MANUEL D’UTILISATION
SER´S MANUAL
FR_FANOXTD_MANU_SIL_Ocefprimarydist_SILA_R019.Docx
1. RÉCEPTION, MANIPULATION ET INSTALLATION .................................. 6
1.1.Démontage .................................................................................................................................. 6
1.2.Réception des relais................................................................................................................... 6
1.3.Manipulation des équipements électroniques ........................................................................ 6
1.4.Installation, mise en marche et service.................................................................................... 7
1.5.Stockage ...................................................................................................................................... 7
1.6.Recyclage .................................................................................................................................... 7
2. DIMENSIONE ET SCHEMAS DE CONNEXION ......................................... 8
2.1.SILAXX Révision A ..................................................................................................................... 8
2.1.1.Dimensions ................................................................................................................................ 8
2.1.2.Diagrammes de connexion ........................................................................................................ 9
2.1.3.Bornes ..................................................................................................................................... 10
2.2.Standard SILA - Révision A ..................................................................................................... 12
2.2.1.Dimensions .............................................................................................................................. 12
2.2.2.Diagrammes de connexion ...................................................................................................... 14
2.2.3.Bornes ..................................................................................................................................... 16
2.3.SILAXX - Révision B ................................................................................................................. 20
2.3.1.Dimensions .............................................................................................................................. 21
2.3.2.Diagrammes de connexion ...................................................................................................... 23
2.3.3.Bornes ..................................................................................................................................... 24
2.4. Standard SILA - Révision B .................................................................................................... 26
2.4.1. Dimensions ............................................................................................................................. 27
2.4.2. Diagrammes de connexion ..................................................................................................... 29
2.4.3. Bornes ................................................................................................................................... 31
3. DESCRIPTION .......................................................................................... 33
3.1. Introduction .............................................................................................................................. 33
3.2. Description ............................................................................................................................... 33
3.3. Schéma fonctionnel ................................................................................................................ 39
3.4. Liste de modèles SIL-A ........................................................................................................... 40
3.5. Sélection CT de phase et CT de neutre ................................................................................. 41
4. PROTECTION FUNCTIONS ..................................................................... 42
4.1. Fonctions 50P_1 et 50P_2. Surintensité instantanée de phase ................................... 42
4.2. Fonction 51P. Surintensité de temps inverse de phase ................................................ 42
4.3. Fonction 50N_1 et 50N_2. Surintensité instantanée de neutre. ................................... 43
4.4. Fonction 51N. Surintensité de temps inverse de neutre ............................................... 44
4.5. Fonction 46. Surintensité instantanée de séquence négative. ..................................... 45
4.6. Function 49. Thermal image protectcion ........................................................................ 46
4.6.1. Curbes .................................................................................................................................... 47
4.7. Fonction 52. Surveillance de l’interrupteur .................................................................... 48
1.1.Démontage
La manipulation des relais est réservée à un personnel qualifié, des précautions particulières
devant être seuils lors du montage et de l’installation afin de protéger toutes les parties contre
tout dommage. Un bon éclairage est recommandé pour faciliter l’examen visuel de l’équipement.
L’installation devra être propre et sèche et il faudra éviter le stockage des relais dans les endroits
exposés à la poussière et à l’humidité. Il faut être particulièrement attentif en cas de travaux de
construction.
www.fanox.com 7/301
1.4.Installation, mise en marche et service
Le personnel chargé de l’installation, de la mise en marche et de la maintenance de ce matériel
devra être qualifié et connaître les procédures de manipulation de celui-ci. Avant l’installation, la
mise en marche ou toute maintenance de l’équipement, il est indispensable de lire la
documentation relative au produit.
Le personnel devra prendre des mesures de protection spéciales pour éviter le risque de
décharge électrique lorsque l’accès à la partie postérieure de l’équipement est bloqué.
Pour garantir la sécurité, il faut utiliser la borne à sertir ronde et l’outil approprié pour répondre
aux besoins d’isolation du bornier. Il faudra utiliser des terminaisons à sertir ronde sur les
raccords de tension et intensité.
Il faut raccorder le matériel à la terre avec la borne correspondante par le biais d’un câble le plus
court possible. Cela permet de garantir la sécurité du personnel mais également d’évacuer les
bruits à fréquences élevées directement à la terre par le biais de cette connexion.
Avant d’alimenter l’équipement, les vérifications suivantes devront être réalisées :
• La tension nominale et la polarité.
• Puissance nominale du circuit de transformateur de courant (CT) et intégrité des
raccords.
• Intégrité du raccord à la terre.
L’équipement doit être utilisé en respectant les plages électriques et environnementales
stipulées.
Remarque relative aux circuits des transformateurs d'intensité : Ne pas ouvrir le circuit
secondaire d’un CT sous tension. La haute tension produite pourrait endommager les isolations
et être mortelle pour les personnes concernées.
1.5.Stockage
Si les relais ne seront pas installés immédiatement, après examen visuel, ils doivent être stockés
dans un air dépourvu de poussière et d’humidité.
1.6.Recyclage
Avant de recycler le matériel, les condensateurs doivent être déchargés par le biais des bornes
extérieures. Auparavant, et afin d’éviter le risque de décharge électrique, toutes les sources
d’alimentation électrique doivent être éliminées.
Ce produit doit être mis au rebus de manière sécurisée en évitant son incinération et tout contact
avec des sources d’eau comme les rivières, les lacs, etc.
2.1.SILAXX Révision A
2.1.1.Dimensions
Dimensions en mm
Découpe de tôle
2.1.2.Diagrammes de connexion
C2 Entrée digitale 6
C3 Entrée digitale 7
C4 Entrée digitale 8
2.2.1.Dimensions
Dimensions en mm
Découpe de tôle
B2 Entrée digitale 2
B3 Entrée digitale 3
B4 Entrée digitale 4
C1 Entrée digitale 5
C2 Entrée digitale 6
C3 Entrée digitale 7
C4 Entrée digitale 8
C1 Entrée digitale 5
C2 Entrée digitale 6
C3 Entrée digitale 7
C4 Entrée digitale 8
3.1. Introduction
Le secteur de l’énergie connaît une transformation profonde au niveau mondial en raison de la
demande élevée en énergie : plus de lignes de distributions sont requises avec des systèmes de
surveillance avancés. Face au besoin de créer des infrastructures intelligentes, FANOX a conçu
la gamme SIL pour remplir cette fonction.
Les relais de la gamme SIL sont conçus pour protéger les centres secondaires de transformation
et les centres de distribution des réseaux électriques. Leurs prestations comprennent la
protection contre les surintensités instantanées et à temps inverse (pour les phases et le neutre)
ainsi qu'une aide pour l'enclenchement extérieur (température, pression, etc.) en fonction des
caractéristiques de chaque modèle.
Les fonctions de protection peuvent être activées de manière sélective par le biais de l’écran
avant ou de la liaison de communication avec le programme SIcom, facilitant une coordination
précise avec les autres équipements.
Tous les modèles disposent d’un autre avantage : ils ont été conçus afin d'être alimentés par une
pile extérieure et de faciliter la mise en marche des centres, la gestion des incidents ou de
fonctionner dans des conditions défavorables.
3.2. Description
L’équipement SIL-A est un relais de protection orienté vers la distribution secondaire.
Il est alimenté avec une tension auxiliaire de 110-230
Vca / 90-300 Vcc. Il est possible de sélectionner une
tension auxiliaire de 24-48 Vcc ou 24-220 Vdc/48-230
Vac en fonction du modèle.
En plus des fonctions de protection contre la
surintensité instantanée à phase et neutre, et de
protection contre la surintensité à temps inverse à
phase et neutre, il est possible de sélectionner en
fonction du réenclencheur, surveillance de disjoncteur
ou surintensité de séquence négative. Il est
également doté d’un système de blocage de
l’enclenchement afin de protéger le sectionneur sur
les centres qui associent sectionneur et fusible.
Tous les modèles comprennent le système de gestion
de l’interrupteur qui contrôle l’état de l’interrupteur, le
nombre des ouvertures et les ampères cumulés, en
générant une indication en cas d’excès de ceux-ci;
cela détermine la production de tout défaut d’ouverture et cela permet le fonctionnement des
commandes d’ouverture et de fermeture de l’interrupteur à partir du HMI et des communications
(sur place ou à distance).
Facultativement, SIL-A révison B offre 49, 74CT, 37, 46BC et blocage de l’enclenchement.
Révision A Révision B
Afin de faciliter l’analyse des incidences, deux systèmes d’enregistrement oscillographiques sont
installés. Le lancement de l’oscillographie peut être configuré par l’utilisateur. Chaque registre
oscillographique contient les courants de phase et de neutre, des démarrages et des
enclenchements des fonctions de protection, des entrées, des sorties, etc. Le format utilisé est
COMTRADE (IEEE C37.111-1991).
Révision A Révision B
L’équipement SIL-A est présenté dans un boîtier métallique avec une isolation galvanisée de
toutes les entrées et sorties, numériques ou pour la mesure (les communications et
l’alimentation de la pile, s’agissant de connexions sporadiques).Cela permet à l’équipement de
présenter le niveau le plus élevé de compatibilité électromagnétique qu’il s’agisse des rayonnés
ou des conduits, en émissivité ou en immunité, ces niveaux étant identiques aux niveaux établis
pour les sous-stations primaires.
Il est doté d’un écran LCD de deux rangées et vingt colonnes, d’un clavier à membrane de 6
touches permettant de consulter l’état de l’équipement, les mesures du courant primaire, les
réglages des critères de protection, et les événements ou incidences associées à l’équipement.
Ces événements, en fonction du modèle, peuvent être stockés dans la mémoire non volatile
pour leur conservation en l’absence d'alimentation.
Il dispose également de huit indicateurs LED.
L’équipement peut stocker jusqu’à 500 événements (révison A) ou 200 événements (révision B)
permettant d’analyser les incidences enregistrées. Le SIL-A est doté d’une horloge en temps réel
(RTC) sur tous les modèles.
Révision A Révision B
Les mesures d’intensité s’effectuent dans des valeurs r.m.s. avec une précision de 2 %. Les
transformateurs de courant utilisés sont des CT standards de 5 A et 1 A.
Il dispose de deux ports de communication : un port avant (RS232) et un port arrière (RS485)
facultatif. Le port RS232 permet la connexion d’un PC et le contrôle de l’équipement en utilisant
le programme de communication SICom (fourni par FANOX). Le port arrière RS485 permet
l’intégration de l’équipement au système (SCADA). Le protocole utilisé pour les deux ports est le
Révision A Révision B
Grâce aux fonctions de protection disponibles, son interface facile à utiliser, ses exigences
réduites de maintenance et son intégration simple, le SIL-A représente une solution précise et
pratique pour la protection des réseaux électriques et des centres de transformation et de
distribution, industriels ou publics.
Les principales caractéristiques de l’équipement sont indiquées dans la liste ci-dessous ; ces
listes seront expliquées dans le manuel:
Protection
79 Réenclencheur 5
52 Nombre d’ouvertures ✓
Ampères cumulés ✓
Mesures
Entrées et sorties
Entrées 8 6
5 4
Sorties 2 (NO/NC) + 3 (NO) 2 (NO/NC) + 2 (NO)
Communication
✓
Port avant
1 port RS232: ModBus RTU
✓ (optionnel) ✓ (optionnel)
2 1:
2 RS485: ModBus 1 port RS485: ModBus RTU ou IEC
RTU et IEC 60870- 60870-5-103
Port arrière 5-103
1 RJ45: IEC61850, DNP3.0 ou IEC
1 RS485 ModBus 60870-104
RTU et 1RJ45: IEC
61850, DNP3.0 ou
IEC 60870-104
Ouverture de session : 4
niveaux d’accès avec clé ✓
configurable
6 touches + 1 bouton de
✓
réinitialisation + 52 + 79
8 leds: 8 leds:
Indicateurs LED 6 configurable All configurable
2 non configurable
Alimentation
24-48 Vdc
Auxiliary voltage . 24-110 Vdc./48-230 Vac
90Vdc–300Vdc /110Vac–230 Vac
Menu de test ✓
Autodiagnostic ✓
Adjustments Table
By general settings
3 setting tables 4 setting tables
By Inputs
Mechanical
*Les événements enregistrés dans la FRAM seront conservés en cas de défaut d’alimentation comme mémoire non
volatile.
PHASE NEUTRAL
0 Standard (In = 1A / 5A). Defined by General Setting
1 In = 1 A; (0,10 – 30,00 A)
5 In = 5 A; (0,50 – 150,00 A)
X X LPCT (Primary In = 50 – 800A). Defined by General Setting
NEUTRAL MEASUREMENT
0 Standard (In = 1A / 5A). Defined by General Setting
1 In = 1 A; (0,10 – 30,00 A)
5 In = 5 A; (0,50 – 150,00 A)
S Sensible (In = 0,1A / 0,5A). Defined by General Setting
X X LPCT: Internally Calculated.
NET FREQUENCY
0 (50Hz / 60Hz). Defined by General Setting
5 50 Hz
6 60 Hz
POWER SUPPLY
A 24-48 Vdc
B 90-300 Vdc / 110-230 Vac
C 24-110 Vdc/48-230Vac
ADDITIONAL FUNCTIONS
0 0 -
1 + 49
2 + 49 + 74CT + 37 + 46BC + Trip Block for switch
disconnector
REAR COMMUNICATIONS
0 RS485: ModBus + IEC 60870-5-103
1 FOP: ModBus + IEC 60870-5-103
2 FOC-ST: ModBus + IEC 60870-5-103
3 RJ45: IEC61850 + RS485: ModBus (not available in LPCT
model)
4
RJ45: DNP3.0 (TCP/IP) + RS485: ModBus(not available in
5 LPCT model)
RJ45: IEC 60870-5-104 + RS485: ModBus (not available in
LPCT model)
INPUTS-OUTPUTS
0 8 Inputs + 5 Outputs. Configurable
1 6 Inputs + 4 Outputs. Configurable.
MECHANICS
0 LPCT model: 4U x ½ Rack
1 Standard model: 4U x ½ Rack
2 LPCT & Standard: 4U x ¼rack
LANGUAGE
A A English, Spanish and German
B B English, Spanish and Turkish
C C English, Spanish and French
D D English, Spanish and Russian
RÉVISION
A -
B -
Révision B
0,1-30 A/0,5-150 A
Raccord résiduelle de phases
SIL-A0S 1 A or 5 A 0,1-30 A/0,5-150 A ou
0.5A or 0.1A
0,01-3A/0.05-15A
0,05-15 A/0,25-75 A
Raccord résiduelle de phases ou
SIL-AS0 0.5A or 2.5A 1A or 5A 0,05-15 A/0,25-75 A
0,1-30 A/0,5-150 A
0,05-15 A/0,25-75 A
Raccord résiduelle de phases ou
SIL-ASS 0.5A or 2.5A 0.5A or 0.1A 0,05-15 A/0,25-75 A
0,01-3A/0.05-15A
I
Seuil 0,10 30,00 0,01 5,00
nominale
Temps
0,02 300,0 0,01 s 0,02
fonctionnement
Si l’option « Temps défini » est sélectionnée lors de l’ajustement de la courbe, l’unité agit comme
une unité de surintensité instantanée. Dans ce cas, le temps de fonctionnement de l’unité est
celui qui est ajusté par le biais du paramètre « Temps de fonctionnement ».
Si une courbe est sélectionnée lors du réglage de la courbe (inverse, très inverse ou
extrêmement inverse), le temps de fonctionnement dépend des réglages des courbe, dial et
seuil.
Temps
0,02 300,0 0,01 s 0,02
fonctionnement
Temps
0,02 300,0 0,01 S 0,02
fonctionnement
Si l’option « Temps défini » est sélectionnée lors de l’ajustement de la courbe, l’unité agit comme
une unité de surintensité instantanée. Dans ce cas, le temps de fonctionnement de l’unité est
celui qui est ajusté par le biais du paramètre « Temps de fonctionnement ».
Si une courbe est sélectionnée lors du réglage de la courbe (inverse, très inverse ou
extrêmement inverse), le temps de fonctionnement dépend des réglages des courbe, dial et
seuil.
Si l’unité fonctionne en temps défini, le démarrage de la fonction se produit à 100 % de la seuil
ajustée et se remplace à 95 %.
Si l’unité fonctionne en courbe, le démarrage de la fonction se produit à 120 % de la seuil
ajustée et se remplace à 100 %. Le remplacement est instantané dans les deux cas.
La précision du temps d’intervention est de ± 5 % ou ± 30 ms, le plus important étant appliqué,
sur le temps théorique d’intervention.
Les courbes utilisées avec IEC 60255-151 et ANSI IEE, sont décrites au paragraphe «Courbes».
Autorisation - - OUI/NO - No
46
Seuil 0,10 7,00 0,01 Inominal 1,00
Révision B
Autorisation - - OUI/NO - No
IEC Extrem.
Courbe - - (1*) -
Inverse
46
Dial 0,02 2,20 0,01 - 1,25
(1*) IEC Inverse, IEC Very Inverse , IEC Extremely Inverse , IEC long time inverse, ANSI Inverse, ANSI very inverse,
ANSI extremely inverse, Defined time
Si une courbe est sélectionnée lors du réglage de la courbe (inverse, très inverse ou
extrêmement inverse), le temps de fonctionnement dépend des réglages des courbe, dial et
seuil.
Si l’unité fonctionne en temps défini, le démarrage de la fonction se produit à 100 % de la seuil
ajustée et se remplace à 95 %.
Si l’unité fonctionne en courbe, le démarrage de la fonction se produit à 120 % de la seuilajustée
et se remplace à 100 %. Le remplacement est instantané dans les deux cas.
La précision du temps d’intervention est de ± 5 % ou ± 30 ms, le plus important étant appliqué,
sur le temps théorique d’intervention.
Les courbes utilisées avec IEC 60255-151 et ANSI IEE, sont décrites au paragraphe «Courbes».
Autorisation - - OUI/No - No
ζ refroidissement 1 6 1 ζ heating 1
Alarme 20 99 1 % 80
Th %
100%
75%
1 2 3 4
alarm
trip
52 Surveillance de l’interrupteur
Dépassement du nombre
1 10000 1 - 10
d’ouvertures
Dépassement du nombre
1 10000 1 - 3
des ouvertures répétées
Temps de dépassement
1,00 300,0 0,01 min 9,00
des ouvertures répétées
Remarque : les unités du réglage « Maximum des ampères cumulés » sont MA² (méga-ampères
carrés). Les unités du « Compteur d’ampères cumulés » sont KA² (kilo-ampères carrés).
Il faut également attribuer les entrées logiques 52a et/ou 52b à une entrée physique.
Cette fonction nous informera de l’état de l’interrupteur et s’il existe une alarme de maintenance.
52 Surveillance de l’interrupteur
Début
Erreur
Ouvert
Fermé
Temps de fermeture
Défaut de fermeture
Défaut Défaut
ouver. ferm.
Faute d'ouverture
Trip
50BF
t>
Imax< 8% Inominal
Pickup
Run
50BF
INIT_50BF = 1
Imax< 8% Inominal
Reset
50BF
INIT_50BF = 0
Imax< 8% Inominal
Révision A
Révision B
This:
Réenclencheur
Autorisation - - OUI/No - No
Nombre de ré-enclenchements 1 5 1 - 3
79 Init Input
Reclose Init
+
Configurable Init TimeOut
N=N+1 Reclose
Time
N > Max Number Shots
TimeOut
52 52 Close
Is Open?
No Hold Time
Hold
TimeOut
Time
Close
TimeOut
Time
Reclose Init
52 Close
Reset
TimeOut
Time
Permission - - OUI/No - No
Time to deactivate
In > 10% CLP
decrementing
Time to deactivate
CLP In < 10%
incrementing Time Out
Time Out
In > 10%
Cold Load
Pickup
Run
In < 10%
Time Out
Time Out
Time to activate
CLP
decrementing In < 10%
Autorisation - - OUI/No - No
Groupe de
1 4 1 - 4
réglage
Pas de temps
0.02 300.00 0.01 s 15
de chargement
Temps de
chargement à 0.02 300.00 0.01 s 15
froid
Temps
0.02 300.00 0.01 s 2
fonctionnement
37P Undercurrent
Autorisation - - OUI/No - No
Temps
0.02 300.00 0.01 s 0.02
fonctionnement
Temps
0.02 300.00 0.01 s 0.02
fonctionnement
Blocage rupteur
Réglages généraux
Fréquence - - 60/50 Hz 50
Langue - - - - English
Table active 1 3 1 - 1
Réglages généraux
Fréquence - - 60/50 Hz 50
Numéro de série - - - - 0
Langue - - - - English
Table active 1 4 1 - 1
Standard model:
Standard:1
1, 5, 0.5 or 2.5
Phase Courant nominal - - A
LPCT: 100
LPCT model:
50-800
Courant nominal neutre (**) - - 1, 5, 0.5 or 0.1 A 1
Modbus
IEC60870-5-
Protocole à distance - - RTU/IEC60870-5- -
103
103
01 Table 1
10 Table 2
11 Table 3
Révision B
01 Table 1
10 Table 2
11 Table 3
A D
t BD K
VP Q
I
V
I adjusted
Curbes:
• Courbe inverse
• Courbe très inverse
• Courbe extrêmement inverse
• Courbe l'inverse de longue durée
A
t TD P B
V 1
I
V
I adjusted
Curbes:
• Courbe inverse
• Courbe très inverse
• Courbe extrêmement inverse
Paramètres A P B
Extrêmement
28,2 2 0,1217
inverse
Très inverse 19,61 2 0,491
5.1. Mesures
Les trois courants de phase, le courant de neutre et la tension de neutre sont fournis en
r.m.s. Un échantillonnage de 16 échantillons/cycle est réalisé.
La précision de la mesure est de ± 2 % sur toute la plage de mesure.
Révision A
SIL-A5* 1-150 A * 5A *
SIL-A1* 0,2-30 A * 1A *
SIL-A*5 * 1-150 A * 5A
SIL-A*1 * 0,2-30 A * 1A
Révision B
In 50 A In 50A In 10A
dcba
In 100 A In 100A In 20A
dcba
In 150 A In 150A In 30A
dcba
dcba
In 250 A In 250A In 50A
dcba
In 300 A In 300A In 60A
dcba
In 350 A In 350A In 70A
dcba
In 400 A In 400A In 80A
dcba
In 450 A In 450A In 90A
dcba
In 500 A In 500A In 100A
dcba
In 550 A In 550A In 110A
dcba
In 600 A In 600A In 120A
dcba
dcba
In 700 A In 700A In 140A
dcba
In 750 A In 750A In 150A
dcba
In 800 A In 800A In 160A
3. Nombre de coups
4. Image thermique
Année
Mois
Jour
Heure
Minutes
Secondes
Millisecondes
Révision A:
Nombre
Groupe Bit État Événements Cause Measure associée
Événements
General
- Déclenchement externe
Bit-1 - - -
entrée
- 46 Identification Identification
Bit-00 1 50P_1 Démarrage de phase A 50P_1 Démarrage de phase A Activation/désactivation Courant phase A
Bit-01 2 50P_1 Démarrage de phase B 50P_1 Démarrage de phase B Activation/désactivation Courant phase B
Bit-02 3 50P_1 Démarrage de phase C 50P_1 Démarrage de phase C Activation/désactivation Courant phase C
Bit-00 1 50P_2 Démarrage de phase A 50P_2 Démarrage de phase A Activation/désactivation Courant phase A
Bit-01 2 50P_2 Démarrage de phase B 50P_2 Démarrage de phase B Activation/désactivation Courant phase B
Bit-02 3 50P_2 Démarrage de phase C 50P_2 Démarrage de phase C Activation/désactivation Courant phase C
Bit-00 01 51P Démarrage de phase A 51P Démarrage de phase A Activation/désactivation Courant phase A
Bit-01 02 51P Démarrage de phase B 51P Démarrage de phase B Activation/désactivation Courant phase B
Bit-02 03 51P Démarrage de phase C 51P Démarrage de phase C Activation/désactivation Courant phase C
Réenclencheur
79 Temps de 79 Temps de
Bit-01 02 Activation nombre de réenclenchement
réenclenchement réenclenchement
Interrupteur
Bit-12 13 52 b 52 b Activation/désactivation -
Entrées logiques
bit-4 5
Entrée de déclenchement Entrée de déclenchement Activation/désactivation -
externe externe
Entrée
Sorties
Sortie 1 Sortie 1
bit-0 1 Activation/désactivation -
Sortie 2 Sortie 2
bit-1 2 Activation/désactivation -
Sortie 3 Sortie 3
bit-2 3 Activation/désactivation -
Sortie 4 Sortie 4
bit-3 4 Activation/désactivation -
Sortie 5 Sortie 5
bit-4 5 Activation/désactivation -
79 Init 79 Init
bit-5 6 Activation/désactivation -
ON Led
bit-8 - - - -
Led -1
bit-9 - - - -
Led -2
bit-10 - - - -
Led -3
bit-11 - - - -
Led -4
bit-12 - - - -
Led -5
bit-13 - - - -
Modbus à distance
Communication à
bit-0 - distance. - --
IEC60870-5-103
Bit-00 Communication à
- distance. - --
Local communication
Bit-07 19 -
Changement des ajustemen. Changement des ajustemen. Activation/désactivation
Bit-16 49 Démarrage - - -
Bit-21 54 Enclenchement de A - - -
Bit-22 55 Enclenchement de B - - -
Bit-23 56 Enclenchement de C - - -
- 57 Enclenchement de neutre - - -
- - Enclenchement de phase - - -
Oscillographie
Bit-00 1 50P_1 Démarrage de phase A 50P_1 Démarrage de phase A Activation/désactivation Courant phase A
Bit-01 2 50P_1 Démarrage de phase B 50P_1 Démarrage de phase B Activation/désactivation Courant phase B
Bit-02 3 50P_1 Démarrage de phase C 50P_1 Démarrage de phase C Activation/désactivation Courant phase C
Bit-00 1 50P_2 Démarrage de phase A 50P_2 Démarrage de phase A Activation/désactivation Courant phase A
Bit-01 2 50P_2 Démarrage de phase B 50P_2 Démarrage de phase B Activation/désactivation Courant phase B
Bit-02 3 50P_2 Démarrage de phase C 50P_2 Démarrage de phase C Activation/désactivation Courant phase C
Bit-00 01 51P Démarrage de phase A 51P Démarrage de phase A Activation/désactivation Courant phase A
Bit-01 02 51P Démarrage de phase B 51P Démarrage de phase B Activation/désactivation Courant phase B
Bit-02 03 51P Démarrage de phase C 51P Démarrage de phase C Activation/désactivation Courant phase C
Bit-01 - 52 Fermer - - -
Bit-02 - 52 Ouvert - - -
Bit-12 02 Cold load Pickup Cold load Pickup Activation/désactivation Courant de phase
Réenclencheur
Interrupteur
Bit-12 13 52 b 52 b Activation/désactivation -
Undercurrent
Bit-00 01 37 Démarrage de phase A 37 Démarrage de phase A Activation/désactivation Courant phase A
Sorties
Bit-08 01 Sortie 1 Sortie 1 Activation/désactivation -
Logique
Bit-13 18 52 a 52 a Activation/désactivation -
Bit-14 19 52 b 52 b Activation/désactivation -
Modbus à distance
Bit-00 Communication à
- - - --
distance
IEC60870-5-103
Bit-00 IEC60870-5-103
- Communication - -- -
Local communication
Les informations des deux rapports de défauts les plus récents sont disponibles à tout
moment. Chaque nouveau rapport de défaut généré est stocké sur le rapport le plus
ancien; les informations de ce dernier sont donc perdues.
L’oscillographie est recueillie par les communications à partir du port avant ou arrière à
travers le protocole Modbus (le protocole est décrit dans ce manuel). Le programme de
communications SICom permet de recueillir l’oscillographie et de la conserver dans un
format COMTRADE (IEEE C37.111-1991).
Les informations comseuils sur chaque enregistrement oscillographique sont les
suivantes:
1 Courant phase A
2 Courant phase B
3 Courant phase C
4 Courant neutre
Les informations complémentaires suivantes sont incluses dans le fichier de titre (*.hdr) de
COMTRADE : date-heure de l’oscillographe, numéro de l’oscillographe, identificateur du
relais et liste de tous les événements générés dans l’équipement pendant la génération de
l’oscillographie.
Voici le format d'un fichier de tête de COMTRADE généré par le programme SICom :
Oscillograph: 41458
Date/Heure: 2008/10/15 11:29:11:85
File de défaut = 15
***************************************************************
Événements de l’Oscillo :
***************************************************************
En utilisant le logiciel SICom, il est possible de sauvegarder l'oscillo sous forme de fichier
COMTRADE
L’oscillographie est recueillie par les communications à partir du port avant ou arrière à
travers le protocole Modbus (le protocole est décrit dans ce manuel). Le programme de
communications SICom permet de recueillir l’oscillographie et de la conserver dans un
format COMTRADE (IEEE C37.111-1991).
Les informations comseuils sur chaque enregistrement oscillographique sont les
suivantes:
1 Courant phase A
2 Courant phase B
3 Courant phase C
4 Courant neutre
Voici le format d'un fichier de tête de COMTRADE généré par le programme SICom :
Oscillograph: 1
Date/Heure: 2016/10/15 11:26:11:85
File de défaut = 15
***************************************************************
Événements de l’Oscillo :
***************************************************************
Une oscillographie est démarrée lorsque l'état "fault init" est activé; c'est un signal logique
configurable. La configuration par défaut est la suivante:
En utilisant le logiciel SCom, il est possible de sauvegarder l'oscillo en tant que fichier
COMTRADE
52 a
52 b
X
Déclenchement externe
50BF Init
Erreur Init
Bloc 50P
Bloc 50N
Réinitialiser
Groupe de paramètres 1
Groupe de paramètres 2
79 Init
79 Activer
79 Bloc
Verrouiller 79
Débloquer 79
74TCS Continuité A
74TCS Continuité B
Signal logique 1
Signal logique 2
ADAPTATION A
Tout état disponible peut être affecté à une sortie. Jusqu'à 16 états différents peuvent être
affectés à une seule sortie en se basant sur la logique suivante (SILA /):
LED 1
LED 2
LED 3
LED 4
LEDs LED 5
LED 6
Sortie 1
Sortie 2
Sortie 4
Sortie 5
Entrée 52 a
Bloc 50N
Erreur init
79 Entrée d'entrée
79 Autorisation
Serrure de niveau 79
Serrure Pulse 79
Pulse 79 déverrouiller
Tableau 1
Tableau 2
79 Init
Faute Init
Toutes les sorties (Leds, sorties physiques et signaux logiques) sont le résultat d'un
CONTRÔLE LOGIQUE PROGRAMMABLE qui peut être configuré depuis HMI ou depuis
le logiciel SICom.
Pour chaque sortie il y a une PORTE LOGIQUE. Il peut effectuer une opération logique
jusqu'à 16 états binaires pour obtenir un autre résultat binaire.
NOR_LACTH
LOGIQUE DE
SORTIE ÉTATS BINAIRES
PORTE
• 50P1 Enclenchement
LED 2 OR_4 LATCH • 50P2 Enclenchement
• 51P Enclenchement
• 50N1 Enclenchement
LEDs LED 3 OR16_LACTH • 50N2 Enclenchement
• 51N Enclenchement
• Général Enclenchement
SORTIES • Disjoncteur ouvert local
PHISIQUES Sortie 4 OR16 • Disjoncteur ouvert modbus à
distance
• Disjoncteur ouvert 60870-5-103
• 79 temps de fermeture
• Disjoncteur fermé local
Sortie 5 OR16 • Disjoncteur fermé modbus à
distance
• Disjoncteur fermé 60870-5-103
• 50P Enclenchement
• 51P Enclenchement
• 50N Enclenchement
79 init OR16
• 51N Enclenchement
• 46 Enclenchement
• 79 entrée
SORTIES
LOGIQUES • Entrée 50BF
• Ouverture IHM / Modbus locale
50BF Init OR16 • Ouverture ModBus
• Ouverture à distance
• General trip
pas configuré -
Niveau 79 Lock
pas configuré -
Serrure Pulse 79
pas configuré -
Pulse 79 déverrouiller
pas configuré -
50BF Init Entrée
pas configuré -
Tableau 2
Logical signals are internal binary states result of the Programmable Logic Control. The
logical signal has a specific and defined meaning to be used by the rest functions of the
Device.
LED 1
LED 2
LED 3
LED 4
LEDs LED 5
LED 6
LED 52
LED 79
Sortie 1
Sortie 2
SORTIES PHISIQUES
Sortie 3
Sortie 4
52a
52b
Déclenchement externe
Début 50BF
Début de la panne
Bloc 50P
Bloc 50N / G
SIGNAUX LOGIQUES
Réinitialiser
Groupe de paramètres 1
Groupe de paramètres 2
Continuité A
Continuité B
Signal logique 1
Signal logique 2
LOGIQUE DE
SORTIE BINARY STATES
PORTE
• 50P1 Enclenchement
LED 2 OR4_LATCH • 50P2 Enclenchement
• 51P Enclenchement
• 50N1 Enclenchement
LED 3 OR4_LACTH • 50N2 Enclenchement
• 51N Enclenchement
LEDs
LED 4 OR4_LACTH • 50BF Enclenchement
• 79 temps de fermeture
• Disjoncteur fermé local
Sortie 2 OR4 • Disjoncteur fermé modbus à
distance
PHYSICAL • Disjoncteur fermé 60870-5-103
OUTPUTS
Sortie 3 OR4 • 50BF Enclenchement
5.11. Autodiagnostic
Des algorithmes de diagnostic sont réalisés au démarrage de l’équipement et en continu
pendant le fonctionnement du relais. Ce diagnostic garantit le bon état de fonctionnement
de l’équipement comme processus préventif.
Considérations générales :
• Les communications entre plusieurs microprocesseurs sont confirmées par les
vérifications d’intégrité correspondantes. En cas d’anomalies continues, une
réinitialisation de l’équipement sera réalisée.
• Les données qui constituent les ajustements sont confirmées par les vérifications
correspondantes. De même, tous les tableaux d’ajustements sont doublés et le relais
peut travailler avec un tableau défectueux mais pas avec deux tableaux défectueux.
• Il existe un mécanisme de WatchDog parmi les différentes CPUs principaux ainsi qu'à
l'intérieure d'elles-mêmes. La perte d’activité dans l’une d’elles supposera la
réinitialisation de l’équipement qui sera indiqué comme un événement.
D’autre part, « Ajustement par défaut » indique que le relais fonctionne avec les
ajustements en usine, et toutes les fonctions de protection sont désactivées
Communication à distance:
Modbus
Local Com.
HMI IEC 60870-5-103
ModBus
IEC61850
DNP 3.0
52 ouvert ✓ ✓ ✓
52 fermer ✓ ✓ ✓
Verrouiller 79 ✓ ✓ ✓
Débloquer 79 ✓ ✓ ✓
Telecontrol OUI ✓ ✓ -
PAS de téléconduite ✓ ✓ -
Effacer 86 ✓ ✓ ✓
Révision B
Communication à
distance Modbus
Local Com. IEC 60870-5-103
HMI
ModBus
IEC61850
DNP 3.0
52 ouvert ✓ ✓ ✓
52 fermer ✓ ✓ ✓
Verrouiller 79 ✓ ✓ ✓
Débloquer 79 ✓ ✓ ✓
Telecontrol OUI ✓ ✓ -
PAS de téléconduite ✓ ✓ -
Effacer 86 ✓ ✓ ✓
Effacer TI ✓ ✓ ✓
5.13. Telecontrol
L'équipement peut uniquement être réglé sur télécontrôle ou contrôle local depuis l'IHM ou
via le logiciel de communication (SICOM).
Si Telecontrol est utilisé, il est recommandé de configurer une led à afficher lorsque
Telecontrol est autorisé et quand ce n'est pas le cas.
Reposicionnement instantanée
Reposicionnement instantanée
Précision du temporisation: ± 30 ms ou ± 0,5% (plus grand des deux)
Dial: 0.05 to 2.20 (pas 0.01) Dial: 0.02 to 2.20 (pas 0.01)
Reposicionnement instantanée
Dial: 0.05 to 2.20 (pas 0.01) Dial: 0.05 to 2.20 (pas 0.01)
50/51N/G (1)
Niveau d’activetion du courbe 110%
Reposicionnement instantanée
Seuil: 0.10 to 1.00 xIn (pas 0.01) Seuil: 0.10 to 7.00 xIn (pas 0.01)
Operating time: 0.02 to 300 s (pas 0.01 s) Curbes IEC 60255-151 et ANSI
Reposicionnement instantanée
État de l’interrupteur : début, ouvert, fermé, erreur, temps d’ouverture, erreur d’ouverture, temps de fermeture,
erreur de fermeture
Function Pickup configurable: Equipment trip, activation of the opening fault input, circuit breaker open control
activation.
Nombre de ré-enclenchements: 1 to 5
Temps fonctionnement: 0.02 to 300 s (pas 0.01 s) Temps fonctionnement: 0.02 to 300 s (pas 0.01 s)
Multiplicateur 50/51: 1 to 5
86 Permet de verrouiller (verrouiller) le déclenchement du contact en raison d'une logique programmable (PLC:
LATCH).
Les courbes de temps de parcours sont valables moins de 20 fois le tap ajusté. Avec des courants supérieurs à 20
fois le tarage ajusté, le temps de déclenchement et la valeur de l'image thermique sont tronqués à 20 fois le taraud
ajusté.
Réinitialisation instantanée
68 (*) Indisponible Disponible via des entrées et sorties configurables grâce à une
logique programmable
Oscillographie 2 enregistrements de 50 cycles: 3 cycles préfault 5 enregistrements de 100 cycles: 3 cycles préfault et 97 cycles
et 47 cycles post-défaut post-défaut
COMTRADE IEEE C37.111-1991 COMTRADE IEEE C37.111-1991
Rapports d'erreur 20 rapports d'erreurs avec 80 événements chacun 20 rapports d'erreurs avec 24 événements chacun
Entrées Même tension que l'alimentation auxiliaire Même tension que l'alimentation auxiliaire
configurables 8 entrées configurables 6 entrées configurables
Mesure de courant Courant de phase (IA, IB, IC), neutre (IN), séquence positive
Courant de phase (IA, IB, IC), neutre (IN) et
(I1), séquence négative (I2), courant maximum (Imax) et image
séquence négative (I2).
thermique (TI)
Real RMS
± 2% Précision sur une bande de ± 20% sur le courant nominal et de 4% sur le reste de la plage
Mesure 3 ou 4 CT / 5 ou / 1
Transformateurs
Mesure 3 LPCT (transformateurs de courant avec sortie de tension)
Boîte métallique
IP-54 on pannel
1.5. Radiated radiofrequency IEC 60255-26 Level 3, Test field strenght 10V/m, Frequency
electromagnetic fields IEC 61000-4-3 80MHZ - 1000MHz and 1400MHz - 2000MHz,
AM Modulation 80% for 1KHz carrier
sinusoidal signal
1.6. Electrical fast transients IEC 60255-26 Level 4, Power supply to Earth terminals ±4kV,
IEC 61000-4-4 Signal and control terminals ±2kV. Repetition
frequency 5KHz, Burst duration 75s.
1.7. Surge IEC 60255-26 Level 4, Line to earth for all terminals ±4kV.
IEC 61000-4-5 Line to Line for all terminals excepts
Communication port ±2kV
1.8. Conducted disturbance IEC 60255-26 Level 3, Applied voltage 10V, Frequency
induced by radio frequency fields IEC 61000-4-6 0.15MHz - 80 MHz, AM Modulation 80% for
1KHz carrier sinusoidal signal, Dwell time 1s.,
Test duration >10s.
1.9. Voltage dips, short IEC 60255-26 DC Voltage Dips: 40%, 130ms and 70%,
interruptions and voltage variations IEC 61000-4-11 100ms, 3 times every 10s.
DC Voltage Interruption: 100ms, 3 times every
IEC 61000-4-29
10s.
1.10. Ripple on DC input power IEC 60255-26 Level 4, Ripple 15%, 50Hz and 100Hz
port IEC 61000-4-17
1.11. Power frequency magnetic IEC 60255-26 Level 5, Continuous field strenght 100 A/m.
field IEC 61000-4-8 Short field strenght for a duration of 3s. 1000
A/m. Frequency 50Hz.
1.12. 100KHz damped oscillatory IEC 61000-4-18 Class 3, Repetition frequency 40Hz, Duration
waves of each application 3s. Common mode:
±2.5kV. Differential mode: ±1kV
2.3. Insulation resistance IEC 60255-27 500V applied between each group to earth
IEC 60255-5 and with rest of the groups in short-circuit
2.4. Protective bonding IEC 60255-27 Test current 2xIn, Test voltage 12Vac during
resistance 60s. Resistance shall be less than 0.1 ohm
3. Burden
3.1. AC burden for CT IEC 60255-1 Declared on manual
3.2. AC burden for VT
3.3. AC, DC burden for power
supply
3.4. AC, DC burden for binary
inputs
4. Contact performance
IEC 60255-27
5. Communication
requirements
ModBus RTU
IEC 61850
IEC 60870-5-103
IEC 60870-5-104
DNP 3.0
6.3 Change of temperature IEC 60068-2-14 Change of Temperature Nb, Upper temp
+70ºC, Lower temp -25ºC, 5 cycles, Exposure
time 3h, Transfer time 2 min.
6.4 Damp heat IEC 60068-2-30 Damp Heat Cyclic Db, Upper temp +40ºC,
Humidity 93%, 2 cycles. Relay energized
7.4. Seismic IEC 60255-21-3 Single Axis Sine Sweep, Class 1, X Axis: 1 to
9Hz, 3.5mm and 9 to 35Hz, 1gn; Y Axis: 1 to
IEC 60068-21-3
9Hz, 1.5mm and 9 to 35Hz, 0.5gn
8. Electrical environmental
requirements
8.1. CT Input continuous IEC 60255-27 3xIn without damage for continuous operation
overload
8.2. CT Input short time IEC 60255-27 70xIn without damage for 1s short time
overload overloading
8.3. VT Input continuous IEC 60255-27 Declared on manual, without damage for
overload continuous operation
8.4. VT Input short time IEC 60255-27 Declared on manual, without damage for 10s
overload short time overloading
9. Enclosure protection
1 SI SI NO NO SI
2 SI SI NO NO NO
3 SI NO SI NO NO
4 SI SI SI NO NO
5 SI SI SI SI NO
2222 2
3333 3
4444 4
5555 5
Révision A
SILA555C2A12BB
0.00 0.00 0.00 0.00
Révision B
• ERREUR DE PROTECTION
• ERREUR DE MESURE
• ERREUR EEPROM
Il n’est pas nécessaire d’introduire un mot de passe pour lire et visualiser les paramétres,
les mesures, les réglages…
Pour modifier n’importe quel paramètre, il est nécessaire d’introduire unj mot de passe de
4 caracteres.
Une fois revenu à l’ecran principale et comme mesure de sécurité, il sera nécessarire de
réintroduire le mot de passe pour réaliser une nouvelle modification.
Pour se déplacer d’une unité à une autre dans un paramètre, il suffit d’utiliser les touches
◄ et ►. Pour modifier chaque unité il faut utiliser les touches ▲, ▼ pour augmenter ou
réduire la valeur. Si une valeur non valide est introduite, il faut utiliser la touche “C” pour
l’effacer.
↓
OK C
01/01/2000 01:43
Révision A
serial number:
▲ C
0
Révision B
À partir l’écran de repos, en appuyant la touche “▼” de manière mantenue, nous visualisons les
paramétres de communication:
LOCAL Settings
1 19200-8-N-1
Set Password
◄▼▲► C
-> 5555
Led-1:
OK C
not activated
Led-1:
OK
<<ACTIVATED>>
Led-2:
OK
<<ACTIVATED>>
Led-3:
▲▼ C
not activated
Led-3:
OK
<<ACTIVATED>>
Led-4:
▲▼ C
not activated
Led-4:
OK
<<ACTIVATED>>
Led-5:
▲▼ C
not activated
Led-5:
OK
<<ACTIVATED>>
Led-6:
C
not activated
Led-79:
▲▼ C
not activated
Led-79:
OK
<<ACTIVATED>>
Led-52:
▲▼ C
not activated
Led-52:
OK
<<ACTIVATED>>
Output 1:
▲▼ C
not activated
Output 1:
OK
<<ACTIVATED>>
Output 2:
▲▼ C
not activated
Output 3:
▲▼ C
not activated
Output 3:
OK
<<ACTIVATED>>
Output 4:
▲▼ C
not activated
Output 4:
OK
<<ACTIVATED>>
Output 5:
▲▼ C
not activated
Output 5:
OK
<<ACTIVATED>>
STATES
▲▼ C
SETTINGS GEN
▲▼ C
T.A=1 COM
EVENTS
▲▼ C
There are 5
COUNTERS
▲▼ C
COMMANDS
▲▼ C
Pour acceder au second niveau à partir l’écran principal, appuyé la touche “OK”. Dans le second niveau, pour se déplacer d’une section du Menu á une
autre, il faut utiliser les touches ▲ et ▼. Pour retourner à un niveau supérieur, utilisez la touche “ C”.
Révision A
↑ MEASUREMENTS SILA555B1001BA
OK C
↓ 0.00 0.00 0.00 0.00
I-A 1/6
OK
0.00 *A
I-B 2/6
▲▼ C
0.00 A
I-0 4/6
▲▼ C
0.00 A
I-2 5/6
▲▼ C
0.00 A
TI 6/6
▲▼ C
20
Révision B
↑ MEASUREMENTS SILA000C2A12BB
OK C
↓ 0.00 0.00 0.00 0.00
I-A 1/8
OK
0.00 *A
I-B 2/8
▲▼ C
0.00 A
I-0 4/8
▲▼ C
0.00 A
I-2 5/8
0.00 A
I-1 6/8
▲▼ C
0.00 A
IMax 7/8
0.00 A
TI 8/8
▲▼ C
20
↑STATES SILA555B1001BA
C
↓ 0.00 0.00 0.00 0.00
Phase B Pickup:
▲▼ C
not activated
Phase C Pickup:
▲▼ C
not activated
Phase Pickup:
▲▼ C
not activated
Phase A Trip:
▲▼ C
not activated
Phase B Trip:
▲▼ C
not activated
Phase Trip:
▲▼ C
not activated
Phase B Pickup:
▲▼ C
not activated
Phase C Pickup:
▲▼ C
not activated
Phase Pickup:
▲▼ C
not activated
Phase A Trip:
▲▼ C
not activated
Phase B Trip:
▲▼ C
not activated
Phase Trip:
▲▼ C
not activated
Phase B Pickup:
▲▼ C
not activated
Phase C Pickup:
▲▼ C
not activated
Phase Pickup:
▲▼ C
not activated
Phase A Trip:
▲▼ C
not activated
Phase C Trip:
▲▼ C
not activated
Phase Trip:
▲▼ C
not activated
Ground Trip:
▲▼ C
not activated
↑STATES
▲▼ Sta. 50N2 C
↓
Ground Pickup:
OK C Sta. 50G2/50N2
not activated
Ground Trip:
▲▼ C
not activated
Trip:
▲▼ C
not activated
Pickup: Sta. 46
OK C
not activated
Trip:
▲▼ C
not activated
Sta. 49 ↑STATES
▲▼ C
↓
Pickup: Sta. 49
OK C
not activated
Trip:
▲▼ C
not activated
50 Hz:
▲▼ C
<<ACTIVATED>>
Measure error:
▲▼ C
not activated
Setting changed:
▲▼ C
not activated
Set Date/Time:
▲▼ C
not activated
No Telecontrol:
▲▼ C
not activated
FactorySetting:
▲▼ C
not activated
Eeprom error:
▲▼ C
not activated
Eeprom changed:
▲▼ C
not activated
I. 52b:
▲▼ C
not activated
I. 50P block:
▲▼ C
not activated
I. 50G/50N block:
▲▼ C
not activated
I. Ext Trip:
▲▼ C
not activated
I. Fault. init:
▲▼ C
not activated
I. 79 Enable:
▲▼ C
not activated
I. 79 Block:
▲▼ C
not activated
I1-Sett Table:
▲▼ C
not activated
I2-Sett Table:
▲▼ C
not activated
Lock 79:
▲▼ C
not activated
Unlock 79:
▲▼ C
not activated
I. 50BF Init:
▲▼ C
not activated
Input 1:
▲▼ C
not activated
Input 3:
▲▼ C
not activated
Input 4:
▲▼ C
not activated
Input 5:
▲▼ C
not activated
Input 6:
▲▼ C
not activated
Input 7:
▲▼ C
not activated
Input 8:
▲▼ C
not activated
Control Voltage:
▲▼ C
not activated
Continuity B:
▲▼ C
not activated
LedON:
OK C
not activated
Led1:
▲▼ C
not activated
Led2:
▲▼ C
not activated
Led3:
▲▼ C
not activated
Led4:
▲▼ C
not activated
Led5:
▲▼ C
not activated
Output 3:
▲▼ C
not activated
Output 4:
▲▼ C
not activated
Output 5:
▲▼ C
not activated
79 Init:
▲▼ C
not activated
50BF Init:
▲▼ C
not activated
Fault Init:
▲▼ C
not activated
Standby:
OK C
not activated
Reclose Time:
▲▼ C
not activated
79 Is 52 Open?:
▲▼ C
not activated
79 Hold Time:
▲▼ C
not activated
79 Close Time:
▲▼ C
not activated
79 Reset Time:
▲▼ C
not activated
79 Lockout:
▲▼ C
not activated
79 Security T.:
▲▼ C
not activated
Sta. 52 ↑STATES
▲▼ C
>52 Open Error ↓
52 Startup:
OK C
not activated
52 Error:
▲▼ C
not activated
52 Open:
▲▼ C
not activated
52 Open Time:
▲▼ C
not activated
52 Open Error:
▲▼ C
<<ACTIVATED>>
52 Close:
▲▼ C
not activated
52 Close Error:
▲▼ C
not activated
I2t Alarm:
▲▼ C
<<ACTIVATED>>
52A contact:
▲▼ C
not activated
52B contact:
▲▼ C
not activated
Command Select:
▲▼ C
not activated
Open Breaker:
▲▼ C
not activated
Close Breaker:
▲▼ C
not activated
Block Recloser:
▲▼ C
not activated
UnBlock Reclos:
▲▼ C
not activated
↑STATES
▲▼ Sta. REMOTE C
↓
Command Select:
▲▼ C
not activated
Open Breaker:
▲▼ C
not activated
Close Breaker:
▲▼ C
not activated
Block Recloser:
▲▼ C
not activated
UnBlock Reclos:
▲▼ C
not activated
Reset 86
not activated
MMI Activity:
▲▼ C
<<ACTIVATED>>
Local Ctrl.:
▲▼ C
not activated
Command Select:
▲▼ C
not activated
Open Breaker:
▲▼ C
not activated
Close Breaker:
▲▼ C
not activated
Block Recloser:
▲▼ C
not activated
No Telecontrol:
▲▼ C
not activated
Telecontrol OUI:
▲▼ C
not activated
Reset 86
not activated
↑STATES SILA000C2A12BB
C
↓ 0.00 0.00 0.00 0.00
50 Hz:
▲▼ C
<<ACTIVATED>>
TripBlck Enab.:
Not activated
Measure error:
▲▼ C
not activated
Ready:
not activated
Setting changed:
▲▼ C
not activated
Local Ctrl.:
▲▼ C
not activated
FactorySetting:
▲▼ C
not activated
Eeprom error:
▲▼ C
not activated
Eeprom changed:
▲▼ C
not activated
Event error:
▲▼ C
not activated
Reset:
▲▼ C
not activated
Pickup:
▲▼ C
not activated
Phase A pickup:
▲▼ C
not activated
Phase C pickup:
▲▼ C
not activated
Ground pickup:
▲▼ C
not activated
Phase A Trip:
▲▼ C
not activated
Phase B Trip:
▲▼ C
not activated
Phase C Trip:
▲▼ C
not activated
Ground Trip:
▲▼ C
not activated
50P Trip:
▲▼ C
not activated
Phase Trip:
▲▼ C
not activated
Phase B Pickup:
▲▼ C
not activated
Phase C Pickup:
▲▼ C
not activated
Phase Pickup:
▲▼ C
not activated
Phase A Trip:
▲▼ C
not activated
Phase B Trip:
▲▼ C
not activated
Phase Trip:
▲▼ C
not activated
Phase B Pickup:
▲▼ C
not activated
Phase C Pickup:
▲▼ C
not activated
Phase Pickup:
▲▼ C
not activated
Phase A Trip:
▲▼ C
not activated
Phase C Trip:
▲▼ C
not activated
Phase Trip:
▲▼ C
not activated
Phase B Pickup:
▲▼ C
not activated
Phase C Pickup:
▲▼ C
not activated
Phase Pickup:
▲▼ C
not activated
Phase A Trip:
▲▼ C
not activated
Phase C Trip:
▲▼ C
not activated
Phase Trip:
▲▼ C
not activated
Ground Trip:
▲▼ C
not activated
↑STATES
▲▼ Sta. 50N2 C
↓
Ground Pickup:
OK C Sta. 50N2
not activated
Ground Trip:
▲▼ C
not activated
Sta. 46 ↑STATES
▲▼ C
↓
Pickup: Sta. 46
OK C
not activated
Trip:
▲▼
not activated
52 Open:
▲▼ C
not activated
52 Def. open:
▲▼ C
not activated
Close CLP:
▲▼ C
not activated
Open CLP:
▲▼ C
not activated
CLP:
▲▼ C
not activated
Trip:
▲▼ C
not activated
Alarm: Sta. 49
OK C
not activated
Trip:
▲▼ C
not activated
Sta. 79 ↑STATES
▲▼ C
>Lockout ↓
Standby: Sta. 79
OK C
not activated >Lockout
Reclose Time:
▲▼ C
not activated
79 Is 52 Open?:
▲▼ C
not activated
79 Hold Time:
▲▼ C
not activated
79 Reset Time:
▲▼ C
not activated
79 Lockout:
▲▼ C
not activated
79 Security T.:
▲▼ C
not activated
79 Manual Open:
▲▼ C
not activated
Sta. 52 ↑STATES
▲▼ C
>52 Error ↓
52 Startup: Sta. 52
OK C
not activated >52 Error
52 Error:
▲▼ C
not activated
52 Open:
▲▼ C
not activated
52 Open Error:
▲▼ C
<<ACTIVATED>>
52 Close:
▲▼ C
not activated
52 Close Time:
▲▼ C
not activated
52 Close Error:
▲▼ C
not activated
I2t Alarm:
▲▼ C
<<ACTIVATED>>
52B contact:
▲▼ C
not activated
74TCS Alarm:
▲▼ C
not activated
74CT Alarm:
▲▼ C
not activated
Phase B Pickup:
▲▼ C
not activated
Phase C Pickup:
▲▼ C
not activated
Phase Pickup:
▲▼ C
not activated
Phase A Trip:
▲▼ C
not activated
Phase B Trip:
▲▼ C
not activated
Phase C Trip:
▲▼ C
not activated
Phase Trip:
▲▼ C
not activated
Trip:
▲▼ C
not activated
Phase B block:
▲▼ C
not activated
Phase C block:
▲▼ C
not activated
Phase block:
▲▼ C
not activated
Input 2:
▲▼ C
not activated
Input 3:
▲▼ C
not activated
Input 4:
▲▼ C
not activated
Input 5:
▲▼ C
not activated
Input 6:
▲▼ C
not activated
Output 2:
▲▼ C
not activated
Output 3:
▲▼ C
not activated
Output 4:
▲▼ C
not activated
Led2:
▲▼ C
not activated
Led4:
▲▼ C
not activated
Led5:
▲▼ C
not activated
Led6:
▲▼ C
not activated
Led-52:
▲▼ C
not activated
Led-79:
▲▼ C
not activated
Ext Trip:
▲▼ C
not activated
50BF Init:
▲▼ C
not activated
Fault Init:
▲▼ C
not activated
Blck. 50P:
▲▼ C
not activated
Blck. 50N:
▲▼ C
not activated
Reset:
▲▼ C
not activated
SettingsG1:
▲▼ C
not activated
79Init:
▲▼ C
not activated
79 Enable:
▲▼ C
not activated
L Lock 79:
▲▼ C
not activated
P Lock 79:
▲▼ C
not activated
P Unlock 79:
▲▼ C
not activated
74TCS A:
▲▼ C
not activated
74TCS B:
▲▼ C
not activated
Logic Sig2:
▲▼ C
not activated
HMI Activity:
▲▼ C
<<ACTIVATED>>
Open Breaker:
▲▼ C
not activated
Close Breaker:
▲▼ C
not activated
P Lock 79:
▲▼ C
not activated
P Unlck 79:
▲▼ C
not activated
Telecontrol:
▲▼ C
not activated
Reset:
▲▼ C
not activated
Reset TI:
▲▼ C
not activated
Open Breaker:
▲▼ C
not activated
Close Breaker:
▲▼ C
not activated
P Unlck 79:
▲▼ C
not activated
Local Ctrl.:
▲▼ C
not activated
Telecontrol:
▲▼ C
not activated
Reset:
▲▼ C
not activated
Reset TI:
▲▼ C
not activated
Révision A
↑ Select table
▲▼ C
↓ 2
↑ Select table
▲▼ C
↓ 3
Set Password
◄▼▲►
-> 5555
Function Enable
OK
NO -> NO
Function Enable
▲▼
NO -> OUI
Function Enable
OK
NO > OUI y/n
SETTING CHANGED
OK
Function Enable
Function Enable
OK
OUI
Current Tap
▲▼ C
1.00 xIn
Operating Time
▲▼ C
0.02 s
Current Tap
▲▼ C
0.20 xIn
Operating Time
▲▼ C
5.00 s
Curve type
▲▼ C
Def Tim
Time Dial
▲▼ C
0.05
Operating Time
▲▼ C
5.00 s
↑
Settings 50N1 SETTINGS GEN
▲▼ C
T.A.=1 COM
↓
Current Tap
▲▼ C
0.50 xIn
Operating Time
▲▼ C
1.00 s
↑
Settings 50N2 SETTINGS GEN
▲▼ C
T.A.=1 COM
↓
Current Tap
▲▼ C
0.30 xIn
↑
Settings 51N SETTINGS GEN
▲▼ C
T.A.=1 COM
↓
Curve type
▲▼ C
Def Tim
Time Dial
▲▼ C
0.05
Current Tap
▲▼ C
0.20 xIn
Operating Time
▲▼ C
5.00 s
↑
Settings CLP SETTINGS GEN
▲▼ C
T.A.=1 COM
↓
Multiplier 50P1
▲▼ C
1.00
Multiplier 50P2
▲▼ C
1.00
Multiplier51P
▲▼ C
1.00
Multiplier 50G1/50N1
▲▼ C
1.00
Multiplier 50G2/50N2
▲▼ C
1.00
Multiplier 51G/51N
▲▼ C
1.00
No Load Time
▲▼ C
15 s
Operating Time
▲▼ C
0.02 s
↑
Settings 46 SETTINGS GEN
▲▼ C
T.A.=1 COM
↓
Current Tap
▲▼ C
0.20 xIn
Operating Time
▲▼ C
0.02 s
↑
Settings 49 SETTINGS GEN
▲▼ C
T.A.=1 COM
↓
Current Tap
▲▼ C
1.00xIn
z Heating constant
▲▼ C
3 min
z Cooling constant
▲▼ C
1
Alarma Level
▲▼ C
80
↑
Settings 79 SETTINGS GEN
▲▼ C
T.A.=1 COM
↓
Hold Enable
▲▼ C
NO
Recloser Number
▲▼ C
1
Reclose 2 Time
▲▼ C
0.02 s
Reclose 3 Time
▲▼ C
1.00 s
Reclose 4 Time
▲▼ C
1.00 s
Reclose 5 Time
▲▼ C
1.00 s
Hold Time
▲▼ C
1.00 s
Reset Time
▲▼ C
1.00 s
↑
Settings 74TCS SETTINGS GEN
▲▼ C
T.A.=1 COM
↓
Pour entrer dans les réglages généraux, à partir l’écran “RÉGLAGES”, nous appuyons la touche “◄”.
El réglage général “Nombre appareil”, peut se visualiser à partir de hmi, mais peut se modifier uniquement qu’en utilisant le logiciel SICom.
Les valeurs des réglages généraux “Phase TC ratio” et “Neutre TC ratio” est le résultat de la division du nombre de tour du primaire entre ce du
secondaire. Por exemple: avec TC 500/5, el réglage sera 100.
La fréquence du réseau est choisie en fonction du modèle. La valeur est seulement de lecture.
CT Phase Ratio
▲▼ C
10
CT Neutral Ratio
▲▼ C
10
VT Ratio
▲▼ C
100
Language
▲▼ C
ENGLISH
Active Settings T.
▲▼ C
1
Remote baudrate
▲▼ C
(*)
ModBus Address
▲▼
19200
ModBus BaudRate
▲▼
19200
Pour introduire la mot de passe il faut utliser les touches ▲, ▼, ◄ et ►. Avec ▲ et ▼ se s’introduit une valeur ou un caractère, et les touches ◄ et ►
servent pour se déplacer d’une position à l’autre. Suite à une erreur, s’il est nécessaire de changer un caractère ou un numéro du mot de passe,
appuyer “C” pour l’effacer. Pour valider le mot de passe appuyer “OK.
↑ Select group
▲▼ C
↓ 2
↑ Select group
▲▼ C
↓ 3
↑ Select group
▲▼
↓ 4
Function Enable
OK
NO -> NO
Function Enable
▲▼
NO -> OUI
Function Enable
OK
NO > OUI y/n
SETTING CHANGED
OK
Function Enable
Function Enable
OK
OUI
Current Tap
▲▼ C
1.00 xIn
Time Delay
▲▼ C
0.02 s
Current Tap
▲▼ C
0.20 xIn
Time Delay
▲▼ C
5.00 s
Curve type
▲▼ C
Def Tim
Time Dial
▲▼ C
0.05
Current Tap
▲▼ C
0.20 xIn
↑
Sett(1) 50N1 SETTINGS GEN
▲▼ C
COM "
↓
Current Tap
▲▼ C
0.50 xIn
Time Delay
▲▼ C
1.00 s
↑
Sett(1) 50N2 SETTINGS GEN
▲▼ C
COM "
↓
Current Tap
▲▼ C
0.30 xIn
Time Delay
▲▼ C
2.00 s
Curve type
▲▼ C
Def Tim
Time Dial
▲▼ C
0.05
Current Tap
▲▼ C
0.20 xIn
Time Delay
▲▼ C
5.00 s
Curve type
▲▼ C
Def Tim
Time Dial
▲▼ C
0.05
Current Tap
▲▼ C
0.20 xIn
Time Delay
▲▼ C
5.00 s
↑
Sett(1) CLP SETTINGS GEN
▲▼ C
COM "
↓
No Load Time
▲▼ C
15 s
↑
Sett(1) 50BF SETTINGS GEN
▲▼ C
COM "
↓
Time Delay
▲▼ C
0.02 s
↑
Sett(1) 49 SETTINGS GEN
▲▼ C
COM "
↓
Current Tap
▲▼ C
1.00xIn
z Cooling constant
▲▼ C
1
Alarma Level
▲▼ C
80
↑
Sett(1) 79 SETTINGS GEN
▲▼ C
COM "
↓
Hold Enable
▲▼ C
NO
Recloser Number
▲▼ C
1
Reclose 1 Time
▲▼ C
0.02 s
Reclose 3 Time
▲▼ C
1.00 s
Reclose 4 Time
▲▼ C
1.00 s
Reclose 5 Time
▲▼ C
1.00 s
Hold Time
▲▼ C
1.00 s
Reset Time
▲▼ C
1.00 s
↑
Sett(1) 52 SETTINGS GEN
▲▼ C
COM "
↓
↑
Sett(1) 74TCS SETTINGS GEN
▲▼ C
COM "
↓
Time Delay
▲▼ C
0.02 s
Time Delay
▲▼ C
0.02 s
Current Tap
▲▼ C
0.20 xIn
Time Delay
▲▼ C
0.02 s
Current Tap
▲▼
50%
Time Delay
▲▼
0.02 s
Current Tap
▲▼
7xIn
Frequency
▲▼ C
50Hz
Serial number
▲▼ C
0
Language
▲▼ C
ENG.
Active Setting G.
▲▼ C
1
CT Phase Ratio
▲▼ C
1.0
CT Neutral Ratio
▲▼ C
1.0
Remote Address
▲▼ C
3
Remote Baudrate
▲▼ C
19200
Remote Protocol
▲▼ C
MODBUS
↑ EVENTS SILA000C2A12BB
C
↓ There are 5 0.00 0.00 0.00 0.00
Set Password
◄▼▲► C
-> 5555
Confirm
OK C
Erased Events y/n?
↑ EVENTS
OK C
↓ There are 1
Associated
Time Event number measurement
Date
01/01/00 00:54:18600 1/120 measurement
EventsErased EventsErased
Activated or
Not activated
Event Description
Révision A
↑COUNTERS SILA555B2001BA
C
↓ 0.00 0.00 0.00 0.00
Accumulated Amps
▲▼ C
14011325 k(A2)
Reclosing Numbers
▲▼ C
25
Thermal Image
▲▼ C
75
↑COUNTERS SILA5000C2A12BB
C
↓ 0.00 0.00 0.00 0.00
Accumulated Amps
▲▼ C
0 k(A2)
Reclosing Numbers
▲▼ C
0
↑ COMMANDS SILA555B2000BA
C
↓ 0.00 0.00 0.00 0.00
↑ COMMANDS
OK
↓
↑ COMMANDS
OK
↓
↑ COMMANDS
OK
↓
↑ COMMANDS
OK
↓
↑ COMMANDS
OK
↓
↑ COMMANDS
OK
↓
↑ COMMANDS
OK
↓
Révision B
↑ COMMANDS SILA000C2A12BB
C
↓ 0.00 0.00 0.00 0.00
4
OK
In progress
↑ COMMANDS
↓
4
OK
In progress
↑ COMMANDS
↓
4
OK
In progress
↑ COMMANDS
↓
4
OK
In progress
↑ COMMANDS
↓
4
OK
In progress
↑ COMMANDS
↓
4
OK
In progress
↑ COMMANDS
↓
4
In progress
↑ COMMANDS
OK
↓
4
In progress
↑ COMMANDS
OK
↓
Révision B
↑ DEMAND SILA000C2A12BB
C
↓ 0.00 0.00 0.00 0.00
08/01/15 13:56
▲▼ C
1.50 0.00 0.0 1.50 1.50
Révision B
À partir l’écran de repos, en appuyant la touche “OK”, nous entrons dans la primière ligne de Menus. Avec les touches “▲” et “▼” nous nous
positionnons sur l’écran d’ “RAPPORT” et nous informe du nombre d’événements dans le buffer. En appuyant “OK” et avec les touches “▲” et “▼” nous
nous positionnons sur chacuns des événements.
Révision A
I. 52a:
OK C Sta. INPUTS
not activated
I. 52a I. 52a:
OK C
Not Asigned not activated
I. 52a
OK
Do not Asign y/n
I. 52a
▲▼
Set to Input 1 y/n?
I. 52a
▲▼
Set to Input 2 y/n?
I. 52a
▲▼
Set to Input 3 y/n?
Configuration
OK
Processing...
I. 52a
OK
Asigned to Input 4
I. 52a
▲▼
Set to Input 5 y/n?
Phase A Pickup:
OK C Sta. 50P1
not activated
Phase B Pickup:
▲▼ C Sta. 50P1
not activated
Phase B Pickup:
► C Sta. 50P1
> LedON y/n?
Configuration
OK
Processing...
Phase B Pickup:
◄
>⌠ Led1 y/n?
Phase B Pickup:
▲▼
> Led2 y/n?
Phase B Pickup:
▲▼
> Led3 y/n?
Phase B Pickup:
▲▼
> Led4 y/n?
Phase B Pickup:
▲▼
> Led5 y/n?
Phase B Pickup:
▲▼
> Output 1 y/n?
Phase B Pickup:
▲▼
> Output 2 y/n?
Phase B Pickup:
▲▼
> Output 3 y/n?
Phase B Pickup:
▲▼
> Output 4 y/n?
Phase B Pickup:
▲▼
> 79 Init y/n?
Phase B Pickup:
▲▼
> 50BF Init y/n?
Phase B Pickup:
▲▼
> Osc Init y/n?
Révision B
Phase B Pickup:
▲▼ C
not activated
Configuration
OK
Processing...
Phase B Pickup:
◄
> Ю Led 2 y/n?
Phase B Pickup:
◄
> ⌠ Led 2 y/n?
Phase B Pickup:
◄ > Led 2 y/n?
Phase B Pickup:
> Φ Led 2 y/n
Phase B Pickup:
◄ > & Led 2 y/n?
Phase B Pickup:
◄ > § Led 2 y/n?
Phase B Pickup:
◄ > O Led 2 y/n?
Phase B Pickup:
◄ > P Led 2 y/n?
Phase B Pickup:
◄ > Q Led 2 y/n?
Phase B Pickup:
◄ > R Led 2 y/n?
Phase B Pickup:
◄ > o Led 2 y/n?
Phase B Pickup:
◄ > p Led 2 y/n?
Phase B Pickup:
◄ > q Led 2 y/n?
Phase B Pickup:
▲▼
> Led 3 y/n?
Phase B Pickup:
> Led 4 y/n?
Phase B Pickup:
> Led 5 y/n?
Phase B Pickup:
> Led 7 y/n?
Phase B Pickup:
> Led-52 y/n?
Phase B Pickup:
> Led-79 y/n?
Phase B Pickup:
> Output 1 y/n?
Phase B Pickup:
> Output 2 y/n?
Phase B Pickup:
> Output 3 y/n?
Phase B Pickup:
> Output 4 y/n?
CODE DE LA 1 octet Il s’agit de l'un des codes de fonction pris en charge par
FONCTION
l’équipement. Dans ce cas, les seuls codes de fonction
pris en charge seront le 3 pour la lecture et le 16 pour
les écritures. Lorsque l’esclave doit répondre avec une
exception à l’un de ces cadres, il l’indique en plaçant sur
1 le bit le plus lourd de la fonction correspondante. Ainsi,
une exception pour la fonction 3, sera indiquée avec un
83 comme code de fonction et une exception pour la
fonction 16 ou 0x10 sur l’hexadécimale, sera indiquée
avec un 0x90.
TEMPS MORT Temps requis pour Un cadre est dit « terminé » lorsque rien n’est reçu sur la
transmettre 3,5
ligne pendant une période de 3,5 octets. C'est-à-dire :
octets
15 ms à 2 400 bps
2 ms à 19 200 bps
…etc.
CODE
HEX NOM MODBUS DÉFINITION COMMENTAIRE
DEC
0x03 Read Holding Lecture de valeurs Cette fonction permet au maître de lire une ou
Registers quelconques. plusieurs adresses consécutives d’un relais.
3 Les registres sont toujours de 16 bits, avec
l'octet le plus lourd en premier. Le nombre
maximum de registres pouvant être lu dans un
même paquet est de 60.
ENUM 1 Entier sans signe de 16 bits. Chaque valeur pouvant être adoptée par cet entier
disposera d’une valeur correspondante dans le tableau auxiliaire de la base des
ASCIIxx xx/2 String : chaîne de caractères de longueur variable. La fin du String sera indiqué
par un ‘\0’.
Exemple : “ABC” 0x41x42x43x00....
FH 5 Année(UINT).mois(UCHAR).jour(UCHAR).heure(UCHAR).minutes(UCHAR).sec
ondes(UCHAR).centièmes(UCHAR).millièmes(UINT)
CONT 13 Indice(UINT).Valeur(DWORD).Description(ASCII20)
EVENT 10 Ancienneté(UINT).Événement(EVENT)
Adresse
Nombre de
Fonction Description de Format
registres
début
16 Voir carte de
Écrire l’Indice de Compteurs 175 1 UINT
compteurs
03 Voir carte de
Lecture de Compteurs 176 13 CONT
compteurs
16 Voir carte de
Écriture de Compteurs 176 13 CONT
compteurs
Voir carte de
16 Sélection de Manœuvre 200 1 UINT
manœuvres
Voir carte de
16 Confirmation de Manœuvre 201 1 UINT
manœuvres
Voir carte de
16 Écrire l’Indice d’Événement 400 1 UINT
manœuvres
4 Thermal Image
6 Reset 86
1 IA
2 IB
3 IC
4 IN
5 I2
6 Thermal Image
Criteria
Criteria Directory Criteria denomination
Number
2 50*256+5+32 50P_2
3 51*256+7 50/51P
4 150*256+5 50N/G_1
5 150*256+5+32 50N/G_2
6 151*256+7 50/51N/G
8 24*256+1 50BF
12 255*256+4 Measurements
13 253*256+8 Inputs
14 254*26+14 Outputs
15 79*256+1 79 (Auto-recloser)
16 52*256+1 52 (Breaker)
17 74*256+1 74TCS
bit-3 Pickup
502 50P_1
bit-8 Phase A trip
bit-11 Trip
bit-3 Pickup
503 50P_2
bit-8 Phase A trip
bit-11 Trip
bit-3 Pickup
504 50/51P
bit-8 Phase A trip
bit-11 Trip
bit-4 Pickup
505 50N/G1
bit-12 Trip
bit-4 Pickup
506 50N/G2
bit-12 Trip
bit-4 Pickup
509 50BF
bit-12 Trip
bit-4 Pickup
510 46
bit-12 Trip
bit-4 Alarm
511 49
bit-12 Trip
bit-0 Trip
General:
Bit-1 External Trip Input
bit-16 Ready
bit-11 Lock 79
bit-12 Unlock 79
bit-17 Input -2
bit-18 Input -3
bit-19 Input -4
bit-20 Input -5
bit-21 Input -6
bit-22 Input -7
bit-23 Input -8
bit-25 A continuity
bit-26 B continuity
bit-0 Output - 1
bit-1 Output - 2
bit-2 Output - 3
bit-3 Output - 4
bit-4 Output - 5
bit-5 79 Init
bit-8 ON Led
bit-9 Led -1
bit-10 Led -2
bit-11 Led -3
bit-12 Led -4
bit-13 Led -5
bit-4 Pickup
517 74TCS
bit-12 Trip
bit-20 Unlock 79
bit-24 Reset 86
bit-19 Lock 79
bit-20 Unlock 79
bit-24 Reset 86
bit-20 Unlock 79
bit-21 Telecontrol No
bit-24 Reset 86
1 50 Pickup up A
2 50 Pickup up B
3 50 Pickup up C
4 50 Pickup up P
50P_1
5 50 Trip A
6 50 Trip B
7 50 Trip C
8 50 Trip P
1 50 Pickup up A
2 50 Pickup up B
3 50 Pickup up C
4 50 Pickup up P
50P_2
5 50 Trip A
6 50 Trip B
7 50 Trip C
8 50 Trip P
1 50/51 Pickup up A
2 50/51 Pickup up B
3 50/51 Pickup up C
4 50/51 Pickup up P
50/51P
5 50/51 Trip A
6 50/51 Trip B
7 50/51 Trip C
8 50/51 Trip P
1 50 Pickup up N/G
50N/G_1
2 50 Trip N/G
1 Pickup
CLP
2 Activation
1 Pickup
50BF
2 Trip
1 Pickup
46
2 Trip
1 Alarm
49
2 Trip
1 General Trip
7 General 50Hz
17 General Ready
22 General Telecontrol NO
46 General identification
49 Neutral pick-up
50 Phase A pick-up
51 Phase B pick-up
52 Phase C pick-up
53 General pick-up
54 Phase A trip
55 Phase B trip
56 Phase C trip
57 50N/G trip
58 50P trip
1 Input 52 a
2 Input 52 b
7 Input init 79
8 Input enable 79
9 Input Locking 79
Inputs
10 Input 1 select table
12 Lock 79
13 Unlock 79
17 Input1
18 Input2
19 Input3
20 Input4
22 Input6
23 Input7
24 Input8
25 Control voltage
26 Coil A continuity
27 Coil B continuity
1 Output1
2 Output2
3 Output3
4 Output4
Outputs
5 Output5
6 79 Init
7 50BF Init
8 Fault Init
1 Status 79 Standby
3 Status 79 Open
7 Status 79 Lockout
1 Status 52 Inicio
2 Status 52 Error
52
3 Status 52 Open
12 Status 52-A
13 Status 52-B
1 Pickup
74TCS
2 Activation
1 Command select
4 Lock 79
ModBus
5 Unlock 79
6 Telecontrol NO
7 Telecontrol OUI
9 Reset 86
1 Command select
4 Lock 79
Remote
5 Unlock 79
6 Telecontrol NO
7 Telecontrol OUI
9 Reset 86
4 Lock 79
Local Modbus
5 Unlock 79
6 Telecontrol NO
7 Telecontrol OUI
9 Reset 86
in ModBus
Maximum
Minimum
Category
Function
ModBus
Type
Step
Unit
Equipment
3001 5001 ASCII20 General -
identifier
Phase CT
3006 5006 LONG General 1 2000 1 -
Ratio
Neutral CT
3007 5007 LONG General 1 2000 1 -
Ratio
DENUM
3008 5008 5060Hz
General Frequency 0 1 1 Hz
DENUM
3009 5009 LANGUAGE
General Language 0 3 1 -
Adresse 01
Fonction 10
Adresse de début H 00
Adresse de début L A8
Nombre de registres H 00
Nombre de registres L 02
Nombre d’Octets 04
Clé 35,35,35,35
Checksum H 4A
Checksum L 50
Et le SIL répondra OK :
Adresse 01
Fonction 10
Adresse de début H 00
Adresse de début L A8
Nombre de registres H 00
Nombre de registres L 02
Nombre d’Octets 04
Checksum H 29
Checksum L 93
Adresse 01
Fonction 03
Adresse de début H 05
Adresse de début L 79
Nombre de registres H 00
Nombre de registres L 08
Checksum H 95
Checksum L 19
Adresse 01
Fonction 10
Nombre d’Octets 10
Mesure IA 00,00,00,00
Mesure IB 00,00,00,00
Mesure IC 00,00,00,00
Mesure IN 00,00,00,00
Checksum H E4
Checksum L 59
Adresse 01
Fonction 03
Adresse de début H 01
Adresse de début L F5
Nombre de registres H 00
Nombre de registres L 3D
Checksum H 95
Checksum L D5
Adresse 01
Fonction 03
Nombre d’Octets 7A
00,00,00,01,00,00,00,00,……,7C,B1,0A,AF,DD 3B 1D
CODE DE LA 1 octet Il s’agit de l'un des codes de fonction pris en charge par
FONCTION
l’équipement. Dans ce cas, les seuls codes de fonction
pris en charge seront le 3 pour la lecture et le 16 pour
les écritures. Lorsque l’esclave doit répondre avec une
exception à l’un de ces cadres, il l’indique en plaçant sur
1 le bit le plus lourd de la fonction correspondante. Ainsi,
une exception pour la fonction 3, sera indiquée avec un
83 comme code de fonction et une exception pour la
fonction 16 ou 0x10 sur l’hexadécimale, sera indiquée
avec un 0x90.
TEMPS MORT Temps requis pour Un cadre est dit « terminé » lorsque rien n’est reçu sur la
transmettre 3,5
ligne pendant une période de 3,5 octets. C'est-à-dire :
octets
15 ms à 2 400 bps
2 ms à 19 200 bps
…etc.
CODE
HEX NOM MODBUS DÉFINITION COMMENTAIRE
DEC
0x03 Read Holding Lecture de valeurs Cette fonction permet au maître de lire une ou
Registers quelconques. plusieurs adresses consécutives d’un relais.
3 Les registres sont toujours de 16 bits, avec
l'octet le plus lourd en premier. Le nombre
maximum de registres pouvant être lu dans un
même paquet est de 60.
ENUM 1 Entier sans signe de 16 bits. Chaque valeur pouvant être adoptée par cet entier
disposera d’une valeur correspondante dans le tableau auxiliaire de la base des
ASCIIxx xx/2 String : chaîne de caractères de longueur variable. La fin du String sera indiqué
par un ‘\0’.
Exemple : “ABC” 0x41x42x43x00....
FH 5 Année(UINT).mois(UCHAR).jour(UCHAR).heure(UCHAR).minutes(UCHAR).sec
ondes(UCHAR).centièmes(UCHAR).millièmes(UINT)
CONT 13 Indice(UINT).Valeur(DWORD).Description(ASCII20)
EVENT 10 Ancienneté(UINT).Événement(EVENT)
Start Number of
Function Description Format
address registries
Setting DENUM
03 and 16 618 2 Phase nominal current
CURRENT
Setting DENUM
03 and 16 620 2 Neutral nominal current
CURRENT
Setting DENUM
03 and 16 760 2 Protocol
PROTOCOL
4 Pulse Lock 79
5 Pulse Unlock 79
6 Local control
7 Telecontrol
9 Reset
Number
H Pickup L Pickup Number of Number of checksum checks
address function of Password
address address H registers L registers H um L
Bytes
01 10 00 A8 00 02 04 35,35,35,35 30 F4
01 10 00 A8 00 02 04 29 93
01 03 05 79 00 08 95 19
And the SIL-A will reply with the IA, IB, IC and I0 measurements in FLOAT format:
Number
Measurement Measurement Measurement Measurement checksum checksum
address function of
IA IB IC IN H L
Bytes
01 03 10 00,00,00,00 00,00,00,00 00,00,00,00 00,00,00,00 E4 59
01 03 01 F5 00 3D 95 D5
10.
00,00,00,01,00,00,00,00,………….…,7C,B1,0A,AF,DD 3B 1D
X RS-485
Transmission speed
X 4800 bits/s
X 9600 bits/s
X 19200 bits/s
X 38400 bits/s
Transmission parameters
parity EVEN
Stop bits 1
<5> Power on
<23> Characteristic 1
<24> Characteristic 2
<25> Characteristic 3
<26> Characteristic 4
<78> Zone 1
<79> Zone 2
<80> Zone 3
<81> Zone 4
<82> Zone 5
<83> Zone 6
<144> Measurement I
<145> Measurement I, V
<116> 79 init
<119> 79 Enabled
<17> 32 Trip
<18> 32 Start
<19> 32 Trip
<20> 32 Start
<21> 32 Trip
<22> 32 Start
<23> 32 Trip
<32> 37 Start A
<33> 37 Start B
<34> 37 Start C
<35> 37 Start P
<36> 37 Trip A
<37> 37 Trip B
<38> 37 Trip C
<96> 67 Start N
<97> 67 Trip N
<98> 67 Start N
<99> 67 Trip N
<100> 67 Start A
<101> 67 Start B
<102> 67 Start C
<103> 67 Start P
<104> 67 Trip A
<105> 67 Trip B
<106> 67 Trip C
<107> 67 Trip P
<108> 67 Start A
<110> 67 Start C
<111> 67 Start P
<112> 67 Trip A
<113> 67 Trip B
<114> 67 Trip C
<115> 67 Trip P
<8> 27 Start A
<9> 27 Start B
<10> 27 Start C
<11> 27 Start P
<12> 27 Trip A
<13> 27 Trip B
<14> 27 Trip C
<15> 27 Trip P
<16> 27 Start A
<17> 27 Start B
<18> 27 Start C
<20> 27 Trip A
<21> 27 Trip B
<22> 27 Trip C
<23> 27 Trip P
<24> 59 Start N
<25> 59 Trip N
<26> 59 Start N
<27> 59 Trip N
<28> 59 Start A
<29> 59 Start B
<30> 59 Start C
<31> 59 Start P
<32> 59 Trip A
<33> 59 Trip B
<34> 59 Trip C
<35> 59 Trip P
<36> 59 Start A
<37> 59 Start B
<38> 59 Start C
<39> 59 Start P
<40> 59 Trip A
<41> 59 Trip B
<43> 59 Trip P
<48> 81 Start
<49> 81 Trip
<50> 81 Lockout
<51> 81 Start
<52> 81 Trip
<53> 81 Lockout
<54> 81 Start
<55> 81 Trip
<56> 81 Lockout
<57> 81 Start
<58> 81 Trip
<59> 81 Lockout
ADAPT ADAPT
FUN INF Description TYP COT
A B
This section describes the implementation of IEC 61850 protocol in standard SILA.
IEC 61850 protocol defines a way of structuring the available information in each device,
that is reflected in the Data Model and a way of managing and sending this information
through communications using specific Services.
SILA device will be known as a Server IED (Intelligent Electronic Device), which services
will be available using the Ethernet through its default IP (192.168.0.121)
MMS will be the used Ethernet protocol for the Client-Server communication and 102 will
be the used port.
GOOSE fast messages is not a Client-Server communication like TCP/IP but a Multicast
communication that sends messages directly to the Link Layer using MAC directions as
destination directions for publishing the GOOSE.
Révision B includes:
System Functions:
DATASETS
A Dataset is a grouping of information from the data model of the IED:
These groupings can be used by other services for the sending of information (GOOSE,
RCB, BRC).
The definition of Datasets has to be made in a IEC61850’s file with extension .ICD (IED
Capability Description) that is provided with the device.
By default there are 4 Datasets, grouped according the functionality (Trips, Measures,
Events and Goose):
Trips, with the name of Trips and the following data objects:
Events, with the name of Events and the following data objects:
REPORTS
The Report service is used for the sending of values from elements of a Dataset to a
communication client that enables the report service (Central unit of Substation, remote
unit o software application).
The use of Reports optimizes the communication when the information of the
associated Dataset is only sent when there is a change of value, when is requested or
time integrity is enabled.
Standard SILA device is pre configured with 10 URCB associated to the Measures
Dataset:
GOOSE
Goose service allows the Multicast sending (to multiple devices) of the existing information
in a Dataset.
Goose message is an Ethernet message that is continuously cast to the Ethernet and
every device can analyze it.
Standard SILA disposes by default a Goose message associated to the Goose Dataset:
This message is sent to the Ethernet with a latency time of 30 seconds till one of the
values of the element of the Dataset changes, then the message is sent immediately in a
repeating way in a short time, increasing till reaching the latency time.
10.3. Operation
Standard SILA is pre configured with a sample configuration to be integrated in an IEC
61850 system.
It disposes all the Data model with all the functionallity available via MMS (using a
software application like IEDScout) or via Reports (with their Event, measure or Trip
Datasets) in case a client needs to receive information from the device.
To retrieve the data model from the device to a PC with an IEC 61850 tool, it is only
required the IP of the device (by default 192.168.0.121).The tool has to be able of asking
the data model automatically.
The name of the IED is by default TEMPLATELD1 and below it there is the data model
with its logical nodes, data objects and data attributes according IEC 61850.
The common way to integrate a new IED in a SCADA is using reports and the ICD files
from SILA provided for this purpose.
From the ICD file of SILA, the client device has to select a Report with the associated
Dataset. This way, client will have a list of signals that will use to configure its own
database. Once client device is configured, the communication between server could be
initiated by the client by enabling the report and receving the existing information from the
report.
Each client has different ways of configuring, so it will be necessary referring to
IEC61850’s configuration chapter from the client’s manual.
Goose message is activated by default and is published with the information from the
Goose dataset (General Trips and Starts) into the net.
One IED that requires the information from a Goose has to be configured using the ICD
file from SILA. In this file appears the default parameters of the Goose message.
DNP V3.00
DEVICE PROFILE DOCUMENT
This document must be accompanied by : Implementation Table and Point List.
Notable objects, functions, and/or qualifiers supported in addition to the Highest DNP Levels
Supported (the complete list is described in the attached table):
For static (non-change-event) object requests, request qualifier codes 07 and 08 (limited
quantity), and 17 and 28 (index) are supported. Static object requests sent with qualifiers
07, or 08, will be responded with qualifiers 00 or 01.
16-bit, 32-bit and Floating Point Analog Change Events with Time may be requested.
Maximum Data Link Frame Size (octets): Maximum Application Fragment Size (octets):
None None
Fixed at ____________________ Configurable
Configurable, from _0_ to _255_
Default, 3
Requires Data Link Layer Confirmation:
Never
Always
Sometimes. If 'Sometimes', when? ____________________________________________
Configurable as Never, Only for multi-frame messages, or Always. Default Never
Never
Attach explanation:
All points support the same Function Codes :Direct Operate and Direct Operate-No ACK
All points support the same Control Codes : Pulse ON, Latch ON, Latch OFF, Pulse OFF
and Trip-Pulse ON.
Reports Binary Input Change Events when Reports time-tagged Binary Input Change
no specific variation requested: Events when no specific variation requested:
Never Never
Only time-tagged Binary Input Change With Time
Only non-time-tagged Binary Input Change With Relative Time
Configurable to send both, one or Configurable (attach explanation)
the
other (attach explanation)
Function Codes 7 6 5 4 3 2 1 0
Index Size Qualifier Code
1 Read
2 Write
3 Select Index Size Qualifier Code
4 Operate
5 Direct Operate 0- No Index, Packed 0- 8-Bit Start and Stop Indices
6 Direct Operate-No ACK 1- 1 byte Index 1- 16-Bit Start and Stop Indices
13 Cold Start 2- 2 byte Index 2- 32-Bit Start and Stop Indices
14 Warm Start 3- 4 byte Index 3- 8-Bit Absolute address Ident.
20 Enable Unsol. Messages 4- 1 byte Object Size 4- 16-Bit Absolute address Ident.
5- 2 byte Object Size 5- 32-Bit Absolute address Ident.
21 Disable Unsol. Messages 6- 4 byte Object Size 6- No Range Field (all)
23 Delay Measurement 7- 8-Bit Quantity
129 Response 8- 16-Bit Quantity
130 Unsolicited Message 9- 32-Bit Quantity
11-(0xB) Variable array
REQUEST RESPONSE
OBJECT
(BCD will parse) (BCD will respond)
Func Qual Func Qual
Obj Var Description Codes Codes Codes Codes Notes
(dec) (hex) (dec) (hex)
1 0 Binary Input – All variations 1 6
Assigned to
1 1 Binary Input 129 1 Class 0.
20,21 6
20,21 6
20,21 6
0
80 1 Internal Indications 2
index=7
-- -- No Object (Cold Start) 13
In SIL-A relay, the value of the currents IL1, IL2 and IL3 have valid values, the other
measures remain with value 0.
Each current value is in the range 0 – 4095 where 4095 corresponds to 1,2*In
e.g. a received value of 806 with a nominal value In=5A corresponds to 1,18A
In SIL-A relay, the value of the currents IL1, IL2 and IL3 have valid values, the other
measures remain with value 0.
Each current value is in the range 0 – 4095 where 4095 corresponds to 1,2*In
e.g. a received value of 806 with a nominal value In=5A corresponds to 1,18A
Application Confirm Timeout: Specifies how long the slave DNP device will wait for an
application layer confirmation from the master.
Source Address: Destination address of the Master device to which the unsolicited responses
are to be sent.
Unsolicited Retry Delay: Specifies the time to delay after an unsolicited confirm timeout before
retrying the unsolicited response.
Unsolicited Max. Retries: How many times should this slave resend Unsols before declaring
the station offline
Unsolicited Offline Retry Delay: How often to retry unsolicited responses after maxRetries
attempts