Вы находитесь на странице: 1из 12

FLICKER

GENERATOR 11kV
Info Operation mode: Swing
Rating kW kV %pf kVA %Eff Poles
5000 11 100 5000 95 4
%Bus Nom.kV FLA RPM
100 262.4 1800

Imp/Model % % Ohm
Xd 19 Xd"/Ra 19 Ra 1 Ra 0.242
X2 18 X2/R2 9 R2 2 R2 0.484
Xo 7 X0/R0 7 R0 1 R0 0.242
Rdc 0 Rdc 0

Grounding Connection
WYE(Y) Type
Resistor
V ln
6.351

TRANSFORMER1 (11kV-230kV)
Info Standard
ANSI
Rating Voltage Rating
kV FLA Nominal Bus kV
Primary 11 7873 11
Secondary 230 376.5 230

Impedance Impedance
%Z X/R R/X %X %R
Positive 10 3.96 0.253 9.696 2.448
Zero 10 3.96 0.253 9.696 2.448

Tap Fixed Tap Per Unit


%Tap kV Tap Turn Ratio
Prim 0 ˄˅ 11 1
Sec 0 ˄˅ 230 1

Grounding Phase Shift


Winding Connection Connection Angle
YD 30

Transformer Loading
kVA kW kvar
MVA Operating 40.346 -0.105 40.346
150 Connected 0.09 0.0765 0.0474
Sizing
TRANSMISSION LINE
Length(mi) From Bus2 (230kV)
50 To Bus3 (230kV)
Info
Parameter Phase Conductor
Conductor type R-T1(25C) R-T2(50C) XaΩ/mi
Al 0.1937 0.2127 0.433
Outside Dia. GMR Xa'Ω/mi
0.433 in 0.433 ft 0.0992

Configuration Phase
Height(FT) Spacing(FT)
35 AB 3
BC 3
CA 6

Conductors
Seperation 12 inch
Conductor/Phase 3

Grouping Tower
Ground Resistance 10 ohms
Average Distance 50 ft

Earth Earth Layers


Number of Earth Layers 1˅
p(ohms-m) e μ
Layer1 100 1 1

Impedance Impedance (per phase)


R-T1 X Y
Pos. 0.06566 0.30309 14.4858
Neg. 0.06566 0.30309 14.4858
Zero 0.34402 2.71037 3.02997

Ampacity Ampacity
Ta Ampacity Conductor Temp.
Lib 25˚C Base 655 A Lib 75˚C
Operating 0 A Top 40˚C
Derated 1124.7 A Tc 75˚C

TRANSFORMER2 (230kV-32.5kV)
Info Standard
ANSI
Rating Voltage Rating
kV FLA Nominal Bus kV
Primary 230 0.377 230
Secondary 32.5 2.665 32.5

Impedance Impedance
%Z X/R R/X %X %R
Positive 10 2.47 0.405 9.269 3.753
Zero 10 2.47 0.405 9.269 3.753

Tap Fixed Tap Per Unit


%Tap kV Tap Turn Ratio
Prim 0 ˄˅ 230 1
Sec 0 ˄˅ 32.5 1

Grounding Phase Shift


Winding Connection Connection Angle
DY 30

Sizing Transformer Loading


kVA kW kvar
kVA Operating 91.73 76.29 50.94
150 Connected 90 76.5 47.41

LUMPED LOAD (receiving end) 34.5kV


Info Connection Reference kV Bus
3-Phase Calculated Bus4 32.5kV

Nameplate Model Type Rated kV


Conventional 34.5

Ratings
kVA kW kvar %PF Amp
90 76.5 47.41 85 1.51

Short-Circuit Short- Circuit Contribution


%LRC 650 • High
Medium
%Total Load 80 Low
HEN

Operation mode: Swing


kW kV %pf kVA %Eff Poles
3000 11 100 3000 95 4
%Bus Nom.kV FLA RPM
100 157.5 1800

% % Ohm

Xd 19 Xd"/Ra 19 Ra 1 Ra 0.403333
X2 18 X2/R2 9 R2 2 R2 0.806667
Xo 7 X0/R0 7 R0 1 R0 0.403333
Rdc 0 Rdc 0

Connection
WYE(Y) Type
Resistor
V ln
6.351

Standard
ANSI
Voltage Rating
kV FLA Nominal Bus kV
Primary 11 7873 11
Secondary 230 376.5 230

Impedance
%Z X/R R/X %X %R
Positive 10 3.96 0.253 9.696 2.448
Zero 10 3.96 0.253 9.696 2.448

Fixed Tap Per Unit


%Tap kV Tap Turn Ratio
Prim 0 ˄˅ 11 1
Sec 0 ˄˅ 230 1

Phase Shift
Winding Connection Connection Angle
YD 30
Transformer Loading
kVA kW kvar
MVA Operating 40.635 -0.0881 40.635
150 Connected 0.07 0.0595 0.0369
Length(mi) From Bus2 (230kV)
50 To Bus3 (230kV)

Phase Conductor
Conductor type R-T1(25C) R-T2(50C) XaΩ/mi
Al 0.1913 0.21 0.424
Outside Dia. GMR Xa'Ω/mi
0.883 in 0.0304 ft 0.098

Phase
Height(FT) Spacing(FT)
35 AB 3
BC 3
CA 6

Conductors
Seperation 12 inch
Conductor/Phase 3

Tower
Ground Resistance 10 ohms
Average Distance 50 ft

Earth Layers
Number of Earth Layers 1˅
p(ohms-m) e μ
Layer1 100 1 1

Impedance (per phase)


R-T1 X Y
Pos. 0.06489 0.30015 14.5801
Neg. 0.06489 0.30015 14.5801
Zero 0.34324 2.70743 3.03403

Ampacity
Ta Ampacity Conductor Temp.
Lib 25˚C Base 666 A Lib 75˚C
Operating 0 A Top 40˚C
Derated 1151.1 A Tc 75˚C

Standard
ANSI
Voltage Rating
kV FLA Nominal Bus kV
Primary 230 0.377 230
Secondary 32.5 2.665 32.5

Impedance
%Z X/R R/X %X %R
Positive 10 2.47 0.405 9.269 3.753
Zero 10 2.47 0.405 9.269 3.753

Fixed Tap Per Unit


%Tap kV Tap Turn Ratio
Prim 0 ˄˅ 230 1
Sec 0 ˄˅ 32.5 1

Phase Shift
Winding Connection Connection Angle
DY 30

Transformer Loading
kVA kW kvar
kVA Operating 70.84 59.21 38.88
150 Connected 70 59.5 36.87

Connection Reference kV Bus


3-Phase Calculated Bus4 32.5kV

Model Type Rated kV


Conventional 34.5

Ratings
kVA kW kvar %PF Amp
70 59.5 36.87 85 1.17

Short- Circuit Contribution


%LRC 650 • High
Medium
%Total Load 80 Low
HAWK

Operation mode: Swing


kW kV %pf kVA %Eff Poles
4000 11 100 4000 95 4
%Bus Nom.kV FLA RPM
100 209.9 1800

% % Ohm
Xd 19 Xd"/Ra 19 Ra 1 Ra 0.3025
X2 18 X2/R2 9 R2 2 R2 0.605
Xo 7 X0/R0 7 R0 1 R0 0.605
Rdc 0 Rdc 0

Connection
WYE(Y) Type
Resistor
V ln
6.351

Standard
ANSI
Voltage Rating
kV FLA Nominal Bus kV
Primary 11 7873 11
Secondary 230 376.5 230

Impedance
%Z X/R R/X %X %R
Positive 10 3.96 0.253 9.696 2.448
Zero 10 3.96 0.253 9.696 2.448

Fixed Tap Per Unit


%Tap kV Tap Turn Ratio
Prim 0 ˄˅ 11 1
Sec 0 ˄˅ 230 1

Phase Shift
Winding Connection Connection Angle
YD 30
Transformer Loading
kVA kW kvar
MVA Operating 40.443 -0.0965 40.433
150 Connected 0.08 0.068 0.0421
Length(mi) From Bus2 (230kV)
50 To Bus3 (230kV)

Phase Conductor
Conductor type R-T1(25C) R-T2(50C) XaΩ/mi
Al 0.1928 0.2117 0.43
Outside Dia. GMR Xa'Ω/mi
0.858 in 0.029 ft 0.0988

Phase
Height(FT) Spacing(FT)
35 AB 3
BC 3
CA 6

Conductors
Seperation 12 inch
Conductor/Phase 3

Tower
Ground Resistance 10 ohms
Average Distance 50 ft

Earth Layers
Number of Earth Layers 1˅
p(ohms-m) e μ
Layer1 100 1 1

Impedance (per phase)


R-T1 X Y
Pos. 0.06537 0.30208 14.5167
Neg. 0.06537 0.30208 14.5167
Zero 0.06537 2.70936 3.03131

Ampacity
Ta Ampacity Conductor Temp.
Lib 25˚C Base 659 A Lib 75˚C
Operating 0 A Top 40˚C
Derated 1133.6 A Tc 75˚C

Standard
ANSI
Voltage Rating
kV FLA Nominal Bus kV
Primary 230 0.377 230
Secondary 32.5 2.665 32.5

Impedance
%Z X/R R/X %X %R
Positive 10 2.47 0.405 9.269 3.753
Zero 10 2.47 0.405 9.269 3.753

Fixed Tap Per Unit


%Tap kV Tap Turn Ratio
Prim 0 ˄˅ 230 1
Sec 0 ˄˅ 32.5 1

Phase Shift
Winding Connection Connection Angle
DY 30

Transformer Loading
kVA kW kvar
kVA Operating 81.24 67.74 44.86
150 Connected 80 68 42.14

Connection Reference kV Bus


3-Phase Calculated Bus4 32.5kV

Model Type Rated kV


Conventional 34.5

Ratings
kVA kW kvar %PF Amp
80 68 42.14 85 1.34

Short- Circuit Contribution


%LRC 650 • High
Medium
%Total Load 80 Low
HAWK

Operation mode: Swing


kW kV %pf kVA %Eff Poles
1000 11 100 1000 95 4
%Bus Nom.kV FLA RPM
100 52.49 1800

% % Ohm
Xd 19 Xd"/Ra 19 Ra 1 Ra 1.21
X2 18 X2/R2 9 R2 2 R2 2.42
Xo 7 X0/R0 7 R0 1 R0 1.21
Rdc 0 Rdc 0

Connection
WYE(Y) Type
Resistor
V ln
6.351

Standard
ANSI
Voltage Rating
kV FLA Nominal Bus kV
Primary 11 7873 11
Secondary 230 376.5 230

Impedance
%Z X/R R/X %X %R
Positive 10 3.96 0.253 9.696 2.448
Zero 10 3.96 0.253 9.696 2.448

Fixed Tap Per Unit


%Tap kV Tap Turn Ratio
Prim 0 ˄˅ 11 1
Sec 0 ˄˅ 230 1

Phase Shift
Winding Connection Connection Angle
YD 30
Transformer Loading
kVA kW kvar
MVA Operating 40.443 -0.0965 40.433
150 Connected 0.05 0.0425 0.0263
Length(mi) From Bus2 (230kV)
50 To Bus3 (230kV)

Phase Conductor
Conductor type R-T1(25C) R-T2(50C) XaΩ/mi
Al 0.2294 0.2518 0.435
Outside Dia. GMR Xa'Ω/mi
0.435 in 0.0277 ft 0.0277

Phase
Height(FT) Spacing(FT)
35 AB 3
BC 3
CA 6

Conductors
Seperation 12 inch
Conductor/Phase 3

Tower
Ground Resistance 10 ohms
Average Distance 50 ft

Earth Layers
Number of Earth Layers 1˅
p(ohms-m) e μ
Layer1 100 1 1

Impedance (per phase)


R-T1 X Y
Pos. 0.07766 0.30411 14.3807
Neg. 0.07766 0.30411 14.3807
Zero 0.35602 2.71139 3.0254

Ampacity
Ta Ampacity Conductor Temp.
Lib 25˚C Base 594 A Lib 75˚C
Operating 0 A Top 40˚C
Derated 1014.6 A Tc 75˚C

Standard
ANSI
Voltage Rating
kV FLA Nominal Bus kV
Primary 230 0.377 230
Secondary 32.5 2.665 32.5

Impedance
%Z X/R R/X %X %R
Positive 10 2.47 0.405 9.269 3.753
Zero 10 2.47 0.405 9.269 3.753

Fixed Tap Per Unit


%Tap kV Tap Turn Ratio
Prim 0 ˄˅ 230 1
Sec 0 ˄˅ 32.5 1

Phase Shift
Winding Connection Connection Angle
DY 30

Transformer Loading
kVA kW kvar
kVA Operating 81.24 67.74 44.86
150 Connected 50 42.5 26.34

Connection Reference kV Bus


3-Phase Calculated Bus4 32.5kV

Model Type Rated kV


Conventional 34.5

Ratings
kVA kW kvar %PF Amp
50 42.5 26.34 85 0.837

Short- Circuit Contribution


%LRC 650 • High
Medium
%Total Load 80 Low