Technical description

How to implement an encoderless safely-limited speed function,


with an ACS880-01 and the safety functions module

This document presents details Safer machines with drive-based provides an encoderless safely-limited
how a safely-limited speed (SLS) functional safety speed (SLS) safety function. The
safety function can be designed and Drive-based safety functions are function ensures that the speed of the
implemented using an ACS880-01 used in applications that require risk motor does not exceed a specified limit
drive and a safety functions module reduction from eg. unexpected and while allowing machine interaction to be
together with other ABB safety hazardous movement. The aim is to performed eg. at slow speed without
devices. The safety function design machines that are safe to use. stopping the drive. The SLS function is
is implemented according to This safety function example can be pre-programmed in the safety functions
EN/IEC 62061, EN ISO 13849-1, implemented with ACS880 series drives module. Only application specific
EN/IEC 60204-1 and EN/IEC 61800- only. parameter configuration is necessary to
5-2 machinery standards. Necessary commission the function in addition to
SIL/PL calculations are presented ACS880-01 industrial drives, together electrical connections.
using ABB’s Functional safety design with the safety functions module,
tool.
ACS880-01 R5 drive Eden OSSD non-contact safety sensor Safety functions module, FSO-12

Effective and reliable encoderless safely-limited speed function


for drive applications
Encoderless safely-limited speed function
Overview of the safety function Operation of the safety function
details The SLS function (Figure 1) ensures When the Eden sensor is activated, the
that the motor speed does not exceed safety functions module detects the
Requirements Safely-limited speed
according to (SLS)
a specified speed limit. In ABB drive sensor signal and activates the SLS
EN/IEC 60204-1 The SLS function prevents solutions, the SLS function can function. If the motor speed is higher
and the motor from exceeding automatically decelerate the motor speed than the specified SLS speed limit at
EN/IEC 61800- the specified speed limit. below the defined speed limit when the time SLS is activated, the drive
5-2
SLS is activated. Both time delay and decelerates the motor speed first below
Safety SIL 3 (EN/IEC 62061), ramp monitoring can be used during the the SLS speed limit, while the safety
integrity level PL e (EN ISO 13849-1) deceleration. The SLS function is suitable functions module monitors the transition
for ensuring that machine runs safely at ramp. When the motor speed is below
the defined speed and that it does not the SLS speed limit, the module begins
accelerate during eg. maintenance or monitoring the SLS to ensure that the
cleaning operations. motor speed does not exceed the
Speed
specified level. Monitoring will continue
until the SLS function is deactivated.

Returning the Eden sensor to the


standby position deactivates the
0 Time SLS function. The drive system will
Ramp SLS active automatically resume operation or it will
monitoring be reset manually, depending on the
Figure 1: Safely-limited speed safety function application requirements. If SLS trips
using the ramp monitoring method.
(activates STO due to overspeed), a
Design of the safety function manual reset is required.
The design of the encoderless safely-
limited speed (SLS) function consists of Ensuring the required safety
an Eden non-contact safety sensor as performance
an activating switch, the safety functions The safety function has to fulfil the
module and a safe torque off (STO) required safety performance determined
-circuit inside the ACS880-01 drive as an by a risk assessment. ABB’s Functional
actuator to stop the drive if the speed of safety design tool (FSDT-01) is used to
the motor exceeds the specified speed design the desired safety function. This
limit. There is no need for a separate is carried out according to the following
encoder when the safety functions steps:
module is used (only for applications that
do not have active loads). See circuit
diagram (Figure 2) for connection details.
2 ABB drives | Technical description
EDEN OSSD FSO-12 ACS880-01 R5
Activating switch Safety functions module Drive
1.1.0.0 1.2.0.0 1.3.0.0

Figure 2: Connection example of the encoderless safely-limited speed Figure 3: Safety calculation and design for the SLS safety function
(SLS) function with ACS880-01 drive. according to EN ISO 13849-1 (can also be made according to EN/IEC
62061). The design is made with the Functional safety design tool.

1. Evaluate the risks to establish target General considerations


Abbreviations
safety performance (SIL/PL level) for the Achieving machinery safety requires
safety function. a systematic approach beyond the Abbr. Reference Description

physical implementation of a safety DCavg EN ISO Diagnostic


2. Design the safety function loop function. The overall machinery safety 13849-1 coverage
and verify the achieved performance generally covers the following areas: MTTFd EN ISO Mean time to
level (PL) or safety integrity level (SIL) 13849-1 dangerous failure
for the safety function loop (according – Planning for and managing functional
PFHd EN/IEC Probability of
to EN ISO 13849-1 or EN/IEC 62061, safety during the lifecycle of the 62061 dangerous failures
respectively), utilizing the device safety machine per hour
data and the application specific – Assuring compliance to local
PL EN ISO Performance level:
characteristics. laws and requirements (such as the 13849-1 corresponds to
Machinery directive/CE marking) SIL, Levels a-e
3. Generate the report for the machine – Assessing machine risks (analysis
SIL EN/IEC Safety integrity
documentation. The report should and evaluation) 62061 level
contain all the calculation results as well – Planning the risk reduction and
as all assumptions made during the establishing safety requirements Note: This is an indicative example. Relevant
installation, design and safety calculations
application design. – Designing the safety functions need to be specifically completed for
– Implementing and verifying the each system implementation according to
Figure 3 shows the design of the safety functions machinery safety standards (EN/IEC 62061,
encoderless safely-limited speed safety – Validating the safety functions EN ISO 13849-1, EN/IEC 60204-1 and
EN/IEC 61800-5-2). ABB does not take
function with the ACS880-01 drive. – Documenting the implemented
any responsibility of the accuracy of the
The function in this document achieves functions and results of risk data used in this document and reserves
PL e (SIL 3). Safety calculation is made assessment, verification and right to make changes without further
using the default safety data available validation notice. For detailed safety function
implementation please contact your local
for the safety devices.
ABB representative.
For more information concerning
Safety function verification and functional safety and the Functional
validation safety design tool, see
In addition to the safety calculations www.abb.com/safety and ABB’s
for the achieved safety performance Technical Guide no. 10.
(SIL/PL), the safety function needs to
be functionally verified as well.

Finally, the implemented safety function


is validated against the risk assessment
to ensure that the implemented safety
function actually reduces the targeted
risk. Technical description | ABB drives 3
Contact us

3AUA0000172917 REV A EN 14.1.2015 #17364


www.abb.com/drives © Copyright 2015 ABB. All rights reserved.