Вы находитесь на странице: 1из 2

Respon

sibilities SITE TEST REPORT Date :


Contractor’s name: Customer:
Legend ALFANAR. NG-SA
CSD
Name of substation: Dammam Housing 115/13.8KV Substation # 1 NG-SA Contract No. :
4400006262
DESCRIPTION : LOCK OUT RELAY TEST
Page 1 of 2
Panel/ Bay No: Equip. No.: Dwg. Ref.: Record No.:

1. GENERAL DATA AND INFORMATION.

Designation LOR

Type

Aux: Voltage

Application

ELECTRICAL TEST

A. PICKUP TEST

COIL VOLTAGE (V DC) CURRENT (mA) LIMITS


OPERATE 30 – 70 V

B. OPERATING TIME TEST:

RESETTING
VOLTAGE OPERATING RESETTING OPERATING
LIMIT (ms)
APPLIED (V DC) TIME (ms) TIME (ms) LIMITS (ms)

< 11 < 80
125

C. OPERATING COIL RESISTANCE TEST:

Resistance Measured (Ω) Limits


93 – 115 Ω

D. OPERATING CURRENT TEST

TEST DATE: TEST EQUIPMENT CALIB.DATE & DETAIL

TESTING ENGINEER CSD- Engineer

Signature: ________________ Signature: ________________


Name : ________________ Name : ________________
SITE TEST REPORT Date :
Contractor’s name: Customer:
ALFANAR. NG-SA

Name of substation: Dammam Housing 115/13.8KV Substation # 1 NG-SA Contract No. :


4400006262
DESCRIPTION : LOCK OUT RELAY TEST
Page 2 of 2
Panel/ Bay No: Equip. No.: Dwg. Ref.: Record No.:

RESET COIL
VOLTAGE APPLIED (V DC) OPERATING COIL (mA)

Limits : The current at rated voltage A


CAUTION: DO NOT GIVE VOLTAGE TO THE LOCK OUT RELAY COIL SLOWLY, TO PICK UP
THE COIL.

TEST EQUIPMENT USED:


1)
2)

TEST DATE: TEST EQUIPMENT CALIB.DATE & DETAIL

TESTING ENGINEER CSD- Engineer

Signature: ________________ Signature: ________________


Name : ________________ Name : ________________