ETAP Page: 1
12.6.0H
Location: Date: 10-10-2019
Contract: SN:
Engineer: Revision: Base
Study Case: SM
Filename: GSK Config.: Normal
Short-Circuit Analysis
ANSI Standard
3-Phase, LG, LL, & LLG Fault Currents
1/2 Cycle Network
Adjustments
Apply Individual
Tolerance Adjustments /Global Percent
Cable Length: No
Apply Individual
Temperature Correction Adjustments /Global Degree C
40 Buses Total
Ohms or Siemens per 1000 ft per Conductor (Cable) or per Phase (Line)
Line/Cable Length
Cable 8 1.0MCUN4 300 260.0 0.0 1 75 0.0232569 0.0216408 0.0000501 0.0732591 0.0532364
Cable 9 1.0MCUN4 150 131.2 0.0 2 75 0.046223 0.0222504 0.000044 0.1456024 0.054736
Cable 10 1.0MCUN4 300 40.0 0.0 1 75 0.0232569 0.0216408 0.0000501 0.0732591 0.0532364
Cable 11 1.0MCUN4 300 426.5 0.0 2 75 0.0232569 0.0216408 0.0000501 0.0732591 0.0532364
Cable 12 1.0MCUN4 300 295.3 0.0 1 75 0.0232569 0.0216408 0.0000501 0.0732591 0.0532364
Cable 13 1.0MCUN4 400 85.0 0.0 1 75 0.0186055 0.0216408 0.0000514 0.0586073 0.0532364
Cable 18 1.0MCUN4 300 426.5 0.0 2 75 0.0232569 0.0216408 0.0000501 0.0732591 0.0532364
Cable 23 1.0MCUN4 240 328.1 0.0 1 75 0.0281989 0.0219456 0.0000477 0.0888266 0.0539862
Cable 24 1.0MCUN4 300 360.9 0.0 1 75 0.0232569 0.0216408 0.0000501 0.0732591 0.0532364
Cable 25. 1.0MCUN4 4.0 360.9 0.0 1 75 1.706471 0.0283464 0.0000175 5.37553 0.0697321
Cable 26 1.0MCUN4 6.0 360.9 0.0 1 75 1.139586 0.0271272 0.0000202 3.589695 0.0667329
Cable 29 1.0MCUN4 6.0 49.2 0.0 1 75 1.139586 0.0271272 0.0000202 3.589695 0.0667329
Cable 30 1.0MCUN4 6.0 19.7 0.0 1 75 1.139586 0.0271272 0.0000202 3.589695 0.0667329
Cable 32 1.0MCUN4 300 360.9 0.0 1 75 0.0232569 0.0216408 0.0000501 0.0732591 0.0532364
Cable 33 1.0MCUN4 300 150.0 0.0 2 75 0.0232569 0.0216408 0.0000501 0.0732591 0.0532364
Cable 34 1.0MCUN4 400 65.0 0.0 1 75 0.0186055 0.0216408 0.0000514 0.0586073 0.0532364
Project:
ETAP Page: 6
12.6.0H
Location: Date: 10-10-2019
Contract: SN:
Engineer: Revision: Base
Study Case: SM
Filename: GSK Config.: Normal
Ohms or Siemens per 1000 ft per Conductor (Cable) or per Phase (Line)
Line/Cable Length
Cable 36 1.0MCUN4 240 295.3 0.0 1 75 0.0281989 0.0219456 0.0000477 0.0888266 0.0539862
Grounding
Branch Connections
CAT 32/2 Diesel 1.000 0.400 1500 19.00 1.000 19.00 0.0 28.00 Wye Solid 19.00 0.368 7.00
CAT C32/1 Diesel 1.000 0.400 1500 19.00 1.000 19.00 0.0 28.00 Wye Solid 19.00 0.368 7.00
Bus 12 Total 0.00 10.365 0.00 93.79 118.11 9.503 9.503 4.85E+002 1.38E+003 1.42E+003 1.41E+003
Bus 10 Bus 12 35.31 10.365 52.25 90.96 101.80 9.503 9.503 4.85E+002 1.38E+003 1.42E+003 1.41E+003
Bus 9 Bus 10 39.96 10.365 58.86 90.23 100.40 9.503 9.503 1.07E+002 1.03E+003 2.29E+002 5.41E+002
Bus 13 Bus 10 35.31 0.000 52.25 90.96 101.80 0.000 0.000
Bus 14 Bus 10 35.31 0.000 52.25 90.96 101.80 0.000 0.000
Bus 15 Bus 10 35.31 0.000 52.25 90.96 101.80 0.000 0.000
Bus 16 Bus 10 35.31 0.000 52.25 90.96 101.80 0.000 0.000
Bus 17 Bus 10 35.31 0.000 52.25 90.96 101.80 0.000 0.000
Bus 18 Bus 10 35.31 0.000 52.25 90.96 101.80 0.000 0.000
Bus 19 Bus 10 35.31 0.000 52.25 90.96 101.80 0.000 0.000
Bus 20 Bus 10 35.31 0.000 52.25 90.96 101.80 0.000 0.000
Bus 21 Bus 10 35.31 0.000 52.25 90.96 101.80 0.000 0.000
Bus 22 Bus 10 35.31 0.000 52.25 90.96 101.80 0.000 0.000
Bus 23 Bus 11 35.31 0.000 52.25 90.96 101.80 0.000 0.000
Bus 24 Bus 11 35.31 0.000 52.25 90.96 101.80 0.000 0.000
Bus 25 Bus 11 35.31 0.000 52.25 90.96 101.80 0.000 0.000
Bus 26 Bus 11 35.31 0.000 52.25 90.96 101.80 0.000 0.000
Bus 27 Bus 11 35.31 0.000 52.25 90.96 101.80 0.000 0.000
Bus 28 Bus 11 35.31 0.000 52.25 90.96 101.80 0.000 0.000
Bus 29 Bus 11 35.31 0.000 52.25 90.96 101.80 0.000 0.000
Bus 30 Bus 11 35.31 0.000 52.25 90.96 101.80 0.000 0.000
Bus 31 Bus 11 35.31 0.000 52.25 90.96 101.80 0.000 0.000
Bus 32 Bus 11 35.31 0.000 52.25 90.96 101.80 0.000 0.000
Bus 33 Bus 11 35.31 0.000 52.25 90.96 101.80 0.000 0.000
Bus 34 Bus 11 35.31 0.000 52.25 90.96 101.80 0.000 0.000
Bus 35 Bus 11 35.31 0.000 52.25 90.96 101.80 0.000 0.000
Bus 36 Bus 11 35.31 0.000 52.25 90.96 101.80 0.000 0.000
Bus 37 Bus 11 35.31 0.000 52.25 90.96 101.80 0.000 0.000
Bus 38 Bus 11 35.31 0.000 52.25 90.96 101.80 0.000 0.000
Bus 39 Bus 11 35.31 0.000 52.25 90.96 101.80 0.000 0.000
Bus 40 Bus 11 35.31 0.000 52.25 90.96 101.80 0.000 0.000
Bus 5 Bus 8 41.91 5.200 61.77 91.35 100.92 4.808 4.887 1.31E+002 1.93E+003 1.97E+002 7.71E+002
Project:
ETAP Page: 12
12.6.0H
Location: Date: 10-10-2019
Contract: SN:
Engineer: Revision: Base
Study Case: SM
Filename: GSK Config.: Normal
(Cont.)
Bus 6 Bus 8 42.70 5.165 62.92 91.36 100.61 4.697 4.622 1.52E+002 1.94E+003 2.64E+002 7.99E+002
* Indicates a zero sequence fault current contribution (3I0) from a grounded Delta- Y transformer
Project:
ETAP Page: 13
12.6.0H
Location: Date: 10-10-2019
Contract: SN:
Engineer: Revision: Base
Study Case: SM
Filename: GSK Config.: Normal
Bus 12 0.42 3.439 -9.778 10.365 4.847 -8.174 9.503 8.487 3.197 9.069 -11.064 0.200 11.066
All fault currents are symmetrical momentary (1/2 Cycle network) values in rms kA
* LLG fault current is the larger of the two faulted line currents
Project:
ETAP Page: 14
12.6.0H
Location: Date: 10-10-2019
Contract: SN:
Engineer: Revision: Base
Study Case: SM
Filename: GSK Config.: Normal
Bus Positive Seq. Imp. (ohm) Negative Seq. Imp. (ohm) Zero Seq. Imp. (ohm) Fault Zf (ohm)
ID kV Resistance Reactance Impedance Resistance Reactance Impedance Resistance Reactance Impedance Resistance Reactance Impedance
Bus 12 0.420 0.00776 0.02207 0.02339 0.00856 0.02127 0.02293 0.02272 0.02250 0.03198 0.00000 0.00000 0.00000
Project:
ETAP Page: 15
12.6.0H
Location: Date: 10-10-2019
Contract: SN:
Engineer: Revision: Base
Study Case: SM
Filename: GSK Config.: Normal
Symmetrical 3-Phase Fault between Bus 12 and New Absorption Chiller. Adjacent to Bus 12.