Calculation Months ..................................... Jan to Dec Zone L/s Sizing .................... Sum of space airflow rates
Sizing Data .................................................. Calculated Space L/s Sizing ................ Individual peak space loads
Total coil load ........................................................ 325.1 kW Load occurs at ................................................... Aug 1300
Sensible coil load ................................................. 199.1 kW OA DB / WB ...................................................... 34.0 / 27.0 °C
Coil L/s at Aug 1300 ............................................ 12642 L/s Entering DB / WB ............................................. 26.6 / 20.5 °C
Max block L/s ...................................................... 12642 L/s Leaving DB / WB .............................................. 13.5 / 13.1 °C
Sum of peak zone L/s ......................................... 12642 L/s Coil ADP ..................................................................... 12.1 °C
Sensible heat ratio ............................................... 0.612 Bypass Factor .......................................................... 0.100
m²/kW ....................................................................... 3.2 Resulting RH ................................................................. 55 %
W/m² ..................................................................... 315.4 Design supply temp. ................................................... 12.8 °C
Water flow @ 5.6 °K rise ...................................... 14.01 L/s Zone T-stat Check .................................................... 1 of 1 OK
Max zone temperature deviation .................................. 0.0 °K
Actual max L/s ..................................................... 12642 L/s Fan motor BHP ........................................................... 0.00 BHP
Standard L/s ........................................................ 12631 L/s Fan motor kW ............................................................. 0.00 kW
Actual max L/(s-m²) .............................................. 12.26 L/(s-m²) Fan static ......................................................................... 0 Pa
Calculation Months ..................................... Jan to Dec Zone L/s Sizing .................... Sum of space airflow rates
Sizing Data .................................................. Calculated Space L/s Sizing ................ Individual peak space loads
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2945.0 W/(L/s)
Site Altitude = 7.3 m
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = 1.206 W/(L/s-K)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 2947.6; At site altitude = 2945.0 W/(L/s)
Site Altitude = 7.3 m
0.016
0.008
0.006
0.004
0.002
0.000
0 5 10 15 20 25 30 35
Temperature ( °C )