STANDARD 5151
First edition
1994-12-15
Reference number
Licensed to SICAL INGENIEROS S.A./PATRICIO URZÚA ISO 5151 :1994(E)
ISO Store order #:931447/Downloaded:2008-07-21
Single user licence only, copying and networking prohibited
ISO 5151:1994(E)
Contents
Page
7 Test results . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
8 Marking provisions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
0 ISO 1994
All rights reserved. Unless otherwise specified, no part of this publication may be reproduced
or utilized in any form or by any means, electronie or mechanical, including photocopying and
microfilm, without Permission in writing from the publisher.
International Organization for Standardization
Case Postale 56 l CH-l 211 Geneve 20 l Switzerland
Printed in Switzerland
Licensed to SICAL INGENIEROS S.A./PATRICIO URZÚA
ISO Store order #:931447/Downloaded:2008-07-21
Single user licence only, copying and networking prohibited
0 ISO ISO 5151:1994(E)
Annexes
D Instruments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ................... 33
E Air-flow measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Licensed to SICAL INGENIEROS S.A./PATRICIO URZÚA
ISO Store order #:931447/Downloaded:2008-07-21
Single user licence only, copying and networking prohibited ...
Ill
ISO 5151:1994(E) 63 ISO
E.2 Nozzles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
F.l General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
F.4 Calculations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
G List of Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Foreword
ISO (the International Organization for Standardization) is a worldwide
federation of national Standards bodies (ISO member bodies). The work
of preparing International Standards is normally carried out through ISO
technical committees. Esch member body interested in a subject for
which a technical committee has been established has the right to be
represented on that committee. International organizations, governmental
and non-governmental, in liaison with ISO, also take patt in the work. ISO
collaborates closely with the International Electrotechnical Commission
(IEC) on all matters of electrotechnical standardization.
Draft International Standards adopted by the technical committees are
circulated to the member bodies for voting. Publication as an International
Standard requires approval by at least 75 % of the member bodies casting
a vote.
International Standard ISO 5151 was prepared by Technical Committee
ISO/TC 86, Refrigeration, Subcommittee SC 6, Factory-made air-con-
ditioning and heat pump unjts.
This first edition cancels and replaces lSO/R 859:1968.
Annexes A, B and C form an integral part of th is International Standard.
Annexes D, E, F and G are for information only.
c) units designed for use with additional ducting; or ISO 817: -+ ßefrigeran ts - Number designa tion.
1) A unit having two or more indoor units connected to a Single outdoor unit.
2) To be published. (Revision of ISO 817:1974)
Licensed to SICAL INGENIEROS S.A./PATRICIO URZÚA
ISO Store order #:931447/Downloaded:2008-07-21
Single user licence only, copying and networking prohibited
1
ISO 5151:1994(E) 0 ISO
3.1 non-ducted air conditioner: An encased as- 3.9 exhaust air-flow: Rate of flow of air from the
sembly or assemblies designed as a unit, primarily for indoor side through the equipment to the outdoor
mounting in a window, or through a Wall, or as a side.
console. lt is designed primarily to provide free deliv-
et-y of conditioned air to an enclosed space, room or 3.10 leakage air-flow: Rate of flow of air inter-
zone (conditioned space). lt includes a Prime Source changed between the indoor side and outdoor side
of refrigeration for cooling and dehumidification and through the equipment as a result of its construction
may also include means for heating other than a heat features and sealing techniques.
pump, and means for the circulation and the cleaning
of air. lt may also include means for heating, humidi- 3.11 bypassed indoor air-flow: Flow of conditioned
fying, ventilating or exhausting air. Where such air directly from the indoor-side outlet to the indoor-
equipment is provided in more than one assembly, side inlet of the equipment.
the separated assemblies (Split-Systems) are to be
designed to be used together, and the requirements
3.12 bypassed outdoor air-flow: Flow of air di-
of rating outlined in this International Standard are
rectly from the outdoor-side outlet to the outdoor-side
based on the use of matched assemblies.
inlet of the equipment.
3.2 non-ducted heat pump: An encased assembly
or assemblies designed as a unit, primarily for 3.13 equalizer opening air-flow: Rate of flow of air
mounting in a window, or through a Wall, or as a through the equalizer opening in the partition wall of
console. lt is designed primarily to provide free deliv- a calorimeter.
ery of conditioned air to an enclosed space, room or
zone (conditioned space). lt includes a Prime Source 3.14 total cooling capacity: Amount of sensible
of refrigeration for heating which takes heat from a and latent heat that the equipment tan remove from
heat Source. lt may be constructed to remove heat the conditioned space in a defined interval of time.
from the conditioned space and discharge it to a heat
sink if cooling and dehumidification are desired from 3.15 heating capacity: Amount of heat that the
the same equipment. lt may also include means for equipment tan add to the conditioned space in a de-
the circulation and the cleaning of air, humidifying, fined interval of time.
ventilating or exhausting air.
3.16 latent cooling capacity; room dehumidifying
3.3 Standard air: Dry air at 20,O “C, and at a stan- capacity: Amount of latent heat that the equipment
dard barometric pressure of 101,325 kPa, having a tan remove from the conditioned space in a defined
mass density of 1,204 kg/m3. interval of time.
NOTE 2 The definitions given in 3.4 to 3.13 relating to
air-flow are illustrated in figure 1. 3.17 sensible cooling capacity: Amount of sensible
heat that the equipment tan remove from the con-
3.4 indoor discharge air-flow: Rate of flow of air ditioned space in a defined interval of time.
from the indoor-side outlet of the equipment into the
conditioned space. 3.18 sensible heat ratio: Ratio of the sensible
cooling capacity to the total cooling capacity.
3.5 indoor intake air-flow: Rate of flow of air into
the equipment from the conditioned space. 3.19 rated voltage(s): Voltage(s) shown on the
nameplate of the equipment.
3.6 Ventilation air-flow: Rate of flow of air intro-
duced to the conditioned space through the equip-
ment from the outside. 3.20 rated frequency(ies): Frequency(ies) shown
on the nameplate of the equipment.
3.7 outdoor discharge air-flow: Discharge rate of
flow of air from the outdoor side of the equipment to 3.21 energy efficiency ratio (EER): Ratio of the
the outdoors. total cooling capacity to the effective power input at
any given set of rating conditions. (Where the EER is
3.8 outdoor intake air-flow: Rate of flow of air into stated without an indication of units, it shall be
the equipment from the outdoor side. understood that it is derived from wattslwatt.)
Exhaust
kee 3.9)
Ventilation
(sec 3.6) 1
/
Indoor intake Outdoor intake
(sec 3.5) (sec 3.8)
4.1.2.2 Equipment manufactured for use in a mod- 4.1.2.5 Equipment manufactured for use in more
erate climate similar to that specified in table 1, col- than one of the types of climate defined in table 1,
umn Tl only, shall have a nameplate rating columns Tl, TZ and T3, shall have marked on the
determined by tests conducted at these specified nameplate the designated type and rating determined
conditions and shall be designated type Tl units. by tests for each of the specified conditions for which
they have been designated and tested.
4.1.2.3 Equipment manufactured for use in a cool
climate similar to that specified in table 1, column TZ 4.1.3 Air-flow conditions
only, shall have a nameplate rating determined by
tests conducted at these specified conditions and When determining air-flow quantities for rating pur-
shall be designated type TZ units. poses, tests shall be conducted at Standard rating
conditions (see table 1) with 0 Pa static maintained at
4.1.2.4 Equipment manufactured for use in a hot the air discharge of the equipment and with the re-
climate similar to that specified in table 1, column T3 frigeration means in Operation and after condensate
only, shall have a nameplate rating determined by equilibrium has been obtained. All air quantities shall
tests conducted at these specified conditions and be expressed as metre cubed per second m3/s of
( )
shall be designated type T3 units. Standard air as defined in 3.3.
1) The wet-bulb temperature condition is not required when testing air-cooled condensers
which do not evaporate the condensate.
2) Representative of equipment working with cooling towers. For equipment designed for
other uses, the manufacturer shall designate the condenser water inlet and outlet tem-
peratures or the water flowrates and the inlet water temperature in the ratings.
3) Equipment with dual-rated frequencies shall be tested at each frequency.
4) The test voltage on dual-rated voltage equipment shall be performed at both voltages
or at the lower of the two voltages if only a Single rating is published.
b) The test capacity shall include the determination 4.2.4 Test conditions
of the sensible, latent or total cooling capacity as
determined in the indoor-side compartment. 4.2.4.1 Preconditions
d Tests shall be conducted under the selected con- The controls of the equipment shall be set for maxi-
ditions with no changes made in fan Speed or mum cooling and all ventilating air dampers and ex-
System resistance to correct for variations from haust air dampers shall be closed. The equipment
the Standard barometric pressure (see 3.3). shall be operated continuously for 1 h after the
specified air temperatures and the equilibrium con-
d) Grille positions, damper positions, fan Speeds, densate level have been established.
etc. shall be set to result in maximum cooling ca-
pacity unless this is contrary to the manufac- 4.2.4.2 Duration of test
turer’s instructions. When tests are made at other
settings, these shall be noted together with the All power to the equipmen t shall be tut off for 3 min
cooling capacity ratings. and then restore d for 1 h.
The test shall then be run for 30 min, recording data 4.2.5.2 The motors of the equipment shall operate
every 5 min, providing seven sets of readings. Vari- continuously for the first hour of the test without
ations allowed in capacity test readings shall be in tripping of the motor-overload protective devices.
accordance with table 12.
4.2.5.3 The motor-overload protective device may
4.2 Maximum cooling test trip only during the first 5 min of Operation after the
shutdown period of 3 min. During the remainder of
4.2.1 General conditions that l-h test period, no motor-overload protective de-
vice shall trip.
The conditions which shall be used during the maxi-
mum cooling test are given in table 2.
4.2.5.4 For those models so designed that resump-
4.2.2 Temperature conditions tion of Operation does not occur after the initial trip
within the first 5 min, the equipment may remain out
Tests shall be carried out under the conditions given of Operation for not longer than 30 min. lt shall then
in column Tl I T2 or T3 of table2, based on the in- operate continuously for 1 h.
1) The wet-bulb temperature condition is not required when testing air-cooled condensers
which do not evaporate the condensate.
2) For equipment with water-cooled condensers, the water flowrate shall be the same as
that used in cooling capacity test (minimum flowrate for equipment with multiple cooling
capacity rating). For equipment incorporating a condenser water control valve, it shall be
allowed to operate normally.
3) Equipment with dual-rated frequencies shall be tested at each frequency.
4.3.4.1 Preconditions
4.3.1 General conditions
The equipment shall be started and operated until the
The conditions which shall be used during the mini-
operating conditions have stabilized.
mum cooling test are given in table3.
4.3.4.2 Duration of test
4.3.2 Temperature conditions
After the operating conditions have stabilized, the
If minimum operating temperature conditions are equipment shall be operated for a period of 4 h.
specified in the manufacturer’s equipment specifi-
cation sheets, they shall be used in lieu of those given 4.3.5 Performance requirements
in table 3.
4.3.5.1 After the end of the starting period of
4.3.3 Air-flow conditions IO min, no safety element shall tut off during the
4 h of Operation.
The controls, fan Speeds, dampers and grilles of the
equipment shall be set to produce the maximum 4.3.5.2 At the end of 4 h, any accumulation of ice
tendency to frost or ice the evaporator, providing such or frost on the evaporator shall not cover more than
settings are not contrary to the manufacturer’s oper- 50 % of the indoor-side face area of the evaporator
ating instructions. coil.
The controls, fans, dampers and grilles of the equip- 4.5 Freeze-up test
ment shall be set to produce the maximum tendency
to sweat, provided such settings are not contrary to
4.5.1 General conditions
the manufacturer’s operating instructions.
The freeze-up tests (air blockage test and drip test)
4.4.4 Test conditions may be conducted simultaneously with the minimum
cooling test. The electrical conditions shall be those
4.4.4.1 Preconditions specified in table 5.
After establishment of the specified temperature
conditions, the equipment shall be started with its 4.5.2 Temperature conditions
condensate collection pan filled to the overflowing
Point, and the equipment shall be run until the con- The temperature conditions for the freeze-up tests are
densate flow has become uniform. given in table 5.
The controls of the equipment shall be set for maxi- 5.1 .l General conditions
mum cooling and the fan Speeds, dampers and grilles
shall be set to produce the maximum tendency to All equipment within the scope of this International
frost or ice the evaporator, provided such settings are Standard shall have the heating capacities and coef-
not contrary to the manufacturer’s operating instruc- ficients of Performance determined in accordance
tions. with the provisions of this International Standard and
rated at the conditions specified in table 6. The elec-
4.5.3.2 Drip test trical input values used for rating purposes shall be
measured during the heating capacity test.
The air inlet shall be covered to block completely the
passage of air, so as to attempt to achieve complete 5.1.2 Temperature conditions
blockage of the evaporator coil by frost.
5.1.2.1 Test conditions stated in table6 shall be
considered Standard rating conditions.
4.5.4 Test conditions
5.1.2.2 If a manufacturer specifies that the equip-
4.5.4.1 Air blockage test ment is not suitable for Operation under the extra-low
temperature test conditions, tests shall be made only
The tez$1t shall be continuous, with the equipment op- at the high and low temperatures specified in table 6.
erating on the cooling cycle for 4 h after establish-
ment 0 f the specified temperature conditions. 5.1.3 Air-flow conditions
4.5.4.2 Drip test 5.1.3.1 Heating-only equipment shall use the air-flow
quantity specified by the manufacturer.
l-l
I ne equipment shall be operated for 6 h after which
the equipment shall be stopped and the air-inlet 5.1.3.2 For equipment which provides both heating
covering removed until the accumulation of ice or and cooling, the test shall be conducted at the same
frost has melted. The equipment shall then be turned air-flowrate as for the cooling capacity rating test.
on again, with the fans operating at the highest
Speed, for 5 min. 5.1.3.3 When determining air-flow quantities for rat-
ing purposes, tests shall be conducted under Standard
rating conditions (see table6) with the heating means
4.5.5 Performance requirements in Operation with 0 Pa static maintained in the air dis-
Charge of the equipment.
4.5.5.1 Air blockage test
5.1.4 Test conditions
At the end of 4 h of Operation, any accumulation of ice
or frost on the evaporator shall not cover more than 5.1.4.1 Preconditions
50 % of the indoor-side face area of the evaporator
coil. 5.1.4.1.1 When using the calorimeter method, two
simultaneous methods of determining capacities shall
4.5.5.2 Drip test be used. One method determines the capacity on the
indoor side, the other measures the capacity on the
During the test, no ice shall drip from the coil and no outdoor side. These two simultaneous determinations
water shall drip or blow off the equipment on the in- shall agree within 4 % of the value obtained on the
door side. indoor side for the test to be valid.
1) If defrosting occurs during the high, low, or extra-low heating capacity tests, testing
under these conditions shall be accomplished using the indoor air-enthalpy method (see
B.2 and C.3.3).
’ 2) Test is to be conducted only if the manufacturer specifies that the equipment is suitable
for Operation under these conditions.
3) Equipment with dual-rated frequencies shall be tested at each frequency.
4) The test voltage on dual-rated voltage equipment shall be performed at both voltages
or at the lower of the two voltages if only a Single rating is published.
5.1.4.1.2 Tests shall be conducted at the selected vided the effect is such that the indoor and outdoor
conditions with no changes in fan Speed or System leaving air temperatures remain within the operating
resistance made to correct for variations from the tolerantes for non-frosting Operation specified in
Standard barometric pressure (see 3.3). table 12. When the leaving air temperature exceeds
the permitted range because of frost, the procedure
5.1.4.1.3 The test room reconditioning apparatus for the heating capacity test in the defrost region de-
and the equipment under test shall be operated until scribed in A.4 of annex A shall be used.
equilibrium conditions are attained, but for not less
than 1 h, before test data are recorded. 5.1.4.3.2 If, under test conditions, defrost action is
experienced within a 3-h period, or the test tolerantes
5.1.4.2 Duration of table 12 are exceeded, then the procedure for
transient heating capacity tests (see B.2) shall be
Data shall then be recorded for 30 min at 5-min inter- used.
vals until seven consecutive sets of readings within
the tolerantes specified in table 12 have been at-
tained. 5.2 Maximum heating test
5.1.4.3.1 Under some conditions of heating, a small The electrical conditions given in table7 shall be used
amount of frost may accumulate on the outdoor coil during the maximum heating test. The determination
and a distinction needs to be made between non- of maximum heating IS not required under perform-
frosting and frosting operations for the test as a ante test conditions. The test voltages shall be main-
whole. For the purposes of this International Stan- tained at the specified percentages under running
dard, the test is to be considered non-frosting pro- conditions.
Licensed to SICAL INGENIEROS S.A./PATRICIO URZÚA
ISO Store order #:931447/Downloaded:2008-07-21
Single user licence only, copying and networking prohibited
10
0 ISO ISO 5151:1994(E)
5.2.2 Temperature conditions - the heat pump motors shall operate continuously
for the first hour of the test without tripping of the
The temperature conditions given in table7 shall be motor-overload protective devices.
used during these tests unless the manufacturer
specifies other conditions in the manufacturer’s 5.2.5.2 The motor-overload protective device may
equipment specification sheets. trip only during the first 5 min following the 3-min
cutoff of power. During the remainder of that l-h test
5.2.3 Air-flow conditions period, no motor-overload protective device shall trip.
The controls of the equipment shall be set for maxi- 5.2.5.3 For equipment that is so designed that re-
mum heating and all ventilating air dampers and ex- sumption of Operation does not occur after the initial
haust air dampers shall be closed. trip within the first 5 min, the equipment may remain
out of Operation for not longer than 30 min. lt shall
5.2.4 Test conditions then operate continuously for 1 h.
The heat pump shall operate throughout the test The heat pump shall remain in Operation for two
without a cutoff by any safety control. complete defrosting periods or for 3 h, whichever is
the longer.
5.4 Automatic defrost test
5.4.5 Performance requirements
5.4.1 General conditions
During and directly after the defrosting periods, the
The electrical conditions given in table9 shall be used air temperature to the outdoor side shall not rise by
during the automatic defrost test for heat Pumps. more than 5 “C. During the defrosting period, the
temperature of the air from the indoor side of the
5.4.2 Temperature conditions equipment shall not be lower than 18 “C for longer
than 1 min. This may be accomplished, if necessary,
The temperature conditions given in table9 shall be by using additional heating, provided and mounted in
used during the automatic defrost test for heat the equipment, or specified for use by the manufac-
Pumps. turer.
6.1.1 Capacity and Performance tests of non-ducted 6.3 Variations in individual readings
air conditioners and heat Pumps are conducted using
either the room calorimeter method or the indoor air- The maximum allowable variations of individual
enthalpy method. Both methods are permitted sub- readings from stated conditions in the Performance
ject to the Provision that the results are within the tests shall be as shown in table 11. The maximum
limits of the uncertainties of measurement estab- permissible Variation of any Observation during the
lished in 6.2. capacity test shall be as shown in table 12.
c) latent cooling capacity, in Watts; The data to be recorded for the capacity tests are
given in tables 13 and 14 for the calorimeter test
d) heating capacity, in Watts; method and in table 15 for the indoor air-enthalpy test
method. The tables identify the general information
e) indoor-side air-flowrate, in cubic metres per sec- required but are not intended to limit the data to be
ond of Standard air; obtained. Electrical input values used for rating pur-
poses shall be those measured during the capacity
f) external resistance to indoor air-flow, in Pascals; tests.
Licensed to SICAL INGENIEROS S.A./PATRICIO URZÚA
ISO Store order #:931447/Downloaded:2008-07-21
Single user licence only, copying and networking prohibited
15
ISO 5151:1994(E)
No. Data
1 Date
2 Observers
3 Barometric pressure
4 Speed of equipment cooling fan(s)
5 Applied voltage
6 Frequency
7 Total power input to equipmentl)
8 Total current input to equipment
9 Control dry-bulb and wet-bulb temperature of air (indoor-side calorimeter compartment)*)
IO Control dry-bulb and wet-bulb temperature of air (outdoor-side calorimeter compartment)*)
11 Average air temperature outside the calorimeter (calibrated room-type; see figure B.4)
12 Total power input to indoor-side and outdoor-side compartments
13 Quantity of water evaporated in humidifier
14 Temperature of humidifier water entering indoor-side and outdoor-side (if used) compartments or in humidifier
tank
15 Cooling water flowrate through outdoor-side compartment heat-rejection coil
16 Temperature of cooling water entering outdoor-side compartment, for heat-rejection coil
17 Temperature of cooling water leaving outdoor-side compartment, from heat-rejection coil
18 Cooling water flowrate through equipment condenser (water-cooled units only)
19 Temperature of water entering equipment condenser (water-cooled units only)
20 Temperature of water leaving equipment condenser (water-cooled units only)
21 Mass of water from equipment which is condensed in the reconditioning equipments)
22 Temperature of condensed water leaving outdoor-side compartment
23 Volume of air-flow through measuring nozzle of separating partition
24 Air-static pressure differente across separating partition of calorimeter compartments
1) Total power input to the equipment, except if more than one external power connection is provided on the
equipment; record input to each connection separately.
2) See B.l.7.
3) For equipment which evaporates condensate on the outdoor coil.
No. Data
-1 Date
2 Observers
3 Barometric pressure
4 Speed of equipment heating fan(s)
5 Applied voltage
6 Frequency
7 Total power input to equipmentl)
8 Total current input to equipment
9 Control dry-bulb and wet-bulb temperature of air (indoor-side calorimeter compartment)*)
10 Control dry-bulb and wet-bulb temperature of air (outdoor-side calorimeter compartment)*)
11 Average air temperature outside the calorimeter (calibrated room-type; see figure B.4)
12 Total power input to indoor-side and outdoor-side compartments
13 Quantity of water evaporated in humidifier
14 Temperature of humidifier water entering indoor-side and outdoor-side (if used) compartments or in humidifier
tank
15 Cooling water flowrate through outdoor-side compartment heat-rejection coil
16 Temperature of cooling water entering outdoor-side compartment, for heat-rejection coil
17 Temperature of cooling water leaving outdoor-side compartment, from heat-rejection coil
18 Water condensed in indoor-side or outdoor-side compartment
19 Temperature of condensed water leaving indoor-side compartment
20 Volume of air-flow through measuring nozzle of separating partition
21 Air-static pressure differente across separating partition of calorimeter compartments
1) Total power input to the equipment, except if more than one external power connection is provided on the
equipment; record input to each connection separately.
2) See B.1.7.
No. Data
1 Date
2 Observers
3 Barometric pressure
4 Time of test
5 Power inputl)
6 Applied voltage(s)
7 Current
8 Frequency
9 External resistance to air-flow
10 Fan Speed(s) (if adjustable)
11 Dry-bulb temperature of air entering equipment
12 Wet-bulb temperature of air entering equipment
13 Dry-bulb temperature of air leaving equipment
14 Wet-bulb temperature of air leaving equipment
15 Volume flowrate of air and all relevant measurements for its calculation
Esch non-ducted air conditioner and heat pump shall 8.3 Refrigerant designation
have a nameplate, firmly attached and in a location
accessible for reading. Refrigerant designation shall be in accordance with
ISO 817.
ditions in accordance with the provisions of this 9.1.4 Esch capacity rating shall be followed by the
International Standard. corresponding voltage and frequency rating.
9.1.2 The values of the Standard capacities shall be 9.2 Other ratings
expressed in kilowatts, rounded to the nearest
0,l kW. Additional ratings may be published based on con-
ditions other than those specified as Standard rating
9.1.3 The values of energy efficiency ratios and conditions if they are clearly specified and the data are
coefficients of Performance shall be expressed in determined by the methods specified in this Inter-
multiples of the nearest 0,05. national Standard, or by analytical methods which are
verifiable by the test methods specified in this Inter-
national Standard.
Annex A
(normative)
Test procedures
A.l General test room requirements A.2.4 All Standard ratings for equipment in which
the condenser and the evaporator are two separate
A.l.l If an indoor-condition test room is required, it assemblies shall be determined with the maximum
shall be a room or space in which the desired test length of refrigerant tubing on each line, of a length
conditions tan be maintained within the specified tol- specified by the manufacturer, or 7,5 m, whichever is
erances. lt is recommended that air velocities in the the shorter. Such equipment in which the intercon-
vicinity of the equipment under test do not exceed necting tubing is furnished as an integral patt of the
2,5 m/s. unit and not recommended for cutting to length
should be tested with the complete length of tubing
furnished. Unless constrained by the design, at least
A.l.2 If an outdoor-condition test room or space is
half of the interconnecting tubing shall be exposed to
required, it shall be of sufficient volume and shall cir-
the outdoor conditions with the rest of the tubing ex-
culate air in a manner such that it does not Change the
posed to indoor conditions. The line diameters, insu-
normal air-circulating Pattern of the equipment under
lation, details of installation, evacuation and charging
test. lt shall be of dimensions such that the distance
shall be in accordance with the manufacturer’s pub-
from any room surface to any equipment surface from
lished recommendations.
which air is discharged is not less than 1,8 m and the
distance from any other room surface to any other
equipment surface is not less than 0,9 m, except for A.3 Electrical supply requirements
floor or wall relationships required for normal equip-
ment installation. The room conditioning apparatus The voltages specified shall be maintained within the
should handle air at a rate not less than the outdoor specified percentages under running conditions. The
air-flowrate, and preferably should take this air from electrical Service supplied to the equipment’s Service
the direction of the equipment air discharge and re- connection shall be such that the voltage will not rise
turn it at the desired conditions uniformly and at low more than 3 % when the equipment is stopped. After
velocities. the Service has been adjusted to accomplish this re-
sult, no subsequent adjustment shall be made during
the test.
A.2 Equipment installation
A.4.2 The test room reconditioning apparatus and shall be recorded at normal 5-min intervals except
the equipment under test shall be operated until that, during the defrost cycle, data shall be recorded
equilibrium conditions are attained, but for not less at least every 10 s to establish accurately the Start
than 1 h, except that normal variations due to oper- and completion of the defrost cycle, the time-
ation of the defrost controls of the equipment may temperature Pattern of the indoor air stream (if the
occur. Under defrost conditions, the normal function- indoor fan is running), and the electrical input to the
ing of the test room reconditioning apparatus may be equipment.
disturbed. Because of this, the oyIerational tolerantes
shall be three times those specif ed in table 12. A.4.4 Transient conditions and internal losses make
it impractical in many cases to obtain accurate simul-
A.4.3 The equipment shall be operated for a test taneous Checks of measured heating capacity. Hence,
period of 3 h. If the equipment is in defrost at the end the accuracy of the primary measurement equipment
of this test period, the cycle shal be completed. Data is verified by means of a qualification test procedure,
as described in E.6 of annex E.
Annex B
(normative)
A
Compartment
Axes of eilipse -, I
equalization pressure
1,
2
qq 0
Nozzle velocity
pressure
.
.; --~----_ Q
Q
Lfl Discharge chamber
e
/- Throat section
.
.-
E Exhaust fan
Q
m EUiptical approach
-
8-:: Damper
.
.- Figure B.2 - Air-flow measuring nozzle
E 2,W min.
D
Ln
e
Damper
I
0,77 m/s maximum air Vetocity ;
-Exhaust fan
i / I
I
I
I
1,SD min. 2,50 min.
- -- Air temperature
Receiving chamber
sampling device
3 000 2,4 Zl 13
Pressure-equalizing device
l-
Cooling coil Cooling toi\
Equipment
Fan under test Fan
Mixers Mixers
Air-sampling tubes
Controlled-temperature
Pressure-equalizing device
air space
f
Indoor-side Outdoor-side
Humidif ier compartmen Humidif ier
Equipment
Fan under test - Fan
Mixers Mixers
L Air-sampling tubes /
B.1.6 Reconditioning apparatus for both compart- encountered in an actual application for both in-
ments shall be provided with fans of sufficient ca- door and outdoor sides, as indicated above.
pacity to ensure air-flows of not less than twice the
quantity of air discharged by the equipment under test b) At the Point of measurement, the temperature of
in the calorimeter, and air velocities at the discharge the air shall not be affected by air discharged from
of the reconditioning apparatus of less than 1 m/s. the equipment. This makes it mandatory that the
The calorimeter shall be equipped with means of temperatures are measured upstream of any re-
measuring or determining specified wet- and dry-bulb circulation produced by the equipment.
temperatures in both calorimeter compartments.
B.l.8 Interior surfaces of the calorimeter compart-
B.l.7 lt is recognized that in both the indoor-side ments shall be of non-porous material with all joints
and outdoor-side compartments, temperature gradi- sealed against air and moisture leakage. The access
ents and air-flow Patterns result from the interaction door shall be tightly sealed against air and moisture
of the reconditioning equipment and test apparatus. leakage by use of gaskets or other suitable means.
Therefore, the resultant conditions are peculiar to and
dependent upon a given combination of compartment B.2 Transient heating capacity test
size, arrangement and size of reconditioning appar-
atus, and the air discharge characteristics of the B.2.1 The test room reconditioning apparatus and
equipment under test. the heat pump under test shall be operated under
specified rating conditions until “equilibrium” con-
The Point of measurement of specified test tempera-
ditions are attained, but for not less than 1 h, except
tures, both wet- and dry-bulb, shall be such that the
that variations due to Operation of defrost controls
following conditions are fulfilled.
may occur. Under defrost conditions, the normal
functioning of the test room reconditioning apparatus
a) The measured temperatures shall be represen-
tative of the temperature surrounding the equip- may be disturbed and the maximum allowable vari-
ation of air temperature readings from rating con-
ment, and shall simulate the conditions
ditions shall be three times those shown in table 12.
Licensed to SICAL INGENIEROS S.A./PATRICIO URZÚA
ISO Store order #:931447/Downloaded:2008-07-21
Single user licence only, copying and networking prohibited
25
ISO 5151:1994(E) 0 ISO
B.2.2 If defrost controls on the heat pump provide the partition may be determined on a proportional area
for stopping the indoor air-flow, Provision shall be basis.
made to stop the test apparatus air-flow to the
equipment on both the indoor and outdoor sides dur- B.3.3 For calibrating the heat leakage through the
ing such a defrost period. If it is desirable to maintain separating partition alone, the following procedure
Operation of the reconditioning apparatus during the may be used.
defrost period, Provision may be made to bypass the
conditioned air around the equipment as long as as- A test is carried out as described above. Then the
surance is provided that the conditioned air does not temperature of the adjoining area on the other side
aid in the defrosting. A watt-hour meter shall be used of the separating partition is raised to equal the tem-
for obtaining the integrated electrical input to the perature in the heated compartment, thus eliminating
equipment under test. heat leakage through the partition, while the 11 “C
differential is maintained between the heated com-
partment and the surrounding ambient temperature
B.2.3 The equipment shall be operated for a mini-
of the other five enveloping surfaces.
mum test period complying with one of the following:
The differente in heat input between the first test and
a) a minimum of three complete defrost cycles;
second test will permit determination of the leakage
through the partition alone.
b) a minimum of 3 h, including one complete defrost
cycle;
B.3.4 For the outdoor-side compartment equipped
c) 6 h, if no defrosting occurs. with means for cooling, an alternative means of cali-
bration may be to cool the compartment to a tem-
B.2.4 If the equipment is in defrost at the end of perature at least 11 “C below the ambient
this test period, the cycle shall be completed. A de- temperature (on six sides) and carry out a similar
frost cycle comprises one complete heating and de- analysis.
frosting interval. Data shall be recorded at not more
than 5-min intervals except that, during the defrost B.3.5 As an alternative to the two-room simul-
cycle and recovery period, data shall be recorded at taneous method of determining capacities, the per-
sufficient frequency to establish accurately the time- formante of the indoor-side compartment shall be
temperature Pattern of the indoor air stream (if the verified at least every 6 months using an industrial
indoor fan is running), and the electrical input to the Standard cooling capacity calibrating device. A cali-
equipment under test. brating device may also be another equipment whose
Performance has been measured by the simultaneous
indoor and outdoor measurement method at an ac-
8.3 Calibrated room-type calorimeter
credited national test laboratory as part of an
industry-wide cooling capacity verification pro-
B.3.1 The calibrated room-type calorimeter is gramme.
shown in figure B.4. Esch calorimeter, including the
separating partition, shall be insulated to prevent heat
leakage (including radiation) in excess of 5 % of the 8.4 Balanced ambient room-type
capacity of the equipment. An air space permitting calorimeter
free circulation shall be provided under the calorimeter
f loor. B.4.1 The balanced ambient room-type calorimeter
is shown in figure B.5 and is based on the principle
B.3.2 Heat leakage may be determined in either the of maintaining the dry-bulb temperatures surrounding
indoor-side or outdoor-side compartment by the fol- the particular compartment equal to the dry-bulb
lowing method. temperatures maintained within that compartment. If
the ambient wet-bulb temperature is also maintained
All openings shafl be closed. Either compartment may equal to that within the compartment, the vapour-
be heated by electric heaters to a temperature of at proofing provisions of B.1.8 are not required.
least 11 “C above the surrounding ambient tempera-
ture. The ambient temperature shall be maintained B.4.2 The floor, ceiling and Walls of the calorimeter
constant within + 1 “C outside all six enveloping sur- compartments shall be spaced a sufficient distance
faces of the compartment, including the separating away from the floor, ceiling and walis of the controlled
partition. If the construction of the partition is identical areas in which the compartments are located in Order
with that of the other Walls, the heat leakage through to provide a uniform air temperature in the intervening
Licensed to SICAL INGENIEROS S.A./PATRICIO URZÚA
ISO Store order #:931447/Downloaded:2008-07-21
Single user licence only, copying and networking prohibited
26
0 ISO ISO 51Fil:%M(E)
space. It is recommended that this distance be at the same temperature differente, whichever is the
least 0,3 m. Means shall be provided to circulate the greater, as tested using the procedure given in B.3.2.
air within the surrounding space to prevent stratifi-
cation. B.5 Calorimeter and auxiliary equipment
for water-cooled condenser tests
B.4.3 Heat leakage through the separating partition
shall be introduced into the heat balance calculation B.5.1 The indoor-side compartment of a room
and may be calibrated in accordance with 8.3.3, or calorimeter of either the calibrated or the balanced
may be calculated. ambient type shall be used.
8.4.4 lt is recommended that the floor, ceiling and B.5.2 Measurements shall be made for determining
Walls of the calorimeter compartments be insulated flow and temperature rise of the condenser cooling
so as to limit heat leakage (including radiation) to no water. Water lines shall be insulated between the
more than 10 % of the test equipment’s capacity,
condenser and the temperature-measuring Points.
with an 11 “C temperature differente, or 300 W for
Annex C
(normative)
C. 1 Cooling capacity calculations @lP is the heat leakage rate into the indoor-side
compartment through the partition separ-
(Calorimeter method) ating the indoor-side and outdoor-side
compartments, as determined from the
C.l.1 The total room-cooling effect on the indoor calibrating test (or may be based on calcu-
side, as tested in either the calibrated or balanced- lation in the case of a balanced-ambient
ambient room-type calorimeter (see figures B.4 and room-type calorimeter), in Watts;
8.5) is calculated as follows:
@Ir is the heat leakage rate into the indoor-side
compartment through Walls, floor and ceil-
ing (but not including the separating par-
tition) as determined from the calibrating
where test, in Watts.
hw2 is the specific enthalpy of condensed @tco is the total cooling capacity as determined
moisture leaving the indoor-side compart- on the outdoor-side compartment, in
ment, since transfer of condensed moist- Watts;
ure from the indoor-side to the
outdoor-side compartment usually takes @c is the heat removed by the cooling coil in
place within the test equipment; when it the outdoor-side compartment, in Watts;
is not practical to measure this tempera- is the sum of all power input to any
CP,
ture, the temperature of the condensate equipment, such as reheaters, circulating
may be assumed to be at the measured, fans, etc., in the outdoor-side compart-
or estimated, wet-bulb temperature of the ment, in Watts;
air leaving the test equipment, in kilojoules
per kilogram; Pt is the total power input to the equipment
under test, in Watts;
w is the rate at which water vapour is con-
densed by the equipment under test, in kV2 is as defined in C.l .l ;
grams per second; this is measured as the
amount of water, in grams per second, h, 3 is the specific enthalpy of the condensed
evaporated into the indoor-side compart- moisture removed by the air-treating coil
ment by the reconditioning to maintain the in the outdoor-side compartment recon-
required humidity; ditioning apparatus, taken at the tempera-
ture at which the condensate leaves the
compartment, in kilojoules per kilogram;
Licensed to SICAL INGENIEROS S.A./PATRICIO URZÚA
ISO Store order #:931447/Downloaded:2008-07-21
Single user licence only, copying and networking prohibited
28
0 ISO ISO 515’1:1994(E)
@ Io0 is the heat leakage from the outdoor side C.2 Heating capacity calculations
(but not including heat leakage through the
separating partition), as determined from
(Calorimeter method)
the calibrating test, in Watts.
c.2.1 Determination of the heating capacity by
measurement in the indoor-side compartment is cal-
C.1.3 The total cooling capacity of a liquid (water)-
culated as follows:
cooled equipment deducted from the condenser side
is calculated as follows: @hi = @lci+ @t + @li - Pi . . . (C-7)
@s is the sensible cooling capacity, in Watts; Oho = po + pt + &/o(k~, - k/vS) + @t + @Io0 - l cca8)
PO
is the total power input to the outdoor-side CPa
is the specific heat of dry air, in joules per
compartment with the exception of the kilogram kelvin;
power input to the equipment, in Watts;
ta2 is the temperature of air leaving the indoor
Pt
is as defined in C.1.2; side, in degrees Celsius;
qwo
is the mass flowrate of water supplied to tal is the temperature of air entering the in-
the outside compartment to maintain the door side, in degrees Celsius;
test conditions, in grams per second;
V’” is the specific volume of air at Point of
hw 4
is the specific enthalpy of the water mass measurement of air-water vapour mixture,
flow supplied to the outdoor-side com- in cubic metres per kilogram;
partment, in kilojoules per kilogram;
wn is the specific humidity of air, in kilograms
h, 5 is the specific enthalpy of the condensed per kilogram of dry air.
water (in the test condition, this is high)
and frost, respectively (in the test con- If line loss corrections are to be made, they shall be
dition, this is low or extra-low) in the included in the capacity calculations.
equipment, in kilojoules per kilogram;
C.3.4 When moisture is deliberately added to the
@t is as defined in C.2.1; indoor air stream in Order to provide humidification,
there is a significant Change in moisture content be-
@Io0 is the heat-flow through the remaining en- tween the indoor air entering and leaving, and the
veloping surfaces into the outdoor-side following expression shall be used:
compartment, in Watts.
4mi@a2 - hal)
NOTE 5 The transfer of energy by the equalizing air-flow Ohi = , - \
. . . K. IO)/
V’n(l + wn)
and the leakage air-flow of the equipment is neglected.
where
C.3 Heating capacity calculations
(Air-enthalpy method) @hi is as defined in C.2.1;
Equation (CS) does not provide allowances for heat leakage in the test equipment.
Licensed to SICAL INGENIEROS S.A./PATRICIO URZÚA
ISO Store order #:931447/Downloaded:2008-07-21
Single user licence only, copying and networking prohibited
30
ISO 5151:1994(E)
Air-f low
c-c
Insulated due t
A
acc to air-measuring
place of air conditioner.
1
Configuration should be suitable for
inlet of adapter duct
B-B A-A
Shield to Limit radiation
to duct Walls Reflective surface
of insulation
Resistance
‘heater
The total, sensible and latent indoor cooling capacities 4mif cpa, ta, and ta2 are as defined in C.3.3;
based on the indoor-side test data are calculated by
the following equations? h,,, h,,, VI, and IV” are as defined in C.3.4;
cpa = 1 005 + 1 846~” wil is the specific humidity of air entering the
indoor-side compartment, in kilograms per
2,47 X 106q,i(~l - Wi2) kilogram of dry air;
%i = . . . (C.13)
V’n(l + W”) wi2 is the specific humidity of air leaving
indoor-side compartment, in kilograms per
= @tci - @.sci kilogram of dry air;
6) Equations (CH) and (C.12) do not provide allowances for heat leakage in the test equipment.
Licensed to SICAL INGENIEROS S.A./PATRICIO URZÚA
ISO Store order #:931447/Downloaded:2008-07-21
Single user licence only, copying and networking prohibited
32
ISO 5151:1994(E)
Annex D
(informative)
Instruments
D.1 Temperature-measuring D.I.7 The response time is the time required for
instruments the instrumentation to obtain 63 % of the final
steady-state temperature differente when subjected
to a step Change in temperature differente of 7 “C or
D.1.1 The smallest scale division of the
more.
temperature-measuring instrument should not exceed
twice the specified accuracy. For example, for the
specified accuracy of & 0,05 “C, the smallest scale D.2 Pressure-measuring instruments
division should not exceed -+ 0,l “C.
D.2.1 The maximum scale interval should not be
D.I.2 Where an instrument accuracy of + 0,05 “C greater than that listed for the range of the
is specified, the instrument should be calibrated by manometer given in table D.I.
comparison with a thermometer certified by a recog-
nized authority, such as a national Standards authority. Table D.l - Range of manometer
Values in Pascals
0.1.3 In all measurements of wet-bulb tempera- Range Maximum scale interval
ture, sufficient wetting should be provided and suf-
ficient time should be allowed for the state of From 1,25 to 25 1,25
evaporative equilibrium to be attained. For mercury- Over 25 to 250 2,5
Over 250 to 500 5,O
in-glass thermometers having a bulb diameter not
Over 500 25
over 6,5 mm, temperatures should be read under \
conditions which ensure a minimum air velocity of
5 m/s. For any other instrument, a sufficient air vel- D.2.2 For air-flowrate measurements, the minimum
ocity should be provided to give the Same equilibrium pressure differential should be:
conditions as those defined above.
a) 25 Pa with an inclined-tube manometer or micro-
D.I.4 Wherever possible, temperature-measuring manometer;
instruments used to measure the Change in tempera-
ture should be arranged so that they tan be readily b) 500 Pa with a vertical tube manometer.
interchanged between inlet and outlet positions to
rmprove accuracy. D.2.3 Calibration Standards should be:
D.I.5 Temperatures of fluids within conduits should a) for instruments with the range 1,25 Pa to 25 Pa,
be measured by inserting the temperature-measuring a micromanometer accurate to +- 0,25 Pa;
instrument directly within the fluid, or within a well
inserted into the fluid. If a glass thermometer is to be b) for instruments with the range 25 Pa to 500 Pa,
inserted directly into the fluid, it should be calibrated a manometer accurate to rt: 2,5 Pa (hook gauge
for the effect of pressure. or micromanometer);
D.3.1 Electrical measurements should be made D.4.2 The liquid quantity meter should employ a
with either of the following instruments: tank having a capacity sufficient to accumulate the
flow for at least 2 min.
a) indicating;
D.5 Other instruments
W integrating.
D.5.1 Time interval measurements should be made
D.3.2 Instruments used for measuring all electrical with instruments whose accuracy is +- 0,2 % of the
inputs to the calorimeter compartments should be quantity measured.
accurate to & 0,5 % of the quantity measured.
D.5.2 Mass measurement should be made with
D.4 Water-flow-measuring instruments apparatus whose accuracy is + 1,O % of the quantity
measured.
D.4.1 Water-flow measurements should be made
with either of the following instruments having an D.5.3 Instruments for measuring rotating Speed
accuracy of + 1,O % of the quantity measured: should be of the remote-sensing type with an accu-
racy of + 1,O % of the quantity measured.
a) liquid quantity meter, measuring either mass or
volume;
Annex E
(informative)
Air-flow measurement
E.l Air-flow determination E.2.2 Nozzle discharge coefficients for the con-
struction shown in figure 8.2 may be determined by
E.l.l The following air quantities may be measured use of the alignment Chart (see figure E.l).
using the apparatus and testing procedures given in Figure E.1 is the Solution of the following equations:
this annex:
cd =f(Re)
a) indoor-side discharge air-flow;
Re = TVDP
b) Ventilation air-flow, if the non-ducted air con-
ditioner or heat pump is equipped to provide
Same;
cd is the discharge coefficient;
Cl exhaust air-flow, if the non-ducted air conditioner
or heat pump is equipped to provide Same; Re is the Reynolds number;
V is the velocity;
E.l.2 Air-flow quantities are determined as mass
flowrates. If air-flow quantities are to be expressed for is the density;
P
rating purposes in volume flowrates, such ratings
should state the conditions (pressure, temperature P is the viscosity
and humidity) at which the specific volume is deter-
mined. and
v = CP(h)
Reynolds
a number
2 1
7e x IO3
ai
5
: 0,75
a
a
c.-h
U
0
2 0,s
40
025
- 60
4-
- 40
- 30
0,960
40 -
- 20
50 -
0,1
0,950 2-
60 -
- 10
0,940
X
Diameter
scale
0,os
Discharge
coef f icient
Instructions: Enter graph using diameter and temperature scales to obtain Point on index (x) scale. Use index and
pressure scales to obtain Reynolds number and discharge coefficient.
E.3 Apparatus for room discharge baffles to accomplish this purpose. Nozzles so in-
stalled may be considered to require a negligible cor-
air-flow measurements
rection for approach velocity.
E.3.1 Room discharge air-flow measurements
E.3.3 To establish a zero static pressure with re-
should be made with apparatus similar to that shown
in figures B.l and B.3. spect to the test room at the discharge of the air
conditioner or heat pump in the receiving chamber, a
manometer should have one side connected to one
E.3.2 One or more nozzles constructed in accord-
or more static pressure connections located flush with
ante with figures 8.2 and B.3 should be fitted into
the inner wall of the receiving chamber.
one wall of the receiving chamber, discbarging into
the discharge chamber, and should be of such a size
that the throat velocity is not less than 15 m/s. Centre E.3.4 Size and arrangement of the discharge cham-
distances between nozzles in use should not be less ber should be such that the distance from the centre
than three throat diameters, and the distance from the of any nozzle to the adjacent side wall is not less than
centre of any nozzle to any of the four adjacent side 1,5 throat diameters and not less than 5 throat diam-
Walls should be not less than 1,5 throat diameters. If eters to the next obstruction, unless suitable diffusion
the nozzles are of different diameters, the distance baffles are used.
between axes should be based upon the average di-
ameter. Size and arrangement of the receiving cham- E.3.5 An exhaust fan should be connected to the
ber should be sufficient to provide uniform approach discharge chamber to overcome the resistance of the
velocity to the nozzle(s) or have suitable diffusion chamber, nozzle(s) and diffusion baffles.
Licensed to SICAL INGENIEROS S.A./PATRICIO URZÚA
ISO Store order #:931447/Downloaded:2008-07-21
Single user licence only, copying and networking prohibited
36
0 ISO ISO 5151:1994(E)
E.4.5 Air mass flowrate through a Single nozzle is E.4.6 Air-flow through multiple nozzles may be cal-
determined as follows: culated in accordance with E.4.5, except that the total
/ flowrate will be the sum of the qm values for each
(E-1> nozzle used.
4m = K&.jA &- . m.
J VI,
E.5.2 With the equalizing device adjusted for a E.6.3 During the calibration test, the air-flow, the
maximum static pressure differential between the inlet temperature, and the outlet temperature should
indoor-side and outdoor-side compartiments of 1 Pa, agree with the values measured during the test of the
the following readings should be taken: equipment, within the tolerantes given in table 11.
The electrical input to the resistance heater should be
a) barometric pressure; adjusted to provide the equivalent test conditions.
b) nozzle wet- and dry-bulb temperatures; E.6.4 The heat input of the resistance heater is cal-
culated as follows:
c) nozzle velocity pressure.
q = Pr . . . (E-4)
E.5.3 Air-flow values should be calculated in ac-
cordante with E.4.5. where
Annex F
(informative)
7) Equations (F.l) and (F.2) do not provide allowances for heat leakage in the test equipment.
Licensed to SICAL INGENIEROS S.A./PATRICIO URZÚA
ISO Store order #:931447/Downloaded:2008-07-21
Single user licence only, copying and networking prohibited
39
ISO 5151:1994(E) 0 ISO
wn is the specific humidity at the nozzle, in @L is the line heat loss in the interconnecting
kilograms per kilogram of dry air; tubing, in Watts;
pt is the total power to equipment, in Watts. Dt is the outside diameter of refrigerant tub-
ing, in millimetres;
F.4.2 The total heating capacity based on outdoor-
side data is calculated by one of the following At is the average temperature differente, in
equations8): degrees Celsius, between the refrigerant
and the surrounding ambient;
4moCha4 - ha3) + p
CD
tho = . . . (F-3) L is the length of refrigerant tubing, in me-
V’n(l + Wn) t
tres;
or, for air-cooled equipment which does not re-
T is the insulation thickness, interconnecting
evaporate:
tubing, in millimetres.
4m&pa ka4 - ta31
@ tho = + Pt . . . 03 The line loss correction should be added algebraically
V’n(l + Wn>
to the outdoor-side capacity.
8) Equations (F-3) and (F.4) do not provide allowances for heat leakage in the test equipment.
Licensed to SICAL INGENIEROS S.A./PATRICIO URZÚA
ISO Store order #:931447/Downloaded:2008-07-21
Single user licence only, copying and networking prohibited
40
ISO 5151:1994(El)
Temperature-measuring
instruments
Enclosure
I
////////////////
Annex G
(informative)
List of Symbols
rm-- h al I specific enthalpy of wet air entering indoor-side compartment kJ/kg of dry air
m-1 specific enthalpy of air entering outdoor-side compartment J/kg of dry air
h a4 specific enthalpy of air leaving outdoor-side compartment J/kg of dry air
@li heat flow through the remaining enveloping surfaces of the indoor-side compartment w
@Io0 heat leakage out of or into the outdoor-side compartment, not including the heat w
leakage through the partition
I (I>
sei sensible cooling capacity, indoor-side data w
heat flow through partition wall I w
I /
‘i other power input to the indoor-side compartment (e.g., illumination, electrical and W
thermal power input to the compensating device, heat balance of the humidification
device
PO total power input to the outdoor-side compartment with the exception of the power W
input to the equipment I
Pr I power input to the resistance heater I W --1
wil specific humidity of air entering indoor-side compartment kg/kg of dry air
wi2 specific humidity of air leaving indoor-side compartment kg/kg of dry air