44232, 44233, 44234, 44235, 44311, 44312, 44313, 44321, 44322, 44323, 44331, 44332,
44333
Elbow Connectors
(Revision history)
- Issued on: Jan. 01, 2007
General Electricity Company of Libya
2/21
Contents
2 NORMATIVE REFERENCES............................................................................................................. 5
3 DEFINITIONS ....................................................................................................................................... 6
5 REQUIREMENTS................................................................................................................................. 9
3/21
5.3.11 Trifurcating glove for 3 core cable .......................................................................................... 12
5.3.12 Tools and equipment required for connecting work ................................................................ 12
5.4 ELECTRICAL REQUIREMENTS ............................................................................................................. 12
5.4.1 AC withstand voltage............................................................................................................... 12
5.4.2 DC withstand voltage .............................................................................................................. 12
5.4.3 Partial discharge voltage......................................................................................................... 12
5.4.4 Impulse voltage withstand ....................................................................................................... 13
5.4.5 Thermal cycling characteristics .............................................................................................. 13
5.4.6 Thermal short circuit current withstand of screen................................................................... 13
5.4.7 Thermal short circuit current withstand of conductor ............................................................. 14
5.4.8 Dynamic short circuit current withstand ................................................................................. 14
5.4.9 Disconnect and connect test .................................................................................................... 14
5.4.10 Operating eye test (if applicable) ............................................................................................ 14
5.4.11 Screen resistance ..................................................................................................................... 14
5.4.12 Screen leakage current ............................................................................................................ 14
5.4.13 Screen fault current initiation .................................................................................................. 14
5.4.14 Operating force........................................................................................................................ 15
5.4.15 Capacitive test point ................................................................................................................ 15
6 TESTS................................................................................................................................................... 15
7 MARKING ........................................................................................................................................... 16
10 WARRANTY........................................................................................................................................ 18
4/21
GES (Technical Specification of GECOL)
Elbow Connectors
for XLPE Insulated Copper Cable (11kV, 30kV)
1.1 Scope
The specification covers the indoor / outdoor use dead break type elbow / tee cable
connectors for armored / non-armored, single / three core(s) stranded copper conductor,
extruded dielectric shielded, XLPE insulated cables rated in preferred voltage of 11kV and
30kV on distribution system in Libya.
2 Normative references
The elbow connectors shall confirm to the latest edition of following international
standards:
(a) IEC 60228: Conductors of insulated cables
(b) IEC 60502: Power cables with extruded insulation and their accessories for rated
voltage from 1kV (Um=1.2kV) up to 30kV (Um=36kV)
(c) IEC 60502-2: Power cables with extruded insulation and their accessories for rated
voltages from 1kV up to 30kV, Part 2 : Cables for rated voltage from 6kV up to 30kV
(d) IEC 60502-4: Test requirements on accessories for cables with rated voltage from 1kV
(Um=1.2kV) up to 30kV (Um=36kV)
(e) IEC 61442: Electric cables – Test methods for accessories for power cables with rated
voltage from 6kV (Um=7.2kV) up to 30kV (Um=36kV)
5/21
(f) IEEE Std 386: Separable insulated connector systems for power distribution system
above 600V
3 Definitions
3.2 Elbow
A connector component for connecting a power cable to a bushing, so designed that
when assembled with the bushing, the axes of the cable and bushing are perpendicular
4.1 Kinds
Kinds of the connector are determined by kinds of cables and to be applied as listed in
Table 1 of this specification.
Table 1 – Kinds of Elbow or Tee connectors
Nominal Cross Sectional
Specification No. of Current Rating
Voltage Armor Screen Area of Cable
No. Core(s) (A)
(kV) (mm2)
4421118 200
4421218 400
4421318 240 630
4421418 800
4421518 11 1 Al Wire Cu Tape 1250
4421220 400
4421320 630
400
4421420 800
4421520 1250
6/21
Nominal Cross Sectional
Specification No. of Current Rating
Voltage Armor Screen Area of Cable
No. Core(s) (A)
(kV) (mm2)
4422118 200
4422218 400
4422318 240 630
4422418 800
4422518 11 1 Non Cu Tape 1250
4422220 400
4422320 630
400
4422420 800
4422520 1250
4423116 200
4423216 400
4423316 150 630
4423416 800
4423516 1250
4423117 200
4423217 400
4423317 11 3 Steel Tape Cu Tape 185 630
4423417 800
4423517 1250
4423118 200
4423218 400
4423318 240 630
4423418 800
4423518 1250
4431120 200
4431220 400 400
4431320 630
30 1 Al Wire Cu Wire
4431122 200
4431222 630 400
4431322 630
7/21
Nominal Cross Sectional
Specification No. of Current Rating
Voltage Armor Screen Area of Cable
No. Core(s) (A)
(kV) (mm2)
4432120 200
4432220 400 400
4432320 630
30 1 Non Cu Wire
4432122 200
4432222 630 400
4432322 630
4433116 200
4433216 150 400
4433316 630
30 3 Steel Tape Cu Tape
4433118 200
4433218 240 400
4433318 630
4.2 Rating
The normal rating specified shall be the continuous rating under the worst temperature
and geographical conditions encountered in Libya.
4.2.3 Earthing
11kV and 30kV systems have no earthing on the line.
8/21
Table 2 - Dimensions of cables
240 18 29 43
Al Wire Cu Tape
400 23 34 49
1
240 18 29 36
Non Cu Tape
8.7/15kV 400 23 34 43
150 14 25 70
Steel
3 Cu Tape 185 16 27 74
Tape
240 18 29 80
400 23 40 59
Al Wire Cu Wire
630 31 48 66
1
400 23 40 54
18/30kV Non Cu Wire
630 31 48 60
Steel 150 14 32 93
3 Cu Tape
Tape 240 18 36 104
5 Requirements
5.1 Type
The connector type shall comply with Table 3 of this specification according to the
continuous current ratings.
Table 3 – Connector and pin type
Continuous current ratings (A) Connector type Pin type
200 Elbow Slide
400 Elbow Slide
630 Elbow or Tee Thread
800 Tee Thread
1250 Tee Thread
9/21
suitable dimensions and structure with mating bushing in Figure 1~4 of this specification
and EN 50181.
Connectors shall be factory engineered kits and shall be the product of one manufacturer.
Connectors shall be fully shielded, suitable for use on 11kV and 30kV distribution system
of Libya. The connector and its material shall be appropriate for each cable size and
applicable voltage.
The connectors shall be easily adapted to accommodate XLPE cable. The connectors
shall be capable of tolerating any variance in the manufactured dimension of the cable such
as oval, out of round, sectored or oversize cable cores.
The connector materials shall be supplied in a complete kit to suit various sizes of cable
and to provide stress control, non tracking and sealing. It shall consist of high permittivity,
high resistivity, stress control, non-tracking polymeric materials and prevent ingress of
moisture and contamination.
All polymeric components shall be non-tracking and suitable for operation in the
presence of severe external contaminating and environment pollution in Libya.
The connectors shall meet the requirements of the latest edition of IEC 60502-4 and
related international standards.
10/21
5.3.1 Connector housing general
The connector housing shall be of one piece type and shall be of reasonable size to
accommodate cables easily. The housing shall be capable of proper sealing, sufficient
strength, robustness and impact resistance. Connector housing shall be able to smooth the
electrical field over the connector and cable screen ends.
The connector shall be connected with well type mating bushing perpendicularly.
Dimensions and structure shall be suitable for connection with its well type bushing
specified in Figure 1 to Figure 4 of this specification and EN 50181.
11/21
5.3.9 Basic insulating plug
Basic insulation plug shall provide insulation and sealing at one side of tee connector. It
shall provide voltage test point.
12/21
7 of this specification. The partial discharge shall not exceed 10pC. The connectors shall be
tested at 5K to 10K above maximum cable conductor temperature in normal operation and
at ambient temperature.
Table 7 - Minimum partial discharge voltage
Rated voltage of connector Minimum partial discharge voltage level
(kV) (kV rms)
8.7/15 15
18/30 30
8.7/15 95
18/30 170
13/21
of the connectors ability.
Table 10 – Short circuit current and duration
Cross sectional area of Short circuit current
Duration
conductor (mm2) (kA)
150 21.5 1 sec.
185 26.5 1 sec.
240 34.3 1 sec.
630 90.0 1 sec.
14/21
5.4.14 Operating force
Open and close force shall be less than 900N measured with conditions of Clause 17 of
IEC 61442.
6 Tests
15/21
7 Marking
The connectors shall be permanently and legibly identified with the following
information items.
(a) Manufacturer’s identification
(b) Model identification
(c) Part identification
(d) Date of manufacture (month and year)
(e) “Use before” (if applicable)
(f) Maximum phase-to-phase voltage ratings
(g) Applicable cable type, cross sectional area of conductor and insulation diameter range
The outer packing must be clearly marked on at least four (4) sides as follows;
(a) Name of the procuring department
(b) Name of the supplier
(c) Contract description and number
(d) Final destination
(e) Gross weight
(f) Any special lifting instructions
(g) Any special handling instructions
16/21
(h) Any relevant pollution or environment classifications
17/21
approved by GECOL)
9.3 Documentation
All documents supplied under this specification shall be documented to the extent that
the end user can easily understand its theory of operation, performance, installation and
maintenance for the product. All documents shall be submitted being filed in order to
approve of GECOL and reorder later.
Language in all documents and drawings shall be written in English and dimensions
shall be used in metric SI-units.
10 Warranty
The supplier shall provide a full three-year limited warranty on all equipment supplied.
The warranty shall cover all parts and all costs, which are directly attributable to the
supplier. Warranty coverage shall begin on the date that the equipment is received.
18/21
Dia 56±0.2
D ia 4 4 .5 ± 0 .2 Dia 46±0.2
D ia 3 2 .5 ± 0 .2 Dia 14 -0.04
0
D ia 3 0 .9 ± 0 .2
D ia 7 .9 - 00 .0 5 40
90±0.2
4 8 -00 .2
10± 1 12±0.2
D ia 4 8 .5 ± 0 .2 Dia 70±0.2
Figure 1 – 200A Plug-in type bushing Figure 2 – 400A Plug-in type bushing
M16x2-6H
M16x2-6H
1.5
30
min
35
30
min 35
90±0.2 81
Figure 3 – 630A Plug-in type bushing Figure 4 – 800A, 1250A Plug-in type bushing
19/21
Appendix A
Technical Data Sheet
1 Manufacturer’s name
2 Applicable standards
3 Identification No. (Model No.)
4 Applicable cable type
5 Applicable cross sectional area of conductor (mm2)
6 Applicable diameter of insulation (mm)
7 Applicable diameter of oversheath (mm)
8 Rating current (A)
9 No. of core(s)
10 Type of connector
11 Voltage rating phase to ground (kV rms)
12 Voltage rating phase to phase (kV rms)
13 Normal operation temperature (°C)
14 Emergency operation temperature (°C)
15 Dimension
a) Diameter (mm)
b) Length (mm)
16 AC withstand voltage test (Dry)
a) Minute(s)
b) Voltage level (kV rms)
17 DC withstand voltage test
a) Minute(s)
b) Voltage level (kV avg)
18 Minimum partial discharge voltage level (kV rms, pC)
a) at above normal operation temperature
b) at ambient temperature
Signature :
20/21
Technical Data Sheet
Signature :
Designation :
Name of Tenderer :
Date :
21/21