components through a classical based energy management HRPS is flexible and can extend as a new PV, SC or battery
system. AC bus connects residential load and utility grid to the are attached to the existing ones without growing the circuit
proposed system. The output voltage of PV is adjusted complexity. The performance and stability of the proposed
through DC–DC boost converter while the power flow of SC system needs the simulation over a period of time. Therefore,
and battery with the system happen through two non-isolated for each distinct component steady-state simulation models
buck boost converters. have been followed. Figure 1 defines the schematic layout of
The DC bus supplies power to the grid and grid-connected the HRPS.
load using three phase inverter. It is essential to state that the
MPPT+Boost Converter Inverter PI
PV Array QI Utility Grid
IPV DC Bus AC Bus
VPV PG,QG
VBUS
PPV
DMPPT, VPVR PIR PGR
Buck Boost Converter QIR QGR
Battery Bank
IB
PL,QL
VB
PB
VPV-REF
PBD/CR PPV
Buck Boost Converter PBD/CR PS
Supercapacitor Bank
PSD/CR POWER PB
IS
PGR,QGR MANAGEMENT PG,QG
SYSTEM PI,QI
PIR,QIR
VS SC
DMPPT
SB
PS
PSD/CR
CONTROL OF SYSTEM COMPONENTS on Ii, the switching operation (i.e., buck or boost) is
Control of Photovoltaic System determined. The control scheme of a battery system is shown
The conversion efficiency of light energy into electrical in figure 3.
energy is very low for PV systems. Since, it is required to
fully convert the available light energy into electrical energy. DC/DC Converter
For this purpose, the PV system is operating at Maximum
Ii<0 Ii
Power Point (MPP). MPP is the ideal point at which PV Buck
system generates its maximum/rated power. To perform Duty Operation
PID Ratio
PWM Iout _+ Error
maximum power transfer, an Incremental Conductance
Controller Generator
Algorithm (ICA) based Maximum Power Point Tracking Boost
(MPPT) is incorporated in boost converter. The controller Ii>0 Operation
used for controlling PV system is Proportional Integral
Derivative (PID) controller. The error “e” signal is generated
by ICA. The PID tries to minimize the error signal by
generating appropriate duty cycle. The entire control scheme
is depicted in figure 2. Figure 3: Control diagram of SC/Battery system
0
Switching Control of Super-capacitor
IPV I I e Signal The SC is also a static energy storage device with high power
e PV PV _+ PID
PWM
VPV VPV VPV Controller density. Therefore, it is directly coupled to DC bus with
corresponding DC-DC converter as shown in figure 1. The
DC-DC converter performs two operations i.e., firstly, it steps
Figure 2: Control schematic of PV system up/down the voltage level for charging/discharging purposes
and secondly it regulates the DC bus. The reference current
Control of Battery (Ii) is calculated using PSD/CR and given as Ii=PSD/CR/VSC. PID
A battery is a static storage device and needs proper voltage controller tries to equate the output current to reference
level for charging/discharging purpose. Stepping up/down current while PMS controls the operation of converters (i.e.,
operation of voltage level is achieved by coupling buck-boost buck or boost) based on Ii as shown in figure 3.
converter with battery as illustrated in figure 1. The reference
power for buck-boost converter is generated by Power
Management System (PMS). Using reference power,
reference current (Ii) is calculated i.e., Ii=PBD/CR/VB. Based
March-April
Sci.Int.(Lahore),28(2),955-964,2016 ISSN 1013-5316; CODEN: SINTE 8 957
March-April
Sci.Int.(Lahore),28(2),955-964,2016 ISSN 1013-5316; CODEN: SINTE 8 959
Start
From
PPV,PG,PL,PB,PS,SB,SS
1
Yes
PL=PPV+PG+PB+PS
No
Yes No
PL>PPV
No Yes
SB>20% SB>90%
No PL-PPV-PB No No PL-PPV-PB No
PL-PPV-PB>0 PL-PPV-PB<0
-PS>0 -PS<0
Goto Goto
Goto Yes Yes Yes Yes Goto
1 1
1 1
Yes No
From
From
From
From
PG R=PL -PP V-PB -PS SS>20% SS>90% PG R=PL -PP V-PB -PS
3
4
2
5
No Yes
Goto Goto Goto Goto
1 3 5 1
SIMULATION RESULTS AND DISSCUSION load and average load are calculated as 2.8 kW and 2.02 kW
Weather Data per home. The peak load starts from 18 H and ends at 21 H.
The weather patterns followed in this HRPS are ambient The residential load demand of 100 houses located at
temperature (°C) and solar irradiance (W/m2). The Chongqing, China is considered. The power factor is taken as
temperature is collected hourly basis while solar irradiance is 0.8 during simulation. On the basis of power factor, the
taken at the interval of one hour. In this research the reactive powers of residential load, grid and inverter is
irradiance and temperature are taken from different weather calculated. The positive means grid is supplying power while
channels. The weather data used in this research are of a negative means grid is taking power and zero means grid is
typical summer day dated 13 June 2015 at Chongqing as disconnected from the proposed HRPS. Residential load real
presented in figure 9. and reactive power is shown in figure 10. Grid real and
reactive power is shown in figure 11 whereas the real and
(a)
reactive power of main inverter is shown in figure 12.
1000
Irradiance (W/m 2)
220
160
0
0 4 8 12 16 20 24 140
Power (kW)
(b) 120
40
Temperature ( oC)
100
80
35
60
30 40
20
0 4 8 12 16 20 24
Time (Hrs) 0
0 4 8 12 16 20 24
Figure 9: Weather statistics (a) Irradiance (b) Temperature Time (Hrs)
Power (W)
5 1.5
Power (kW)
1 PL
0.5 PREF
0
0
0 4 8 12 16 20 24
4
x 10 (b)
-5 15
Power (W)
10
-10
0 4 8 12 16 20 24 QL
Time (Hrs) 5
QREF
Figure 11: Utility grid power demand
0
0 4 8 12 16 20 24
220 Time (Hrs)
200 Real Power Figure 13: Residential load (a) Real power (b) Reactive power
180 Reactive Power
4
x 10 (a)
160 2
140
1
Power (kW)
Power (W)
120
0
100
PG
80 -1
PGR
60
-2
0 4 8 12 16 20 24
40
20 4
x 10 (b)
1
0
0 4 8 12 16 20 24
Time (Hrs)
Power (W)
0
Figure 12: Power flow through main inverter
QG
-1
QGR
Residential Load Results
The residential load demand is shown in figure 13. In figure -2
0 4 8 12 16 20 24
13, the solid blue lines show the actual power delivered to the Time (Hrs)
load while the dotted red line represents the load demand Figure 14: Utility grid power (a) Real power (b) Reactive power
reference. The entire simulation is carried out for 24 H. At
t=0 to 10 H, the load demand increases from 67 kW to 200 PV System Results
kW of real power while 40 kW to 120 kW of reactive power. Figure 15 shows the actual output and the reference power of
There are two peaks presented in the figure 13. The first peak PV system. As stated earlier, the PV array rating is 260 kW,
lies at 12 H while the second peak lies at 21 H. The first peak so, the maximum output power is 252 kW. During a summer
is due to the office timing and peak sun hours while the day, the sun rises at 5 H, but sun shines start at 5:30 H.
second peak is due to the night timing which includes the Similarly, the sun sets at 7:50 H while sun rays disappears at
lighting and cooling loads. The off peak hours are 0-6 H, it is 7:30 H which is clearly revealed from the above figure 15.
due to night timing. However, the residential load demand The next major fact about the above figure is maximum
varies between 50 kW and 210 kW. power extraction. The incremental conductance based MPPT
Utility Grid Results algorithm is controlled by PI controller. The dotted line
Figure 14 shows the real and reactive actual and reference represents the maximum power for each temperature and
powers of the utility grid. Generally, the grid is used to take irradiance level, whereas the solid line represents the actual
power during peak load hours while it delivers powers during output power produced by PV using PI controlled based
off peak load hours. During 0 to 8 H, it is off peak hours and boost converter. At 12 H, the PV output power is at
the grid is supplying power ranging from 1 to 10 kW. maximum of 252 kW on 1050 W/m2 irradiance and 40°C
Furthermore, during peak load hours i.e., 11 to 17 H, the grid temperature.
takes power from HRPS ranging from 1 to 15 kW. Similarly,
the corresponding reactive power is provided or delivered.
The reference power shown in figure 14 is a step change
while in actual scenario, the PI based controller is used to
control the grid power, hence, an overshoots, undershoots,
transients and settling time are the major factors behind a
March-April
Sci.Int.(Lahore),28(2),955-964,2016 ISSN 1013-5316; CODEN: SINTE 8 961
300 fully charged at 14 H and its power is zero while SC is
PREF
charged up to 88%. After 19 H, the evening starts and PV
PPV
250 power become zero, so, SC and battery delivers its available
power and their SOCs decrease accordingly.
200 (a)
100
Power (KW)
SOCs (%age)
150 80
100 60 SB
SS
50 40
0 4 8 12 16 20 24
5
0 x 10 (b)
0 4 8 12 16 20 24 2
Time (Hrs)
Power (W)
1
1.5
1
PI and SC also plays its role by delivering 50 kW and 23 kW
PIR powers, respectively. For t=3 to 4 H, the grid is disconnected
0.5
and 90 kW of load demand is satisfied with battery (50 kW)
0
0 4 8 12 16 20 24 and SC (40 kW). For t=4 to 5 H, a load of 100 kW is applied
5
on HRPS and the utility grid also needs a power of 3 kW.
x 10 (b)
2 Therefore, cumulative load demand of residential load and
grid load is shared between battery and SC by providing 50
1.5
kW and 53 kW of power, respectively. Till now PV does not
Power (W)
March-April
962 ISSN 1013-5316; CODEN: SINTE 8 Sci.Int.(Lahore),28(2),955-964,2016
5
x 10
3
PL
2.5
PPV
PB
2
PS
1.5 PG
Power (W)
0.5
-0.5
-1
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Time (Hrs)
Figure 18: Output power of different energy sources/loads
For t=11 to 14 H, the load demand varies between 195 kW equal to the power consumption. From figure 20, it is clearly
and 203 kW. It’s a peak load hour, thus the grid also acts as a revealed that the net power inside the system is less than 1 W
load in this duration and take power from HRPS ranging from (which is negligible). So, the proposed system is called as
5 kW to 15 kW. A like previous case, the PV is generating stable system.
power more than the load demand, SC and battery are 1
than the load demand (180 kW to 130 kW). On the other side
the battery is fully charged, so its power consumption is zero,
whereas SC is still charged with maximum power of 66 kW -1
0 4 8 12 16 20 24
and also grid takes maximum 12 kW of power. For t= 8 to 9 Time (Hrs)
H, the PV output power decreases and become zero while the Figure 20: Net power on AC bus
battery and SC start discarding again. For t=19 to 24, there is For this system the fundamental load voltage and frequency
another load peak. The residential load varies between 150 are 440 V and 50 Hz, respectively. The acceptable values
kW and 210 kW, where the grid is disconnected for the according to IEEE standards are ±5% for voltage and ±0.8%
majority of the time due to peak load hours. The battery for frequency. So, their ranges are calculated as 418 V and
shares its maximum 50 kW of power and the remaining 462 V for load voltage while 50.4 Hz and 49.6 Hz for load
power is efficiently provided by SC only frequency. From figure 21, the load voltage and the
Stability Analysis frequency are in the acceptable limits.
According to IEEE standards [24], the allowable limits for (a)
460
bus voltage is ±5%. So for 700 V DC bus, the allowable
Load Voltage RMS (V)
limits are ±35V of 700 V i.e., 665 V and 735 V. From figure 450
19, it is clearly revealed that the DC bus voltage is inside 665 440
715
50.05
710
Voltage (V)
50
705
49.95
700
49.9
695 0 4 8 12 16 20 24
Time (Hrs)
690
0 4 8 12 16 20 24 Figure 21: Load parameters (a) Voltage (b) Frequency
Time (Hrs)
Figure 19: DC bus voltage
March-April
Sci.Int.(Lahore),28(2),955-964,2016 ISSN 1013-5316; CODEN: SINTE 8 963
As stated earlier the load voltage RMS and frequency should [4] Hassan, S.Z., Li, H., Kamal, T. and Awais, M.,"Stand-
be in ±5% and ±0.8%. The time vs percent change plots of alone/grid-tied wind power system with
load voltage RMS and frequency are shown in figure 22. battery/supercapacitor hybrid energy storage," 2015
Whereas on the other side, the THD in a load voltage should International Conference on Emerging Technologies
be less than 5%. From figure 22, it is revealed that the THD (ICET):1-6 (2015).
is also in its acceptable limits. [5] Kamal, T., Hassan, S.Z., Li, H. and Awais, M.,"Design
and power control of fuel
cell/electrolyzer/microturbine/ultra-capacitor hybrid
power plant," International Conference on Emerging
Technologies (ICET):1-6 (2015).
[6] Mahmood, H., Michaelson, D. and Jiang, J.,"Control
strategy for a standalone PV/battery hybrid system,"
IECON 2012-38th Annual Conference on IEEE
Industrial Electronics Society: 3412-3418 (2012).
[7] Islam, S. and Belmans, R.,"Grid independent
photovoltaic fuel-cell hybrid system: design and control
strategy," KIEE International Transactions on Electrical
Machinery and Energy Conversion Systems, 5: 399-
405(2005).
[8] Wu, Z., Tazvinga, H. and Xia, X., "Demand side
management of photovoltaic-battery hybrid system,"
Figure 22: Power quality parameters (a) % change in load Applied Energy, 148: 294-304(2015)
voltage RMS (b) % change in load voltage frequency (c) THD of [9] Glavin, M., Chan, P.K., Armstrong, S. and Hurley,
load voltage W.,"A stand-alone photovoltaic supercapacitor battery
hybrid energy storage system," in Power Electronics and
CONCLUSION
Motion Control Conference: 1688-1695(2008).
The PV/SC/battery hybrid system is developed for grid-off [10] Logerais, P.O., Riou, O., Camara, M. A. and Durastanti,
and grid-on residential applications with proper simple J. F.,"Study of Photovoltaic Energy Storage by
energy management strategy. The detailed modeling of Supercapacitors through Both Experimental and
system components, their integration, and control along with Modelling Approaches," Journal of Solar Energy: 2013,
the utility grid is provided. The PV system has controlled by (2013).
an incremental conductance based MPPT method followed [11] Kollimalla, K. S., Mishra, M. K., and Narasamma, N.
by PI controllers. The performance of the system is tested L.,"Coordinated control and energy management of
under different weather patterns and load conditions for the hybrid energy storage system in PV system,"
simulation of one complete day. The proposed system International Conference on Computation of Power,
exhibits excellent performance in terms of stability, voltage Energy, Information and Communication (ICCPEIC):
regulation and power quality. All the system components are 363-368(2014).
developed in Matlab/Simulink. [12] Mao, M., Liu, Y., Jin, P., Huang, H., and Chang,
L.,"Energy coordinated control of hybrid battery-
ACKNOWLEDGMENT
supercapacitor storage system in a microgrid," 4th IEEE
The research work is supported by National Natural Science International Symposium on Power Electronics for
Foundation of China (No.51377184), International Science & Distributed Generation Systems (PEDG):1-6 (2013).
Technology Cooperation Program of China (No.2013DF [13] Fahmi, M., Rajkumar, R. K., Arelhi, R. and Isa,
G61520) and Fundamental Research Funds for the Central D.,"Study on the effect of supercapacitors in solar PV
Universities (No.CDJZR12150074). system for rural application in Malaysia," 50th
REFERENCES International Universities Power Engineering
Conference (UPEC): 1-5 (2015).
[1] Hassan, S. Z. Mumtaz, S., Kamal, T. and Khan, L., [14] Kamal, T., Hassan, S. Z., Khan, L. and Mumtaz,
"Performance of grid-integrated photovoltaic/fuel cell/ S.,"Energy management and control of grid-connected
electrolyzer/battery hybrid power system," Power wind/fuel cell/battery hybrid renewable energy system,"
Generation System and Renewable Energy Technologies IEEE International Conference on Intelligent Systems
(PGSRET), 2015: 1-8(2015). Engineering (ICISE 2016): 1-6 (2016).
[2] Uzunoglu, M., Onar, O. and Alam, M.,"Modeling, [15] Espinosa-Trujillo, M., Flota-Bañuelos, M., Pacheco-
control and simulation of a PV/FC/UC based hybrid Catalán, D., Smit, M. and Verde-Gómez, Y.,"A novel
power generation system for stand-alone applications," stand-alone mobile photovoltaic/wind
Renewable Energy, 34:509-520(2009). turbine/ultracapacitor/battery bank hybrid power
[3] Onar, O., Uzunoglu, M. and Alam, M.,"Dynamic system," Journal of Renewable and Sustainable Energy,
modeling, design and simulation of a wind/fuel 7(2): 023125(2015).
cell/ultra-capacitor-based hybrid power generation [16] El-Shater, T. F., Eskander, M. N. and El-Hagry, M.
system," Journal of Power Sources, 161: 707-722(2006). T.,"Energy flow and management of a hybrid
March-April
964 ISSN 1013-5316; CODEN: SINTE 8 Sci.Int.(Lahore),28(2),955-964,2016
wind/PV/fuel cell generation system," Energy [21] Kamarzaman, A. N., and Tan, C. W.,"A comprehensive
Conversion and Management, 47(9-10): 1264- review of maximum power point tracking algorithms for
1280(2006). photovoltaic systems," Renewable and Sustainable
[17] Hannan, A. and Hasan, K. M., "ABC algorithm based Energy Reviews, 37: 585-598(2014).
scheduling and control of renewable hybrid power [22] Hajizadeh, A. and Golkar, M. A.,"Intelligent power
system," Science International, 27(2): 1069-1074(2015). management strategy of hybrid distributed generation
[18] Ali, A., Amjad, M., Mehmood, A., Asim, U. and Abid, system," International Journal of Electrical Power &
A.,"Cost effective power generation using renewable Energy Systems, 29: 783-795(2007).
energy based hybrid system for Chakwal, Pakistan," [23] Spyker, R. L., and Nelms, R. M.,"Analysis of double-
Science International 27(6): 6017-6022(2015). layer capacitors supplying constant power loads," IEEE
[19] Josephs, R., Solar cell array design handbook: NASA: Transactions on Aerospace and Electronic Systems, 36:
(1976). 1439-1443(2000).
[20] Rodrigues, E., Melício, R., Mendes, V. and Catalão, [24] "IEEE Standard for Interconnecting Distributed
J.,"Simulation of a solar cell considering single-diode Resources with Electric Power Systems," IEEE Std
equivalent circuit model," International conference on 1547-2003: 1-28(2003).
renewable energies and power quality, Spain: 13-
15(2011).
March-April