Академический Документы
Профессиональный Документы
Культура Документы
confusion for many Code users. The first step in eliminating this confusion
is to understand that the NEC defines a branch circuit as “the conductors
between the branch circuit final overcurrent device protecting the circuit
and the outlets” (such as receptacles or lights) [Art. 100], as shown in Fig.
1. By contrast, a feeder circuit runs from the service equipment, the source
of a separately derived system, or other power supply to (rather than from)
the final branch circuit overcurrent device.
Fig. 1. The conductors between the final overcurrent device and the outlet(s) are defined as
branch circuit conductors.
The size of the circuit breaker installed on a branch circuit, not the
conductor size, determines the rating of the circuit. Therefore, if the
conductor size is increased to accommodate for voltage drop or for
ampacity adjustment or correction purposes, the rating of the circuit
remains the same as the circuit breaker size supplying it [210.3].
The size of the circuit breaker installed on a branch circuit, not the
conductor size, determines the rating of the circuit. Therefore, if the
conductor size is increased to accommodate for voltage drop or for
ampacity adjustment or correction purposes, the rating of the circuit
remains the same as the circuit breaker size supplying it [210.3].
You’ll find branch circuit requirements for conductor sizing, overcurrent
protection, identification, GFCI protection, receptacles, and lighting outlets
in Art. 210. Other Articles may apply to your installation; you’ll find those
listed in 210.2.
ADVERTISING
For personnel safety, each multiwire branch circuit must have a means to
simultaneously disconnect all ungrounded conductors at its origin
[210.4(B)]. If that origin is two or more breakers, you can provide this
disconnect by using single-pole circuit breakers with handle ties identified
for the purpose [240.15(B)(1)].
Identification
If you have more than one voltage system, then for each ungrounded
conductor [210.5(C)]:
Voltage limitations
In dwelling units, the voltage between conductors must not exceed 120V,
nominal, when they supply the terminals of [210.6(A)] luminaires or cord-
and plug-connected loads less than ¼ hp or less than or equal to 1,440VA
[21.6].
If two or more branch circuits supply devices (or equipment) on the same
yoke, a means must be provided at the circuit’s point of origin to disconnect
simultaneously all ungrounded conductors that supply those devices
[210.7].
Bathrooms.
Garages and accessory buildings.
Outdoors.
Crawl spaces.
Unfinished basements.
Serving kitchen countertops.
Within 6 ft of the outside edge of sinks, in addition to the requirements for
kitchen sinks.
Boathouses.
Also:
Each dwelling unit of a multifamily dwelling that has its own grade level
entrance must have at least one accessible GFCI-protected receptacle at 6½
ft or less above grade [210.52(E)(2)].
Balconies, decks, and porches attached to the dwelling unit and accessible
from inside the dwelling must have at least one GFCI-protected receptacle
outlet accessible from the balcony, deck, or porch [210.52(E)(3)].
Install GFCI at a readily accessible location for all 15A and 20A, 125V
receptacles in any of the following commercial/industrial locations
[210.8(B)]:
Bathrooms.
Kitchens (not required for hard-wired equipment).
Rooftops (A 15A or 20A, 125V receptacle must be installed within 25 ft of
heating, air-conditioning, and refrigeration equipment [210.63]).
Outdoors.
Sinks (except in laboratories where removal of power would introduce a
greater hazard or in patient bed locations of general care or critical care
areas of health care facilities).
Indoor wet locations.
Locker rooms with associated showering facilities.
Garages (where electrical diagnostic equipment, electrical hand tools, or
portable lighting equipment are to be used).
Boat hoists.
Number of circuits
Required circuits
It’s not just the total number of outlets that matters. The NEC also requires
certain types of circuits in specific places in addition to the minimum
requirements based on the VA/square foot calculation.
The size of the circuit breaker installed on a branch circuit, not the
conductor size, determines the rating of the circuit. Therefore, if the
conductor size is increased to accommodate for voltage drop or for
ampacity adjustment or correction purposes, the rating of the circuit
remains the same as the circuit breaker size supplying it [210.3].
You’ll find branch circuit requirements for conductor sizing, overcurrent
protection, identification, GFCI protection, receptacles, and lighting outlets
in Art. 210. Other Articles may apply to your installation; you’ll find those
listed in 210.2.
ADVERTISING
For personnel safety, each multiwire branch circuit must have a means to
simultaneously disconnect all ungrounded conductors at its origin
[210.4(B)]. If that origin is two or more breakers, you can provide this
disconnect by using single-pole circuit breakers with handle ties identified
for the purpose [240.15(B)(1)].
Identification
If you have more than one voltage system, then for each ungrounded
conductor [210.5(C)]:
Voltage limitations
In dwelling units, the voltage between conductors must not exceed 120V,
nominal, when they supply the terminals of [210.6(A)] luminaires or cord-
and plug-connected loads less than ¼ hp or less than or equal to 1,440VA
[21.6].
If two or more branch circuits supply devices (or equipment) on the same
yoke, a means must be provided at the circuit’s point of origin to disconnect
simultaneously all ungrounded conductors that supply those devices
[210.7].
Bathrooms.
Garages and accessory buildings.
Outdoors.
Crawl spaces.
Unfinished basements.
Serving kitchen countertops.
Within 6 ft of the outside edge of sinks, in addition to the requirements for
kitchen sinks.
Boathouses.
Also:
Each dwelling unit of a multifamily dwelling that has its own grade level
entrance must have at least one accessible GFCI-protected receptacle at 6½
ft or less above grade [210.52(E)(2)].
Balconies, decks, and porches attached to the dwelling unit and accessible
from inside the dwelling must have at least one GFCI-protected receptacle
outlet accessible from the balcony, deck, or porch [210.52(E)(3)].
Install GFCI at a readily accessible location for all 15A and 20A, 125V
receptacles in any of the following commercial/industrial locations
[210.8(B)]:
Bathrooms.
Kitchens (not required for hard-wired equipment).
Rooftops (A 15A or 20A, 125V receptacle must be installed within 25 ft of
heating, air-conditioning, and refrigeration equipment [210.63]).
Outdoors.
Sinks (except in laboratories where removal of power would introduce a
greater hazard or in patient bed locations of general care or critical care
areas of health care facilities).
Indoor wet locations.
Locker rooms with associated showering facilities.
Garages (where electrical diagnostic equipment, electrical hand tools, or
portable lighting equipment are to be used).
Boat hoists.
Number of circuits
Required circuits
It’s not just the total number of outlets that matters. The NEC also requires
certain types of circuits in specific places in addition to the minimum
requirements based on the VA/square foot calculation.
Provide one 20A, 120V branch circuit for the receptacle outlets required by
210.52(F) for the laundry room. The 20A laundry room receptacle circuit
can supply more than one receptacle in the laundry room. This receptacle
can’t supply other outlets, such as the laundry room lighting or receptacles
in other rooms (Fig. 2).
Fig. 2. A 20A laundry room receptacle circuit can supply more than one receptacle in the laundry
room, but there are restrictions, as outlined in 210.52(F).
GFCI protection isn’t required for 15A and 20A, 125V receptacles in a
laundry room, unless they’re within 6 ft of a sink [210.8(A)(7)].
Provide one 20A, 120V branch circuit for the receptacle outlets required by
210.52(D) for a dwelling unit bathroom or multiple bathrooms. This circuit
can’t supply other outlets, such as receptacles in rooms other than
bathrooms or lighting outlets [210.11(C)(3)], as shown in Fig. 3.
Fig. 3. A minimum of one 20A circuit is required to supply the required bathroom receptacles.
Other outlets aren’t permitted on the bathroom receptacle circuit.
An alternate method allows this circuit to supply all of the outlets in a single
bathroom, including lighting and fans, if no single load fastened in place is
rated more than 10A [210.11(C)(3) Ex and 210.23(A)], as shown in Fig. 4.
Fig. 4. A single 20A, 120V circuit can supply all of the outlets in a single bathroom, as long as
no single load exceeds 10A.
This gives you a good start on understanding branch circuit requirements.
In our next issue, we’ll look at some additional branch circuit requirements,
starting with arc fault circuit interrupters (AFCIs).