/4"
REFER TO
ENLARGED PLANS CW
FOR LOCATION 3/4" 3" 3" CW SUPPLY

1 1/2"

1/2" POLISHED CHROME


BRANCH LINES FROM HEADER AQUASTAT PEX "DROP EAR" ELBOW
BRANCH LINES FROM HEADER STOP VALVE
TO WATER HEATER 1 1/2" SET TEMPERATURE ANCHORED TO SUPPORT
TO WATER HEATER
3" HEADER TO BE EQUAL IN LENGTH BLOCKING IN WALL
TO BE EQUAL IN LENGTH
3" 3" (CHROME TO PEX
CIRCUIT SETTER TRANSITION FITTING)
BALANCING VALVE (CP-1) CIRC PUMP
EXTERIOR WALL
3" (TYPICAL) REFER TO SCHEDULE ON
3" 1"
DRAWING P7.01
3"
1 1/2" OUTLET THERMOMETER
(TYPICAL) (TYPICAL)
1/2" POLISHED CHROME PIPE
T&P VALVE
(TYPICAL) BALL VALVE
(TYPICAL) NOTE: POLISHED CHROME
DWH-8 DWH-7 DWH-6 DWH-5 DWH-4 DWH-3 DWH-2 DWH-1 ESCUTCHEON PLATE
1) MIXING VALVE NOT REQUIRED FOR APPLICATIONS
UTILIZING SUPPLY WATER TEMPERATURE GREATER
3" NOTE:
UNION (TYPICAL) ROUGH-IN SIMILAR FOR SHOWERS AND BATHTUBS
MIXING VALVE
(REFER TO DETAIL
ON DRAWING P5.01)

FIN. FLOOR
02 TYPICAL PEX TO CHROME PIPING TRANSITION DETAIL FOR SUITE PLUMBING FIXTURES
NOT TO SCALE

FLOOR/FUNNEL DRAIN (TYPICAL)


1 1/2" INLET
(TYPICAL) 4" HIGH CONCRETE PAD (TYP). 100 GALLON GAS FIRED DOMESTIC
REFER TO DETAIL ON WATER HEATER (TYPICAL FOR 8)
THERMAL EXPANSION TANK DRAWING P6.01 REFER TO SCHEDULE
53 GALLON TOTAL VOLUME ON DRAWING P7.01
34.5 GALLON MAXIMUM ACCEPTANCE VOLUME
150 PSIG WORKING PRESSURE FOR CONTINUATION REFER TO FLOOR PLAN
CHARGE INITIAL PRESSURE EQUAL TO
DOMESTIC WATER HEATER SCHEMATIC DIAGRAM
01
SYSTEM PRESSURE DETERMINED AT SITE 1/2" COLD WATER LINE
NOT TO SCALE

1/2" DUAL CHECK VALVE PLUMBING CONTRACTOR SHALL INSTALL BALL VALVES, STRAINER, BEVERAGE BACKFLOW
BACKFLOW PREVENTER PREVENTER W/VENT (WILKINS MODEL 470 OR APPROVED EQUAL) AND WATER FILTER ALONG
WALL BESIDE KITCHEN EQUIPMENT FOR EASY MAINTENANCE.
1/2" STRAINER
1/2" BALL VALVE PROVIDE IN-LINE WATER FILTER, COORDINATE WITH OTHERS.

1/2" COLD WATER LINE THROUGH 1/2" BALL TO TRAP PRIMER


1/2" DUAL CHECK VALVE WALL WITH CHROME PLATED VALVE REFER TO DETAIL
BACKFLOW PREVENTER ESCUTCHEON PLATE ON DRAWING P5.01
CPVC PIPING NOTE: COUNTER
W/INSULATION TYPICAL SUITE SCHEMATIC IS FOR ONE SUITE, IN
1/2" STRAINER BP F
PEX MANIFOLD SOME AREAS BACK TO BACK SUITES WILL BE UNION.
(SEE TO SPECIFICATIONS) SUPPLIED FROM ONE (1) PEX MANIFOLD. REFER
(QUANTITY OF CONNECTIONS VARIES) 4'-0" AFF
TO FLOOR PLANS AND RISER DIAGRAM FOR
LOCATIONS. FINISHED
1/2" HOT WATER
FOR CONTINUATION FLOOR
PEX TUBING TO
REFER TO FLOOR PLAN KITCHEN EQUIPMENT PROVIDED BY OTHERS. PLUMBING
FIXTURES
CONTRACTOR TO MAKE FINAL WATER CONNECTION. PC
REFRIGERATOR FOR CONTINUATION REFER 4" SHALL COORDINATE FINAL CONNECTION OF UTILITIES
TO FLOOR PLAN AND LOCATION OF EQUIPMENT WITH FOOD SERVICE
2" TOP CONNECTION
DRAWINGS. INCLUDING, BUT NOT LIMITED TO COFFEE
RELIEF VENT
WALL MACHINE, ESPRESSO MACHINE, SODA MACHINE.
1/2" COLD WATER DISHWASHER
PEX TUBING TO 4"FD-4, FLOOR DRAIN W/RAISED LIP
2 SINK 4" OUTLET, TRAP PRIMER CONNECTION.
FIXTURES 1 LAVATORY

TYPICAL KITCHEN EQUIPMENT WATER PIPING DETAIL


2
NOT IN ALL SUITES
REFER TO ENLARGED
SUITE PLANS FOR
05 NOT TO SCALE

3 1 2 LOCATIONS
2 1
1 PRE-RINSE SINK PROVIDED BY OTHERS.
1 PLUMBING CONTRACTOR TO MAKE
FINAL WATER CONNECTION. PC SHALL
COORDINATE FINAL CONNECTION OF
UTILITIES AND LOCATION OF BOLTED STEEL COVER GAS AND
3 EQUIPMENT WITH FOOD SERVICE WATERTIGHT - FLUSH WITH CURB
3 3 3
SHOWER OR DRAWINGS.
CPVC WATER RISERS W/ INSULATION BATHTUB BASE CABINET 2" DISCHARGE PIPING
REFER TO FLOOR PLANS FOR SIZES FLUSH TANK POWER AND 3" SUMP VENT PIPE
WATER CLOSET FINISHED SENSOR CABLES
FLOOR
HIGH WATER
ALARM WIRING
ACCESS HAND HOLE
KEY NOTES:
1 1/2" COLD WATER PEX TO MANIFOLD.
PRE-RINSE SINK PIPING SCHEMATIC
2 1/2" HOT WATER PEX TO MANIFOLD. 04 NOT TO SCALE
NOTE: ALL PEX PIPING SHALL BE 1/2"
3 SEE TRANSITION DETAIL ON THIS SHEET TOP VIEW

BALL VALVE
TYPICAL SUITE PEX SCHEMATIC
03 NOT TO SCALE
1" SPRINKLER PIPING INTO EACH
GUEST ROOM
CHECK
VALVE
UNION 2" DISCHARGE PIPE
1" SPRINKLER PIPING INTO EACH WIRING TO CONTROL
GUEST ROOM PANEL-BY EC
3" VENT PIPE

8"W x 4"H EXH DUCT 8"W x 4"H SA DUCT

POWER CABLE
1"C STUBS FOR TELEPHONE AND
CABLE TV WIRING IN EACH 6x6 SDC 4" INLET
GUESTROOM (TYPICAL).
PLUMBING CONTRACTOR SHALL PROVIDE BALL VALVES, STRAINER, 6x6 ERC DOWN 8" HIGH MAX SUPPLY AIR DUCT

0-6"
MIN
DUAL CHECK VALVE AND WATER FILTER. INSTALL BALL VALVES, GUESTROOM TV COAX AND/OR TELE/DATA HOMERUNS LIGHT WIDTH VARIES, REFER TO FLOOR PLANS HIGH WATER LEVEL
1/2" (PEX) COLD WATER LINE STRAINER, DUAL CHECK VALVE AND WATER FILTER BELOW COUNTER BUNDLED TOGETHER ABOVE THE CEILING WITH PLENUM SPRINKLER PIPE 1" CONDUITS
TOP, INSIDE OF CASEWORK THAT IS ADJACENT TO THE REFRIGERATOR,
RATED TIE-WRAPS 5'-0" O.C. AND SUPPORTED FROM 8" HIGH MAX EXHAUST AIR DUCT
FOR EASY OF MAINTENANCE. COORDINATE INSTALLATION OF BALL
THE STRUCTURE ABOVE THE BRIDAL RINGS 10'-0" OC (TYP) WIDTH VARIES, REFER TO FLOOR PLANS
VALVES, STRAINER, DUAL CHECK VALVE AND WATER FILTER WITH
GENERAL CONTRACTOR AND OTHER CONTRACTORS.
WATER FILTER FOR MORE INFORMATION REFER TO
SPECIFICATION.
1/2" DUAL CHECK VALVE SUMP BASIN - 30" DIAMETER
BACKFLOW PREVENTER CORRIDOR BY 6'-6" DEEP
NOTE: REFER TO SPECIFICATIONS

2'-0"
1/2" STRAINER BATHROOM HVAC, PLUMBING, AND ELECTRICAL CONTRACTORS

MIN
SHALL COORDINATE LOCATIONS OF ALL DUCTS,
1/2" BALL VALVE REFRIGERATOR WITH ICE MAKER-BY OTHERS. PIPING, CONDUIT, ETC., IN THE CORRIDOR SPACE. SUMP PUMP:
COUNTER TOP PLUMBING CONTRACTOR TO MAKE FINAL
1/2" COLD WATER LINE THROUGH REFER TO SPECIFICATIONS
BY OTHERS WATER LINE CONNECTION. PLUMBING
WALL WITH CHROME
CONTRACTOR SHALL COORDINATE FINAL CORRIDOR WALL
PLATED ESCUTCHEON PLATE
PIPING CONNECTION SIZE AND LOCATION OF
REFRIGERATOR WITH GENERAL CONTRACTOR CORRIDOR WALL
CASEWORK AND OTHER CONTRACTORS. LOW WATER LIMIT

1'-0"
MIN
BY OTHERS (STOP PUMP LEVEL)
GROUTING
1/8" PEX TUBING.

1/2" BALL VALVE


FINISHED FLOOR BULB CONTROLLERS (TYP) 4" THICK CONCRETE PAD
UNION. SECTION
POURED IN PLACE
1/2" x 1/8" REDUCER
NOTES: DETAILS
1. SIMPLEX PUMP SHALL BE INTERFACED
WITH THE SUMP PUMP CONTROL PANEL PLUMBING
TO ALERT MAINTENANCE PERSONNEL OF
REFRIGERATOR WITH ICE MAKER PIPING DETAIL
06 NOT TO SCALE
LOW WATER LEVEL OR HIGH WATER ALARM

2. FURNISH AND MOUNT SUMP PUMP


CONTROL PANEL AS SPECIFIED.
WIRING BY ELECTRICAL CONTRACTOR.

P6.03
07 DETAIL CORRIDOR SECTION FOR ELECTRICAL & MECHANICAL ITEMS
NOT TO SCALE
SUMP PUMP (SP-2) SYSTEM DETAIL
08 NOT TO SCALE
MODERN PIPE SUPPORTS FIGURE 87
DOUBLE BOLT PIPE CLAMP, OR
MODERN PIPE SUPPORTS FIGURE 87
EQUAL, PLAIN FINISH
DOUBLE BOLT PIPE CLAMP, OR
EQUAL, PLAIN FINISH MODERN PIPE SUPPORTS
PERFORATED BAR FIGURE 30,
MODERN PIPE SUPPORTS
SIZE 2 FOR PIPING 4" THRU 6"
PERFORATED BAR FIGURE 30,
SIZE 3 FOR PIPING 8" AND
SIZE 2 FOR PIPING 4" THRU 6"
LARGER, OR EQUAL;
SIZE 3 FOR PIPING 8" AND
(ONE REQUIRED) BLACK FINISH
LARGER, OR EQUAL;
(ONE REQUIRED) BLACK FINISH IF DISTANCE LESS IF DISTANCE MORE
THAN 20', NO PIPE THAN 20', INCREASE
INCREASE ONE PIPE SIZE

MODERN PIPE SUPPORTS FIGURE 87 MODERN PIPE SUPPORTS FIGURE 87


REVENT LINE TIE IN
DOUBLE BOLT PIPE CLAMP, OR DOUBLE BOLT PIPE CLAMP, OR
2" ABOVE THE FLOOD
EQUAL, PLAIN FINISH EQUAL, PLAIN FINISH RIM LEVEL USING A WYE
MODERN PIPE SUPPORTS BRANCH LOOKING UP
MODERN PIPE SUPPORTS PERFORATED
PERFORATED BAR FIGURE 30, IF WASTE OVER 15'
BAR FIGURE 30,SIZE 2 FOR PIPING
SIZE 2 FOR PIPING 4" THRU 6" 27' MAX
4" THRU 6"SIZE 3 FOR PIPING 8"
SIZE 3 FOR PIPING 8" AND
AND LARGER, OR EQUAL;
LARGER, OR EQUAL;
(ONE REQUIRED) BLACK FINISH
(ONE REQUIRED) BLACK FINISH
15' MAX

15' MAX

HUBLESS FITTING RESTRAINTS HUB AND SPIGOT FITTING RESTRAINTS


MODERN PIPE SUPPORTS NOT TO SCALE NOT TO SCALE
FIGURE 503, CLAMP MODERN PIPE SUPPORTS
W/FIGURE 504 SOCKET ALL THREAD ROD FIGURE 503 CLAMP ALL THREAD ROD
WASHER, OR EQUAL; BLACK FINISH W/FIGURE 504 SOCKET
WASHER, OR EQUAL;
MODERN PIPE SUPPORTS BLACK FINISH MODERN PIPE SUPPORTS
FIGURE 1000, 11 GAUGE FIGURE 1000, 11 GAUGE
CHANNEL, OR EQUAL; CHANNEL, OR EQUAL; TYPICAL UNIT SCHMATIC PLAN
BLACK FINISH. PROVIDE BLACK FINISH. PROVIDE NOT TO SCALE
DRILL HOLES AS REQUIRED DRILL HOLES AS REQUIRED

CLEANOUT PLUG CLEANOUT PLUG

HUBLESS CLEANOUT RESTRAINTS HUB AND SPIGOT CLEANOUT RESTRAINTS REVENT LINE TIE IN
ABOVE THE FLOOD
NOT TO SCALE NOT TO SCALE RIM LEVEL USING A WYE
BRANCH LOOKING UP REVENT LINE TIE IN
ALL THREAD ROD ALL THREAD ROD ABOVE THE FLOOD
RIM LEVEL USING A WYE
MODERN PIPE SUPPORTS MODERN PIPE SUPPORTS BRANCH LOOKING UP
FIGURE 503 CLAMP FIGURE 503 CLAMP
W/FIGURE 504 SOCKET W/FIGURE 504 SOCKET
WASHER, OR EQUAL; WASHER, OR EQUAL;
BLACK FINISH (TYP) PRESSURE RELIEF
BLACK FINISH (TYP) PRESSURE RELIEF
VENT LINE
A VENT LINE
PRESSURE RELIEF
MAIN BUILDING DRAIN VENT LINE B SOIL OR WASTE BRANCHES MAY
A CONNECT DIRECTLY INTO THE
VERTICAL STACK DIRECTLY BELOW
BRANCH WASTE
B THE BASE FITTING ONLY WHEN
HUBLESS PIPING RESTRAINTS HUB AND SPIGOT PIPING RESTRAINTS CL CL LINE
THE CONNECTIONS ARE MADE USING
NOT TO SCALE NOT TO SCALE SECTION 'A-A' SECTION 'B-B' FITTINGS SUCH AS COMBINATION WYE
AND 1/8 BEND.

* SUPPLY ON ALL ABOVE GROUND RAIN WATER CONDUCTOR LINE 10 PIPE DIAMETERS
MINIMUM
BRANCH CONNECTION DIAGRAM
TYPICAL SCHMATIC RISER OFFSET
NOT TO SCALE
NOT TO SCALE
STORM DRAINAGE PIPING RESTRAINING DETAILS
01 NOT TO SCALE
TYPICAL SCHMATIC RISER DIAGRAM
NOT TO SCALE

FINISHED WALL
WASHING MACHINE
PROVENT SCHEMATIC DETAILS
SINGLE LEVER ON/OFF
WATER SUPPLY
10 3/4" SUPPLY AND WASTE
UNIT (REFER TO
SPECIFICATIONS)
02 NOT TO SCALE

CONTROL VALVE

12"x 18" ACCESS PANEL


8 1/4"

(SEE SPECIFICATIONS) CAP W/BLIND FLANGE


1/2" COMBINATION FOR FUTURE CONNECTION
2"V-EXTEND AS
MPT BRASS SWEAT
INDICATED ON PLAN
CONNECTION METER PROVIDED BY P.C.
PRESSURE INSTALLED BY PWSA
INCREASER 3" REDUCED PRESSURE
GAUGE BACKFLOW PREVENTER
EXTENSION PIPE
18" MINIMUM-
48" MAXIMUM

2" EXTENSION PIPE AIR GAP 3"


2" WASTE 3" STRAINER
36" ABOVE FINISHED FLOOR

CONNECTION 3"
BLW W/WATER HAMMER TO 2"W & V
ARRESTER - SIZE 'A', 4 1/2"
CHECK VALVE ASSEMBLY CONNECT 1/2" TO
ON EACH SUPPLY NEAREST WATER LINE
3"
3/4" HOSE END DRAIN PIPE SLEEVE
VALVE WITH VACUUM 3" BALL VALVE (TYPICAL) THRU FLOOR
2" WASTE 1/2"H & C-
WATER SUPPLY BREAKER 3"
ACCESS PANEL FINISHED
LINES TRAP PRIMER DISTRIBUTION STATION, PIPE SUPPORTS (TYPICAL)
FLOOR
INSTALL IN ACCESSIBLE LOCATION
2" ADJUSTABLE
P-TRAP FINISHED WALL P-TRAP

FINISH FLOOR FINISH FLOOR


CONNECT AND EXTEND REFLIEF VENT DRAIN AND
FIXED AIR GAP FITTING DETAIL
FRONT
SECTION 06 NOT TO SCALE
TERMINATE OVER FLOOR/FUNNEL DRAIN WITH
APPROVED AIR GAP FITTING.
3" WATER SERVICE SUPPLY, FOR
CONTINUATION REFER TO DRAWING P6.05

WASHING MACHINE SUPPLY AND DRAIN UNIT


05 NOT TO SCALE
07 DOMESTIC WATER SERVICE DIAGRAM (TENANT)
NOT TO SCALE

NOTE:
REFER TO WATER BOOSTER PUMP SYSTEM
PIPING SCHEMATIC ON THIS DRAWING.
4"
BY PLUMBING 4"
CONTRACTOR BY PLUMBING CONTRACTOR
4" BYPASS
CHECK VALVE (TYP)
4"
SEE FLOOR PLAN FOR CONTINUATION MANUFACTURER DISCHARGE MANUFACTURER
ASSEMBLY MANIFOLD ASSEMBLY

4" WIRING BY EC
CONTROL 4" 4"
PANEL CONTROL PANEL
4" MANIFOLD
PRESSURE
GAUGE (TYP)

SUCTION PILOT OPERATED PRV


FLEXIBLE MANIFOLD AND CHECK VALVE (TYP)
CONNECTION
(TYPICAL)
4" DISCHARGE LINE
FLANGES
(TYPICAL) ISOLATION
4" SUCTION LINE 3/4" PRESSURE RELIEF
VALVE (TYP)
VALVE SET @ 135 PSI
FLOOR
FLOOR W/DRAIN TO FUNNEL DRAIN
UNION
DETAILS
SIDE VIEW FRONT VIEW
WATER PRESSURE
PLUMBING
DUPLEX PUMPS BOOSTER PUMPS 3/4"
MANUFACTURER
3/4" HOSE END
ASSEMBLY
4" HIGH CONCRETE DRAIN VALVE
SHUT OFF VALVE (TYP)
PAD BY G.C. CONTRACTOR BY PLUMBING CONTRACTOR
* BOOSTER PUMP PACKAGE - REFER TO SPECIFICATIONS * BOOSTER PUMP PACKAGE - REFER TO SPECIFICATIONS

WATER PRESSURE BOOSTER PUMP PIPING SCHEMATIC


P6.04
08 DOMESTIC WATER SYSTEM BOOSTER PUMP DETAIL
NOT TO SCALE
09 NOT TO SCALE
WATER CLOSETS AND URINALS BATHTUBS
W WATER CLOSET
FIXTURE MANUFACTURER AND FIXTURE ACCESSORIES MAKE
FIXTURE MOUNTING FIXTURE MOUNTING FIXTURE MANUFACTURER AND FIXTURE ACCESSORIES MAKE LAVATORY
DESCRIPTION MODEL NUMBER AND MODEL NUMBER FOOTNOTES AND REMARKS DESCRIPTION FOOTNOTES AND REMARKS L
IDENTIFICATION REQUIREMENTS IDENTIFICATION REQUIREMENTS MODEL NUMBER AND MODEL NUMBER
(OR APPROVED EQUAL) (OR APPROVED EQUAL)
SINK
S
WATER CLOSET --- SS SERVICE RECEPTOR
FLOOR MTD FLOOR MTD SHOWER HEAD FURNISHED BY OWNER
W-1 TANK TYPE FURNISHED BY OWNER -- 1, 4 BT-1 BATHTUB FURNISHED BY OWNER 1, 2, 3, 4, 5, 6, 7
STD HT STD (2.0 GPM) SH SHOWER
1.0 GALLON PER FLUSH ---
SHOWER ARM FURNISHED BY OWNER
BT BATH TUB
WATER CLOSET ---
FLOOR MTD TRIM KIT FOR FURNISHED BY OWNER D WATER COOLER
W-2 TANK TYPE FURNISHED BY OWNER -- 1, 4
ADA HT VALVE
1.0 GALLON PER FLUSH --- FD FLOOR DRAIN
RD ROOF DRAIN
WATER CLOSET WALL MTD
W-3 FURNISHED BY OWNER FURNISHED BY OWNER 1, 2 VALVE FURNISHED BY OWNER
1.28 GALLON PER FLUSH STANDARD WH WALL HYDRANT
HB HOSE BIBB
WATER CLOSET WALL MTD DIVERTER SPOUT FURNISHED BY OWNER LS LAUNDRY SINK
W-4 FURNISHED BY OWNER FURNISHED BY OWNER 1, 2
1.28 GALLON PER FLUSH ADA
EF EMERGENCY FIXTURE
SHOWER HEAD (ADA) FURNISHED BY OWNER
FLOOR MTD (2.0 GPM)
BT-2 BATHTUB FURNISHED BY OWNER 1, 2, 3, 4, 5, 6, 7
ADA SHOWER HOSE FURNISHED BY OWNER NOTE: 1. SUFFIXES FOR FIXTURE LETTERS
STANDARD SHOWER HEAD AND TRIM - REFER TO BT-1 AS SPECIFIED.
---
WATERLESS URINAL WALL MTD 2. REFER TO PROJECT SPECIFICATIONS
U-1 FURNISHED BY OWNER -- 1, 3, 5
ADA TRIM KIT FOR FURNISHED BY OWNER
--- FOR PLUMBING ACCESSORIES,
VALVE SPECIALTIES AND EQUIPMENT.
VALVE FURNISHED BY OWNER

IN WALL DIVERTER FURNISHED BY OWNER


WATER CLOSETS FOOTNOTES:
1. REFER TO SPECIFICATIONS FOR REQUIREMENTS OF MATERIALS, COLOR, FINISHES, INSTALLATION, APPROVED EQUAL MANUFACTURERS, ETC.. DIVERTER SPOUT FURNISHED BY OWNER

2. PROVIDE COMPLETE WITH SEAT, CARRIER, AND SUPPLY AND WASTE ROUGH-IN ASSEMBLIES IN ACCORDANCE WITH SPECIFICATIONS.
SHOWERS AND BATHTUB FOOTNOTES:
3. PROVIDE COMPLETE WITH CARRIER, AND WASTE ROUGH-IN ASSEMBLIES IN ACCORDANCE WITH SPECIFICATIONS. 1. REFER TO SPECIFICATIONS FOR REQUIREMENTS OF MATERIALS, COLOR, FINISHES, INSTALLATION.

4. PROVIDE COMPLETE WITH SEAT, AND SUPPLY AND WASTE ROUGH-IN ASSEMBLIES IN ACCORDANCE WITH SPECIFICATIONS. 2. PROVIDE COMPLETE WITH SUPPLY AND WASTE ROUGH-IN ASSEMBLIES IN ACCORDANCE WITH SPECIFICATIONS.
PLUMBING FIXTURE CONNECTION SCHEDULE
5. PROVIDE 3/4" CAPPED CONNECTION FOR FUTURE CONNECTION. 3. SHOWER STALL SHALL BE CONSTRUCTED UNDER THE GENERAL CONTRACT. FURNISH AND INSTALL SHOWER VALVING AS SPECIFIED HEREIN. COLD HOT RIM FOOTNOTES AND
SYMBOL FIXTURE TRAP DRAIN VENT MOUNTING
WATER WATER HEIGHT REMARKS
4. SHOWER HEAD TO BE MOUNTED AT A MINIMUM HEIGHT OF 6'-10" AFF.
--- --- --- REFER TO ARCHTECTURAL
W-1 WATER CLOSET 1/2" 4" FLOOR
LAVATORIES AND SINKS 5. PROVIDE COMPLETE WITH DRAIN, NOBLE CLAMPING RING OR APPROVED EQUAL.
DRAWINGS
--- --- --- REFER TO ARCHTECTURAL
W-2 WATER CLOSET 1/2" 4" FLOOR
FIXTURE MANUFACTURER AND FIXTURE ACCESSORIES MAKE 6. PROVIDE COMPLETE W/FLOW RESTRICTOR FOR 2.0 GPM MAXIMUM. DRAWINGS
FIXTURE MOUNTING
DESCRIPTION MODEL NUMBER AND MODEL NUMBER FOOTNOTES AND REMARKS --- --- REFER TO ARCHTECTURAL
IDENTIFICATION REQUIREMENTS W-3 WATER CLOSET 1" 4" 2" WALL
(OR APPROVED EQUAL) (OR APPROVED EQUAL) 7. DRAWINGS
--- --- REFER TO ARCHTECTURAL
W-4 WATER CLOSET 1" 4" 2" WALL
DRAWINGS
LAVATORY FURNISHED BY OWNER
L-1 STANDARD FURNISHED BY OWNER 1, 2, 3, 7 --- --- REFER TO ARCHTECTURAL
VITREOUS CHINA (1.0 GPM) U-1 URINAL 2" 2" 2" WALL 2
DRAWINGS
SHOWERS L-1 LAVATORY 1/2" 1/2" 1 1/2" 2" --- COUNTER
REFER TO ARCHTECTURAL
LAVATORY FURNISHED BY OWNER DRAWINGS
L-2 ADA FURNISHED BY OWNER 1, 2, 3, 4, 7 REFER TO ARCHTECTURAL
VITREOUS CHINA (1.0 GPM) FIXTURE MOUNTING FIXTURE MANUFACTURER AND FIXTURE ACCESSORIES MAKE L-2 LAVATORY 1/2" 1/2" 1 1/2" 2" --- COUNTER
DESCRIPTION FOOTNOTES AND REMARKS DRAWINGS
IDENTIFICATION REQUIREMENTS MODEL NUMBER AND MODEL NUMBER
REFER TO ARCHTECTURAL
L-3 LAVATORY 1/2" 1/2" 1 1/2" 1 1/2" 1 1/2" COUNTER
LAVATORY FURNISHED BY OWNER DRAWINGS
L-3 ADA FURNISHED BY OWNER 1, 2, 3, 4, 6 REFER TO ARCHTECTURAL
VITREOUS CHINA (0.5 GPM) FLOOR MTD BUILT-UP SHOWER L-4 LAVATORY 1/2" 1/2" 1 1/2" 1 1/2" 1 1/2" WALL
SH-1 SHOWER SHOWER HEAD FURNISHED BY OWNER 1, 2, 3, 4, 6, 7 DRAWINGS
STD BY GENERAL CONTRACTOR (2.0 GPM)
REFER TO ARCHTECTURAL
WALL SHOWER ARM FURNISHED BY OWNER BT-1 BATHTUB 1/2" 1/2" 2" 2" AS NOTED FLOOR
LAVATORY FURNISHED BY OWNER DRAWINGS
L-4 MOUNTED FURNISHED BY OWNER 1, 2, 3, 4, 6
VITREOUS CHINA (0.5 GPM) REFER TO ARCHTECTURAL
ADA TRIM KIT FOR FURNISHED BY OWNER BT-2 BATHTUB 1/2" 1/2" 2" 2" AS NOTED FLOOR
DRAWINGS
VALVE
REFER TO ARCHTECTURAL
SH-1 SHOWER 1/2" 1/2" 2" 2" AS NOTED FLOOR
DRAWINGS
REFER TO ARCHTECTURAL
VALVE FURNISHED BY OWNER SH-2 SHOWER 1/2" 1/2" 2" 2" AS NOTED FLOOR
DRAWINGS
REFER TO ARCHTECTURAL
SINK FURNISHED BY OWNER SH-3 SHOWER 1/2" 1/2" 2" 2" 2" FLOOR
S-1 STD FURNISHED BY OWNER 1, 2, 3, 5 DRAWINGS
SINGLE BOWL STAINLESS (2.2 GPM)
DRAIN FURNISHED BY OWNER --- --- --- --- --- REFER TO ARCHTECTURAL
SH-4 SHOWER FLOOR 1
DRAWINGS
FURNISHED BY OWNER REFER TO ARCHTECTURAL
SINK FURNISHED BY OWNER S-1 SINK 1/2" 1/2" 1 1/2" 2" AS NOTED FLOOR
S-2 ADA 1, 2, 3, 4, 5 SHOWER HEAD (ADA) FURNISHED BY OWNER DRAWINGS
SINGLE BOWL STAINLESS (2.2 GPM) FLOOR MTD BUILT-UP SHOWER (2.0 GPM) REFER TO ARCHTECTURAL
SH-2 ROLL IN SHOWER 1, 2, 3, 4, 6, 7 S-2 SINK 1/2" 1/2" 1 1/2" 2" AS NOTED FLOOR
ADA BY GENERAL CONTRACTOR SHOWER HOSE FURNISHED BY OWNER DRAWINGS
STANDARD SHOWER HEAD AND TRIM - REFER TO SH-1 REFER TO ARCHTECTURAL
SS-1 SERVICE SINK 3/4" 3/4" 3" 3" 2" FLOOR
DRAWINGS
REFER TO ARCHTECTURAL
TRIM KIT FOR FURNISHED BY OWNER LT-1 LAUNDRY SINK 1/2" 1/2" 2" 2" 2" FLOOR
DRAWINGS
SERVICE FLOOR FURNISHED BY OWNER VALVE
SS-1 1, 2 --- REFER TO ARCHTECTURAL
RECEPTOR MOUNTED FURNISHED BY OWNER (2.0 GPM) D-1 ELECTRIC WATER COOLER 1/2" 1 1/4" 1 1/4" 1 1/4" WALL
VALVE FURNISHED BY OWNER DRAWINGS
--- --- REFER TO ARCHTECTURAL
EF-1 EMERGENCY EYEWASH 1 1/4" 2" 2" WALL 1
DRAWINGS
IN WALL DIVERTER FURNISHED BY OWNER
3"FD-1 FLOOR DRAIN --- --- 3" 3" AS NOTED FLOOR ---
DRAIN FURNISHED BY OWNER
4"FD-1 FLOOR DRAIN --- --- 4" 4" AS NOTED FLOOR ---
FLOOR FURNISHED BY OWNER
LT-1 LAUNDRY SINK FURNISHED BY OWNER 1, 2, 3 SHOWER HEAD (ADA) FURNISHED BY OWNER --- ---
MOUNTED (2.0 GPM) FD-2 - 5 FLOOR DRAIN 4" 4" AS NOTED FLOOR ---
FLOOR MTD (2.0 GPM)
SH-3 SHOWER FURNISHED BY OWNER 1, 2, 3, 4, 6, 7
ADA SHOWER HOSE FURNISHED BY OWNER --- --- --- ---
HB-1 HOSE BIBB 3/4" WALL ---
STANDARD SHOWER HEAD AND TRIM - REFER TO SH-1
HB-2 HOSE BIBB --- 3/4" --- --- --- WALL ---
TRIM KIT FOR FURNISHED BY OWNER
WH-1 WALL HYDRANT 3/4" --- --- --- --- WALL ---
LAVATORIES AND SINK FOOTNOTES: VALVE

1. REFER TO SPECIFICATIONS FOR REQUIREMENTS OF MATERIALS, COLOR, FINISHES, INSTALLATION, APPROVED EQUAL MANUFACTURERS, ETC.. VALVE FURNISHED BY OWNER * MINIMUM WASTE PIPING 4" BELOW SLAB
FOOTNOTES AND REMARKS
2. PROVIDE COMPLETE WITH SUPPLY AND WASTE ROUGH-IN ASSEMBLIES IN ACCORDANCE WITH SPECIFICATIONS. 1. PROVIDE A 1/2 " TEMPERED WATER LINE TO UNIT.
IN WALL DIVERTER FURNISHED BY OWNER
3. PROVIDE A POINT OF USE THERMOSTATIC MIXING VALVE ON THE HOT WATER SUPPLY TO THE SINK. INSTALL THE THERMOSTATIC MIXING VALVE BELOW THE SINK. SET 2. PROVIDE 3/4" CAPPED CONNECTION FOR FUTURE CONNECTION.

4. PROVIDE SUPPLY AND DRAIN INSULATION KIT FOR ALL ADA MOUNTED FIXTURES. FOR INFORMATION ON INSULATION KIT REFER TO PROJECT SPECIFICATIONS. COORDINATE
ADA MOUNTED FIXTURE WITH ARCHITECTURAL DRAWINGS AND GENERAL CONTRACTOR. FLOOR MTD BUILT-UP SHOWER SHOWER HEAD FURNISHED BY OWNER
SH-4 SHOWER 1, 2, 3, 4, 5, 6
ADA BY GENERAL CONTRACTOR (2.0 GPM)
5. PROVIDE COMPLETE WITH GARBAGE DISPOSAL "GE MODEL NO. GFC320F" OR APPROVED EQUAL SHOWER ARM FURNISHED BY OWNER

6. PROVIDE AND INSTALL GRID STRAINER ON ALL LAVATORIES LOCATED IN PUBLIC AREAS TRIM KIT FOR FURNISHED BY OWNER
VALVE
7. PROVIDE AND INSTALL POP-UP ASSEMBLY ON ALL LAVATORIES LOCATED IN GUEST SUITES.

VALVE FURNISHED BY OWNER

DRAIN FURNISHED BY OWNER

WATER COOLERS AND EMERGENCY FIXTURES


SHOWERS AND BATHTUB FOOTNOTES:
FIXTURE MOUNTING FIXTURE MANUFACTURER AND FIXTURE ACCESSORIES MAKE
DESCRIPTION FOOTNOTES AND REMARKS 1. REFER TO SPECIFICATIONS FOR REQUIREMENTS OF MATERIALS, COLOR, FINISHES, INSTALLATION.
IDENTIFICATION REQUIREMENTS MODEL NUMBER AND MODEL NUMBER
2. PROVIDE COMPLETE WITH SUPPLY AND WASTE ROUGH-IN ASSEMBLIES IN ACCORDANCE WITH SPECIFICATIONS.
WALL MTD ---
ELECTRIC BI-LEVEL COOLER --
D-1 STANDARD 1, 2 3. SHOWER STALL SHALL BE CONSTRUCTED UNDER THE GENERAL CONTRACT. FURNISH AND INSTALL SHOWER VALVING AS SPECIFIED HEREIN.
WATER COOLER FURNISHED BY OWNER ---
ACCESSIBLE
4. SHOWER HEAD TO BE MOUNTED AT A MINIMUM HEIGHT OF 6'-10" AFF.

5. HWR CIRC PUMP SCHEDULE


---
6. PROVIDE COMPLETE W/FLOW RESTRICTOR FOR 2.0 GPM MAXIMUM. CIRC
--- PIPE
WALL MTD PUMP LOCATION GPM FT/HD HP RPM ELECTRIC REMARKS
EMERGENCY FURNISHED BY OWNER -- SIZE
EF-1 ADA 1, 2, 3 7. NUMBER
EYE WASH ---
ACCESSIBLE
MECH -
CP-1 1 1/2" 5 8 1/12 1750 1-60-115V
EQUIP ROOM
MECH -
CP-2 1 1/2" 5 8 1/12 1750 1-60-115V
EQUIP ROOM

WATER COOLER FOOTNOTES:


1. REFER TO SPECIFICATIONS FOR REQUIREMENTS OF MATERIALS, COLOR, FINISHES, INSTALLATION.
2. PROVIDE COMPLETE WITH SUPPLY AND WASTE ROUGH-IN ASSEMBLIES IN ACCORDANCE WITH SPECIFICATIONS.
3. PROVIDE COMPLETE WITH THERMOSTATIC MIXING VALVE LAWLER MODEL # 911-E-F OR APPROVED EQUAL IN ACCORDANCE WITH SPECIFICATIONS.
4. GAS FIRED DOMESTIC WATER HEATER SCHEDULE
WATER EXHAUST INTAKE BURNER WATER TEMP STORAGE
FUEL DEG F RECOVERY
HEATER LOCATION FLUE FLUE INPUT APACITY REMARKS
TYPE GPH
NUMBER SIZE SIZE BTU HR IN OUT GALLONS

WATER
DWH-1 NAT. GAS 4" 4" 199,900 40 140 230 100
SERVICE 007
WATER
DWH-2 NAT. GAS 4" 4" 199,900 40 140 230 100
SERVICE 007
WATER
DWH-3
SERVICE 007
NAT. GAS 4" 4" 199,900 40 140 230 100
SCHEDULES
DWH-4
WATER
SERVICE 007
NAT. GAS 4" 4" 199,900 40 140 230 100 PLUMBING
WATER
DWH-5 NAT. GAS 4" 4" 199,900 40 140 230 100
SERVICE 007
WATER
DWH-6 NAT. GAS 4" 4" 199,900 40 140 230 100
SERVICE 007

DWH-7

DWH-8
WATER
SERVICE 007
WATER
NAT. GAS

NAT. GAS
4"

4"
4"

4"
199,900

199,900
40

40
140

140
230

230
100

100
P7.01
SERVICE 007