Вы находитесь на странице: 1из 1

AEVR SAFETY PRECAUTION This manual uses the following symbols to ensure safe operation of this product.

MULTI-FUNCTIONABLE WARNING Warnings are indicated when mishandling this product might result in death or serious injury
to user.
DIGITAL VOLTAGE CONTROLLER Cautions are indicated when mishandling this product might result in minor injury to the user,
CAUTION or only physical damage to the timer.
User's Manual
WARNING
RESTRICTIONS ON USE
ΘNote this incorrect wiring of this product can damage it and lead to other hazards. Make sure the product has
When using this product in applications been correctly wired before turning the power ON.
that require particular safety or when ΘBefore wiring, or removing / mounting the product, be sure to turn the power OFF. Failure to do so might cause
using this product in important facilities, electric shock.
please pay attention to the safety of the ΘDo not touch electrically charged parts such as the power terminals. Doing so might cause electric shock.
overall system and equipment. Install fail- ΘDo not disassemble the product. Doing so might cause electric shock or faulty operation.
safe mechanisms, perform redundancy
checks and periodic inspections and CAUTION
adopt other appropriate safety measures ΘUse the product within the operating ranges recommended in the specification (temperature, humidity, voltage,
when it is necessary. shock, mounting direction, atmosphere and etc.). Failure to do so might cause fire or faulty operation.
ΘMake sure the product is firmly connected to the socket. Failure to do so might cause electric shock or fire.

SPECIFICATIONS NAMES AND FUNCTIONS OF FACEPLATE


Operating voltage AC/DC : 100 ~ 240V Display Voltage indicatior
Allowable operating
voltage range 85 ~ 110% of rated operating voltage

Rated frequency 50 / 60 Hz Phase sequence Time indicatior in second


R V
S
T S
Contact rating 250VAC 5A (Resistive load)
Under voltage setting Over voltage tripping delay
ANLY
TYPE
Display Display resolution ²1% AEVR

Power consumption Approx. 3.3VA OVER UNDER OVER UNDER


Over voltage setting VOLT VOLT TIME TIME Under voltage tripping delay
UNBAL. AUTO
Life Mechanical : 5,000,000 times / Electrical : 100,000 times REV. 5S
1S

Ambient temperature -10 ~ +50 °C Setting values display TEST OFF RESET Manual reset
Ambient humidity MAX 85% RH

Weight Approx. 135g Function settings

SETTING PROCEDURE

1. Over voltage Setting 3. Over voltage tripping delay setting 5. The function of DIP switches 6. Setting values display
R V R
S
V UNBAL. AUTO
By pressing "TEST" button, all setting value
S
T S OVER
VOLT
T S OVER
TIME
REV. 5S will be shown ordinally as follows. The display
1S
Set the desired value for over voltage. Set the tripping delay for over voltage. will show existing 3-phase voltages after 10
The display will show existing 3-phase The display will show existing 3-phase OFF seconds.
voltages after 10 seconds. voltages after 10 seconds.
ON Reverse phase protected R V OVER VOLTAGE
S
REV. T S SETTING VALUE
2. Under voltage Setting 4. Under voltage tripping delay setting OFF Reverse phase unprotected
ON Unbalance protected R V UNDER VOLTAGE
S
R V R V UNBAL. T S SETTING VALUE
S
T S UNDER
S
T S UNDER OFF Unbalance unprotected
VOLT TIME
ON Auto reset R V
OVER VOLTAGE DELAY
Set the desired value for under voltage. Set the tripping delay for under voltage. AUTO
S
T S

OFF Manual reset


The display will show existing 3-phase The display will show existing 3-phase R V
ON Auto reset delay 5 sec UNDER VOLTAGE DELAY
voltages after 10 seconds. voltages after 10 seconds. 5S/1S
S
T S

OFF Auto reset delay 1 sec

DISPLAY TIMING CHART

1. 3-phase voltages display 2. Fault indications


Reverse Time
The existing 3-phase voltages Reset Time Phase-loss Time
Over Time Under Time Reset Time Unbalance Time
will be shown ordinally every 3
R V R V
seconds as follows. S
T S
S
T S
Over Voltage
R S T SR T R S >+
- 5%
LINE Normal
R V Under Voltage
S
T S R V R V Phase Loss
S S
T S T S
R V
S
T S N.O. ( 1-3 )

R V R V R V
N.C. ( 1-4 )
S S S
T S T S T S

CONNECTION
3-Phase 3-Wire 3-Phase 4-Wire 1-Phase 2-Wire DC Voltage
MG.SW 1C 2b
Bottom View LINE
MOTOR MG.SW
R Bottom View LINE LINE LINE
MOTOR ~ LINE
M S R AC
~
~ DC
AC
T
M S
4 5 4 5 ~ 4 5
T 3 6 3 6 3 6
N
2 7 2 7 2 7
4 5 1 8 1 8 1 8
3 6
4 5
2 7 3 6
1 8
2 7 SOURCE SOURCE SOURCE
1 8 AC/DC 100~240V AC/DC 100~240V AC/DC 100~240V

SOURCE
AC/DC 100~240V

M-AEVR-D-B
ANLY ELECTRONICS CO., LTD.
http://www.anly.com.tw Printed in Taiwan