Project Title : Proposed Two Storey Residential Building

Location : #13 Palmyra st., Llanes compound, Sto. Rosario, Iligan City
Owner : Mrs. Mercuria L. Jones
Subject : Slab Design Investigation

COMPUTATION AND ANALYSIS


Slab Properties: Loading:
Shorter Side (La) = 3.00 m
Longer Side (Lb) = 3.30 m Live Load = 1.44 KPa
Slab Thickness = 100 mm Dead Load = 2.40 KPa
Wu = 5.81 KPa

Design Investigation:

For Long Direction: Lb = 3.30 m Rebars = 10 mm dia. Bar


Grade 40 = 280 Mpa
Midspan: Mu (required) = 3.9531 kN-m
Spacing = 300 mm by per meter strip we get n = 3.3 then use n = 3
As = 235.62 mm² rho = 0.0031 a= 3.7
Mu (capacity) = 4.3419 kN-m > Mu (required) /:. It is SAFE

Continuous: Mu (required) = 5.7499 kN-m


Spacing = 100 mm by per meter strip we get n = 10 then use n = 10
As = 785.40 mm² rho = 0.0105 a= 12
Mu (capacity) = 13.6072 kN-m > Mu (required) /:. It is SAFE

For Short Direction: La = 3.00 m Rebars = 10 mm dia. Bar


Grade 40 = 280 Mpa
Midspan: Mu (required) = 3.2670 kN-m
Spacing = 300 mm by per meter strip we get n = 3.3 then use n = 3
As = 235.62 mm² rho = 0.0031 a= 3.7
Mu (capacity) = 4.3419 kN-m > Mu (required) /:. It is SAFE

Continuous: Mu (required) = 4.7520 kN-m


Spacing = 100 mm by per meter strip we get n = 10 then use n = 10
As = 785.40 mm² rho = 0.0105 a= 12
Mu (capacity) = 13.6072 kN-m > Mu (required) /:. It is SAFE

Conclusion:

Therefore the said design is safe!

Reminder: Every documents must have the SEAL and SIGNATURE for it to be VALID.