PRODUCT DESCRIPTION AND Material Safety Data Sheet (MSDS) for the most
APPLICATION current data and complete information.
ELIMIN-OX can be used in boiler systems ELIMIN-OX is not approved by the USDA.
operating at pressures up to 2,500 psig (172 ELIMIN-OX is not regulated as a hazardous
barg). ELIMIN-OX does not contribute waste or toxic pollutant.
dissolved solids, so it can be used ahead of spray
attemperation water take-offs. It can also be Please refer to the MSDS, SECTION 15, for the
used for wet lay-up of boilers and non-drainable most recent information on approvals.
superheater.
MATERIALS OF COMPATIBILITY
PHYSICAL & CHEMICAL
PROPERTIES Compatible Not Compatible
Buna-N Bronze
Form Liquid Hypalon Copper
Appearance Colorless Plasite 7122 Mild steel
Odor None Polypropylene Neoprene
Specific Gravity @20°C 1.02 Stainless steel Nickel
Density 8.5 – 8.6 lb/gal (1.02 – 1.03 kg/L) Teflon Nylon
pH (Neat) 8.3 Vinyl
pH (1%) 6.7 Viton
Solubility in Water Complete
Viscosity @15°C 3.0 cps See your local Nalco representative for
Freeze Point –2°C compatibility information.
Flash Point (PMCC) N/A
The feedwater dosage of ELIMIN-OX will vary Please refer to the MSDS, SECTIONS 3 and 8,
based on the feedwater oxygen level, boiler for the most current data.
operating pressure and the boiler water cycles of
concentration. For your specific application, STORAGE
your local Nalco sales engineer will make the
appropriate feed rate recommendations. Store ELIMIN-OX at temperatures below 49°C
and above 4°C to avoid loss of stability and
Underfeed of ELIMIN-OX will result in precipitate formation. Once formed, the
serious oxygen corrosion to the preboiler, boiler precipitate cannot be resolubilized and loss of
and condensate system. Severe damage can product activity will occur.
occur very quickly in economizers or feedwater
preheaters. Oxygen corrosion will also increase Keep ELIMIN-OX from freezing. Freeze-thaw
iron levels in the feedwater. Iron deposits will recovery is incomplete (small amount of
form in the high heat-flux areas of the boiler and precipitation). Freeze point is –2°C.
could possibly cause tube failures.
The in-plant storage limit for ELIMIN-OX is
Overfeed of ELIMIN-OX will result in high one year under proper storage conditions.
levels of ammonia in the condensate system.
This may be sufficient to increase the measured Bulk tanks should be of polyethylene or stainless
pH of the condensate system. The neutralizing steel construction.
amine dosage should not be reduced. This would
result in inadequate protection of the condensate Please refer to the MSDS, SECTION 7, for the
system. The combination of ammonia and most current data.
oxygen in-leakage is extremely corrosive to
copper-containing metallurgies. REMARKS
Overfeed will also significantly affect the cost of If you need assistance or more information on
the chemical program. this product, please call your nearest Nalco
Representative. For more news about Nalco
For complete dosage, feeding points and feeding Company, visit our website at www.nalco.com.
equipment, consult your Nalco representative.
For Medical and Transportation Emergencies
ENVIRONMENTAL AND TOXICITY involving Nalco products, please see the
DATA Material Safety Data Sheet for the phone
number.
Biological Oxygen Demand (BOD5) N/A
Chemical Oxygen Demand (COD) N/A
Total Organic Carbon (TOC) N/A