CONTENTS

Product Specification.………………..…………………...1

Refrigeration Diagram……………………………….…....3

Introductions of Installation………………….……………6

Remote Controller Introductions……………….……….13

Brief Introduction for Usage…………………..………….21

Wiring Diagram……………………………..……………..27

Troubleshooting Guide……………………………………31

Exploded Views & Parts List……………………………..48

I
Chapter 1 Product Specification
1.1 Photo of Product

Indoor Unit

Outdoor Unit

Reminder: All views here are for reference only, Specifications are subject

to the physical product.


1
1.2 Outline

Indoor Unit

MODEL 9000BTU 12000BTU 18000BTU 24000BTU


W mm 680 750 880 1080

D mm 185 185 208 232

H mm 255 255 280 300

Dimensions

Outdoor Unit

MODEL 9000BTU 12000BTU 18000BTU 24000BTU


W mm 663 700 760 800

D mm 254 225 260 300

H mm 421 500 540 590

2
Chapter 2 Refrigeration Diagrams
2.1 Cooling Only

Cooling Mode

Cooling Cycle
Steam-gas of low pressure
Indoor heat exchanger Compressor
(Evaporation) (Compression)

Liquid of low pressure Gas of high pressure


(also a little gas) & temperature

Super cooled liquid


of high pressure
Capillary Outdoor heat exchanger
(Throttling) (Condensation)
3
2.2 Cooling & Heating
Cooling Mode

Cooling Cycle
Indoor heat exchanger Steam-gas of low pressure Compressor
(Evaporation) (Compression)

4-way valve
Liquid of low pressure
(Heat pump only)
(also a little gas)
Gas of high
pressure &
Super cooled liquid temperature
Capillary of high pressure Outdoor heat exchanger
(Throttling) (Condensation)

4
Heating Mode

Heating Cycle
Gas of high
Indoor heat exchanger Pressure & temperature Compressor
(Condensation) (Compression)

4-way valve
(Heat pump only)
Super cooled liquid of low pressure

Steam-gas of
low pressure
Super cooled liquid
of high pressure
Capillary Outdoor heat exchanger
(Throttling) (Evaporation)

5
Chapter 3 Instructions of Installation

SPLIT TYPE WALL MOUNTED AIR-CONDITIONER INSTALLATION INSTRUCTIONS


The Installation Instructions is used to Split type wall mounted air-conditioner installation .

6
The distance between indoor and outdoor unit should be 5 meters and pipe length can
go up to maximum 15 meters with additional refrigerant charge.

Max. Allowable Limit of Tubing Limit of Elevation Requires Amount


Tubing Length at Length(m) Difference H(m) of Additional
Shipment(m) Refrigerant (g/m)
CC 12000Btu CC 18000Btu

5 15 5 20 30

7
10
Unscrew the screw, take off the control panel cover from the unit.
Connect the cable to their terminals according to their number.
The grounded wire connection:
1.loosen the grounded screw of electrical shelf.
2.Connect the grounded wire with the grounded screw then setscrew in the mark formerly.
Fix the cable to the terminal board with fastening piece.
Reinstall the cover with the screw. Terminal board
NOTE:
Cover
Don't reverse the power polarity.
The wrong connection lead to the malfunction
of some electrical parts.
Must fix the screwnail of the firmly wire, then Grounded wire
More than 5mm

drag the wire lightly, confirmation whether it's firmly.


Interconnection cord

Must changed if the wire slide, the self-drive screw Electrical Shelf

Fastener for cable


can't used to the electric connection. connection

If there is a connector, connect it directly.

Terminal board for outdoor unit Compressor signal wire connector and
Compressor signal wire connector temperature control wire connector
Temperature control wire connector (only for cooling pump type (only for heat pump type 6000W/7000W)
(only for heat pump type) 6000W/7000W)

Heat-pump type
Terminal board for outdoor unit and

Single wire Double wires

11
Test the out and in air temperature
Make sure whether the outlet air temperature subtract from inlet sgives more than 10

Plastic Strap

12
AIR-CONDITIONER REMOTE
CONTROLLER INSTRUCTIONS

SET TEMPERATURE( )
AUTO FAN
COOL HIGH
DRY MID
HEAT LOW

ON/OFF

SET

MODE CLEAN SPEED

SLEEP FRESH STRONG

SWING DUST FEELING

HEALTH FUNGUSPROOF SCREEN TIMER

Read this instructions carefully so that


you can use the air-conditioner safely and
correctly.
Take good care of the instructions so
that it can be referred to at any time.
13
Buttons description
LCD displays instruction
SET TEMPERATURE( ) TRANSMIT DIGITAL ON/OFF

AUTO FAN SET ROOM RUNNING


COOL HIGH MODE
DRY MID RUNNING
MODE SPEED
HEAT LOW
TIMER ON OFF
ON/OFF
TIMER FEELING
9 SET 1
ON/OFF display:
10 2 when the remote controller is
MODE CLEAN SPEED
11 3
the on state, the LCD will be
SLEEP FRESH STRONG displays otherwise will not be
12 4 display.
SWING DUST FEELING Digital display:
13 5
6
Under the state of normal
HEALTH FUNGUSPROOF SCREEN TIMER
working. It displays set
14 7
temperature, while the feeling
function is start. It will displays
15 8 room temperature, and under
the state of timer mode. It will
displays set timer.

1. ON/OFF button
You can start the air-conditioner by pressing this button and stop its
operation by pressing it again.
2. FRESH button
This button is invalidation.
3. SPEED button
You can select fan speed show as the follow:

Low Med High Auto

4. STRONG button
Only under the state of cooling or heating mode, press this button, the fan speed is
adjusted to strong auto-maticlly and the LCD displays high fan , the strong
function is started to reach the highest cooling or heating.

14
5. FEELING button
When it displays FEELING button:
Press this button can be used to set the feeling function. The LCD shows
the actual room temperature when the function set and it shows the setting
temperature when the function cancelled. This function is invalid when the
appliance at the Fan mode.
6. DUST button
This button is invalidation.
7. TIMER button
Setting the ON timer time
a. When remote controller is at off state, press TIMER button, the LCD displays
TIMER ON and the timer time, the range of setting time is 0.5h to 24h.
b. You can press the or button to adjust the timer time, each touch will
be set time to increase or reduce 0.5h before 10 hours ago, after ten hours will be
set time to increase or reduce 1h per pressing, to enables your required timer.
c. Press TIMER button again, to set the timer on function.
d. You can set another function to insure the suitable state after air conditioner turn
on (including mode, temperature, swing, fan speed and etc). The LCD will displays
all your setting and keep it, when the timer reach to the set time, the air conditioner
will be working according to your set automatically.
Setting the OFF timer time
a. When remote controller is at on state, press TIMER button, the LCD displays
TIMER OFF and the timer time, the range of setting time is 0.5h to 24h.
b. You can press the or button to adjust the timer time, each touch will
be set time to increase or reduce 0.5h before 10 hours ago, after ten hours will be
set time to increase or reduce 1h per pressing, to enables your required timer.
c. Press TIMER button again, to set the timer off function.

8. SCREEN button
You can let the LCD displays working or not by pressing this button.

9. or button
Press the + or - button,you can set the temperature range from 16 to
32 ,Display will change as you touch the button.
10. CLEAN button
a. When remote controller is at the off state, press clean button, the wind
guiding bars turn to initial postions for cooling, the A/C runs clean function
with max duration 35mins.The purpose of its function is to clean dust on evapo
rator and dry the inside water of evaporator and to prevent the evaporator going
moldy due to water deposition and boasting strange smell.
b. After setting clean function, press clean button again to cancel clean
function or press ON/OFF button to cancel clean function and start A/C.
c. The clean function will be no working after 35 minutes running working without
any operation.

15
Note: clean function can be set in parallel with time start function;
in this case , time start function will be executed after clean function.
11. MODE button
Which enables you to select different operation mode,after each pressing, the
operation mode will be changed. It shows in the following display.
AUTO COOL DRY HEAT FAN AUTO
Remark: cold wind type has no heating function.
12. SLEEP button
1.press the SLEEP button, the sleeping indicator light of indoor unit flashes on.
2.after the setting of sleeping mode, the cooling operation enables the set te
mperature to increase 1 after 1hour and another 1 automatically after 1 hour.
3.after the setting of sleeping mode, the heating operation enables the set
temperature to drop 2 after 1hour and another 2 automatically after 1 hour.
4.the air-conditioner runs in sleeping mode for 7 hours and stops automatically.
Remark: press the MODE or ON/OFF button, the remote controller clears
sleeping mode away.
13. SWING button
Press this button, the horizontal wind direction vanes can rotate automatically,
when you have the desired vertical wind direction, press it again, the horizontal
wind direction vanes will be stopped at the situation of your choice.
14. HEALTH button
Press this button, you can turn on or off the health function.
15. FUNGUSPROOF button
This A/C has special dry and anti-mold function which has yes or no
two selections. This function is controlled by the remote controller under cooling,
dry and auto (cooling and dry) modes, the horizontal wind guiding bars are at the
initial position for cooling. The A/C runs under heating mode(the cooling only A/C
only runs under fan mode), the internal fan runs for three minutes with weak wind
before stop. The purpose of this function is to dry the inside of the evaporator and
to prevent the evaporator from going mouldy due to water deposition and thus disp
ersing strange smell.
Note:
1.This function has not been set in the factory. You may freely set and cancel
this function. The setting method is: under off status of the A/C and the re
mote controller, point the remote controller toward the A/C and continuously
press FUNGUSPROOF pushbutton for one time, the buzzer keep beeps five
times again after five times beeps, indicating that this function is ready. In case
this function has been set, unless the whole A/C is powered off or the function is
manually cancelled, the A/C then has this function as a default;
2.To cancel the function: 1. Power off the whole A/C; 2. Under off status of
theA/C and the remote controller, point the remote controller toward the A/C
and continuously press FUNGUSPROOF pushbutton for one time, the buzzer
keep beeps three times again after five times beeps, indicating that this function
has been cancelled;
3.When this function is on, it is suggested not to restart the A/C before it is co
mpletely stop;
4.This function will not run in case of time stop or sleep stop.

16
Usage
Fix batteries

1.Slide open the cover according the direction indicated by arrowhead.


2.Put into two brand new batteries (7#), position the batteries to right electric
poles (+ -).
3.Put back the cover.

Automatic operation mode


1.Press the MODE button, select the automatic operation mode.
2.Press the SPEED button, you can select fan speed.You can select fan
speed from LOW, MID, HIGH, AUTO.
3.Press the ON/OFF button, the operation indicator is on, the air-conditioner
starts to operate the automatic mode.Press the button again, the air-conditioner
stops.
Cooling/Heating operation mode
(cold wind type has no heating function)
1.Press the MODE button, select the Cooling or Heating operation mode.
2.Press the or button, set the temperature, temperature can
be set at 1 difference range from 16-32 .
3.Press the SPEED button, you can select fan speed.You can select fan speed
from LOW, MID, HIGH, AUTO.
4.Press the ON/OFF button, the operation indicator is on, the air-conditioner starts
to operate the automatic mode.Press the button again, the air-conditioner stops.
Fan operation mode
1.Press the MODE button, select the Cooling or Heating operation mode.
2.Press the SPEED button, you can select fan speed.You can select fan speed
from LOW, MID, HIGH.
3.Press the ON/OFF button, the operation indicator is on, the air-conditioner
starts to operate the automatic mode.Press the button again, the air-conditio
ner stops.
Remark: In the circulation operation mode, to set the temperature is
noneffective.

Drying operation mode


1.Press the MODE button, select the Dry operation mode.
2.Press the or button, set the temperature, temperature can be set
at 1 difference range from 16-32 .
3.Press the SPEED button, you can select fan speed.You can select fan speed
from LOW, MID, HIGH, AUTO.
4.Press the ON/OFF button, the operation indicator is on, the air-conditioner starts
to operate the automatic mode.Press the button again, the air-conditioner stops.
17
Night Luminous Function of Remote Controller(Only the rem
ote controller with this function can be used)
For your convenient use of the remote controller in the darkness without any
lighting, this remote controller has blue background light and luminous pushbuttons.
Function at you press on any of the pushbutton, the background light will immediately
release soft light so that you are easy to operate the remote controller. If you do not
operate the controller within 10 seconds, the background light will automatically
disappear.
Note:
All the figures above are the displays after being initially electrified or
re-electrified after power off. In actual operations, the remote controller
screen displays related items only.
Attention
1.Aim the remote controller towards the receiver on the air-conditioner.
2.The remote controller should be within 8 meters away from the receiver.
3.No obstacles between the remote controller and receiver.
4.Do not drop or throw the remote controller.
5.Do not put the remote controller under the forceful sunrays or heating facilities
and other heating sources.
6.Use two 7# batteries, do not use the electric batteries.
7.Take the batteries out of remote controller before stop its using for long.
8.When the noise of transmitting signal can t be heard indoor unit or the transmission
symbol on the display screen doesn t flare, batteries need be replaced.
9.If reset phenomenon occurs on pressing the button of the remote controller, the
electric quantity is deficient and new batteries need to be substituted.
10.The waste battery should be disposed properly.

18
19
20
Chapter 5 Brief Introduction for Usage

21
22
23
24
25
26
Chapter 6 Wiring Diagram
6.1 Electric chart for 09/12/18K/12K(115V)(Non inverter)

Indoor unit

27
Outdoor unit

28
6.2 Electric chart for 24K(Non inverter)

Indoor unit

29
Outdoor unit

30
Chapter 7 Troubleshooting Guide

7.1 Error Code


No. Error Code Problem

1 E1 Temperature sensor of air intake fault

2 E2 Temperature sensor of outdoor coil fault

3 E3 Temperature sensor of indoor coil fault

4 E4 PG motor of indoor unit feedback fault

7.2 Troubleshooting Guide for 09-12K


1. The Foremost Inspecting Items
⑴The input voltage must be within +10% tolerance of the rated Voltage. If it

is not the case, the air-conditioner will probably not work normally.

⑵Check the connecting cord between indoor unit and outdoor unit to see if

it is properly connected. The connecting must be done according to the

wiring diagram, please also notice that even different models may have the

connecting cord of the same specification.

Please check if the marks at the connecting terminal and the marks on the

cord can match, otherwise, the air-conditioner will not work normally.

⑶If the following phenomena are found, the problem is not from the

air-conditioner itself.
31
NO. Problems Causes
Since the air-conditioner is powered on, it
The motor is heard operating but the
will come to working condition as long as you
1 air-conditioner dose not work when
press the ON/OFF button of the remote
the indoor unit is powered on
control and the Signal is well received.
The compressor stops running but If you turn off the air-conditioner and restart it
the indoor fan motor keeps working immediately, it will return to normal in 3
2 when it is at cooling mode with the minutes, after that, the air-conditioner will
indoor temperature higher than set automatically adjust the indoor fan speed to
temperature. what you set.
The compressor works The air-conditioner will automatically control
3 discontinuously at dehumidifying the working of the compressor according to
mode. the inside temperature
The TIMER is set with the air-conditioner; it
The air-conditioner does not work will be in hold on condition. If the TIMER
4
while the LED display is on. setting is cancelled, the air-conditioner will
return to normal working condition
The compressor works
The compressor stops internally or the fan
discontinuously at cooling and
5 motor slows down to prevent the indoor heat
dehumidifying mode, and the indoor
exchanger from being frozen.
fan motor slows down.

32
2. No Power Display
⑴Items

a) Check if the input voltage is correct?

b) Check if the AC power supply connecting is correct?

c) Check if the output voltage of the manostat L7805 (IC2) is correct?

⑵Trouble shooting procedure

33
3. The Indoor Fan Motor Does Not Work
⑴Items

a) Check if the indoor fan motor is connected correctly to the connector (CN8)?

b) Check if the AC input voltage is correct?

c) Check if the IC of indoor fan motor is connected correctly to the connector

(CN2)?

d) Check if the capacity of indoor fan motor is connected correctly to the

connector (CN8)?

⑵Trouble shooting procedure

34
4. The Outdoor Unit Does Not Work
⑴Items

a) Check if the input voltage is correct?

b) Check if the wire connection of the outdoor connecting terminal is correct?

⑵Trouble shooting procedure

35
5. The Step Motor Does Not Work
⑴Items

a) Check if the input voltage is correct?

b) Check if the step motor controlling the up-down movement firmly

connected to Cn2?

⑵Trouble shooting procedure

36
6. Heating Mode Can Work, But No Hot Air Blow
⑴Check if the set temperature is lower than the indoor temperature?

⑵Check if the indoor PCB is connected to the terminal correctly?

37
7. Remote Control Can Not Work
Trouble shooting procedure

38
8. The Failure Analysis of the Main Parts

39
7.3 Troubleshooting Guide for 18-36K
1. The Foremost Inspecting Items
⑴The input voltage must be within +10% tolerance of the rated Voltage. If it

is not the case, the air-conditioner will probably not work normally.

⑵Check the connecting cord between indoor unit and outdoor unit to see if

it is properly connected. The connecting must be done according to the

wiring diagram, please also notice that even different models may have the

connecting cord of the same specification.

Please check if the marks at the connecting terminal and the marks on the

cord can match, otherwise, the air-conditioner will not work normally.

⑶If the following phenomena are found, the problem is not from the

air-conditioner itself.

NO. Problems Causes


Since the air-conditioner is powered on, it will come to
The motor is heard operating but the
working condition as long as you press the ON/OFF
1 air-conditioner dose not work when the indoor
button of the remote control and the signal is well
unit is powered on
received.

The compressor stops running but the indoor fan If you turn off the air-conditioner and restart it
motor keeps working when it is at cooling mode immediately, it will return to normal in 3 minutes, after
2
with the indoor temperature higher than set that, the air-conditioner will automatically adjust the
temperature. indoor fan speed to what you set.

The compressor works discontinuously at The air-conditioner will automatically control the working
3
dehumidifying mode. of the compressor according to the inside temperature
The TIMER is set with the air-conditioner; it will be in hold
The air-conditioner does not work while the LED
4 on condition. If the TIMER setting is cancelled, the
display is on.
air-conditioner will return to normal working condition.
The compressor works discontinuously at cooling The compressor stops internally or the fan motor slows
5 and dehumidifying mode, and the indoor fan down to prevent the indoor heat exchanger from being
motor slows down. frozen.

40
2. No Power Display
⑴Items

①Check if the input voltage is correct?

②Check if the AC power supply connecting is correct?

③Check if the output voltage of the manostat L7805(IC2)is correct?

⑵Trouble shooting procedure

41
3. The Indoor Fan Motor Does Not Work
⑴Items

①Check if the indoor fan motor is connected correctly to the connector(CN8)?

②Check if the AC input voltage is correct?

③ Check if the IC of indoor fan motor is connected correctly to the

connector(CN2)?

④Check if the capacity of indoor fan motor is connected correctly to the

connector(CN8)?

⑵Trouble shooting procedure

42
4. The Outdoor Unit Does Not Work
⑴Items

①Check if the input voltage is correct?

②Check if the wire connection of the outdoor connecting terminal is correct?

⑵Trouble shooting procedure

43
5. The Step Motor Does Not Work
⑴Items

①Check if the input voltage is correct?

②Check if the step motor controlling the up-down movement firmly connected

to Cn2?

⑵Trouble shooting procedure

44
6. Heating Mode Can Work, But No Hot Air Blow
⑴Check if the set temperature is lower than the indoor temperature?

⑵Check if the indoor PCB is connected to the terminal correctly?

45
7. Remote Control Can Not Work
Trouble shooting procedure

46
8. The Failure Analysis of the Main Parts

47
Chapter 8 Exploded Views & Parts List
8.1 Indoor unit for PAC9040A/PAC13040A/PAC12520A

48
Parts List of Indoor unit for PAC9040A/PAC13040A/PAC12520

Exploded View
Name Pcs Part No.
No
1 Panel 1
2 Display board 1
3 Indication lamp holder 1
4 Electrostatic precipitator 1
5 Sterilization filter 1
6 Filter 2
7 In box screw cap 3
8 Horizontal air-blade 1
9 Cover of medium frame 1
10 Panel clasper 1
11 Stand bar 2
12 Medium frame 1
13 Wire mesh enclosure 1
14 sleeve 1
15 Step motor 1
16 Air-vent holder 1
17 Vertical air-blade 2
18 Bracket of airflow vanes 1
19 Evaporator assembly 1
20 Cross flow fan 1
21 Fan motor 1
22 Motor cover 1
23 Negative ion 1
24 Chassis 1
25 Mounting plate 1
26 Left plastic-crutch for evaporator 1
27 Bearing holder for indoor fan 1
28 Cover of controller box 1
29 Power supply clamp 1
30 Connection cable clamp 1
31 Terminal board 1
32 Main PCB 1
33 Controller box 1
34 Transformer 1
35 Power supply 1
36 Connection cable 1

49
8.2.1 Outdoor unit for PAC9040A

50
Parts List of Outdoor unit for PAC9040A
Exploded
Name Pcs Part No.
View No
1 Electric cover 1
2 Right side plate 1
3 Gas valve assembly 1
4 Liquid valve assembly 1
5 Valve plate 1
6 Chassis assembly 1
7 right footing 1
8 Pump bolt 3
9 left footing 1
10 rubber cushion 3
11 Compressor assembly 1
12 Big washer 3
13 Hexagonal nut 3
14 Front net 1
15 Panel 1
16 Hexagonal nut 1
17 Light spring washer 1
18 Propeller fan 1
19 Fan motor 1
20 Holder for fan motor 1
21 Partition plate 1
22 Left clapboard 1
23 Top cover board 1
24 Condensor assembly 1
25 Front net 1
26 Condenser inlet pipe assembly 1
27 4-Ways valve pipe assembly 1
28 Capillary assembly 1
29 Fan motor capacitor 1
30 Capacitor clamp 1
31 Compressor capacitor 1
32 Holder for E-parts 1
33 Terminal board 1
34 electricity cord clamp 1

51
8.2.2 Outdoor unit for PAC 13040A/PAC12520A

52
Parts List of Outdoor unit for PAC 13040A/PAC12520A
Exploded
Name Pcs Remark
View No
1 Panel net 1
2 Panel 1
3 Axial-flow fan 1
4 Fan motor 1
5 Motor bracket 1
6 Condenser assembly 1
7 Top cover 1
8 Partition plate 1
9 Compressor capacitor 1
10 Capacitor clamp 1
11 Fan capacitor 1
12 Holder of electrical unit 1
13 Terminal board 1
14 Chassis assembly 1
15 Handle 1
16 Back net 1
17 Right side plate 1
18 Liquid valve 1
19 Gas valve 1
20 Valve plate 1
21 Compressor tubing assembly 1
22 Air inlet tube of condenser 1
23 Compress 1
24 Capillary 1
25 Left side plate 1

53
8.3 Indoor unit for PAC18040 A

54
Parts List of Indoor unit for PAC18040 A
No Name Quantity Remark
1 Panel 1
2 Filter 2
3 Panel clasper 3
4 Medium frame 1
5 Horizontal airflow blade 1
6 Air-vent holder 2
7 Connecting rod for airflow vanes 1
8 Vertical airflow vanes A 7
9 Vertical airflow vanes B 7
10 Bracket of airflow vanes 1
11 Bearing for indoor fan 1
12 Cross-flow fan 1
13 Left-hand propping holder for evaporator 1
14 Evaporator assembly 1
15 chassis 1
16 Foam of left chassis 1
17 Mounting plate 1
18 Foam of right chassis 1
19 Pipe clamp 1
20 Negative ion 1
21 Right-hand propping holder for evaporator 1
22 Motor cover 1
23 Indoor fan motor 1
24 Step motor of airflow vanes 1
25 Controller box 1
26 Vertical airflow vanes 1
27 Transformer 1
28 Clamp of cable A 1
29 Clamp of cable B 1
30 Room temperature sensor 1
31 Main PCB 1
32 Step motor of airflow blade 1
33 pipe temperature sensor 1
34 Terminal board 1
35 Cover of controller box 1
36 Connection cable 1
37 Power supply plug 1
38 Screw cover 1
39 Cover of medium frame 1
40 Stand bar 1
41-42 Display board55 1
43 Panel 1
Outdoor unit for PAC18040 A

56
Parts List of Outdoor unit for PAC18040 A
NO Item Description Pcs Remark

1 Panel net 1
2 Panel 1
3 Axial-flow fan 1

4 Fan motor 1
5 Motor bracket 1

6 Condenser assembly 1

7 Top cover 1
8 Partition plate 1

1
9 Compressor capacitor

10 Capacitor clamp 1

11 Fan capacitor 1

1
12 Holder of wiring uint

13 Terminal board 1

14 Chassis assembly 1

15 handle 1

16 Back net 1
1
17 Right side plate

18 Liquid valve 1

19 Gas valve 1
20 Valve plate 1

1
21 Compressor tubing assembly

1
22 Air inlet tube of condenser

23 Compressor 1

24 Capillary assembly 1

25 Left side plate 1

57
8.4 Indoor unit forPAC2404 0A

58
Parts List of Indoor unit for PAC2404 0A
No Name Quantity Remark
1 Panel 1
2 Filter 2
3 Panel clasper 3
4 Medium frame 1
5 Horizontal airflow blade 1
6 Air-vent holder 2
7 Connecting rod for airflow vanes 1
8 Vertical airflow vanes A 7
9 Vertical airflow vanes B 7
10 Bracket of airflow vanes 1
11 Bearing for indoor fan 1
12 Cross-flow fan 1
13 Left-hand propping holder for evaporator 1
14 Evaporator assembly 1
15 chassis 1
16 Foam of left chassis 1
17 Mounting plate 1
18 Foam of right chassis 1
19 Pipe clamp 1
20 Negative ion 1 optional
21 Right-hand propping holder for evaporator 1
22 Motor cover 1
23 Indoor fan motor 1
24 Step motor of airflow vanes 1
25 Controller box 1
26 Vertical airflow vanes 1
27 Transformer 1
28 Clamp of cable A 1
29 Clamp of cable B 1
30 Room temperature sensor 1
31 Main PCB 1
32 Step motor of airflow blade 1
33 pipe temperature sensor 1
34 Terminal board 1
35 Cover of controller box 1
36 Connection cable 1
37 Power supply plug 1
38 Screw cover 1
39 Cover of medium frame 1
40 Stand bar 1
41 Holder of display board 1
42 Display screen 1
43 Panel 1

59
Outdoor unit for PAC2404 0A

60
Parts List of Outdoor unit for PAC2404 0A
Exploded
Name Pcs Remark
View No

1 Left clapboard 1
2 Front net 1
3 Big flat head self-drilling screw 40
4 Top cover board 1
5 Panel 1
6 Condensor assembly 1
7 Right side plate 1
8 Capacitor clamp 1
9 Compressor capacitor 1
10 Fan motor capacitor 1
11 Electric cover 1
12 Holder for E-parts 1
13 Terminal board 1
14 Partition plate 1
15 Compressor assembly 1
16 Capillary assembly 1
17 Compressor pipe assenbly 1
18 Liquid valve assembly 1
19 Gas valve assembly 1
20 Chassis assembly 1
21 Phillips screw 4
22 Valve plate 1
23 Propeller fan 1
24 Holder for fan motor 1
25 Fan motor 1
26 Phillips pan head self-drilling screw 1