Вы находитесь на странице: 1из 1

PRODUCED BY AN AUTODESK STUDENT VERSION

H. NOTES ON COLUMNS
A. GENERAL D. NOTES ON MASONRY
1. Confinement ties shall be provided on all columns at beam column intersection, unless otherwise
1. Construction notes and typical details apply to all drawings unless otherwise shown or 1. All non-load bearing type of concrete blocks shall have a unit weight not to exceed 80 pcf. For
shown in structural plans.
noted. Modify typical details as directed to meet special conditions. non-load bearing type concrete blocks, a minimum compressive strength of 2.76 MPa (400psi) and
5.17 MPa (750 psi) for load bearing type shall be developed. 2. Column ties shall be protected everywhere by covering of concrete cast monolithically with the core
2. Shop drawings with erection and placing diagrams of all structural steel, miscellaneous iron, of minimum thickness of 40mm.
pre-cast concrete, etc. shall be submitted for Engineer's approval before fabrication. 2. Provide 1-Ø16 extra vertical bars at corners, intersections, end of walls, and each side of openings
as shown. 3. Splices should be made within the center half of the column length.
3. Contractor shall verify all dimensions before all work s to begin. Check with mechanical an 4. Splices to be confined by a minimum of 3 links. Top most link to be at top of lower splice bar.
3. Lintel beams or mintel blocks shall bear at least 8 inches (200mm) on each side of masonry wall
electrical contractors for conduits, pipe sleeves, etc. to be embedded in concrete.
opening. 5. No more than half of bars may be spliced at any one section. Splices must be at least 1.00 meter
4. It shall be the contractor's responsibility to provide adequate shorings and bracings of the 4. Wall reinforcements shall be as follows: apart from each other.
structure for all loads that maybe imposed during construction. 6. Welded splice for longitudinal bars with coupling can be considered subject to final approval by
VERTICAL HORIZONTAL
WALL THICKNESS Structural Engineer.
REINFORCEMENT REINFORCEMENT

PRODUCED BY AN AUTODESK STUDENT VERSION


B. CONCRETE & REINFORCEMENT 8 in. Ø12 400mm Ø10 600mm 7. Splices shall be confined by hoops 100mm in spacing through the splice length.
PRODUCED BY AN AUTODESK STUDENT VERSION

6 in. Ø10 400mm Ø10 600mm


1. All materials and workmanship shall conform with the latest building code of American
4 in. Ø10 400mm Ø10 600mm
Concrete Institute (ACI-318).
LAP SPLICE & ANCHORAGE
2. All concrete shall develop a minimum compressive strength at the end of twenty eight (28) 5. Block wall reinforcing bars shall be lapped a minimum of 30 bar diameters where spliced, LAP SPLICE (m) MIN. LAP SPLICE
days with corresponding maximum size aggregate and slumps as follows: horizontal/vertical dowels from footings, column/walls, or slabs shall extend into the block wall a BAR
STANDARD HOOK (m)
UNIT
LENGTH OF COL.
REINF. INDIVIDUAL
ANCHORAGE BARS
DIAMETER TENSION BAR COMPRESSION BAR WEIGHT
LENGTH (m)
minimum of 30 bars diameters or a minimum of 400 mm whichever is longer and dowels to match (mm) (Kg/m)

LOCATION 28 DAYS STRENGTH MAX. SIZE AGGREGATE MAX SLUMP vertical reinforcements of wall. 90° 180° 135° TOP BAR OTHERS TOP BAR OTHERS W/ TIES W/ SPIRAL

Curbs & Slab on Grade 3000 psi (210kg/cm)2 1 in. (25mm) 4 in. (100mm) 6. All cells containing reinforcing vars or inserts shall be solidly filled with concrete grout. (Refer to 10 0.5000 0.1500 0.1300 0.1000 0.4200 0.3000 0.4200 0.3000 0.6170 0.3000 0.3000

(except Found) Specifications) 12 0.5000 0.2000 0.1500 0.1200 0.4200 0.3000 0.4200 0.3000 0.8890 0.3000 0.3000
Foundation 3000 psi (210kg/cm)2 ¾ in. (19mm) 4 in. (100mm)
E. TYPICAL RC WALL REINFORCEMENT
Columns & Walls 3000 psi (210kg/cm)2 ¾ in. (19mm) 4 in. (100mm) 16 0.6000 0.2500 0.1800 0.1400 0.7300 0.5200 0.8700 0.6200 1.5800 0.5200 0.4700

Beams & Slabs 3000 psi (210kg/cm)2 ¾ in. (19mm) 4 in. (100mm) 1. RC Wall Reinforcement shall be as follows: 20 0.6000 0.3000 0.2000 0.2000 0.9100 0.6500 1.1000 0.7800 2.4690 0.6500 0.5800

VERTICAL HORIZONTAL 25 0.6800 0.4000 0.2800 0.2600 1.1500 0.8200 1.4000 1 3.8580 0.8000 0.7300
2.1Light weight concrete shall have a unit weight of 110 pcf, Fc' =3000 psi at 28 days. Submit a WALL THICKNESS
REINFORCEMENT REINFORCEMENT
brochure and material sample for Engineer's approval. 28 0.8600 0.4800 0.3800 - 1.4500 1.0300 1.5300 1.0900 4.8400 0.9000 0.8200
8 in. Ø10 300mm E.F. Ø10 300mm E.F.
1. Reinforcing bars shall be grade 40 and diameter 10 and smaller, grade 60 for diameter 12 and larger, 6 in. Ø10 250mm E.F. Ø10 300mm E.F. 32 1.1200 0.6100 0.4300 - 1.9000 1.3500 1.7400 1.2400 6.3270 1.0300 0.9300

and conform to ASTM A706M (PNS 49). 5 in. Ø10 300mm Ø10 400mm 36 1.4300 0.6100 0.4800 - 2.4000 1.7000 2.0000 1.4000 8 1.2000 1.0500

2. In general, the latest edition of ACI-315, Manual standard practice detailing reinforced concrete 4 in. Ø10 400mm Ø10 400mm NOTES:

structures hall be adhered to, unless otherwise shown or noted. 2. Vertical Reinforcing shall be continuous from structural level to structural level unless noted 1. ACI SECTION 12.4 STATES THAT DEVELOPMENT LENGTH OF INDIVIDUAL BARS W/ IN A BUNDLE, IN TENSION
OR COMPRESSION, SHALL BE THAT FOR THE INDIVIDUAL BAR, INCREASED 20% FOR THREE BAR BUNDLE,
AND 33% FOR FOUR BAR BUNDLE.

otherwise. 2. FOR COLUMNS, AT ANY LEVEL NO MORE THAN ALTERNATE BARS SHOULD BE SPLICED. NOT MORE THAN
33% OF THE BARS SHALL BE SPLICED W/ IN THE REQUIRED LAP LENGTH. MINIMUM DISTANCE BETWEEN

3. Maintain minimum concrete cover for reinforcing steel as follows: 3.


TWO ADJACENT BAR SPLICES SHALL BE 600MM.
TOP BARS ARE HORIZONTAL BARS W/ MORE THAN 300 MM DEPTH OF CONCRETE CAST BELOW THE
REINFORCEMENT.
3. Horizontal spacing shall start and end from not more than1/2 the schedule spacing. 4. AS MUCH AS POSSIBLE, SPLICES SUBJECTED TO TENSILE STRESSES ARE DISCOURAGE, THERE SHOULD

i. Suspended slabs ………………………………………………………………...........………….. ¾ in. (19mm) BE AVOIDED OR PROVIDED W/ STANDARD HOOKS.

4. Splices n horizontal reinforcement shall be staggered, splices in two curtains shall not focus in the
ii. Slab on grade ……………………………………………………………………............………... 1 ½ in. (38mm)
same location.
iii. Walls about grade ……………………………………………….………………….……. 1 in. (25mm)
5. This table applies to walls which are architecturally exposed to view.
iv. Beam stirrups and Column ties ……………………………….………………….... 1 ½ in. (38mm)
6. Tension splices shall be as for seismic tension splices.
v. Where concrete is exposed to earth but poured against forms …...… 2 in. (50mm) 12MM Ø VERTICAL REINFORCEMENT
SPCD @ 0.60M
vi. Where concrete is deposited directly against earth ……………….……… 3 in. (75 mm) F. NOTES ON CONSTRUCTION SLAB
4. Splices shall be securely wired together and shall lap or extend in accordance to table 1 (Table of lap 1. All Slab reinforcement shall be at least 25mm clear minimum fom bottom and top of slab.
splice and anchorage length) unless otherwise shown on drawings, splices shall be staggered
whenever possible. 2. If slab are reinforced bothways, bars along the short span shall be place below those along the long
span at the center and over the longer span bars near the supports. 12MMØ HORIZONTAL REINFORCEMENT
5. All anchor bolts, dowels, and other inserts shall be properly positioned and secured in place prior to
3. Temperature bars for slabs shall be generally placed near the face in tension and shall not be less @EVERY THREE LAYERS
placing of concrete.
than 0.002 bt for Grade 40 & 0.0018 for Grade 60.
6. Contractor shall note and provide all miscellaneous curbs, sills, stools, equipment, and mechanical
bases that are required by the architectural, electrical, and mechanical drawings. MASONRY
7. All concrete shall be kept moist for a minimum of seven (7) consecutive days immediately after G. NOTES ON REINFORCED CONCRETE BEAMS AND GIRDERS 1. ALL CONCRETE HOLLOWBLOCKS
pouring by the use of wet burlap, fog spraying, curing componds or other approved methods. 1. If beam reinforcing bars end in wall, the clear distance from the bar to the farther face of the wall WALL SHALL BE LAID IN RUNNING
BOND (INTERLOCKING COURSE) WITH
8. Stripping of forms and shores: shall not be less than 5 bar diameters. The reinforcing bars shall terminate on a standard 90° hook,
FULL MORTAR BEDDING,
a.Foundation……………………………………………………………………..………......24 hrs. 2. If there are two or more layers of reinforcing bars, use 25mm separator between layers of bars at STACK BOND SHALL BE USED ONLY
900mm O.C. In no case shall there be less than two separators between layers of bars. WHEN SPECIFIED.
b.Suspended Slab except when additional loads are
imposed…………………….……………….……….………...................................8 days 3. When a beam crosses a girder, girder bars shall be on top of beam bars. 2. ALL CELLS SHALL BE SOLIDLY FILL
THE CONCRETE GROUT.
c. Columns & Walls…………………………….…………………….……………………….18 hrs. 4. Generally, no splice shall be permitted on beans at points where critical bending stresses occur.
Welded splices shall develop on tension at least 125 percent of the specified yield strength of the
d.Beams………………………………………………………………………….………….……14 days bar. Not more than 50 percent of the bars at any section shall be splice therein.
C. FOUNDATION 5. Pipes are allowed to cross beams in a transverse manner only within the middle third of the span
1. Foundation is designed for a soil bearing capacity of 140 KPa (2800 psf) and should be placed 50mm below the beam mid-depth. The pipes should be encased.
2. Foundation shall rest on natural soil unless otherwise noted by the Engineer. No part of the
foundation shall rest on a fill.
3. The contractor shall notify the Engineer after footing excavation have been completed and prior to
concreting to confirm the design SBC.

NOTE: PROJECT TITLE: SUBMITTED BY SECTION CAD BY: SHEET CONTENT: SHEET NO:
REPUBLIC ACT 9266: This drawing is an instrument of DESIGN BY:
service is the property of the Architect, registered Architect
and as such must not be reproduced or copied in part or in PROPOSED 5 STOREY RESIDENTIAL AND ATIENZA, RACHELLE CHECKED BY:
whole without permission. All drawings are to be returned CE182-1L / E03 ENGR. WYNDELL ALMENOR
COMMERCIAL BLDG. W/ DECK MAYUGA, DANIEL APPROVED BY:
when no longer in use. PRESIDENTIAL DECREE NO. 49:
"Protection of Intellectual Property" Works of Art, NAKPIL KEILAH
REG. NO. - PTR. NO. - PRODUCED BY AN AUTODESK STUDENT VERSION
Architecture, Model and Designs are creative works and
REVISION:
TIN NO. DATE: PLACE: considered as part of the intellectual property of the author. LOCATION: 638 TOMAS MAPUA ST., STA. CRUZ, MANILA DATE:

Вам также может понравиться