4 essential ground-fault protective schemes you should know


about
Home / Technical Articles / 4 essential ground-fault protective schemes you should know about

Ground-fault & protection relaying


While ground-fault protective schemes may be elaborately developed, depending on the ingenuity of the
relaying engineer, nearly all schemes in common practice are based on one or more of the methods of
ground-fault detection discussed in this article.

Stop 📃
https://electrical-engineering-portal.com/ground-fault-protective-schemes#residually-connected-overcurrent-relays 1/16
11/3/2019 4 essential ground-fault protective schemes you should know about | EEP

4 essential ground-fault protective schemes you should know about

Distribution circuits that are solidly grounded or grounded through low impedance require fast clearing of
ground faults. This need for speed is especially true in low-voltage grounded wye circuits that are connected
to busways or long runs of metallic conduit.

The problem involves sensitivity in detecting low ground-fault currents as well as coordination between main
and feeder circuit protective devices.
Stop 📃
https://electrical-engineering-portal.com/ground-fault-protective-schemes#residually-connected-overcurrent-relays 2/16
11/3/2019 4 essential ground-fault protective schemes you should know about | EEP

This article is primarily directed to ground-fault protection of major portions of circuits and equipment.

The discussions relate to various forms of ground-fault protection to prevent excessive damage to electrical
equipment with current sensitivity in the order of amperes to hundreds of amperes.

Now, let’s talk a little bit about the these methods of ground-fault detection:

1. Residually connected overcurrent relays


2. Core balance sensing of feeder conductors
3. Detection of ground-return current in the equipment grounding circuit
4. Differential relaying

1. Residual connection

A residually connected ground relay is widely used to protect medium-voltage systems. The actual ground
current is measured by CTs that are interconnected in such a way that the ground relay responds to a
current proportional to the ground-fault current.

This scheme, using individual relays and CTs, is not often applied to low-voltage systems. However, low-
voltage systems are available with three CTs built into them and connected residually with the solid-state trip
devices to provide ground-fault protection.

The term residual in common usage is normally reserved for three-phase system connections and seldom
applied to single-phase or multiple-signal mixing.

The basic residual scheme is shown in Figure 1. Each phase relay is connected in the output circuit of its
respective CT, while a ground relay connected in the common or residual circuit measures the ground-fault
current.
Stop 📃
https://electrical-engineering-portal.com/ground-fault-protective-schemes#residually-connected-overcurrent-relays 3/16
11/3/2019 4 essential ground-fault protective schemes you should know about | EEP

Figure 1 – Residually connected ground relay

In three-phase three-wire systems, no current flows in the residual leg under normal conditions because the
resultant current of the three CTs is zero.

This situation is true for phase-to-phase short circuits also. When a ground-fault occurs, the short-circuit
current, returning through earth, bypasses the phase conductors and their CTs, and the resultant current
flows in the residual leg and operates its relay.

On four-wire circuits, a fourth CT should be connected in the neutral circuit as shown in the dashed portion
of the current. The neutral conductor carries both 60 Hz single-phase load unbalance current as well as
zero-sequence harmonic currents caused by the nonlinear inductance of single-phase loads, such as
fluorescent lighting.
Stop 📃
https://electrical-engineering-portal.com/ground-fault-protective-schemes#residually-connected-overcurrent-relays 4/16
11/3/2019 4 essential ground-fault protective schemes you should know about | EEP

Without the neutral-conductor CT, the current in that conductor would appear to the ground relay as ground-
fault current, and the ground relay would have to be desensitized sufficiently to prevent opening under
unbalanced load conditions.

The selectivity of residually connected relays is determined by the CT ratio and the relay pickup setting. The
CT ratio must be high enough for normal load circuits.

Also to be considered are the unbalanced primary currents in each phase, the sum of which may contain
sufficient asymmetrical current to cause a trip during a motor start.

For this reason, sensitive ground-fault protection schemes do not use instantaneous trips when a residually connected circuit is
involved. If ground-fault protection with greater sensitivity is needed, the core-balance method should be considered (see next paragraphs).

Go back to contents ↑

2. Core balance

The core-balance method is based on primary current phasor addition or flux summation. The remaining
zero-sequence component, if any, is then transformed to the secondary.

The core-balance CT or sensor is the basis of several low-voltage ground-fault protective systems.

The core-balance CT is frequently called a zero-sequence sensor or window CT, but the term core
balance is preferable because it more specifically describes the function of the CT.

The principle of the core-balance CT circuit is shown in Figure 2.

Stop 📃
https://electrical-engineering-portal.com/ground-fault-protective-schemes#residually-connected-overcurrent-relays 5/16
11/3/2019 4 essential ground-fault protective schemes you should know about | EEP

Figure 2 – Core-balance CT encircling


all phase and neutral conductors

All load-carrying conductors pass through the same opening in the CT and are surrounded by the same
magnetic core.

Core-balance CTs are available in several convenient shapes and sizes, including rectangular designs for
use over busbars.

Stop 📃
https://electrical-engineering-portal.com/ground-fault-protective-schemes#residually-connected-overcurrent-relays 6/16
11/3/2019 4 essential ground-fault protective schemes you should know about | EEP

This method can be more sensitive than the residual method because the sensor rating is large enough for the possible imbalance, not
for the individual conductor load current.

Core-balance CTs various sizes (photo credit: newelec.co.za)

Under normal conditions (i.e., balanced, unbalanced, or single-phase load currents or short circuits not
involving ground – if all conductors are properly enclosed), all current flows out and returns through the CT.
The net flux produced in the CT core is zero, and no current flows in the ground relay.
Stop 📃
https://electrical-engineering-portal.com/ground-fault-protective-schemes#residually-connected-overcurrent-relays 7/16
11/3/2019 4 essential ground-fault protective schemes you should know about | EEP

When a ground fault occurs, the ground-fault current returns through the equipment grounding circuit
conductor (and possibly other ground paths) and bypasses the CT. The flux produced in the CT core is
proportional to the ground-fault current, and a proportional current flows from the CT secondary to the relay
circuit.

Relays connected to core-balance CTs can be made quite sensitive. However, care is necessary to
prevent false opening from unbalanced inrush currents that may saturate the CT core or through faults not
involving ground.

If only phase conductors are enclosed and neutral current is not zero, the transformed current is proportional
to the load zero-sequence or neutral current.

Systems with grounded conductors, such as cable shielding, should have the CT surround only the phase
and neutral conductors, if applicable, and not the grounded conductor.

By properly matching the CT and relay, ground-fault detection can be made as sensitive as the application requires.

Stop 📃
https://electrical-engineering-portal.com/ground-fault-protective-schemes#residually-connected-overcurrent-relays 8/16
11/3/2019 4 essential ground-fault protective schemes you should know about | EEP

The speed of the relay limits damage and may be adjustable (for current or time, or both) in order to obtain
selectivity. Many ground protective systems now have solid-state relays specially designed to operate with
core-balance CTs. The relays in turn open the circuit protective device. Power circuit breakers, MCCBs with
shunt trips, or electrically operated fused switches can be used.

The last category includes service protectors, which use circuit breaker contacts and mechanisms, but
depend on current-limiting fuses to interrupt the high available short-circuit currents.

Fused contactors and combination motor starters may be used where the device-interrupting capability
equals or exceeds the available ground-fault current.

Stop 📃
https://electrical-engineering-portal.com/ground-fault-protective-schemes#residually-connected-overcurrent-relays 9/16
11/3/2019 4 essential ground-fault protective schemes you should know about | EEP

Figure 3 – Physical installation of a core-balanced CT for


shielded cable termination

Figure 3 shows a typical termination of a medium-voltage shielded cable. After the cable is pulled up
through the core-balance CT, the cable jacket is removed to expose the shielding tape or braid. Jumpering
the shields together, the connection to the ground is made after this shield lead is brought back through the
CT.

This precaution would have been necessary only if the shield had been pulled through the CT.

Stop 📃
https://electrical-engineering-portal.com/ground-fault-protective-schemes#residually-connected-overcurrent-relays 10/16
11/3/2019 4 essential ground-fault protective schemes you should know about | EEP

Between multiple shield ground connections on a single conductor cable, a potential exists that drives a
circulating current, often of such a magnitude as to require derating of the cable ampacity.

When applying the core-balance CT, the effects of this circulating current should be subtracted from the
measuring circuit.

Go back to contents ↑

3. Ground return

Ground-return relaying is illustrated in Figure 4. The ground-fault current returns through the CT in the
neutral-bus to ground-bus connection.

For feeder circuits, an insulating segment may be introduced in busway or conduit, as shown in Figure 4,
and a bonding jumper connected across the insulator to carry the ground-fault current. A CT enclosing this
jumper then detects a ground fault.

This method is not recommended for feeder circuits due to the likelihood of multiple ground-current return paths and the difficulty of
maintaining an insulated joint.

Stop 📃
https://electrical-engineering-portal.com/ground-fault-protective-schemes#residually-connected-overcurrent-relays 11/16
11/3/2019 4 essential ground-fault protective schemes you should know about | EEP

Figure 4 – Ground-return relay scheme

Go back to contents ↑

Stop 📃
https://electrical-engineering-portal.com/ground-fault-protective-schemes#residually-connected-overcurrent-relays 12/16
11/3/2019 4 essential ground-fault protective schemes you should know about | EEP

4. Ground differential

A generic term, ground differential is used for a variety of schemes that utilize phasor or algebraic
subtraction or addition of signals. The currents may be produced by any of the methods discussed in
sections 1 through 3.

Figure 5, for example, shows a ground differential protection for single-phase center-tapped loads and is
similar to the residual method.

Figure 5 – Differential protection center-tapped loads

One core-balance sensor could detect ground faults in a plurality of loads (see Figure 6). Ground-
differential relaying is effective for main bus protection because it has inherent selectivity.

Stop 📃
https://electrical-engineering-portal.com/ground-fault-protective-schemes#residually-connected-overcurrent-relays 13/16
11/3/2019 4 essential ground-fault protective schemes you should know about | EEP

Figure 6 – Differential protection multiple loads

With the differential scheme (see Figure 7), core-balance CTs are installed on each of the outgoing
feeders and another lower ratio CT is placed in the transformer neutral connection to ground.

This arrangement can be made sensitive to low ground-fault currents without false opening for ground
faults beyond the feeder CTs.

All CTs should be carefully matched to prevent improper opening for high-magnitude faults occurring outside
the differential zone.

Stop 📃
https://electrical-engineering-portal.com/ground-fault-protective-schemes#residually-connected-overcurrent-relays 14/16
11/3/2019 4 essential ground-fault protective schemes you should know about | EEP

Figure 7 – Ground-differential scheme bus and transformer

Bus-differential protection protects only the zone between CTs and does not provide backup protection for
feeder faults.

Go back to contents ↑

Circuit sensitivity

Factors that affect the sensitivity of ground-fault sensing include the following:

1. Circuit-charging current drawn by surge arrestors, shielded cables, and motor windings
2. The number of coordination steps between the branch circuit and the supply
Stop 📃
https://electrical-engineering-portal.com/ground-fault-protective-schemes#residually-connected-overcurrent-relays 15/16
11/3/2019 4 essential ground-fault protective schemes you should know about | EEP

3. Primary rating and accuracy of the largest CT used to supply residually connected relays in the
coordination
4. How well the CTs used for residually connected relays are matched
5. Burden on the CTs, in particular the burden of the residually connected relay (Solid-state and some
induction disk relays have burdens of 40 VA for a 0.1 A tap.)
6. Maximum through-fault current and its effect upon the CTs, with selected relays for phase and residual
connections
7. Fault contact resistance
8. Location of conductors within core-balance transformers

Go back to contents ↑

Reference // IEEE Recommended Practice for Protection and Coordination of Industrial and Commercial
Power Systems (IEEE Std 242)

Edvard Csanyi

Electrical engineer, programmer and founder of EEP. Highly specialized for design of LV/MV switchgears
and LV high power busbar trunking (<6300A) in power substations, commercial buildings and industry
facilities. Professional in AutoCAD programming.