1. Summary
Ventilation Sizing Method ASHRAE Std 62.1-2007
Design Condition Cooling operation
Occupant Diversity (D) 1.000
Uncorrected Outdoor Air Intake (Vou) 61 L/s
System Ventilation Efficiency (Ev) 1.000
Outdoor Air Intake (Vot) 61 L/s
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' GL Fast Fashion 6 '' IN ZONE '' Level Thirteen ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 34.8 °C / 27.2 °C HEATING OA DB / WB 20.6 °C / 14.2 °C
OCCUPIED T-STAT 23.9 °C OCCUPIED T-STAT 21.1 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 0 m² 0 - 0 m² 0 -
Roof Transmission 0 m² 0 - 0 m² 0 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 0 m² 0 - 0 m² 0 -
Partitions 80 m² 1335 - 80 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 1148 W 1148 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 2488 W 2488 - 0 0 -
People 10 785 757 0 0 0
Infiltration - 237 509 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 599 127 0% 0 0
>> Total Zone Loads - 6593 1392 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' GL Fast Fashion 6 '' IN ZONE '' Level Thirteen ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
0.016
2 0.012
5
34 0.010
0.008
0.006
0.004
0.002
0.000
0 5 10 15 20 25 30 35
Temperature ( °C )