Вы находитесь на странице: 1из 3

S.NO Building no.

Area SERVICE

1 B01 ALL FLOORS


2 B01 ALL FLOORS
3 B01 ALL FLOORS
4 B01 ALL FLOORS
5 B01 ALL FLOORS Fire Fighting
6 B01 ALL FLOORS
7 B01 ALL FLOORS
8 B01
9 B01 GF
10 B01

11 B01 BSMT Plumbing

12 B01 BSMT, GF, FF

13 B01 FF

HVAC

14 B01 BSMT

15 B03 Power station Mechanical


16 B04 Plant area Mechanical
17 B05 Plant room Mechanical
18 B01 Main Hospital Building Mechanical
19 B01 Main Hospital Building Mechanical
20 B01 Main Hospital Building Mechanical

# CLASSIFICATION: INTERNAL
FARASAN HOSPITAL MECHANICAL QUERIES

DESCRIPTION BOQ QTY./Cap.

Qty. of fire hose cabinet 24


Qty. of zone control valve 8
Qty. of flow switch 8
Qty. of pressure reducing valve 8
Qty. of flow meter 8
Qty. of drain valve 8
FM200 Cylinder capacity-Medical Records (6.6x3.3x3m) 25
FM200 Cylinder capacity-Medical Records (6.6x3.3x3m) 80
FM200 Cylinder capacity-Medical Record Filing (12x3.3x3m) 100
FM200 Cylinder capacity-CT Scan Room (10x5x3m) 100
Submersible Pump:16.0 m3/h @ 10.0 m Head 2
Submersible Pump:8.0 m3/h @ 3.0 m Head 2
Submersible Pump:4.0 m3/h @ 3.0 m Head 4
FCU Capacity 2.0 TR 35
FCU Capacity 1.5 TR 35
FCU Capacity 1.0 TR 35

Air Devices (Grilles, diffusers, etc)

CAV BOX 0
Humidifier - ; Capacity 13.67 kg/hr 1
Humidifier -; Capacity 14.54 kg/hr 1
Humidifier -; Capacity 45.05 kg/hr 1
Humidifier - ; Capacity 31.0 kg/hr 2
Humidifier - ; Capacity 36.0 kg/hr 3
Humidifier - ; Capacity 82.0 kg/hr 2
Humidifier - ; Capacity 93.0 kg/hr 1
Humidifier - ; Capacity 160.0 kg/hr 1
Humidifier - ; Capacity 103.0 kg/hr 1
Humidifier - ; Capacity 135.0 kg/hr 1
Humidifier - ; Capacity 48.0 kg/hr 1
Humidifier - ; Capacity 95.0 kg/hr 1
HVAC Drawings not availaible
HVAC Drawings not availaible
HVAC Drawings not availaible
Basement & Roof HVAC Ducting Drawings not availaible
All Floors Chilled water piping drawings are not available
Majority of HVAC duct sizes are missing and not shown in the avl. drawings

# CLASSIFICATION: INTERNAL
DWG QTY./Cap. UOM REMARK

17 No's
3 No's
3 No's
3 No's
4 No's
4 No's
37 kg
37 kg
66 kg
83 kg
0 No's
0 No's Drawing # NEC-B01-M50-403 not showing any sump pump
0 No's
9 No's
qty. checked only as per dwg. # NEC-B01-M50-303 & 304.
10 No's Other Dwg's are missing (NEC-B01-M50-302,305 & 306)
18 No's
qty. checked only as per dwg. # NEC-B01-M50-303 & 304.
No's Other Dwg No.'s NEC-B01-M50-302,305 & 306 are missing
hence all qt's can not be checked/verified witout complete set of
drawings
200 No's
0 No's
0 No's
0 No's
0 No's
0 No's
0 No's Humidifier not shown in available dwg's. # NEC-B01-M50-303 & 304.
0 No's Other Dwg's are missing (NEC-B01-M50-302,305 & 306)
0 No's
0 No's
0 No's
0 No's
0 No's