Gas fired room sealed fan assisted
combination boiler
with integrated 15 litre power store
GB
Table of Contents
Page Page
12
1
11 2
11
11
o
C
VRC-VC
o
I
C
10
3
8
4
7
5
1 1 Boiler
2 1 Flue restriction ring
3 1 Controls cover door
4 1 Lower cover plate (packed in bottom
packaging)
5 1 Cold water inlet valve
6 3 Flow and return service value, gas service
valve
7 5 Copper tails for gas and water pipework
8 1 Template
9 2 Guarantee Card and Benchmark log book
10 1 Installation and connection accessories and
PRV packages incl. DHW outlet union nut
11 3 Installation and Servicing, Users and Flue
Installation Instructions
12 1 Hanging bracket
3 Boiler Specification
3.1 Technical data
Key: Key:
1 Heating system return (22 mm tail) 1 Air duct
2 Cold water connection with shut off valve (15 mm 2 Fan
tail) 3 Power store
3 Gas connection (22 mm tail) 4 Main heat exchanger
4 Hot water connection (15 mm tail) 5 Temperature sensor (NTC I)
5 Heating system flow (22 mm tail) 6 Temperature sensor (NTC III)
6 Flue outlet (100 mm flue with turret) 7 Diverter valve
7 Hanging bracket 8 DHW pressure relief valve
9 Temperature sensor (NTC IV)
10 DHW heat exchanger
11 DHW expansion vessel
12 DHW pump
6 13 Automatic bypass valve
122
310
180
1 30
3
29
4 28
6 27
8 26
25
9 24
10 23
11
22
21
12 20
13
19
14 18
15 17
16
70
750
15
48
70
4
603
48
C Below eaves 25
650
If the nominal capacity of the built in expansion vessel is
Lift [mbar]
600
450
additional expansion vessel can be installed external to 400
Part 1. 200
50
0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700
Clearances required
Mount the boiler on a flat and vertical area of wall of
sufficient area for the boiler plus the required
5 5 500
clearances for installation and servicing.
The clearances are as detailed below and are shown on
the installation template supplied with the boiler:
Note: If the boiler is to be fitted in a timber framed Fig. 5.2: Free space required for installation
building, it should be fitted in accordance with Institute
of Gas Engineers Publication IGE/UP/7/1998 "Guide for
Gas Installations in Timber Framed Dwellings". 5.1.2 Selecting position of boiler
Refer to "Boiler location" for information regarding
siting the appliance. In general the boiler must be
positioned such that:
497
> 210
- The position of the connections.
- The position of the flue exit hole.
122
- Upper hole (2) indicates top outlet flue with flue
turret facing rearward. 5 30,5 5
780
Mark the centre of the selected air/flue duct and its
circumference, e.g. by drilling through the template.
08/2001
124175 GB
5.3 Fitting the boiler hanging bracket 5.6 Removing boiler casing
Fix the hanging bracket (2) to the wall using the fixings
supplied. (it may be necessary to use additional or • Turn both securing fasteners (1) anti-clockwise by 90°
alternative fixings to ensure adequate support). to release control panel (2).
• Pull the case (3) forward at the bottom to disengage
Note: If the boiler is to be fitted in a timber framed from the securing clips.
building ensure that the bracket is secured to a • Lift the case slightly to clear the top locations and
substantial part of the timber frame capable of taking pull forward to remove.
the weight of the boiler.
90° 90°
2
VRC-VC 1
I
0
3 2
I
0
3
5.5 Fitting the boiler
Fig. 5.5: Remove of boiler casing
• Lift the boiler (3) up to the wall so that it is slightly
above the hanging bracket (1).
5.7 Gas supply 5.8 Cold water mains inlet and hot water outlet
Flush all foreign matter from the mains supply before
• Connect the 15 mm compression gas service cock (1) connecting to the boiler.
and 22 mm copper outlet tail (3) as supplied with the
appliance (2) and tighten. • Connect the cold water service valve (1) to the cold
• Connect a gas supply pipe of not less than 22 mm inlet water connection (3) of the appliance with the
diameter to the copper tail. washer (2) provided and tighten.
• Tighten all connections. • Connect the 15 mm cold water inlet pipe copper tail
(Ensure the gas supply pipework is adequately sized (4) to the cold water service valve (1) and tighten.
such that a 20 mbar gas pressure is available at the • Connect the 15 mm hot water outlet copper tail (6) to
boiler inlet at full flow rate). the hot water outlet connection of the appliance (8)
with the washer provided (7) and tighten.
Note: The hot water outlet union nut is packed in
with the PRV fitting pack.
• Connect the cold water service pipe and hot water
outlet pipework to the copper tails.
I
0
I
0
4
1
6
1
2
7
2
3
5.9 Central heating flow and return pipework 5.10 Connect the flue system to the boiler
Before connecting the heating circuit to the boiler
appliance, all pipework and radiators must be • Refer to separate air/flue duct installation instructions
thoroughly flushed to remove any installation debris. included with the boiler.
I
0
3
6
7
8
The boiler is supplied for connection to 230 V, ~ 50 Hz • Lower the control panel.
supply fused at 3 A rating. • Unclip the terminal box cover (1) from the control
panel (2).
Connection to the mains supply shall be made via a • Feed the power supply cord in to the appliance as
fused 3 pin plug to an unswitched shuttered socket, shown (Fig 5.10).
both complying to the requirements of BS1363. • Use cable clamps.
• Connect the power supply cord as follows (Fig. 5.11, on
(Alternatively, connection may be made via a 3 A fused page 20).
double pole isolator having a contact separation of at Green/yellow (earth) wire boiler terminal Earth sign
least 3 mm in all poles and supplying the boiler and Blue (neutral) wire boiler terminal N
controls only). Brown (live) wire boiler terminal L
The point of connection to the mains supply must allow Note: DO NOT use boiler terminal connections 7-8-9.
complete electrical isolation of the boiler and its
ancillary controls. It should be readily accessible and
adjacent to the boiler. A 3 core flexible cord according • Refit the terminal box cover by pushing into place
to BS6500 tables 6, 8 or 16 (3 x 0.75 to 3 x 1.5 mm2) until it clips back into position.
should be used. • Raise the control panel and secure in place.
7 8 9 L N 3 4 5
RT 24V 230V RT 230V
F3
7 8 9
24V
Do not use!
L N
3 4 5
F1
Fig. 5.11: Connection wiring
L N 1 2 3 4
Switchmaster
SM300
L N 4 3
Important: The arrowed numbers indicate connection ACL Drayton L N 1 2 A B C 3 4
Switchmaster 980
into the relevant terminal in the boiler terminal strip. L N 4 3
Danfoss Randall 1 2 3 6 5 E
103 Series
ACL Drayton L N 1 2 3 4 4 3 L N E
Lyfestyle PT271, PT371 Danfoss Randall L N E 1 2 3 4 5 6
Set 1E, TS975
L N 3 4
L N E 4 3
ACL Drayton 1 2 3
Digistat 2, 3, 4 Danfoss Randall L N 1 2 3 4
TS715
3 4
L N 3 4
ACL Drayton L N 1 2 3
Digistat RF - SCR Receiver Grässlin Towerchron L N 1 2 3 4
QE1, QM1
L N 3 4
L N 3 4
Danfoss Randall 3 2 1 Honeywell L N 1 2 3 4
TP4, TP5, TP5E ST610A, ST6100C
4 3 L N 3 4
3 4 Sunvic L N 1 2 3 4
Select 107
Landis & Staefa L L1
REV 11, REV 15, REV 22 L N 3 4
3 4
Smiths Timeguard L N 3 4 Fig. 5.13 Connection details for time switch
ProgramaSTAT PRT11, PRT17
L N 3 4
Sunvic 1 2 3
Upon completion of all electrical connections refit the
TLX 6501
3 4
terminal box cover by pushing into place. The cover is
Sunvic L N 1 2 3 4
secured by two locking clips.
TLX RFP, TLX RFD
L N 3 4
Vaillant 3 4 5
VRT 220, 230
3 4 5
6 Commissioning Part I
6.1 Preliminary electrical checks
Check the electrical installation by carrying out short
circuit, earth continuity and resistance to earth tests
and a check for correct polarity.
Warning!
The plastic cap (2)must be fitted for the gas
valve assembly to function correctly.
10
Warning!
The main burner pressure must be rechecked
after adjusting the ignition rate.
Warning!
DO NOT open any hot water tap while carrying
out this procedure.
Fig. 7.5: Using nozzle pressure to check and adjust the heating
system partial load
Note! Following adjustment of the central heating 5 After setting, press and hold the "i" button for five
output, the new output can be checked using the gas seconds or until the display stops flashing. The new
rate table as detailed. setting value is now memorised. The new main burner
pressure can now be checked. If the new output is not
correct repeat steps 3 to 5.
1 Simultaneously press the "i" and "+" buttons keys.
~5s
L.P.G. 3+ Burner pressure1) [mbar] for G30 2.8 2.8 3.5 5.9 7.3 8.9 12.6 16.8 19.1 22.9 28.2
Natural gas 2H Gas rate1) [m3/h] for G20 1.3 1.4 1.9 2.2 2.4 2.8 3.3 3.5 3.9 4.3
1)
15 °C, 1013 mbar, dry
2)
The nozzles are stamped with the mark shown in this table. The
marking corresponds to the nozzle hole diameter multiplied by 100.
• Carefully push case (1) onto the boiler such that the
locating points either side at the top of the boiler
engage. Push the casing onto the securing clips at the
bottom of the boiler.
• Close control panel (2).
• Secure control panel by turning both securing
fasteners (3) clockwise by 90°.
• Close front door (4).
• Open the punch-out holes in the cover panel (6) for
the pipework installation.
• Fit the bottom cover (6).
1
2
90¡ 90¡
VRC-VC 3
I
8 Functional checks (Commissioning This appliance is fitted with a display unit that uses
Part III) symbols to show the current operating status of the
boiler. Additionally to this the status of the boiler can be
checked using the Status Mode.
8.1 Functional checks
Once the unit has been installed and the gas supply has
been checked, operate the system to ensure that it is 8.2 Hot-water supply
working correctly.
• Activate the system.
• Operate the system, following the operating • Fully open one of the hot water taps in the system.
instructions supplied with the boiler. • Press the ”i“ key.
• Check the system for water leaks and escaping gas.
• Check that the flue has been correctly installed, Status code “S.14” appears on the display to indicate
according to the fitting instructions supplied with the that the hot-water supply is functioning correctly.
flue assembly.
• Check the burner for correct ignition and flame
picture.
• Check the hot water system for correct operation.
• Check the heating system for correct operation.
I
0
Leave the user instructions, the boiler log book and the
installation and servicing instructions with the user. Before commencing any servicing or maintenance work,
carry out an initial inspection of the system as follows:
Note: Leave the Benchmark Log Book with the end user.
• Inspect the flue, pipework and electrical connections
for indications of damage or deterioration.
• Inspect the air supply and ventilation arrangements of
8.8 Anti legionella protection the installation.
Advise the user that if the power store is turned off or • Check the heating and water system, in particular the
if the domestic hot water thermostat is at a low setting condition of radiator valves, evidence of leakage from
the boiler will operate daily to charge the store and the heating system and dripping hot water taps.
protect against legionella (the power store is turned off
during production). 9.2 Functional check of boiler operation
Note: Very hot water will be discharged during tapping • Carry out a functional check of the boiler operation as
after this operation. prevoiusly detailed.
• Remove the appliance casing as detailed on page 15
and operate the boiler by fully opening a hot water
tap. Inspect the burner operation through the viewing
window. Check that the flames are evenly covering the
surface of the burner. Inspect for signs of excessive
flame lift or sooting.
10 Fault finding 8 7
10.1 Introduction
The aquaPLUS boilers have an inbuilt advanced
multifunction diagnostic display to assist with fault
finding in the unlikely event of a boiler malfunction.
The display features the following four modes:
Normal Mode 1 2 3 4 5 6
Under normal conditions the boiler display will show the
boiler flow temperature, this indicates that the boiler is
operating correctly after an internal self check. o
C
Status Mode
The status display is helpful in diagnosing faults where a o
C
VRC-VC
Diagnostic Mode
In order to assist with the pinpointing of a particular
fault it is possible to use the boiler display in a
diagnostic mode to interrogate the boiler about the
status of certain components. Fig. 10.1: Display indications
Fault Mode
Should a fault develop in the boiler the display will show 10.2 Logical fault finding procedure
a fault code indicating what the problem may be. These checks must be carried out before attempting to
use the fault finding guide.
Display key:
1. Carry out electrical safety checks (See Section
1 Fan speed malfunction ‘Preliminary Electrical Checks’).
2 Heating demand 2.Check that the external electricity supply to the boiler
3 Hot-water demand is on, and a supply of 230 V~ is present between
4 Power store on (Comfort mode) boiler terminals ‘L’ and ‘N’.
5 Pump on 3. Check that the gas supply to the boiler is on, that it
6 Gas valve on has been correctly purged and that an inlet pressure
7 Actual Heating-system flow temperature (e.g. 50 °C) of 20 mbar is available at the gas valve. (See Section
or ‘Gas Supply’).
Displaying of a status/error code 4.Ensure the heating system is full of water and
8 Correct burner operation (normal flame) or charged to between 1 and 1.5 bar. If not, refill and vent
lock out (crossed-out flame) the system. (See Section ‘Filling the heating system’).
Ensure boiler flow and return service valves are open.
5.Check that the main on/off control is set to the ‘on’
position.
6.Set the central heating temperature to maximum.
7. Set the domestic hot water temperature to maximum.
8.Check that all external controls are on and calling for
heat (if, no external controls are fitted, boiler
terminals 3 and 4 must be linked). Check that the
boiler anti-cycling economiser is not engaged.
10.2.1 Procedure
mode mode
Diagnostic mode Press the "i" and "+" Press the "i" and "+"
10.3 Status Mode To cancel the status code mode proceed as follows:
The status mode provides information about the current
operating status of the boiler. • Press the "i" button below the display
To display status mode proceed as follows: or
• Do not press any key for approximately four minutes.
• Press the "i" button below the display, and a status The display will now revert back to showing the
code will appear in the display indicating the current current flow temperature.
operational status of the boiler (see table below).
Display Indication
S.15 Fan and water pump over run (hot water operation)
S.32 Main heat exchanger anti freeze protection due to fan speed deviation too great
S.33 Check air/flue system
S.54 Delay mode due to flow temperature gradient too steep (approx 10 mins.)
10.4 Diagnostic Modes • If necessary, you can now alter the value by pressing
In order to assist with the pinpointing of a particular "+" or "-" buttons. (When altering values display will
fault it is possible to use the boiler display in a flash). Press and hold the "i" button to save the value
diagnostic mode to interrogate the boiler about the to memory, when the value is saved the display will
status of certain components. stop flashing.
• Press the "i" and "+" buttons below the display Diagnosic mode is cancelled as follows:
simultaneously. The display will now show "d.00".
• Use "+" or "-" buttons to scroll up or down to the • Press the "i" and "+" buttons simultaneously
desired diagnosic number. or
• Press "i" button to display the corresponding • Do not press any key for approximately four minutes.
diagnosic information. The display will now revert back to showing the
current flow temperature.
flow temperature
d.71 Maximum target value for heating system flow 0 = 82 ° C, 1 = 87 °C (factory-adjustment: 82 °C)
temperature
d.72 Pump over run time after filling hot water store 0, 1, 2, .....250 s (factory-adjustment: 80 s)
d.76 Gas type set H36 (nat gas) P36 (LPG) E36 (E+gas).
10.5 Fault codes • Use the "+" button to scroll back through the list of
Fault codes take priority over all other display functions memorised errors.
in the event of a system fault occurring. To cancel fault error memory display mode, proceed as
If multiple faults occur, the corresponding fault codes follows:
are displayed alternately for about two seconds each.
• Press the "i" button below the display.
10.6 Fault memory or
The fault memory stores detalis of the ten most recent • Do not touch any key for about four minutes. The
faults. display will now revert back to showing the current
• Press the "i" and "-" buttons simultaneously. flow temperature.
No
Yes Yes
No Yes
Yes No
Replace fuse F1
Yes
No No
No
43
44
Check central heating and controls Sheet C
No No
Does ignition
Is 230 VAC present across terminals 4 and 5 Yes Disconnect built in timer (if fitted)
commence?
No Yes
No No No
Check diagnostic code D.24 Check status code Check electrodes and
electrode leads.
(see page 39) equal 1? (see page 38) is S.33?
Replace as necessary.
Yes Yes
No
No
45
46
Check gas valve and central heating system pressure Sheet E
Does burner light 1st Is burner indicator Does burner shut down after
Yes Yes No Go to sheet F
attempt? illuminated? approx. 15 secs.
10 Fault finding
No No Yes
Check flame
Does burner light within 3
No Reset boiler rectification lead and Does status code (see page 38)
ignition attempts?
electrode
show S. 53?
Yes
Yes
Yes
Check burner pressure
Check pump is running?
settings are correct
No
Does burner light?
Yes
Yes
47
48
Check D.H.W operation Sheet G
No
No
Check cold water inlet is fully open
and adjustment is at maximum
flow rate
Go to sheet B/C/E or F
No
11 Diagrams
11.1 Functional Flow diagram: aquaPLUS VUI 362-7
CONTROL BOX
MAIN SWITCH
F2A
L N
2 1
Central heating
demand indicator
Burner lock out
indicator
Ignition indicator
MAIN
Hot water
demand indicator TRANSFORMER
Hot water
demand indicator
230V
POWER SUPPLY
20V
F1,25A
MAIN SWITCHBOARD
gr AIR
plug in gr PRESSURE
connector SWITCH
r
bl
b
gr
b FAN
br
y/g
plus / minus buttons
reset button
b
br PUMP DHW
info button PUMP
p y/g b br y/g
DHW
p
Aqua NTC FLOW
p t
Sensor TEMPERATURE
bl
SENSOR
w
bl
DIVERTER NTC RETURN
bl br
VALVE TEMPERATURE
bl
SENSOR
NTC
Legend or
TANK
vi TEMPERATURE
b blue SENSOR
br brown r r br b br
y/g yellow/green IGNITION
r red br ELECTRODES
p pink
or orange NTC
t transparent GAS t FLAME
DHW
bl black VALVE SENSOR TEMPERATURE
gr grey y/g SENSOR
w white
vi violet
NTC
return
NTC
flow
11 Diagrams
EV2
Aqua sensor
1
2
EV1
3
4
X12
X4 (VUV) X7 accessories X8
1
2
3
4
5
6
7
8
9
1
2
7 8 9 L N 3 4 5
3
4
X20
13
14
15
16
17
18
19
20
21
22 10
23 11
24 12
X1 X14 X13 X601
X2 X2 U100 coding resistor NTC DHW
X2
13
14
15
16
17
18
19
20
21
22 10
23 11
24 12
X3
Flow-NTC/Return-NTC
Storage tank-NTC 252 805 Fig. 10.6
Warmstart-NTC
* For these components, please observe the associated installation and removal instructions relating to spare parts.
* * *