The document appears to be an experiment report determining the coefficient of performance (COP) of a vapor absorption refrigeration system. It includes an observation table with temperature, pressure, power input, heat rejection, and COP measurements. The actual COP was calculated to be 3.43 and the Carnot COP was calculated to be 4.57 based on the temperature measurements.
The document appears to be an experiment report determining the coefficient of performance (COP) of a vapor absorption refrigeration system. It includes an observation table with temperature, pressure, power input, heat rejection, and COP measurements. The actual COP was calculated to be 3.43 and the Carnot COP was calculated to be 4.57 based on the temperature measurements.
The document appears to be an experiment report determining the coefficient of performance (COP) of a vapor absorption refrigeration system. It includes an observation table with temperature, pressure, power input, heat rejection, and COP measurements. The actual COP was calculated to be 3.43 and the Carnot COP was calculated to be 4.57 based on the temperature measurements.
Air conditioning (DETERMINATION OF C.O.P. OF VAPOR ABSORPTION REFRIGERATION SYSTEM) COP
Observation table:
Sl. Temperature Pressure Refriger Heat Actual
No C ant rejection C.O.P bar Power in Input, flow condens W kW rate, er kg/min kW Carnot COP Volt - Amps T1 T2 T3 T4 Plow Phigh - P = VI 1 11.1 73.3 42.5 6.3 3.5 16.2 0.97 35 3.43 4.57 h1 = 410 kJ/kg h2 = 445 kJ/kg h3 = 290 kJ/kg h4 = 290 kJ/kg
Heat rejected in condenser= h2 - h1 = 35 kW COP actual = (h1-h4)/(h2-h1) =