Вы находитесь на странице: 1из 2

CONDITION GPM PSI

6x5x14 SSC
RATED 1250 238 1250 GPM
150% 1875 154.7 145 to 238 psi
NOL (MAX) POWER
Impeller D-6954
PATTERSON PUMP COMPANY 298 HP
A Gorman-Rupp Company Phone: (706) 886-2101 Catalog Curve A02-68431-3
Post Office Box 790 www.pattersonpumps.com
Toccoa, Georgia 30577 U.S.A. 2950 RPM UL LISTED / FM APPROVED

SHUT-OFF HEAD= 264 PSI FRESH WATER (1.0 SG) 140% RATED HEAD= 333.2 PSI
NOTE: Performance curve indicates preliminary expected performance. Actual performance is subject to ANSI/HI 14.6 Grade 1U testing tolerances. Actual impeller diameter(s), shut-off head, and NOL (MAX) power
determined by testing. ONLY the Rated Condition (GPM & PSI) is guaranteed. Velocity head is included. Confirm all critical shut-off requirements with factory before placing an order.
A B C D E F G H J K L M N P R S T U V W X
ZONE REV ECR DATE BY
MOTOR A B C D E F FF G H J K L M 6 38371 2-17-2016 CW 1
1
364 TS 58-13/16" 15-1/4" 11-5/16" 18-3/4" 12" 33" 33" 70" 3/8" 3-1/2" 12-3/8" 15" 30"
365 TS 59-13/16" 15-5/8" 11-15/16" 18-3/4" 12" 33" 33" 70" 3/8" 3-1/2" 12-3/8" 15" 30"
404 TS 61-3/4" 17" 12-1/2" 18-3/4" 12" 33" 33" 70" 3/8" 3-1/2" 12-3/8" 15" 30"
405 TS 63-1/4" 17-3/4" 13-1/4" 18-3/4" 12" 33" 33" 70" 3/8" 3-1/2" 12-3/8" 15" 30"
2 444 TS 66-1/4" 19-1/2" 14-1/2" 18-3/4" 12" 33" 33" 70" 3/8" 3-1/2" 12-3/8" 15" 30" 2
445 TS 68-1/4" 20-1/2" 15-1/2" 18-3/4" 12" 33" 33" 70" 3/8" 3-1/2" 12-3/8" 15" 30"
447 TS 71-3/4" 22-1/4" 17-1/4" 18-3/4" 12" 38" 38" 80" 3/8" 3-1/2" 13" 15" 30"
449 TS 76-3/4" 24-3/4" 19-3/4" 18-3/4" 12" 38" 38" 80" 3/8" 3-1/2" 13" 15" 30"
3 3
CONTROLLER AA BB CC
FIRETROL FTA 1000A 26" 67-5/8" 34" 5X-O1" HOLES
(6X-O1" HOLES FOR 447/449 ONLY)
UNIT: PPC ORDER No:
4 JOB: CUSTOMER PO No: 4

PUMP: CAPACITY: GPM.@: FT. HD.


MOTOR: MAKE: FRAME:
PACKAGE MOUNTED
5 HP PHASE CYCLE VOLT R.P.M. 5
CONTROLLER
CONTROLLER:
(OPTIONAL)
CERTIFIED BY: DATE:

NOTES:
6 1) CLOCKWISE ROTATION SHOWN WHEN VIEWED FROM THE 6
DRIVER END. SUCTION IS ON THE RIGHT, DISCHARGE IS ON THE LEFT.
FOR COUNTERCLOCKWISE ROTATION, SUCTION IS ON LEFT,
1" DIA SLOT
DISCHARGE IS ON RIGHT. WHEN VIEWED FROM DRIVER END. PLAN VIEW
X 1-1/4"LG
2) GROUT HOLES ARE PROVIDED.
7 7
3) IMPORTANT; BASEPLATES MUST BE GROUTED TO THEIR FULL DEPTH.

4) ALL DIMENSIONS ARE IN INCHES,

8 5) ALL DIMENSIONS ARE ± 1/4" (EXCEPT FOR FLANGE DRILLINGS). 8

A
13 5/8" 18 1/4" B C
9 16" 13" AA 9
H BB
1 1/8" 1 3/8" COUPLING
GUARD

10 10

11 7 1/4" 7 1/4" 11

125# D
6" SUCTION 250#
12-1/2" O.D. FLANGE 5" DISCHARGE
12 8X-O7/8" BOLT HOLES 11" O.D. FLANGE 12
J
EQ. SP. ON 8X-O7/8" BOLT HOLES
9-1/2" D.B.C. EQ. SP. ON ‰ PUMP 2"
K K 9-1/4" D.B.C.
L L E 1 1/2"
M GROUT MIN.
13 2" F FF 13
G CC
J+1/2"
4X-O3/4"
DRAIN HOLES
14 DWG. NO. REV. 14

1 1/2"
AC-11895 6
3" K K TYP R OUTLINE DIMENSIONS DRAWN DATE
TYP M FOR MERCK/WBR 7-20-93/4-18-00
PATTERSON PUMP COMPANY SCALE APPRVD. SHEET OF
15 DRIP RIM BASE (OPTIONAL) A GORMAN-RUPP COMPANY 6X5X14 SSCH NONE A.P. 1 1
15

A B C D E F G H J K L M N P R S T U V W X

Вам также может понравиться