Академический Документы
Профессиональный Документы
Культура Документы
Version V2.4
Revision date November 18, 2008
BOM 31011614
Emerson Network Power provides customers with technical support. Users may contact the nearest
Emerson local sales office or service center.
Chapter 1 Overview
This chapter introduces the features, main parts, requirements on transportation and storage environment of the
Liebert.PEX series air conditioner.
P1 020 U W P M S 1 R
Humidity type: 0-none; R-infrared; S-steam generating
Reheat type: 0-none; 1-one stage -standard; 2-two stage
iCOM display: S-standard display; L-large display
Power supply: M-three phase/50Hz/400V
System configuration: R-R22, scroll, 2 compressors; P-R22, scroll, 1 compressor
S-R407C, scroll, 2 compressors; Z-R407C, scroll, 1 compressor
Cooling type: A-air cooled; W-water cooled; G-glycol cooled
Air path: U-upflow; F-downflow; D-duct
Cooling capacity class: kW
Unit frame: 1-one bay; 2-two bay; 3-three bay
Liebert.PEX series
Compressor
The Copeland scroll compressor features low vibration, low noise and high reliability. The connection mode of
Rotalock makes the maintenance easier.
Evaporator
Finned tube evaporator with high heat dissipation efficiency is used. The distributor, with its model-specific design,
ensures that the refrigerant is distributed evenly in each loop, improving the evaporator efficiency to a great extent.
Thermal expansion valve
The external equalizer type thermal expansion valve collects temperature and pressure signals at the same time, so
that it can regulate the refrigerant flow more accurately.
Infrared humidifier
The infrared humidifier is designed with a simple structure, which is easy for teardown, cleaning and maintenance. It is
adjustable to a wide range of water qualities, with fast startup and high humidifying efficiency.
Fan
The system uses centrifugal fan with high efficiency and reliability, large airflow and long blowing distance. With the
belt transmission mechanism, it is easy for maintenance.
Electric reheat
The system uses screw finned U type stainless steel electric heating tube, with fast heating speed and evenly
distributed heat volume.
Sight glass
The sight glass is the window for observing the system refrigerant recycle, mainly the moisture content of system.
When the moisture content is too high, the color will change from green to yellow.
Filter drier
The filter drier can effectively eliminate the moisture in system within a period of time, filtrate the impurities generated
during long-term system operation and ensure normal system operation.
PHE (for water-cooled series)
The system uses soldered auto-cleansing PHE, which features compact construct and high heat exchanging
efficiency.
Water flow regulator (for water-cooled series)
The water flow regulator controls the water flow in the PHE by regulating the valve position according to the collected
high-pressure signal in the cooling system, thus ensuring the stable system operation.
1.3.3 Controller
The micro-processing controller of Liebert.PEX series air conditioner uses the LCD screen with blue backlight and 128
× 64 pixels. The user interface operation is simple. The multi-level password protection can effectively prevent illegal
operation. The controller also features power failure auto-restoration and high / low voltage protection function. The
operation time of components is available through the menus. The expert-level fault diagnosis system can display the
current fault information automatically, facilitating the maintenance. The controller can store 400 records of historical
events. The panel of micro-processing controller is shown in Figure 1-2.
This chapter introduces the mechanical installation of the Liebert.PEX series air conditioner, which includes
transportation, installation arrangement and installation procedures.
When moving the indoor unit,, keep the obliquity within 75° ~ 105°, as shown in Figure 2-2.
10
5 75
2.1.2 Unpacking
Move the product to the place most close to the final installation site before unpacking the unit.
Follow the procedures below to unpack the unit:
1. Removing the side boards and top cover
Liebert.PEX series air conditioner uses the international packaging. You can use a hammer or straight screwdriver to
straighten the hook, as shown in Figure 2-3.
At first, straighten all the hooks that fix side board I, and remove side board 1. Then straighten all the hooks that fix
side board 2, and remove side board 2. At last remove top cover 3, as shown in Figure 2-4.
2
1
2.1.3 Inspection
After receiving the product, you should check against the packing list. If any parts are found missing, distorted or
damaged, please report to the carrier immediately. If any covert defects are found, please report to the carrier and the
distributor.
Before installation, make sure that the installation environment meets the requirements (see 1.4 Environment
Requirements) and the building should be transformed to accommodate the construction work of piping, wiring and
ventilation ducts.
Follow the design drawings strictly when installing the equipment, and reserve the space for maintenance. The
manufacturer’s engineering dimensions drawings can serve as a reference.
Condenser coil
Evaporator coil
Check valve+
Distributor
Traps*(every 7.5m
of vertical lift)
Sight glass
Filter drier Hot gas Dehum solenoid valve
Solenoid valve+ bypass valve (#1 system only)
(single compressor)
Sensing bulb
Ball valves
High pressure switch
Charging port Low pressure switch
Discharge line Suction line
Service valve
Scroll compressor
Note: the hot gas bypass valve is only for the single system unit.
Note
1. The single system is used as an example to describe the double system.
2. : Factory piping.
3. : Field piping (by others).
4. *: Components are not supplied by Emerson but are recommended for proper circuit operation and maintenance.
5. +: Components are required when the equivalent length exceeds 30m.
Evaporator coil
Distributor
Liquid
bypass High pressure
valve switch Low pressure switch
Discharge Charging port
line
Suction line
Pipe nipple joints Service valve
Pressure gauges*
Scroll compressor
Note: hot gas bypass valve component is only for the single system unit.
Note
1. The single system is used as an example to describe the double system.
2. : Factory piping;
3. : Field piping (completed by the technicians).
4. *: Components are not supplied by Emerson but are recommended for proper circuit operation and maintenance.
5. : Components are not supplied by Emerson. Please select and install the female joints according to the dimensions of male
joints provided at the field.
Note
1. If the condenser is installed higher than the compressor, an external back bend should be fitted to the suction line and liquid
return line of the condenser, so as to prevent the liquid refrigerant from flowing back when the condenser stops.
2. The top end of the back bend must be installed higher than the highest copper pipe of the condenser.
Outdoor unit Back bend (higher than the highest copper pipe of condenser)
Max. 7.5m
Slope dicharge
The earth surface
Humidifier
water in
Condenser
water out
Seal
Heat insulation floor Floor
Indoor unit
Slope dicharge
Seal
The earth surface
Humidifier water in
Slope liquid
Heat insulation floor Floor
Outdoor unit
Figure 2-10 shows the arrangement of the cooling water system, which requires the water supply hotter than 39.2°F.
Use heaters if the water source cannot meet this requirement. The cooling tower is the closed type.
Expansion water tank
Manameter Filter
Pump
Exhaust water valve
T P
Temperature
gauge
Strainer
PEX Unit
P
T
T
Ball
valve
Drain valve
853
54
6 853
25
6
25
400
1970
1970
4
4
87
87
54
256 17
17 04
24 04
0 4
0 0
42
0
40
0
1970
1970
874 87
4
54 2
256 40
40 25
0 53
42 25
0 53
40
0
46
5
40
0
1970
1970
4
87
4 87
Plenum
You can select the air supply plenum with grids for the upflow system. The appearance of the plenum is shown in
Figure 2-14, Figure 2-15 and Figure 2-16. The dimensions are listed in Table 2-2.
A B
A B
Figure 2-14 One bay plenum Figure 2-15 Two bay plenum
A
B
Note
If the height of the plenum selected for air conditioner unit exceeds 600mm, consult the factory for non-standard production..
Outdoor unit
See Liebert.PEX Condenser User Manual for the dimensions and mechanical parameters.
3. Prevent the outdoor air from entering the equipment room, because the outdoor air that enters the equipment room
may increase the load of heating, cooling, humidifying and dehumidification of the system. It is recommended that the
inhalation of outdoor air be kept below 5% of the total indoor airflow.
4. All the doors and windows should be closed and the seams should be as narrow as possible.
Note
Liebert.PEX series air conditioner system will generate condensed water, and water leakage may damage the precision equipment
nearby. So do not install the system in the vicinity of any precision equipment, and the installation site must provide draining
pipes.
1. To ensure normal operation, the installation space for the indoor unit shall be capacious enough.
2. Too small space for the indoor unit will baffle the airflow, shorten the cooling cycle; the air supply and air exhaust
may mix, and the decibel may rise.
3. Do not place the indoor unit in a concave or at the end of a strip area.
4. Do not huddle multiple indoor units, lest there should be mixed airflow, unbalanced load and competitive operation.
5. For the convenience of daily maintenance, do not install other equipment (such as smoke detector) above the
cabinet.
Figure 2-17 shows the installation place of the indoor unit.
Good place
Unit
Note:
46.5
Front side of cabinet
853
760
46.5
820
.5
680
H
67
Rubber cushion(top)
161.5 Angle steel
4- Ф14 cabinet installation hole
530
Rear side of 161.5
cabinet
Installation hole Steel plate
Rubber cushion (lateral) Rubber cushion (bottom)
for expansion bolt
46.5
46.5
67
Upflow
46.5
161
82
0
3
59
46.5
67
Downflow
Figure 2-19 Mounting base of two bay series
0
0.5
82
255
68
3
Rubber cushion(top)
161
0
67
46.5
16
1.5
53
0 H
3
68
0
Steel plate
82
Installation hole for expansion bolt
73
0
Rubber cushion (lateral)
67
12
Angle steel Rear side of cabinet 1.5
Upflow
255
3
68
46.5
16
1.5
53
0 H
Rubber cushion(bottom)
0
3
82
59
Steel plate
Installation hole for expansion bolt 730
67
Downflow
Figure 2-20 Mounting base of three bay series
Table 2-3 Specifications of indoor unit mounting base
Item Specification Remark
Steel plate 100mm × 100mm × (5 ~ 6.5)mm -
Angle steel 40mm × 40mm × 3mm -
Top Thickness: 3mm ~ 5mm -
Rubber
Lateral Thickness: 2mm ~ 3mm -
cushion
Botton Thickness: 10mm ~ 12mm -
Installation hole for
- Install the holes according to your requirements
expansion hole
One bay 1. Only three-bay unit needs the middle leg
support (front and rear)
Two bay H = 200mm (upflow unit)
2. The upflow unit do not need the flow deflector
H H = 300mm (downflow unit, according to the floor
3. The H dimension is only a reference. It should
height)
Three bay be determined accroding to your actual
requirements during making the mounting base
Note:
The external side boards of the unit cannot bear weight. Take this into consideration while selecting angle steel and fixing holes
2. Lay a layer of rubber cushion on the top, lateral of mounting base and on the bottom of the steel plate respectively.
See Figure 2-18, Figure 2-19 and Figure 2-20 for their positions and see Table 2-3 for the thickness.
3. Identify the installation position. Fix the mounting base onto the mounting base according to the site conditions and
your requirement.
4. Fix the AC unit onto the mounting base with nuts, spring washers, flat washers and bolts.
2.6 Piping
2. The pipe sizes recommended in Table 2-5 are ‘equivalent lengths’, which has included the resistance brought about
by bends and valves. You should confirm that the sizes are appropriate for the site conditions.
Table 2-5 Equivalent lengths of partial components
Outer Diameter (OD) of Equivalent length (m)
liquid pipe (inch) 90°bend 45°bend T type three way
3/8 0.21 0.10 0.76
1/2 0.24 0.12 0.76
5/8 0.27 0.15 0.76
3/4 0.3 0.18 0.76
7/8 0.44 0.24 1.1
1-1/8 0.56 0.3 1.4
Note
A trap is required for every 7.5m of vertical lift. Please consult the factory for detailed information.
Connecting pipes
The pipes to connect include:
1. Cooling water drain-pipe of indoor unit
2. Water supply pipe of infrared humidifier
3. Connecting copper pipe (exhaust pipe and liquid return pipe) between indoor unit and outdoor unit
4. Installing extension subassembly (optional)
Connecting cooling water drain-pipe of indoor unit
The cooling water of infrared humidifier and evaporator is converged by the cross connector and drains through the
draining pipe, as shown in Figure 2-21. The OD of the pipe is 25mm. If the draining pipe is used by three or more units,
the minimal OD of the pipe should be 40mm.
Note
Because the humidifier contains boiling water, the plastic pipe must be rated higher than 194°F.
Connector of condensation
water drain pipe
To infrared humidifier
water pan
To condensation water
To condensation water pan of evaporator
pan of evaporator
Cross connector
Hose clamp
To the condensation
water drain pipe
Note
1. A Φ25 hose clamp is delivered as an accessory to connect the draining pipe.
2. When connecting the draining pipe, make sure that the U bend is installed vertically and the ‘U’ shape is not distorted, so as to
ensure that the cooling water can be drained immediately and effectively.
Note
Main water supply connections must be made in accordance with local laws and regulations.
Over-temperature protection
Water pan fixing screw switch (under the pan)
Water level sensor
Connecting copper pipe (exhaust pipe and liquid return pipe) between indoor unit and outdoor unit
The indoor unit and outdoor unit are connected through welded copper pipes. The connection of discharge pipe / liquid
pipe of indoor unit is shown in Figure 2-23. Note that the ball valve must be wrapped with a wet cloth before welding. In
addition, many notes and instruction labels are pasted onto the base board and side board close to the ball valve. Do
not have them burned during the welding operation.
Note
The exposure time of system pipes do not exceed 15min. Otherwise, it will lead to the POE refrigeration oil moisture effect the
life of the key components and the system operation stability.
Horizontal sections of discharge pipes should be sloped downward from the compressor, with a slope of at least 1:200
(5mm down for each 1m run). Discharge pipes should be heat insulated where they are routed in the conditioned
space (including under a raised floor).
The liquid pressure drop should not exceed 40kPa (5psi ~6psi), provided that there is no loss of refrigeration. The
liquid line pressure drop is the sum of liquid flow resistance from the tubing and fitting (including the drier), plus the
loss of head pressure due to elevation above the condenser. If the liquid temperature is 100.4°F, the static pressure
loss is 11kPa (1.6 psi) per meter of lift.
Considering the effect of the pipe OD to the system pressure drop, the pipe OD of indoor unit and outdoor unit should
be determined according to the specifications listed Table 2-6.
Table 2-6 Recommended pipe sizes
Recommended pipe size
Model P1020 P1025 P1030 P1035 P2040 P2045 P2050
Eq.Lgth D L D L D L D L D L D L D L
10m 22 13 22 13 22 13 22 13 22 13 22 13 22 13
20m 22 13 22 13 22 13 22 16 22 13 22 16 22 13
30m 22 13 22 13 22 16 25 16 22 13 25 16 22 13
40m* 22 13 22 13 22 16 25 16 22 13 25 16 22 13
50m* 22 13 22 16 25 16 25 16 22 13 28 19 22 16
60m* 22 16 22 16 25 16 25 19 22 16 28 19 22 16
Model P2055 P2060 P2070 P3080 P3090 P3100
Eq.Lgth D L D L D L D L D L D L
10m 22 16 22 13 22 13 22 13 22 13 22 16
20m 25 16 22 13 22 16 22 16 25 16 25 16
30m 28 19 22 16 25 16 25 16 25 16 28 19
40m* 28 19 22 16 25 16 25 16 25 16 28 19
50m* 28 19 25 16 25 16 28 19 28 19 28 19
60m* 32 19 25 16 25 19 28 19 28 19 32 19
Notes:
1. Extension subassembly should be added to the “Eq.Lgth” marked with *.
2. D: discharge line, L: liquid line.
3. Consult factory if the line length exceeds 60m
So, during installing the solenoid valve, you need not to cut the indoor unit pipes. After the whole system is installed,
you can open the ball valve to keep pressure and carry out vacuum operation, avoiding the moisture absorption of the
compressor refrigeration oil and ensuring the operation safety and life of the compressor. For installation valve of the
check valve, refer to Figure 2-6.
For the electrical connections of the extension subassembly, refer to 3.2.4 Wiring Of Extension Subassembly
Solenoid Valve (For Site Installation).
Charging refrigerant and adding refrigerant oil
The male connector of the water inlet / outlet for Liebert.PEX indoor unit is shown in Figure 2-24. You can select a
suitable female connector, or connect through welding. However, screw connection is recommended. Make sure the
junction is well sealed.
PHE
Screw connector
(G1-1/4")
Water
Screw connector outlet
(G1-1/4") Water
inlet
Waterflow regulator
Figure 2-24 Screw connector (water-cooled)
F 4- Φ 13 knock-out F
25
680.5
798
72.5
D 2- Φ 35 knock-out 25
2- Φ 64 knock-out 72 109
80
IRWI P
Φ 40
WO/LL K K
200
161
WI/DL
140
F F
45 760 45
F F
4- Φ13knock-out
25 25
683
F F
70
70
45 81 45
166 81
25
683
25
72.5
2- Φ 35 knock-out
WO/LL/D WI/DL 2- Φ 40
6- Φ 64 knock-out 116 WI/DL
WO/LL D
80
knock-out
62.5
WO/LL
k k WI/DL/IRWI k k P P
k k
200
183
161
F F F F
70
72.5
45 81 90 45
166 81
160 530
4- Φ 13
Fan aperture
680.5
2- Φ 35 knock-out
D 45
WI/DL
Φ40
80
WO/LL P
F F
140
IRWI k k
143
81
72.5
45 45
72.5
70 2- Φ 64 knock-out 75 103.5
120 730
4- Φ 13 knock-out
45
F F
2- Φ 35 knock-out
80 148
80
Φ 50 45
WI/DL Φ 40
F
WO/LL/D WI/DL/IRWI WO/LL F
187.8
160
160
230
k k k k P
70
70
50
45 50
123 80 4- Φ 64 knock-out
817.9
F F F F
8- Φ13
Fan aperture Fan aperture Fan aperture
593
2- Φ 35 knock-out 70
2- Φ 35 knock-out
80 45 45
160
F WO/LL/D WI/DL/IRWI WO/LL WI/DL P
143 80
F 90 Φ 40
WO/LL WI/DL
230
P Φ40
160
140
k k k k k k
81
F F
70
70
45
72.5
45 45 72.5
50
70 6- Φ 64 knock-out 50 75 103.5
123 80 80 148
Fixing plates
Figure 2-28 Compressor fixing plates
After the installation and before the commissioning, remove the three fixing plates, then restore the washers and bolts.
The fastening torque of the bolts is (12 ± 1)N.m.
Removing transport fastener of fan compoents
1. Upflow unit
The motor base of the fan is designed with a semi-free self-tension structure to minimize the fan operation noise and
prolong the belt life. During the transportation, to protect the semi-free structure from failing or collapsing due to
resonation, the upflow unit is especially fastened with bolts (left and right symmetrical, two at either side), as shown in
Figure 2-29. You should cut the binding string on the belt and remove the four fixing bolts before the power-on
operation, otherwise the fan could be damaged and even cause personal injury. Removing the bolts requires the
collaboration of two persons, with one holding the motor and the other removing the bolts.
Note
After you open the front door of unit, you will see a warning label concerning bolt removal on the sealing panel of the fan. Do
remove the bolts by following the preceding instructions.
Transportation bolts
(two on either side)
Binding string
Figure 2-29 Fixed bolts and trap wrench of transport fan components
2. Downflow unit
During the transportation, some cushion foam is inserted into the triangle formed by the motor base and the fan.
Remove the foam before the power-on operation.
Warning
Never put hands into the triangle gap between the motor base and fan.
ti on
ec
g dir
in
ov Bolts
R em
Fastener 1
2. Remove two bolts and then fastener 1 along the arrow direction, as shown in Figure 2-30.
3. Remove two bolts shown in Figure 2-31. Pull out the barb gently and then remove the fastener 2 along the arrow
direction, as shown in Figure 2-31.
Barb
Fastener 2
Bolts Fastener 2
g
vin
e mo ion
R ect
dir
45m
m
Figure 2-32 Water level regulator adjustment
This chapter introduces the electrical installation of the Liebert.PEX series air conditioner, which includes work
introduction, installation notes, wiring of indoor unit, connecting power cables for outdoor unit and installation
inspection.
电源接口
Power interface
Control
控制接口 interface N/PEN/PE端子排
terminal block
电源接口
Power interface
Control
控制接口 interface N/PEN/PE端子排
terminal block
Note
The two-bay single system has only one compressor MCB and contactor.
Power
Power interface
电源接口 supply interface
控制接口
Control interface P/NN/PE端子排
N/PE terminalblock
terminal block
Cable clamp
N PE
N PE
L1 L2 L3
Figure 3-4 Amplified figure of power supply interface Figure 3-5 Cable clamp
Note
The cable sizes should meet the local wiring rules.
Model Upflow air-cooled series UA Upflow water-cooled series UW Downflow air-cooled series FA Downflow water-cooled series FW
1020 23.1 23.1 23.1 23.1
1025 25.2 25.2 25.2 25.2
1030 30.4 30.4 30.4 30.4
1035 32.3 32.3 32.3 32.3
2040 42.9 42.9 42.9 42.9
2045 48.5 48.5 48.5 48.5
2050 47.1 47.1 47.1 47.1
2055 53.5 53.5 53.5 53.5
2060 57.5 57.5 57.5 57.5
2070 61.3 61.3 61.3 61.3
3080 71.9 71.9 71.9 71.9
3090 77.7 77.7 77.7 77.7
3100 87.7 87.7 87.7 87.7
41 43 83 88 89 75 76 94 95 96 97 91 92 93 80 81 11 12 77 78 72 73
41 43 83 88 89 75 76 94 95 96 97 91 92 93 80 81 11 12 77 78 72 73
Note
The wiring personnel must take antistatic measures before wiring the control cables.
Water-under-floor sensor
Every unit is supplied with one water sensor. You should connect one end of the sensor to terminal 51, and the other
end to the common terminal 24. The number of sensors in parallel connection is not limited, but there is only one water
alarm for each unit.
Remote shutdown
Terminals 37 and 38 can be connected to the remote shutdown switch. By default, terminals 37 and 38 are shorted.
Remove the shorting wire if remote shutdown is needed. When terminals 37 and 38 are open, the system is shut down.
Terminals 37C, 38C, 37B and 38B are series connected between terminals 37 and 38 (the connecting wire is user
self-prepared), so that you can series connect three remote shutdown devices.
Smoke sensor
The smoke sensor can be connected to terminals 91, 92 and 93, with 91 being the common terminal, 92 being the NO
contact, and 93 the NC contact. You can select NO or NC contact according to the smoke sensor logic.
Terminals 80 and 81 are used to output external alarms for the smoke sensor.
This chapter introduces the power-on commissioning and function test of air-cooled series and water-cooled series,
including the preparation before commissioning and commissioning procedures.
66 55 44 33 22 11
77
66 55 4 33 2 11
77
Note
The two-bay single system has only one compressor MCB and one compressor contactor.
66 55 4 33 2 1
1: Compressor MCB 3: Electrical heater MCB 5: Outdoor unit (air-cooled) MCB 7: Main isolation switch
2: Fan MCB 4: Infrared humidifier MCB 6: Control board MCB
Note
After the test, restore the temperature and humidity settings to the defaults or the original settings.
5. Pump the cooling system vacuum to -30in.Hg (pumping time: >3hrs), and hold the state for 4hr. The pressure
should not rise, and the sight glass appears green (to make sure the cooling system vacuum and dry, pump the
cooling system repeatedly at least three times).
After checking the vacuum state of the cooling system, pump in proper amount of liquid refrigerant quickly before the
power-on (usually pump until the pressures inside the refrigerant container equalizes with that in the cooling system).
Connect the composite pressure gauge to the interface on the high/low pressure needle valve.
Connect the composite pressure gauge to the refrigerant cylinder. Note to exhaust the air inside the tube of the gauge.
1) Change the temperature setting to start cooling, or start cooling manually. Make sure the dehumidification and hot
gas bypass valve is closed. Measure in real time all the phase currents of the compressor.
To start cooling (start the compressor), you should:
Change the temperature setting (see 5.7 SERVICE MENUS) to 41°F lower than the indoor temperature. The control
system should then trigger the cooling demand, and the compressor starts to work. After at least three minutes of
cooling, change the temperature setting to 41°F higher than the indoor temperature. If the compressor stops working
then, it means the cooling function is normal.
Note
After the test, restore the temperature setting to the default or the original setting.
2) Check and confirm the working current of the condenser fan. Make sure the fan runs stably.
3) Start the compressor, and charge refrigerant gas (R22) or refrigerant liquid (R407C) slowly to the compressor inlet
until the subcooling degree reaches 5K (or 8K ~ 10K) and the sight glass contains no air bulbs.
The condensing temperature should be kept at 113°F.
Keep charging and adjust the thermostatic expansion valve to 41°F ~ 46.4°F superheat degree. The adjustment step
of the valve should be smaller than 1/4 round, and the interval between two steps should be at least 15min.
Observe the compressor suction pipes and make sure there is no water condensing on the surface of the compressor
and the pipes, so as to avoid the risk of slugging the compressor.
At the return of 71.6°F/50%, 16Bar ~ 17Bar condensing pressure, the compressor suction pressure should be above 5
Bar.
At the return of 75.2°F/50%, 16Bar ~ 17Bar condensing pressure, he compressor suction pressure should be above
5.5Bar.
4) Check the dehumidification function
To trigger dehumidification, you should:
Change the humidify setting (see 5.7 SERVICE MENUS) to 10% lower than the indoor RH. The control system
should then trigger the call for dehumidification, the dehumidification solenoid valve switches on, and the
dehumidification indicator Q3 on the control panel turns on. Then change the humidity setting higher than the indoor
RH. If the dehumidification solenoid valve switches off, and the dehumidification indicator Q3 turns off, it means the
dehumidification function is normal. Note that during the commissioning process, if the indoor temperature is 37.4°F
higher than the temperature setting, the system may enter the forced cooling mode, and the dehumidification demand
will not be responded.
Note
After the test, restore the humidity setting to the default or the original setting.
Note
After the test, restore the temperature setting to the default or the original setting.
5. Switch on the humidification MCB and change the humidity setting to start the humidifier, or start the humidifier
manually. Measure all the phase currents of the humidifier. Manually charge water into the cooling system to check
that the charge-/drainage-pipes do not leak and the drainage pipes are clear.
To trigger the humidifier, you should:
Adjust the humidity setting (see 5.7 SERVICE MENUS) to 10% higher than the indoor Relative Humidity (RH). The
control system should then trigger the call for humidification, and the humidifier starts to work. If the humidifier stops
working when the humidity setting is lower than the indoor RH, it means the humidifying function is normal.
Note
After the test, restore the humidity setting to the default or the original setting.
6. The condensing temperature should be kept at 113°F.
Change the temperature setting to start cooling, or start cooling manually. Make sure the dehumidification and hot gas
bypass valve are closed. Measure in real time all the phase currents of the compressor.
Check the condensation subcooling degree, suction superheating and air bulbs of the sight glass to make sure the
compressor works normally, and add refrigerant if necessary.
To start cooling (start the compressor), you should:
Change the temperature setting (see 5.7 SERVICE MENUS) to 41°F lower than the indoor temperature. The control
system should then trigger the call for cooling, and the compressor starts to work. After at least 3min of cooling,
change the temperature setting to 41°F higher than the indoor temperature. If the compressor stops working then, it
means the cooling function is normal.
7. Check the dehumidification function
To trigger dehumidification, you should:
Change the humidify setting (see 5.7 SERVICE MENUS) to 10% lower than the indoor RH. The control system
should then trigger the call for dehumidification, the dehumidification solenoid valve switches on, and the
dehumidification indicator Q3 on the control panel turns on. Then change the humidity setting higher than the indoor
RH. If the dehumidification solenoid valve switches off, and the dehumidification indicator Q3 turns off, it means the
dehumidification function is normal. Note that during the commissioning process, if the indoor temperature is 37.4°F
higher than the temperature setting, the system may enter the forced cooling mode, and the dehumidification demand
will not be responded.
Note
After the test, restore the humidity setting to the default or the original setting.
The iCOM controller adopts menu operation. It can monitor, display and operate the precision cooling air conditioner
unit and control the environment temperature within a set temperature range.
This chapter introduces the menu operation of iCOM controller, control features and parameter settings.
5.1 LCD
An LCD is located on the front panel of the Liebert.PEX series air conditioner. The LCD can display the current state of
the equipment room, such as temperature and humidity. You can read and modify the parameter settings through the
LCD.
The LCD uses blue back lighting. If no button is pressed within a certain period of time (settable; by default: 5min), the
back lighting will be off, until the next time any button is pressed.
Operation indicator
Escape Help Down
button button button
Figure 5-1 Buttons and indicators of controller
1. Alarm indicator
The alarm indicator is off during normal operation. It turns on in red only upon alarms.
2. Operation indicator
The operation indicator is on in green when the air conditioner is operating; or turns when air conditioner unit is shut
down, the operation indicator will be on in yellow.
3. ON/OFF button
Function one: switch on/off the system.
Press the ON/OFF button to shut down an operating system, or to start an idle system.
Note
After the system is powered on, the system will assume the operation state before the power-off. For example, if the system is in
the work state when powered off, it will enter the work state automatically after power on.
Function two: test the operation indicator and the back lighting of the LCD.
After power-on, when the system is in the standby state (or test state as defined in this manual), pressing the ON/OFF
button will switch between the indicator (green then) and the LCD backlight. This function is used to test whether or not
the LCD backlight and the operation indicator is normal.
Note
The settings of the system when the system is in the test state will not be written into the microprocessor.
4. Enter button
Function one: enter the selected menu, or save the setting after parameters are changed. When you are entering a
menu or changing a parameter, the menu and the parameter will be high lighted.
Function two: test the display of characters.
When the system is in the test state, pressing the enter button will display the ASCII code. This function is used to test
whether or not the characters are displayed normally on the LCD.
5. Escape button
Function one: quit the current menu.
Function two: abolish the current change of parameter.
Function three: test the LCD high light.
Pressing the escape button to switch the LCD between light and high light when the system is in the test state. This
function can test whether or not the LCD high light is normal.
6. Up button
Function one: increase the value of the displayed parameter during parameter setting.
Function two: scroll a row or a screen up in the query state.
Function three: test the buzzer.
Pressing the up button when the system is in the test state will increase the buzzing frequency (initial value: 0%).
Meanwhile the buzzer will sound at the set frequency. This function is used to test whether or not the buzzer is normal.
7. Down button
Function one: decrease the value of the displayed parameter during parameter setting.
Function two: scroll a row or a screen down in the query state.
Function three: test the buzzer.
If the buzzer frequency is not 0%, pressing the down button when the system is in the test state will decrease the
buzzing frequency. Meanwhile the buzzer will sound at the set frequency. This function is used to test whether or not
the buzzer is normal.
8. Left button
Function one: select the left bit during the parameter setting operation.
Function two: test the LCD contrast.
Pressing the left button when the system is in the test state will decrease the LCD contrast (by default: 100%). This
function is used to test whether or not the LCD contrast is normal.
9. Right button
Function one: select the right bit during the parameter setting operation.
Function two: test the LCD contrast.
If the LCD contrast is not 100%, pressing the right button when the system is in the test state will increase the LCD
contrast. This function is used to test whether or not the LCD contrast is normal.
10. Alarm silence button
Function one: silence the alarm sound that is raised upon system alarms.
Function two: clear the current alarm after the alarm sound is silenced.
Function three: test the alarm indicator, and rest the LCD contrast and buzzer frequency.
Pressing the alarm silence button when the system is in the test state will switch the alarm indicator between on and
off. It can test whether or not the alarm indicator is normal. Meanwhile, the LCD contrast and buzzer frequency will be
reset to their defaults.
11. Help button
Function one: display the online help.
Function two: test the yellow display of the LCD operation indicator.
When the system is in the test state, pressing the help button will switch on and off the LCD operation indicator. This
function is used to test whether or not the yellow display of the LCD operation indicator is normal.
UNIT 1 SYS ON
20℃ 42% Setting value
32℃ 43% RC T Present value
UNIT 1 SYS ON
20℃ 42% Setting value
32 ℃ 43% RCT Present value
100% 0%
100% 0%
0% 0%
0%
The detailed icon meanings of graphical mode and simple mode on main interface are listed in Table 5-1.
Table 5-1 Meanings of icons
Icon Meaning Icon Meaning
Fan running Natural cooling
Cooling Maintenance
Hot water heating Dehumidifying
5.6.1 PASSWORD
The password is necessary for some settings. After inputting the password (user password: 149), use the up button
and down button to browse all the options, and press the enter button to enter the submenu.
5.6.2 SETPOINTS
The setpoints are saved as permanent memory. You can enter to query and set parameters in the ‘SETPOINTS’
submenu through the USER MENUS. The left row displays the parameter codes; the middle row, the parameter name;
the right row, the settings, as shown in Table 5-2.
Table 5-2 Descriptions of SETPOINTS submenu parameters
Parameters Default Setting range Description
U102 TEMP SET 73°F 41°F ~ 104°F Temperature setpoint
U103 HUM SET 50% 1% ~ 80% Humidity setpoint
Pred (predictive), comp
U104 HUM CTRL Pred Humidity control type
(compensable), rel (relative)
U105 SUP LIM Dsabl Dsabl, enabl Air temperature limit enable type
U106 SUP TEMP 59°F 41°F ~ 77°F Air temperature limit setting value
U107 BACK TSP 59°F 41°F ~ 104°F Backup temperature setpoints
If you want to modify the preceding settings, you should input the password before entering the submenu
‘SETPOINTS’. Then press the enter button to highlight the menu and use the up or down button to scroll the
parameters. Press the enter button to select one parameter, use the up or down button to set the value, and press the
enter button to save the change.
EVENT LOG P 0 01
(01)1/31/2007 10 : 00
Warning
Power loss
The EVENT LOG submenu saves the last 400 system records. The event types include message, warning and alarm.
When the event type is message, the LCD will display the event name only.
When the event type is warning, the LCD will display the event name and the alarm indicator will turn on in red.
When the event type is alarm, the LCD will display the event name, the alarm indicator will turn on in red, and an
audible alarm will be raised.
5.6.4 GRAPHICS
The GRAPHICS submenu provides two kinds of graphs: the RETURN TEMP and the RETURN HUMIDITY. These
graphs reflect the temperature and humidity changes over a period of time in the past.
In the graphs, the current temperature or humidity is the origin, the time is the horizontal axis, and the temperature or
humidity is the vertical axis, as shown in Figure 5-7.
As the horizontal axis, the time range can be set into eight kinds. Each pixel indicates different time in different time
ranges. See Table 5-3 for the detailed time range.
Table 5-3 Time range
Time range Time indicated by each pixel Time range Time indicated by each pixel
8min 6s 2 days 36min
32min 24s 4 days 72min
1hr 45s 8 days 144min
12hr 9min 16 days 288min
24hr 18min
The scaling of the vertical axis can also be set. For the RETURN TEMP, the scaling range is ±3 ~ ±20; for the
RETURN HUMIDITY, the scaling range is ±10 ~ ±30. The bigger the scaling range is, the bigger the value each pixel
indicates will be, and the more centered the curves will be.
You can set the parameters without inputting the password. Press the enter button to highlight the parameters, use the
up or down button to select one parameter. Then press the enter button again to enter the parameter, and use the up
or down button to set the value. Press the enter button to save the change at last.
Note
The system defaults are not recommended to be changed. If you consider it necessary to change the defaults, consult with
professionals first and set the alarm settings under the guidance of them.
To browse through the submenu, press the enter button to highlight the parameters, and use the up or down button to
scroll.
Password is required for changing the settings. Then, enter the ‘SET ALARMS’ submenu, press the enter button to
highlight the parameters, use the up or down button to select one parameter, and press the enter button to enter the
selected parameter. Use the up or down button to change the setting, and press the enter button to save the change,
or press the ESC button the quit the change.
Note
There is no need to reset the timers unless the components are replaced.
The parameters on this submenu are described in Table 5-7. The ‘LIMIT’ under the component name is the run time
limit of the corresponding component.
Table 5-7 TOTAL RUN HRS parameter description
Parameters Default Related equipment Parameter Default Related equipment
U502 MOTOR(S) 0hr U507 EL HEAT1 0hr
Fan motor Electric reheat 1
U502 LIMIT 32000hr U507 LIMIT 32000hr
U503 COMP1 0hr U508 EL HEAT2 0hr
Compressor 1 Electric reheat 2
U503 LIMIT 32000hr U508 LIMIT 32000hr
U504 COMP2 0hr U509 EL HEAT3 0hr
Compressor 2 Electric reheat 3
U504 LIMIT 32000hr U509 LIMIT 32000hr
U505 CW/FC 0hr Chilled water / free U510 HUM 0hr
Humidifier
U505 LIMIT 32000hr cool U510 LIMIT 32000hr
U506 HG / HW 0hr U511 DEHUM 0hr
Hot Gas/ Hot water Dehumidification
U506 LIMIT 32000hr U511 LIMIT 32000hr
5.7.2 SETPOINTS
Different from the SETPOINTS in the USER MENUS, the SETPOINTS in SERVICE MENUS has many more
parameters. See Table 5-9 for the parameter descriptions.
Table 5-9 SETPOINTS parameter description
Parameters Default Setting range Description
S102 TEMP SET 66°F 41°F ~ 104°F Temperature setpoint
S103 CTRL TYPE PI Prop, PI, PID, intel Control type selection
S104 TEMP PB 7k 1k ~ 30k Temperature proportional band, or the P in PID control
S105 TEMP INT min - Temperature integration time, or the I in PID control
S106 TEMP DER s - Temperature derivative time, or the D in PID control
S107 AUTOSET Yes Yes, no Autoset enable
S108 TEMP DB 32°F 32°F ~ 68°F Temperature deadband setting range
S109 2ND SETP 73°F 41°F ~ 104°F -
5.7.3 STANDBY
The parameters of the STANDBY submenu are described in Table 5-10.
Table 5-10 STANDBY parameters description
Parameters Default Setting range Description
S502 #STANDBY 1 0 ~ 32 Number of standby units
Rotation frequency. Range:
Daily: rotate once a day.
Daily, MON ~ MON ~ SUN: rotate once a week. The rotation occurs on Monday ~
SUN, M - Sunday of the week. For example, MON means rotation occurs on
S503 ROTATION Daily
MON ~ M - Monday of every week.
SUN M - MON ~ M - SUN: rotate once a month. The rotation occurs on
Monday ~ Sunday of the first week of the month. For example, M –
MON means rotation occurs on Monday of the first week of every month
S504 ROT HOUR hr - Used to set hour of the detailed time while rotation
S505 ROT MIN min - Used to set minute of the detailed time while rotation
S506 ROT BY 1 1~8 The unit number for rotation
S507 DO ROT No Yes, no Perform one rotation
CO/HE, yes, Cascade selection. The ‘Yes’ correspond to temperature and humidity control
S508 CASCADE No
no and ‘no’ corresponds to closing the cascade
S509 STBY HT No Yes, no Start all standby units by HT
5.7.4 WELLNESS
The controller calculates the bonus and penalty over the equipment maintenance based on the parameters in the
WELLNESS submenu and the equipment operation log, so as to find out the next system maintenance time.
Informing the maintenance personnel of the maintenance time makes the system run in the optimal mode, which
reduces the chances of faults and raises the system reliability.
The WELLNESS submenu includes nine groups of parameters, including the WELL BASICs and WELLNESS COMPs.
See Table 5-11 ~ Table 5-19 for details.
WELLNESS BASIC1
WELLNESS BASIC2
WELLNESS MOTOR
WELLNESS COMP1
WELLNESS COMP2
WELLNESS HEAT1
WELLNESS HEAT2
WELLNESS HEAT3
WELLNESS HUM
5.7.5 DIAGNOSTICS
The DIAGNOSTICS submenu is classified into two groups. After entering the menu, pressing the up button and down
button can switch between two groups and pressing the enter button can enter into the options of each group. Some
parameters of DIAGNOSTICS submenu are settable and used to help the maintenance personnel to start and cut off
devices by hand on site, realizing the diagnosis for devices. The other ones are only readable and they can only reflect
the fault condition of the devices. See Table 5-20 for details.
Table 5-20 DIAGNOSTICS submenu
Parameters Default Description
S302 HP1 CODE 0 HP 1 alarm counter. This parameter can be reset to 0
S303 HP2 CODE 0 HP 2 alarm counter. This parameter can be reset to 0
S304 HT1 CNT 0 HT 1 Alarm counter. This parameter can be reset to 0
S305 HT2 CNT 0 HT 2 Alarm counter. This parameter can be reset to 0
S306 LP1 CODE 0 LP 1 alarm counter. This parameter can be reset to 0
S307 LP2 CODE 0 LP 2 alarm counter. This parameter can be reset to 0
S308 LP1 ACT br Actual LP 1
Manual on/off control of compressor 2. Range: On, Off. Note that the On setting of this
S308 COMP2 Off
parameter can start compressor 1 only when the fan has been started
S309 LP2 ACT br Actual LP 2
S310 HP1 ACT br Actual HP 1
S311 HP2 ACT br Actual HP 2
S313 MANUAL No Manual equipment on/off control. Range: Yes, No
S314 MOTOR(S) On Manual on/off control of the fan motor. Range: On, Off
Manual on/off control of compressor 1. Range: On, Off. Note that the On setting of this
S315 COMP1 Off
parameter can start compressor 1 only when the fan has been started
S315 C1 MODE Run Compressor 1 mode. Range: Run, Evac (evacuate), Charg (charge)
S316 C1 CAP Off Refrigeration capacity of digital scroll compressor 1
S317 C1 CYCLE 0% Cycle of digital scroll compressor 1
S318 LLSV 1 Off Diagnostic of liquid line solenoid valve of compressor 1. Range: On, Off
S319 C2 MODE Run Compressor 2 mode. Range: Run, Evac, Charg
S320 C2 CAP Off Refrigeration capacity of digital scroll compressor 2
S321 C2 CYCLE % Cycle of digital scroll compressor 2
S322 LLSV2 Off Diagnostic of liquid line solenoid valve of compressor 2. Range: On, Off
Diagnostic of electric reheat 1. Range: On, Off. The On setting of this parameter can
S324 EL HEAT1 Off
start electric reheat 1 only when the air loss is normal
Diagnostic of electric reheat 2. Range: On, Off. The On setting of this parameter can
S325 EL HEAT2 Off
start electric reheat 1 only when the air loss is normal
Diagnostic of electric reheat 3. Range: On, Off. The On setting of this parameter can
S326 EL HEAT3 Off
start electric reheat 1 only when the air loss is normal
S327 DEHUM Off Dehumidification. Range: On, Off
S328 LWD Val - -
S329 HUM FILL Off Diagnostic of solenoid valve of water supply to the humidifier. Range: On, Off
Diagnostic of humidifier. Range: On, Off. The On setting of this parameter can start
S330 HUM Off
electric reheat 1 only when the air loss is normal
S331 H DRAIN - -
S332 HUM.C. 0.00A Electric current of humidifier
CUST IN1, CUST IN2, CUST IN3 and CUST IN4 can be set to 21 types of input. See Table 5-22 for details.
Table 5-22 Customer input types
Types Description Types Description Types Description
SMOKE Smoke alarm HUM Humidifier lockout En FC Enable FC
WATER Water alarm RH+HU Rht + Hum lockout RJVFD HTRJ VFD
C PMP Cooling pump alarm COMP Compressor lockout RJTVS HTRJ TVSS
FLOW Insufficient water alarm Call Call service Fire Fire Alarm
G PMP Standby pump alarm Temp High temperature alarm 2.Set 2nd Setpoint
STBY Standby unit alarm Air Air loss NoP No Power
C-In1 Customized alarm 1 FC L. FC lockout LSI LSI
C-In2 Customized alarm 2 HeatA Heater alarm Cnd1 Cond 1 Fail
C-In3 Customized alarm 3 FLOSD Flow AL SD Cnd2 Cond 2 Fail
C-In4 Customized alarm 4 FLOLC Flow AL LC
RHT Reheater lockout ComPD Comp Lock PD
C1 ACT, C2 ACT, C3 ACT and C4 ACT correspond to the customer alarms. OPEN means normally open, CLOSE
means normally closed.
Setting alarm delays
The alarm delays are the time after faults occur and before the alarms are triggered. See Figure 5-9 for the menu
format.
SET ALARMS 2 / 9 01
DEL EN T
S225 FOL 5 Yes ALM
S226 LOA 3 Yes ALM
S227 CF 2 Yes WRN
S228 HRT 30 Yes WRN
S229 LRT 30 Yes WRN
S230 HRH 30 Yes WRN
The alarm name, delay time, delay enabling and alarm type are displayed from left to right in the list.
The alarm delay can be set to 0 ~ 9999. Unit: second.
The delay enabling determines whether or not the delay will be valid. Options include yes and no.
The alarm type can be set to ALM (alarm), WRN (warning) and MSG (message). They determine the alarm degree of
the corresponding event.
The alarm names are listed in Table 5-23.
Table 5-23 Alarm description
Alarm/event Alarm/event
SN Description SN Description
name name
S225 FOL Fan overload S253 WUF Water under floor
S226 LOA Loss of airflow S254 CPH Conderser pump high water
S227 CF Filter clogged S255 LOF Loss of flow
S228 HRT High room temp. S256 SGP Standby glycol pump on
S229 LRT Low room temp. S257 STB Standby unit on
S230 HRH High room hum. S258 HUP Humidifier problem
S231 LRH Low room hum. S259 NOC No connection w/Unit1
S232 HTA High temperature sensor A S260 - Unit X disconnected
S233 LTA Low temperature sensor A S261 LOP Loss of power
S234 HHA High humidity sensor A S264 CI1 Customer input 1
S235 LHA Low humidity sensor A S265 CI2 Customer input 2
S238 OL1 Compressor 1 overload S266 CI3 Customer input 3
S239 OL2 Compressor 2 overload S267 CI4 Customer input 4
S240 HP1 Compressor 1 high pressure S268 CS Call service
S241 HP2 Compressor 2 high pressure S269 HTD High temperature
S242 LP1 Compressor 1 low pressure S270 LB1 Loss of air blower 2
S243 LP2 Compressor 2 low pressure S271 RL Reheat lockout
S244 PD1 Compressor 1 pumpdown fail S272 HL Humidifier lockout
S245 PD2 Compressor 2 pumpdown fail S273 FCL FC lockout
Alarm/event Alarm/event
SN Description SN Description
name name
S246 HT1 Digital scroll 1 high temperature S274 CL Compressor(s) lockout
S247 HT2 Digital scroll 2 high temperature S277 SC1 -
S248 EHO EL heat high temperature S278 SC2 -
S251 WHE Working hours exceeded S279 NOP -
S252 SMO Smoke detected S280 CN1 -
5.7.7 CALIBRATION
The CALIBRATION submenu can calibrate sensors by setting offsets. The parameters are listed in Table 5-24. The
parameters are in pairs: the former is the calibrated value, the latter is the calculated value, or the sum of the
measured value and the calibrated value. This value is engaged in the calculation of control need.
Table 5-24 CALIBRATION parameter description
Parameters Default Description
Calibrated return temperature. It can be set as a negative value. Use the up/down button
S602 RTN TEMP K
the change the setting, 0.01K at each step
Sum of calibrated value and measured return temperature. This value is compared with
S603 CAL TEMP 75.6°F
the setting as the system actual temperature and is engaged in the calculation
Calibrated return humidity. It can be set as a negative value. Use the up/down button the
S604 RTN HUM +0.0%
change the setting, 1% at each step
Sum of calibrated value and measured return humidity. This value is compared with the
S605 CAL HUM 39.5%
setting as the system actual humidity and is engaged in the calculation
Calibrated digital scroll 1NTC. It can be set as a negative or positive value. Use the
S606 DS1 NTC +0.0K
up/down button the change the setting, 0.1K at each step
Sum of calibrated value and return humidity measured by digital scroll 1NTC sensor. This
S607 CAL DS1 84°F
value is engaged in the calculation
Calibrated digital scroll 2NTC. It can be set as a negative or positive value. Use the
S608 DS2 NTC +0.0K
up/down button the change the setting, 0.1K at each step
Sum of calibrated value and return humidity measured by digital scroll 2NTC sensor. This
S609 CAL DS2 84°F
value is engaged in the calculation
S613 TEMP A +0.0K Calibrated value of temperature sensor A
S614 CAL A °F Calculated value corresponding to temperature sensor A
S615 HUM A +0.0% Calibrated value of humidity sensor A
S616 CAL A % Calculated value corresponding to humidity sensor A
S617 TEMP B +0.0K Calibrated value of temperature sensor B
S618 CAL B °F Calculated value corresponding to temperature sensor B
S619 HUM B +0.0% Calibrated value of humidity sensor B
S620 CAL B % Calculated value corresponding to humidity sensor B
Free cooling temperature sensor. PTC or NTC sensor can be configured according to the
S624 FC SNSR -
actual configuration
S625 FC SNSR °F Calibrated value of free cooling temperature sensor
S626 CAL FC °F Calculated value of free cooling temperature sensor
S627 SUP SNSR NTC Air supply temperature sensor. PTC or NTC sensor can be configured
S628 SUP TEMP +0K Calibrated value of air supply temperature sensor
S629 CAL SUP °F Calculated value of air supply temperature sensor
S630 TEMP C +0K Calibrated value of temperature sensor C
S631 CAL C °F Calculated value of temperature sensor C
S632 HUM C +0.0% Calibrated value of humidity sensor C
S633 CAL C % Calculated value of humidity sensor C
Other settings
This chapter introduces the application of the host communication component INTELLISLOT, including the
introduction, installation and commissioning of the host communication card.
调试口 port
Console
Network 网口
port
调试口 port
Console
RS485口
485 port
Bolts
Communication card
Installation box 1
Installation box 2
Connection
The electrical schematic figure of the host communication configuration is shown in Figure 6-4. P61, P65 and P67
cables have been connected in factory. So you should only connect the communication card to the monitoring center.
Communication
P61 cable
P65
Monitoring center
485 or TCP/IP communication card
Intellislot
P67
Note
Before commissioning, you must access into the ‘SERVICE Menus’ of the iCOM control board to set S824 MON ADD as ‘3’,
S835 MON PORT as ‘Vlcty(Velocity)’ and S843 BL CTRL as ‘S+R’.
tt
2. In the Connect To dialog box, choose the serial port being used (such as ‘COM1’), and click the OK button, as
shown in Figure 6-6.
3. Set the communication parameters as shown in Figure 6-7 and click the OK button.
4. Type ‘1’ and select Modbus protocol, the following figure will appear.
5. Type ‘3’ and select the ID used to communicate between the communication card and the host, the following figure
will appear.
6. Type the server ID under the command prompt, as shown in the following figure.
8. Type ‘1’, ‘2’ or ‘3’ to select the baud rate, and the following figure will appear.
9. Press the ESC button to exit to return the main interface. If you type ‘x’, the setting can be saved. After saving, the
485 communication card will be restarted.
10. On the main interface, typing ‘4’ can view whether the communication status between the communication card and
the Liebert.PEX series air conditioner is normal, as shown in the following figure.
4. Press ESC button to return the main interface, as shown in the following figure. If you type ‘x’, the setting can be
saved. After saving, the TCP/IP communication card will be started.
5. On the main interface, typing ‘5’ can view whether the communication status between the communication card and
the Liebert.PEX series air conditioner is normal, as shown in the following figure.
Complete
After normal communication, the interface will appear as shown in Figure 6-9.
2. Click the configure tab to enter the configuration interface, as shown in Figure 6-10.
3. Click the Access on SNMP at the left hand of the interface, as shown in Figure 6-11. Type user name ‘Liebert’ and
password ‘Liebert’ and click the OK button to enter the setting interface of configure. Note that the user name and
password are case-sensitive.
Connect to
Username
Password
OK Cancel
4. Configure the Network Management System (NMS) of the host monitoring center in Figure 6-12. Click the Edit
button and type the IP address of the NMS in IP Address. Select the ‘read’ or ‘write’, type ‘Public’ in Community and
then click the Save button.
Note
1. Before setting the NMS, the Edit button is displayed in the interface. After editing the configuration, the Edit button will
become the Save button.
2. After the NMS is configured, you must click the Save button to save the setting.
Figure 6-12 NMS configuration interface of SNMP host monitoring center (1)
5. Unfold the SNMP at the left hand of the interface shown in figure 6-13 and click Traps to set IP Address, Port and
Community of the NMS for receiving Traps. After modifying, you must click Save to save the setting.
Figure 6-13 NMS configuration interface of SNMP host monitoring center (2)
Network cable
connection
AC n TCP/IP card
Note
The single unit does not need HUB.
The networking figure of the 485 communication card (Modbus protocol) is shown in Figure 6-15. Up to 32 air
conditioner units can be connected.
485 connection
AC 1 485 card
485 connection
AC 32 485 card
This chapter introduces the operation and maintenance of the Liebert.PEX series air conditioner.
Note
1. During the operation of the Liebert.PEX system, lethal voltage may be present in the internal parts. It is a must to obey all the
notes and warnings marked on the equipment or contained in this manual, otherwise injury or fatality may occur.
2. Only qualified maintenance and repairing personnel can operate and process the system.
8. Check the specification and aging situation of the control cable and power cable between the indoor unit and the
condenser, and replace the cable when necessary.
9. Use temperature/humidity measuring meter with high precision to proof-read and calibrate the temperature/humidity
sensor. Note to set the humidity control mode to RH control during the process of calibration.
10. Check the following external sensors.
1) Smoke detector (optional)
The power supply of the smoke detector is located at the bottom (or top) of the upflow (or downflow) unit. It
incessantly samples the air, analyzes the samples and makes judgment. It requires no calibration.
2) Water leak detector
The water leak detector has a dry contactor. The contactor will close when the detector probes detect water or
other conductive liquid.
The detector should be placed away from any water pool or drainage trench on the floor, 2m ~ 2.5m away from the
machine. Do not place it directly under the machine. The recommended location for the water leak detector is
shown in Figure 7-1.
Liebert system
Location of leak
detection sensor
Location of leak
detection sensor
Note
1. Before connecting any mechanical parts or cables, make sure the power supply of the control unit has been disconnected.
2. Do not use the water leak detector adjacent to flammable liquid or use it to detect flammable liquid.
11. Adjust the set points. Check the auto-flush control logic and HG bypass logic of water pan of the infrared humidifier
and the action of the functional parts according to control logic.
12. Simulate the fault scenario to check the work state of protection devices including high/low voltage alarm, high/low
temperature alarm, high/low water level alarm and over-temperature protection device.
过滤网堵塞开关调节旋钮
Rotary switch for filter
clogging switch
Filter过滤网堵塞开关
clogging switch
风机气流安全开关
Pressure difference
switch
Power off before replacing the filter. You need to adjust the setting point of the filter clogging switch if the new filter is of
a different model. The filter clogging switch is located in the electric control box. It samples the air pressures before
and behind the filter through a black hose, and decides the output after comparing the two values.
To adjust the setting point of the filter clogging switch, you should:
1. After replacing the filter, restore and seal all the panels, so that the alarm point can be found precisely.
2. Keep the fan running, and rotate the rotary switch of the filter clogging switch counter clockwise until the filter alarm
is triggered.
3. Rotate the rotary switch clockwise for 2.5 rounds, or rotate it according to the new filter’s model.
Note
1. Set the setting point properly. Otherwise, the filter alarm may be triggered too frequently; or, in the opposite case, the dust
accumulation on the filter could not trigger the alarm, endangering the system operation due to deteriorated ventilation.
2. If you are unsure about the setting point, consult with Emerson before using a filter of a different model to replace the old one.
7.3.2 Belt
Measure the belt tension with a tension meter. You can also press down the belt at the middle point between the two
pulleys. The displacement should be 0.5” ~ 1”.
If the belt is found worn out or distorted, replace it with a new belt. The new belt should be of the same model as the
old one.
7.3.3 Motor
To replace the failed motor, you need to be very careful, especially with the upflow unit. Use a dedicated fixture to hold
the motor before removing the fixing bolts at the bottom of the motor.
Note
Before removing the water pan, make sure that the power has been cut off, and the water in the water pan is not too hot.
The autoflush function of the humidifier can prolong the cleansing cycle. However, timed check and maintenance are
indispensable.
Replacing the lamps of the humidifier
The lamp of the infrared humidifier is shown in Figure 7-3. Follow the procedures below to replace it.
Fixing screw of
ceramic socket
Ceramic socket Lamp supporting bracket Lamp supporting bracket
7. Remove the screws that fix the cables of the lamp to be replaced from the ceramic sockets (note to hold the lamp
with hand).
8. Pull down the lamp.
9. Install a new lamp.
Note
Do not touch the quartz lamp with bare hands! Greasy sediment and finger prints can seriously shorten the life span of quartz
lamps. Therefore, put on clean cotton gloves during the operation.
Note
The normal operation of the autoflush system, the humidifier demands a water source with minimum water flow of 1gpm (0.063
l/s) and minimum pressure of 20 psig (138kPa).
HMV pre-fill
On in last No
Call for humidification
15 hours? IFS: 30s
IFL: 60s
Yes
Humidification
lamps only refill
8min: IFS 110% ~ 500%
10min: IFL
Note
1. Before delivery, the refrigerant of water-cooled unit has been charged, and the expansion valve has been adjusted. If you need
to adjust the expansion valve, please contact Emerson.
2. Every time you rotate the rotary switch, do not rotate it for more than one round, and it may take up to 30mins to reach a new
balance.
Compressor
Condenser
Figure 7-6 Hot gas bypass
The control logic of the hot gas bypass is shown in Figure 7-7.
Compressor off Compressor on
0% 50 % 100% + Temperature
Setpoint
Figure 7-7 Control logic of hot gas bypass
7.6.6 Liquid Line Bypass Solenoid Valve (For Water-cooled Series Only, Compressor-on Bypass)
The water-cooled series uses the Plate Heat Exchanger (PHE) as its condenser. Thanks to the high efficiency and
compact structure of the PHE, the volume of PHE is small, as compared to the air-cooled condenser. Before the
power-on, the PHE could be the coldest part in the system, and partial coolant would move to the PHE. Upon system
power-on, the system high pressure would soon reach the system HP protection point, and trigger the protection. The
liquid line bypass solenoid valve is designed to bypass the coolant upon system power-on, as shown in Figure 7-8.
The valve is normally off. It turns on when the compressor starts upon system power-on. The lead-time before the
bypass and the bypass time are settable.
Dehumidification
solenoid valve Evaporator
HG
bypass valve Expansion
valve
Bypass
Compressor solenoid
valve
Water outlet
When the system demands cooling, while the compressor fails to start after frequent on-off (within 10 min, after three
on-offs, HP alarm still occurs upon the forth on) due to the high pressure, make sure the bypass valve is on. If the
bypass valve is on while the compressor still cannot start, check whether or not the temperature of the water input to
the PHE is within the stipulated range.
To raise the condensing pressure, turn the square adjusting screw counter clockwise to the desired setting.
Function test
Shut down the cooling system first. After 5mins ~ 10mins, the water flow should stop. If the water flow does not stop, it
means the valve setting is improper, or the connection between the pressure sensitive capillary tubes and the
condenser is incorrect.
Warning
No direct contact between the refrigerant or lubricant and the skin when replacing the compressor, or serious burning or frostbite
may occur. Put on gloves with long sleeves when processing polluted parts.
The Liebert.PEX system uses the highly reliable Copeland scroll compressor. If handled properly, the failure rate is
extremely low.
It is rare for the motor of the compressor to get burned due to short circuit. In the few cases when the motor does get
burned, the cause is usually mechanical or due to poor lubrication, in other words, due to over-temperature.
If the causes that lead to the compressor failure could be discovered and corrected in time, most failures are avoidable.
The maintenance personnel should check the operation situation periodically and take necessary measures to ensure
the system normal operation. This practice is both easy and cost saving, when you compare it with replacing the
compressor upon faults that result from negligence.
When diagnosing the compressor, check the operation situation of all the electric parts of the compressor.
1. Check all the fuses and circuit breakers.
2. Check the operation of HP and LP switches.
3. When the compressor is faulty, find out the nature of the cause: is it an electrical fault or a mechanical fault?
For mechanical faults
Upon a mechanical fault, there is no burned smell. You should try spinning the motor. If the fault is proved to be
mechanical, the compressor has to be replaced. If the motor is burned, you should remove the fault that leads to the
burning of the motor and clean the system. It must be pointed out that the compressor motor is usually burned
because the system is not cleaned properly.
For electric faults
You can tell an electric fault by the unpleasant smell. If serious burning occurred, the lubricant will appear black and
become acid. When electric fault occurs and the compressor motor is entirely burned, the system must be cleaned to
remove the acid material from the system and to avoid such faults in the future.
Note
The damage to the compressor components due to improper way of cleaning is classified in the warranty agreement as improper
usage of the product, thus is not covered by the warranty.
When the compressor is entirely burned, you need to replace the filter drier together with the compressor. In addition,
check the expansion valve. If the valve is faulty, replace it too. Before the replacement, you must clean the system. If
you are unsure about the cleaning method, please consult with Emerson service personnel.
Compressor replacing procedures
1. Cut off the power supply.
2. Connect the LP and HP tubes of the pressure gauge to the needle valves of the suction and exhaustion pipes
respectively to recycle the refrigerant.
Note
The refrigerant must be recycled or disposed in accordance with the local regulations. Discharging the refrigerant into the air is
harmful to the environment and illegal.
6. If the compressor has been entirely burned, you need to clean the pipes of the cooling system and replace the filter
drier.
Note
Do not remove the rubber covers from the suction opening and exhaust opening of the new compressor too early. The time that
the openings are exposed to the air should not exceed 15mins so as to prevent the compressor refrigeration oil from absorbing
water and bringing the water into the system.
7. Install the new compressor, and connect the pipes and electric cables.
8. Pump the system vacuum and add refrigerant in accordance with the commissioning regulations.
9. Power on the system by following the ordinary startup commissioning procedures and check the system operation
parameters. Observe the refrigerant state through the sight glass, and determine the amount of refrigerant to be added
by considering the system pressure and temperature until the system enters normal operation.
Chapter 8 Troubleshooting
This chapter introduces the troubleshooting. You can read this part by referring to the part concerning the alarms.
Caution
1. Certain circuits carry lethal voltages. Only professional technicians are allowed to maintain the machine.
2. Extra care should be taken when troubleshooting online.
Note
If jumpers are used for troubleshooting, remember to remove the jumpers after the troubleshooting, or the connected jumpers
may bypass certain control function and become a potential risk to the equipment.
Signature: _________________________________________________________
Note: copy this table for filing.
Heating system
Air-cooled condenser (if used)
___ 1. Check the re-heater operation
___ 1. Check the fins cleanness
___ 2. Check the erosion situation of the
___ 2. The fan base should be firm
components
___ 3. The fan vibration absorber is not deteriorated
___ 3. Check and fasten the circuit connections
or damaged
___ 4. The SPD board should be effective (in the
storming seasons, the SPD board should be check Infrared humidifier
once a week) ___ 1. Check clogging of the drain pipes
___ 5. Check the voltage regulating function of the ___ 2. Check the lamps of the humidifier
rotation speed controller ___ 3. Check the mineral sediments on the water
___ 6. The temperature switch is set at the required pan
position ___ 4. Check and fasten the circuit connections
___ 7. The refrigerant pipes are properly supported
___ 8. Check and fasten the circuit connections Electric control part
___ 1. Check the fuses and MCB
Water-cooled condenser (if used) ___ 2. Check and fasten the circuit connections
___ 1. Clean the water pipe system ___ 3. Check the control program
___ 2. Check the water flow regulating valve ___ 4. Check the contactor action
Signature _________________________________________________________
Note: copy this table for filing.
99 21
A
A处 19
19
20 20
20
21
22
22
Amplified figure of A
A处放大
10 11 12
13 1314
12 14 15 16 1718
17 18
8 7
6 65 455 34 3
2 2 11
99 21
21
A
A处
22
22
10
10 11 12 13 14
14 15 16 17 18
17 18
19
19
20 20
Amplified
A处放大figure of A
Note
The two-bay single system has only one compressor MCB and contactor.
1: Compressor MCB 7: Control board MCB 13: N/PE terminal block 19: Main N terminal
2: Busbar 8: Fuse board 14: Humidifier contactor 20: Main grounding terminal
3: Fan MCB 9: Control board 15: Electric reheat contactor 21: Fan contactor
4: Electric reheat MCB 10: Control terminal block 16: Fan over-current protector 22: Temp./hum. sensor board
5: Infrared humidifier MCB 11: Power transformer 17: Compressor contactor
6: Outdoor unit (air-cooled) MCB 12: Isolation transformer 18: Main isolation switch
8 7
67 566 545 4
34 233 22 11
21
21
99 A
A处
22
22
10
10 11
11 12
12 13 1415
23 14 15 16
16 17 18
17 18
19
19
20 20
Amplified
A处放大 figure of A
1: Compressor MCB 7: Control board MCB 13: N/PE terminal block 19: Main N terminal
2: Busbar 8: Fuse board 14: Humidifier contactor 20: Main grounding terminal
3: Fan MCB 9: Control board 15: Electric reheat contactor 21: Fan contactor
4: Electric reheat MCB 10: Control terminal block 16: Fan over-current protector 22: Temp./hum. sensor board
5: Infrared humidifier MCB 11: Power transformer 17: Compressor contactor
6: Outdoor unit (air-cooled) MCB 12: Isolation transformer 18: Main isolation switch
8 7 6 5 4 3 2 1
NOTES
LINE L1 Y 1. ALL FIELD WIRING TO BE PER LOCAL CODES. USE COPPER CONDUCTORS ONLY.
SEE UNIT NAMEPLATE
VOLTAGE UNIT DISPLAY 65-1 12-1 R 42 ANALOG 67-1
FOR MAIN SUPPLY 66-1 2. FAN MOTOR OVERLOAD SYSTEM DEPENDENT ON FAN MOTOR MANUFACTURER,
3 PHASE L2 GN UNIT ALARM INTELLISLOT 1 INPUTS #1 TH/HU CONTROL VOLTAGE OVERLOAD SYSTEM SHOWN IN SHADED AREAS,
WIRE SIZING SUPPLY 65-4 INTELLISLOT 12-2 BK 67-6
66-6 41 LINE VOLTAGE OVERLOAD SYSTEM SHOWN IN BOXED AREA.
L3 R T1 POWER SUPPLY
T8 24V P64 WIRES INCLUDED ON 3. LLBP IS ONLY FOR WATER COOLED UNIT WITH BRASED PLATE HEAT EXCHANGER
FACTORY MOUNTED MAIN UNIT SWITCH 64-1 LARGE DISPLAY ONLY INTELLISLOT
61-1 12-5 R 44 ANALOG LLBP
INTELLISLOT 2
5 64-8 INPUTS #2 5 4. JUMPER TO BE REMOVED WHEN OPTIONAL COMPONENT IS USED.
EARTH EARTH GROUND CONNECTION 61-8 12-6 BK 43
CP 5. OPTIONAL SMOKE DETECTOR: TERMINALS SUPPLIED IN FIELD WIRING
COMPARTMENT FOR REMOTE INDICATION. FIELD TO CONNECT 24V MAX.
NEUTRAL
4-1 R 4-1 24-2 24-1 E-1 BK E1 6. OPTIONAL MAIN FAN AUXILIARY SIDE SWITCH: TERMINALS LOCATED IN FIELD D
T2 WIRING COMPARTMENT FOR REMOTE INDICATION. FIELD TO CONNECT 24V MAX.
D 4-2 R 4-2 44-2 R 44-1 41-1 OR R 41-3 42-1 E2
E5 7. OPTIONAL EMERGENCY POWER LOCKOUT OF REHEAT AND/OR HUMIDIFIER:
4-3 R 4-3 PCB CONTROL FUSES 43-1 R 43-1 E3 CONNECTIONS PROVIDED FOR REMOTE 24V AC SOURCE.
10 70 GN/Y 10 8. OPTIONAL CONDENSATE PUMP ALARM RELAY TERMINALS LOCATED IN WIRING
77 R 4-4 R 4-4 41-2 OR R 41-4 42-2 E4
W/OR 65-2 COMPARTMENT FOR REMOTE INDICATION.
SEE NOTE 13 78 HEAT REJECTION 71 5C1 43-2 R 43-2 K3
OR 65-1 DEVICE BR 23,23 9. HGBP1 IS STANDARD CONFIGURATION FOR SINGLE SYS UNITS.HGBP ARE
CONNECTION OPTIONAL FOR DOUBLE SYS UNITS
40-10
REMOVE FOR EXTRA RSD TERMINALS
10. LLSV IS ONLY OPTIONAL FOR LONG PIPE APPLICATION AS ONE OF THE
70A OR OR SEE NOTE 4
58 R U23 40-11 40-9 COMPONENTS OF EXTENSION KITS
REMOTE LIQUITECT P 37C RSD3 38C 37B RSD2 38B 37 RSD1 38 HMV
INDICATOR 2LQR 5C2 Q6 HMV HMV 11. k11 RELAY CONTACTS HAVE SEPARATE TERMINALS MARKED 72 AND 73 ON DUAL
59 71A 39-1 OR 39-2 39-3 OR 39-4 35-3 R R 35-4
P BR COOL K11
15 HWA Q5 FC-C FC FC-NO 15
SEE NOTE 12 8-7 R R 8-5 U20 36-1 OR OR 36-2 U21 12. A DUAL HEAT REJECTION DIVICE APPLY TO DOUBLE SYS UNITS
NEED TO
82 OR OR
P EM1 43,49 TERMINAL 70 AND 71
CONNECT 70 TO 70A AND TO CONNECT 71 TO 71A
4MF1 4MF2 4MF3
SEE NOTE 7 ARE USED OR 70A AND 71A ARE USED
83 OR OR OR OR 36-6 U22
P 72 13. OPTIONAL SITESCAN SYETEM KIT, CONNECT AT TERMINALS 77 AND 78
R
OL1
MFAS SEE NOTE 11 K11
73 40-12 OR 40-13 36-3 BR MF1 OR 36-8 17,19,66,67,68
BR
84 P REMOVE WIRES WHEN R3 IS PRESENT
SEE NOTE 6 BR BR OL2 NOMENCLATURE
20 85 P 1-4 MF2 20 STANDARD DEVICES LINE STANDARD DEVICES LINE
L3 L2 L1 1LQR 1CPAR 17,19,66,67,68
24 RAD1 50 38-3
97 U16 BR BR AS - AIR SAFETY SWITCH 37
P 8-6 R OR 8-1 OL3
2CPAR 40-2
3R3 51 SEE NOTE 4 MF3 17,19,66,67,68 C1 - COMPRESSOR CONTACTOR 1 72
88 P 96 40-1 WUF BR 8-2 U17 Q18 - LIQUID LINE BYPASS1 TRIAC
SEE NOTE 8 P K3 C2 - COMPRESSOR CONTACTOR 2
CPSS 55 40-4 K3 61 / CGV ACTUATOR CLOSING TRIAC 30
89 P 95 40-3 P P OR 8-3 U18 40-15 40-13 40-14 OR R3
P 22,24,27
40-6 CCH1 - CRANKCASE HEATER NO.1 38
COMMON ALARM 2R3 56 SEE NOTE 2
94 40-5 4RH1 OR RS1,2,3 - REHEAT SAFETY STATS
C SDT CONNECTION P CCH2 - CRANKCASE HEATER NO.2 39 41 C
BR BR 8-4 U19 40-7 INCLUDED WITH R3
25 80 BR OR 1-8 25 DHV - DE HUMIDIFICATION VALVE RH1 - REHEAT STAGE 1 CONTACTOR 41
4RH2 44
SEE NOTE5 76 SDT
81 BR OR BR BR BR DLT1 - DISCHARGE LINE TH - TEMPERATURE SENSOR 2
40-8 TEMPERATURE SWITCH 68
75 1R3 R LQR R 14,21 T1 - UNIT CONTROL TRANSFORMER 4
ALL FIELD WIRING SEE NOTE 1 OR DLT2 - DISCHARGE LINE 57
P CPAR P 21,22 TEMPERATURE SWITCH T2 - ISOLATION TRANSFORMER 8
38-1 R FC - FILTER CLOG SWITCH 15
LLBP1
U1-U30 - OPTO ISOLATORS
LLBP1
CUSTOMER CONNECTIONS ALSO SEE LINES 2,3,5,14,21,22,23,24,29,31,32,33,36,45,51,54,64,66 GN/Y SD H - HUMIDIFIER CONTACTOR 47 WUF - WATER UNDER FLOOR 22
LLBP1 R SDT BK
Q18 LLBP1 1 5 50 24 90 G5 BR 38-2
30 LLBP1 30 HGBP1-HOT GAS BYPASS 1(single sys) 67
52-5 22-1 BR BR 22-5 3 93
EARTH GROUND CONNECTION BR 1 R 93 OPTIONAL DEVICES LINE
Q17 LLBP2 5 2 HMV - HUMIDIFIER MAKE-UP VALVE 14
BL 52-1 LLBP2 2 92
22-3 R R 22-2 OR RESET OR 92 SEE NOTE 1&5 ELECTRIC REHEAT
LLBP2 6 3 HP1 - HIGH PRESSURE SWITCH NO.1 70
REMOTE CONDENSER 1,2 R 91 BR - BACKUP REHEAT CONTACTOR 36
52-2 22-6 LLBP2 LLBP2 22-4 4 BR 91
GN/Y BR SDC HP2 - HIGH PRESSURE SWITCH NO.2 59
52-3 CT - CURRENT TRANSFORMER 55
L1 52-4 HS1 - AUTO RESET TEMPERATURE
SAFETY SWITCH 41
53-2 53-3 53-5 SEE NOTE 3 RH2 - REHEAT STAGE 2 CONTACTOR 43
53-1 53-4
RC1,2 L2 HS3 - MANUAL RESET HUMIDIFIER
35 54-2 54-3 54-5 35 48 ECON-O-CYCLE
54-1 54-4 SAFETY(UNDER PAN)
K11 - ECON-O-COIL RELAY 64
L3 HU - HUMIDITY SENSOR ECON-O-COIL
R BR 2
MISCELLANEOUS
AS-C AS AS-NO 24DH 24DG
36-4 BR 34-12
HWA - HIGH WATER ALARM 15 CP - CONDENSATE PUMP 5
CCH1 4C1 R 36-7 R R R 34-3 34-1 R 34-2
BK 24H GCD 24G
R R AS-NC K3 - COMMON ALARM RELAY 24V, CPAR - CONDENSATE PUMP ALARM 28
OR 36-5 U15 1.0A MAX CONTACT LOAD 11
CCH2 4C2 RELAY
R R BK OPTIONAL WITH GCD
CPSS - CONDENSATE PUMP SAFETY 23
40 INFRARED HUMIDIFIER RS1 RS2 RS3 LLBP1 - LIQUID LINE BYPASS 1 30 SWITCH
B RS1 RS1 RS2 RS3 40 B
RS1 HS1
RS1 HS1-4 HUM-S1 1H RS1 RS2 RS3 SEE NOTE 4 LLBP2 - LIQUID LINE BYPASS 2
R L1 31 EM1 - EMERGENCY POWER 16
A HS1-2 7-1 LOCKOUT RELAY
Q1 LP1 - LOW PRESSURE SWITCH NO.1
RS2 RS2 HS1-1 HUM-S2 2H 34-4 R RH1 34-5 34-11 OR OR 34-10 25,56,57,58 70
R L2 7-2 GCD - GROUNDED CURRENT 37
RS2 B HS1-3 LP2 - LOW PRESSURE SWITCH NO.2 DETECTOR
3H RS4 RS4 RS4
RS5 RS5
RS6 RS6 1EM1 59
RS3 HUM-S3
RS3 R L3 Q2 RS5 RS6 MF1 - MAIN FAN CONTACTOR NO.1
C 34-6 R RH2 RS4 34-7 26,61,62,63 18 HGBP1 - HOT GAS BYPASS 1(dual sys) 67
1-3 Q3 MF2 - MAIN FAN CONTACTOR NO.2 20
BR DHV DHV BR HGBP2 - HOT GAS BYPASS 2(dual sys) 55
45 34-8 34-9 45
COMPRESSOR NO.1 1 CP1 1C1 C1AUX 35-7 V DHV MF3 - MAIN FAN CONTACTOR NO.3 22
DH LQR - LIQUITECT SHUTDOWN RELAY 26
Y L1
GN/Y Q1 - REHEAT STAGE 1 TRIAC
2C1 51-1 41 LLSV1 - LIQUID LINE SOLENOID 1 65
GN L2 Q4 HUM-A1 Q2 - REHEAT STAGE 2 TRIAC 43
51-2 HUM-A2 LLSV2 - LIQUID LINE SOLENOID 2 52
35-1 BR H BR 35-2 35-6 R R R 41,42,43
3C1 SEE NOTE 4 35-5
HS3 Q3 - DEHUMIDIFICATION TRIAC 44
R L3 51-3 LPT1 - LOWPRESSURE TRANSDUCER1 68
HS3 2EM1 Q4 - HUMIDIFICATION TRIAC 47
COMPRESSOR NO.2 CP2 1C2 C2AUX 51-5 1-7 LPT2 - LOWPRESSURE TRANSDUCER2 58
50 Y L1 Q5 - MAIN FAN TRIAC 15
50 MFAS - MAIN FAN AUXILIARY SIDE 19
2C2 LLSV2 51-4
LLSV2 Q6 - HUMIDIFIER MAKE-UP TRIAC 14 SWITCH
GN L2 GN/Y LLSV2
Q8 LLSV2 LLSV2 Q8 - LIQUID LINE SOLENOID 2 TRIAC 52 R3 - EXTRA COMMON ALARM 24V, 23
3C2 32-3 BR BR 33-3 3.0A MAX CONTACT LOAD
R L3 Q9 - HOT GAS BYPASS 2 TRIAC 55
SEE NOTE 10 RAD REMOTE ALARM DEVICE 21
Q10 - COMPRESSOR NO.2 TRIAC 61 (75VA MIN. RATING)
HGBP2 HGBP2
1 BAY REHEAT 2 USES CB OF REHEAT 1 GN/Y HGBP2
CT REHEAT 2 CB2 NOT FITTED Q12 - LIQUID LINE SOLENOID 1 TRIAC 65 RSD - REMOTE SHUTDOWN DEVICE 15
ELECTRIC REHEAT 1 Q9 HGBP2 HGBP2
55 1 2 33-4 BR BR 33-5 55 BY OTHERS (75VA MIN RATING)
1RH1 Q13 - HOT GAS BYPASS 1 TRIAC 67
OR L1 SEE NOTE 9 SD - SMOKE DETECTOR 30
A DLT2-COM DLT2 DLT2-NO Q14 - COMPRESSOR NO.1 TRIAC 72 A
2RH1 63 SDC - SMOKE DETECTOR CONTROL 33
OR L2 Q15 - NOT USED
HP2-NO SDT - SMOKE DETECTOR TROUBLE 30
1-2 BL 33-9 U26 11-5 R OR BR BK 11-6 Q17 - LIQUID LINE BYPASS 2 TRIAC
3RH1 31
HP2-COM HP2 LP2 LP2-NC
LPT2 / CGV ACTUATOR OPENING TRIAC
OR L3
32-5 W BL 33-8 U25 11-7 W R BR BK 11-8 WIRING LEGEND
BL 32-12
LP2-COM
( ) W - WHITE GY - GRAY
( ) BK GN/Y-INSUL ATION COLOR&TRACER COLOR GLOBAL PEX 50 Hz
8 7 6 5 4 3 2 1
FORM NO. 180205 REV 1
User Menus
SETPOINTS EVENT LOG GRAPHICS SET ALARMS SENSOR DATA DISPLAY SETUP TOTAL RUN HRS SLEEP MODE SERVICE INFO ACTIVE ALARMS
U102 TEMP SET U 202 RTN SNSR U 301 TEMP A U401 LANGUAGE U 502 MOTOR(S) U 602 MON
U103 HUM SET U 203 HI TEMP U302 HUM A U402 YEAR U502 LIMIT U 602 TUE
U104 HUM CTRL U 204 LO TEMP U303 TEMP B U402 MONTH U503 COMP1 U 602 WED
U105 SUP LIM U 205 HI HUM U304 HUM B U402 DAY U503 LIMIT U602 THU
U106 SUP TEMP U 206 LOW HUM U305 TEMP C U403 HOUR U504 COMP2 U602 FRI
U107 BACK TSP U 207 SENSOR A U306 HUM C U403 MINUTE U504 LIMIT U602 SAT
U 208 HI TEMPA U 307 FC TEMP U403 SECOND U505 CW/FC U 602 SUN
U 209 LO TEMPA U 308 AMB TEMP U404 TEMP F/C U505 LIMIT U 605 START 1
U211 LO HUM A U 310 DS1 TEMP U406 BUZ FREQ U506 LIMIT U605 STOP 1
U 311 DS2 TEMP U406 BUZ TEST U507 EL HEAT1 U605 STOP 1
U315 Hi Humi
U316 Lo Hu H
U 316 Lo Hu M
U 316 Lo Hu S
U 316 Lo Humi
SERVICE MENUS
SETPOINTS STANDBY SETTINGS WELLNESS BASIC1 DIAGNOSTICS SET ALARMS CALIBRATION NETWORK SETUP OPTIONS SETUP SERVICE INFO
S102 TEMP SET S502 #STANDBY S002 FREQ/YR S049 BEST S302 HP1 CODE S202 RTN SNSR S602 RTN TEMP S802 # UNITS S402 COMP SEQ
S103 CTRL TYP S503 ROTATION S003 BONUS S050 WORST S303 HP2 CODE S203 HI TEMP S603 CAL TEMP S803 TEAMWORK S403 LP DELAY
S104 TEMP PB S504 ROT HOUR S004 PENALTY S051 ALARMS S304 HT1 CNT S204 LO TEMP S604 RTN HUM S809 CS CTRL S404 LP1 ACT
S105 TEMP INT S505 ROT MIN S005 LAST PM S052 BONUS S305 HT2 CNT S205 HI HUM S605 CAL HUM S809 CS STAT S405 LP2 ACT
S106 TEMP DER S506 ROT BY S005 LAST PM S057 S306 LP1 CODE S206 LOW HUM S606 DS1 NTC S810 NW CTRL
STARTS S406 EL HEAT
S107 AUTOSET S507 DO ROT S005 LAST PM S058 S307 LP2 CODE S207 SENSOR A S607 CAL DS1
RUN HRS S810 NW STAT S407 HW HEAT
S108 TEMP DB S508 CASCADE S006 NAME S059 AVG RUN S313 MANUAL S208 HI TEMPA S608 DS2 NTC
S109 2ND SETP S509 STBY HT S007 CONFIRM S813 IP #1 S408 ALL HEAT
S060 S314 MOTOR(S) S209 LO TEMPA S609 CAL DS2
S110 BACK TSP BEST S813 IP #2 S409 LWDconn
S008 NEXT PM S315 COMP1 S210 HI HUM A
S113 HUM SET S061 WORST S613 TEMP A
S013 STARTS S315 C1 MODE S211 LO HUM A S813 IP #3 S410 3P RUN
S114 HUM CTRL S062 ALARMS S614 CAL A
S014 RUN HRS S316 C1 CAP S813 IP #4
S115 HUM PB S063 BONUS S213 CUST IN1 S615 HUM A S411 3P DIR
S015 AVG RUN S814 NM #1
S116 HUM INT S068 S317 C1 CYCLE S214 C1 ACT S616 CAL A S413 HUM ENAB
S016 BEST STARTS S814 NM #2
S117 HUM DB S318 LLSV 1 S215 CUST IN2 S617 TEMP B
S017 WORST S069 RUN HRS S814 NM #3 S414 IR FLUSH
S118 LO LIM 2 S319 COMP2 S216 C2 ACT S618
S018 ALARMS S070 AVG RUN CAL B S415 HUMSTEAM
S119 LO LIM 1 S319 C2 MODE S814 NM #4
S019 BONUS S071 BEST S217 CUST IN3 S619 HUM B
S124 SUP LIM S320 C2 CAP S815 GW #1 S416 HUM.TIME
S024 STARTS S072 WORST S218 C3 ACT S620 CAL B
S125 SUP TEMP S321 C2 CYCLE S815 GW #2 S417 HUM.MAN
S126 S025 RUN HRS S073 ALARMS S219 CUST IN4 S624 FC SNSR
AMB TYPE S322 LLSV 2 S418 DEHUM EN
S127 AMB DT S026 AVG RUN S074 BONUS S220 C4 ACT S625 FC SNSR S815 GW #3
S324 EL HEAT1
S128 FC TYPE S027 BEST S079 STARTS S221 WA AC AL S626 CAL FC S815 GW #4 S419 REST EN
S325 EL HEAT2
S129 FC DT S028 WORST S080 RUN HRS S222 AL.RES. S627 SUP SNSR S817 U2U PROT S420 RESTART
S326 EL HEAT3
S130 MIN CW S029 HP AL S081 AVG RUN S628 SUP TEMP S818 U2U ADD
S328 LWD Val S421 ONOFF EN
S131 MIN CW S030 S082 BEST
LP AL S329 HUM FILL S629 CAL SUP S819 U2U GRP S424 CW FLUSH
S135 FANSPEED S083
S031 OL AL WORST S330 HUM S630 TEMP C S821 BL CTRL
S136 VSD SET S425 FC FLUSH
S137 VSD MIN S032 DS HT AL S084 ALARMS H DRAIN
S331 S631 CAL C S821 BL STAT
S138 VSD DEH S033 BONUS S085 BONUS HUM.C. S426 HW FLUSH
S332 S632 HUM C S824 MON ADD
S139 VSD NOP S035 STARTS S333 LSI S427 BALL OFF
S633 CAL C S831 CS CTRL
S146 CTRLTYPE S036 RUN HRS S335 ALM REL
S147 CO1 ON S831 CS STAT
S037 AVG RUN S336 FC REL
S148 CO1 OFF S832 NW CTRL
S038 BEST S337 3P OPEN
S149 CO2 ON S832 NW STAT
S039 WORST S338 3P CLOSE
S150 CO2 OFF S835 MON PROT
S040 HP AL S340 BV CTRL
S151 CO1 TD S836 IP #1
S341 ANALOG1
S152 CO2 TD S041 LP AL ANALOG2
S342 S836 IP #2
S153 CYCLET S042 OL AL
S343 ANALOG3 S836 IP #3
S154 SCRFACT S043 DS HT AL
S155 ACT SCR S344 ANALOG4
S836 IP #4
S044 BONUS S345 RSD
S837 NM #1
S046 STARTS S346 AIR LOSS
S047 RUN HRS MOTOR OL S837 NM #2
S347
S048 AVG RUN S348 FILTER S837 NM #3
S349 CUSTOM 1 S837 NM #4
S350 CUSTOM 2 S838 GW #1
S351 CUSTOM 3 S838 GW #2
S352 CUSTOM 4 S838 GW #3
S353 HEAT SAF S838 GW #4
S354 FLOW AT S840 U2U PROT
S355 FLOW ACT S841 U2U ADD
HP1 S842 U2U GRP
S356
S843 BL CTRL
S357 LP1
S843 BL STAT
S358 C1 OL
S844 SR CTRL
S359 HP2 S844 SR STAT
S360 LP2
S361 C2 OL
S367 HUM PROB
S368 DT1
S369 DT2
S370 DT3
S371 MIN CW