Name of work :- Rectangular Sump freee board 0.50m , above GL 0.3 0.25 15.10 m 0.25
1 Tank size 15.10 x 11.33 x 6.30 m
2 Tank capacity 991843.5 ltr 0.266 m
3 Angle of repose 30 Degree Saturated soil unit wt 17.00 kN/m3
4 Conrete M 25 unit weight 25000 N/m3 8 mm f bars 10 mm f bars 40 mm
scbc 8.5 N/mm 2
m 11 70 mm c/c 10 mm f bars 20 mm
5 Steel fy 500 Tensile stress 130 N/mm 2
short span
0.266
6 Nominal Cover 30 mm Water unit wt 9.81 kN/m3 top roof
7 Thickness Walls 250 mm 0.25 m 20 mm f bars 11.33 m
Top roof 150 mm 15 cm 0.15 m 150 mm c/c 12 mm f bars 150 mm
Bottom slab 300 mm 0.30 m 10 mm f bars 200 mm
8 Depth of ground water from soil 1.00 m
Height of tank above Ground level 0.30 m
Saturated depth of soil 5.30
7 Reinforcement Wall 4.89 20 mm f bars 150 mm 4.89
Long out side vertical 20 mm F 150 mm c/c 2.65 m height
Out side vertical 20 mm F 300 mm c/c upto top 0.30
in side vertical 16 mm F 100 mm c/c 2.65 m height
in side vertical 16 mm F 200 mm c/c upto top Bottom slab steel detail
Distribution 8 mm F 150 mm c/c on each face
Short out side vertical 12 mm F 150 mm c/c 2.10 m height 0.25 16 mm f bars 250 mm c/c 0.25
Out side vertical 12 mm F 300 mm c/c upto top 8 mm f bars 150 mm c/c
in side vertical 12 mm F 150 mm c/c 2.10 m height 20 mm f bars 300 mm c/c
in side vertical 12 mm F 300 mm c/c upto top 4.20 m 16 mm f bars 250 mm c/c
Out side Horizontal 16 mm F 125 mm c/c 4.69 m height 12 mm f bars 300 mm c/c
Out side Horizontal 16 mm F 250 mm c/c upto top 16 mm f bars 200 mm c/c
In side Horizontal 16 mm F 125 mm c/c 4.69 m height 12 mm f bars 300 mm c/c
In side Horizontal 16 mm F 250 mm c/c upto top 12 mm f Bars 150 mm c/c
8 Roof 16 mm f bars 125 mm c/c
Main 10 mm F 20 mm c/c 2.10 m 16 mm f bars 100 mm c/c
Distribution 8 mm F 70 mm c/c 16 mm f bars 125 mm c/c
8 Base Main 20 mm F 150 mm c/c at the Bottom face 20 mm f bars 150 mm c/c
Main 12 mm F 150 mm c/c at the top face 12 mm f bars 150 mm c/c
Distribution 10 mm F 200 mm c/c
0.30
###
Solution, general:- There are four components of design.
(I) Design of long wall (II) Design of short wall
(III) Design of roof slab (IV) Design of base slab
The design of walls will be done under two condition.
(a) Tank full with water, with no earth fill out side.
(b) Tank empty, with full earth pressure due to saturated earth fill.
The base slab will be designed for uplift pressure and the hole tank is to be tasted against floatation. As the L/B ratio is
greater than 2 the long wall will be designed as cantilever. The bottom one metre ( >H /4) of short walls will be designed as cantilever
while the top portion will designed as slab supported by long walls .
5.30 5.30
Maximum B.M. at the base of wall = 51993 x x = 243413.895 N-m or 243413895 N-mm
2 3
350599269.375 350599269
Required depth = = 479 mm
1.530 x 1000
Provide total depth = 479 + 30 = 250 mm so that available d = 220 mm
350599269.375
Ast = = 14245 mm 2
130 x 0.861 x 220
3.14xdia 2
3.14 x 20 x 20
using 20 mm bars A = = = 314 mm2
4 x100 4 x 100
Spacing of Bars = 1000 x 314 / 14245 = 22 say = 150 mm
Hence Provided 20 mm F bar, @ 150 mm c/c on out side face, at bottom of long wall
Cutailment of reinfocrement. Since B.M. is proportional to h3, we have:
Asth h 3 Asth 1/3
= = From which h = H x
Ast H3 Ast
If Asth =1/2. Ast (i.e.half the bars being curtailed). H= H(1/2)'1/3 = 6.45 x( 0.5 )1/3 = 5.117 m
\ Height from the base = 6.45 - 5.117003 = 1.33 m However as per code requirement,
the bars are to be continued further for distance of 12 F = 12 x 20 = 240 mm or d = 220 mm,
whichever is more, beyond this point. Hence curtail half the bars at 1.33 + 0.6 = 2.20 m from base.
Similarly, depth where only 0.25% reinforcement is requiredd is h=H(0.25)1/3= 6.45 x( 0.25 )1/3= 4.06
\ Height from the base = 6.45 - 4.06 = 2.39 m However as per code requirement,
the bars are to be continued further for distance of 12 F = 12 x 20 = 240 mm or d = 220 mm,
whichever is more, beyond this point. Hence curtail half the bars at 2.39 + 0.22 = 2.65 m from base.
250 - 100
Minimum, % Reinforcement = 0.3 - 0.1 x = 0.2571 %
450 - 100
250 x 1000
Min = 0.257143 x = 643 mm2
100
This is < Than 0.25 % of Ast at bottom . O.K.
Hence the reinforcement will be provided as under,
(I) At base : 20 mm f bars @ 150 mm c/c
(II) At 2.20 m above base , up to top : 20 mm f bars @ 300 mm c/c
Distribution steel :-
250 - 100
% of distribution steel = 0.3 - 0.1 x = 0.257 %
450 - 100
250 x 1000
Astd = 0.257 x = 643 mm2, Area of each face = 321.5 mm2
100
3.14xdia2 3.14 x 8 x 8
using 8 mm bars A = = = 50.2 mm2
4 x100 4 x 100
Spacing of Bars = 1000 x 50.2 / 322 = 156 say = 150 mm
Hence Provided 8 mm F bar, @ 150 mm c/c on Each face,
1000 x 50.2
having, Ast = 2x = 670 mm2
150
Direct compression in long walls:- The earth pressure acting on short walls will cause compression
in long walls, because top portion of shorts walls act as slab supported on long walls
At h = 6.45 / 4 = 1.6125 or 1.61 m above the base of walls .
Pa=KaY' (H-h) + Yw (H-h) = 0.333 x 7190 x( 6.30 - 1.61 )+ 9810 x 4.69 = 57219
This direct compression devloped on long walls and wall section. N/m2
11.33
PLC =Pa.x B/2 57219 x = 324001 N
2
This will be well taken by distribution steel and wall section
(b) Tank full with water and no earth fill out side.
P = Y x wh = 9810 x 5.80 = 56898 N/m2
HxH 5.80 x 5.80
M=p x = 56898 x = 319008.12 N-m or 319008120 N-mm
2x3 2 x 3
319008120
Ast = = 12962 mm2
130 x 0.861 x 220
3.14xdia2 3.14 x 16 x 16
using 16 mm bars A = = = 201 mm2
4 x100 4 x 100
Spacing of Bars = 1000 x 201 / 12962 = 16 say = 100 mm
Hence Provided 16 mm F bar, @ 100 mm c/c at the in side face.
Curtailement of reinforcement:-
Asth h3 Asth 1/3
= = From which h = H x
Ast H3 Ast
If Asth =1/2. Ast (i.e.half the bars being curtailed). H= H(1/2)'1/3 = 5.80 x( 0.5 )1/3 = 4.601 m
\ Height from the base = 6.45 - 4.601336 = 1.85 m However as per code requirement,
the bars are to be continued further for distance of 12 F = 12 x 16 = 192 mm or d = 220 mm,
whichever is more, beyond this point. Hence curtail half the bars at 1.85 + 0.22 = 2.10 m from base.
Similarly, depth where only 0.25% reinforcement is requiredd is h=H(0.25)1/3= 6.45 x( 0.25 )1/3= 4.06
\ Height from the base = 6.45 - 4.06 = 2.39 m However as per code requirement,
the bars are to be continued further for distance of 12 F = 12 x 16 = 192 mm or d = 220 mm,
whichever is more, beyond this point. Hence curtail half the bars at 2.39 + 0.22 = 2.65 m from base.
250 - 100
Minimum, % Reinforcement = 0.3 - 0.1 x = 0.2571 %
450 - 100
250 x 1000
Min = 0.257143 x = 643 mm2
100
This is < Than 0.25 % of Ast at bottom . O.K.
Hence the reinforcement will be provid as under,
(I) At base : 16 mm f bars @ 100 mm c/c
(II) At 2.10 m above base , up to top : 16 mm f bars @ 200 mm c/c
Direct tensio on long wall:- Since the top portion of short wall act as slab supported on long walls,
the water pressure acting on short walls will cause in long walls.
B 11.33
PL= P x Where p= 9810 x = 55549.13 N/m2 at 1.61 m height
2 2
11.33
\ PL = 55549 x = 314546.9203 N, As required = 314546.9 / 130 = 2420 mm2
2
Area of distribution steel provided in horizontal direction = 670 mm2
Hece distribution steel will take direct tension.
### Design of short walls :-
(a) Tank empty, with pressure of satureted soil from outside.
(I)
Top Portion . The bottom 1.61 m act as cantilever, while the remaining 4.69 m
act as slab supported on long walls.
Pa = KaY' (H-h) + Yw (H-h) = 0.33 x 7190 x 4.84 + 9810 x 3.69 = 11594 + 36174.375
= 47768 N/m2
PaL2 47768 x 11.58 2
Mf (at supports ) = = = 533332 N-m (causing tension out side )
12 12
PaL2 PaL2 47768 x 11.58 2 N-m (causing tension in
M ( at centre ) = - Mf = = = 266666
8 24 24 side )
d = 250 - ( 30 + 16 ) = 204 mm
533332000
At Supports, Ast = = 23369 mm2
130 x 0.861 x 204
3.14xdia2 3.14 x 16 x 16
using 16 mm bars A = = = 201 mm2
4 x100 4 x 100
Spacing of Bars = 1000 x 201 / 23369 = 9 say =125 mm
Hence Provided 16 mm F bar, @ 125 mm c/c at the out side face at 4.69 m below the top
At mid span, Ast = 23369 x 0.5 = 11685 mm2 minimum Ast = 11684.5 mm2
3.14xdia2 3.14 x 16 x 16
using 16 mm bars A = = = 201 mm2
4 x100 4 x 100
Spacing of Bars = 1000 x 201 / 11685 = 17 say = 250 mm
Hence Provided 16 mm F bar, @ 250 mm c/c at inner side face
(III) Bottom portion The bottom 1.61 m will bend as cantilever.
Intensity of earth pressure at bottom = 67451.5 N/m2
1 1
\ M = x 67451.5 x 1 x = 11242 N-m
2 3 (with tension at out side face)
11242 x 1000
\ Ast = = 457 mm2
130 x 0.861 x 220
Minimum steel @ 0.257 % "= 643 mm2
3.14xdia2 3.14 x 12 x 12
using 12 mm bars A = = = 113 mm2
4 x100 4 x 100
Spacing of Bars = 1000 x 113 / 643 = 176 say = 150 mm
Hence Provided 12 mm F bar, @ 150 mm c/c at out side face, in vertical direction for
bottom 2.10 m height. The spacing can be doubled for upper portion.
(III) Direct compression in short walls:-
Though the long walls bend as cantilever, it is observed that end 2.10 metre
width of long wall contributes to push in short walla, due to earth pressure, and its magnitude is given by
PBC = Pa x 2 = 47768 x 2 = 100313 N
This is quite small, and hence its effect has not been considered.
(b) Tank full with water , and no earth fill out side.
(I) Top Portion . The bottom 1.61 m act as cantilever, while the remaining 4.69 m
act as slab supported on long walls.
p = w (H-h) = 9810 x( 5.80 - 1.61 )= 41079.375 N/m2
PB 2
41079.38 x 11.58 2
causing tension at
Mf (at supports ) = = = 458653.361 N-m
12 12 the inside
PB2 41079.38 x 11.58 2 causing tension at
Mc (At centre) = = = 229326.681 N-m
24 24 the outside
Direct tension in short wall:- Due to water pressure on the end 1.61 metre width of long wall is
pB = w (H-h) x1 = 9810 x( 5.80 - 1.61 )x 1.0 = 41079.375 N/m2
Effective d, for horizontal steel = 204 mm
\ Distance = (x - d ) x T / 2 = 204 - 250 / 2 = 79 mm
Mf - PB.x PB
Hence net B.M. = M - PB. x \ Ast1 = Ast2 =
sst,j.d ss
At inside face (end of short walls)
Mf - PB.x 458653 x 1000 - 41079.38 x 79
Ast1 = = = 19955 mm2
sst,j.d 130 x 0.861 x 204
PB 41079.38
Ast2 = = = 316 mm2 \ total Ast = 19955 + 316 = 20271 mm2
ss 130
3.14xdia2 3.14 x 16 x 16
using 16 mm bars A = = = 201 mm2
4 x100 4 x 100
Spacing of Bars = 1000 x 201 / 20271 = 10 say = 125 mm
Hence Provided 16 mm F bar, @ 125 mm c/c at the inner face,
At the out side face (middle of short walls)
Mc - PB.x 229327 x 1000 - 41079.38 x 79
Ast1 = = = 9906 mm2
sst , j . d 130 x 0.861 x 204
PB 41079.38
Ast2 = = = 316 mm2 \ total Ast = 9906 + 316 = 10222 mm2
ss 130
Minimum reinforcement required = 10222 mm2
3.14xdia2 3.14 x 16 x 16
using 16 mm bars A = = = 201 mm2
4 x100 4 x 100
Spacing of Bars = 1000 x 201 / 10222 = 20 say = 250 mm
Hence Provided 16 mm F bar, @ 250 mm c/c at the outside face,
hence provide projection in slab, beyond the face of vertical walls, by an amount x m alround, so that weight of soil column supported by
projection will provide additional down war force. It is assumed that if the tank is floted, the earth would rupture on vrtical planes shown by
dotted lines. (fig ) .Most soil would tend torupture on an inclined planes, thus tendind to increase the effective down ward load from the
earth but this might be small in waterlogged non-cohesive ground.
3.14xdia2 3.14 x 10 x 10
using 10 mm bars A = = = 78.5 mm2
4 x100 4 x 100
Spacing of hoop Bars = 1000 x 78.5 / -4286 = -18 say = 200 mm
Hence Provided 10 mm F bar, @ 200 mm c/c. on each face
0.30
0.25
mm f @ mm c/c
0.266
12 mm f @ 300 mm c/c
16 mm f @ 500 mm c/c
mm f @ mm c/c 4.69 m
6.30 mm f @ mm c/c
16 mm f @ 125 mm c/c
12 mm f @ 150 mm c/c
16 mm f @ 125 mm c/c 1.61 m
0.25 16 mm f @ 250 mm c/c 0.25
0.3
Grade of concrete M-15 M-20 M-25 M-30 M-35 M-40 Grade of concrete
tc.max 1.6 1.8 1.9 2.2 2.3 2.5 sct.max