SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
PLATE 3
GRANDTOTALHEAT(TC) 21592.07
TOTALSENSIBLEHEAT(SC) 15338.27
DEHUMIDIFIEDCFM 729.82
Estimate Flow for Chilled Water in Gallons per minute for Fan Coil
GIVEN:
𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦 (𝑓𝑜𝑟 𝐹𝑎𝑛 𝐶𝑜𝑖𝑙 𝑅𝑜𝑜𝑚 301) = (𝑐𝑜𝑛𝑣𝑒𝑟𝑡 𝐺𝑇𝐻)𝑇𝑜𝑛𝑠
𝑇𝑒𝑟𝑚𝑖𝑛𝑎𝑙 𝐷𝑖𝑓𝑓𝑒𝑟𝑒𝑛𝑐𝑒 (𝑇𝐷) = 10℉
12 000 𝑥 𝑇𝑅
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 𝑇𝐷
12 000 𝑥 1.7993
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 10
1
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
2
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
SCHEMATICDIAGRAMOFFANCOILUNITSHOWINGTHE
DIFFERENT PARAMETERS
TRANECOOLINGCOILAIRSIDE
FCU302(13.5Hours)
3
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
HIGHLIGHTED SELECTED DATA ON THE BROCHURE
INTERPOLATING:
43 − 44 27.50 − 𝑇𝐶
= → 𝑻𝑪 = 𝟐𝟔. 𝟏𝟑
43 − 45 27.50 − 24.76
43 − 44 21.34 − 𝑆𝐶
= → 𝑺𝑪 = 𝟐𝟎. 𝟕𝟏
43 − 45 21.34 − 20.08
43 − 44 5.48 − 𝐺𝑃𝑀
= → 𝑮𝑷𝑴 = 𝟓. 𝟐𝟏
43 − 45 5.48 − 4.94
43 − 44 14.36 − 𝑃𝐷
= → 𝑷𝑫 = 𝟏𝟑. 𝟏𝟏𝟓
43 − 45 14.36 − 11.87
4
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
Estimate Flow for Chilled Water in Gallons per minute for Fan Coil
GIVEN:
𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦 (𝑓𝑜𝑟 𝐹𝑎𝑛 𝐶𝑜𝑖𝑙 𝑅𝑜𝑜𝑚 302) = (𝑐𝑜𝑛𝑣𝑒𝑟𝑡 𝐺𝑇𝐻)𝑇𝑜𝑛𝑠
𝑇𝑒𝑟𝑚𝑖𝑛𝑎𝑙 𝐷𝑖𝑓𝑓𝑒𝑟𝑒𝑛𝑐𝑒 (𝑇𝐷) = 10℉
12 000 𝑥 𝑇𝑅
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 𝑇𝐷
12 000 𝑥 2.2322
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 10
5
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
6
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
SCHEMATICDIAGRAMOFFANCOILUNITSHOWINGTHE
DIFFERENT PARAMETERS
TRANECOOLINGCOILAIRSIDE
FCU302(13.5Hours)
7
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
HIGHLIGHTED SELECTED DATA ON THE BROCHURE
INTERPOLATING:
43 − 44 42.55 − 𝑇𝐶
= → 𝑻𝑪 = 𝟒𝟎. 𝟒𝟓
43 − 45 42.55 − 38.35
43 − 44 33.29 − 𝑆𝐶
= → 𝑺𝑪 = 𝟑𝟐. 𝟓𝟒𝟓
43 − 45 33.29 − 31.8
43 − 44 33.29 − 𝐺𝑃𝑀
= → 𝑮𝑷𝑴 = 𝟐𝟎. 𝟔𝟒𝟓
43 − 45 33.29 − 7.64
43 − 44 8.48 − 𝑃𝐷
= → 𝑷𝑫 = 𝟏𝟎. 𝟒𝟒𝟓
43 − 45 8.48 − 12.81
8
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
Estimate Flow for Chilled Water in Gallons per minute for Fan Coil
GIVEN:
𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦 (𝑓𝑜𝑟 𝐹𝑎𝑛 𝐶𝑜𝑖𝑙 𝑅𝑜𝑜𝑚 303) = (𝑐𝑜𝑛𝑣𝑒𝑟𝑡 𝐺𝑇𝐻)𝑇𝑜𝑛𝑠
𝑇𝑒𝑟𝑚𝑖𝑛𝑎𝑙 𝐷𝑖𝑓𝑓𝑒𝑟𝑒𝑛𝑐𝑒 (𝑇𝐷) = 10℉
12 000 𝑥 𝑇𝑅
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 𝑇𝐷
12 000 𝑥 1.4698
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 10
9
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
10
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
SCHEMATICDIAGRAMOFFANCOILUNITSHOWINGTHE
DIFFERENT PARAMETERS
TRANECOOLINGCOILAIRSIDE
FCU303(13.5Hours)
11
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
INTERPOLATING:
43 − 44 20.12 − 𝑇𝐶
= → 𝑻𝑪 = 𝟏𝟗. 𝟎𝟔
43 − 45 20.12 − 18
43 − 44 14.14 − 𝑆𝐶
= → 𝑺𝑪 = 𝟏𝟑. 𝟕𝟐
43 − 45 14.14 − 13.30
43 − 44 4.01 − 𝐺𝑃𝑀
= → 𝑮𝑷𝑴 = 𝟑. 𝟖𝟎
43 − 45 4.01 − 3.59
43 − 44 6.79 − 𝑃𝐷
= → 𝑷𝑫 = 𝟔. 𝟏𝟕𝟓
43 − 45 6.79 − 5.56
12
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
GRANDTOTALHEAT(TC) 17444.20
11190.40
TOTALSENSIBLEHEAT(SC)
DEHUMIDIFIEDCFM 483.86
Estimate Flow for Chilled Water in Gallons per minute for Fan Coil
GIVEN:
𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦 (𝑓𝑜𝑟 𝐹𝑎𝑛 𝐶𝑜𝑖𝑙 𝑅𝑜𝑜𝑚 304) = (𝑐𝑜𝑛𝑣𝑒𝑟𝑡 𝐺𝑇𝐻)𝑇𝑜𝑛𝑠
𝑇𝑒𝑟𝑚𝑖𝑛𝑎𝑙 𝐷𝑖𝑓𝑓𝑒𝑟𝑒𝑛𝑐𝑒 (𝑇𝐷) = 10℉
12 000 𝑥 𝑇𝑅
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 𝑇𝐷
12 000 𝑥 1.4537
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 10
13
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
14
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
SCHEMATICDIAGRAMOFFANCOILUNITSHOWINGTHE
DIFFERENT PARAMETERS
TRANECOOLINGCOILAIRSIDE
FCU304(13.5Hours)
15
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
INTERPOLATING:
43 − 44 20.12 − 𝑇𝐶
= → 𝑻𝑪 = 𝟏𝟗. 𝟎𝟔
43 − 45 20.12 − 18
43 − 44 14.14 − 𝑆𝐶
= → 𝑺𝑪 = 𝟏𝟑. 𝟕𝟐
43 − 45 14.14 − 13.30
43 − 44 4.01 − 𝐺𝑃𝑀
= → 𝑮𝑷𝑴 = 𝟑. 𝟖𝟎
43 − 45 4.01 − 3.59
43 − 44 6.79 − 𝑃𝐷
= → 𝑷𝑫 = 𝟔. 𝟏𝟕𝟓
43 − 45 6.79 − 5.56
16
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
Estimate Flow for Chilled Water in Gallons per minute for Fan Coil
GIVEN:
𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦 (𝑓𝑜𝑟 𝐹𝑎𝑛 𝐶𝑜𝑖𝑙 𝑅𝑜𝑜𝑚 305) = (𝑐𝑜𝑛𝑣𝑒𝑟𝑡 𝐺𝑇𝐻)𝑇𝑜𝑛𝑠
𝑇𝑒𝑟𝑚𝑖𝑛𝑎𝑙 𝐷𝑖𝑓𝑓𝑒𝑟𝑒𝑛𝑐𝑒 (𝑇𝐷) = 10℉
12 000 𝑥 𝑇𝑅
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 𝑇𝐷
12 000 𝑥 1.4500
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 10
17
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
18
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
SCHEMATICDIAGRAMOFFANCOILUNITSHOWINGTHE
DIFFERENT PARAMETERS
TRANECOOLINGCOILAIRSIDE
FCU305(13.5Hours)
19
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
INTERPOLATING:
43 − 44 20.12 − 𝑇𝐶
= → 𝑻𝑪 = 𝟏𝟗. 𝟎𝟔
43 − 45 20.12 − 18
43 − 44 14.14 − 𝑆𝐶
= → 𝑺𝑪 = 𝟏𝟑. 𝟕𝟐
43 − 45 14.14 − 13.30
43 − 44 4.01 − 𝐺𝑃𝑀
= → 𝑮𝑷𝑴 = 𝟑. 𝟖𝟎
43 − 45 4.01 − 3.59
43 − 44 6.79 − 𝑃𝐷
= → 𝑷𝑫 = 𝟔. 𝟏𝟕𝟓
43 − 45 6.79 − 5.56
20
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
GRANDTOTALHEAT(TC) 17914.05
11660.25
TOTALSENSIBLEHEAT(SC)
509.53
DEHUMIDIFIEDCFM
ENTERINGDRY BULB/ 80.71 / 69.20
ENTERINGWETBULB
LEAVINGDRY 59.52 / 58.70
BULB/LEAVINGWETBULB
CHILLEDWATERFLOW 3.5828
INGALLONSPER MINUTE
ENTERING/ 44 °F / 54 °F
LEAVINGCHILLEDWATERTEMP, °F
Estimate Flow for Chilled Water in Gallons per minute for Fan Coil
GIVEN:
𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦 (𝑓𝑜𝑟 𝐹𝑎𝑛 𝐶𝑜𝑖𝑙 𝑅𝑜𝑜𝑚 306) = (𝑐𝑜𝑛𝑣𝑒𝑟𝑡 𝐺𝑇𝐻)𝑇𝑜𝑛𝑠
𝑇𝑒𝑟𝑚𝑖𝑛𝑎𝑙 𝐷𝑖𝑓𝑓𝑒𝑟𝑒𝑛𝑐𝑒 (𝑇𝐷) = 10℉
12 000 𝑥 𝑇𝑅
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 𝑇𝐷
12 000 𝑥 1.4928
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 10
21
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
22
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
SCHEMATICDIAGRAMOFFANCOILUNITSHOWINGTHE
DIFFERENT PARAMETERS
TRANECOOLINGCOILAIRSIDE
FCU306(13.5Hours)
23
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
INTERPOLATING:
43 − 44 20.12 − 𝑇𝐶
= → 𝑻𝑪 = 𝟏𝟗. 𝟎𝟔
43 − 45 20.12 − 18
43 − 44 14.14 − 𝑆𝐶
= → 𝑺𝑪 = 𝟏𝟑. 𝟕𝟐
43 − 45 14.14 − 13.30
43 − 44 4.01 − 𝐺𝑃𝑀
= → 𝑮𝑷𝑴 = 𝟑. 𝟖𝟎
43 − 45 4.01 − 3.59
43 − 44 6.79 − 𝑃𝐷
= → 𝑷𝑫 = 𝟔. 𝟏𝟕𝟓
43 − 45 6.79 − 5.56
24
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
TOTALSENSIBLEHEAT(SC) 18924.26
948.30
DEHUMIDIFIEDCFM
ENTERINGDRY BULB/ 78.53 / 67.20
ENTERINGWETBULB
LEAVINGDRY 59.15 / 58.80
BULB/LEAVINGWETBULB
CHILLEDWATERFLOW 5.0356
INGALLONSPER MINUTE
ENTERING/ 44 °F / 54 °F
LEAVINGCHILLEDWATERTEMP, °F
Estimate Flow for Chilled Water in Gallons per minute for Fan Coil
GIVEN:
𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦 (𝑓𝑜𝑟 𝐹𝑎𝑛 𝐶𝑜𝑖𝑙 𝑅𝑜𝑜𝑚 307) = (𝑐𝑜𝑛𝑣𝑒𝑟𝑡 𝐺𝑇𝐻)𝑇𝑜𝑛𝑠
𝑇𝑒𝑟𝑚𝑖𝑛𝑎𝑙 𝐷𝑖𝑓𝑓𝑒𝑟𝑒𝑛𝑐𝑒 (𝑇𝐷) = 10℉
12 000 𝑥 𝑇𝑅
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 𝑇𝐷
12 000 𝑥 2.0982
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 10
25
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
NOMINALAIRFLOW 1000
GRANDTOTALHEAT(TC) 33465
TOTALSENSIBLEHEAT(SC) 26550
FINTYPE Louver
FINTYPEPERINCH 18
NO.OFROWCOIL 3
DRAINCONNECTIONSIZE 1/2
FANTYPE Centrifugal
NO.USED 2
DRIVETYPE Direct
MOTORPOWER,W 162
ENTERINGDRYBULB/ENTERINGWETBULB 80/ 67
LEAVINGDRYBULB/LEAVINGWETBULB 57.7/ 56.6
CHILLEDWATERFLOWINGALLONSPERMI
6.67
NUTE
WATERPRESSUREDROPPD,FTINWATER 8.70
26
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
SCHEMATICDIAGRAMOFFANCOILUNITSHOWINGTHE
DIFFERENT PARAMETERS
TRANECOOLINGCOILAIRSIDE
FCU307(13.5Hours)
27
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
INTERPOLATING:
43 − 44 35.23 − 𝑇𝐶
= → 𝑻𝑪 = 𝟑𝟑. 𝟒𝟔𝟓
43 − 45 35.23 − 31.70
43 − 44 27.33 − 𝑆𝐶
= → 𝑺𝑪 = 𝟐𝟔. 𝟓𝟓
43 − 45 27.33 − 25.77
43 − 44 7.02 − 𝐺𝑃𝑀
= → 𝑮𝑷𝑴 = 𝟔. 𝟔𝟕
43 − 45 7.02 − 6.32
43 − 44 9.53 − 𝑃𝐷
= → 𝑷𝑫 = 𝟖. 𝟕𝟎
43 − 45 9.53 − 7.87
28
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
TOTALSENSIBLEHEAT(SC) 11146.27
481.45
DEHUMIDIFIEDCFM
ENTERINGDRY BULB/ 80.98 / 69.60
ENTERINGWETBULB
LEAVINGDRY 59.55 / 58.90
BULB/LEAVINGWETBULB
CHILLEDWATERFLOW 3.4800
INGALLONSPER MINUTE
ENTERING/ 44 °F / 54 °F
LEAVINGCHILLEDWATERTEMP, °F
Estimate Flow for Chilled Water in Gallons per minute for Fan Coil
GIVEN:
𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦 (𝑓𝑜𝑟 𝐹𝑎𝑛 𝐶𝑜𝑖𝑙 𝑅𝑜𝑜𝑚 305) = (𝑐𝑜𝑛𝑣𝑒𝑟𝑡 𝐺𝑇𝐻)𝑇𝑜𝑛𝑠
𝑇𝑒𝑟𝑚𝑖𝑛𝑎𝑙 𝐷𝑖𝑓𝑓𝑒𝑟𝑒𝑛𝑐𝑒 (𝑇𝐷) = 10℉
12 000 𝑥 𝑇𝑅
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 𝑇𝐷
12 000 𝑥 1.4500
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 10
29
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
30
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
SCHEMATICDIAGRAMOFFANCOILUNITSHOWINGTHE
DIFFERENT PARAMETERS
TRANECOOLINGCOILAIRSIDE
FCU308(13.5Hours)
31
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
INTERPOLATING:
43 − 44 20.12 − 𝑇𝐶
= → 𝑻𝑪 = 𝟏𝟗. 𝟎𝟔
43 − 45 20.12 − 18
43 − 44 14.14 − 𝑆𝐶
= → 𝑺𝑪 = 𝟏𝟑. 𝟕𝟐
43 − 45 14.14 − 13.30
43 − 44 4.01 − 𝐺𝑃𝑀
= → 𝑮𝑷𝑴 = 𝟑. 𝟖𝟎
43 − 45 4.01 − 3.59
43 − 44 6.79 − 𝑃𝐷
= → 𝑷𝑫 = 𝟔. 𝟏𝟕𝟓
43 − 45 6.79 − 5.56
32
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
Estimate Flow for Chilled Water in Gallons per minute for Fan Coil
GIVEN:
𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦 (𝑓𝑜𝑟 𝐹𝑎𝑛 𝐶𝑜𝑖𝑙 𝑅𝑜𝑜𝑚 309) = (𝑐𝑜𝑛𝑣𝑒𝑟𝑡 𝐺𝑇𝐻)𝑇𝑜𝑛𝑠
𝑇𝑒𝑟𝑚𝑖𝑛𝑎𝑙 𝐷𝑖𝑓𝑓𝑒𝑟𝑒𝑛𝑐𝑒 (𝑇𝐷) = 10℉
12 000 𝑥 𝑇𝑅
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 𝑇𝐷
12 000 𝑥 1.9212
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 10
33
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
NOMINALAIRFLOW 1000
GRANDTOTALHEAT(TC) 33465
TOTALSENSIBLEHEAT(SC) 26550
FINTYPE Louver
FINTYPEPERINCH 18
NO.OFROWCOIL 3
DRAINCONNECTIONSIZE 1/2
FANTYPE Centrifugal
NO.USED 2
DRIVETYPE Direct
MOTORPOWER,W 162
ENTERINGDRYBULB/ENTERINGWETBULB 80/ 67
LEAVINGDRYBULB/LEAVINGWETBULB 57.7/ 56.6
CHILLEDWATERFLOWINGALLONSPERMI
6.67
NUTE
WATERPRESSUREDROPPD,FTINWATER 8.70
34
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
SCHEMATICDIAGRAMOFFANCOILUNITSHOWINGTHE
DIFFERENT PARAMETERS
TRANECOOLINGCOILAIRSIDE
FCU309(13.5Hours)
35
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
INTERPOLATING:
43 − 44 35.23 − 𝑇𝐶
= → 𝑻𝑪 = 𝟑𝟑. 𝟒𝟔𝟓
43 − 45 35.23 − 31.70
43 − 44 27.33 − 𝑆𝐶
= → 𝑺𝑪 = 𝟐𝟔. 𝟓𝟓
43 − 45 27.33 − 25.77
43 − 44 7.02 − 𝐺𝑃𝑀
= → 𝑮𝑷𝑴 = 𝟔. 𝟔𝟕
43 − 45 7.02 − 6.32
43 − 44 9.53 − 𝑃𝐷
= → 𝑷𝑫 = 𝟖. 𝟕𝟎
43 − 45 9.53 − 7.87
36
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
TOTALSENSIBLEHEAT(SC) 12414.38
522.96
DEHUMIDIFIEDCFM
ENTERINGDRY BULB/ 80.64 °F / 69.2 °F
ENTERINGWETBULB
LEAVINGDRY 59.54 °F / 58.8 °F
BULB/LEAVINGWETBULB
CHILLEDWATERFLOW 3.6089 GPM
INGALLONSPER MINUTE
ENTERING/ 44 °F / 54 °F
LEAVINGCHILLEDWATERTEMP, °F
Estimate Flow for Chilled Water in Gallons per minute for Fan Coil
GIVEN:
𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦 (𝑓𝑜𝑟 𝐹𝑎𝑛 𝐶𝑜𝑖𝑙 𝑅𝑜𝑜𝑚 310) = (𝑐𝑜𝑛𝑣𝑒𝑟𝑡 𝐺𝑇𝐻)𝑇𝑜𝑛𝑠
𝑇𝑒𝑟𝑚𝑖𝑛𝑎𝑙 𝐷𝑖𝑓𝑓𝑒𝑟𝑒𝑛𝑐𝑒 (𝑇𝐷) = 10℉
12 000 𝑥 𝑇𝑅
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 𝑇𝐷
12 000 𝑥 1.5037
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 10
37
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
38
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
SCHEMATICDIAGRAMOFFANCOILUNITSHOWINGTHE
DIFFERENT PARAMETERS
TRANECOOLINGCOILAIRSIDE
FCU310(13.5Hours)
39
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
HIGHLIGHTED SELECTED DATA ON THE BROCHURE
INTERPOLATING:
43 − 44 20.12 − 𝑇𝐶
= → 𝑻𝑪 = 𝟏𝟗. 𝟎𝟔
43 − 45 20.12 − 18
43 − 44 14.14 − 𝑆𝐶
= → 𝑺𝑪 = 𝟏𝟑. 𝟕𝟐
43 − 45 14.14 − 13.30
43 − 44 4.01 − 𝐺𝑃𝑀
= → 𝑮𝑷𝑴 = 𝟑. 𝟖𝟎
43 − 45 4.01 − 3.59
43 − 44 6.79 − 𝑃𝐷
= → 𝑷𝑫 = 𝟔. 𝟏𝟕𝟓
43 − 45 6.79 − 5.56
40
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
TOTALSENSIBLEHEAT(SC) 16561.53
805.79
DEHUMIDIFIEDCFM
ENTERINGDRY BULB/ 78.93 / 67.50
ENTERINGWETBULB
LEAVINGDRY 59.04 / 58.40
BULB/LEAVINGWETBULB
CHILLEDWATERFLOW 4.5631
INGALLONSPER MINUTE
ENTERING/ 44 °F / 54 °F
LEAVINGCHILLEDWATERTEMP, °F
Estimate Flow for Chilled Water in Gallons per minute for Fan Coil
GIVEN:
𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦 (𝑓𝑜𝑟 𝐹𝑎𝑛 𝐶𝑜𝑖𝑙 𝑅𝑜𝑜𝑚 309) = (𝑐𝑜𝑛𝑣𝑒𝑟𝑡 𝐺𝑇𝐻)𝑇𝑜𝑛𝑠
𝑇𝑒𝑟𝑚𝑖𝑛𝑎𝑙 𝐷𝑖𝑓𝑓𝑒𝑟𝑒𝑛𝑐𝑒 (𝑇𝐷) = 10℉
12 000 𝑥 𝑇𝑅
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 𝑇𝐷
12 000 𝑥 1.9013
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 10
41
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
NOMINALAIRFLOW 1000
GRANDTOTALHEAT(TC) 33465
TOTALSENSIBLEHEAT(SC) 26550
FINTYPE Louver
FINTYPEPERINCH 18
NO.OFROWCOIL 3
DRAINCONNECTIONSIZE 1/2
FANTYPE Centrifugal
NO.USED 2
DRIVETYPE Direct
MOTORPOWER,W 162
ENTERINGDRYBULB/ENTERINGWETBULB 80/ 67
LEAVINGDRYBULB/LEAVINGWETBULB 57.7/ 56.6
CHILLEDWATERFLOWINGALLONSPERMI
6.67
NUTE
WATERPRESSUREDROPPD,FTINWATER 8.70
42
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
SCHEMATICDIAGRAMOFFANCOILUNITSHOWINGTHE
DIFFERENT PARAMETERS
TRANECOOLINGCOILAIRSIDE
FCU311(13.5Hours)
43
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
HIGHLIGHTED SELECTED DATA ON THE BROCHURE
INTERPOLATING:
43 − 44 35.23 − 𝑇𝐶
= → 𝑻𝑪 = 𝟑𝟑. 𝟒𝟔𝟓
43 − 45 35.23 − 31.70
43 − 44 27.33 − 𝑆𝐶
= → 𝑺𝑪 = 𝟐𝟔. 𝟓𝟓
43 − 45 27.33 − 25.77
43 − 44 7.02 − 𝐺𝑃𝑀
= → 𝑮𝑷𝑴 = 𝟔. 𝟔𝟕
43 − 45 7.02 − 6.32
43 − 44 9.53 − 𝑃𝐷
= → 𝑷𝑫 = 𝟖. 𝟕𝟎
43 − 45 9.53 − 7.87
44
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
Estimate Flow for Chilled Water in Gallons per minute for Fan Coil
GIVEN:
𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦 (𝑓𝑜𝑟 𝐹𝑎𝑛 𝐶𝑜𝑖𝑙 𝑅𝑜𝑜𝑚 312) = (𝑐𝑜𝑛𝑣𝑒𝑟𝑡 𝐺𝑇𝐻)𝑇𝑜𝑛𝑠
𝑇𝑒𝑟𝑚𝑖𝑛𝑎𝑙 𝐷𝑖𝑓𝑓𝑒𝑟𝑒𝑛𝑐𝑒 (𝑇𝐷) = 10℉
12 000 𝑥 𝑇𝑅
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 𝑇𝐷
12 000 𝑥 1.5037
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 10
45
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
46
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
SCHEMATICDIAGRAMOFFANCOILUNITSHOWINGTHE
DIFFERENT PARAMETERS
TRANECOOLINGCOILAIRSIDE
FCU312(13.5Hours)
47
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
HIGHLIGHTED SELECTED DATA ON THE BROCHURE
INTERPOLATING:
43 − 44 20.12 − 𝑇𝐶
= → 𝑻𝑪 = 𝟏𝟗. 𝟎𝟔
43 − 45 20.12 − 18
43 − 44 14.14 − 𝑆𝐶
= → 𝑺𝑪 = 𝟏𝟑. 𝟕𝟐
43 − 45 14.14 − 13.30
43 − 44 4.01 − 𝐺𝑃𝑀
= → 𝑮𝑷𝑴 = 𝟑. 𝟖𝟎
43 − 45 4.01 − 3.59
43 − 44 6.79 − 𝑃𝐷
= → 𝑷𝑫 = 𝟔. 𝟏𝟕𝟓
43 − 45 6.79 − 5.56
48
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
Estimate Flow for Chilled Water in Gallons per minute for Fan Coil
GIVEN:
𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦 (𝑓𝑜𝑟 𝐹𝑎𝑛 𝐶𝑜𝑖𝑙 𝑅𝑜𝑜𝑚 309) = (𝑐𝑜𝑛𝑣𝑒𝑟𝑡 𝐺𝑇𝐻)𝑇𝑜𝑛𝑠
𝑇𝑒𝑟𝑚𝑖𝑛𝑎𝑙 𝐷𝑖𝑓𝑓𝑒𝑟𝑒𝑛𝑐𝑒 (𝑇𝐷) = 10℉
12 000 𝑥 𝑇𝑅
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 𝑇𝐷
12 000 𝑥 1.9013
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 10
49
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
NOMINALAIRFLOW 1000
GRANDTOTALHEAT(TC) 33465
TOTALSENSIBLEHEAT(SC) 26550
FINTYPE Louver
FINTYPEPERINCH 18
NO.OFROWCOIL 3
DRAINCONNECTIONSIZE 1/2
FANTYPE Centrifugal
NO.USED 2
DRIVETYPE Direct
MOTORPOWER,W 162
ENTERINGDRYBULB/ENTERINGWETBULB 80/ 67
LEAVINGDRYBULB/LEAVINGWETBULB 57.7/ 56.6
CHILLEDWATERFLOWINGALLONSPERMI
6.67
NUTE
WATERPRESSUREDROPPD,FTINWATER 8.70
50
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
SCHEMATICDIAGRAMOFFANCOILUNITSHOWINGTHE
DIFFERENT PARAMETERS
TRANECOOLINGCOILAIRSIDE
FCU313(13.5Hours)
51
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
HIGHLIGHTED SELECTED DATA ON THE BROCHURE
INTERPOLATING:
43 − 44 35.23 − 𝑇𝐶
= → 𝑻𝑪 = 𝟑𝟑. 𝟒𝟔𝟓
43 − 45 35.23 − 31.70
43 − 44 27.33 − 𝑆𝐶
= → 𝑺𝑪 = 𝟐𝟔. 𝟓𝟓
43 − 45 27.33 − 25.77
43 − 44 7.02 − 𝐺𝑃𝑀
= → 𝑮𝑷𝑴 = 𝟔. 𝟔𝟕
43 − 45 7.02 − 6.32
43 − 44 9.53 − 𝑃𝐷
= → 𝑷𝑫 = 𝟖. 𝟕𝟎
43 − 45 9.53 − 7.87
52
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
Estimate Flow for Chilled Water in Gallons per minute for Fan Coil
GIVEN:
𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦 (𝑓𝑜𝑟 𝐹𝑎𝑛 𝐶𝑜𝑖𝑙 𝑅𝑜𝑜𝑚 305) = (𝑐𝑜𝑛𝑣𝑒𝑟𝑡 𝐺𝑇𝐻)𝑇𝑜𝑛𝑠
𝑇𝑒𝑟𝑚𝑖𝑛𝑎𝑙 𝐷𝑖𝑓𝑓𝑒𝑟𝑒𝑛𝑐𝑒 (𝑇𝐷) = 10℉
12 000 𝑥 𝑇𝑅
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 𝑇𝐷
12 000 𝑥 1.4500
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 10
53
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
54
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
SCHEMATICDIAGRAMOFFANCOILUNITSHOWINGTHE
DIFFERENT PARAMETERS
TRANECOOLINGCOILAIRSIDE
FCU314(13.5Hours)
55
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
HIGHLIGHTED SELECTED DATA ON THE BROCHURE
INTERPOLATING:
43 − 44 20.12 − 𝑇𝐶
= → 𝑻𝑪 = 𝟏𝟗. 𝟎𝟔
43 − 45 20.12 − 18
43 − 44 14.14 − 𝑆𝐶
= → 𝑺𝑪 = 𝟏𝟑. 𝟕𝟐
43 − 45 14.14 − 13.30
43 − 44 4.01 − 𝐺𝑃𝑀
= → 𝑮𝑷𝑴 = 𝟑. 𝟖𝟎
43 − 45 4.01 − 3.59
43 − 44 6.79 − 𝑃𝐷
= → 𝑷𝑫 = 𝟔. 𝟏𝟕𝟓
43 − 45 6.79 − 5.56
56
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
Estimate Flow for Chilled Water in Gallons per minute for Fan Coil
GIVEN:
𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦 (𝑓𝑜𝑟 𝐹𝑎𝑛 𝐶𝑜𝑖𝑙 𝑅𝑜𝑜𝑚 309) = (𝑐𝑜𝑛𝑣𝑒𝑟𝑡 𝐺𝑇𝐻)𝑇𝑜𝑛𝑠
𝑇𝑒𝑟𝑚𝑖𝑛𝑎𝑙 𝐷𝑖𝑓𝑓𝑒𝑟𝑒𝑛𝑐𝑒 (𝑇𝐷) = 10℉
12 000 𝑥 𝑇𝑅
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 𝑇𝐷
12 000 𝑥 1.9189
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 10
57
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
NOMINALAIRFLOW 1000
GRANDTOTALHEAT(TC) 33465
TOTALSENSIBLEHEAT(SC) 26550
FINTYPE Louver
FINTYPEPERINCH 18
NO.OFROWCOIL 3
DRAINCONNECTIONSIZE 1/2
FANTYPE Centrifugal
NO.USED 2
DRIVETYPE Direct
MOTORPOWER,W 162
ENTERINGDRYBULB/ENTERINGWETBULB 80/ 67
LEAVINGDRYBULB/LEAVINGWETBULB 57.7/ 56.6
CHILLEDWATERFLOWINGALLONSPERMI
6.67
NUTE
WATERPRESSUREDROPPD,FTINWATER 8.70
58
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
SCHEMATICDIAGRAMOFFANCOILUNITSHOWINGTHE
DIFFERENT PARAMETERS
TRANECOOLINGCOILAIRSIDE
FCU315(13.5Hours)
59
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
HIGHLIGHTED SELECTED DATA ON THE BROCHURE
INTERPOLATING:
43 − 44 35.23 − 𝑇𝐶
= → 𝑻𝑪 = 𝟑𝟑. 𝟒𝟔𝟓
43 − 45 35.23 − 31.70
43 − 44 27.33 − 𝑆𝐶
= → 𝑺𝑪 = 𝟐𝟔. 𝟓𝟓
43 − 45 27.33 − 25.77
43 − 44 7.02 − 𝐺𝑃𝑀
= → 𝑮𝑷𝑴 = 𝟔. 𝟔𝟕
43 − 45 7.02 − 6.32
43 − 44 9.53 − 𝑃𝐷
= → 𝑷𝑫 = 𝟖. 𝟕𝟎
43 − 45 9.53 − 7.87
60
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
Estimate Flow for Chilled Water in Gallons per minute for Fan Coil
GIVEN:
𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦 (𝑓𝑜𝑟 𝐹𝑎𝑛 𝐶𝑜𝑖𝑙 𝑅𝑜𝑜𝑚 306) = (𝑐𝑜𝑛𝑣𝑒𝑟𝑡 𝐺𝑇𝐻)𝑇𝑜𝑛𝑠
𝑇𝑒𝑟𝑚𝑖𝑛𝑎𝑙 𝐷𝑖𝑓𝑓𝑒𝑟𝑒𝑛𝑐𝑒 (𝑇𝐷) = 10℉
12 000 𝑥 𝑇𝑅
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 𝑇𝐷
12 000 𝑥 1.4928
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 10
61
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
62
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
SCHEMATICDIAGRAMOFFANCOILUNITSHOWINGTHE
DIFFERENT PARAMETERS
TRANECOOLINGCOILAIRSIDE
FCU316(13.5Hours)
63
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
HIGHLIGHTED SELECTED DATA ON THE BROCHURE
INTERPOLATING:
43 − 44 20.12 − 𝑇𝐶
= → 𝑻𝑪 = 𝟏𝟗. 𝟎𝟔
43 − 45 20.12 − 18
43 − 44 14.14 − 𝑆𝐶
= → 𝑺𝑪 = 𝟏𝟑. 𝟕𝟐
43 − 45 14.14 − 13.30
43 − 44 4.01 − 𝐺𝑃𝑀
= → 𝑮𝑷𝑴 = 𝟑. 𝟖𝟎
43 − 45 4.01 − 3.59
43 − 44 6.79 − 𝑃𝐷
= → 𝑷𝑫 = 𝟔. 𝟏𝟕𝟓
43 − 45 6.79 − 5.56
64
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
Estimate Flow for Chilled Water in Gallons per minute for Fan Coil
GIVEN:
𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦 (𝑓𝑜𝑟 𝐹𝑎𝑛 𝐶𝑜𝑖𝑙 𝑅𝑜𝑜𝑚 317) = (𝑐𝑜𝑛𝑣𝑒𝑟𝑡 𝐺𝑇𝐻)𝑇𝑜𝑛𝑠
𝑇𝑒𝑟𝑚𝑖𝑛𝑎𝑙 𝐷𝑖𝑓𝑓𝑒𝑟𝑒𝑛𝑐𝑒 (𝑇𝐷) = 10℉
12 000 𝑥 𝑇𝑅
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 𝑇𝐷
12 000 𝑥 1.8415
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 10
65
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
66
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
SCHEMATICDIAGRAMOFFANCOILUNITSHOWINGTHE
DIFFERENT PARAMETERS
TRANECOOLINGCOILAIRSIDE
FCU317(13.5Hours)
67
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
HIGHLIGHTED SELECTED DATA ON THE BROCHURE
INTERPOLATING:
43 − 44 27.50 − 𝑇𝐶
= → 𝑻𝑪 = 𝟐𝟔. 𝟏𝟑
43 − 45 27.50 − 24.76
43 − 44 21.34 − 𝑆𝐶
= → 𝑺𝑪 = 𝟐𝟎. 𝟕𝟏
43 − 45 21.34 − 20.08
43 − 44 5.48 − 𝐺𝑃𝑀
= → 𝑮𝑷𝑴 = 𝟓. 𝟐𝟏
43 − 45 5.48 − 4.94
43 − 44 14.36 − 𝑃𝐷
= → 𝑷𝑫 = 𝟏𝟑. 𝟏𝟏𝟓
43 − 45 14.36 − 11.87
68
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
Estimate Flow for Chilled Water in Gallons per minute for Fan Coil
GIVEN:
𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦 (𝑓𝑜𝑟 𝐹𝑎𝑛 𝐶𝑜𝑖𝑙 𝑅𝑜𝑜𝑚 305) = (𝑐𝑜𝑛𝑣𝑒𝑟𝑡 𝐺𝑇𝐻)𝑇𝑜𝑛𝑠
𝑇𝑒𝑟𝑚𝑖𝑛𝑎𝑙 𝐷𝑖𝑓𝑓𝑒𝑟𝑒𝑛𝑐𝑒 (𝑇𝐷) = 10℉
12 000 𝑥 𝑇𝑅
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 𝑇𝐷
12 000 𝑥 1.4500
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 10
69
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
70
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
SCHEMATICDIAGRAMOFFANCOILUNITSHOWINGTHE
DIFFERENT PARAMETERS
TRANECOOLINGCOILAIRSIDE
FCU318(13.5Hours)
71
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
HIGHLIGHTED SELECTED DATA ON THE BROCHURE
INTERPOLATING:
43 − 44 20.12 − 𝑇𝐶
= → 𝑻𝑪 = 𝟏𝟗. 𝟎𝟔
43 − 45 20.12 − 18
43 − 44 14.14 − 𝑆𝐶
= → 𝑺𝑪 = 𝟏𝟑. 𝟕𝟐
43 − 45 14.14 − 13.30
43 − 44 4.01 − 𝐺𝑃𝑀
= → 𝑮𝑷𝑴 = 𝟑. 𝟖𝟎
43 − 45 4.01 − 3.59
43 − 44 6.79 − 𝑃𝐷
= → 𝑷𝑫 = 𝟔. 𝟏𝟕𝟓
43 − 45 6.79 − 5.56
72
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
Estimate Flow for Chilled Water in Gallons per minute for Fan Coil
GIVEN:
𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦 (𝑓𝑜𝑟 𝐹𝑎𝑛 𝐶𝑜𝑖𝑙 𝑅𝑜𝑜𝑚 319) = (𝑐𝑜𝑛𝑣𝑒𝑟𝑡 𝐺𝑇𝐻)𝑇𝑜𝑛𝑠
𝑇𝑒𝑟𝑚𝑖𝑛𝑎𝑙 𝐷𝑖𝑓𝑓𝑒𝑟𝑒𝑛𝑐𝑒 (𝑇𝐷) = 10℉
12 000 𝑥 𝑇𝑅
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 𝑇𝐷
12 000 𝑥 1.9503
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 10
73
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
NOMINALAIRFLOW 1000
GRANDTOTALHEAT(TC) 33465
TOTALSENSIBLEHEAT(SC) 26550
FINTYPE Louver
FINTYPEPERINCH 18
NO.OFROWCOIL 3
DRAINCONNECTIONSIZE 1/2
FANTYPE Centrifugal
NO.USED 2
DRIVETYPE Direct
MOTORPOWER,W 162
ENTERINGDRYBULB/ENTERINGWETBULB 80/ 67
LEAVINGDRYBULB/LEAVINGWETBULB 57.7/ 56.6
CHILLEDWATERFLOWINGALLONSPERMI
6.67
NUTE
WATERPRESSUREDROPPD,FTINWATER 8.70
74
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
SCHEMATICDIAGRAMOFFANCOILUNITSHOWINGTHE
DIFFERENT PARAMETERS
TRANECOOLINGCOILAIRSIDE
FCU319(13.5Hours)
75
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
HIGHLIGHTED SELECTED DATA ON THE BROCHURE
INTERPOLATING:
43 − 44 35.23 − 𝑇𝐶
= → 𝑻𝑪 = 𝟑𝟑. 𝟒𝟔𝟓
43 − 45 35.23 − 31.70
43 − 44 27.33 − 𝑆𝐶
= → 𝑺𝑪 = 𝟐𝟔. 𝟓𝟓
43 − 45 27.33 − 25.77
43 − 44 7.02 − 𝐺𝑃𝑀
= → 𝑮𝑷𝑴 = 𝟔. 𝟔𝟕
43 − 45 7.02 − 6.32
43 − 44 9.53 − 𝑃𝐷
= → 𝑷𝑫 = 𝟖. 𝟕𝟎
43 − 45 9.53 − 7.87
76
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
Estimate Flow for Chilled Water in Gallons per minute for Fan Coil
GIVEN:
𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦 (𝑓𝑜𝑟 𝐹𝑎𝑛 𝐶𝑜𝑖𝑙 𝑅𝑜𝑜𝑚 303) = (𝑐𝑜𝑛𝑣𝑒𝑟𝑡 𝐺𝑇𝐻)𝑇𝑜𝑛𝑠
𝑇𝑒𝑟𝑚𝑖𝑛𝑎𝑙 𝐷𝑖𝑓𝑓𝑒𝑟𝑒𝑛𝑐𝑒 (𝑇𝐷) = 10℉
12 000 𝑥 𝑇𝑅
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 𝑇𝐷
12 000 𝑥 1.4574
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 10
77
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
78
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
SCHEMATICDIAGRAMOFFANCOILUNITSHOWINGTHE
DIFFERENT PARAMETERS
TRANECOOLINGCOILAIRSIDE
FCU320(13.5Hours)
79
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
HIGHLIGHTED SELECTED DATA ON THE BROCHURE
INTERPOLATING:
43 − 44 20.12 − 𝑇𝐶
= → 𝑻𝑪 = 𝟏𝟗. 𝟎𝟔
43 − 45 20.12 − 18
43 − 44 14.14 − 𝑆𝐶
= → 𝑺𝑪 = 𝟏𝟑. 𝟕𝟐
43 − 45 14.14 − 13.30
43 − 44 4.01 − 𝐺𝑃𝑀
= → 𝑮𝑷𝑴 = 𝟑. 𝟖𝟎
43 − 45 4.01 − 3.59
43 − 44 6.79 − 𝑃𝐷
= → 𝑷𝑫 = 𝟔. 𝟏𝟕𝟓
43 − 45 6.79 − 5.56
80
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
Estimate Flow for Chilled Water in Gallons per minute for Fan Coil
GIVEN:
𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦 (𝑓𝑜𝑟 𝐹𝑎𝑛 𝐶𝑜𝑖𝑙 𝑅𝑜𝑜𝑚 305) = (𝑐𝑜𝑛𝑣𝑒𝑟𝑡 𝐺𝑇𝐻)𝑇𝑜𝑛𝑠
𝑇𝑒𝑟𝑚𝑖𝑛𝑎𝑙 𝐷𝑖𝑓𝑓𝑒𝑟𝑒𝑛𝑐𝑒 (𝑇𝐷) = 10℉
12 000 𝑥 𝑇𝑅
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 𝑇𝐷
12 000 𝑥 1.4500
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 10
81
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
82
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
SCHEMATICDIAGRAMOFFANCOILUNITSHOWINGTHE
DIFFERENT PARAMETERS
TRANECOOLINGCOILAIRSIDE
FCU321(13.5Hours)
83
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
HIGHLIGHTED SELECTED DATA ON THE BROCHURE
INTERPOLATING:
43 − 44 20.12 − 𝑇𝐶
= → 𝑻𝑪 = 𝟏𝟗. 𝟎𝟔
43 − 45 20.12 − 18
43 − 44 14.14 − 𝑆𝐶
= → 𝑺𝑪 = 𝟏𝟑. 𝟕𝟐
43 − 45 14.14 − 13.30
43 − 44 4.01 − 𝐺𝑃𝑀
= → 𝑮𝑷𝑴 = 𝟑. 𝟖𝟎
43 − 45 4.01 − 3.59
43 − 44 6.79 − 𝑃𝐷
= → 𝑷𝑫 = 𝟔. 𝟏𝟕𝟓
43 − 45 6.79 − 5.56
84
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
Estimate Flow for Chilled Water in Gallons per minute for Fan Coil
GIVEN:
𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦 (𝑓𝑜𝑟 𝐹𝑎𝑛 𝐶𝑜𝑖𝑙 𝑅𝑜𝑜𝑚 306) = (𝑐𝑜𝑛𝑣𝑒𝑟𝑡 𝐺𝑇𝐻)𝑇𝑜𝑛𝑠
𝑇𝑒𝑟𝑚𝑖𝑛𝑎𝑙 𝐷𝑖𝑓𝑓𝑒𝑟𝑒𝑛𝑐𝑒 (𝑇𝐷) = 10℉
12 000 𝑥 𝑇𝑅
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 𝑇𝐷
12 000 𝑥 1.4928
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 10
85
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
86
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
SCHEMATICDIAGRAMOFFANCOILUNITSHOWINGTHE
DIFFERENT PARAMETERS
TRANECOOLINGCOILAIRSIDE
FCU322(13.5Hours)
87
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
HIGHLIGHTED SELECTED DATA ON THE BROCHURE
INTERPOLATING:
43 − 44 20.12 − 𝑇𝐶
= → 𝑻𝑪 = 𝟏𝟗. 𝟎𝟔
43 − 45 20.12 − 18
43 − 44 14.14 − 𝑆𝐶
= → 𝑺𝑪 = 𝟏𝟑. 𝟕𝟐
43 − 45 14.14 − 13.30
43 − 44 4.01 − 𝐺𝑃𝑀
= → 𝑮𝑷𝑴 = 𝟑. 𝟖𝟎
43 − 45 4.01 − 3.59
43 − 44 6.79 − 𝑃𝐷
= → 𝑷𝑫 = 𝟔. 𝟏𝟕𝟓
43 − 45 6.79 − 5.56
88
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
Estimate Flow for Chilled Water in Gallons per minute for Fan Coil
GIVEN:
𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦 (𝑓𝑜𝑟 𝐹𝑎𝑛 𝐶𝑜𝑖𝑙 𝑅𝑜𝑜𝑚 323) = (𝑐𝑜𝑛𝑣𝑒𝑟𝑡 𝐺𝑇𝐻)𝑇𝑜𝑛𝑠
𝑇𝑒𝑟𝑚𝑖𝑛𝑎𝑙 𝐷𝑖𝑓𝑓𝑒𝑟𝑒𝑛𝑐𝑒 (𝑇𝐷) = 10℉
12 000 𝑥 𝑇𝑅
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 𝑇𝐷
12 000 𝑥 1.8939
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 10
89
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
NOMINALAIRFLOW 1000
GRANDTOTALHEAT(TC) 33465
TOTALSENSIBLEHEAT(SC) 26550
FINTYPE Louver
FINTYPEPERINCH 18
NO.OFROWCOIL 3
DRAINCONNECTIONSIZE 1/2
FANTYPE Centrifugal
NO.USED 2
DRIVETYPE Direct
MOTORPOWER,W 162
ENTERINGDRYBULB/ENTERINGWETBULB 80/ 67
LEAVINGDRYBULB/LEAVINGWETBULB 57.7/ 56.6
CHILLEDWATERFLOWINGALLONSPERMI
6.67
NUTE
WATERPRESSUREDROPPD,FTINWATER 8.70
90
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
SCHEMATICDIAGRAMOFFANCOILUNITSHOWINGTHE
DIFFERENT PARAMETERS
TRANECOOLINGCOILAIRSIDE
FCU323(13.5Hours)
91
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
HIGHLIGHTED SELECTED DATA ON THE BROCHURE
INTERPOLATING:
43 − 44 35.23 − 𝑇𝐶
= → 𝑻𝑪 = 𝟑𝟑. 𝟒𝟔𝟓
43 − 45 35.23 − 31.70
43 − 44 27.33 − 𝑆𝐶
= → 𝑺𝑪 = 𝟐𝟔. 𝟓𝟓
43 − 45 27.33 − 25.77
43 − 44 7.02 − 𝐺𝑃𝑀
= → 𝑮𝑷𝑴 = 𝟔. 𝟔𝟕
43 − 45 7.02 − 6.32
43 − 44 9.53 − 𝑃𝐷
= → 𝑷𝑫 = 𝟖. 𝟕𝟎
43 − 45 9.53 − 7.87
92
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
Estimate Flow for Chilled Water in Gallons per minute for Fan Coil
GIVEN:
𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦 (𝑓𝑜𝑟 𝐹𝑎𝑛 𝐶𝑜𝑖𝑙 𝑅𝑜𝑜𝑚 324) = (𝑐𝑜𝑛𝑣𝑒𝑟𝑡 𝐺𝑇𝐻)𝑇𝑜𝑛𝑠
𝑇𝑒𝑟𝑚𝑖𝑛𝑎𝑙 𝐷𝑖𝑓𝑓𝑒𝑟𝑒𝑛𝑐𝑒 (𝑇𝐷) = 10℉
12 000 𝑥 𝑇𝑅
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 𝑇𝐷
12 000 𝑥 1.8331
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 10
93
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
94
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
SCHEMATICDIAGRAMOFFANCOILUNITSHOWINGTHE
DIFFERENT PARAMETERS
TRANECOOLINGCOILAIRSIDE
FCU324(13.5Hours)
95
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
HIGHLIGHTED SELECTED DATA ON THE BROCHURE
INTERPOLATING:
43 − 44 27.50 − 𝑇𝐶
= → 𝑻𝑪 = 𝟐𝟔. 𝟏𝟑
43 − 45 27.50 − 24.76
43 − 44 21.34 − 𝑆𝐶
= → 𝑺𝑪 = 𝟐𝟎. 𝟕𝟏
43 − 45 21.34 − 20.08
43 − 44 5.48 − 𝐺𝑃𝑀
= → 𝑮𝑷𝑴 = 𝟓. 𝟐𝟏
43 − 45 5.48 − 4.94
43 − 44 14.36 − 𝑃𝐷
= → 𝑷𝑫 = 𝟏𝟑. 𝟏𝟏𝟓
43 − 45 14.36 − 11.87
96
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
Estimate Flow for Chilled Water in Gallons per minute for Fan Coil
GIVEN:
𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦 (𝑓𝑜𝑟 𝐹𝑎𝑛 𝐶𝑜𝑖𝑙 𝑅𝑜𝑜𝑚 325) = (𝑐𝑜𝑛𝑣𝑒𝑟𝑡 𝐺𝑇𝐻)𝑇𝑜𝑛𝑠
𝑇𝑒𝑟𝑚𝑖𝑛𝑎𝑙 𝐷𝑖𝑓𝑓𝑒𝑟𝑒𝑛𝑐𝑒 (𝑇𝐷) = 10℉
12 000 𝑥 𝑇𝑅
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 𝑇𝐷
12 000 𝑥 2.1536
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 10
97
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
NOMINALAIRFLOW 1000
GRANDTOTALHEAT(TC) 33465
TOTALSENSIBLEHEAT(SC) 26550
FINTYPE Louver
FINTYPEPERINCH 18
NO.OFROWCOIL 3
DRAINCONNECTIONSIZE 1/2
FANTYPE Centrifugal
NO.USED 2
DRIVETYPE Direct
MOTORPOWER,W 162
ENTERINGDRYBULB/ENTERINGWETBULB 80/ 67
LEAVINGDRYBULB/LEAVINGWETBULB 57.7/ 56.6
CHILLEDWATERFLOWINGALLONSPERMI
6.67
NUTE
WATERPRESSUREDROPPD,FTINWATER 8.70
98
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
SCHEMATICDIAGRAMOFFANCOILUNITSHOWINGTHE
DIFFERENT PARAMETERS
TRANECOOLINGCOILAIRSIDE
FCU325(13.5Hours)
99
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
HIGHLIGHTED SELECTED DATA ON THE BROCHURE
INTERPOLATING:
43 − 44 35.23 − 𝑇𝐶
= → 𝑻𝑪 = 𝟑𝟑. 𝟒𝟔𝟓
43 − 45 35.23 − 31.70
43 − 44 27.33 − 𝑆𝐶
= → 𝑺𝑪 = 𝟐𝟔. 𝟓𝟓
43 − 45 27.33 − 25.77
43 − 44 7.02 − 𝐺𝑃𝑀
= → 𝑮𝑷𝑴 = 𝟔. 𝟔𝟕
43 − 45 7.02 − 6.32
43 − 44 9.53 − 𝑃𝐷
= → 𝑷𝑫 = 𝟖. 𝟕𝟎
43 − 45 9.53 − 7.87
100