General Features
• Main Input - 24Vac
The PS-MZ 100/200 is ideal for
• Controls up to 4 zones (PS-MZ100) or 7 zones (PS-
residential, commercial or industrial MZ200)
applications. It is compatible with • Zone 1 also serves as Master (same thermostat)
Heat/Cool or Heat Pump HVac • Selectable system configuration- Heat/Cool or Heat pump
applications and can control up to 4 • Up to 5 stages of Heat and 5 stages of Cool
• Selectable Heat output- Electric or Oil/Gas (jumper
(PS-MZ100) or 7 (PS-MZ200) different
selectable)
zones. • Modes: Cool, Heat, Auto-change Over, Fan Only-
One of the zone serves also as the selectable through Master ONLY
master, and different types of • T1- Indoor temperature sensor- option (for Fresh Air
Damper)
thermostats can be selected as zones.
• T2- Outdoor temperature sensor- option (for Fresh Air
Zones can also be programmed for Damper)
ON/OFF, ideal for times when the zone • T3- Indoor Coil sensor (freeze protection in Cool and
is less occupied. overheat protection in Heat)
• Output for dampers- On/Off, 3-wire, 24Vac
The main board offers inputs for • Zone dampers- On/Off, 3-wire
Bypass and Fresh Air dampers, and 3 • Fresh Air Dampers- 2 logics for open/close:
different temperature sensors. 1. by timer (min per hour) OR
2. by temperature difference (T1-T2)
Other features such as Auto-
• Bypass Damper (On/Off, 3-wire) output
Changeover mode and quick • Display temperature available in C or F- depending on
connectors from the thermostats to the model ordered
main board, make this multi-zone the • Economy mode (Unoccupied mode)
simplest and most efficient climate • Zone thermostats with weekly program- option depending
on model ordered
control system.
• Weekly Program type- (5-1-1)- 4 times Set Cool/Set Heat

File: PS-MZ 100 / 200.ppt


Pg.1 www.meitavtec.com | Email: info@meitavtec.com | Tel: +972 (3) 962 6462 Rev.1 Date: 21.06.2005
meitav-tec
Multi-Zone System PS-MZ 100 / 200

Master and Zone 1 M100


Functions of thermostat as MASTER:
• Controls main system functions:
• On/Off
• Mode (Cool, Heat, Auto, Fan Only)
• Activate or de-activate Economy Mode
(Unoccupied Mode)
• Set Fresh Air damper logic

Functions of thermostat as ZONE 1: Prog


• Local Fan Non-Prog
• Local set point
• Weekly program- option depending on thermostat ordered

Main Board PS-MZ100 / 200


General Features
• Main Supply- 24 Vac
• Up to 4 zones (PS-MZ100) or 7 zones (PS-MZ200)
• System Configuration selectable on the unit:
• Heat/Cool, Heat Pump
• Heat Output- electric Heat or Oil/Gas
• Multiple stages
• Bypass damper output (3-wire)
• Fresh Air Damper output with 2 options:
• by timer (certain number of minutes per hour)
• by temperature difference (T1-T2)
• 3 temperature sensors:
•T1- indoor temperature sensor (Fresh Air Damper)
•T2- outdoor temperature sensor (Fresh Air Damper)
•T3- indoor coil sensor (freeze protection in Cool, overheat protection in Heat)
• Economy (Set Back) Mode available for all system

Zone Z100
General Features
• Set local On/Off status
• Set local set point
• Weekly program- option
(depending on thermostat ordered)

Prog Non-Prog

Cable Connection
The connection between the
main board and the thermostat
is made by telephone jack as
shown, and the necessary cable
Tel. Cable Main Board Zone
is shown here.

File: PS-MZ 100 / 200.ppt


Pg.2 www.meitavtec.com | Email: info@meitavtec.com | Tel: +972 (3) 962 6462 Rev.1 Date: 21.06.2005
meitav-tec
Multi-Zone System PS-MZ 100 / 200

Electrical Diagram
*Zone
To AC System Controllers-
Telephone
Jacks

Heat Pump in

Heat Pump in
Compressor 1

Compressor 2

Master &
Main Input- Indoor Outdoor Indoor Coil

Zone 1

Zone 4
Zone 3
Heat 1

Zone 2
Heat 2

Heat

Cool
24Vac Sensor- Sensor- Sensor-

Fan
option option option

Y1 Y2 W1 W2 B O G Rc Rh C T1 T1 T2 T2 T3 T3

Main Board PS-MZ100 / 200

R C 0P COM CL 0P COM CL 0P COM CL 0P COM CL 0P COM CL 0P COM CL

24Vac-
Fresh Air Zone 1 Zone 2 Fresh Air Zone 4
power for Bypass Damper Damper Damper Damper Damper
dampers and damper
zone
controller *Note: PS-MZ200 offers up to 7 zones

Components

Main Board PS-MZ100 Controls up to 4 zones


(1 required per system) PS-MZ200 Controls up to 7 zones

ETN-M100-C Master & Zone controller, wall-mount, display in °C

Master & Zone 1 ETN-M100-F Master & Zone controller, wall-mount, display in °F
(1 required per system) ETN-M100-Prog-C Master & Zone controller with 5-1-1 program, wall-mount, display in °C

ETN-M100-Prog-F Master & Zone controller with 5-1-1 program, wall-mount, display in °F

ETN-Z100-C Zone controller, wall-mount, display in °C

ETN-Z100-F Zone controller, wall-mount, display in °F


Thermostats for Zones
ETN-Z100-Prog-C Zone controller with 5-1-1 program, wall-mount, display in °C

ETN-Z100-Prog-F Zone controller with 5-1-1 program, wall-mount, display in °F

Note: All Master and Zone thermostats are available in flush-mount models (FMT) as well.