Академический Документы
Профессиональный Документы
Культура Документы
ELECTRICAL HAZARDS
6/14/2006
SOP. 49C 1
SOP #49C
ELECTRICAL HAZARDS
INTRODUCTION
There are many types of electrical hazards that the Boston Fire Department (BFD)
responds to. Agencies with very dangerous electrical equipment include, but are not
limited to, NSTAR, MBTA and AMTRAK. Regardless of the source, all electrical
equipment must be treated with respect and safe operations must be a priority.
49C.1 PURPOSE
The purpose of this Standard Operating Procedure (SOP) is to ensure that all members
are aware that electricity can be fatal and that extreme safety precautions shall be taken at
all incidents.
49C.2 SAFETY
Figure 1
Telephone wires, Fire Alarm cables and Television cable wires: These
may become energized with higher voltage/amperes due to unidentified
conditions away from the response area
Primary Wires on telephone poles: 13,800 volts
Secondary wires on telephone poles: 120/240 volts
Residential service drops: 120/240 volts
Residential and Commercial wiring: (e.g.; 110, 220, 440 volts)
6/14/2006
SOP. 49C 2
Figure 2
Position the apparatus the distance of at least two light poles away from downed
overhead wires on the opposite side of the street if at all possible due to potential
for unseen damage to other overhead wires
Do not attempt a rescue of a worker in contact with a power line until the utility
company de-energizes the line
Secure area from vehicle and pedestrian traffic with tape or cones
Minimum circle of safety is 30 feet from point of contact for downed power lines
Minimum circle of safety is 100 feet from point of contact for transmission lines
and 300 feet for non-essential personnel
Minimum distances are under the best possible conditions. Wind, water or other
environmental situations may affect safe operating distances. Increase distance
if conditions warrant it.
Aerials, tower ladders and ground ladders must be kept a minimum of ten feet
from overhead electrical wires at all raised aerial incidents, e.g. building fires with
power and communication wires present.
Insulation from vehicle tires or B.F.D. personal protective equipment (gloves, boots ect.)
will not provide protection from electrical shock. These products contain carbon or
carbon black, which conducts electricity. The ground surrounding the point of contact
could be electrically charged.
6/14/2006
SOP. 49C 3
Reclosers (Figure 4) are similar to a circuit breaker in that it opens the circuit if
there is a fault but unlike the typical circuit breaker, it recloses automatically after a
predetermined time. It can be made to repeat this cycle several times before it locks
itself open. This is one of many reasons not to touch a downed wire because it is
impossible to tell whether the wire is energized or not.
The following information should be considered at ALL incidents with downed wires:
large area. Always keep constant watch on the entire area, especially above you.
Buildings in the area affected may have to be inspected
Remember that your Personal Protective Equipment (PPE) will NOT prevent you
from being electrocuted
Do not use non-rated equipment such as rakes or ropes etc. to move downed wires
whether or not they are coming from the perceived source
Notify the District Fire Chief, through the Fire Alarm Office (FAO), of any
changes in the situation (i.e. more wires falling at different locations, or if people
are trapped in vehicles that are in contact with wires)
Do not use water streams for pole transformer fires until the power is confirmed
shut down
When protecting exposures near electrical hazards, use dry chemical or a fog
nozzle.
Stand by the scene until arrival of the power company and/or the police to secure
the area
Stay clear of Sub-Station fires. Protect exposures and let equipment burn itself out
6/14/2006
SOP. 49C 4
Vehicle accidents, heavy equipment and personnel in contact with power lines pose an
unusual problem for first responders. Contact with power lines, downed power lines, in
contact with pad mounted transformers, or any electrically charged equipment (MBTA
LRV 600 volt high voltage storage lockers (SOP 3)) require special attention. (Figure 5)
If there are occupants in the vehicle, they should be directed to remain in the vehicle
unless there is immediate threat to life or safety until the utility company de-energizes the
line.
Notify Fire Alarm to have the District Chief to respond to the incident
Figure 5
If the parties involved are in immediate danger due to fire or other life threatening injury,
and are physically able to escape, they should be directed to exit the vehicle with both
feet at the same time and not come in contact with the ground and the vehicle at the
same time. They shall be directed to shuffle away from the vehicle both feet as close
together as possible. This is due to the danger of step potential.
6/14/2006
SOP. 49C 5
.
Figure 6
BFD members shall not use water on a vehicle fire if the vehicle has downed wires or other
potential electrical hazards, in contact with or in close proximity to the vehicle. Dry chemical
shall be used in these situations and only in a life-threatening situation. If there is no life
hazard, let vehicle burn and protect exposures. Proper distances shall be maintained to protect
members from electrical shock.
Notify the utility or agency responsible to respond through the Fire Alarm Office.
According to the electrical code, all electrical circuits are required to have circuit breakers.
There are still many types of circuit breakers in use. Older model circuit breakers e.g. the old
Edison Plug Fuse, Type-S Fuse (Figure 7) or Cartridge Fuse may still be found today. Most
cartridge fuse types and some Type S Fuse boxes have either a push handle or a pull down
handle to de-energize the power. Newer style breakers are pushed left or right (Figure 8).
Either type should be marked indicating if it is on or off.
Figure 7 Figure 8
6/14/2006
SOP. 49C 6
The Boston Fire Department coordinates with other departments by routinely holding In-
Service Inspections of buildings, Fire Prevention Division Inspections and investigations by
the Fire Investigation Unit. Even though some of the causes of electrical hazards have
decreased due to new codes, regulations and inspections, there are still numerous causes.
Although not seen frequently, it does exist. There are many methods to it; all of which pose a
threat to the public and public safety members. The most obvious of these is:
6/14/2006
SOP. 49C 7
If illegal use of power is present or suspected, notify NSTAR and the Inspectional
Services Department (ISD) through the Fire Alarm Office (FAO).
Aerials, tower ladders and ground ladders must be kept a minimum of ten feet from all
overhead electrical wires. Wire could drop onto ladders. Arcing from 13.8 kilovolts is
possible across several feet of air gap, especially if humid, damp, or raining.
If fire or water has damaged or in any way impacted electrical wiring and/or hardware,
the power must be shut down to that portion of the structure or to the entire building if
necessary by way of the circuit breaker or fuse panel. (Do not pull the electrical meter)
Notify Inspectional Services and have NSTAR respond through the Fire Alarm Office
if the service drop needs to be cut
All elevators shall be recalled and checked for occupants prior to shutting down the
power
Heating systems by code should be on a separate circuit breaker. Shut down emergency
-o-
NSTAR can open circuits from their dispatch operation center if necessary. This
includes large fires, multiple buildings, commercial complexes as well as smaller
dwellings. This will take out a larger area than the specific property but if required for
firefighting operations it must be ordered. (Closest pole # or address must be given at
the time of order, and this should always be backed up with field testing by utility
personnel) (Figure 9)
6/14/2006
SOP. 49C 8
Electrical hazards are often caused by water leaks. These hazards are one of the most over-
looked and under-estimated situations that involve life safety. The size of the leak should
determine the area to be shut down. This depends on how much water has leaked into areas
where electrical fixtures, wiring and appliances may be present. Incidents that may require
shutting off power, related to water leaks include but are not limited to the following:
Water leaks in the building, coming from excess water on the roofs;
Leaks from plumbing from the floors above;
Broken sprinkler piping;
Any large amounts of water in the basement from any source;
If an electrical hazard occurs inside a structure it becomes the responsibility of the Boston
Inspectional Services Division. NSTAR does not have State Licensed Master Electricians.
They no longer maintain an inside electrical division. Their jurisdiction ends at the termination
of their equipment. This is usually at the service drop
socket. If the source of the problem is not immediately known or if there is any question, the
Incident Commander shall notify Fire Alarm to have NSTAR respond to cut the service.
6/14/2006
SOP. 49C 9
NSTAR cannot restore the power to any structure once it is cut until ISD has given
a State Licensed Master Electrician to the site to inspect and repair the damage. The electrician
must apply for a permit through ISD before any repair work can be done. The City of Boston
Inspectional Services Department then must re-inspect the building. This applies to all
electrical power shutoffs whether for water, fire or mechanical damage.
Inspectional Services shall be notified through the Fire Alarm Office if an electrical
inspector is needed at any time day or night.
1. If the extent of water damage is known, then a limited area can be shut down, leaving
the rest of the building with the power on. If unknown or unable to verify the area
affected, shut down additional electrical service to insure all affected electrical outlets
and fixtures are de-energized. (Do not the pull the electrical meter because a blinding
arc may result if under load, causing eye injury and or flash burns to exposed skin )
2. Thermal Imagers shall be used at all electrical hazard incidents
3. All elevators shall be checked for occupants if water has entered the hoist way or
elevator machine room.
4. Members shall not restore electrical service to the building once the power
has been shut down
5. Request through the Fire Alarm Office that an ISD electrical inspector be dispatched to
the scene and request an E.T.A.
6. The Fire Alarm office shall be given an update for ISD with all pertinent information.
7. The Incident Commander shall have the appropriate number of companies remain on
scene to await the arrival of the ISD inspector.
8. The Incident Commander shall notify the Fire Alarm Office that: the problem has been
isolated, the unit(s) are STANDING BY awaiting the arrival of the ISD inspector.
9. If an estimated time of arrival from I.S.D. is not available or a lengthy response time is
given, the incident commander shall notify the District Chief to respond .
10. The District Chief shall be notified if people have to be evacuated due to fire alarm
systems, or sprinkler systems being impaired.
11. The Incident Commander shall notify the Fire Alarm Office upon the arrival of the
I.S.D. electrical inspector. They shall also notify the FAO when they are returning to
quarters and that they have turned control of the incident over to the I.S.D. electrical
inspector.
12. Under emergency conditions, for example: multiple water leaks due to thawing of
broken sprinkler piping, heavy rains and or flash flooding, the Fire Alarm Office,
shall after conferring with the Division Commander in the affected area(s), strike
a Special Signal 10-43 that suspends STANDBY status. The Fire Alarm Office will
announce that STANDBY status as referenced above in section 49C.12.8 is suspended.
When conditions return to normal and after conferring with the Division Commander in
the affected area(s), Fire Alarm shall strike a 10-43 and announce that STANDBY status
is back in effect.
6/14/2006
SOP. 49C 10
There are facilities or areas at an incident, where shutting all power down could possibly lead
to a larger and more hazardous condition, with a high degree of risk and life safety.
If it is determined that the power should be shut down for any period of time, the Incident
Commander should ask for a representative from the utility to respond to the incident for
technical assistance and also notify ISD. Planning should take place prior to the order to shut
down power if at all possible to minimize the harmful effects that it may cause. The following
are a few areas for concern:
49C.15 SUMMARY
Remember the following principles when dealing with all electrical emergencies:
Aerials, tower ladders and ground ladders must be kept a minimum of ten feet from all
overhead electrical wires
Notify the Fire Alarm Office to contact the local authority that owns the source of
power whenever high voltage is involved
If inside a building, shut down the individual circuit breakers(s) or main circuit breaker
to the smallest area possible to mitigate the hazard if it is safe to do so
Treat all wire as energized and dangerous. Even low voltage can cause severe injury or
death
Establish a circle of safety depending on the type of electrical hazard present and
prevent unauthorized entry to the area
Substation fires-Do not enter, secure the area outside the fence line and notify the utility
If the BFD shuts down the power, never turn it back on. ISD must be notified
through the Fire Alarm Office giving the circumstances and extent of the problem.
6/14/2006