G.T.P
For Maintained
I. General
1 Manufacturer
2 Country of manufacture
20.2 Insulation
20.3 Power frequency withstand voltage kV(rms) 70
20.4 Rated lightning, impulse withstand kV(peak) 170
voltage
21 LV Windings
21.1 Material, wire or strip Copper wire/strip
21.2 Insulation
21.3 Power frequency withstand voltage kV(rms) 3
32 Secondary
32.1 Manufacturer
32.2 Type (DIN type or eqvt.) Yes
32.3 rated current A 1000
32.4 power frequency test level (at 1000 kV,min 8
m)
32.5 lightning impulse level (at 1000 m) kV
32.6 clearance across insulator mm 60
32.7 creep age distance mm
32.8 Metal oxide Lightning Arrestor kV,kA 18,12
V. Tests
33 Routine tests: IEC 60076 and on each unit
Specifications
34 Separate source over-voltage on each unit
withstand test
35 Induced over voltage withstand test, on each unit
36 test voltage / primary (tap 1) (IEC kV Yes
test standard)
37 test voltage / secondary (IEC test kV Yes
standard)
38 Type tests: IEC 60076 and on one unit
Specifications
39 test voltage / full wave (IEC test kV Yes
standard)
40 test voltage / chopped wave (IEC test kV Yes
standard)
41 Heat-run test on one unit
42 Noise level at a measuring distance dB(A) <46
of 0.3meter
VI. Materials, Masses, Measures
and Drawings
43 Transformer tank, material steel
43.1 Transformer total mass kg
I. General
1 Manufacturer
2 Country of manufacture
20.2 Insulation
20.3 Power frequency withstand voltage kV(rms) 70
20.4 Rated lightning, impulse withstand kV(peak) 170
voltage
21 LV Windings
21.1 Material, wire or strip Copper wire/strip
21.2 Insulation
21.3 Power frequency withstand voltage kV(rms) 3
32 Secondary
32.1 Manufacturer
32.2 Type (DIN type or eqvt.) Yes
32.3 rated current A 1000
32.4 power frequency test level (at 1000 kV min. 3
m)
32.5 lightning impulse level (at 1000 m) kV
32.6 clearance across insulator mm 60
32.7 Min. creep age distance mm
32.8 Metal oxide Lightning Arrestor kV,kA 18,12
V. Tests
33 Routine tests: IEC 60076 and on each unit
Specifications
34 Separate source over-voltage on each unit
withstand test
35 Induced over voltage withstand test, on each unit
36 test voltage / primary (tap 1) (IEC kV Yes
test standard)
37 test voltage / secondary (IEC test kV Yes
standard)
38 Type tests: IEC 60076 and on one unit
Specifications
39 test voltage / full wave (IEC test kV Yes
standard)
40 test voltage / chopped wave (IEC test kV Yes
standard)
41 Heat-run test on one unit
42 Noise level at a measuring distance dB(A) <44
of 0.3meter
VI. Materials, Masses, Measures
and Drawings
43 Transformer tank, material steel
43.1 Transformer total mass kg
I. General
1 Manufacturer
2 Country of manufacture
20.2 Insulation
20.3 Power frequency withstand voltage kV(rms) 70
20.4 Rated lightning, impulse withstand kV(peak) 170
voltage
21 LV Windings
21.1 Material, wire or strip Copper wire/strip
21.2 Insulation
21.3 Power frequency withstand voltage kV(rms) 3
32 Secondary
32.1 Manufacturer
32.2 Type (DIN type or eqvt.) Yes
32.3 rated current A 1000
32.4 power frequency test level (at 1000 kV min. 3
m)
32.5 lightning impulse level (at 1000 m) kV
32.6 clearance across insulator mm 60
32.7 Min. creep age distance mm
32.8 Metal oxide Lightning Arrestor kV,kA 18,12
V. Tests
33 Routine tests: IEC 60076 and on each unit
Specifications
34 Separate source over-voltage on each unit
withstand test
35 Induced over voltage withstand test, on each unit
36 test voltage / primary (tap 1) (IEC kV Yes
test standard)
37 test voltage / secondary (IEC test kV Yes
standard)
38 Type tests: IEC 60076 and on one unit
Specifications
39 test voltage / full wave (IEC test kV Yes
standard)
40 test voltage / chopped wave (IEC test kV Yes
standard)
41 Heat-run test on one unit
42 Noise level at a measuring distance dB(A) <44
of 0.3meter
VI. Materials, Masses, Measures
and Drawings
43 Transformer tank, material Steel
43.1 Transformer total mass kg
I. General
1 Manufacturer
2 Country of manufacture
20.2 Insulation
20.3 Power frequency withstand voltage kV(rms) 70
21.2 Insulation
21.3 Power frequency withstand voltage kV(rms) 3
32 Secondary
32.1 Manufacturer
32.2 Type (DIN type or eqvt.) Yes
32.3 rated current A 1000
32.4 power frequency test level (at 1000 kV min. 3
m)
32.5 lightning impulse level (at 1000 m) kV
32.6 clearance across insulator mm 60
32.7 Minimum creep age distance mm
32.8 Metal oxide Lightning Arrestor kV,kA 18,12
V. Tests
33 Routine tests: IEC 60076 and on each unit
Specifications
34 Separate source over-voltage on each unit
withstand test
35 Induced over voltage withstand test, on each unit
36 test voltage / primary (tap 1) (IEC kV Yes
test standard)
37 test voltage / secondary (IEC test kV Yes
standard)
38 Type tests: IEC 60076 and on one unit
Specifications
39 test voltage / full wave (IEC test kV Yes
standard)
40 test voltage / chopped wave (IEC test kV Yes
standard)
41 Heat-run test on one unit
42 Noise level at a measuring distance dB(A) <46
of 0.3meter
VI. Materials, Masses, Measures
and Drawings
43 Transformer tank, material Steel
I. General
1 Manufacturer
2 Country of manufacture
20.2 Insulation
20.3 Power frequency withstand voltage kV(rms) 70
21.2 Insulation
21.3 Power frequency withstand voltage kV(rms) 3
32 Secondary
32.1 Manufacturer
32.2 Type (DIN type or eqvt.) Yes
32.3 rated current A 1000
32.4 power frequency test level (at 1000 kV min. 3
m)
32.5 lightning impulse level (at 1000 m) kV
32.6 clearance across insulator mm 60
32.7 Min. creep age distance mm
32.8 Metal oxide Lightning Arrestor kV,kA 18,12
V. Tests
33 Routine tests: IEC 60076 and on each unit
Specifications
34 Separate source over-voltage on each unit
withstand test
35 Induced over voltage withstand test, on each unit
36 test voltage / primary (tap 1) (IEC kV Yes
test standard)
37 test voltage / secondary (IEC test kV Yes
standard)
38 Type tests: IEC 60076 and on one unit
Specifications
39 test voltage / full wave (IEC test kV Yes
standard)
40 test voltage / chopped wave (IEC test kV Yes
standard)
41 Heat-run test on one unit
42 Noise level at a measuring distance dB(A) <44
of 0.3meter
VI. Materials, Masses, Measures
and Drawings
43 Transformer tank, material steel
I. General
1 Manufacturer
2 Country of manufacture
20.2 Insulation
20.3 Power frequency withstand voltage kV(rms) 70
21.2 Insulation
21.3 Power frequency withstand voltage kV(rms) 3
32 Secondary
32.1 Manufacturer
32.2 Type (DIN type or eqvt.) Yes
32.3 rated current A 1000
32.4 power frequency test level (at 1000 kV min. 3
m)
32.5 lightning impulse level (at 1000 m) kV
32.6 clearance across insulator mm 60
32.7 Min. creep age distance mm
32.8 Metal oxide Lightning Arrestor kV,kA 18,12
V. Tests
33 Routine tests: IEC 60076 and on each unit
Specifications
34 Separate source over-voltage on each unit
withstand test
35 Induced over voltage withstand test, on each unit
36 test voltage / primary (tap 1) (IEC kV Yes
test standard)
37 test voltage / secondary (IEC test kV Yes
standard)
38 Type tests: IEC 60076 and on one unit
Specifications
39 test voltage / full wave (IEC test kV Yes
standard)
40 test voltage / chopped wave (IEC test kV Yes
standard)
41 Heat-run test on one unit
42 Noise level at a measuring distance dB(A) <44
of 0.3meter
VI. Materials, Masses, Measures
and Drawings
I. General
1 Manufacturer
2 Country of manufacture
20.2 Insulation
20.3 Power frequency withstand voltage kV(rms) 70
21.2 Insulation
21.3 Power frequency withstand voltage kV(rms) 3
32 Secondary
32.1 Manufacturer
32.2 Type (DIN type or eqvt.) Yes
32.3 rated current A 800
32.4 power frequency test level (at 1000 kV min. 3
m)
32.5 lightning impulse level (at 1000 m) kV
32.6 clearance across insulator mm 60
32.7 Min. creep age distance mm
32.8 Metal oxide Lightning Arrestor kV,kA 18,12
V. Tests
33 Routine tests: IEC 60076 and on each unit
Specifications
34 Separate source over-voltage on each unit
withstand test
35 Induced over voltage withstand test, on each unit
36 test voltage / primary (tap 1) (IEC kV Yes
test standard)
37 test voltage / secondary (IEC test kV Yes
standard)
38 Type tests: IEC 60076 and on one unit
Specifications
39 test voltage / full wave (IEC test kV Yes
standard)
40 test voltage / chopped wave (IEC test kV Yes
standard)
41 Heat-run test on one unit
42 Noise level at a measuring distance dB(A) <44
of 0.3meter
VI. Materials, Masses, Measures
and Drawings
43 Transformer tank, material steel
I. General
1 Manufacturer
2 Country of manufacture
20.2 Insulation
20.3 Power frequency withstand voltage kV(rms) 70
20.4 Rated lightning, impulse withstand kV(peak) 170
voltage
21 LV Windings
21.1 Material, wire or strip
Copper wire/strip
21.2 Insulation
21.3 Power frequency withstand voltage kV(rms) 3
32 Secondary
32.1 Manufacturer
32.2 Type (DIN type or eqvt.) Yes
32.3 rated current A 1000
32.4 power frequency test level (at 1000 kV min. 3
m)
32.5 lightning impulse level (at 1000 m) kV
32.6 clearance across insulator mm 60
32.7 Min. creep age distance mm
32.8 Metal oxide Lightning Arrestor kV,kA 18,12
V. Tests
33 Routine tests: IEC 60076 and on each unit
Specifications
34 Separate source over-voltage on each unit
withstand test
35 Induced over voltage withstand test, on each unit
36 test voltage / primary (tap 1) (IEC kV Yes
test standard)
37 test voltage / secondary (IEC test kV Yes
standard)
38 Type tests: IEC 60076 and on one unit
Specifications
39 test voltage / full wave (IEC test kV Yes
standard)
40 test voltage / chopped wave (IEC test kV Yes
standard)
41 Heat-run test on one unit
42 Noise level at a measuring distance dB(A) <44
of 0.3meter
VI. Materials, Masses, Measures
and Drawings
43 Transformer tank, material steel
43.1 Transformer total mass kg
I. General
1 Manufacturer
2 Country of manufacture
20.2 Insulation
20.3 Power frequency withstand voltage kV(rms) 70
20.4 Rated lightning, impulse withstand kV(peak) 170
voltage
21 LV Windings
21.1 Material, wire or strip Copper wire/strip
21.2 Insulation
21.3 Power frequency withstand voltage kV(rms) 3
32 Secondary
32.1 Manufacturer
32.2 Type (DIN type or eqvt.) Yes
32.3 rated current A 1250
32.4 power frequency test level (at 1000 kV min. 3
m)
32.5 lightning impulse level (at 1000 m) kV
32.6 clearance across insulator mm 60
32.7 Minimum creep age distance mm
32.8 Metal oxide Lightning Arrestor kV,kA 18,12
V. Tests
33 Routine tests: IEC 60076 and on each unit
Specifications
34 Separate source over-voltage on each unit
withstand test
35 Induced over voltage withstand test, on each unit
36 test voltage / primary (tap 1) (IEC kV Yes
test standard)
37 test voltage / secondary (IEC test kV Yes
standard)
38 Type tests: IEC 60076 and on one unit
Specifications
39 test voltage / full wave (IEC test kV Yes
standard)
40 test voltage / chopped wave (IEC test kV Yes
standard)
41 Heat-run test on one unit
42 Noise level at a measuring distance dB(A) <44
of 0.3meter
VI. Materials, Masses, Measures
and Drawings
43 Transformer tank, material steel
43.1 Transformer total mass kg
I. General
1 Manufacturer
2 Country of manufacture