Вы находитесь на странице: 1из 10

SUPPLEMENT 4

Combination Standpipe/
Sprinkler Risers
Maurice Pilette
Christian Dubay

Editor's Note: This supplement provides information related to the application of combina-
tion standpipe/sprinkler risers and is limited to combination standpipe/sprinkler systems as
addressed by NFPA 14, Standard for the Installation of Standpipe and Hose Systems, and
NFPA 13, Standard for the Installation of Sprinkler Systems. Guidelines in the application
of combination standpipe/sprinkler systems relative to the overall design, water supply,
piping, valves, and installation requirements, as determined by NFPA 14 and NFPA 13,
are also covered.

OVERVIEW System Design


The primary use of a combination standpipe/sprinkler sys- The designer should review the applicable regulatory codes
tem piping arrangement is to reduce the use and installation and consult with the authority having jurisdiction (AHJ)
of multiple risers within a building when a sprinkler system and building owner prior to designing a combination stand-
and standpipes are required. This arrangement combines pipe/sprinkler system, and then determine if a combination
the method of the water supply delivery for both the sprin- system is appropriate for a given application or building
kler system and fire department use to a given location project. The designer should consider, but not be limited
or floor of a building. Combination standpipe/sprinkler to, the following issues:
systems include control valves, check valves, and flow
alarm devices as part of the overall installation require- • Hazard and risk assessment
ments. When these devices are installed, coordination with • Water supply, municipal or prívate
the fire alarm system designer should be completed as part • Fire pumps and storage tanks
of an overall system design for the building. • Piping system installation restrictions

Maurice Pilette, P.E., Registered Pire Protection Engineer, has 25 years of professional practice, is a
member of several NPPA committees, and was the past Chair of the Standpipe committee.
Christian Dubay, P.E., NPPA Principal Pire Protection Engineer, is the Staff Liaison for NPPA's
Automatic Sprinkler Systems Project and the Editor of the Automatic Sprinkler Systems Handbook
and the Automatic Sprinkler Systems for Residential Occupancies Handbook.

965
966 Supplement 4 • Combination Standpipe/Sprinkler Risers

• Listed and/or approved equipment and devices departments and those trained in handling heavy fire
• Appropriate use and limitations of pressure regulating streams. [14:3.3.15.1]
devices, if applicable Class III System. A system that pro vides 1 Y2 in. (40
• Testing, inspection, and maintenance feasibility mm) hose stations to supply water for use by trained
personnel and 2Y2 in. (65 mm) hose connections to
• Fire department instructions on the use of the equip-
supply a larger volume of water for use by fire depart-
ment
ments and those trained in handling heavy fire streams.
• Equipment and devices, functions integrated with [14:3.3.15.3]
other building fire safety systems
• Overall cost impact NFPA 14 defines a standpipe system as follows.

Standpipe System. An arrangement of piping, valves,


Application hose connections, and allied equipment installed in a
building or structure, with the hose connections located
Careful consideration should be given if the combination
in such a manner that water can be discharged in streams
standpipe/sprinkler system is going to be a system other
or spray pattems through attached hose and nozzles, for
than a wet-type system. NFPA 14 does not restrict or pro- the purpose of extinguishing a fire, thereby protecting a
vide guidelines for the design or installation of a combina- building or structure and its contents in addition to
tion system design as an automatic dry pipe, pre-action, protecting the occupants. [14:3.3.12]
or semi-automatic system. A system design other than a Standpipe System. This arrangement is accomplished
wet-type application is considered unique and must be by means of connections to water supply systems or
appropriately analyzed for its intended use and application. by means of pumps, tanks, and other equipment neces-
The use of a dry pipe system can add significant complica- sary to provide an adequate supply of water to the hose
tions and restrictions where interconnected with the sprin- connections. [14:A.3.3.12]
kler system. A once common restriction is the prohibition Additionally, NFPA 14 specifically defines a combined
of NFPA 13 against gridded dry sprinkler systems, and in system as follows.
sorne cases a combined standpipe/sprinkler system can
result in a gridded dry sprinkler system due to the cross or Combined System. A standpipe system having piping
interconnection piping. Once the final design applicability that supplies both hose connections and automatic
sprinklers. [14:3.3.12.2]
parameters, including equipment and performance expecta-
tions, have been determined, the criteria of the various
flow rates required by NFPA 14 and NFPA 13 and piping GENERAL INSTALLATION REQUIREMENTS
installation requirements are expected to be incorporated
in the final design. Role of AHJ and Local Codes
Neither NFPA 13 nor NFPA 14 mandates that combination
System Definitions standpipe/sprinkler systems be installed in buildings that
require both standpipes and sprinkler systems. Both stan-
The main goals for installing a combination standpipe/
dards only establish the design and installation require-
sprinkler system are to protect life and property and to
ments for each respective system. The decision to use a
provide reliable, effective performance for fire fighter
combination standpipe/sprinkler system within a building
safety. Designers, building owners, and others involved in
is generally left up to the discretion of the designer. In
the design process should evaluate each building's unique
sorne cases, local, state, or a model code may require
design, any new fire protection requirements, and the avail-
the use of a combination system in certain buildings, and
able equipment technology to determine if a combination
additional requirements may be mandatory based on those
system is a good fit for a project, based on the issues of
local regulations. The designer must design the combina-
design, installation, testing and maintenance, and cost.
tion system in accordance with the requirements of NFPA
The use of a standpipe and hose system that also
14, NFPA 13, and with any additional requirements man-
provides the necessary water supply for an automatic sprin-
dated by the AHJ.
kler system to a portion of a building is commonly referred
An example of an AHJ requirement that would exceed
to as a combination or combined system. Combination
the requirements established by NFPA 14 and NFPA 13 is
risers are generally restricted to Class I and Class III stand-
a jurisdiction that requires that all floors of a high-rise
pipes, as defined by NFPA 14.
building be served by a minimum of two combination
Class I System. A system that provides 2112 in. (65 standpipe/sprinkler systems and that the sprinkler system
mm) hose connections to supply water for use by fire be cross connected (looped) between a mínimum of two

2007 Automatic Sprinkler Systems Handbook


Supplement 4 • Combination Standpipe/Sprinkler Risers 967

risers or multiple risers as a backup for the sprinkler system 14 and NFPA 13) or a sprinkler riser restricted to a sprinkler
water supply to a given floor of a building should one riser system only with 1 Yz in. hose valves or hose stations for
be impaired for any reason. Neither NFPA 14 nor NFPA occupant use (NFPA 13 only).
13 requires the interconnection of risers. However, if it is
required as part of the local jurisdiction or design specifica- PIPING AND VALVE INSTALLATION
tion requirements, then NFPA 14 and NFPA 13 provide
REQUIREMENTS
requirements for cross connection of combination system
risers. Pipe lnstallation
Where automatic sprinkler systems are cross con-
NFPA 14 and NFPA 13 have established similar piping
nected with two or more risers, careful consideration needs
installation requirements for combination standpipe/sprin-
to be given to the method of sizing the sprinkler piping.
kler systems. Both 6.3.5 of NFPA 14 and 8.17.5.2.2(1) of
At the discretion of the AHJ or the designer, the hydraulic
NFPA 13 state that "each connection from a standpipe that
calculations can be restricted using only one of the combi-
is part of a combined system to a sprinkler system shall
nation standpipe/sprinkler risers or the required flow can
have an individual control valve and check valve of the
be split using multiple risers.
same size as the connection." Both standards recognize
One of the reasons that the designer may elect to split
and have correlated the installation requirements for combi-
the flow between multiple risers is that this approach allows
nation standpipe/sprinkler system piping interconnection.
the reduction of sprinkler pipe sizing to the sprinkler system
Exhibit S4.1 and Exhibit S4.2 show two typical designs
on a given floor. However, should a riser be impaired, the
for a combination standpipe/sprinkler system where the
required hydraulic flow rate may not be achieved through
sprinkler system pres sures exceed 17 5 psi (12.1 bar).
a single riser. The AHJ may see it differently and would
NFPA 13 does have an additional requirement in the
not necessarily permit the split of flow using multiple risers
design of combination standpipe/sprinkler systems where
and might require that the hydraulic calculations use only
the sprinkler system pressures exceed 175 psi, and pres-
one combination standpipe/sprinkler riser. This method
sure-reducing valves are required per 8.15.1.2 of NFPA
would provide the hydraulic flow rate per the design should
13. NFPA 14 does not address the NFPA 13 requirement
the other riser be impaired. The method of not splitting
relative to the use of sprinkler system pressure-reducing
the hydraulic flows of multiple risers defeats any financia!
valves; it requires only that a combination system be pro-
savings that may be achieved by reducing pipe sizing to
vided with a control valve anda check valve. The designer
the sprinkler system, but provides additional reliability
should consider the use of pressure-reducing valves that
since each floor or area will be served by multiple risers
have been listed as a "combination indicating control
each capable of meeting the required hydraulic flow rates.
valve, pressure-reducing valve and check valve." If the
designer uses valves that are not listed as described above,
Use of NFPA 13 or NFPA 14 there would be multiple redundancies in control valve and
check valve arrangements required by each standard. The
The designer and the AHJ should understand the criteria
AHJ should be consulted prior to the acceptance of an
for combination systems established by NFPA 14 and
arrangement that does not meet the requirements of NFPA
NFPA 13. As previously discussed, combination standpipe/
14 and NFPA 13. NFPA 14 and NFPA 13 provide identical
sprinkler systems as defined by NFPA 14 are generally
annex figures to address the interconnection requirements
limited to Class I and/or Class III standpipes, which require
between a sprinkler system and a standpipe system. Exhibit
2112 in. hose valve connections for fire department use and
S4.3 and Exhibit S4.4 illustrate these requirements. Addi-
permit the interconnection of the sprinkler system to the
tionally, Exhibit S4.5 and Exhibit S.4.6 illustrate fire hose
standpipe system. Not to be confused with standpipes for
valves with floor control at main floor and mid-landing
fire department use, NFPA 13 establishes requirements for
locations, respectively.
the installation of 1112 in. hose valves and hose stations
where required for occupant use, which are connected to
Valve lnstallation
the sprinkler system when standpipes are not part of the
design or installation requirements. The designs for pipe NFPA 14 has the following additional requirements relative
sizing, type and style of various hose valves, and connec- to the installation of control valves and check valves.
tions to various portions of the systems are significantly Where sprinkler system piping supplied by a combined
different in scope and application. Effectively, the system system is supplied by more than one standpipe ("loop"
is either a standpipe riser with 2V2 in. hose valves for fire or "dual feed" design), a sign shall be located at each
department use with a sprinkler system attached (NFPA dual or multiple feed connection to the combination sys-

Automatic Sprinkler Systems Handbook 2007


968 Supplement 4 • Combination Standpipe/Sprinkler Risers

lndicating control valve


Check valve
��=��ir
Pressure gauge } high pressures

/
l ¡J i
/
Pressure reducing valve

r-
I Pressure gauge
Flow switch
} Listed for 175 psi

To sprinklers

\ } Mustbe
Test-drain sized for verification
3 in. drain valve
valve of sprinkler flow
riser� demand

� Pressure reducingl Must be


fire hose valve J
listed for high pressures

1--- Combination system

...------ Fire hose valve


test connection

EXH/8/T 54. 1 Typica/ Design for Combination System with System Pressures over 175 psi.

tem standpipe to indicate that in order to isolate the sprin- system is supplied from multiple directions. These signs
kler system served by the control valve, an additional are intended to reduce the potential of disassembly of a
control val ve or val ves at other standpipes shall be shut pressure-charged sprinkler system and to facilitate rapid
off. [14:6.3.8.3] shutdown in the event of system damage.
The sign also shall identify the location of the addi-
Additionally, the requirements for sprinkler system
tional control valves. [14:6.3.8.3.1]
control valves to permit the shutdown of the sprinkler
Exhibit S4.7 illustrates an interconnection (loop or dual system for any reason without impairment to the 2112 in.
feed) design. fire department hose valve are intended to ensure that,
Additionally, NFPA 13 provides the following require- when at all possible, the standpipe system remain in service.
ments where a sprinkler system is served from multiple Examples of when a sprinkler system shutdown may be
directions or risers. necessary include needing to do the following:
Systems that have more than one control valve that • Shut down the sprinkler system for repairs
must be closed to work on a system or space shall have
• Remove that portion of the sprinkler system connected
a sign referring to existence and location of other val ves.
to the standpipe risers, as required for building area
[13:6. 7.4.3.1]
renovations
These requirements ensure that where a combined stand- • Shut off or limit sprinkler water flow after a fire inci-
pipe/sprinkler system is installed and is interconnected, dent while retaining a necessary unimpaired water
signs be provided so that when the sprinkler system is to supply available for fire department operations at the
be isolated for maintenance or repair it is clear that the 2112 in. fire hose valve connection

2007 Automatic Sprinkler Systems Handbook


Supplement 4 • Combination Standpipe/Sprinkler Risers 969

Pressure gauge
listed for high
pressure Combination
pressure reducing valve
listed for use as
a PRV, indicating control valve,
and check valve

r- Pressure gauge

� Flow switch
/

\ } Must be sized for


Test-drain verification of
valve valve sprinkler flow
demand

3 in. drain
� Combination system
riser --"*

%-+ � Pressure reducing firJJ Must be listed for high pressures


hose valve

.------ Fire hose valve test connection

EXH/8/T S4.2 Typica/ Design for Combination System with System Pressures over 175
psi Using a Usted Combination Sprinkler System Pressure-Reducing Valve-lndicating
Control Va/ve and Check Va/ve.

The requirement for a check valve to be included as part addition, when combination risers are cross connected
of the connection to the sprinkler system is to permit the (loop or dual feed), the check valves will limit the flow
standpipe riser to be drained and refilled in a limited to the appropriate floor where sprinklers have activated
amount of time should repair be necessary to any portian and limit circulation of water throughout multiple levels
of the standpipe riser, fire department hose valves, pipe, of the building.
and fittings, etc. The check valve arrangements shown in
Exhibit S4.3 and Exhibit S4.4 permit the standpipe system
to be drained while allowing the sprinkler pipe to remain SYSTEM PIPE SIZING
water filled. In general, the check valve between the two
System Pipe Sizing - Fully Sprinklered Buildings
systems maintains the water volume supplied within the
sprinkler piping, thereby limiting the drain and refill time When sizing the waterflow demands for a combination
of the overall combination standpipe/sprinkler system. In standpipe/sprinkler system, the designer must establish

Automatic Sprinkler Systems Handbook 2007


970 Supplement 4 • Combination Standpipe/Sprinkler Risers

lndicating-type floor control Control valve


valve with supervisory switch and check valve

\ \ Floor

Mid-landing \

Drain
riser
\
lnspector's
test and drain
\ connection Optional location
for drain riser
Drain riser
� Combination sprinkler/
standpipe riser Mid-landing\

EXHIBIT 54.3 Acceptable Piping Arrangement for


Combined 5prinkler!Standpipe System with System
Pressures less than 175 psi. [Source: Figure A.6.3.5(a),
NFPA 14, 2007 ed.J

EXHIBIT 54.5 Design Showing Fire Hose Va/ve and Floor


Control at Main Floor.

Control valve
and check valve

Drain
riser
\
I nspector's
-, \
2V2 in.
(65 mm) min.
Fire hose valve
test and drain
connection Mid-landing \

+--- Combination sprinkler/ Combination riser Floor


standpipe riser

EXHIBIT 54.4 Acceptable Piping Arrangement for


Combined Sprinkler!Standpipe System with System
Pressures less than 175 psi. [Source: Figure A.6.3.5(b), Mid-landing
NFPA 14, 2007 ed.J

how the requirements of NFPA 14 and NFPA 13 are to be


applied. Where a building requires a standpipe system and
a sprinkler system, and the designer plans to utilize the stand-
EXHIBIT 54.6 Design Showing Fire Hose Va/ve and Floor
pipe riser as the water supply for the sprinkler system, then
Control at Mid-Landing.
the requirements of 7.10.1.3 in NFPA 14 apply and the re-
quirements of 11.1.5.6 in NFPA 13 apply, since the arrange-
ment will be a combined sprinkler/standpipe system.
Where the sprinkler system water supply requirement,
Combíned Systems, [14:7.10.1.3] including the hose stream allowance as determined in
For a building protected throughout by an approved accordance with NFPA 13, Standardfor the Installation
automatic sprinkler system, the system demand estab- of Sprinkler Systems, exceeds the system demand estab-
lished by Section 7.7 and 7.10.1 also shall be permitted lished by Section 7.7 and 7.10.1, the larger of the two
to serve the sprinkler system. [14:7.10.1.3.1] values shall be provided. [14:7.10.1.3.1.1]

2007 Automatic Sprinkler Systems Handbook


Supplement 4 • Combination Standpipe/Sprinkler Risers 971

r
Control valve
1
and check valve
�:lve
Sprinkler system for thisj �������:
floor is interconnected Cross connection
with an additional or loop sprinklers prinkler system for this floor
control valve between risers interconnected with an
in stair #2

-. -----,e----+-, /
dditional control valve in
a1r
#1

Sign

Floor
Combination riser
Combination riser

Stair 1 Stair 2
EXHIBIT 54. 7 Typical lnterconnection Design.

A separate sprinkler demand shall not be required. and should be limited to 50 gpm at each hose valve to
[14:7.10.1.3.1.2] a maximum of 100 gpm. [13:A.11.1.5.6]
For a combined system in a building equipped with
For fully sprinklered buildings, both NFPA 14 and NFPA 13
partial automatic sprinkler protection, the flow rate re-
quired by 7 .10.1 shall be increased by an amount equal establish the same requirements in 7.10.1.3.1.1 ofNFPA 14
to the hydraulically calculated sprinkler demand or 150 and 11.1.5.6(1) and (2) in NFPA 13. In this case, the system
gpm (568 L/min) for light hazard occupancies, or by demand requirements from NFPA 14 are compared to the
500 gpm (1893 L/min) for ordinary hazard occupancies, sprinkler system and hose stream requirements of NFPA 13,
whichever is less. [14:7.10.1.3.2] and the final system demand is the larger of the two values.
When hose valves for fire department use are attached It should also be noted that where the standpipe demand ex-
to wet pipe sprinkler system risers in accordance with ceeds the sprinkler and hose stream demands of NFPA 13,
8.17 .5.2, the following shall apply: 7.10.1.3.1.2 in NFPA 14 specifically states that a separate
( 1) The water supply shall not be required to be added sprinkler system demand is not required to be added to the
to standpipe demandas determined from NFPA 14, standpipe demand, which is already in excess of the required
Standardfar the Installation of Standpipe and Hose sprinkler and hose demand. (See Exhibit S4.8.)
Systems. One common area of confusion involves a fully sprin-
(2) Where the combined sprinkler system demand and klered building that does not require a standpipe system
hose stream allowance of Table 11.2.3.1.2 exceeds but the designer and/or AHJ determine that 21h in. valves
the requirements of NFPA 14, Standard far the for fire department use should be attached to the sprinkler
Installation of Standpipe and Hose Systems, this
system. The main difference here is that the sprinkler sys-
higher demand shall be used.
tem will be supplying 21h in. valves for fire department
(3) For partially sprinklered buildings, the sprinkler de-
mand, not including hose stream allowance, as indi- use, but the system will not be a combined standpipe/
cated in Figure 11.2.3.1.1 shall be added to the sprinkler system. Where this is the case, 8.17 .5 .1.4 in NFPA
requirements given in NFPA 14, Standard.far the 13 applies, and only the inside hose stream requirements
Installation of Standpipe and Hose Systems. from Table 11.2.3.1.2 in NFPA 13 would apply. The re-
[13: 11.1.5.6] quirements of NFPA 14 would not be applicable to this
specific arrangement.
For fully sprinklered buildings, if hose val ves or stations
are provided on a combination sprinkler riser and stand- System Pipe Sizing - Partially Sprinklered
pipe for fire department use in accordance with NFPA Buildings
14, Standard far the Installation of Standpipe and Hose
Systems, the hydraulic calculation for the sprinkler sys- Determining the combination standpipe/sprinkler system
tem is not required to include the standpipe allowance demand in a building protected by a partial automatic sprin-

Automatic Sprinkler Systems Handbook 2007


972 Supplement 4 • Combination Standpipe/Sprinkler Risers

To sprinklers (light
hazard typical
throughout
building at all floors)
------+-=--------+----.1r-..-_-_::-_R_o_o 150 gpm sprinklers
Standpipe flow rates
50 gpm sprinkler
500 gpm @ remate riser inside hose stream
250 gpm additional riser allowance
250 gpm
750 gpm total demand
----+----5 Sprinkler flow rates
of 200 gpm less
than standpipe
flow rate of 500 gpm

Sprinkler flow
rates not required
to be added to
FDC standpipe flow
rates.

Add additional �XXJ----,ir--�\_ Riser assembly


50 gpm outside 750 gpm
sprinkler hose
stream allowance City water supply
far light hazard
occupancy

EXHIBIT 54.8 Sizing Combination System - Two Standpipes and Sprinklers Throughout
(Standpipe Flow Rate Only).

kler system results in a potential conflict between the re- 500 gpm (1893 L/min) for ordinary hazard occupancies,
quirements of each document. This situation is addressed then the requirements of NFPA 13 and NFPA 14 are the
in 7.10.1.3.2 of NFPA 14 and 11.1.5.6(3) of NFPA 13 same and the required sprinkler and hose stream would be
in a slightly different way, which can result in differing added to the NFPA 14 required demand.
requirements. However, where the required sprinkler and hose stream
demand of NFPA 13 exceeds the limits established in
For a combined system in a building equipped with
partial automatic sprinkler protection, the flow rate
7.10.1.3.2 of NFPA 14, the requirements of NFPA 13 and
required by 7.10.1 shall be increased by an amount NFPA 14 would be different and would result in NFPA 13
equal to the hydraulically calculated sprinkler demand requiring a higher flow and NFPA 14 requiring a lower
or 150 gpm (568 L/min) for light hazard occupancies, flow. Where both documents are applicable to a partially
or by 500 gpm (1893 L/min) for ordinary hazard occu- sprinklered building, this conflict can be avoided by provid-
pancies, whichever is less. [14:7.10.1.3.2] ing the high flow required by NFPA 13. The final design
For partially sprinklered buildings, the sprinkler de- flow would then exceed the minimum requirements of
mand, not including hose stream allowance, as indi- NFPA 14 while meeting the mínimum requirements of
cated in Figure 11.2.3.1.1 shall be added to the NFPA 13. (See Exhibit S4.9.)
requirements given in NFPA 14, Standardfor the Jnstal-
An example of a combination standpipe/sprinkler riser
lation of Standpipe and Hose Systems. [13:11.1.5.6(3)]
with partial sprinkler protection in a building would be
Paragraph 7.10.1.3.2 of NFPA 14 requires that standpipe automatic sprinkler protection for a light hazard occupancy
demand from NFPA 14 be increased by the hydraulically located on the fifth floor of a six-story unsprinklered build-
calculated sprinkler demand or the specific allowances ing. The combination riser would initially be sized for the
from 7.10.1.3.2, whichever is less, while 11.1.5.6 of NFPA standpipe flow rate demand of 500 gpm (1893 L/min),
13 requires that the sprinkler demand and hose stream which would include 250 gpm (946 L/min)for each remote
required by NFPA 13 be added to the required standpipe fire department hose valve on the riser. The added NFPA
demand from NFPA 14. Where the required sprinkler and 14 sprinkler flow rate of 150 gpm (568 L/min) results in
hose stream demand of NFPA 13 is less than 150 gpm a total combined flow of 650 gpm (2460 L/min), and this
(568 L/min) for light hazard occupancies or is less than total flow rate establishes the initial system demand for

2007 Automatic Sprinkler Systems Handbook


Supplement 4 • Combination Standpipe/Sprinkler Risers 973

To sprinklers
(ordinary hazard
typical throughout
building at all floors)

Combined flow rates -------+-------------.i�---� Roof


;--- 500 gpm sprinklers

600 gpm @ remote riser ..- 25 gpm 100 gpm sprinkler

250 gpm additional riser ----+------ 6 inside hose stream


850 gpm total demand allowance
Combination ------,.,...•
riser
Sprinkler flow
rates of 600 gpm
exceed standpipe
----+------4 flow rate of
Standpipe 500 gpm. Size
flow rate ,.,....
riser for 600 gpm.
500 gpm

FDC 'l600 gpm


150 gpm +
outsideh� -,
stream } Riser assembly
allowance e �<1----e- J
for ordinary ( 850 gpm
hazard
occupancy City water supply

EXHIBIT 54.9 5izing Combination 5ystem - Two 5tandpipes and 5prinklers Throughout
(Sprinkler Flow Rate Exceeds Standpipe Flow Rate).

Combined flow rates ---------1--------------� Roof


500 gpm @ remote riser To partial sprinklers
(light hazard
250 gpm additional riser
occupancy at
150 gpm for partial sprinklers �., ,_.,.. floor 5)
900 gpm total demand

riser

FDC
No additional
sprinkler hose

stream allowan�
required to be H=*-----ilc---'
added � 900 gpm

City water supply

EXH/8/T 54. 10 Sizing Combination System - Two Standpipes and Partial Sprinklers
Throughout (Combined Flow Rates).

the combined standpipe/sprinkler system. At this point the This demand would then be compared to the demand estab-
required sprinkler and hose demand for the sprinklered lished by NFPA 14, and the more demanding arrangement
area of the building would be determined and added at the should be selected to ensure both the requirements ofNFPA
appropriate point(s) of connection to the standpipe system. 13 and NFPA 14 are met. If there are additional standpipe

Automatic Sprinkler Systems Handbook 2007


974 Supplement 4 • Combination Standpipe/Sprinkler Risers

risers, those additional standpipe flow rates would be added reliable, effective performance for fire fighter safety, as
to the rest of the system piping at the various points of well as to protect life and property. In the end, careful
connection. (See Exhibit S4.10.) planning and design analysis can ensure that the require-
ments of NFPA 14 and NFPA 13 can be met when providing
a combined system.
SUMMARY
REFERENCES CITED
The evaluation of a unique building design, new fire protec-
tion material, and equipment technology make combination National Pire Protection Association, 1 Batterymarch Park,
standpipe/sprinkler systems an ongoing challenge im- Quincy, MA 02169-7471.
pacting design, installation, testing, maintenance, and cost NFPA 13, Standard for the Installation of Sprinkler Sys-
of a combination system, particularly in high-rise build- tems, 2007 edition.
ings. However, the most important challenge to any design NFPA 14, Standard for the Installation of Standpipe and
is to satisfy the intended purpose of the system and provide Hose Systems, 2007 edition.

2007 Automatic Sprinkler Systems Handbook

Вам также может понравиться