Вы находитесь на странице: 1из 41

Proyecto de Modernización

de la Refinería de Talara
Project No.: 02070

HDT GASOILS
CAUSE & EFFECT MATRIX

TR6 30/SEP/2016 Issued for Construction (revised) TFC JLT MAO


TR5 23/NOV/2015 Issued for Construction JLT JAS MAO
TR4 23/MAR/2015 Issued for design TFC RRR CGC / MAO
TR3 25/UL/2012 Issued for FEED (new interlocks included) AYG CGC PSP
TR2 06/FEB/2012 Isued for FEED (review as indicated) YGF / LSJ CGC PSP
TR1 16/MAY/2011 Issued for FEED YGF / JEP ECD PSP
REV. DATE DESCRIPTION PREPARED BY CHECKED BY APPROVED BY
DOCUMENT TITLE
CAUSE & EFFECT MATRIX
DOCUMENT NUMBER REVISION
02070-HTD-PRO-TAB-001 Page 1 of 41 TR6

THE PRESENT DOCUMENT OR DRAWING IS THE PROPERTY OF TECNICAS REUNIDAS AND SHALL NOT, UNDER ANY CIRCUNSTANCES BE TOTALLY OR PARTIALLY, DIRECTLY OR INDIRECTLY, TRANSFERRED, REPRODUCED, COPIED, DISCLOSED OR USED
WITHOUT ITS PRIOR WRITTEN CONSENT, FOR ANY PURPOSE AND IN ANY WAY OTHER THAM THAT FOR WHICH IS SPECIFICALLY FURNISHED OR OUTSIDE THE EXTENT OF THE AGREED UPON RIGHT OF USE.
SITE : TALARA REFINERY - PETROPERU
CAUSE & EFFECT MATRIX PROJECT : 02070 - PETROPERU
UNIT: HDT GASOILS (HTD) HTD - HDT GASOILS UNIT MODERNIZACIÓN REFINERIA TALARA (PERU)
Page 2 of 41

DATE: 30/SEP/2016 DOCUMENT No: 02070-HTD-PRO-TAB-001 REV. TR6


GENERAL NOTES:
(1) Action delayed adjustable 0-10 seconds.
(2) Inactivation by key operated switch during start-up for catalyst drying (Process override switches, P.O.S.).
(3) Signal coming from PLC shall be pulse type. After the duration of pulse, the reset pushbutton shall be used to reset the IS-005 trip and allow to start the standby compressor motor.
(4) Final element to be reset on Control Panel after reset of IS-0Unit.
(5) Final element to be reset locally after reset of IS-0Unit.
(6) This trip is active if more than 50% burners are out. This percentage to be confirmed by vendor. Also, the trip IS-007A/B/C/D/E denotes that the DCS programmer should create 5 interlock
block, one for each burner.
(7) This trip is active if more than 50% burners are out. This percentage to be confirmed by vendor. Also, the trip IS-009A/B/C/D/E denotes that the DCS programmer should create 5 interlock
block, one for each burner.
(8) This trip is active if more than 50% burners are out. This percentage to be confirmed by vendor. Also, the trip IS-012A/B/C/D/E denotes that the DCS programmer should create 5 interlock
block, one for each burner.
(9) Start-up and maintenance overrides (where indicated) and resets shall be initiated and registered on DCS and SER (System Events Record).
(10) Refer to HTN-K-002-A/B vendor Cause and Effect Diagram (V-020700501-M184-HTD-K-002A-0025-C).
(11) Refer to HTN-K-001 vendor Cause and Effect Diagram (V-020700502-H057-HTD-K-001-0026-C).

BASED ON:
P&IDs Rev. P&IDs Rev.
02070-HTD-PRO-PID-001-1 06 02070-HTD-PRO-PID-032 06
02070-HTD-PRO-PID-001-2 06 02070-HTD-PRO-PID-033 06
02070-HTD-PRO-PID-002 06 02070-HTD-PRO-PID-034 07
02070-HTD-PRO-PID-003 06 02070-HTD-PRO-PID-035 06
02070-HTD-PRO-PID-004 06 02070-HTD-PRO-PID-036 06
02070-HTD-PRO-PID-005 06 02070-HTD-PRO-PID-037 06
02070-HTD-PRO-PID-006 06 02070-HTD-PRO-PID-038 06
02070-HTD-PRO-PID-007 06 02070-HTD-PRO-PID-039 06
02070-HTD-PRO-PID-008-1 07 02070-HTD-PRO-PID-040 06
02070-HTD-PRO-PID-008-2 02 02070-HTD-PRO-PID-041 06
02070-HTD-PRO-PID-009 07 02070-HTD-PRO-PID-042 06
02070-HTD-PRO-PID-011 06 02070-HTD-PRO-PID-045 06
02070-HTD-PRO-PID-012 06 02070-HTD-PRO-PID-046 06
02070-HTD-PRO-PID-013 06 02070-HTD-PRO-PID-047 06
02070-HTD-PRO-PID-014 06 02070-HTD-PRO-PID-048-1 06
02070-HTD-PRO-PID-015 06 02070-HTD-PRO-PID-048-2 06
02070-HTD-PRO-PID-016 06 02070-HTD-PRO-PID-051 06
02070-HTD-PRO-PID-017 07 02070-HTD-PRO-PID-052 06
02070-HTD-PRO-PID-018 06 02070-HTD-PRO-PID-053 06
02070-HTD-PRO-PID-019-1 06 02070-HTD-PRO-PID-054 06
02070-HTD-PRO-PID-019-2 01 02070-HTD-PRO-PID-055 03
02070-HTD-PRO-PID-019-3 01 02070-HTD-PRO-PID-056 03
02070-HTD-PRO-PID-020 06 02070-HTD-PRO-PID-074 06
02070-HTD-PRO-PID-021-1 06 02070-HTD-PRO-PID-075 06
02070-HTD-PRO-PID-021-2 06 02070-HTD-PRO-PID-076 06
02070-HTD-PRO-PID-021-3 06 02070-HTD-PRO-PID-077 06
02070-HTD-PRO-PID-022-1 06 02070-HTD-PRO-PID-078 02
02070-HTD-PRO-PID-022-2 06 02070-HTD-PRO-PID-079 02
02070-HTD-PRO-PID-022-3 06 02070-HTD-PRO-PID-701-1 02
02070-HTD-PRO-PID-023 06 02070-HTD-PRO-PID-701-2 02
02070-HTD-PRO-PID-024 07 02070-HTD-PRO-PID-702 02
02070-HTD-PRO-PID-025 06 02070-HTD-PRO-PID-703 02
02070-HTD-PRO-PID-026 06 02070-HTD-PRO-PID-801-1 02
02070-HTD-PRO-PID-027 06 02070-HTD-PRO-PID-801-2 01
02070-HTD-PRO-PID-028-1 06 02070-HTD-PRO-PID-801-3 01
02070-HTD-PRO-PID-028-2 06 02070-HTD-PRO-PID-802 03
02070-HTD-PRO-PID-029 07 02070-HTD-PRO-PID-803 01
02070-HTD-PRO-PID-030-1 06 02070-HTD-PRO-PID-850 00
02070-HTD-PRO-PID-030-2 06 02070-HTD-PRO-PID-851 00
02070-HTD-PRO-PID-031 06
SITE : TALARA REFINERY - PETROPERU
CAUSE & EFFECT MATRIX PROJECT : 02070 - PETROPERU
UNIT: HDT GASOILS (HTD) HTD - HDT GASOILS UNIT MODERNIZACIÓN REFINERIA TALARA (PERU)
Page 3 of 41

DATE: 27/JUN/2016 DOCUMENT No: 02070-HTD-PRO-TAB-001 REV. TR6

REVISION CONTENT
SHEET
TR4 TR5 TR6 DESCRIPTION DESIGNATION P&ID NOTES
1 X X X COVER SHEET
2 X X X GENERAL NOTES
3 X X X INDEX
INTERLOCKS
4 X IS-001 TRIP OF FEED FROM BATTERY LIMIT IS-001
5 X X IS-002 TRIP OF FEED TO REACTION SECTION IS-002
6 X X IS-003 TRIP OF DEPRESSURISATION OF HP LOOP IS-003
7 X X X IS-004 TRIP OF RECYCLE GAS COMPRESSOR K-001 IS-004
8 X X X IS-005 TRIP OF MAKE-UP GAS COMPRESSOR K-002-A/B IS-005
9 X IS-006 BLOCK FEED TO HP LOOP IS-006
10 X X IS-007A/B/C/D/E TRIP OF FUEL GAS BURNER A/B/C/D/E OF HEATER HTD-H-001 IS-007A/B/C/D/E
11 X X IS-008 TOTAL FUEL GAS BURNER TRIP IN HEATER HDT-H-001 IS-008
12 X X IS-009A/B/C/D/E TRIP OF FLEXI GAS BURNER A/B/C/D/E OF HEATER HTD-H-001 IS-009A/B/C/D/E
13 X X IS-010 TOTAL FLEXI GAS BURNER TRIP OF HEATER HTD-H-001 IS-010
14 X X IS-012A/B/C/D/E TRIP OF PILOT BURNER A/B/C/D/E OF HEATER HTD-H-001 IS-012A/B/C/D/E
15 X X IS-013 TOTAL PILOT BURNER TRIP OF HEATER HTD-H-001 IS-013
16 X IS-014 TRIP OF LIQUID FROM HP HOT SEPARATOR HTD-D-002 IS-014
17 X IS-015 TRIP OF HYDROCARBON LIQUID FROM HP COLD SEPARATOR HTD-D-003 IS-015
18 X IS-016 TRIP OF WATER FROM HP COLD SEPARATOR HTD-D-003 IS-016
19 X IS-018 TRIP OF STEAM TO PRODUCT STRIPPER HTD-C-001 IS-018
20 X IS-019 TRIP OF GASOIL PRODUCT PUMP P-008-A/B IS-019
21 X X IS-020 TRIP OF WASH WATER PUMPS P-006-A/B IS-020
22 X IS-021 TRIP OF WATER TO WASH WATER SURGE DRUM HTD-D-007 IS-021
23 X IS-022 TRIP OF NON CRACKED SLOPS PUMP (HTD-P-011 A/B) IS-022
24 X IS-023 TRIP OF CRACKED SLOPS PUMP (HTD-P-012 A/B) IS-023
25 X IS-024 TRIP OF SOUR WATER FROM HTD-D-005 IS-024
26 X IS-025 TRIP OF SOUR WATER FROM HTD-D-015 IS-025
27 X IS-026 TRIP OF RICH AMINE FROM HTD-C-002 IS-026
28 X X X IS-027 TRIP OF MAKE-UP GAS COMPRESSOR K-002-A IS-027
29 X X X IS-028 TRIP OF MAKE-UP GAS COMPRESSOR K-002-B IS-028
30 X X IS-029 TRIP OF LP STEAM TP HTD-H-001 SUPERHEATING COIL IS-029
31 X IS-030 TRIP OF PRODUCT OIL TRANSFER TO STORAGE IS-030
32 X IS-031 TRIP OF LEAN AMINE FEED TO ABSORBER IS-031
33 X X I-001 NON CRACKED SLOPS PUMP (HTD-P-011-A/B) OPERATIONAL INTERLOCK I-001
34 X X I-002 CRACKED SLOPS PUMP (HTD-P-012-A/B) OPERATIONAL INTERLOCK I-002
35 X I-004 LP HOT SEPARATOR (HTD-D-004) HOT LIQUID OUTLET OPERATIONAL INTERLOCK I-004
36 X I-005 LP COLD SEPARATOR (HTD-D-005) COLD LIQUID OUTLET OPERATIONAL INTERLOCK I-005
37 X I-006 MAKE-UP GAS COMP. (HTD-K-002-A/B) 1st STAGE SUCTION DRAIN BOOT OPERATIONAL INT. I-006
38 X I-007 MAKE-UP GAS COMP. (HTD-K-002-A/B) 2nd STAGE SUCTION DRAIN BOOT OPERATIONAL INT. I-007
39 X I-008 MAKE-UP GAS COMP. (HTD-K-002-A/B) 3rd STAGE SUCTION DRAIN BOOT OPERATIONAL INT.
40 X I-009 FEED COALESCER DRAIN BOOT OPERATIONAL INT. I-008
41 X I-010 RECYCLE GAS K.O DRUM LIQUID OUTLET OPERATIONAL INTERLOCK
NOTES
REV.

TR4

TR4

TR4

TR4

TR4

TR4
CAUSE AND EFFECT
CHART FOR UNIT HTD

NOTES
CUSTOMER NAME: Petroperú PROJECT No: 2070

LOCATION: Talara (Perú) UNIT No: HDT GASOILS


SERVICE: Page 4 of 41

HTD-PID-

HTD-PID-

HTD-PID-

HTD-PID-

HTD-PID-

HTD-PID-
001-1

001-1

001-2
P&ID

002

003

005
Doc Class: DOCUMENT No:02070-HTD-PRO-TAB-001

REVISION TR1 TR2 TR3 TR4


IS-001

SRGO+LVGO FROM B.L TO HTD-


DATE 16/MAY/2011 06/FEB/2012 25/UL/2012 23/MAR/2015

HTD-D-018 HIGH HIGH LEVEL

HTD-D-001 HIGH HIGH LEVEL


TRIP OF FEED FROM BATTERY LIMIT

VALVE UPSTREAM OF F-001


ORIG. BY YGF / JEP YGF / LSJ AYG TFC

VALVE EN LKGO FEED LINE


VALVE IN LCO FEED LINE
APP. BY PSP PSP PSP CGC / MAO

SERVICE

LOW LOW FLOW AT


LEGEND ABBREVIATIONS USED IN THE CHART:
HH HIGH HIGH
H HIGH C = Close

D-018 LINE
L LOW O = Open

ALARM

ALARM
LL LOW LOW I = Start
S = Stop
FMC - FORCE MANUAL CLOSE X = General Action
FMO - FORCE MANUAL OPEN
OOS - START-UP OVERRIDE SWITCH E = Enable

EFFECTS
FUNCTION PERFORMED
MOS - MAINTENANCE OVERRIDE SWITCH D = Disable
SOE - SEQUENCE OF EVENTS MR = Manual Reset

HIGH HIGH LEVEL ALARM

HIGH HIGH LEVEL ALARM


LOW LOW FLOW ALARM
D - DELETED RR = Remote Reset
A = Activate
REFERENCES: V = oVerride
T = Trip
P&ID No. P = Permissive
HTD-PID-001-1 B = Bypass

CLOSE

CLOSE

CLOSE
HTD-PID-001-2
HTD-PID-002
HTD-PID-003
HTD-PID-005

DESCRIPTION

LAHH-00101 DCS LEVEL ALARM

LAHH-00501 DCS LEVEL ALARM


FALL-00101 DCS FLOW ALARM
ON-OFF VALVE

ON-OFF VALVE

ON-OFF VALVE
XV-00101

XV-00201

XV-00301
ACTUATING
DEVICE
CAUSES #

10

11

12

13

14

15

16

17

18

21

22

23

24

25

26

27

28

29

30
1

9
INITIATING OOS MOS
REV. EQUIPMENT DESCRIPTION DEVICE
SERVICE P&ID NOTES #
(b) (b)

TR4 MANUAL ACTIVATION FROM CONTROL ROOM HS-001B TRIP PUSHBUTTON (PANEL IN CONTROL ROOM) 1 C C C

FT-00101 LOW LOW FLOW AT HIGH SULFUR DIESEL FROM B.L TO HTD-D-018 LINE (VOTE
TR4 NON CRACKED FEED (SRGO+LVGO) X (*) HTD-PID-001-1 GENERAL NOTES 1 2 C C A
A/B/C 2oo3)

TR4 HTD-D-018 FEED COALESCER BOOT LT-00101 A/B/C DRUM HTD-D-018 HIGH HIGH LEVEL (VOTE 2oo3) X (*) HTD-PID-001-2 GENERAL NOTES 1 3 C C C A

TR4 HTD-D-001 FEED SURGE DRUM LT-00501 A/B/C DRUM HTD-D-001 HIGH HIGH LEVEL (VOTE 2oo3) X (*) HTD-PID-005 GENERAL NOTES 1 4 C C C A

10

11

12

13

14

15

16

17

18

19

20

21

(*) 1 MOS FOR EACH TRANSMITTER 22

23

24

25

RESET

TR4 HS-001A RESET PUSHBUTTON (DCS) 1

9
REV.

TR4

TR4

TR6

TR4

TR6

TR4

TR4
CAUSE AND EFFECT
CHART FOR UNIT HTD

NOTES
CUSTOMER NAME: Petroperú PROJECT No: 2070

LOCATION: Talara (Perú) UNIT No: HDT GASOILS


SERVICE: Page 5 of 41

HTD-PID-

HTD-PID-

HTD-PID-

HTD-PID-
001-1
P&ID

N/A

N/A
006

006

005
DOCUMENT No:02070-HTD-PRO-TAB-001
Doc Class:
REVISION TR1 TR2 TR3 TR4 TR6

HTD-D-001 HIGH HIGH LEVEL


DATE 16/MAY/2011 06/FEB/2012 25/UL/2012 23/MAR/2015 30/SEP/2016 IS-002

BLOCK FEED TO HP LOOP


PARTIAL SHUTDOWN OF
ORIG. BY YGF / JEP YGF / LSJ AYG TFC TFC TRIP OF FEED TO REACTION SECTION

LOW LOW FLOW ALARM


FEED PUMP MOTOR A

FEED PUMP MOTOR B


APP. BY PSP PSP PSP CGC / MAO MAO

HEATER HDT-H-001
SERVICE
LEGEND ABBREVIATIONS USED IN THE CHART:
HH HIGH HIGH C = Close
H HIGH O = Open

ALARM
L LOW
LL LOW LOW I = Start
S = Stop
FMC - FORCE MANUAL CLOSE X = General Action
FMO - FORCE MANUAL OPEN E = Enable

EFFECTS
FUNCTION PERFORMED
OOS - START-UP OVERRIDE SWITCH D = Disable
MOS - MAINTENANCE OVERRIDE SWITCH

HIGH HIGH LEVEL ALARM


MR = Manual Reset

LOW LOW FLOW ALARM


SOE - SEQUENCE OF EVENTS RR = Remote Reset
D - DELETED
A = Activate

LOGIC ACTIVATE

LOGIC ACTIVATE
V = oVerride
REFERENCES: T = Trip
P = Permissive
P&ID No. B = Bypass
HTD-PID-005

STOP

STOP
HTD-PID-006
HTD-PID-007

INDIVIDUAL PUMP TRIPS TO BE SPECIFIED BY PUMP


VENDOR.

DESCRIPTION

LAHH-00501 DCS LEVEL ALARM


FALL-00101 DCS FLOW ALARM
MOTOR PUMP

MOTOR PUMP
MX-00601

MX-00602
ACTUATING

IS-008

IS-006
DEVICE
CAUSES #

10

11

12

13

14

15

16

17

18

21

22

23

24

25

26

27

28

29

30
1

9
INITIATING OOS (b) MOS
REV. EQUIPMENT DESCRIPTION DEVICE
SERVICE P&ID NOTES #
General Note 2 (b)

TR6 MANUAL ACTIVATION FROM CONTROL ROOM HS-002B TRIP PUSHBUTTON (PANEL IN CONTROL ROOM) 1 S S A A

TR6 IS-003 DEPRESSURISATION OF HP-LOOP 2 S S A A


LOW LOW FLOW AT TREAT GAS FROM HTD-K-001 LINE
TR6 TREAT GAS FROM HTD-K-001 TO HEATER HTD-H-001 LINE FT-00701 A/B/C HS-002C X (*) HTD-PID-007 GENERAL NOTE 1 3 S S A A X
(VOTE 2oo3)

TR6 IS-004 TRIP OF RECYCLE GAS COMPRESSOR HTD-K-001 4 S S A A

TR6 HTD-D-001 FEED SURGE DRUM LT-00501 A/B/C DRUM HTD-D-001 LOW LOW LEVEL (VOTE 2oo3) HS-002D X (*) HTD-PID-005 GENERAL NOTE 1 5 S S A A X

MYS-00601
TR6 HTD-P-005-A/B FEED PUMPS BOTH PUMPS NOT RUNNING HS-002E HTD-PID-006 GENERAL NOTES 1, 3 6 S S A A
MYS-00602
TR6 HTD-P-005-A/B MOV-00501 UPSTREAM HTD-P-005-A/B MHS-00501G MOV-00501 CLOSE PUSHBUTTON (DCS) HS-002F HTD-PID-005 7 S S A A

TR6 HTD-P-005-A/B MOV-00501 UPSTREAM HTD-P-005-A/B MHS-00501CC MOV-00501 CLOSE PUSHBUTTON (LOCAL PANEL) HS-002F HTD-PID-005 8 S S A A

TR6 HTD-P-005-A/B MOV-00501 UPSTREAM HTD-P-005-A/B MZSO-00501 VALVE MOV-00501 NOT FULLY OPEN HS-002F HTD-PID-005 9 S S A A

10

11

12

13

14

15

16

17

18

19

20

21

(*) 1 MOS FOR EACH TRANSMITTER 22

23

24

25

RESET

TR4 HS-002A RESET PUSHBUTTON (DCS) 1

9
REV.

TR4

TR5

TR5

TR5

TR5
CAUSE AND EFFECT
CHART FOR UNIT HTD

NOTES
CUSTOMER NAME: Petroperú PROJECT No: 2070

LOCATION: Talara (Perú) UNIT No: HDT GASOILS


SERVICE: Page 6 of 41

HTD-PID-
P&ID

N/A

N/A

N/A

N/A
014
DOCUMENT No:02070-HTD-PRO-TAB-001
Doc Class:
REVISION TR1 TR2 TR3 TR4 TR5
IS-003

TRIP OF FEED TO REACTION


DATE 16/MAY/2011 06/FEB/2012 25/UL/2012 23/MAR/2015 23/NOV/2015

TOTAL PILOT BURNER TRIP


XV-01403 DEPRESSURISATION
TRIP OF DEPRESSURISATION OF HP

COMPRESSOR K-002-A/B
ORIG. BY YGF / JEP YGF / LSJ AYG TFC JLT

TRIP OF MAKE-UP GAS

TRIP OF WASH WATER


OF HEATER HDT-H-001
LOOP
APP. BY PSP PSP PSP CGC / MAO MAO

SERVICE

PUMPS P-006-A/B
LEGEND ABBREVIATIONS USED IN THE CHART:
HH HIGH HIGH C = Close

SECTION
H HIGH O = Open
L LOW

VALVE
LL LOW LOW I = Start
S = Stop
FMC - FORCE MANUAL CLOSE X = General Action
FMO - FORCE MANUAL OPEN E = Enable

EFFECTS
FUNCTION PERFORMED
OOS - START-UP OVERRIDE SWITCH D = Disable
MOS - MAINTENANCE OVERRIDE SWITCH MR = Manual Reset
SOE - SEQUENCE OF EVENTS RR = Remote Reset
D - DELETED
A = Activate

LOGIC ACTIVATE

LOGIC ACTIVATE

LOGIC ACTIVATE

LOGIC ACTIVATE
V = oVerride
REFERENCES: T = Trip
P = Permissive
P&ID No. B = Bypass
HTD-PID-014

OPEN
DESCRIPTION

ON-OFF VALVE
XV-01403
ACTUATING

IS-002

IS-005

IS-013

IS-020
DEVICE
CAUSES #

10

11

12

13

14

15

16

17

18

21

22

23

24

25

26

27

28

29

30
1

9
INITIATING OOS MOS
REV. EQUIPMENT DESCRIPTION DEVICE
SERVICE P&ID NOTES #
(b) (b)

TR5 MANUAL ACTIVATION FROM CONTROL ROOM HS-003B TRIP PUSHBUTTON (PANEL IN CONTROL ROOM) 1 O A A A A

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

RESET

TR4 HS-003A RESET PUSHBUTTON (DCS) 1

9
REV.

TR5

TR4

TR4

TR4

TR4

TR4

TR4

TR5

TR6
CAUSE AND EFFECT
CHART FOR UNIT HTD

NOTE 11
NOTE 1

NOTE 1

NOTE 1
NOTES
CUSTOMER NAME: Petroperú PROJECT No: 2070

LOCATION: Talara (Perú) UNIT No: HDT GASOILS


SERVICE: Page 7 of 41

HTD-PID-

HTD-PID-

HTD-PID-

VALVE DOWNSTREAM HTD-K- HTD-PID-

HTD-PID-

HTD-PID-

HTD-PID-
019-1

019-1

019-1

019-1

019-1

019-1
P&ID

N/A

018
DOCUMENT No:02070-HTD-PRO-TAB-001
Doc Class:
REVISION TR1 TR2 TR3 TR4 TR5 TR6
30/SEP/201 IS-004

HTD-D-006 HIGH HIGH LEVEL


TRIP OF FEED TO REACTION
DATE 16/MAY/2011 06/FEB/2012 25/UL/2012 23/MAR/2015 23/NOV/2015

VALVE IN ANTISURGE LINE


6 TRIP OF RECYCLE GAS

VALVE UPSTREAM HTD-K-


ORIG. BY YGF / JEP YGF / LSJ AYG TFC JLT TFC

TURBINE IN COMPRESSOR
COMPRESSOR K-001
APP. BY PSP PSP PSP CGC / MAO MAO MAO

VALVE IN STEAM LINE


SERVICE

UPSTREAM TURBINE
LEGEND ABBREVIATIONS USED IN THE CHART:

RECYCLE GAS
COMPRESSOR

COMPRESSOR
VENDOR SCOPE

RECYCLE GAS
HH HIGH HIGH
C = Close

HTD-K-001
H HIGH

SECTION
L LOW O = Open

ALARM
LL LOW LOW I = Start

001

001
FMC - FORCE MANUAL CLOSE S = Stop
FMO - FORCE MANUAL OPEN X = General Action
OOS - START-UP OVERRIDE SWITCH E = Enable
MOS - MAINTENANCE OVERRIDE SWITCH

EFFECTS
FUNCTION PERFORMED
SOE - SEQUENCE OF EVENTS D = Disable

HIGH HIGH LEVEL ALARM


D - DELETED MR = Manual Reset
RR = Remote Reset
REFERENCES: A = Activate

LOGIC ACTIVATE
V = oVerride
P&ID No. T = Trip
HTD-PID-018
HTD-PID-019 P = Permissive
B = Bypass

ALARM
CLOSE

CLOSE

CLOSE

CLOSE
STOP

TRIP
FOR COMPRESSOR VENDOR INTERLOCK SEE
V-020700502-H057-HTD-K-001-0026
NOTE 1: THE MOTOR OPERATED VALVE SHALL BE
CLOSED WITH DELAY AFTER COMPRESSOR
SHUTDOWN (COMPLETE STANDSTILL) TO PREVENT
COMPRESSOR DAMAGE. THE TIME DELAY SHALL BE
10s ACCORDING TO COMPRESSOR VENDOR.

COMPRESSOR HTD-K-001 SHUT DOWN


DESCRIPTION

COMPRESSOR HTD-K-001 TRIP


LAHH-01801 DCS LEVEL ALARM
TURBINE STOP

ON-OFF VALVE

MOV-01901 ON-OFF VALVE

MOV-01902 ON-OFF VALVE

MOV-01903 ON-OFF VALVE

XA-70375
XY-01961

XV-01904
ACTUATING

IPS-703
IS-002
DEVICE
CAUSES #

10

11

12

13

14

15

16

17

18

21

22

23

24

25

26

27

28

29

30
1

9
INITIATING OOS MOS
REV. EQUIPMENT DESCRIPTION DEVICE
SERVICE P&ID NOTES #
(b) (b)

TR4 MANUAL ACTIVATION FROM CONTROL ROOM HS-004B TRIP PUSHBUTTON (PANEL IN CONTROL ROOM) 1 A T C C C C A
LT-01801
TR4 HTD-D-006 RECYCLE GAS DRUM DRUM HTD-D-006 HIGH HIGH LEVEL (VOTE 2oo3) X (*) HTD-PID-018 GENERAL NOTE 1 2 A T C C C C X A
A/B/C

TR4 HTD-K-001 MOV-01901 UPSTREAM HTD-K-001 MZSO-01901 VALVE MOV-01901 NOT FULLY OPEN HTD-PID-019-1 3 A T C C C C A

TR4 HTD-K-001 MOV-01902 DOWNSTREAM HTD-K-001 MZSO-01902 VALVE MOV-01902 NOT FULLY OPEN HTD-PID-019-1 4 A T C C C C A

TR4 HTD-K-001 MOV-01903 IN ANTISURGE LINE HTD-K-001 MZSO-01903 VALVE MOV-01903 NOT FULLY OPEN HTD-PID-019-1 5 A T C C C C A

TR4 HTD-K-001 MOV-01902 DOWNSTREAM HTD-K-001 MZLC-01902 VALVE MOV-01902 CLOSED HTD-PID-019-1 6 A T C C C C A

TR4 HTD-K-001 MOV-01901 UPSTREAM HTD-K-001 MHS-01901G MOV-01901 CLOSE PUSHBUTTON (DCS) HTD-PID-019-1 7 A T C C C C A

TR4 HTD-K-001 MOV-01901 UPSTREAM HTD-K-001 MHS-01901CC MOV-01901 CLOSE PUSHBUTTON (LOCAL PANEL) HTD-PID-019-1 8 A T C C C C A

TR4 HTD-K-001 MOV-01902 DOWNSTREAM HTD-K-001 MHS-01902G MOV-01902 CLOSE PUSHBUTTON (DCS) HTD-PID-019-1 9 A T C C C C A

TR4 HTD-K-001 MOV-01902 DOWNSTREAM HTD-K-001 MHS-01902CC MOV-01902 CLOSE PUSHBUTTON (LOCAL PANEL) HTD-PID-019-1 10 A T C C C C A

TR4 HTD-K-001 MOV-01903 IN ANTISURGE LINE HTD-K-001 MHS-01903G MOV-01903 CLOSE PUSHBUTTON (DCS) HTD-PID-019-1 11 A T C C C C A

TR4 HTD-K-001 MOV-01903 IN ANTISURGE LINE HTD-K-001 MHS-01903CC MOV-01903 CLOSE PUSHBUTTON (LOCAL PANEL) HTD-PID-019-1 12 A T C C C C A

TR6 HTD-K-001 RECYCLE GAS COMPRESSOR XS-70375 COMPRESSOR TRIP 13 X

14

15

16

17

18

19

20

21

(*) 1 MOS FOR EACH TRANSMITTER 22

23

24

25

RESET

TR4 HS-004A RESET PUSHBUTTON (DCS) 1

9
REV.

TR6

TR6

TR6

TR6

TR6

TR6

TR6

TR6
CAUSE AND EFFECT

GENERAL NOTE 10

GENERAL NOTE 10
CHART FOR UNIT HTD

NOTES
CUSTOMER NAME: Petroperú PROJECT No: 2070

LOCATION: Talara (Perú) UNIT No: HDT GASOILS


SERVICE: Page 8 of 41

HTD-PID-

HTD-PID-

HTD-PID-

HTD-PID-
021-1

021-3

021-1

022-1
P&ID
Doc Class: DOCUMENT No:02070-HTD-PRO-TAB-001

REVISION TR1 TR2 TR3 TR4 TR5 TR6


16/MAY/2011 06/FEB/2012 25/UL/2012 23/MAR/2015 23/NOV/15
30/SEP/201 IS-005
DATE

DISCHARGE VALVE TO HTF


6 TRIP OF MAKE-UP GAS COMPRESSOR
ORIG. BY YGF / JEP YGF / LSJ AYG TFC JLT TFC
K-002-A/B

HTD-K-002-A/B COMMON
APP. BY PSP PSP PSP CGC / MAO MAO MAO

SERVICE

HTD-K-002-A/B 1st

DISCHARGE VALVE
LEGEND ABBREVIATIONS USED IN THE CHART:

COMPRESSOR

COMPRESSOR

COMPRESSOR

COMPRESSOR
MAKE-UP GAS

MAKE-UP GAS

MAKE-UP GAS

MAKE-UP GAS
HH HIGH HIGH
H HIGH C = Close
L LOW O = Open
LL LOW LOW I = Start
FMC - FORCE MANUAL CLOSE S = Stop
FMO - FORCE MANUAL OPEN X = General Action
OOS - START-UP OVERRIDE SWITCH E = Enable
MOS - MAINTENANCE OVERRIDE SWITCH

EFFECTS
FUNCTION PERFORMED
SOE - SEQUENCE OF EVENTS D = Disable
D - DELETED MR = Manual Reset
RR = Remote Reset
REFERENCES: A = Activate
V = oVerride
P&ID No. T = Trip
HTD-PID-021-1
HTD-PID-021-2 P = Permissive
HTD-PID-021-3 B = Bypass

ALARM

ALARM
CLOSE

CLOSE
HTD-PID-022-1

TRIP

TRIP
HTD-PID-022-2
HTD-PID-022-3

FOR COMPRESSOR VENDOR INTERLOCK SEE


V-020700501-M184-HTD-K-002A-0025.

DESCRIPTION

XA-70172A COMPRESSOR HTD-K-002A TRIP

XA-70172B COMPRESSOR HTD-K-002B TRIP


XS-70175A COMPRESSOR HTD-K-002-A

XS-70175B COMPRESSOR HTD-K-002-B


ON-OFF VALVE

ON-OFF VALVE
XV-02102

XV-02104
ACTUATING
DEVICE
CAUSES #

10

11

12

13

14

15

16

17

18

21

22

23

24

25

26

27

28

29

30
1

9
INITIATING OOS MOS
REV. EQUIPMENT DESCRIPTION DEVICE
SERVICE P&ID NOTES #
(b) (b)

TR6 MANUAL ACTIVATION FROM CONTROL ROOM HS-005B TRIP PUSHBUTTON (PANEL IN CONTROL ROOM) HTD-PID-021-3 1 C C T T

TR6 IS-003 DEPRESSURISATION OF HP-LOOP 2 C C T T

TR6 HTD-K-002-A/B XV-02104 COMMON DISCHARGE VALVE ZLO-02104 VALVE XV-02104 NOT FULLY OPEN HTD-PID-021-3 3 C C T T

TR6 4

TR6 HTD-K-002A MAKE-UP GAS COMPRESSOR A XS-70172A COMPRESSOR TRIP (WHEN IN OPERATION) HTD-PID-021-1 GENERAL NOTES 1, 3 5 C C T T X

TR6 HTD-K-002B MAKE-UP GAS COMPRESSOR B XS-70172B COMPRESSOR TRIP (WHEN IN OPERATION) HTD-PID-022 -1 GENERAL NOTES 1, 3 6 C C T T X

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

RESET

TR4 HS-005A RESET PUSHBUTTON (DCS) 1

TR6 HS-005C RESET XS-70172A PUSHBUTTON (DCS) GENERAL NOTE 3 2

TR6 HS-005D RESET XS-70172B PUSHBUTTON (DCS) GENERAL NOTE 3 3

9
REV.

TR4

TR4
CAUSE AND EFFECT
CHART FOR UNIT HTD

NOTES
CUSTOMER NAME: Petroperú PROJECT No: 2070

LOCATION: Talara (Perú) UNIT No: HDT GASOILS


SERVICE: Page 9 of 41

HTD-PID-

HTD-PID-
P&ID

006

006
DOCUMENT No:02070-HTD-PRO-TAB-001
Doc Class:
REVISION TR1 TR2 TR3 TR4
16/MAY/2011 06/FEB/2012 25/UL/2012 23/MAR/2015 IS-006

LOW LOW FLOW GAS OIL TO


DATE

GAS OIL FEED TO HP LOOP


ORIG. BY YGF / JEP YGF / LSJ AYG TFC BLOCK FEED TO HP LOOP
APP. BY PSP PSP PSP CGC / MAO

SERVICE

HP LOOP ALARM
LEGEND ABBREVIATIONS USED IN THE CHART:
HH HIGH HIGH C = Close
H HIGH O = Open

VALVE
L LOW
LL LOW LOW I = Start
S = Stop
FMC - FORCE MANUAL CLOSE X = General Action
FMO - FORCE MANUAL OPEN E = Enable

EFFECTS
FUNCTION PERFORMED
OOS - START-UP OVERRIDE SWITCH D = Disable
MOS - MAINTENANCE OVERRIDE SWITCH MR = Manual Reset

LOW LOW FLOW ALARM


SOE - SEQUENCE OF EVENTS RR = Remote Reset
D - DELETED
A = Activate
V = oVerride
REFERENCES: T = Trip
P = Permissive
P&ID No. B = Bypass

CLOSE
HTD-PID-006

DESCRIPTION

FALL-00603 DCS FLOW ALARM


ON-OFF VALVE
XV-00601
ACTUATING
DEVICE
CAUSES #

10

11

12

13

14

15

16

17

18

21

22

23

24

25

26

27

28

29

30
1

9
INITIATING OOS (b) MOS
REV. EQUIPMENT DESCRIPTION DEVICE
SERVICE P&ID NOTES #
General Note 2 (b)

TR4 MANUAL ACTIVATION FROM CONTROL ROOM HS-006B TRIP PUSHBUTTON (PANEL IN CONTROL ROOM) 1 C

TR4 IS-002 TRIP OF FEED TO REACTION SECTION 2 C

TR4 GAS OIL TO HP LOOP FT-00603 A/B/C LOW LOW FLOW AT FEED TO HTD-E-002-A/C LINE (VOTE 2oo3) HS-006C X (*) HTD-PID-006 GENERAL NOTE 1 3 C X

10

11

12

13

14

15

16

17

18

19

20

21

(*) 1 MOS FOR EACH TRANSMITTER 22

23

24

25

RESET

TR4 HS-006A RESET PUSHBUTTON (DCS) 1

9
REV.

TR4

TR4

TR4
CAUSE AND EFFECT

GENERAL NOTE 6
CHART FOR UNIT HTD

NOTE 1

NOTE 1
NOTES
CUSTOMER NAME: Petroperú PROJECT No: 2070

LOCATION: Talara (Perú) UNIT No: HDT GASOILS


SERVICE: Page 10 of 41

HTD-PID-

HTD-PID-
P&ID

N/A
009

008
DOCUMENT No:02070-HTD-PRO-TAB-001
Doc Class:
REVISION TR1 TR2 TR3 TR4 TR5
16/MAY/2011 06/FEB/2012 25/UL/2012 23/MAR/2015 23/NOV/15
IS-007A/B/C/D/E
DATE

TRIP IN HEATER HDT-H-001


TRIP OF FUEL GAS BURNER A/B/C/D/E

TOTAL FUEL GAS BURNER


FAILURE OF BURNER A IN
FUEL GAS TO BURNER A OF
ORIG. BY YGF / JEP YGF / LSJ AYG TFC JLT

HEATER HTD-H-001 VALVE


OF HEATER HTD-H-001
APP. BY PSP PSP PSP CGC / MAO MAO

HEATER HTD-H-001
SERVICE
LEGEND ABBREVIATIONS USED IN THE CHART:
HH HIGH HIGH
H HIGH C = Close
L LOW O = Open
LL LOW LOW I = Start
S = Stop
FMC - FORCE MANUAL CLOSE
FMO - FORCE MANUAL OPEN X = General Action
OOS - START-UP OVERRIDE SWITCH E = Enable

EFFECTS
FUNCTION PERFORMED
MOS - MAINTENANCE OVERRIDE SWITCH D = Disable
SOE - SEQUENCE OF EVENTS

BURNER FAILURE ALARM


D - DELETED MR = Manual Reset
RR = Remote Reset
A = Activate
REFERENCES:

LOGIC ACTIVATE
V = oVerride
P&ID No. T = Trip
HTD-PID-008 P = Permissive
HTD-PID-008 B = Bypass

CLOSE
NOTE 1:. ARRANGEMENT FOR BURNER BLOCK A (IS-
007A). THE DCS PROGRAMMER SHOULD CREATE 5
INTERLOCK BLOCKS, ONE FOR EACH BURNER (IS-
007A/B/C/D/E).

DESCRIPTION

DCS BURNER FAILURE


For IS-007A/B/C/D/E information refer to

ON-OFF VALVE
XV-00975
ACTUATING

00861B
BSAL-

IS-008
DEVICE
CAUSES #

10

11

12

13

14

15

16

17

18

21

22

23

24

25

26

27

28

29

30
1

9
HTD-H-001 vendor document
INITIATING OOS MOS
REV. EQUIPMENT DESCRIPTION DEVICE
SERVICE P&ID NOTES #
(b) (b)

TR4 MANUAL ACTIVATION FROM CONTROL ROOM HS-007AB TRIP PUSHBUTTON (PANEL IN CONTROL ROOM) NOTE 1 1 C X

TR4 IS-008 TOTAL FUEL GAS BURNER TRIP IN HEATER HDT-H-001 2 C

TR4 HTD-H-001 FAILURE OF BURNER A IN HEATER HTD-H-001 BSSL-00861B BURNER FAILURE HTD-PID-008 NOTE 1 3 C X X

TR4 HTD-H-001 ACTIONS DEFINED BY HEATER HTD-H-001 VENDOR 4 C X

V-020700105-T153-HTD-H-001-0018
5

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

RESET

TR4 HS-007AA RESET PUSHBUTTON (DCS) NOTE 1 1

9
REV.

TR4

TR4

TR4

TR4

TR4

TR4

TR4

TR4

TR4

TR4

TR4

TR4
CAUSE AND EFFECT

GENERAL NOTE 5

GENERAL NOTE 5

GENERAL NOTE 4
CHART FOR UNIT HTD

NOTES
PROJECT No: 2070
CUSTOMER NAME: Petroperú
UNIT No: HDT GASOILS
LOCATION: Talara (Perú)
of 41
Page 11

HTD-PID-009

HTD-PID-009

HTD-PID-008

HTD-PID-032

HTD-PID-006

HTD-PID-008

HTD-PID-008

HTD-PID-009

HTD-PID-009

HTD-PID-008
SERVICE:

P&ID

N/A
DOCUMENT No:02070-HTD-PRO-TAB-001
Doc Class:
REVISION TR1 TR2 TR3 TR4 TR5
IS-008

ROG/NG KNOCK OUT DRUM HTD-


A/B/C/D/E OF HEATER HTD-H-
HEATER HTD-H-001 INLET VALVE

LOW LOW FLOW GAS OIL TO


16/MAY/2011 06/FEB/2012 25/UL/2012 23/MAR/2015 23/NOV/15

TRIP OF FUEL GAS BURNER

STACK DAMPER (SOLENOID


DATE

OF HEATER HTD-H-001 LINE TO

HIGH HIGH TEMPERATURE OF

HIGH HIGH TEMPERATURE OF


D-014 LOW LOW LEVEL ALARM
VENT FUEL GAS TO BURNERS
TOTAL FUEL GAS BURNER TRIP IN

HIGH HIGH PRESSURE IN


FUEL GAS TO BURNERS OF
ORIG. BY YGF / JEP YGF / LSJ AYG TFC JLT
HEATER HDT-H-001

ATM AT SAFE LOCATION

HIGH HIGH FUEL GAS


LOW LOW FUEL GAS
APP. BY PSP PSP PSP CGC / MAO MAO

SERVICE

VALVE HYV-00861)

PROCESS OUTLET
HP LOOP ALARM
LEGEND

STACK IN HEATER
ABBREVIATIONS USED IN THE CHART:

HEATER BOX
HH HIGH HIGH

PRESSURE

PRESSURE
H HIGH C = Close
L LOW O = Open
LL LOW LOW I = Start

001
S = Stop
FMC - FORCE MANUAL CLOSE
FMO - FORCE MANUAL OPEN X = General Action
OOS - START-UP OVERRIDE SWITCH E = Enable

HIGH HIGH PRESSURE ALARM

HIGH HIGH PRESSURE ALARM


LOW LOW PRESSURE ALARM
MOS - MAINTENANCE OVERRIDE SWITCH

FUNCTION PERFORMED
D = Disable

HIGH HIGH TEMPERATURE

HIGH HIGH TEMPERATURE


SOE - SEQUENCE OF EVENTS

EFFECTS
MR = Manual Reset

LOW LOW LEVEL ALARM

LOW LOW FLOW ALARM


D - DELETED
RR = Remote Reset
A = Activate
REFERENCES:

LOGIC ACTIVATE
V = oVerride
P&ID No. T = Trip
HTD-PID-006 P = Permissive
HTD-PID-008 B = Bypass

ALARM

ALARM
CLOSE
HTD-PID-009

OPEN

OPEN
HTD-PID-032
INTERLOCK TO BE COMPLETED BY HEATER VENDOR.

OTHER ACTIONS TO DE DEFINED BY HEATER


DESCRIPTION

For IS-008 information refer to


DCS TEMPERATURE ALARM

DCS TEMPERATURE ALARM


MANUAL CONTROL VALVE

DCS PRESSURE ALARM

DCS PRESSURE ALARM

DCS PRESSURE ALARM


DCS LEVEL ALARM

DCS FLOW ALARM


ON-OFF VALVE

ON-OFF VALVE

VENDOR
IS-007A/B/C/D/E

TAHH-00862

PAHH-00863

PAHH-00864

TAHH-00801
FALL-00603

PALL-00864
LALL-03201

HTD-H-001 vendor document


HV-00861
XV-00963

XV-00964
ACTUATING
DEVICE

CAUSES #

10

11

12

13

14

15

16

17

18

21

22

23

24

25

26

27

28

29

30
1

9
DESCRIPTION INITIATING
SERVICE OOS (b) MOS NOTES
REV. EQUIPMENT
DEVICE P&ID #
General Note 2 (b)

TR4 MANUAL ACTIVATION FROM CONTROL ROOM HS-008B TRIP PUSHBUTTON (PANEL IN CONTROL ROOM) 1 C O X O X

V-020700105-T153-HTD-H-001-0018
TR4 HTD-D-014 ROG/NG KNOCK OUT DRUM HTD-D-014 LT-03201 A/B/C DRUM HTD-D-014 HIGH HIGH LEVEL (VOTE 2oo3) X (*) HTD-PID-032 GENERAL NOTE 1 2 C O X O X X

TR4 IS-007A/B/C/D/E TRIP OF 3 FUEL GAS BURNERS OF HEATER HTD-H-001 GENERAL NOTES 3, 6 3 C O X O X

TR4 IS-002 TRIP OF FEED TO REACTION SECTION 4 C O X O X


LOW LOW FLOW AT FEED TO HTD-E-002 A-C LINE (VOTE
TR4 GAS OIL TO HP LOOP FT-00603 A/B/C HS-008C X (*) HTD-PID-006 GENERAL NOTE 1 5 C O X O X X
2oo3)

TR4 HTD-H-001 STACK TEMPERATURE IN HEATER TT-00862 A/B/C HIGH HIGH TEMPERATURE (VOTE 2oo3) X (*) HTD-PID-008 GENERAL NOTE 1 6 C O X O X X

TR4 HTD-H-001 HEATER BOX PRESSURE - (CAMARA DE COMBUSTION) PT-00863 A/B/C HIGH HIGH PRESSURE (VOTE 2oo3) X (*) HTD-PID-008 GENERAL NOTE 1 7 C O X O X X

TR4 HTD-H-001 FUEL GAS PRESSURE PT-00964 A/B/C LOW LOW PRESSURE (VOTE 2oo3) X (*) HTD-PID-009 GENERAL NOTE 1 8 C O X O X X

TR4 HTD-H-001 FUEL GAS PRESSURE PT-00964 A/B/C HIGH HIGH PRESSURE (VOTE 2oo3) X (*) HTD-PID-009 GENERAL NOTE 1 9 C O X O X X

TR4 HTD-H-001 PROCESS OUTLET TEMPERATURE IN HEATER TT-00801 A/B/C HIGH HIGH TEMPERATURE (VOTE 2oo3) X (*) HTD-PID-008 GENERAL NOTE 1 10 C O X O X X
EMERGENCY SHUTDOWN PUSHBUTTON (LOCAL PANEL,
TR4 HTD-H-001 HEATER EMERGENCY SHUTDOWN HSS-00801 HTD-PID-008 11 C O X O X
SAFE DISTANCE FROM HEATER)

TR4 HTD-H-001 ACTIONS DEFINED BY HEATER HTD-H-001 VENDOR 12 C O X O X

13

14

15

16

17

18

19

20

21

(*) 1 MOS FOR EACH TRANSMITTER 22

23

24

25
RESET

TR4 HS-008A RESET PUSHBUTTON (DCS) 1

9
REV.

TR4

TR4

TR4
CAUSE AND EFFECT

GENERAL NOTE 7
CHART FOR UNIT HTD

NOTE 1

NOTE 1
NOTES
CUSTOMER NAME: Petroperú PROJECT No: 2070

LOCATION: Talara (Perú) UNIT No: HDT GASOILS


SERVICE: Page 12 of 41

HTD-PID-

HTD-PID-
P&ID

N/A
008

008
DOCUMENT No:02070-HTD-PRO-TAB-001
Doc Class:
REVISION TR1 TR2 TR3 TR4 TR5
IS-009A/B/C/D/E

FLAME FAILURE OF FLEXI GAS BURNER


DATE 16/MAY/2011 06/FEB/2012 25/UL/2012 23/MAR/2015 23/NOV/15

TRIP OF HEATER HTD-H-001


BURNER A OF HEATER HTD-H-

TOTAL FLEXI GAS BURNER


YGF / JEP YGF / LSJ AYG TFC
TRIP OF FLEXI GAS BURNER
ORIG. BY JLT
A/B/C/D/E OF HEATER HTD-H-001

FLEXI GAS TO FLEXI GAS

A IN FEED HEATER HTD-H-001


APP. BY PSP PSP PSP CGC / MAO MAO

SERVICE
LEGEND ABBREVIATIONS USED IN THE CHART:
HH HIGH HIGH
H HIGH C = Close

001 VALVE
L LOW O = Open
LL LOW LOW I = Start
S = Stop
FMC - FORCE MANUAL CLOSE
FMO - FORCE MANUAL OPEN X = General Action
OOS - START-UP OVERRIDE SWITCH E = Enable

EFFECTS
FUNCTION PERFORMED
MOS - MAINTENANCE OVERRIDE SWITCH D = Disable
SOE - SEQUENCE OF EVENTS MR = Manual Reset
D - DELETED

FLAME FAILURE ALAMR


RR = Remote Reset
A = Activate
REFERENCES:

LOGIC ACTIVATE
V = oVerride
P&ID No. T = Trip
HTD-PID-008 P = Permissive
HTD-PID-009 B = Bypass

CLOSE
NOTE 1:. ARRANGEMENT FOR BURNER BLOCK A (IS-
009A). THE DCS PROGRAMMER SHOULD CREATE 5
INTERLOCK BLOCKS, ONE FOR EACH BURNER (IS-
009A/B/C/D/E).

DESCRIPTION

DCS FLAME FAILURE


For IS-009A/B/C/D/E information refer to

ON-OFF VALVE
XV-00971
ACTUATING

00861C
BSAL-

IS-010
DEVICE
CAUSES #

10

11

12

13

14

15

16

17

18

21

22

23

24

25

26

27

28

29

30
1

9
HTD-H-001 vendor document
INITIATING OOS MOS
REV. EQUIPMENT DESCRIPTION DEVICE
SERVICE P&ID NOTES #
(b) (b)

TR4 MANUAL ACTIVATION FROM CONTROL ROOM HS-009AB TRIP PUSHBUTTON (PANEL IN CONTROL ROOM) NOTE 1 1 C X

TR4 IS-010 TOTAL FLEXI GAS BURNER TRIP OF HEATER HDT-H-001 2 C

TR4 HTD-H-001 FLAME FAILURE OF FLEXI GAS BURNER A IN FEED HEATER HTD-H-001 BSSL-00861C FLAME FAILURE HTD-PID-008 NOTE 1 3 C X X

TR4 HTD-H-001 ACTIONS DEFINED BY HEATER HTD-H-001 VENDOR 4 C X

V-020700105-T153-HTD-H-001-0018
5

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

RESET

TR4 HS-009AA RESET PUSHBUTTON (DCS) NOTE 1 1

9
REV.

TR4

TR4

TR4

TR4

TR4

TR4

TR4

TR4

TR4

TR4
CAUSE AND EFFECT

GENERAL NOTE 5

GENERAL NOTE 5

GENERAL NOTE 4
CHART FOR UNIT HTD

NOTES
CUSTOMER NAME: Petroperú PROJECT No: 2070

LOCATION: Talara (Perú) UNIT No: HDT GASOILS


SERVICE: Page 13 of 41

HTD-PID-

HTD-PID-

HTD-PID-

HTD-PID-

HTD-PID-

HTD-PID-

HTD-PID-

HTD-PID-

HTD-PID-
P&ID

N/A
009

009

008

006

008

008

009

009

008
DOCUMENT No:02070-HTD-PRO-TAB-001
Doc Class:
REVISION TR1 TR2 TR3 TR4 TR5
IS-010

A/B/C/D/E OF HEATER HTD-H-


TRIP OF FLEXI GAS BURNER
16/MAY/2011 06/FEB/2012 25/UL/2012 23/MAR/2015 23/NOV/15

LOW LOW FLOW GAS OIL TO


DATE

STACK DAMPER (SOLENOID


OF HEATER HTD-H-001 LINE TO
VENT FLEXI GAS TO BURNERS

HIGH HIGH TEMPERATURE OF

HIGH HIGH TEMPERATURE OF


TOTAL FLEXI GAS BURNER TRIP OF

HIGH HIGH PRESSURE IN


FLEXI GAS TO BURNERS OF
ORIG. BY YGF / JEP YGF / LSJ AYG TFC JLT

HEATER HTD-H-001 VALVE


HEATER HTD-H-001

HIGH HIGH FLEXI GAS


ATM AT SAFE LOCATION

LOW LOW FLEXI GAS


APP. BY PSP PSP PSP CGC / MAO MAO

SERVICE

VALVE HYV-00861)

HP LOOP ALARM

PROCESS OUTLET
STACK IN HEATER
LEGEND ABBREVIATIONS USED IN THE CHART:

HEATER BOX
HH HIGH HIGH

PRESSURE

PRESSURE
H HIGH C = Close
L LOW O = Open
LL LOW LOW I = Start

001
S = Stop
FMC - FORCE MANUAL CLOSE
FMO - FORCE MANUAL OPEN X = General Action
OOS - START-UP OVERRIDE SWITCH E = Enable

HIGH HIGH PRESSURE ALARM

HIGH HIGH PRESSURE ALARM


LOW LOW PRESSURE ALARM
EFFECTS
FUNCTION PERFORMED
MOS - MAINTENANCE OVERRIDE SWITCH D = Disable

HIGH HIGH TEMPERATURE

HIGH HIGH TEMPERATURE


SOE - SEQUENCE OF EVENTS MR = Manual Reset
D - DELETED

LOW LOW FLOW ALARM


RR = Remote Reset
A = Activate
REFERENCES:

LOGIC ACTIVATE
V = oVerride
P&ID No. T = Trip
HTD-PID-006 P = Permissive
HTD-PID-008 B = Bypass

ALARM

ALARM
CLOSE

OPEN

OPEN
HTD-PID-009
INTERLOCK TO BE COMPLETED BY HEATER VENDOR.

ACTIONS DEFINED BY HEATER HTD-H-001 VENDOR


DESCRIPTION

TAHH-00862 DCS TEMPERATURE ALARM

TAHH-00801 DCS TEMPERATURE ALARM


MANUAL CONTROL VALVE

PAHH-00863 DCS PRESSURE ALARM

PALL-00862 DCS PRESSURE ALARM

PAHH-00862 DCS PRESSURE ALARM


For IS-010 information refer to

FALL-00603 DCS FLOW ALARM


ON-OFF VALVE

ON-OFF VALVE

009A/B/C/D/E

HV-00861
XV-00961

XV-00962
ACTUATING
DEVICE

IS-
CAUSES #

10

11

12

13

14

15

16

17

18

21

22

23

24

25

26

27

28

29

30
1

9
HTD-H-001 vendor document
INITIATING OOS MOS
REV. EQUIPMENT DESCRIPTION DEVICE
SERVICE P&ID NOTES #
(b) (b)

TR4 MANUAL ACTIVATION FROM CONTROL ROOM HS-010B TRIP PUSHBUTTON (PANEL IN CONTROL ROOM) 1 C O X O X
IS-
TR4 TRIP OF 3 FLEXI GAS BURNERS OF HEATER HTD-H-001 GENERAL NOTES 3, 7 2 C O X O X
009A/B/C/D/E
TR4 IS-002 TRIP OF FEED TO REACTION SECTION 3 C O X O X
LOW LOW FLOW AT FEED TO HTD-E-002 A-C LINE (VOTE
TR4 GAS OIL TO HP LOOP FT-00603 A/B/C X (*) HTD-PID-006 GENERAL NOTE 1 4 C O X O X X
2oo3)

V-020700105-T153-HTD-H-001-0018
TR4 HTD-H-001 STACK TEMPERATURE IN HEATER TT-00862 A/B/C HIGH HIGH TEMPERATURE (VOTE 2oo3) X (*) HTD-PID-008 GENERAL NOTE 1 5 C O X O X X
PT-00863
TR4 HTD-H-001 HEATER BOX PRESSURE HIGH HIGH PRESSURE (VOTE 2oo3) X (*) HTD-PID-008 GENERAL NOTE 1 6 C O X O X X
A/B/C
PT-00962
TR4 HTD-H-001 FLEXI GAS PRESSURE LOW LOW PRESSURE (VOTE 2oo3) X (*) HTD-PID-009 GENERAL NOTE 1 7 C O X O X X
A/B/C
PT-00962
TR4 HTD-H-001 FLEXI GAS PRESSURE HIGH HIGH PRESSURE (VOTE 2oo3) X (*) HTD-PID-009 GENERAL NOTE 1 8 C O X O X X
A/B/C
TR4 HTD-H-001 PROCESS OUTLET TEMPERATURE IN HEATER TT-00801 A/B/C HIGH HIGH TEMPERATURE (VOTE 2oo3) X (*) HTD-PID-008 GENERAL NOTE 1 9 C O X O X X
EMERGENCY SHUTDOWN PUSHBUTTON (LOCAL PANEL,
TR4 HTD-H-001 HEATER EMERGENCY SHUTDOWN HSS-00801 HTD-PID-008 10 C O X O X
SAFE DISTANCE FROM HEATER)

TR4 HTD-H-001 ACTIONS DEFINED BY HEATER HTD-H-001 VENDOR 11 C O X O X

12

13

14

15

16

17

18

19

20

21

(*) 1 MOS FOR EACH TRANSMITTER 22

23

24

25

RESET

TR4 HS-010A RESET PUSHBUTTON (DCS) 1

9
REV.

TR4

TR4

TR4
CAUSE AND EFFECT

GENERAL NOTE 5

GENERAL NOTE 8
CHART FOR UNIT HTD

NOTE 1

NOTE 1
NOTES
CUSTOMER NAME: Petroperú PROJECT No: 2070

LOCATION: Talara (Perú) UNIT No: HDT GASOILS


SERVICE: Page 14 of 41

HTD-PID-

HTD-PID-
P&ID

009

008

N/A
DOCUMENT No:02070-HTD-PRO-TAB-001
Doc Class:
REVISION TR1 TR2 TR3 TR4 TR5
IS-012A/B/C/D/E

FAILURE OF PILOT BURNER A IN


DATE 16/MAY/2011 06/FEB/2012 25/UL/2012 23/MAR/2015 23/NOV/15

PILOT GAS TO PILOT BURNER A

TOTAL PILOT BURNER TRIP OF


TRIP OF PILOT BURNER A/B/C/D/E OF

OF HEATER HTD-H-001 VALVE


ORIG. BY YGF / JEP YGF / LSJ AYG TFC JLT
HEATER HTD-H-001
APP. BY PSP PSP PSP CGC / MAO MAO

SERVICE

HEATER HTD-H-001

HEATER HTD-H-001
LEGEND ABBREVIATIONS USED IN THE CHART:
HH HIGH HIGH
H HIGH C = Close
L LOW O = Open
LL LOW LOW I = Start
S = Stop
FMC - FORCE MANUAL CLOSE
FMO - FORCE MANUAL OPEN X = General Action
OOS - START-UP OVERRIDE SWITCH E = Enable

EFFECTS
FUNCTION PERFORMED
MOS - MAINTENANCE OVERRIDE SWITCH D = Disable
SOE - SEQUENCE OF EVENTS MR = Manual Reset

BURNER FAILURE ALARM


D - DELETED
RR = Remote Reset
A = Activate
REFERENCES:

LOGIC ACTIVATE
V = oVerride
P&ID No. T = Trip
HTD-PID-008 P = Permissive
HTD-PID-009 B = Bypass

CLOSE
NOTE 1:. ARRANGEMENT FOR BURNER BLOCK A (IS -
009A). THE DCS PROGRAMMER SHOULD CREATE 5
INTERLOCK BLOCKS, ONE FOR EACH BURNER (IS -
009A/B/C/D/E).

DESCRIPTION
For IS-012A/B/C/D/E information refer to

BSAL-00861A DCS BURNER FAILURE


ON-OFF VALVE
ACTUATING

XV-00979

IS-013
DEVICE
HTD-H-001 vendor document
CAUSES #

10

11

12

13

14

15

16

17

18

21

22

23

24

25

26

27

28

29

30
1

9
DESCRIPTION INITIATING
SERVICE OOS MOS NOTES
REV. EQUIPMENT
DEVICE
P&ID #
(b) (b)

TR4 MANUAL ACTIVATION FROM CONTROL ROOM HS-012AB TRIP PUSHBUTTON (PANEL IN CONTROL ROOM) NOTE 1 1 C X

TR4 IS-013 TOTAL PILOT BURNER TRIP IN HEATER HTD-H-001 2 C

TR4 HTD-H-001 FAILURE OF PILOT BURNER A IN HEATER HTD-H-001 BSSL-00861A BURNER FAILURE HTD-PID-008 NOTE 1 3 C X X

TR4 HTD-H-001 ACTIONS DEFINED BY HEATER HTD-H-001 VENDOR 4 C X

V-020700105-T153-HTD-H-001-0018
5

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

RESET

TR4 RESET PUSHBUTTON (DCS) NOTE 1 1

9
REV.

TR4

TR4

TR4

TR4

TR4
CAUSE AND EFFECT

GENERAL NOTE 5

GENERAL NOTE 5
CHART FOR UNIT HTD

NOTES
CUSTOMER NAME: Petroperú PROJECT No: 2070

LOCATION: Talara (Perú) UNIT No: HDT GASOILS


SERVICE: Page 15 of 41

HTD-PID-

HTD-PID-

HTD-PID-
P&ID

N/A

009

009

008
DOCUMENT No:02070-HTD-PRO-TAB-001
Doc Class:
REVISION TR1 TR2 TR3 TR4 TR5
IS-013

A/B/C/D/E OF HEATER HTD-H-

NATURAL GAS TO BURNERS


DATE 16/MAY/2011 06/FEB/2012 25/UL/2012 23/MAR/2015 23/NOV/15

OF HEATER HTD-H-001 LINE


TO ATM AT SAFE LOCATION
BURNERS OF HEATER HTD-H-
YGF / JEP YGF / LSJ AYG TFC
TOTAL PILOT BURNER TRIP OF
ORIG. BY JLT

TRIP OF PILOT BURNER


HEATER HTD-H-001

NATURAL GAS TO PILOT

LOW LOW PILOT GAS


APP. BY PSP PSP PSP CGC / MAO MAO

SERVICE
LEGEND ABBREVIATIONS USED IN THE CHART:

PRESSURE
HH HIGH HIGH C = Close

001 VALVE
H HIGH O = Open
L LOW
LL LOW LOW I = Start

001
S = Stop
FMC - FORCE MANUAL CLOSE X = General Action
FMO - FORCE MANUAL OPEN E = Enable

LOW LOW PRESSURE ALARM


EFFECTS
FUNCTION PERFORMED
OOS - START-UP OVERRIDE SWITCH D = Disable
MOS - MAINTENANCE OVERRIDE SWITCH MR = Manual Reset
SOE - SEQUENCE OF EVENTS RR = Remote Reset
D - DELETED
A = Activate

LOGIC ACTIVATE
V = oVerride
REFERENCES: T = Trip
P = Permissive
P&ID No. B = Bypass

CLOSE
HTD-PID-008

OPEN
HTD-PID-009

ACTIONS DEFINED BY HEATER HTD-H-001 VENDOR


INTERLOCK TO BE COMPLETED BY HEATER VENDOR.

DESCRIPTION

PALL-00968 DCS PRESSURE ALARM


For IS-013 information refer to

ON-OFF VALVE

ON-OFF VALVE
012A/B/C/D/E

XV-00965

XV-00966
ACTUATING
DEVICE

IS-
CAUSES #

10

11

12

13

14

15

16

17

18

21

22

23

24

25

26

27

28

29

30
1

9
HTD-H-001 vendor document
INITIATING OOS MOS
REV. EQUIPMENT DESCRIPTION DEVICE
SERVICE P&ID NOTES #
(b) (b)

TR4 MANUAL ACTIVATION FROM CONTROL ROOM HS-013B TRIP PUSHBUTTON (PANEL IN CONTROL ROOM) 1 X C O X
IS-
TR4 TRIP OF 3 PILOT BURNERS OF HEATER HTD-H-001 GENERAL NOTES 3, 8 2 X C O X
012A/B/C/D/E
TR4 IS-003 DEPRESSURISATION OF HP-LOOP 3 X C O X
PT-00968
TR4 HTD-H-001 PILOT GAS LINE LOW LOW PRESSURE AT PILOT GAS LINE (VOTE 2oo3) X (*) HTD-PID-009 GENERAL NOTE 1 4 X C O X X
A/B/C
EMERGENCY SHUTDOWN PUSHBUTTON (LOCAL PANEL,
TR4 HTD-H-001 HEATER EMERGENCY SHUTDOWN HSS-00801 HTD-PID-008 5 X C O X

V-020700105-T153-HTD-H-001-0018
SAFE DISTANCE FROM HEATER)

TR4 HTD-H-001 ACTIONS DEFINED BY HEATER HTD-H-001 VENDOR 6 X C O X

10

11

12

13

14

15

16

17

18

19

20

21

(*) 1 MOS FOR EACH TRANSMITTER 22

23

24

25

RESET

TR4 HS-013A RESET PUSHBUTTON (DCS) 1

9
REV.

TR4

TR4
CAUSE AND EFFECT
CHART FOR UNIT HTD

NOTES
CUSTOMER NAME: Petroperú PROJECT No: 2070

LOCATION: Talara (Perú) UNIT No: HDT GASOILS


SERVICE: Page 16 of 41

HTD-PID-

HTD-PID-
P&ID

012

012
DOCUMENT No:02070-HTD-PRO-TAB-001
Doc Class:
REVISION TR1 TR2 TR3 TR4
16/MAY/2011 06/FEB/2012 25/UL/2012 23/MAR/2015
IS-014
DATE

HTD-D-002 LOW LOW LEVEL


TRIP OF LIQUID FROM HP HOT

VALVE ON HC STREAM OF HP
ORIG. BY YGF / JEP YGF / LSJ AYG TFC
SEPARATOR HTD-D-002

SEPARATOR HTD-H-002
APP. BY PSP PSP PSP CGC / MAO

SERVICE
LEGEND ABBREVIATIONS USED IN THE CHART:
HH HIGH HIGH C = Close
H HIGH O = Open

ALARM
L LOW
LL LOW LOW I = Start
S = Stop
FMC - FORCE MANUAL CLOSE X = General Action
FMO - FORCE MANUAL OPEN E = Enable

EFFECTS
FUNCTION PERFORMED
OOS - START-UP OVERRIDE SWITCH D = Disable
MOS - MAINTENANCE OVERRIDE SWITCH MR = Manual Reset

LOW LOW LEVEL ALARM


SOE - SEQUENCE OF EVENTS RR = Remote Reset
D - DELETED
A = Activate
V = oVerride
REFERENCES: T = Trip
P = Permissive
P&ID No. B = Bypass

CLOSE
HTD-PID-012

DESCRIPTION

LALL-01203 DCS LEVEL ALARM


ON-OFF VALVE
XV-01201
ACTUATING
DEVICE
CAUSES #

10

11

12

13

14

15

16

17

18

21

22

23

24

25

26

27

28

29

30
1

9
INITIATING OOS MOS
REV. EQUIPMENT DESCRIPTION DEVICE
SERVICE P&ID NOTES #
(b) (b)

TR4 MANUAL ACTIVATION FROM CONTROL ROOM HS-014B TRIP PUSHBUTTON (PANEL IN CONTROL ROOM) 1 C

TR4 HTD-D-002 HP HOT SEPARATOR LT-01203 A/B/C DRUM HTD-D-002 LOW LOW LEVEL (VOTE 2oo3) X (*) HTD-PID-012 GENERAL NOTE 1 2 C X

10

11

12

13

14

15

16

17

18

19

20

21

(*) 1 MOS FOR EACH TRANSMITTER 22

23

24

25

RESET

TR4 HS-014A RESET PUSHBUTTON (DCS) 1

9
REV.

TR4

TR4
CAUSE AND EFFECT
CHART FOR UNIT HTD

NOTES
CUSTOMER NAME: Petroperú PROJECT No: 2070

LOCATION: Talara (Perú) UNIT No: HDT GASOILS


SERVICE: Page 17 of 41

HTD-PID-

HTD-PID-
P&ID

014

014
DOCUMENT No:02070-HTD-PRO-TAB-001
Doc Class:
REVISION TR1 TR2 TR3 TR4 IS-015
DATE 16/MAY/2011 06/FEB/2012 25/UL/2012 23/MAR/2015 TRIP OF HYDROCARBON LIQUID

HYDROCARBON LEVEL ALARM


ORIG. BY YGF / JEP YGF / LSJ AYG TFC FROM HP COLD SEPARATOR HTD-D-

VALVE DOWN STREAM ON


HYDROCARBON LIQUID
APP. BY PSP PSP PSP CGC / MAO 003

SERVICE

HTD-D-003 LOW LOW


LEGEND ABBREVIATIONS USED IN THE CHART:
HH HIGH HIGH C = Close
H HIGH O = Open
L LOW
LL LOW LOW I = Start
S = Stop
FMC - FORCE MANUAL CLOSE X = General Action
FMO - FORCE MANUAL OPEN E = Enable

EFFECTS
FUNCTION PERFORMED
OOS - START-UP OVERRIDE SWITCH D = Disable
MOS - MAINTENANCE OVERRIDE SWITCH MR = Manual Reset

LOW LOW LEVEL ALARM


SOE - SEQUENCE OF EVENTS RR = Remote Reset
D - DELETED
A = Activate
V = oVerride
REFERENCES: T = Trip
P = Permissive
P&ID No. B = Bypass

CLOSE
HTD-PID-014

DESCRIPTION

LALL-01403 DCS LEVEL ALARM


ON-OFF VALVE
XV-01402
ACTUATING
DEVICE
CAUSES #

10

11

12

13

14

15

16

17

18

21

22

23

24

25

26

27

28

29

30
1

9
INITIATING OOS MOS
REV. EQUIPMENT DESCRIPTION DEVICE
SERVICE P&ID NOTES #
(b) (b)

TR4 MANUAL ACTIVATION FROM CONTROL ROOM HS-015B TRIP PUSHBUTTON (PANEL IN CONTROL ROOM) 1 C

TR4 HTD-D-003 HP COLD SEPARATOR LT-01403 A/B/C DRUM HTD-D-003 LOW LOW LEVEL (VOTE 2oo3) X (*) HTD-PID-014 GENERAL NOTE 1 2 C X

10

11

12

13

14

15

16

17

18

19

20

21

(*) 1 MOS FOR EACH TRANSMITTER 22

23

24

25

RESET

TR4 HS-015A RESET PUSHBUTTON (DCS) 1

9
REV.
CAUSE AND EFFECT
CHART FOR UNIT HTD

NOTES
CUSTOMER NAME: Petroperú PROJECT No: 2070

LOCATION: Talara (Perú) UNIT No: HDT GASOILS


SERVICE: Page 18 of 41

HTD-PID-

HTD-PID-
P&ID

014

014
DOCUMENT No:02070-HTD-PRO-TAB-001
Doc Class:
REVISION TR1 TR2 TR3 TR4
IS-016

HTD-D-003 LOW LOW WATER


DATE 16/MAY/2011 06/FEB/2012 25/UL/2012 23/MAR/2015
YGF / JEP YGF / LSJ AYG TFC
TRIP OF WATER FROM HP COLD
ORIG. BY
SEPARATOR HTD-D-003

VALVE ON SOUR WATER


APP. BY PSP PSP PSP CGC / MAO

SERVICE
LEGEND ABBREVIATIONS USED IN THE CHART:

LEVEL ALARM
HH HIGH HIGH C = Close
H HIGH O = Open

OUTLET
L LOW
LL LOW LOW I = Start
S = Stop
FMC - FORCE MANUAL CLOSE X = General Action
FMO - FORCE MANUAL OPEN E = Enable

EFFECTS
FUNCTION PERFORMED
OOS - START-UP OVERRIDE SWITCH D = Disable
MOS - MAINTENANCE OVERRIDE SWITCH MR = Manual Reset

LOW LOW LEVEL ALARM


SOE - SEQUENCE OF EVENTS RR = Remote Reset
D - DELETED
A = Activate
V = oVerride
REFERENCES: T = Trip
P = Permissive
P&ID No. B = Bypass

CLOSE
HTD-PID-014

DESCRIPTION

LALL-01402 DCS LEVEL ALARM


ON-OFF VALVE
XV-01401
ACTUATING
DEVICE
CAUSES #

10

11

12

13

14

15

16

17

18

21

22

23

24

25

26

27

28

29

30
1

9
INITIATING OOS MOS
REV. EQUIPMENT DESCRIPTION DEVICE
SERVICE P&ID NOTES #
(b) (b)

TR4 MANUAL ACTIVATION FROM CONTROL ROOM HS-016B TRIP PUSHBUTTON (PANEL IN CONTROL ROOM) 1 C

TR4 HTD-D-003 HP COLD SEPARATOR LT-01402 A/B/C DRUM HTD-D-003 LOW LOW LEVEL (VOTE 2oo3) X (*) HTD-PID-014 GENERAL NOTE 1 2 C X

10

11

12

13

14

15

16

17

18

19

20

21

(*) 1 MOS FOR EACH TRANSMITTER 22

23

24

25

RESET

TR4 HS-016A RESET PUSHBUTTON (DCS) 1

9
REV.

TR4

TR4

TR4

TR4
CAUSE AND EFFECT
CHART FOR UNIT HTD

NOTES
CUSTOMER NAME: Petroperú PROJECT No: 2070

LOCATION: Talara (Perú) UNIT No: HDT GASOILS


SERVICE: Page 19 of 41

HTD-PID-

HTD-PID-

HTD-PID-

HTD-PID-
P&ID

023

023

017

017
DOCUMENT No:02070-HTD-PRO-TAB-001
Doc Class:
REVISION TR1 TR2 TR3 TR4
IS-018

VALVE FOR LIQUID FEED TO

VALVE FOR LIQUID FEED TO


DATE 16/MAY/2011 06/FEB/2012 25/UL/2012 23/MAR/2015

HIGH HIGH LEVEL IN PRODUCT

PRODUCT STRIPPER C-001.

PRODUCT STRIPPER C-001


YGF / JEP YGF / LSJ AYG TFC
TRIP OF STEAM TO PRODUCT
ORIG. BY

(SOLENOID VALVE FYV-


STRIPPER HTD-C-001

VALVE FOR STEAM TO


PRODUCT STRIPPER
APP. BY PSP PSP PSP CGC / MAO

SERVICE
LEGEND ABBREVIATIONS USED IN THE CHART:

STRIPPER ALARM
HH HIGH HIGH C = Close
H HIGH O = Open
L LOW

01702)
LL LOW LOW I = Start
S = Stop
FMC - FORCE MANUAL CLOSE X = General Action
FMO - FORCE MANUAL OPEN E = Enable

EFFECTS
FUNCTION PERFORMED
OOS - START-UP OVERRIDE SWITCH D = Disable
MOS - MAINTENANCE OVERRIDE SWITCH

HIGH HIGH LEVEL ALARM


MR = Manual Reset
SOE - SEQUENCE OF EVENTS RR = Remote Reset
D - DELETED
A = Activate
V = oVerride
REFERENCES: T = Trip
P = Permissive
P&ID No. B = Bypass

CLOSE

CLOSE

CLOSE
HTD-PID-023
HTD-PID-017

SIL REQUIREMENT: SIL 2

DESCRIPTION

LAHH-2301 DCS LEVEL ALARM

CONTROL VALVE
ON-OFF VALVE

HAND VAÑVE
HV-01702

FV-01702
ACTUATING

XV-2301
DEVICE
CAUSES #

10

11

12

13

14

15

16

17

18

21

22

23

24

25

26

27

28

29

30
1

9
INITIATING OOS MOS
REV. EQUIPMENT DESCRIPTION DEVICE
SERVICE P&ID NOTES #
(b) (b)

TR4 MANUAL ACTIVATION FROM CONTROL ROOM HS-018B TRIP PUSHBUTTON (PANEL IN CONTROL ROOM) 1 C C C

TR4 HTD-C-001 PRODUCT STRIPPER LT-2301 A/B/C HTD-C-001 HIGH HIGH LEVEL (VOTE 2oo3) X (*) HTD-PID-023 GENERAL NOTE 1 2 C X C C

10

11

12

13

14

15

16

17

18

19

20

21

(*) 1 MOS FOR EACH TRANSMITTER 22

23

24

25

RESET

TR4 HS-018A RESET PUSHBUTTON (DCS) 1

9
REV.

TR4

TR4

TR4
CAUSE AND EFFECT
CHART FOR UNIT HTD

NOTES
CUSTOMER NAME: Petroperú PROJECT No: 2070

LOCATION: Talara (Perú) UNIT No: HDT GASOILS


SERVICE: Page 20 of 41

HTD-PID-

HTD-PID-

HTD-PID-
P&ID

026

026

023
Doc Class: DOCUMENT No:02070-HTD-PRO-TAB-001

REVISION TR1 TR2 TR3 TR4


16/MAY/2011 06/FEB/2012 25/UL/2012 23/MAR/2015
IS-019
DATE

LOW LOW LEVEL IN PRODUCT


YGF / JEP YGF / LSJ AYG TFC
TRIP OF GASOIL PRODUCT PUMP P-

GASOIL PRODUCT PUMP

GASOIL PRODUCT PUMP


ORIG. BY
008-A/B
APP. BY PSP PSP PSP CGC / MAO

SERVICE
LEGEND ABBREVIATIONS USED IN THE CHART:

STRIPPER ALARM
HH HIGH HIGH C = Close

MOTOR A

MOTOR B
H HIGH O = Open
L LOW
LL LOW LOW I = Start
S = Stop
FMC - FORCE MANUAL CLOSE X = General Action
FMO - FORCE MANUAL OPEN E = Enable

EFFECTS
OOS - START-UP OVERRIDE SWITCH

FUNCTION PERFORMED
D = Disable
MOS - MAINTENANCE OVERRIDE SWITCH MR = Manual Reset

LOW LOW LEVEL ALARM


SOE - SEQUENCE OF EVENTS RR = Remote Reset
D - DELETED
A = Activate
V = oVerride
REFERENCES: T = Trip
P = Permissive
P&ID No. B = Bypass
HTD-PID-023

STOP

STOP
HTD-PID-026

INDIVIDUAL PUMP TRIPS TO BE SPECIFIED BY


VENDOR.

DESCRIPTION

LALL-02301 DCS LEVEL ALARM


MOTOR PUMP

MOTOR PUMP
MX-00601

MX-00602
ACTUATING
DEVICE
CAUSES #

10

11

12

13

14

15

16

17

18

21

22

23

24

25

26

27

28

29

30
1

9
INITIATING OOS MOS
REV. EQUIPMENT DESCRIPTION DEVICE
SERVICE P&ID NOTES #
(b) (b)

TR4 MANUAL ACTIVATION FROM CONTROL ROOM HS-019B TRIP PUSHBUTTON (PANEL IN CONTROL ROOM) 1 S S

TR4 HTD-C-001 PRODUCT STRIPPER LT-02301 A/B/C HTD-C-001 LOW LOW LEVEL (VOTE 2oo3) X (*) HTD-PID-023 GENERAL NOTE 1 2 S S X
MYS-02601
TR4 HTD-P-008-A/B GASOIL PRODUCT PUMPS BOTH PUMPS NOT RUNNING HTD-PID-026 GENERAL NOTES 1, 3 3 S S
MYS-02602

TR4 HTD-P-008-A/B MOV-02301 UPSTREAM HTD-P-008-A/B MHS-02301G MOV-02301 CLOSE PUSHBUTTON (DCS) HTD-PID-023 4 S S

TR4 HTD-P-008-A/B MOV-02301 UPSTREAM HTD-P-008-A/B MHS-02301CC MOV-02301 CLOSE PUSHBUTTON (LOCAL PANEL) HTD-PID-023 5 S S

TR4 HTD-P-008-A/B MOV-02301 UPSTREAM HTD-P-008-A/B MZSO-02301 VALVE MOV-02301 NOT FULLY OPEN HTD-PID-023 6 S S

10

11

12

13

14

15

16

17

18

19

20

21

(*) 1 MOS FOR EACH TRANSMITTER 22

23

24

25

RESET

TR4 HS-019A RESET PUSHBUTTON (DCS) 1

9
REV.

TR4

TR4

TR4

TR4
CAUSE AND EFFECT

GENERAL NOTE 4
CHART FOR UNIT HTD

NOTES
CUSTOMER NAME: Petroperú PROJECT No: 2070

LOCATION: Talara (Perú) UNIT No: HDT GASOILS


SERVICE: Page 21 of 41

HTD-PID-

HTD-PID-

HTD-PID-

HTD-PID-
030-2

030-2

030-2

030-1
P&ID
DOCUMENT No:02070-HTD-PRO-TAB-001
Doc Class:
REVISION TR1 TR2 TR3 TR4 TR6
IS-020

WASH WATER PUMP MOTOR

WASH WATER PUMP MOTOR


DATE 16/MAY/2011 06/FEB/2012 25/UL/2012 23/MAR/2015 30/SEP/2016
TRIP OF WASH WATER PUMPS P-006-

VALVE ON HTD-P-006-A/B
ORIG. BY YGF / JEP YGF / LSJ AYG TFC TFC

LOW LOW LEVEL IN WASH


A/B

WATER DRUM HTD-D-007


APP. BY PSP PSP PSP CGC / MAO MAO

SERVICE

DISCHARGE LINE
LEGEND ABBREVIATIONS USED IN THE CHART:
HH HIGH HIGH
H HIGH C = Close
L LOW O = Open

ALARM
LL LOW LOW I = Start
S = Stop

B
FMC - FORCE MANUAL CLOSE X = General Action
FMO - FORCE MANUAL OPEN
OOS - START-UP OVERRIDE SWITCH E = Enable

EFFECTS
FUNCTION PERFORMED
MOS - MAINTENANCE OVERRIDE SWITCH D = Disable
SOE - SEQUENCE OF EVENTS MR = Manual Reset

LOW LOW LEVEL ALARM


D - DELETED RR = Remote Reset
A = Activate
REFERENCES: V = oVerride
T = Trip
P&ID No. P = Permissive
HTD-PID-030-1 B = Bypass

CLOSE
HTD-PID-030-2

STOP

STOP
INDIVIDUAL PUMP TRIPS TO BE SPECIFIED BY
VENDOR.

DESCRIPTION

LALL-03001 DCS LEVEL ALARM


ON-OFF VALVE
MOTOR PUMP

MOTOR PUMP
MX-03001

MX-03002

XY-03002
ACTUATING
DEVICE
CAUSES #

10

11

12

13

14

15

16

17

18

21

22

23

24

25

26

27

28

29

30
1

9
INITIATING OOS MOS
REV. EQUIPMENT DESCRIPTION DEVICE
SERVICE P&ID NOTES #
(b) (b)

TR4 MANUAL ACTIVATION FROM CONTROL ROOM HS-020B TRIP PUSHBUTTON (PANEL IN CONTROL ROOM) 1 S S C

TR4 HTD-D-007 WASH WATER SURGE DRUM LT-03001 A/B/C DRUM HTD-D-007 LOW LOW LEVEL (VOTE 2oo3) X (*) HTD-PID-030-1 GENERAL NOTE 1 2 S S C X
MYS-03001
TR4 HTD-P-006-A/B WASH WATER PUMPS BOTH PUMPS NOT RUNNING HTD-PID-030-2 GENERAL NOTES 1, 3 3 S S C
MYS-03002
TR4 IS-003 DEPRESSURISATION OF HP-LOOP 4 S S C

10

11

12

13

14

15

16

17

18

19

20

21

(*) 1 MOS FOR EACH TRANSMITTER 22

23

24

25

RESET

TR4 HS-020A RESET PUSHBUTTON (DCS) 1

TR6 HS-020C FINAL ELEMENT RESET PUSHBUTTON (DCS) 2

9
REV.

TR4

TR4
CAUSE AND EFFECT
CHART FOR UNIT HTD

NOTES
CUSTOMER NAME: Petroperú PROJECT No: 2070

LOCATION: Talara (Perú) UNIT No: HDT GASOILS


SERVICE: Page 22 of 41

HTD-PID-

HTD-PID-
030-1

030-1
P&ID
DOCUMENT No:02070-HTD-PRO-TAB-001
Doc Class:
REVISION TR1 TR2 TR3 TR4
IS-021

VALVE ON BOILER FEED WATER


DATE 16/MAY/2011 06/FEB/2012 25/UL/2012 23/MAR/2015
YGF / JEP YGF / LSJ AYG TFC
TRIP OF WATER TO WASH WATER
ORIG. BY

HIGH HIGH LEVEL IN WASH


SURGE DRUM HTD-D-007

WATER DRUM HTD-D-007


APP. BY PSP PSP PSP CGC / MAO

SERVICE
LEGEND ABBREVIATIONS USED IN THE CHART:

LINE FROM BL
HH HIGH HIGH C = Close
H HIGH O = Open

ALARM
L LOW
LL LOW LOW I = Start
S = Stop
FMC - FORCE MANUAL CLOSE X = General Action
FMO - FORCE MANUAL OPEN E = Enable

EFFECTS
FUNCTION PERFORMED
OOS - START-UP OVERRIDE SWITCH D = Disable
MOS - MAINTENANCE OVERRIDE SWITCH

HIGH HIGH LEVEL ALARM


MR = Manual Reset
SOE - SEQUENCE OF EVENTS RR = Remote Reset
D - DELETED
A = Activate
V = oVerride
REFERENCES: T = Trip
P = Permissive
P&ID No. B = Bypass

CLOSE
HTD-PID-030-1

DESCRIPTION

LAHH-03001 DCS LEVEL ALARM


ON-OFF VALVE
XV-03001
ACTUATING
DEVICE
CAUSES #

10

11

12

13

14

15

16

17

18

21

22

23

24

25

26

27

28

29

30
1

9
INITIATING OOS MOS
REV. EQUIPMENT DESCRIPTION DEVICE
SERVICE P&ID NOTES #
(b) (b)

TR4 MANUAL ACTIVATION FROM CONTROL ROOM HS-021B TRIP PUSHBUTTON (PANEL IN CONTROL ROOM) 1 C

TR4 HTD-D-007 WASH WATER SURGE DRUM LT-03001 A/B/C HTD-D-007 HIGH HIGH LEVEL (VOTE 2oo3) X (*) HTD-PID-030-1 GENERAL NOTE 1 2 C X

10

11

12

13

14

15

16

17

18

19

20

21

(*) 1 MOS FOR EACH TRANSMITTER 22

23

24

25

RESET

TR4 HS-021A RESET PUSHBUTTON (DCS) 1

9
REV.

TR4

TR4

TR4

TR4
CAUSE AND EFFECT
CHART FOR UNIT HTD

NOTES
CUSTOMER NAME: Petroperú PROJECT No: 2070

LOCATION: Talara (Perú) UNIT No: HDT GASOILS


SERVICE: Page 23 of 41

HTD-PID-

HTD-PID-

HTD-PID-

HTD-PID-
P&ID

037

037

037

037
DOCUMENT No:02070-HTD-PRO-TAB-001
Doc Class:
REVISION TR1 TR2 TR3 TR4
IS-022

NON CRACKED SLOPS PUMP

NON CRACKED SLOPS PUMP


16/MAY/2011 06/FEB/2012 25/UL/2012 23/MAR/2015

CRACKED SLOPS DRUM HTD-D-


DATE

HIGH HIGH TEMPERATURE


TRIP OF NON CRACKED SLOPS PUMP

IN NON CRACKED SLOPS


ORIG. BY YGF / JEP YGF / LSJ AYG TFC
(HTD-P-011 A/B)

COOLER OUTLET LINE


LOW LOW LEVEL IN NON
APP. BY PSP PSP PSP CGC / MAO

SERVICE
LEGEND ABBREVIATIONS USED IN THE CHART:
HH HIGH HIGH C = Close

019 ALARM
MOTOR A

MOTOR B
H HIGH O = Open

ALARM
L LOW
LL LOW LOW I = Start
S = Stop
FMC - FORCE MANUAL CLOSE X = General Action
FMO - FORCE MANUAL OPEN E = Enable

EFFECTS
FUNCTION PERFORMED
OOS - START-UP OVERRIDE SWITCH D = Disable

HIGH HIGH TEMPERATURE


MOS - MAINTENANCE OVERRIDE SWITCH MR = Manual Reset

LOW LOW LEVEL ALARM


SOE - SEQUENCE OF EVENTS RR = Remote Reset
D - DELETED
A = Activate
V = oVerride
REFERENCES: T = Trip
P = Permissive
P&ID No. B = Bypass

ALARM
HTD-PID-037

STOP

STOP
DESCRIPTION

TAHH-03704 DCS TEMPERATURE ALARM


LALL-03701 DCS LEVEL ALARM
MOTOR PUMP

MOTOR PUMP
MX-03701

MX-03702
ACTUATING
DEVICE
CAUSES #

10

11

12

13

14

15

16

17

18

21

22

23

24

25

26

27

28

29

30
1

9
INITIATING OOS MOS
REV. EQUIPMENT DESCRIPTION DEVICE
SERVICE P&ID NOTES #
(b) (b)

TR4 MANUAL ACTIVATION FROM CONTROL ROOM HS-022B TRIP PUSHBUTTON (PANEL IN CONTROL ROOM) 1 S S

TR4 HTD-D-019 NON CRACKED SLOPS DRUM LT-03701 LOW LOW LEVEL AT DRUM HTD-D-019 X HTD-PID-037 GENERAL NOTE 1 2 S S X
HIGH HIGH TEMPERATURE AT NON CRACKED SLOPS
TR4 NON CRACKED SLOPS COOLER OUTLET LINE TT-03704 X HTD-PID-037 GENERAL NOTE 1 3 S S X
COOLER OUTLET LINE

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

RESET

TR4 HS-022A RESET PUSHBUTTON (DCS) 1

9
REV.

TR4

TR4

TR4

TR4
CAUSE AND EFFECT
CHART FOR UNIT HTD

NOTES
CUSTOMER NAME: Petroperú PROJECT No: 2070

LOCATION: Talara (Perú) UNIT No: HDT GASOILS


SERVICE: Page 24 of 41

HTD-PID-

HTD-PID-

HTD-PID-

HTD-PID-
P&ID

038

038

038

037
DOCUMENT No:02070-HTD-PRO-TAB-001
Doc Class:
REVISION TR1 TR2 TR3 TR4
IS-023

IN CRACKED SLOPS COOLER


SLOPS DRUM HTD-D-020 ALARM
DATE 16/MAY/2011 06/FEB/2012 25/UL/2012 23/MAR/2015

HIGH HIGH TEMPERATURE


LOW LOW LEVEL IN CRACKED
YGF / JEP YGF / LSJ AYG TFC
TRIP OF CRACKED SLOPS PUMP (HTD-
ORIG. BY

CRACKED SLOPS PUMP

CRACKED SLOPS PUMP


P-012 A/B)

OUTLET LINE ALARM


APP. BY PSP PSP PSP CGC / MAO

SERVICE
LEGEND ABBREVIATIONS USED IN THE CHART:
HH HIGH HIGH C = Close

MOTOR A

MOTOR B
H HIGH O = Open
L LOW
LL LOW LOW I = Start
S = Stop
FMC - FORCE MANUAL CLOSE X = General Action
FMO - FORCE MANUAL OPEN E = Enable

EFFECTS
FUNCTION PERFORMED
OOS - START-UP OVERRIDE SWITCH D = Disable

HIGH HIGH TEMPERATURE


MOS - MAINTENANCE OVERRIDE SWITCH MR = Manual Reset

LOW LOW LEVEL ALARM


SOE - SEQUENCE OF EVENTS RR = Remote Reset
D - DELETED
A = Activate
V = oVerride
REFERENCES: T = Trip
P = Permissive
P&ID No. B = Bypass

ALARM
HTD-PID-038

STOP

STOP
DESCRIPTION

TAHH-03704 DCS TEMPERATURE ALARM


LALL-03801 DCS LEVEL ALARM
MOTOR PUMP

MOTOR PUMP
MX-03801

MX-03802
ACTUATING
DEVICE
CAUSES #

10

11

12

13

14

15

16

17

18

21

22

23

24

25

26

27

28

29

30
1

9
INITIATING OOS MOS
REV. EQUIPMENT DESCRIPTION DEVICE
SERVICE P&ID NOTES #
(b) (b)

TR4 MANUAL ACTIVATION FROM CONTROL ROOM HS-023B TRIP PUSHBUTTON (PANEL IN CONTROL ROOM) 1 S S

TR4 HTD-D-020 CRACKED SLOPS DRUM LT-03801 LOW LOW LEVEL AT DRUM HTD-D-020 X HTD-PID-038 GENERAL NOTE 1 2 S S X
HIGH HIGH TEMPERATURE AT CRACKED SLOPS COOLER
TR4 CRACKED SLOPS COOLER OUTLET LINE TT-03804 X HTD-PID-038 GENERAL NOTE 1 3 S S X
OUTLET LINE

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

RESET

TR4 HS-023A RESET PUSHBUTTON (DCS) 1

9
REV.

TR4

TR4
CAUSE AND EFFECT
CHART FOR UNIT HTD

NOTES
CUSTOMER NAME: Petroperú PROJECT No: 2070

LOCATION: Talara (Perú) UNIT No: HDT GASOILS


SERVICE: Page 25 of 41

HTD-PID-

HTD-PID-
P&ID

017

017
DOCUMENT No:02070-HTD-PRO-TAB-001
Doc Class:
REVISION TR1 TR2 TR3 TR4
16/MAY/2011 06/FEB/2012 25/UL/2012 23/MAR/2015
IS-024
DATE

SEPARATOR HTD-D-005-ALARM
WATER BOTTOM OUTLET LINE
TRIP OF SOUR WATER FROM HTD-D-

LOW LOW LEVEL IN LP COLD


VALVE ON HTD-D-005-SOUR
ORIG. BY YGF / JEP YGF / LSJ AYG TFC
005
APP. BY PSP PSP PSP CGC / MAO

SERVICE
LEGEND ABBREVIATIONS USED IN THE CHART:
HH HIGH HIGH C = Close
H HIGH O = Open
L LOW
LL LOW LOW I = Start
S = Stop
FMC - FORCE MANUAL CLOSE X = General Action
FMO - FORCE MANUAL OPEN E = Enable

EFFECTS
FUNCTION PERFORMED
OOS - START-UP OVERRIDE SWITCH D = Disable
MOS - MAINTENANCE OVERRIDE SWITCH MR = Manual Reset

LOW LOW LEVEL ALARM


SOE - SEQUENCE OF EVENTS RR = Remote Reset
D - DELETED
A = Activate
V = oVerride
REFERENCES: T = Trip
P = Permissive
P&ID No. B = Bypass

CLOSE
HTD-PID-017

DESCRIPTION

LALL-01703 DCS LEVEL ALARM


ON-OFF VALVE
XV-01701
ACTUATING
DEVICE
CAUSES #

10

11

12

13

14

15

16

17

18

21

22

23

24

25

26

27

28

29

30
1

9
INITIATING OOS MOS
REV. EQUIPMENT DESCRIPTION DEVICE
SERVICE P&ID NOTES #
(b) (b)

TR4 MANUAL ACTIVATION FROM CONTROL ROOM HS-024B TRIP PUSHBUTTON (PANEL IN CONTROL ROOM) 1 C

TR4 HTD-D-005 LP COLD SEPARATOR LT-01703 A/B/C DRUM HTD-D-005-LOW LOW LEVEL (VOTE 2oo3) X (*) HTD-PID-017 GENERAL NOTE 1 2 C X

10

11

12

13

14

15

16

17

18

19

20

21

(*) 1 MOS FOR EACH TRANSMITTER 22

23

24

25

RESET

TR4 HS-024A RESET PUSHBUTTON (DCS) 1

9
REV.

TR4

TR4
CAUSE AND EFFECT
CHART FOR UNIT HTD

NOTES
CUSTOMER NAME: Petroperú PROJECT No: 2070

LOCATION: Talara (Perú) UNIT No: HDT GASOILS


SERVICE: Page 26 of 41

HTD-PID-

HTD-PID-
P&ID

029

029
DOCUMENT No:02070-HTD-PRO-TAB-001
Doc Class:
REVISION TR1 TR2 TR3 TR4
IS-025

WATER DEGASSING DRUM HTD-


DATE 16/MAY/2011 06/FEB/2012 25/UL/2012 23/MAR/2015

VALVE ON HTD-D-015 BOTTOM


YGF / JEP YGF / LSJ AYG TFC
TRIP OF SOUR WATER FROM HTD-D-
ORIG. BY

LOW LOW LEVEL IN SOUR


015
APP. BY PSP PSP PSP CGC / MAO

SERVICE
LEGEND ABBREVIATIONS USED IN THE CHART:

D-015 ALARM
OUTLET LINE
HH HIGH HIGH C = Close
H HIGH O = Open
L LOW
LL LOW LOW I = Start
S = Stop
FMC - FORCE MANUAL CLOSE X = General Action
FMO - FORCE MANUAL OPEN E = Enable

EFFECTS
FUNCTION PERFORMED
OOS - START-UP OVERRIDE SWITCH D = Disable
MOS - MAINTENANCE OVERRIDE SWITCH MR = Manual Reset

LOW LOW LEVEL ALARM


SOE - SEQUENCE OF EVENTS RR = Remote Reset
D - DELETED
A = Activate
V = oVerride
REFERENCES: T = Trip
P = Permissive
P&ID No. B = Bypass

CLOSE
HTD-PID-029

DESCRIPTION

DCS LEVEL ALARM


ON-OFF VALVE

LALL-2901
ACTUATING

XV-2901
DEVICE
CAUSES #

10

11

12

13

14

15

16

17

18

21

22

23

24

25

26

27

28

29

30
1

9
INITIATING OOS MOS
REV. EQUIPMENT DESCRIPTION DEVICE
SERVICE P&ID NOTES #
(b) (b)

TR4 MANUAL ACTIVATION FROM CONTROL ROOM HS-025B TRIP PUSHBUTTON (PANEL IN CONTROL ROOM) 1 C

TR4 HTD-D-015 SOUR WATER DEGASSING DRUM LT-02901 A/B/C DRUM HTD-D-015 LOW LOW LEVEL (VOTE 2oo3) X (*) HTD-PID-029 GENERAL NOTE 1 2 C X

10

11

12

13

14

15

16

17

18

19

20

21

(*) 1 MOS FOR EACH TRANSMITTER 22

23

24

25

RESET

TR4 HS-025A RESET PUSHBUTTON (DCS) 1

9
REV.

TR4

TR4
CAUSE AND EFFECT
CHART FOR UNIT HTD

NOTES
CUSTOMER NAME: Petroperú PROJECT No: 2070

LOCATION: Talara (Perú) UNIT No: HDT GASOILS


SERVICE: Page 27 of 41

HTD-PID-

HTD-PID-
P&ID

036

036
DOCUMENT No:02070-HTD-PRO-TAB-001
Doc Class:
REVISION TR1 TR2 TR3 TR4
DATE 16/MAY/2011 06/FEB/2012 25/UL/2012 23/MAR/2015 IS-026

VALVE ON HTD-C-002 BOTTOM

AMINE ABSORBER HTD-C-002


LOW LOW LEVEL IN OFF GAS
ORIG. BY YGF / JEP YGF / LSJ AYG TFC TRIP OF RICH AMINE FROM HTD-C-002
APP. BY PSP PSP PSP CGC / MAO

SERVICE
LEGEND ABBREVIATIONS USED IN THE CHART:

OUTLET LINE
HH HIGH HIGH C = Close
H HIGH O = Open

ALARM
L LOW
LL LOW LOW I = Start
S = Stop
FMC - FORCE MANUAL CLOSE X = General Action
FMO - FORCE MANUAL OPEN E = Enable

EFFECTS
FUNCTION PERFORMED
OOS - START-UP OVERRIDE SWITCH D = Disable
MOS - MAINTENANCE OVERRIDE SWITCH MR = Manual Reset

LOW LOW LEVEL ALARM


SOE - SEQUENCE OF EVENTS RR = Remote Reset
D - DELETED
A = Activate
V = oVerride
REFERENCES: T = Trip
P = Permissive
P&ID No. B = Bypass

CLOSE
HTD-PID-036

DESCRIPTION

LALL-03601 DCS LEVEL ALARM


ON-OFF VALVE
XV-03601
ACTUATING
DEVICE
CAUSES #

10

11

12

13

14

15

16

17

18

21

22

23

24

25

26

27

28

29

30
1

9
INITIATING OOS MOS
REV. EQUIPMENT DESCRIPTION DEVICE
SERVICE P&ID NOTES #
(b) (b)

TR4 MANUAL ACTIVATION FROM CONTROL ROOM HS-026B TRIP PUSHBUTTON (PANEL IN CONTROL ROOM) 1 C

TR4 HTD-C-002 OFF GAS AMINE ABSORBER LT-03601 A/B/C HTD-C-002 LOW LOW LEVEL (VOTE 2oo3) X (*) HTD-PID-036 GENERAL NOTE 1 2 C X

10

11

12

13

14

15

16

17

18

19

20

21

(*) 1 MOS FOR EACH TRANSMITTER 22

23

24

25

RESET

TR4 HS-026A RESET PUSHBUTTON (DCS) 1

9
REV.

TR5

TR6

TR6

TR6

TR6

TR6

TR6

TR6

TR6
CAUSE AND EFFECT

GENERAL NOTE 10
CHART FOR UNIT HTD

NOTES
CUSTOMER NAME: Petroperú PROJECT No: 2070

LOCATION: Talara (Perú) UNIT No: HDT GASOILS


SERVICE: Page 28 of 41

HTD-PID-

HTD-PID-

HTD-PID-

HTD-PID-

HTD-PID-

HTD-PID-

HTD-PID-

HTD-PID-
021-1

021-3

021-3

021-1

021-2

021-2

021-3

021-1
P&ID
DOCUMENT No:02070-HTD-PRO-TAB-001
Doc Class:
REVISION TR1 TR2 TR3 TR4 TR5 TR6
30/SEP/201 IS-027

SUCTION VALVE HTD-K-002-A


16/MAY/2011 06/FEB/2012 25/UL/2012 23/MAR/2015 23/NOV/15

DISCHARGE VALVE HTD-K-002-


DATE

SUCTION VALVE OF HTD-K-002-

SUCTION VALVE OF HTD-K-002-


DISCHARGE VALVE OF HTD-K-

DISCHARGE VALVE OF HTD-K-


6 TRIP OF MAKE-UP GAS COMPRESSOR

CONTROL VALVE (SOLENOID


ORIG. BY YGF / JEP YGF / LSJ AYG TFC JLT TFC
K-002-A

HTD-K-002-A KICK BACK


APP. BY PSP PSP PSP CGC / MAO MAO MAO

SERVICE

VALVE HYV-02101)
LEGEND ABBREVIATIONS USED IN THE CHART:

002-A 2nd STAGE

COMPRESSOR
002-A 1st STAGE

MAKE UP GAS
HH HIGH HIGH

A 2nd STAGE

A 3rd STAGE
H HIGH C = Close
L LOW O = Open
LL LOW LOW I = Start
S = Stop

A
FMC - FORCE MANUAL CLOSE
FMO - FORCE MANUAL OPEN X = General Action
OOS - START-UP OVERRIDE SWITCH E = Enable

EFFECTS
FUNCTION PERFORMED
MOS - MAINTENANCE OVERRIDE SWITCH D = Disable
SOE - SEQUENCE OF EVENTS MR = Manual Reset
D - DELETED
RR = Remote Reset
A = Activate
REFERENCES: V = oVerride
P&ID No. T = Trip
HTD-PID-021-1 P = Permissive
HTD-PID-021-2 B = Bypass

CLOSE

CLOSE

CLOSE

CLOSE

CLOSE

CLOSE

CLOSE
HTD-PID-021-3

TRIP
INTERLOCK TO BE COMPLETED BY COMPRESSOR
VENDOR.

XS-70175A COMPRESSOR HTD-K-002-A SHUTDOWN


DESCRIPTION

MANUAL CONTROL VALVE


ON-OFF VALVE

ON-OFF VALVE

ON-OFF VALVE

ON-OFF VALVE

ON-OFF VALVE

ON-OFF VALVE
XV-02101

XV-02103

PV-02101

XV-02105

XV-02106

XV-02107

XV-02108
ACTUATING
DEVICE
CAUSES #

10

11

12

13

14

15

16

17

18

21

22

23

24

25

26

27

28

29

30
1

9
INITIATING OOS MOS
REV. EQUIPMENT DESCRIPTION DEVICE
SERVICE P&ID NOTES #
(b) (b)

TR4 MANUAL ACTIVATION FROM CONTROL ROOM HS-027B TRIP PUSHBUTTON (PANEL IN CONTROL ROOM) 1 C C C C C C C A

TR6 2
K-002-A EMERGENCY SHUTDOWN PUSHBUTTON (LOCAL
TR4 HTD-K-002-A GAS COMPRESSOR HTD-K-002-A EMERGENCY SHUTDOWN HS-02101 B HTD-PID-021-1 3 C C C C C C C A
PANEL AT SAFE LOCATION)

TR4 HTD-K-002-A XV-02101 SUCTION VALVE OF HTD-K-002-A ZLO-02101 VALVE XV-02101 NOT FULLY OPEN HTD-PID-021-1 4 C C C C C C C A

TR4 HTD-K-002-A XV-02103 DISCHARGE VALVE OF HTD-K-002-A ZLO-02103 VALVE XV-02103 NOT FULLY OPEN HTD-PID-021-3 5 C C C C C C C A

TR4 HTD-K-002-A XV-02105 DISCHARGE VALVE OF HTD-K-002-A 1st STAGE ZLO-02105 VALVE XV-02105 NOT FULLY OPEN HTD-PID-021-1 6 C C C C C C C A

TR4 HTD-K-002-A XV-02107 DISCHARGE VALVE OF HTD-K-002-A 2nd STAGE ZLO-02107 VALVE XV-02107 NOT FULLY OPEN HTD-PID-021-2 7 C C C C C C C A

TR4 HTD-K-002-A XV-02106 SUCTION VALVE OF HTD-K-002-A 2nd STAGE ZLO-02106 VALVE XV-02106 NOT FULLY OPEN HTD-PID-021-2 8 C C C C C C C A

TR4 HTD-K-002-A XV-02108 SUCTION VALVE OF HTD-K-002-A 3rd STAGE ZLO-02108 VALVE XV-02108 NOT FULLY OPEN HTD-PID-021-3 9 C C C C C C C A

TR5 10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

RESET

TR4 HS-027A RESET PUSHBUTTON (DCS) 1

9
REV.

TR5

TR6

TR6

TR6

TR6

TR6

TR6

TR6

TR6
CAUSE AND EFFECT

GENERAL NOTE 10
CHART FOR UNIT HTD

NOTES
CUSTOMER NAME: Petroperú PROJECT No: 2070

LOCATION: Talara (Perú) UNIT No: HDT GASOILS


SERVICE: Page 29 of 41

HTD-PID-

HTD-PID-

HTD-PID-

HTD-PID-

HTD-PID-

HTD-PID-

HTD-PID-

HTD-PID-
022-1

022-3

022-3

022-1

022-2

022-2

022-3

022-1
P&ID
DOCUMENT No:02070-HTD-PRO-TAB-001
Doc Class:
REVISION TR1 TR2 TR3 TR4 TR5 TR6
30/SEP/201 IS-028

SUCTION VALVE HTD-K-002-B


16/MAY/2011 06/FEB/2012 25/UL/2012 23/MAR/2015 23/NOV/15

DISCHARGE VALVE HTD-K-002-


DATE

SUCTION VALVE OF HTD-K-002-

SUCTION VALVE OF HTD-K-002-


DISCHARGE VALVE OF HTD-K-

DISCHARGE VALVE OF HTD-K-


6 TRIP OF MAKE-UP GAS COMPRESSOR

CONTROL VALVE (SOLENOID


ORIG. BY YGF / JEP YGF / LSJ AYG TFC JLT TFC
K-002-B

HTD-K-002-B KICK BACK


APP. BY PSP PSP PSP CGC / MAO MAO MAO

SERVICE

VALVE HYV-02201)
LEGEND ABBREVIATIONS USED IN THE CHART:

002-B 2nd STAGE

COMPRESSOR
002-B 1st STAGE

MAKE UP GAS
HH HIGH HIGH

B 2nd STAGE

B 3rd STAGE
H HIGH C = Close
L LOW O = Open
LL LOW LOW I = Start
S = Stop

B
FMC - FORCE MANUAL CLOSE
FMO - FORCE MANUAL OPEN X = General Action
OOS - START-UP OVERRIDE SWITCH E = Enable

EFFECTS
FUNCTION PERFORMED
MOS - MAINTENANCE OVERRIDE SWITCH D = Disable
SOE - SEQUENCE OF EVENTS MR = Manual Reset
D - DELETED
RR = Remote Reset
A = Activate
REFERENCES: V = oVerride
P&ID No. T = Trip
HTD-PID-022-1 P = Permissive
HTD-PID-022-2 B = Bypass

CLOSE

CLOSE

CLOSE

CLOSE

CLOSE

CLOSE

CLOSE
HTD-PID-022-3

TRIP
INTERLOCK TO BE COMPLETED BY COMPRESSOR
VENDOR.

XS-70175B COMPRESSOR HTD-K-002-B SHUT DOWN


DESCRIPTION

MANUAL CONTROL VALVE


ON-OFF VALVE

ON-OFF VALVE

ON-OFF VALVE

ON-OFF VALVE

ON-OFF VALVE

ON-OFF VALVE
XV-02201

XV-02203

PV-02202

XV-02204

XV-02205

XV-02206

XV-02207
ACTUATING
DEVICE
CAUSES #

10

11

12

13

14

15

16

17

18

21

22

23

24

25

26

27

28

29

30
2

9
INITIATING OOS MOS
REV. EQUIPMENT DESCRIPTION DEVICE
SERVICE P&ID NOTES #
(b) (b)

TR4 MANUAL ACTIVATION FROM CONTROL ROOM HS-028B TRIP PUSHBUTTON (PANEL IN CONTROL ROOM) 1 C C C C C C C A

TR6 2
K-002-A EMERGENCY SHUTDOWN PUSHBUTTON (LOCAL
TR4 HTD-K-002-B GAS COMPRESSOR HTD-K-002-B EMERGENCY SHUTDOWN HS-02201 B HTD-PID-022-1 3 C C C C C C C A
PANEL AT SAFE LOCATION)

TR4 HTD-K-002-B XV-02201 SUCTION VALVE OF HTD-K-002-B ZLO-02201 VALVE XV-02201 NOT FULLY OPEN HTD-PID-022-1 4 C C C C C C C A

TR4 HTD-K-002-B XV-02203 DISCHARGE VALVE OF HTD-K-002-B ZLO-02203 VALVE XV-02203 NOT FULLY OPEN HTD-PID-022-3 5 C C C C C C C A

TR4 HTD-K-002-B XV-02204 DISCHARGE VALVE OF HTD-K-002-B 1st STAGE ZLO-02204 VALVE XV-02204 NOT FULLY OPEN HTD-PID-022-1 6 C C C C C C C A

TR4 HTD-K-002-B XV-02206 DISCHARGE VALVE OF HTD-K-002-B 2nd STAGE ZLO-02206 VALVE XV-02206 NOT FULLY OPEN HTD-PID-022-2 7 C C C C C C C A

TR4 HTD-K-002-B XV-02205 SUCTION VALVE OF HTD-K-002-B 2nd STAGE ZLO-02205 VALVE XV-02206 NOT FULLY OPEN HTD-PID-022-2 8 C C C C C C C A

TR4 HTD-K-002-B XV-02207 SUCTION VALVE OF HTD-K-002-B 3rd STAGE ZLO-02207 VALVE XV-02208 NOT FULLY OPEN HTD-PID-022-3 9 C C C C C C C A

TR5 10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

RESET

TR4 HS-028A RESET PUSHBUTTON (DCS) 1

9
REV.

TR5

TR5

TR5
CAUSE AND EFFECT
CHART FOR UNIT HTD

NOTES
CUSTOMER NAME: Petroperú PROJECT No: 2070

LOCATION: Talara (Perú) UNIT No: HDT GASOILS


SERVICE: Page 30 of 41

HTD-PID-

HTD-PID-

HTD-PID-
008-1

008-1

008-1
P&ID
DOCUMENT No:02070-HTD-PRO-TAB-001
Doc Class:
REVISION TR1 TR2 TR3 TR4 TR5
16/MAY/2011 06/FEB/2012 25/UL/2012 23/MAR/2015 23/NOV/15
IS-029
DATE

SUPERHEATING COIL OUTLET


HIGH HIGH TEMPERATURE AT
YGF / JEP YGF / LSJ AYG TFC
TRIP OF LP STEAM TP HTD-H-001
ORIG. BY JLT
SUPERHEATING COIL

SUPERHEATING COIL

SUPERHEATING COIL
APP. BY PSP PSP PSP CGC / MAO MAO

SERVICE

HTD-H-001 STEAM

HTD-H-001 STEAM
LEGEND

HTD-H-001 STEAM
ABBREVIATIONS USED IN THE CHART:

BYPASS VALVE
OUTLET VALVE
HH HIGH HIGH
H HIGH C = Close
L LOW O = Open

ALARM
LL LOW LOW I = Start
S = Stop
FMC - FORCE MANUAL CLOSE
FMO - FORCE MANUAL OPEN X = General Action
OOS - START-UP OVERRIDE SWITCH E = Enable

EFFECTS
FUNCTION PERFORMED
MOS - MAINTENANCE OVERRIDE SWITCH D = Disable

HIGH HIGH TEMPERATURE


SOE - SEQUENCE OF EVENTS MR = Manual Reset
D - DELETED
RR = Remote Reset
A = Activate
REFERENCES: V = oVerride
P&ID No. T = Trip
HTD-PID-008 P = Permissive
B = Bypass

ALARM
CLOSE

OPEN
DESCRIPTION

TAHH-00805 DCS TEMPERATURE ALARM


ON-OFF VALVE

ON-OFF VALVE
XV-00801

XV-00802
ACTUATING
DEVICE
CAUSES #

10

11

12

13

14

15

16

17

18

21

22

23

24

25

26

27

28

29

30
1

9
INITIATING OOS MOS
REV. EQUIPMENT DESCRIPTION DEVICE
SERVICE P&ID NOTES #
(b) (b)

TR4 MANUAL ACTIVATION FROM CONTROL ROOM HS-029B TRIP PUSHBUTTON (PANEL IN CONTROL ROOM) 1 C O
HIGH HIGH TEMPERATURE AT HTD-H-001 STEAM
TR4 HTD-H-001 HTD-H-001 STEAM SUPERHEATING COIL OUTLET TT-00805 A/B/C X (*) HTD-PID-008 2 C O X
SUPERHEATING COIL OUTLET (VOTE 2oo3)

10

11

12

13

14

15

16

17

18

19

20

21

(*) 1 MOS FOR EACH TRANSMITTER 22

23

24

25

RESET

TR4 HS-029A RESET PUSHBUTTON (DCS) 1

9
REV.

TR4

TR4
CAUSE AND EFFECT
CHART FOR UNIT HTD

NOTES
CUSTOMER NAME: Petroperú PROJECT No: 2070

LOCATION: Talara (Perú) UNIT No: HDT GASOILS


SERVICE: Page 31 of 41

HTD-PID-

HTD-PID-
028-2

028-1
P&ID
DOCUMENT No:02070-HTD-PRO-TAB-001
Doc Class:
REVISION TR1 TR2 TR3 TR4
IS-030

VALVE DOWNSTREAM HTD-D-


DATE 16/MAY/2011 06/FEB/2012 25/UL/2012 23/MAR/2015

GASOIL PRODUCT LINE ALARM


HIGH HIGH TEMPERATURE AT
TRIP OF PRODUCT OIL TRANSFER TO

012 (GASOIL PRODUCT TO


ORIG. BY YGF / JEP YGF / LSJ AYG TFC
STORAGE
APP. BY PSP PSP PSP CGC / MAO

SERVICE
LEGEND ABBREVIATIONS USED IN THE CHART:
HH HIGH HIGH
H HIGH C = Close
L LOW O = Open
LL LOW LOW I = Start

BL)
S = Stop
FMC - FORCE MANUAL CLOSE
FMO - FORCE MANUAL OPEN X = General Action
OOS - START-UP OVERRIDE SWITCH E = Enable

EFFECTS
FUNCTION PERFORMED
MOS - MAINTENANCE OVERRIDE SWITCH D = Disable

HIGH HIGH TEMPERATURE


SOE - SEQUENCE OF EVENTS MR = Manual Reset
D - DELETED
RR = Remote Reset
A = Activate
REFERENCES: V = oVerride
P&ID No. T = Trip
HTD-PID-028-1 P = Permissive
HTD-PID-028-2 B = Bypass

ALARM
CLOSE
DESCRIPTION

TAHH-02803 DCS TEMPERATURE ALARM


ON-OFF VALVE
XV-03602
ACTUATING
DEVICE
CAUSES #

10

11

12

13

14

15

16

17

18

21

22

23

24

25

26

27

28

29

30
1

9
INITIATING OOS MOS
REV. EQUIPMENT DESCRIPTION DEVICE
SERVICE P&ID NOTES #
(b) (b)

TR4 MANUAL ACTIVATION FROM CONTROL ROOM HS-030B TRIP PUSHBUTTON (PANEL IN CONTROL ROOM) 1 C
HIGH HIGH TEMPERATURE AT GASOIL PRODUCT LINE (VOTE
TR4 GAS OIL PRODUCT LINE TT-02803 A/B/C X (*) HTD-PID-028-1 2 C X
2oo3)

10

11

12

13

14

15

16

17

18

19

20

21

(*) 1 MOS FOR EACH TRANSMITTER 22

23

24

25

RESET

TR4 HS-030A RESET PUSHBUTTON (DCS) 1

9
REV.

TR4

TR4
CAUSE AND EFFECT
CHART FOR UNIT HTD

NOTES
CUSTOMER NAME: Petroperú PROJECT No: 2070

LOCATION: Talara (Perú) UNIT No: HDT GASOILS


SERVICE: Page 32 of 41

HTD-PID-

HTD-PID-
P&ID

036

036
DOCUMENT No:02070-HTD-PRO-TAB-001
Doc Class:
REVISION TR1 TR2 TR3 TR4
16/MAY/2011 06/FEB/2012 25/UL/2012 23/MAR/2015
IS-031
DATE

HIGH HIGH LEVEL IN OFF GAS


TRIP OF LEAN AMINE FEED TO

AMINE ABSORBER HTD-C-002


VALVE UPSTREAM HTD-C-
ORIG. BY YGF / JEP YGF / LSJ AYG TFC

002 (LEAN AMINE FEED)


ABSORBER
APP. BY PSP PSP PSP CGC / MAO

SERVICE
LEGEND ABBREVIATIONS USED IN THE CHART:
HH HIGH HIGH
H HIGH C = Close
L LOW O = Open
LL LOW LOW I = Start
S = Stop
FMC - FORCE MANUAL CLOSE
FMO - FORCE MANUAL OPEN X = General Action
OOS - START-UP OVERRIDE SWITCH E = Enable

EFFECTS
FUNCTION PERFORMED
MOS - MAINTENANCE OVERRIDE SWITCH D = Disable
SOE - SEQUENCE OF EVENTS

HIGH HIGH LEVEL ALARM


D - DELETED MR = Manual Reset
RR = Remote Reset
A = Activate
REFERENCES: V = oVerride
P&ID No. T = Trip
HTD-PID-036 P = Permissive
B = Bypass

CLOSE
SIL REQUIREMENT: SIL 2 (AS PER 02070-GEN-HSE-STU-
002)

DESCRIPTION

LAHH-03601 DCS LEVEL ALARM


ON-OFF VALVE
XV-03602
ACTUATING
DEVICE
CAUSES #

10

11

12

13

14

15

16

17

18

21

22

23

24

25

26

27

28

29

30
1

9
INITIATING OOS MOS
REV. EQUIPMENT DESCRIPTION DEVICE
SERVICE P&ID NOTES #
(b) (b)

TR4 MANUAL ACTIVATION FROM CONTROL ROOM HS-031B TRIP PUSHBUTTON (PANEL IN CONTROL ROOM) 1 C
HIGH HIGH LEVEL IN OFF GAS AMINE ABSORBER HTD-C-002
TR4 HTD-C-002 OFF GAS AMINE ABSORBER LT-03601 A/B/C X (*) HTD-PID-036 GENERAL NOTE 1 2 C X
(VOTE 2oo3)

10

11

12

13

14

15

16

17

18

19

20

21

(*) 1 MOS FOR EACH TRANSMITTER 22

23

24

25

RESET

TR4 HS-031A RESET PUSHBUTTON (DCS) 1

9
REV.

TR5

TR5

TR5

TR5

TR4

TR4
CAUSE AND EFFECT
CHART FOR UNIT HTD

NOTES
CUSTOMER NAME: Petroperú PROJECT No: 2070

LOCATION: Talara (Perú) UNIT No: HDT GASOILS


SERVICE: Page 33 of 41

HTD-PID-

HTD-PID-

HTD-PID-

HTD-PID-

HTD-PID-

HTD-PID-
P&ID

037

037

037

037

037

037
DOCUMENT No:02070-HTD-PRO-TAB-001
Doc Class:
REVISION TR1 TR2 TR3 TR4 TR5
I-001

NON CRACKED SLOPS PUMP

NON CRACKED SLOPS PUMP

NON CRACKED SLOPS PUMP

NON CRACKED SLOPS PUMP


DATE 16/MAY/2011 06/FEB/2012 25/UL/2012 23/MAR/2015 23/NOV/15

HIGH LEVEL IN NON CRACKED

LOW LEVEL IN NON CRACKED


YGF / JEP YGF / LSJ AYG TFC
NON CRACKED SLOPS PUMP (HTD-P-
ORIG. BY JLT
011-A/B) OPERATIONAL INTERLOCK

SLOPS DRUM HTD-D-019

SLOPS DRUM HTD-D-019


APP. BY PSP PSP PSP CGC / MAO MAO

SERVICE
LEGEND ABBREVIATIONS USED IN THE CHART:
HH HIGH HIGH
H HIGH C = Close

MOTOR A

MOTOR A

MOTOR B

MOTOR B
L LOW O = Open
LL LOW LOW
I = Start
FMC - FORCE MANUAL CLOSE S = Stop
FMO - FORCE MANUAL OPEN
OOS - START-UP OVERRIDE SWITCH X = General Action
MOS - MAINTENANCE OVERRIDE SWITCH E = Enable

EFFECTS
FUNCTION PERFORMED
SOE - SEQUENCE OF EVENTS D = Disable
D - DELETED
MR = Manual Reset
RR = Remote Reset
REFERENCES:

HIGH LEVEL ALARM


A = Activate

LOW LEVEL ALARM


P&ID No. V = oVerride
HTD-PID-037 T = Trip
P = Permissive
THROUGH THIS OPERATIONAL INTERLOCK PUMPS B = Bypass

START

START
STOP

STOP
HTD-P-011-A/B WILL START AT HLL IN HTD-D-019 AND
WILL STOP AT LLL IN HTD-D-019.

PUMPS HTD-P-011-A/B MAY OPERATE IN MANUAL OR


AUTO MODE THROUGH SELECTOR HS-03701/03702
RESPECTIVELY.

DESCRIPTION

LAH-03702 DCS LEVEL ALARM

DCS LEVEL ALARM


MHSR-03701 MOTOR PUMP

MHSS-03701 MOTOR PUMP

MHSR-03702 MOTOR PUMP

MHSS-03702 MOTOR PUMP

LAL-03702
ACTUATING
DEVICE
CAUSES #

10

11

12

13

14

15

16

17

18

21

22

23

24

25

26

27

28

29

30
1

9
INITIATING OOS MOS
REV. EQUIPMENT DESCRIPTION DEVICE
SERVICE P&ID NOTES #
(b) (b)

TR5 1

TR5 2

TR4 HTD-D-019 NON CRACKED SLOPS DRUM LT-03702 HIGH LEVEL IN NON CRACKED SLOPS DRUM HTD-D-019 HTD-PID-037 3 I I X

TR4 HTD-D-019 NON CRACKED SLOPS DRUM LT-03702 LOW LEVEL IN NON CRACKED SLOPS DRUM HTD-D-019 HTD-PID-037 4 S S X

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

RESET

9
REV.

TR5

TR5

TR5

TR5

TR4

TR4
CAUSE AND EFFECT
CHART FOR UNIT HTD

NOTES
CUSTOMER NAME: Petroperú PROJECT No: 2070

LOCATION: Talara (Perú) UNIT No: HDT GASOILS


SERVICE: Page 34 of 41

HTD-PID-

HTD-PID-

HTD-PID-

HTD-PID-

HTD-PID-

HTD-PID-
P&ID

038

038

038

038

038

038
DOCUMENT No:02070-HTD-PRO-TAB-001
Doc Class:
REVISION TR1 TR2 TR3 TR4 TR5
I-002

LOW LEVEL IN CRACKED SLOPS


DATE 16/MAY/2011 06/FEB/2012 25/UL/2012 23/MAR/2015 23/NOV/15
YGF / JEP YGF / LSJ AYG TFC
CRACKED SLOPS PUMP (HTD-P-012-
ORIG. BY JLT

CRACKED SLOPS PUMP

CRACKED SLOPS PUMP

CRACKED SLOPS PUMP

CRACKED SLOPS PUMP


A/B) OPERATIONAL INTERLOCK

HIGH LEVEL IN CRACKED


SLOPS DRUM HTD-D-020
APP. BY PSP PSP PSP CGC / MAO MAO

SERVICE
LEGEND ABBREVIATIONS USED IN THE CHART:

DRUM HTD-D-020
HH HIGH HIGH
H HIGH C = Close

MOTOR A

MOTOR A

MOTOR B

MOTOR B
L LOW O = Open
LL LOW LOW
I = Start
FMC - FORCE MANUAL CLOSE S = Stop
FMO - FORCE MANUAL OPEN
OOS - START-UP OVERRIDE SWITCH X = General Action
MOS - MAINTENANCE OVERRIDE SWITCH E = Enable

EFFECTS
FUNCTION PERFORMED
SOE - SEQUENCE OF EVENTS D = Disable
D - DELETED
MR = Manual Reset
RR = Remote Reset
REFERENCES:

HIGH LEVEL ALARM


A = Activate

LOW LEVEL ALARM


P&ID No. V = oVerride
HTD-PID-038 T = Trip
P = Permissive
THROUGH THIS OPERATIONAL INTERLOCK PUMPS B = Bypass

START

START
STOP

STOP
HTD-P-012-A/B WILL START AT HLL IN HTD-D-020 AND
WILL STOP AT LLL IN HTD-D-020.

PUMPS HTD-P-012-A/B MAY OPERATE IN MANUAL OR


AUTO MODE THROUGH SELECTOR HS-03801/03802
RESPECTIVELY.

DESCRIPTION

LAH-03802 DCS LEVEL ALARM

DCS LEVEL ALARM


MHSR-03801 MOTOR PUMP

MHSS-03801 MOTOR PUMP

MHSR-03802 MOTOR PUMP

MHSS-03802 MOTOR PUMP

LAL-03802
ACTUATING
DEVICE
CAUSES #

10

11

12

13

14

15

16

17

18

21

22

23

24

25

26

27

28

29

30
1

9
INITIATING OOS MOS
REV. EQUIPMENT DESCRIPTION DEVICE
SERVICE P&ID NOTES #
(b) (b)

TR5 1

TR5 2

TR4 HTD-D-020 CRACKED SLOPS DRUM LT-03802 HIGH LEVEL IN CRACKED SLOPS DRUM HTD-D-020 HTD-PID-038 3 I I X

TR4 HTD-D-020 CRACKED SLOPS DRUM LT-03802 LOW LEVEL IN CRACKED SLOPS DRUM HTD-D-020 HTD-PID-038 4 S S X

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

RESET

9
REV.

TR4
CAUSE AND EFFECT
CHART FOR UNIT HTD

NOTES
CUSTOMER NAME: Petroperú PROJECT No: 2070

LOCATION: Talara (Perú) UNIT No: HDT GASOILS


SERVICE: Page 35 of 41

HTD-PID-
P&ID

015
DOCUMENT No:02070-HTD-PRO-TAB-001
Doc Class:
REVISION TR4 I-004

(SOLENOID VALVE XY-01501)


DATE 20/MAR/2015 LP HOT SEPARATOR (HTD-D-004) HOT

LP HOT SEPARATOR HOT


ORIG. BY TFC LIQUID OUTLET OPERATIONAL

LIQUID OUTLET VALVE


APP. BY CGC / MAO INTERLOCK

SERVICE
LEGEND ABBREVIATIONS USED IN THE CHART:
HH HIGH HIGH
H HIGH C = Close
L LOW O = Open
LL LOW LOW I = Start
S = Stop
FMC - FORCE MANUAL CLOSE
FMO - FORCE MANUAL OPEN X = General Action
OOS - START-UP OVERRIDE SWITCH E = Enable

EFFECTS
FUNCTION PERFORMED
MOS - MAINTENANCE OVERRIDE SWITCH D = Disable
SOE - SEQUENCE OF EVENTS MR = Manual Reset
D - DELETED
RR = Remote Reset
A = Activate
REFERENCES: V = oVerride

OPEN / CLOSE
P&ID No. T = Trip
HTD-PID-015 P = Permissive
B = Bypass
THIS OPERATIONAL INTERLOCK OPENS HTD-HV-01501
THROUGH HTD-HS-01501C AND CLOSES HTD-HV-01501
THROUGH HTD-HS-01501A/B.

DESCRIPTION

ON-OFF VALVE
HV-01501
ACTUATING
DEVICE
CAUSES #

10

11

12

13

14

15

16

17

18

21

22

23

24

25

26

27

28

29

30
1

9
INITIATING OOS MOS
REV. EQUIPMENT DESCRIPTION DEVICE
SERVICE P&ID NOTES #
(b) (b)

TR4 HV-01501 LP HOT SEPARATOR HOT LIQUID OUTLET HS-01501A HV-01501 CLOSE PUSHBUTTON (DCS) HTD-PID-015 1 C
HV-01501 CLOSE PUSHBUTTON (LOCAL PANEL AT SAFE
TR4 HV-01501 LP HOT SEPARATOR HOT LIQUID OUTLET HS-01501B HTD-PID-015 2 C
LOCATION)
HV-01501 OPEN PUSHBUTTON (LOCAL PANEL AT SAFE
TR4 HV-01501 LP HOT SEPARATOR HOT LIQUID OUTLET HS-01501C HTD-PID-015 3 O
LOCATION)

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

RESET

9
REV.

TR4
CAUSE AND EFFECT
CHART FOR UNIT HTD

NOTES
CUSTOMER NAME: Petroperú PROJECT No: 2070

LOCATION: Talara (Perú) UNIT No: HDT GASOILS


SERVICE: Page 36 of 41

HTD-PID-
P&ID

017
DOCUMENT No:02070-HTD-PRO-TAB-001
Doc Class:
REVISION TR4 I-005

(SOLENOID VALVE XY-01702)


20/MAR/2015 LP COLD SEPARATOR (HTD-D-005)

LP COLD SEPARATOR COLD


DATE
ORIG. BY TFC COLD LIQUID OUTLET OPERATIONAL

LIQUID OUTLET VALVE


APP. BY CGC / MAO INTERLOCK

SERVICE
LEGEND ABBREVIATIONS USED IN THE CHART:
HH HIGH HIGH
H HIGH C = Close
L LOW O = Open
LL LOW LOW I = Start
S = Stop
FMC - FORCE MANUAL CLOSE
FMO - FORCE MANUAL OPEN X = General Action
OOS - START-UP OVERRIDE SWITCH E = Enable

EFFECTS
FUNCTION PERFORMED
MOS - MAINTENANCE OVERRIDE SWITCH D = Disable
SOE - SEQUENCE OF EVENTS MR = Manual Reset
D - DELETED
RR = Remote Reset
A = Activate
REFERENCES: V = oVerride

OPEN / CLOSE
P&ID No. T = Trip
HTD-PID-017 P = Permissive
B = Bypass
THIS OPERATIONAL INTERLOCK OPENS HTD-HV-01702
THROUGH HTD-HS-01702C AND CLOSES HTD-HV-01702
THROUGH HTD-HS-01702A/B.

DESCRIPTION

ON-OFF VALVE
HV-01702
ACTUATING
DEVICE
CAUSES #

10

11

12

13

14

15

16

17

18

21

22

23

24

25

26

27

28

29

30
1

9
INITIATING OOS MOS
REV. EQUIPMENT DESCRIPTION DEVICE
SERVICE P&ID NOTES #
(b) (b)

TR4 HV-01702 LP COLD SEPARATOR COLD LIQUID OUTLET HS-01702A HV-01702 CLOSE PUSHBUTTON (DCS) HTD-PID-017 1 C
HV-01702 CLOSE PUSHBUTTON (LOCAL PANEL AT SAFE
TR4 HV-01702 LP COLD SEPARATOR COLD LIQUID OUTLET HS-01702B HTD-PID-017 2 C
LOCATION)
HV-01705 OPEN PUSHBUTTON (LOCAL PANEL AT SAFE
TR4 HV-01702 LP COLD SEPARATOR COLD LIQUID OUTLET HS-01702C HTD-PID-017 3 O
LOCATION)

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

RESET

9
REV.

TR4
CAUSE AND EFFECT
CHART FOR UNIT HTD

NOTES
CUSTOMER NAME: Petroperú PROJECT No: 2070

LOCATION: Talara (Perú) UNIT No: HDT GASOILS


SERVICE: Page 37 of 41

HTD-PID-
P&ID

020
DOCUMENT No:02070-HTD-PRO-TAB-001
Doc Class:
REVISION TR4 I-006
DATE 20/MAR/2015 MAKE-UP GAS COMPRESSOR (HTD-K-

MAKE-UP COMPRESSOR 1st

VALVE (SOLENOID VALVE


ORIG. BY TFC 002-A/B) 1st STAGE SUCTION DRAIN

SUCTION DRAIN BOOT


APP. BY CGC / MAO BOOT OPERATIONAL INTERLOCK

SERVICE
LEGEND ABBREVIATIONS USED IN THE CHART:
HH HIGH HIGH

LYV-02003)
H HIGH C = Close
L LOW O = Open
LL LOW LOW I = Start
S = Stop
FMC - FORCE MANUAL CLOSE
FMO - FORCE MANUAL OPEN X = General Action
OOS - START-UP OVERRIDE SWITCH E = Enable

EFFECTS
FUNCTION PERFORMED
MOS - MAINTENANCE OVERRIDE SWITCH D = Disable
SOE - SEQUENCE OF EVENTS MR = Manual Reset
D - DELETED
RR = Remote Reset
A = Activate
REFERENCES: V = oVerride

OPEN / CLOSE
P&ID No. T = Trip
HTD-PID-020 P = Permissive
B = Bypass

THROUGH THIS OPERATIONAL INTERLOCK VALVE


HTD-LV-02003 WILL OPEN AT HLL IN MAKE-UP GAS
COMPRESSOR 1st STAGE SUCTION DRAIN BOOT AND
WILL CLOSE AT LLL IN MAKE-UP GAS COMPRESSOR
1st STAGE SUCTION DRAIN BOOT.

DESCRIPTION

LEVEL CONTROL VALVE


LV-02003
ACTUATING
DEVICE
CAUSES #

10

11

12

13

14

15

16

17

18

21

22

23

24

25

26

27

28

29

30
1

9
INITIATING OOS MOS
REV. EQUIPMENT DESCRIPTION DEVICE
SERVICE P&ID NOTES #
(b) (b)
HIGH LEVEL IN MAKE-UP GAS COMPRESSOR 1st STAGE
TR4 MAKE-UP GAS COMPRESSOR (HTD-K-002-A/B) 1st STAGE SUCTION DRAIN BOOT LT-02003 HTD-PID-020 1 O
SUCTION DRAIN BOOT
LOW LEVEL IN MAKE-UP GAS COMPRESSOR 1st STAGE
TR4 MAKE-UP GAS COMPRESSOR (HTD-K-002-A/B) 1st STAGE SUCTION DRAIN BOOT LT-02003 HTD-PID-020 2 C
SUCTION DRAIN BOOT

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

RESET

9
REV.

TR4
CAUSE AND EFFECT
CHART FOR UNIT HTD

NOTES
CUSTOMER NAME: Petroperú PROJECT No: 2070

LOCATION: Talara (Perú) UNIT No: HDT GASOILS


SERVICE: Page 38 of 41

HTD-PID-
021-1
P&ID
DOCUMENT No:02070-HTD-PRO-TAB-001
Doc Class:
REVISION TR4 I-007

MAKE-UP COMPRESSOR 2nd


DATE 20/MAR/2015 MAKE-UP GAS COMPRESSOR (HTD-K-

VALVE (SOLENOID VALVE


ORIG. BY TFC 002-A/B) 2nd STAGE SUCTION DRAIN

SUCTION DRAIN BOOT


APP. BY CGC / MAO BOOT OPERATIONAL INTERLOCK

SERVICE
LEGEND ABBREVIATIONS USED IN THE CHART:
HH HIGH HIGH

LYV-02108)
H HIGH C = Close
L LOW O = Open
LL LOW LOW I = Start
S = Stop
FMC - FORCE MANUAL CLOSE
FMO - FORCE MANUAL OPEN X = General Action
OOS - START-UP OVERRIDE SWITCH E = Enable

EFFECTS
FUNCTION PERFORMED
MOS - MAINTENANCE OVERRIDE SWITCH D = Disable
SOE - SEQUENCE OF EVENTS MR = Manual Reset
D - DELETED
RR = Remote Reset
A = Activate
REFERENCES: V = oVerride

OPEN / CLOSE
P&ID No. T = Trip
HTD-PID-021-1 P = Permissive
B = Bypass

THROUGH THIS OPERATIONAL INTERLOCK VALVE


HTD-LV-02108 WILL OPEN AT HLL IN MAKE-UP GAS
COMPRESSOR 2nd STAGE SUCTION DRAIN BOOT AND
WILL CLOSE AT LLL IN MAKE-UP GAS COMPRESSOR
2nd STAGE SUCTION DRAIN BOOT.

DESCRIPTION

LEVEL CONTROL VALVE


LV-02108
ACTUATING
DEVICE
CAUSES #

10

11

12

13

14

15

16

17

18

21

22

23

24

25

26

27

28

29

30
1

9
INITIATING OOS MOS
REV. EQUIPMENT DESCRIPTION DEVICE
SERVICE P&ID NOTES #
(b) (b)
HIGH LEVEL IN MAKE-UP GAS COMPRESSOR 2nd STAGE
TR4 MAKE-UP GAS COMPRESSOR (HTD-K-002-A/B) 2nd STAGE SUCTION DRAIN BOOT LT-02108 HTD-PID-021-1 1 O
SUCTION DRAIN BOOT
LOW LEVEL IN MAKE-UP GAS COMPRESSOR 2nd STAGE
TR4 MAKE-UP GAS COMPRESSOR (HTD-K-002-A/B) 2nd STAGE SUCTION DRAIN BOOT LT-02108 HTD-PID-021-1 2 C
SUCTION DRAIN BOOT

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

RESET

9
REV.

TR4
CAUSE AND EFFECT
CHART FOR UNIT HTD

NOTES
CUSTOMER NAME: Petroperú PROJECT No: 2070

LOCATION: Talara (Perú) UNIT No: HDT GASOILS


SERVICE: Page 39 of 41

HTD-PID-
021-2
P&ID
DOCUMENT No:02070-HTD-PRO-TAB-001
Doc Class:
REVISION TR4 I-008
20/MAR/2015 MAKE-UP GAS COMPRESSOR (HTD-K-

MAKE-UP COMPRESSOR 3rd


DATE

VALVE (SOLENOID VALVE


ORIG. BY TFC 002-A/B) 3rd STAGE SUCTION DRAIN

SUCTION DRAIN BOOT


APP. BY CGC / MAO BOOT OPERATIONAL INTERLOCK

SERVICE
LEGEND ABBREVIATIONS USED IN THE CHART:
HH HIGH HIGH

LYV-02110)
H HIGH C = Close
L LOW O = Open
LL LOW LOW I = Start
S = Stop
FMC - FORCE MANUAL CLOSE
FMO - FORCE MANUAL OPEN X = General Action
OOS - START-UP OVERRIDE SWITCH E = Enable

EFFECTS
FUNCTION PERFORMED
MOS - MAINTENANCE OVERRIDE SWITCH D = Disable
SOE - SEQUENCE OF EVENTS MR = Manual Reset
D - DELETED
RR = Remote Reset
A = Activate
REFERENCES: V = oVerride

OPEN / CLOSE
P&ID No. T = Trip
HTD-PID-021-2 P = Permissive
B = Bypass

THROUGH THIS OPERATIONAL INTERLOCK VALVE


HTD-LV-02110 WILL OPEN AT HLL IN MAKE-UP GAS
COMPRESSOR 3rd STAGE SUCTION DRAIN BOOT AND
WILL CLOSE AT LLL IN MAKE-UP GAS COMPRESSOR
3rd STAGE SUCTION DRAIN BOOT.

DESCRIPTION

LEVEL CONTROL VALVE


LV-02110
ACTUATING
DEVICE
CAUSES #

10

11

12

13

14

15

16

17

18

21

22

23

24

25

26

27

28

29

30
1

9
INITIATING OOS MOS
REV. EQUIPMENT DESCRIPTION DEVICE
SERVICE P&ID NOTES #
(b) (b)
HIGH LEVEL IN MAKE-UP GAS COMPRESSOR 3rd STAGE
TR4 MAKE-UP GAS COMPRESSOR (HTD-K-002-A/B) 3rd STAGE SUCTION DRAIN BOOT LT-02110 HTD-PID-021-2 1 O
SUCTION DRAIN BOOT
LOW LEVEL IN MAKE-UP GAS COMPRESSOR 3rd STAGE
TR4 MAKE-UP GAS COMPRESSOR (HTD-K-002-A/B) 3rd STAGE SUCTION DRAIN BOOT LT-02110 HTD-PID-021-2 2 C
SUCTION DRAIN BOOT

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

RESET

9
REV.

TR5
CAUSE AND EFFECT
CHART FOR UNIT HTD

NOTES
CUSTOMER NAME: Petroperú PROJECT No: 2070

LOCATION: Talara (Perú) UNIT No: HDT GASOILS


SERVICE: Page 40 of 41

HTD-PID-
001-2
P&ID
DOCUMENT No:02070-HTD-PRO-TAB-001
Doc Class:
REVISION TR5
23/NOV/15
I-009
DATE
FEED COALESCER DRAIN BOOT

VALVE (SOLENOID VALVE


ORIG. BY JLT

HTD-D-018 DRAIN BOOT


OPERATIONAL INTERLOCK
APP. BY MAO

SERVICE
LEGEND ABBREVIATIONS USED IN THE CHART:
HH HIGH HIGH

LYV-00101)
H HIGH C = Close
L LOW O = Open
LL LOW LOW I = Start
S = Stop
FMC - FORCE MANUAL CLOSE
FMO - FORCE MANUAL OPEN X = General Action
OOS - START-UP OVERRIDE SWITCH E = Enable

EFFECTS
FUNCTION PERFORMED
MOS - MAINTENANCE OVERRIDE SWITCH D = Disable
SOE - SEQUENCE OF EVENTS MR = Manual Reset
D - DELETED
RR = Remote Reset
A = Activate
REFERENCES: V = oVerride

OPEN / CLOSE
P&ID No. T = Trip
HTD-PID-021-2 P = Permissive
B = Bypass

THROUGH THIS OPERATIONAL INTERLOCK VALVE


HTD-LV-02110 WILL OPEN AT HLL IN MAKE-UP GAS
COMPRESSOR 3rd STAGE SUCTION DRAIN BOOT AND
WILL CLOSE AT LLL IN MAKE-UP GAS COMPRESSOR
3rd STAGE SUCTION DRAIN BOOT.

DESCRIPTION

LEVEL CONTROL VALVE


LV-00101
ACTUATING
DEVICE
CAUSES #

10

11

12

13

14

15

16

17

18

21

22

23

24

25

26

27

28

29

30
1

9
INITIATING OOS MOS
REV. EQUIPMENT DESCRIPTION DEVICE
SERVICE P&ID NOTES #
(b) (b)

TR5 FEED COALESCER (HTD-D-018) DRAIN BOOT LT-00101 A/B/C HIGH LEVEL IN HTD-D-018 DRAIN BOOT HTD-PID-001-2 1 O

TR5 FEED COALESCER (HTD-D-018) DRAIN BOOT LT-00101 A/B/C LOW LEVEL IN HTD-D-018 DRAIN BOOT HTD-PID-001-2 2 C

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

RESET

9
REV.

TR5
CAUSE AND EFFECT
CHART FOR UNIT HTD

NOTES
CUSTOMER NAME: Petroperú PROJECT No: 2070

LOCATION: Talara (Perú) UNIT No: HDT GASOILS


SERVICE: Page 41 of 41

HTD-PID-
P&ID

018
DOCUMENT No:02070-HTD-PRO-TAB-001
Doc Class:
REVISION TR5
23/NOV/15
I-010
DATE
RECYCLE GAS K.O DRUM LIQUID

HTD-D-006 LIQUIT OUTLET


VALVE (SOLENOID VALVE
ORIG. BY JLT
OUTLET OPERATIONAL INTERLOCK
APP. BY MAO

SERVICE
LEGEND ABBREVIATIONS USED IN THE CHART:
HH HIGH HIGH

LYV-01801)
H HIGH C = Close
L LOW O = Open
LL LOW LOW I = Start
S = Stop
FMC - FORCE MANUAL CLOSE
FMO - FORCE MANUAL OPEN X = General Action
OOS - START-UP OVERRIDE SWITCH E = Enable

EFFECTS
FUNCTION PERFORMED
MOS - MAINTENANCE OVERRIDE SWITCH D = Disable
SOE - SEQUENCE OF EVENTS MR = Manual Reset
D - DELETED
RR = Remote Reset
A = Activate
REFERENCES: V = oVerride

OPEN / CLOSE
P&ID No. T = Trip
HTD-PID-021-2 P = Permissive
B = Bypass

THROUGH THIS OPERATIONAL INTERLOCK VALVE


HTD-LV-02110 WILL OPEN AT HLL IN MAKE-UP GAS
COMPRESSOR 3rd STAGE SUCTION DRAIN BOOT AND
WILL CLOSE AT LLL IN MAKE-UP GAS COMPRESSOR
3rd STAGE SUCTION DRAIN BOOT.

DESCRIPTION

LEVEL CONTROL VALVE


LV-01801
ACTUATING
DEVICE
CAUSES #

10

11

12

13

14

15

16

17

18

21

22

23

24

25

26

27

28

29

30
1

9
INITIATING OOS MOS
REV. EQUIPMENT DESCRIPTION DEVICE
SERVICE P&ID NOTES #
(b) (b)

TR5 RECYCLE GAS K.O DRUM (HTD-D-006) LIQUID OUTLET OPERATIONAL INTERLOCK LT-01801 A/B/C HIGH LEVEL IN HTD-D-006 HTD-PID-018 1 O

TR5 RECYCLE GAS K.O DRUM (HTD-D-006) LIQUID OUTLET OPERATIONAL INTERLOCK LT-01801 A/B/C LOW LEVEL IN HTD-D-006 HTD-PID-018 2 C

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

RESET