VOIR LE COMMENTE SHEETS

A.OULD KADDOUR 13/01/2019

Statu code 2
PROJECT: SECURITY CAMP OUED ZINE FOR TOUAT GAS DEVELOPMENT ALGERIA

SCHEDULE OF AIR COOLED CHILLERS WITH HEAT PUMP

RFQ DATA SKM DATA


COOLING DATA HEATING DATA COOLING DATA HEATING DATA
(SUMMER CONDITION) (WINTER CONDITION) (SUMMER CONDITION) (WINTER CONDITION) SOUND PRESSURE
TOTAL POWER TOTAL POWER
DESIGN DESIGN DESIGN LEVEL IN Db ref
DESIGN AMBIENT HOT WATER ENTERING / HOT WATER INPUT FOR INPUT FOR HEAT
S.NO. EQUIPMENT NO. MODEL NAME QTY TYPE TOTAL COOLING ENTERING / LEAVING HEATING AMBIENT TOTAL COOLING AMBIENT HEATING AMBIENT REFRIGERANT 2X10ˉ5 Pa @ 1m in
TEMPERATURE TEMP LEAVING WATER TEMP COOLING PUMP
CAPACITY WATER CAPACITY TEMPERATURE CAPACITY TEMPERATURE CAPACITY TEMPERATURE KW KW
free field
(°C) (ENTERING/LE TEMPERATURE (ENTERING/L
(KW) TEMPERATURE (°C) (KW) (°C) (KW) (°C) (KW) (DB) (°C) (Overall dBA)
AVING)°C (°C) EAVING)°C
1 BDV-ADM-CEG-01 APCL-5085CHPM 3 CHILLER WITH HEAT PUMP 204 11/6 51 53 40/45 -5 210.2 11/6 51 261.2 38.7 / 45 -5 R407C 130.2 113.48 76.3
2 BDV-RES-CEG-01 On Hold
3 BDV-FOY-CEG-01 APCL-5015CHPM 3 CHILLER WITH HEAT PUMP 43.8 11/6 51 17.2 40/45 -5 43.8 11/6 51 50.33 38.7 / 45 -5 R407C 24.62 21.46 71.0
4 BDV-SPO-CEG-01 APCL-5055CHPM 3 CHILLER WITH HEAT PUMP 140 11/6 51 100 40/45 -5 140.7 11/6 51 167.23 39.5 / 45 -5 R407C 82.86 73.86 75.0
5 BDV-SPO-CEG-02 APCL-5015HPM 1 CHILLER WITH HEATING ONLY N/A N/A N/A 50 40/45 -5 N/A N/A N/A 50.33 38.7 / 45 -5 R407C - 21.46 71.0
6 BDV-FPS-CEG-01 APCL-5040CM 1 CHILLER WITH COOLING ONLY 106.5 11/6 51 - - - 106.5 11/6 51 N/A N/A N/A R407C 65.84 - 74.5
11
Special Notes/ Options:
* Chillers have scroll compressor
* Voltage 380V/3AC/50Hz + Ground + Neutral
* Altitude is 320m
* Refrigerant - R407c
* Condenser fans motor shall be with VFD (As per SKM design requirements)
* Disconnect switch with door interlock for control panel
* Shell & tube evaporator for all Chillers
* Suction & discharge pressure gauges
* RS-485 interface for supervising systems with protocol MODSUS
* External spring anti vibration mounts
* Full chiller shall be suitable for aggressive Marine conditions
* CU/AL fins with Aeris coating
* Oil separators
* IP-55 control panel with ventillation fan & filter
* AISI SS316L Sunshade & rain hood for the Control panel
* Victaulic connections shall be provided for chillers
* Chillers shall be with DOL starting method.
* Anti-freeze up protection for evaporator
* Suction line accumulator
* Accumulators
* Extra shut off valve
* Microprocessor shall have the provision to display "kWh" electricity consumption of the refrigeration unit
* Industrial type waterproof light for control panel with door limit switch.
ENGINEERING SPECIFICATION ISSUE : 1

AERIS GUARD COIL COATING DATE : JULY 6,2005

Description:
Aeris Guard Coil Coat is a self etching high performance epoxy water based finish. It is specially designed
to protect condenser and indoor coils used in the Air-Conditioning . Also, small quantities of microbial
biocide have been added to inhibit microbial colonisation and protect heat exchange surfaces.
Aeris Guard Coil Coat is ideally suited for the corrosion protection of coil products located in coastal
regions and a majority of hazardous environments encountered in both commercial and industrial
application.

Product Performance Tests:


1-Salt Spray Resistance Test:

Extensive tests conducted in NATA laboratory confirmed the high performance against other coatings.
For single dip coating there was no evidence of corrosion after exposure to 5% Neutral Salt Spray under
AS 2331.32-1980 (ASTM B-117) conditions over periods in excess of 3000 hours.

Results showed virtual disintegration of the bare aluminum fin after 100 hours, with no effect on the
Aeris Guard Coated aluminum fin.

Aeris Guard Coated copper fins showed no deterioration and gave no black spotting after 100 hours
exposure.

2-Electrolysis Test:

Results of test carried out with samples immersed in 20% phosphoric acid at 70° C for one hour showed
visual disintegration of the bare aluminum fin, with no failure of the coating of the Aeris Guard Coated
aluminum fin.

Properties:
Colour : Blue
Gloss Level : Full
Chemical Resistance: Excellent, see chemical resistance information
Solvent Resistance: Dependent upon selection of solvent
Temperature Range: Up to 120 ° C
Fin pattern: Corrugated and waffle louver.
Fin Type: All metallic and non metallic combinations
Odour: Slight non toxic odour during application, nil in service
Technical Data:

Application method: Total Coil Immersion (Dipping).


Immersion Cycle: Dependent upon coil size
Curing Cycle: Dependent upon coil size
Application film build up: 4-6 microns d.f.t. (dry film thickness) per coat
Heat Transfer: Negligible impairment at the given thickness less than 0.5%
Suitable Environments: Ideal for many aggressive environments i.e. commercial, industrial and coastal
regions.
Chemical Resistance:
Corrosive Agent Concentration Rating

Hydrochloric Acid 20% Excellent


Hydrochloric Acid 30% Good
Sulphuric Acid 20% Excellent
Sulphuric Acid 30% Good
Phosphoric Acid 30% Excellent
Phosphoric Acid 50% Excellent
Acetic Acid 10% Good
Sodium Hydroxide 10% Poor
Trichloroethylene Good
Toluene Good
Methylated Spirits Good
Mineral T Good
Acetone Poor
MEK (Methyl Ethyl Ketone) Poor

In addition the above Aeris Guard Coil Coat demonstrates excellent resistance to fumes from Lactic Acid,
Oxalic Acid, Humid Acid and Saltwater.

Features:
Environmentally safe in both the makeup and application
Total Surface Protection including sealing all surfaces between the copper tubes and aluminum/copper fins.
User Friendly
Negligible heat transfer impairment at the required thickness
High resistance to acids and salt spray
Hard yet flexible
Demonstrates high resistance to ambient temperatures
Minimizes linting
Promotes the flow of water over the protected surface & improves air flow.
Inhibits microbial colonization for life of coating
Air Cooled Chillers
APCL5085CHPM
CUSTOMER SALES ENGINEER

PROJECT SECURITY CAMP OUED ZINE FOR TOUAT GAS DATE

UNIT TAG BDV-ADM-CEG-01

PERFORMANCE DATA

COOLING CAPACITY : 210.2 kW LEAVING WATER TEMPERATURE : 6.0 ºC

COMPRESSOR POWER INPUT : 117.3 kW WATER TEMPERATURE DROP : 5.0 ºC

TOTAL PI (Comps. + Cond. motors) : 130.2 kW WATER FLOW RATE : 10.1 l/s

WATER PRESSURE DROP : 49.7 kpa


BDV-ADM-CEG-01
AMBIENT TEMPERATURE : 51.0 ºC REFRIGERANT : R-407C

EVAPORATOR FOULING FACTOR : 0.018 m2ºC/kW REFRIGERANT CIRCUITS : 2

ALTITUDE, above sea level : 320 m

SPECIFICATIONS

COMPRESSOR CONDENSER FAN


COMPRESSOR TYPE : Hermetic Scroll FAN TYPE : Direct Driven Propeller
COMP 1 CODE / QTY : ZR380KCE / 2#
FAN CODE / QTY : MW800/38.5/5 / 8#
COMP 2 CODE / QTY : ZR310KCE / 2#
CAPACITY STEPS : 100-78-50-28-0 CONDENSER MOTOR
EVAPORATOR MOTOR TYPE : TEAO, Class F, 6-Pole, IP-55

EVAPORATOR TYPE : Shell & Tube MOTOR SIZE / QTY : 1.5 kW / 8#

EVAPORATOR CODE / QTY : DH2-212H / 1# CONDENSER COIL


42x78 / 3R/ 12FPI /8# (HI-X)Aluminum with Aeris-Coated Fins

MAIN POWER SUPPLY : 380V/3Ph/50Hz

Power input mentioned/provided here is at rated condition only, and should not be used for cable/fuse
selection. For MCA/MFA values (whenever required), please consult Engineering – Electrical

SKM Air Conditioning LLC


P.O.Box: 6004, Sharjah Email : skm.sales@skmaircon.com
Tel : +971 6 5143333, Fax : +971 6 5143300 Visit us at www.skmaircon.com
HEATING MODE
APCL 5085-CHPM (Heating mode)
Cap: 261.2 kW (@ -5ºC ambient)
Comp PI : 100.6 kW
Water Flow Rate : Same as in cooling mode
Inlet temp : 38.7 °C
Outlet temp : 45.0 °C
PRELIMINARY DRG.
UNIT TAG: BDV-ADM-CEG-01

A1 A3 A5

A2 A4 A6

88.27 200.35
[2242] 1 2 [5089] 5

VENTILATION FAN
& FILTER WITH
HOSE PROOF HOOD

FILTERED
VENTILATION WITH
[2345]
92.33

HOSE PROOF HOOD

CABLE ENTRY

3 6 4 RIGGING HOLES CH.W.IN CH.W.OUT


4x Ø7/8 [22]

ALL DIMENSIONS ARE IN INCHES [MM]

TITLE EQUIPMENT LAYOUT SKM Airconditioning LLC


POST BOX No: 6004, SHARJAH, U.A.E.
AIR CONDITIONING EQUIPMENT TEL : +971 6 514 3333 , FAX : +971 6 514 3300
6- SUCTION ACCUMULATOR MODEL APCL5085CHPM
5- CONTROL PANEL
NAME SIGN DATE
JOB No. - QTY. - SCALE 1:50
4- EVAPORATOR
3- COMPRESSOR
DESIGNED KENUS 11.09.2017 CLIENT
DRAWN LV 11.09.2017
2- CONDENSER COIL PROJECT Security camp OUED ZINE for Touat gas Devlopment
P1 18.01.18 LV FAN MODEL & UNIT HEIGHT CHANGED. 1- CONDENSER FAN E.CHECKED
REV. DATE NAME REMARKS LEGEND APPROVED DRG. No. M7417005 REV. P1 SHEET 1 / 1
Air Cooled Chillers
APCL-5015CHPM
CUSTOMER SALES ENGINEER
PROJECT SECURITY CAMP OUED ZINE FOR TOUAT GAS DATE
UNIT TAG BDV-FOY-CEG-01

PERFORMANCE DATA

COOLING CAPACITY : 43.8 kW LEAVING WATER TEMPERATURE : 6.0 ºC

COMPRESSOR POWER INPUT : 21.40 kW WATER TEMPERATURE DROP : 5.0 ºC

TOTAL PI (Comps. + Cond. motors) : 24.62 kW WATER FLOW RATE : 1.936 l/s

WATER PRESSURE DROP : 31.89 kpa

AMBIENT TEMPERATURE : 51.0 ºC REFRIGERANT : R-407C

EVAPORATOR FOULING FACTOR : 0.018 m2ºC/kW REFRIGERANT CIRCUITS : 1

ALTITUDE, above sea level : 320 m

SPECIFICATIONS

COMPRESSOR CONDENSER FAN


COMPRESSOR TYPE : Hermetic Scroll FAN TYPE : Direct Driven Propeller
COMP 1 CODE / QTY : ZR125KCE / 2#
FAN CODE / QTY : MW800/38.5/5 / 2#

CAPACITY STEPS : 100-50-0 CONDENSER MOTOR


EVAPORATOR MOTOR TYPE : EC motor- TEAO, Class F, 6-Pole, IP-55

EVAPORATOR TYPE : Shell & Tube MOTOR SIZE / QTY : 1.5 kW/ 2#

EVAPORATOR CODE / QTY : DH1-144/ 1# CONDENSER COIL


42x78 / 2R/ 12FPI /2# (HI-X)Aluminum with Aeris-Coated Fins

MAIN POWER SUPPLY : 380V/3Ph/50Hz

Power input mentioned/provided here is at rated condition only, and should not be used for cable/fuse
selection. For MCA/MFA values (whenever required), please consult Engineering – Electrical

SKM Air Conditioning LLC


P.O.Box: 6004, Sharjah Email : skm.sales@skmaircon.com
Tel : +971 6 5143333, Fax : +971 6 5143300 Visit us at www.skmaircon.com
HEATING MODE
APCL 5015-CHPM (Heating mode)
Cap: 50.33 kW (@ -5 ºC ambient)
Comp PI : 18.24 kW
Water Flow Rate : Same as in cooling mode
Inlet temp : 38.7 °C
Outlet temp : 45.0 °C
PRELIMINARY DRG.
UNIT TAG: BDV-FOY-CEG-01

10 68.27 10
[254] [1734] [254]

A1 A3

A2 A4

88.27 61.02
[2242] [1550]
1 2 5

SUNSHADE & RAIN HOOD

VENTILATION FAN
& FILTER WITH
HOSE PROOF HOOD

FILTERED
VENTILATION WITH
[2406]
94.72

HOSE PROOF HOOD

CABLE ENTRY

C.W. IN C.W. OUT RIGGING HOLES 4 6 3


[MPT 2''] [MPT 2''] 4 x Ø1 [25.4]

ALL DIMENSIONS ARE IN INCHES [MM]

TITLE EQUIPMENT LAYOUT SKM Airconditioning LLC


POST BOX No: 6004, SHARJAH, U.A.E.
AIR CONDITIONING EQUIPMENT TEL : +971 6 514 3333 , FAX : +971 6 514 3300
6- SUCTION ACCUMULATOR MODEL APCL5015CHPM
5- CONTROL PANEL
NAME SIGN DATE
JOB No. - QTY. - SCALE 1:40
4- EVAPORATOR
3- COMPRESSOR
DESIGNED KENUS 22.05.2018 CLIENT
DRAWN LV 22.05.2018
2- CONDENSER COIL PROJECT Security camp OUED ZINE for Touat gas Devlopment
1- CONDENSER FAN E.CHECKED
REV. DATE NAME REMARKS LEGEND APPROVED DRG. No. M7418004 REV. - SHEET 1 / 1
Air Cooled Chillers
APCL-5055CHPM
CUSTOMER SALES ENGINEER
PROJECT SECURITY CAMP OUED ZINE FOR TOUAT GAS DATE
UNIT TAG BDV-SPO-CEG-01

PERFORMANCE DATA

COOLING CAPACITY : 140.7 kW LEAVING WATER TEMPERATURE : 6.0 ºC

COMPRESSOR POWER INPUT : 73.20 kW WATER TEMPERATURE DROP : 5.0 ºC

TOTAL PI (Comps. + Cond. motors) : 82.86 kW WATER FLOW RATE : 6.725 l/s

WATER PRESSURE DROP : 17.19 kpa

AMBIENT TEMPERATURE : 51.0 ºC REFRIGERANT : R-407C

EVAPORATOR FOULING FACTOR : 0.018 m2ºC/kW REFRIGERANT CIRCUITS : 2

ALTITUDE, above sea level : 320 m

SPECIFICATIONS

COMPRESSOR CONDENSER FAN


COMPRESSOR TYPE : Hermetic Scroll FAN TYPE : Direct Driven Propeller
COMP 1 CODE / QTY : ZR250KCE / 2 #
FAN CODE / QTY : MW800/38.5/5 / 6#
COMP 2 CODE / QTY : ZR190KCE / 2 #
CAPACITY STEPS : 100-78-50-28-0 CONDENSER MOTOR
EVAPORATOR MOTOR TYPE : TEAO, Class F, 6-Pole, IP-55

EVAPORATOR TYPE : Shell & Tube MOTOR SIZE / QTY : 1.5 kW/ 6#

EVAPORATOR CODE / QTY : DH2-211 / 1# CONDENSER COIL


42x78 / 3R/ 12FPI / 6# (HI-X)Aluminum with Aeris-Coated Fins

MAIN POWER SUPPLY : 380V/3Ph/50Hz

Power input mentioned/provided here is at rated condition only, and should not be used for cable/fuse
selection. For MCA/MFA values (whenever required), please consult Engineering – Electrical

SKM Air Conditioning LLC


P.O.Box: 6004, Sharjah Email : skm.sales@skmaircon.com
Tel : +971 6 5143333, Fax : +971 6 5143300 Visit us at www.skmaircon.com
HEATING MODE
APCL 5055-CHPM (Heating mode)
Cap: 167.23 kW (@ -5 ºC ambient)
Comp PI : 64.2 kW
Water Flow Rate : Same as in cooling mode
Inlet temp : 39.5 °C
Outlet temp : 45.0 °C
PRELIMINARY DRG.
A1 A3 UNIT TAG: BDV-SPO-CEG-01

A2 A4

88.27 152.08
[2242] [3863]
1 2 5

VENTILATION FAN
& FILTER WITH
HOSE PROOF HOOD

FILTERED
VENTILATION WITH
HOSE PROOF HOOD
[2320]
91.35

CABLE ENTRY

CH.W.IN CH.W.OUT
3 6 4 RIGGING HOLES
4x Ø7/8 [22]

ALL DIMENSIONS ARE IN INCHES [MM]

TITLE EQUIPMENT LAYOUT SKM Airconditioning LLC


POST BOX No: 6004, SHARJAH, U.A.E.
AIR CONDITIONING EQUIPMENT TEL : +971 6 514 3333 , FAX : +971 6 514 3300
6- SUCTION ACCUMULATOR MODEL APCL5055CHPM
5- CONTROL PANEL
NAME SIGN DATE
JOB No. - QTY. - SCALE 1:40
4- EVAPORATOR
3- COMPRESSOR
DESIGNED KENUS 11.09.2017 CLIENT
DRAWN LV 11.09.2017
2- CONDENSER COIL PROJECT Security camp OUED ZINE for Touat gas Devlopment
P1 18.01.18 LV FAN MODEL & UNIT HEIGHT CHANGED. 1- CONDENSER FAN E.CHECKED
REV. DATE NAME REMARKS LEGEND APPROVED DRG. No. M7417008 REV. P1 SHEET 1 / 1
Air Cooled Chillers
APCL-5015HPM
CUSTOMER SALES ENGINEER
PROJECT SECURITY CAMP OUED ZINE FOR TOUAT GAS DATE
UNIT TAG BDV-SPO-CEG-02

PERFORMANCE DATA

COOLING CAPACITY : 43.8 kW LEAVING WATER TEMPERATURE : 6.0 ºC

COMPRESSOR POWER INPUT : 21.40 kW WATER TEMPERATURE DROP : 5.0 ºC

TOTAL PI (Comps. + Cond. motors) : 24.62 kW WATER FLOW RATE : 1.936 l/s

WATER PRESSURE DROP : 31.89 kpa

AMBIENT TEMPERATURE : 51.0 ºC REFRIGERANT : R-407C

EVAPORATOR FOULING FACTOR : 0.018 m2ºC/kW REFRIGERANT CIRCUITS : 1

ALTITUDE, above sea level : 320 m

SPECIFICATIONS

COMPRESSOR CONDENSER FAN


COMPRESSOR TYPE : Hermetic Scroll FAN TYPE : Direct Driven Propeller
COMP 1 CODE / QTY : ZR125KCE / 2#
FAN CODE / QTY : MW800/38.5/5 / 2#

CAPACITY STEPS : 100-50-0 CONDENSER MOTOR


EVAPORATOR MOTOR TYPE : EC motor- TEAO, Class F, 6-Pole, IP-55

EVAPORATOR TYPE : Shell & Tube MOTOR SIZE / QTY : 1.5 kW/ 2#

EVAPORATOR CODE / QTY : DH1-144/ 1# CONDENSER COIL


42x78 / 2R/ 12FPI /2# (HI-X)Aluminum with Aeris-Coated Fins

MAIN POWER SUPPLY : 380V/3Ph/50Hz

Power input mentioned/provided here is at rated condition only, and should not be used for cable/fuse
selection. For MCA/MFA values (whenever required), please consult Engineering – Electrical

SKM Air Conditioning LLC


P.O.Box: 6004, Sharjah Email : skm.sales@skmaircon.com
Tel : +971 6 5143333, Fax : +971 6 5143300 Visit us at www.skmaircon.com
HEATING MODE
APCL 5015-CHPM (Heating mode)
Cap: 50.33 kW (@ -5 ºC ambient)
Comp PI : 18.24 kW
Water Flow Rate : Same as in cooling mode
Inlet temp : 38.7 °C
Outlet temp : 45.0 °C
PRELIMINARY DRG.
UNIT TAG: BDV-SPO-CEG-02

10 68.27 10
[254] [1734] [254]

A1 A3

A2 A4

88.27 61.02
[2242] [1550]
1 2 5

SUNSHADE & RAIN HOOD

VENTILATION FAN
& FILTER WITH
HOSE PROOF HOOD

FILTERED
VENTILATION WITH
[2406]
94.72

HOSE PROOF HOOD

CABLE ENTRY

C.W. IN C.W. OUT RIGGING HOLES 4 6 3


[MPT 2''] [MPT 2''] 4 x Ø1 [25.4]

ALL DIMENSIONS ARE IN INCHES [MM]

TITLE EQUIPMENT LAYOUT SKM Airconditioning LLC


POST BOX No: 6004, SHARJAH, U.A.E.
AIR CONDITIONING EQUIPMENT TEL : +971 6 514 3333 , FAX : +971 6 514 3300
6- SUCTION ACCUMULATOR MODEL APCL5015HPM
5- CONTROL PANEL
NAME SIGN DATE
JOB No. - QTY. - SCALE 1:40
4- EVAPORATOR
3- COMPRESSOR
DESIGNED KENUS 22.05.2018 CLIENT
DRAWN LV 22.05.2018
2- CONDENSER COIL PROJECT Security camp OUED ZINE for Touat gas Devlopment
1- CONDENSER FAN E.CHECKED
REV. DATE NAME REMARKS LEGEND APPROVED DRG. No. M7418004 REV. - SHEET 1 / 1
Air Cooled Chillers
APCL5040CM
CUSTOMER SALES ENGINEER
PROJECT SECURITY CAMP OUED ZINE FOR TOUAT GAS DATE
UNIT TAG BDV-FPS-CEG-01

PERFORMANCE DATA

COOLING CAPACITY : 106.5 kW LEAVING WATER TEMPERATURE : 6.0 ºC

COMPRESSOR POWER INPUT : 59.40 kW WATER TEMPERATURE DROP : 5.0 ºC

TOTAL PI (Comps. + Cond. motors) : 65.84 kW WATER FLOW RATE : 5.090 l/s

WATER PRESSURE DROP : 26.97 kpa

AMBIENT TEMPERATURE : 51.0 ºC REFRIGERANT : R-407C

EVAPORATOR FOULING FACTOR : 0.018 m2ºC/kW REFRIGERANT CIRCUITS : 1

ALTITUDE, above sea level : 320 m

SPECIFICATIONS

COMPRESSOR CONDENSER FAN


COMPRESSOR TYPE : Hermetic Scroll FAN TYPE : Direct Driven Propeller
COMP 1 CODE / QTY : ZR380KCE / 1#
COMP 2 CODE / QTY : ZR310KCE / 1# FAN CODE / QTY : MW800/38.5/5 / 4#

CAPACITY STEPS : 100-55-0 CONDENSER MOTOR


EVAPORATOR MOTOR TYPE : TEAO, Class F, 6-Pole, IP-55

EVAPORATOR TYPE : Shell & Tube MOTOR SIZE / QTY : 1.5 kW/ 4#

EVAPORATOR CODE / QTY : DH1-192 / 1# CONDENSER COIL


42x78 / 3R/ 12FPI / 4# (HI-X)Aluminum with Aeris-Coated Fins

MAIN POWER SUPPLY : 380V/3Ph/50Hz

Power input mentioned/provided here is at rated condition only, and should not be used for cable/fuse
selection. For MCA/MFA values (whenever required), please consult Engineering – Electrical

SKM Air Conditioning LLC


P.O.Box: 6004, Sharjah Email : skm.sales@skmaircon.com
Tel : +971 6 5143333, Fax : +971 6 5143300 Visit us at www.skmaircon.com
PRELIMINARY DRG.
UNIT TAG: BDV-FPS-CEG-01
A1 A3

A2 A4

88.27 105.98
[2242] [2692]
1 2 5

VENTILATION FAN
& FILTER WITH
HOSE PROOF HOOD

FILTERED
VENTILATION WITH
HOSE PROOF HOOD
[2320]
91.35

CABLE ENTRY

C.W. IN C.W. OUT


3 4 RIGGING HOLES
4x Ø7/8 [22]
ALL DIMENSIONS ARE IN INCHES [MM]

TITLE EQUIPMENT LAYOUT SKM Airconditioning LLC


POST BOX No: 6004, SHARJAH, U.A.E.
AIR CONDITIONING EQUIPMENT TEL : +971 6 514 3333 , FAX : +971 6 514 3300
MODEL APCL5040CM
5- CONTROL PANEL
NAME SIGN DATE
JOB No. - QTY. - SCALE 1:40
4- EVAPORATOR
3- COMPRESSOR
DESIGNED KENUS 22.03.2018 CLIENT
DRAWN LV 22.03.2018
2- CONDENSER COIL PROJECT Security camp OUED ZINE for Touat gas Devlopment
1- CONDENSER FAN E.CHECKED
REV. DATE NAME REMARKS LEGEND APPROVED DRG. No. M7418002 REV. - SHEET 1 / 1
Partie 1

1-Concernant le commentaire de DOL Direct on line et du démarreur progressive Soft Start


Compresseur.

Veuillez noter que les deux compresseurs résultent à un fonctionnement à pleine vitesse. Il
ne fonctionnera pas à vitesse variable.

• DOL atteindra 50 HZ après 2 minutes. Les chiller avec des compresseurs scroll
contiennent plusieurs compresseur et leur démarrage est temporiser.
• Le démarreur SOFT ou progressive atteindra 50 Hz en 5 à 10 minutes en raison de
l'utilisation du module électronique VFD qui augmentera la fréquence par étapes
jusqu'à ce que les compresseurs atteignent les 50 Hz et leur vitesse opérationnel.
• Vous devez savoir que la variation de fréquence est seulement au démarrage;
• Ce compresseur ne fonctionnera pas avec une fréquence variable une fois démarré.
• Conclusion les deux compresseurs ont le même résultat.

Avantage:

Le démarreur progressif utilisera Amp de 2 à 30 Amp a 46 DC MAX , puis restera dans la


même Ampère il est utilisé dans pour les grand chiller a VIS + 100 Amp pas les scroll qui ont
un petit ampérage.

Inconvénient:

Cette variation de fréquence est assurée par des relais électronique VFD a caractéristiques
température ambiante limitée conçu pour 35 à 46 Dc MAX concernant les scroll de série

A ne pas confondre avec Ci-dessous:

1- Dans les industries de détente directe 'expansion directe DX VRV ou VRF, le système
est basé sur la circulation du fluide frigorigène de l'unité de condensation vers le
ventilo-convecteur terminal comme le split domestique standard. Les fabricants
utilisent des compresseurs à débit variable appelés inverter ou DIGITAL SCROLL.
Possible de les utiliser a 41 DC pour des PAC mais très déconseillée.

2- Pour votre Information, Le fondateur du VRV a était dans l’obligation d’assure un


système de refroidissement externe dans l'unité de condensation pour refroidir les
relais des VFD qui causer des pannes dans les hautes températures.

3- Pourquoi il a fait ça ? car cette fonctionnalité est obligatoire dans les systèmes à
détente DX VFD et VRV car le compresseur fonctionne avec une vitesse variable et
non seulement au démarrage mais tout le temps.

4- Notre Scope et domaine d'application est Chiller PAC HP pour 51 DC et avec


compresseurs Scroll. Selon le BOQ et notre award.
• Dans le système d'eau glacée, les étages de capacité du refroidisseur sont assurés par
d'autres technologies comme ci-dessous.

 Une fois que le compresseur fonctionne à pleine fréquence signifie démarrage


progressif ou DOL, les étages de capacité sont assurés comme ci-dessous.
 Tous les ventilateurs de condensateurs sont VFD voir submittal, auto master pour
SKM
 cela signifie que la capacité du condenseur est modulée selon le système et en
utilisant des régulateurs de capteurs de pression / températures
 La soupape de détente électronique jouera dans le flux de réfrigérant en modulant
l'orifice de la soupape de détente.
 Cela réduira la capacité et assurera une charge partielle.
 Débit variable par détendeurs électronique.
 Autre procéder sont confidentiel
 C'est ainsi que les refroidisseurs PAC chiller assureront de nombreuses capacités,
comme déjà fait par SKM pour ce projet et clairement montré dans les sélections et
la feuille de résumé.
 SKM utilise comme STD dans tous les refroidisseurs Chiller ou PAC.

Comment puis-je confirmer cela en utilisant la sélection autre fabricant ?. Cela avec tous le
respect et afin de vous démontrée par un autre fabricant.

 Sélection d'un concurrent professionnel en utilisant des compresseurs de démarreur


progressif limités à 46 Dc pour PAC et 51Dc froid seul déclarer par le fabricant même.
 Joint le détails de cette PAC mêmes étapes de capacités du refroidisseur. 22-44-72-
100%.
 Aucun fabricant HVAC au monde ne fait des PAC INVERTER pour 51 DC car il Ya pas
de compresseur qui couvre ça

Conclusion

• Le démarreur progressif n'a aucune relation avec les capacités. Il s'agit d'une option
électrique pour le démarrage du compresseur uniquement.

 Ceci est pour confirmer que l'option de compresseur de démarreur progressif n'a
aucun effet dans les étages de capacité des refroidisseurs GEG PAC.

 Cette option est important pour les GEG à vis ou les ampérages arrive a 100 Amp
notre scope est scroll avec des intensités faibles Amp

Pourquoi SKM utilise DOL?

- Parce que SKM offre une solution correcte de conception de refroidisseurs pour 51
DC et plus et capable de travailler à 55 Dc ++
- SKM utilise des compresseurs Copeland USA avec des spécifications spéciaux
attachés à l'enveloppe du compresseur utilisé.
- Voir les compresseurs SKM utilisés pour le projet GTG pour voir l'enveloppe de
température.

J'espère que ce courrier clarifie les compresseurs DOL / VS / Soft starter

Partie 2
2-Équilibrage hydraulique et charge partielle. Circuit primaire seulement ou primaire
secondaire
système hydraulique .

Comment assurer un système hydraulique équilibré en utilisant un seul circuit pour éviter
tout travail supplémentaire et économiser les accumulateurs les ballons et l’espace et des
réservoirs secondaires +++ ??? avec une PAC sans compresseur inverter 51DC

Besoin d'avoir un calcul de charge précis avec charge partielle puis de simuler le
nombre de refroidisseurs et ses étapes de capacités.
Exemple pour bâtiment ADM avec 2 refroidisseurs, chaque refroidisseur a 28-50-78-
100% de capacité (SKM PAC)
Conclusion : vos refroidisseurs peuvent fournir: 14-28-25-50-37-78-100%.
Besoin de comparer avec le calcul de la charge Min/MAX puis de donner des
instructions claires à la compagnie lot régulation GTC partenaire.
Ensuite, si les capacités des PAC coïncident avec les charges vous pouvez aller circuit
primaire seulement
Si les puissances ne coïncident pas avec les PAC 'il est indispensable de faire deux
circuit et équilibrer le système avec le système secondaire.

• Encore une fois c'est parce que nous utilisons une PAC pompe à chaleur avec des
compresseurs Scroll 51 DC Ce n'est pas un système DX.
• Avec une philosophie que je déconseille celle des régulations par 2T
• Mon conseille est de partir pour le 3T car les pompes à vitesse variable utilisent des
VFD très vulnérable au haute température et fluctuation de courant très fréquente
au sud.
• Il faut climatiser les locaux des pompes.

A ne pas confondre.

Dans les industries des refroidisseurs Chillers, il existe des chiller à vis et des chiller
centrifuges qui fonctionnent en mode froid seul.

Pas moyen d'avoir cette technologie en pompe à chaleur. Pour ces Mega chiller l’option soft
Start est impérative et de série chez SKM.

Il est possible d'avoir une source d'eau chaude à partir des condenseurs de chiller
fonctionnent en Mode FROID comme dans la spec de DAH.
Si c’est le cas dite nous ?
Cela signifie que nous pouvons créer un système hydraulique pour distribuer l'eau chaude
come préciser dans les synoptique spécifications du projet. de l’appel d'offres DAH.

Oui En même temps produire de l’eau glacer et eau chaude pour les cassette 4 tube Mis
saison ou autres besoins. Nous savons faire et nous l’avons fait plusieurs fois ??

Mais encore une fois ce n'est pas la pompe à chaleur comme demander dans les BPU.

A toutes fin utile si jamais DAH veut ça ?

• SKM a fournie des GEG froid seul compresseur scroll avec génération eau chaude des
condenseur Photo attachée.

• S'il vous plaît voir la feuille DAH dans le même système, ils décrivent SCROLL ensuite
VIS ensuite chauffage par condenseur?

• Es qu’ils veulent compresseur vis eau chaude du condenseur ou le Quantitatif a était


changer ?

OU utiliser cette technologie? ............ Vis centrifuge

• Cette technologie est pour des projets énormes comme pour les refroidisseurs GEG à vis
SKM peuvent atteindre 1,825 KW
• Le groupe centrifuge SKM atteint 9,450 kW.
• http://www.skmaircon.com/catalogues_new/APCY-H.pdf 1.825 KW
• http://www.skmaircon.com/catalogues_new/centrifugal-water-chiller.pdf 9.450 KW.