Академический Документы
Профессиональный Документы
Культура Документы
Database Version : 4.3.20190228 AHU Version : 4.3 Patch 26 Pricing Version : 4.3.20190228
Daikin Refrigeration Malaysia Sdn. Bhd is participating in the EUROVENT CERTIFICATION Programme for Air Handling Units. The range DM2 and DM2TB is certified under the
number 09.11.441 and presented on www.eurovent-certification.com.
AHU specified in this report are manufactured by Daikin Refrigeration Malaysia Sdn. Bhd.
*Supply Air Volume Flow 8400.00 CFM *Return Air Volume Flow 8400.00 CFM *Unit Type : DM2
Rate :
3.96 m³/s Rate : 3.96 m³/s :Polyurethane-PU 40 kg/m³
*Insulation Mat. :Polyurethane-PU
*Inner Skin Thickness 0.5
::0.5 mm *Outer Skin Thickness : 0.5 mm *Delivery Mode : CBU
*Inner Skin Material GI
::GI *Outer Skin Material GI
::GI *Insulation Thickness:50
50 mm
*Inner Surface Painted : No *Outer Surface Painted : Yes Unit Orientation : Horizontal
*Painted Internal Metal No
::No :No
*SSTL Fastener at Frame :No Unit Height (Btm) : 1530 mm
*Painted Base Frame : No *Ceiling Hung Unit :No Unit Height (Top) : 0 mm
*Special Base Height : No *Rubber Cord at Frame Yes
::Yes Unit Width : 1750 mm
*All C-Channel Base : No Cross Section Air Velocity :1.78
1.78 m/s Unit Length : 2550 mm
Cross Section Air Velocity
*Floor Plate : No 0 m/s : 1350 x 1650 mm
Internal Dim. (HxW) :1350
(Upper) :
*Canopy : No Design outdoor
Internal Dim.
temperature 27.00 °C - mm
(HxW, Upper) :
:
Application Type : Recirculation units or units with design inlet temperatures always > 9°C
CAL Class@ -400 Pa : L1 Ext.Leakage +ve. Pressure : 0.15 %
CAL Class@ +700 Pa : L2 Ext.Leakage -ve. Pressure : 0.03 %
ErP Identification Code : NRVU-UVU Internal Specific Fan Power : 4.71 W/(m³/s)
Database Version : 4.3.20190228 AHU Version : 4.3 Patch 26 Pricing Version : 4.3.20190228
Daikin Refrigeration Malaysia Sdn. Bhd is participating in the EUROVENT CERTIFICATION Programme for Air Handling Units. The range DM2 and DM2TB is certified under the
number 09.11.441 and presented on www.eurovent-certification.com.
AHU specified in this report are manufactured by Daikin Refrigeration Malaysia Sdn. Bhd.
Section No #1 #2 #3 #4 #5 #6 #7 #8
Depth mm 2550
Weight kg 586.0
Depth mm
Weight kg
1 PRIMARY FILTER
Database Version : 4.3.20190228 AHU Version : 4.3 Patch 26 Pricing Version : 4.3.20190228
Daikin Refrigeration Malaysia Sdn. Bhd is participating in the EUROVENT CERTIFICATION Programme for Air Handling Units. The range DM2 and DM2TB is certified under the
number 09.11.441 and presented on www.eurovent-certification.com.
AHU specified in this report are manufactured by Daikin Refrigeration Malaysia Sdn. Bhd.
3 SUPPLY FAN
Supply Air Volume 8400.00 CFM Brand : Yilida *Eff Type : IE3 (Premium eff)
Flow Rate : 3.96 m³/s *Model : SYD450R *Brand : TECO
Altitude : 0.00 m Fan Size : 450 mm *Motor Output Power 7.50
: kW
Air Temperature : 20.00 °C Disch. Open (HxW) : 575x575 mm Frame Size : 132M
Air Density : 1.20 kg/m³ At Frequency : 60 Hz N Voltage : 380 V
Internal Static
316.37 Pa Max. Frequency : - Hz N Current : 14.5 A
Pressure :
External Static
500.00 Pa Total Efficiency : 68.0 % Efficiency : 91.7 %
Pressure :
Other Static
4.00 Pa Static Efficiency : 61.3 % Speed : 1770 RPM
Pressure :
Fan System Input
Velocity Pressure : 89.98 Pa 7.52 kW
Power :
*Total Pressure : 910.35 Pa Duct Velocity : 11.99 m/s Watt / CMH : 0.41
*VPT : No *Speed : 1011 RPM *Electrical Supply : 380V/3Ph/ 60Hz
*VFD : Yes *Shaft Diameter : 35 mm *Pole :4
Database Version : 4.3.20190228 AHU Version : 4.3 Patch 26 Pricing Version : 4.3.20190228
Daikin Refrigeration Malaysia Sdn. Bhd is participating in the EUROVENT CERTIFICATION Programme for Air Handling Units. The range DM2 and DM2TB is certified under the
number 09.11.441 and presented on www.eurovent-certification.com.
AHU specified in this report are manufactured by Daikin Refrigeration Malaysia Sdn. Bhd.
*Standby Motor With Specific Fan Power (SFP) : 1.46 kW/(m³/s) *Thermistor : No
No
Heater :
# Design based on wet condition.
# The fan system effect is taken into account in the fan performance.
Sound
Sound Power 63 Hz 125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz Total (dBA)
In-duct Outdoor Air (Lw) dB 87 88 83 86 80 79 77 72 90
In-duct Supply Air (Lw) dB 88 96 87 95 84 82 78 73 95
Casing Sound Power Level (LwA) dB N/A 84 74 80 70 69 53 38 79
# The airborne total (dBA) is calculated for range 125Hz till 8kHz
DOOR LOCATION
ACCESSORIES
SPECIAL REMARK