MAPÚA UNIVERSITY

SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

PLATE 3

EQUIPMENT SELECTION FAN


COIL UNIT (3rdFLOOR)
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

HOTEL ROOM 301


FAN COIL UNIT SELECTION DATA
ITEM FAN COIL UNIT ROOM 301

CAPACITY INTONS 1.7993

GRANDTOTALHEAT(TC) 21592.07

TOTALSENSIBLEHEAT(SC) 15338.27

DEHUMIDIFIEDCFM 729.82

ENTERINGDRY BULB/ 78.29 / 68.10


ENTERINGWETBULB
LEAVINGDRY 59.83 / 59
BULB/LEAVINGWETBULB
CHILLEDWATERFLOW 4.3184
INGALLONSPER MINUTE
ENTERING/ 44 °F / 54 °F
LEAVINGCHILLEDWATERTEMP, °F

Estimate Flow for Chilled Water in Gallons per minute for Fan Coil
GIVEN:
𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦 (𝑓𝑜𝑟 𝐹𝑎𝑛 𝐶𝑜𝑖𝑙 𝑅𝑜𝑜𝑚 301) = (𝑐𝑜𝑛𝑣𝑒𝑟𝑡 𝐺𝑇𝐻)𝑇𝑜𝑛𝑠
𝑇𝑒𝑟𝑚𝑖𝑛𝑎𝑙 𝐷𝑖𝑓𝑓𝑒𝑟𝑒𝑛𝑐𝑒 (𝑇𝐷) = 10℉
12 000 𝑥 𝑇𝑅
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 𝑇𝐷
12 000 𝑥 1.7993
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 10

CHILLED WATER FLOW = 4.3184 GPM

1
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

FAN COILED SELECTED DATA


ITEM FANCOILUNIT(13.5Hours)
UNITMODEL/SIZE HFCA08C000A /Size 08
NOMINALAIRFLOW 800
GRANDTOTALHEAT(TC) 26130
TOTALSENSIBLEHEAT(SC) 20710
FINTYPE Slit
FINTYPEPERINCH 15
NO.OFROWCOIL 3
DRAINCONNECTIONSIZE 1/2
FANTYPE Centrifugal
NO.USED 2
DRIVETYPE Direct
MOTORPOWER,W 59
ENTERINGDRYBULB/ENTERINGWETBULB 80/ 67
LEAVINGDRYBULB/LEAVINGWETBULB 57.7/ 56.6
CHILLEDWATERFLOWINGALLONSPERMI
5.21
NUTE
WATERPRESSUREDROPPD,FTINWATER 13.115

2
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

SCHEMATICDIAGRAMOFFANCOILUNITSHOWINGTHE
DIFFERENT PARAMETERS
TRANECOOLINGCOILAIRSIDE
FCU302(13.5Hours)

Water Pressure Drop = 13.115 ft WG

Dcfm = 800 cfm


Fan Type:
Centrifugal

GPM = 5.21 GPM

3
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
HIGHLIGHTED SELECTED DATA ON THE BROCHURE

INTERPOLATING:
43 − 44 27.50 − 𝑇𝐶
= → 𝑻𝑪 = 𝟐𝟔. 𝟏𝟑
43 − 45 27.50 − 24.76
43 − 44 21.34 − 𝑆𝐶
= → 𝑺𝑪 = 𝟐𝟎. 𝟕𝟏
43 − 45 21.34 − 20.08
43 − 44 5.48 − 𝐺𝑃𝑀
= → 𝑮𝑷𝑴 = 𝟓. 𝟐𝟏
43 − 45 5.48 − 4.94
43 − 44 14.36 − 𝑃𝐷
= → 𝑷𝑫 = 𝟏𝟑. 𝟏𝟏𝟓
43 − 45 14.36 − 11.87

4
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

HOTEL ROOM 302


FAN COIL UNIT SELECTION DATA
ITEM FAN COIL UNIT ROOM 302
2.2322
CAPACITY INTONS
26786.27
GRANDTOTALHEAT(TC)
20532.47
TOTALSENSIBLEHEAT(SC)
1040.22
DEHUMIDIFIEDCFM
ENTERINGDRY BULB/ 78.31 / 67.20
ENTERINGWETBULB
LEAVINGDRY 59.28 / 58.50
BULB/LEAVINGWETBULB
CHILLEDWATERFLOW 5.3573
INGALLONSPER MINUTE
ENTERING/ 44 °F / 54 °F
LEAVINGCHILLEDWATERTEMP, °F

Estimate Flow for Chilled Water in Gallons per minute for Fan Coil
GIVEN:
𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦 (𝑓𝑜𝑟 𝐹𝑎𝑛 𝐶𝑜𝑖𝑙 𝑅𝑜𝑜𝑚 302) = (𝑐𝑜𝑛𝑣𝑒𝑟𝑡 𝐺𝑇𝐻)𝑇𝑜𝑛𝑠
𝑇𝑒𝑟𝑚𝑖𝑛𝑎𝑙 𝐷𝑖𝑓𝑓𝑒𝑟𝑒𝑛𝑐𝑒 (𝑇𝐷) = 10℉
12 000 𝑥 𝑇𝑅
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 𝑇𝐷
12 000 𝑥 2.2322
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 10

CHILLED WATER FLOW = 5.3573 GPM

5
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

FAN COILED SELECTED DATA


ITEM FANCOILUNIT(13.5Hours)
UNITMODEL/SIZE HFCA08C000A /Size 08
NOMINALAIRFLOW 12000
GRANDTOTALHEAT(TC) 40450
TOTALSENSIBLEHEAT(SC) 32545
FINTYPE
FINTYPEPERINCH 18
NO.OFROWCOIL 3
DRAINCONNECTIONSIZE 1/2
FANTYPE Centrifugal
NO.USED 2
DRIVETYPE Direct
MOTORPOWER,W 59
ENTERINGDRYBULB/ENTERINGWETBULB 80/ 67
LEAVINGDRYBULB/LEAVINGWETBULB 57.7/ 56.6
CHILLEDWATERFLOWINGALLONSPERMI
20.645
NUTE
WATERPRESSUREDROPPD,FTINWATER 10.445

6
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

SCHEMATICDIAGRAMOFFANCOILUNITSHOWINGTHE
DIFFERENT PARAMETERS
TRANECOOLINGCOILAIRSIDE
FCU302(13.5Hours)

Water Pressure Drop = 10.445 ft WG

Dcfm = 800 cfm


Fan Type:
Centrifugal

GPM = 20.645 GPM

7
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
HIGHLIGHTED SELECTED DATA ON THE BROCHURE

INTERPOLATING:
43 − 44 42.55 − 𝑇𝐶
= → 𝑻𝑪 = 𝟒𝟎. 𝟒𝟓
43 − 45 42.55 − 38.35
43 − 44 33.29 − 𝑆𝐶
= → 𝑺𝑪 = 𝟑𝟐. 𝟓𝟒𝟓
43 − 45 33.29 − 31.8
43 − 44 33.29 − 𝐺𝑃𝑀
= → 𝑮𝑷𝑴 = 𝟐𝟎. 𝟔𝟒𝟓
43 − 45 33.29 − 7.64
43 − 44 8.48 − 𝑃𝐷
= → 𝑷𝑫 = 𝟏𝟎. 𝟒𝟒𝟓
43 − 45 8.48 − 12.81

8
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

HOTEL ROOM 303


FAN COIL UNIT SELECTION DATA
ITEM FAN COIL UNIT ROOM 303
1.4698
CAPACITY INTONS
17637.54
GRANDTOTALHEAT(TC)
TOTALSENSIBLEHEAT(SC) 11383.74
494.42
DEHUMIDIFIEDCFM
ENTERINGDRY BULB/ 80.85 / 69.40
ENTERINGWETBULB
LEAVINGDRY 59.54 / 58.80
BULB/LEAVINGWETBULB
CHILLEDWATERFLOW 3.5275
INGALLONSPER MINUTE
ENTERING/ 44 °F / 54 °F
LEAVINGCHILLEDWATERTEMP, °F

Estimate Flow for Chilled Water in Gallons per minute for Fan Coil
GIVEN:
𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦 (𝑓𝑜𝑟 𝐹𝑎𝑛 𝐶𝑜𝑖𝑙 𝑅𝑜𝑜𝑚 303) = (𝑐𝑜𝑛𝑣𝑒𝑟𝑡 𝐺𝑇𝐻)𝑇𝑜𝑛𝑠
𝑇𝑒𝑟𝑚𝑖𝑛𝑎𝑙 𝐷𝑖𝑓𝑓𝑒𝑟𝑒𝑛𝑐𝑒 (𝑇𝐷) = 10℉
12 000 𝑥 𝑇𝑅
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 𝑇𝐷
12 000 𝑥 1.4698
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 10

9
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

CHILLED WATER FLOW = 3.5275 GPM

FAN COILED SELECTED DATA


ITEM FANCOILUNIT(13.5Hours)
UNITMODEL/SIZE HFCA06C000A /Size 06
NOMINALAIRFLOW 600
GRANDTOTALHEAT(TC) 19060
TOTALSENSIBLEHEAT(SC) 13720
FINTYPE Slit
FINTYPEPERINCH 12
NO.OFROWCOIL 3
DRAINCONNECTIONSIZE 1/2
FANTYPE Centrifugal
NO.USED 2
DRIVETYPE Direct
MOTORPOWER,W 47
ENTERINGDRYBULB/ENTERINGWETBULB 80/ 67
LEAVINGDRYBULB/LEAVINGWETBULB 57.7/ 56.6
CHILLEDWATERFLOWINGALLONSPERMI
3.80
NUTE
WATERPRESSUREDROPPD,FTINWATER 6.175

10
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

SCHEMATICDIAGRAMOFFANCOILUNITSHOWINGTHE
DIFFERENT PARAMETERS
TRANECOOLINGCOILAIRSIDE
FCU303(13.5Hours)

11
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

HIGHLIGHTED SELECTED DATA ON THE BROCHURE

INTERPOLATING:
43 − 44 20.12 − 𝑇𝐶
= → 𝑻𝑪 = 𝟏𝟗. 𝟎𝟔
43 − 45 20.12 − 18
43 − 44 14.14 − 𝑆𝐶
= → 𝑺𝑪 = 𝟏𝟑. 𝟕𝟐
43 − 45 14.14 − 13.30
43 − 44 4.01 − 𝐺𝑃𝑀
= → 𝑮𝑷𝑴 = 𝟑. 𝟖𝟎
43 − 45 4.01 − 3.59
43 − 44 6.79 − 𝑃𝐷
= → 𝑷𝑫 = 𝟔. 𝟏𝟕𝟓
43 − 45 6.79 − 5.56

12
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

HOTEL ROOM 304


FAN COIL UNIT SELECTION DATA
ITEM FAN COIL UNIT ROOM 304

CAPACITY INTONS 1.4537

GRANDTOTALHEAT(TC) 17444.20
11190.40
TOTALSENSIBLEHEAT(SC)
DEHUMIDIFIEDCFM 483.86

ENTERINGDRY BULB/ 80.96 / 69.60


ENTERINGWETBULB
LEAVINGDRY 58.24 / 58.90
BULB/LEAVINGWETBULB
CHILLEDWATERFLOW 3.4888
INGALLONSPER MINUTE
ENTERING/ 44 °F / 54 °F
LEAVINGCHILLEDWATERTEMP, °F

Estimate Flow for Chilled Water in Gallons per minute for Fan Coil
GIVEN:
𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦 (𝑓𝑜𝑟 𝐹𝑎𝑛 𝐶𝑜𝑖𝑙 𝑅𝑜𝑜𝑚 304) = (𝑐𝑜𝑛𝑣𝑒𝑟𝑡 𝐺𝑇𝐻)𝑇𝑜𝑛𝑠
𝑇𝑒𝑟𝑚𝑖𝑛𝑎𝑙 𝐷𝑖𝑓𝑓𝑒𝑟𝑒𝑛𝑐𝑒 (𝑇𝐷) = 10℉
12 000 𝑥 𝑇𝑅
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 𝑇𝐷
12 000 𝑥 1.4537
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 10

13
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

CHILLED WATER FLOW = 3.4888 GPM

FAN COILED SELECTED DATA


ITEM FANCOILUNIT(13.5Hours)
UNITMODEL/SIZE HFCA06C000A /Size 06
NOMINALAIRFLOW 600
GRANDTOTALHEAT(TC) 19060
TOTALSENSIBLEHEAT(SC) 13720
FINTYPE Slit
FINTYPEPERINCH 12
NO.OFROWCOIL 3
DRAINCONNECTIONSIZE 1/2
FANTYPE Centrifugal
NO.USED 2
DRIVETYPE Direct
MOTORPOWER,W 47
ENTERINGDRYBULB/ENTERINGWETBULB 80/ 67
LEAVINGDRYBULB/LEAVINGWETBULB 57.7/ 56.6
CHILLEDWATERFLOWINGALLONSPERMI
3.80
NUTE
WATERPRESSUREDROPPD,FTINWATER 6.175

14
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

SCHEMATICDIAGRAMOFFANCOILUNITSHOWINGTHE
DIFFERENT PARAMETERS
TRANECOOLINGCOILAIRSIDE
FCU304(13.5Hours)

15
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

HIGHLIGHTED SELECTED DATA ON THE BROCHURE

INTERPOLATING:
43 − 44 20.12 − 𝑇𝐶
= → 𝑻𝑪 = 𝟏𝟗. 𝟎𝟔
43 − 45 20.12 − 18
43 − 44 14.14 − 𝑆𝐶
= → 𝑺𝑪 = 𝟏𝟑. 𝟕𝟐
43 − 45 14.14 − 13.30
43 − 44 4.01 − 𝐺𝑃𝑀
= → 𝑮𝑷𝑴 = 𝟑. 𝟖𝟎
43 − 45 4.01 − 3.59
43 − 44 6.79 − 𝑃𝐷
= → 𝑷𝑫 = 𝟔. 𝟏𝟕𝟓
43 − 45 6.79 − 5.56

16
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

HOTEL ROOM 305


FAN COIL UNIT SELECTION DATA
ITEM FAN COIL UNIT ROOM 305
1.4500
CAPACITY INTONS
17400.07
GRANDTOTALHEAT(TC)
11146.27
TOTALSENSIBLEHEAT(SC)
481.45
DEHUMIDIFIEDCFM
ENTERINGDRY BULB/ 80.98 / 69.60
ENTERINGWETBULB
LEAVINGDRY 59.55 / 58.90
BULB/LEAVINGWETBULB
CHILLEDWATERFLOW 3.4800
INGALLONSPER MINUTE
ENTERING/ 44 °F / 54 °F
LEAVINGCHILLEDWATERTEMP, °F

Estimate Flow for Chilled Water in Gallons per minute for Fan Coil
GIVEN:
𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦 (𝑓𝑜𝑟 𝐹𝑎𝑛 𝐶𝑜𝑖𝑙 𝑅𝑜𝑜𝑚 305) = (𝑐𝑜𝑛𝑣𝑒𝑟𝑡 𝐺𝑇𝐻)𝑇𝑜𝑛𝑠
𝑇𝑒𝑟𝑚𝑖𝑛𝑎𝑙 𝐷𝑖𝑓𝑓𝑒𝑟𝑒𝑛𝑐𝑒 (𝑇𝐷) = 10℉
12 000 𝑥 𝑇𝑅
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 𝑇𝐷
12 000 𝑥 1.4500
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 10

CHILLED WATER FLOW = 3.4800 GPM

17
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

FAN COILED SELECTED DATA


ITEM FANCOILUNIT(13.5Hours)
UNITMODEL/SIZE HFCA06C000A /Size 06
NOMINALAIRFLOW 600
GRANDTOTALHEAT(TC) 19060
TOTALSENSIBLEHEAT(SC) 13720
FINTYPE Slit
FINTYPEPERINCH 12
NO.OFROWCOIL 3
DRAINCONNECTIONSIZE 1/2
FANTYPE Centrifugal
NO.USED 2
DRIVETYPE Direct
MOTORPOWER,W 47
ENTERINGDRYBULB/ENTERINGWETBULB 80/ 67
LEAVINGDRYBULB/LEAVINGWETBULB 57.7/ 56.6
CHILLEDWATERFLOWINGALLONSPERMI
3.80
NUTE
WATERPRESSUREDROPPD,FTINWATER 6.175

18
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

SCHEMATICDIAGRAMOFFANCOILUNITSHOWINGTHE
DIFFERENT PARAMETERS
TRANECOOLINGCOILAIRSIDE
FCU305(13.5Hours)

19
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

HIGHLIGHTED SELECTED DATA ON THE BROCHURE

INTERPOLATING:
43 − 44 20.12 − 𝑇𝐶
= → 𝑻𝑪 = 𝟏𝟗. 𝟎𝟔
43 − 45 20.12 − 18
43 − 44 14.14 − 𝑆𝐶
= → 𝑺𝑪 = 𝟏𝟑. 𝟕𝟐
43 − 45 14.14 − 13.30
43 − 44 4.01 − 𝐺𝑃𝑀
= → 𝑮𝑷𝑴 = 𝟑. 𝟖𝟎
43 − 45 4.01 − 3.59
43 − 44 6.79 − 𝑃𝐷
= → 𝑷𝑫 = 𝟔. 𝟏𝟕𝟓
43 − 45 6.79 − 5.56

20
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

HOTEL ROOM 306


FAN COIL UNIT SELECTION DATA
ITEM FAN COIL UNIT ROOM 306

CAPACITY INTONS 1.4928

GRANDTOTALHEAT(TC) 17914.05
11660.25
TOTALSENSIBLEHEAT(SC)
509.53
DEHUMIDIFIEDCFM
ENTERINGDRY BULB/ 80.71 / 69.20
ENTERINGWETBULB
LEAVINGDRY 59.52 / 58.70
BULB/LEAVINGWETBULB
CHILLEDWATERFLOW 3.5828
INGALLONSPER MINUTE
ENTERING/ 44 °F / 54 °F
LEAVINGCHILLEDWATERTEMP, °F

Estimate Flow for Chilled Water in Gallons per minute for Fan Coil
GIVEN:
𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦 (𝑓𝑜𝑟 𝐹𝑎𝑛 𝐶𝑜𝑖𝑙 𝑅𝑜𝑜𝑚 306) = (𝑐𝑜𝑛𝑣𝑒𝑟𝑡 𝐺𝑇𝐻)𝑇𝑜𝑛𝑠
𝑇𝑒𝑟𝑚𝑖𝑛𝑎𝑙 𝐷𝑖𝑓𝑓𝑒𝑟𝑒𝑛𝑐𝑒 (𝑇𝐷) = 10℉
12 000 𝑥 𝑇𝑅
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 𝑇𝐷
12 000 𝑥 1.4928
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 10

CHILLED WATER FLOW = 3.5828 GPM

21
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

FAN COILED SELECTED DATA


ITEM FANCOILUNIT(13.5Hours)
UNITMODEL/SIZE HFCA06C000A /Size 06
NOMINALAIRFLOW 600
GRANDTOTALHEAT(TC) 19060
TOTALSENSIBLEHEAT(SC) 13720
FINTYPE Slit
FINTYPEPERINCH 12
NO.OFROWCOIL 3
DRAINCONNECTIONSIZE 1/2
FANTYPE Centrifugal
NO.USED 2
DRIVETYPE Direct
MOTORPOWER,W 47
ENTERINGDRYBULB/ENTERINGWETBULB 80/ 67
LEAVINGDRYBULB/LEAVINGWETBULB 57.7/ 56.6
CHILLEDWATERFLOWINGALLONSPERMI
3.80
NUTE
WATERPRESSUREDROPPD,FTINWATER 6.175

22
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

SCHEMATICDIAGRAMOFFANCOILUNITSHOWINGTHE
DIFFERENT PARAMETERS
TRANECOOLINGCOILAIRSIDE
FCU306(13.5Hours)

23
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

HIGHLIGHTED SELECTED DATA ON THE BROCHURE

INTERPOLATING:
43 − 44 20.12 − 𝑇𝐶
= → 𝑻𝑪 = 𝟏𝟗. 𝟎𝟔
43 − 45 20.12 − 18
43 − 44 14.14 − 𝑆𝐶
= → 𝑺𝑪 = 𝟏𝟑. 𝟕𝟐
43 − 45 14.14 − 13.30
43 − 44 4.01 − 𝐺𝑃𝑀
= → 𝑮𝑷𝑴 = 𝟑. 𝟖𝟎
43 − 45 4.01 − 3.59
43 − 44 6.79 − 𝑃𝐷
= → 𝑷𝑫 = 𝟔. 𝟏𝟕𝟓
43 − 45 6.79 − 5.56

24
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

HOTEL ROOM 307


FAN COIL UNIT SELECTION DATA
ITEM FAN COIL UNIT ROOM 307
2.0982
CAPACITY INTONS
GRANDTOTALHEAT(TC) 25178.06

TOTALSENSIBLEHEAT(SC) 18924.26
948.30
DEHUMIDIFIEDCFM
ENTERINGDRY BULB/ 78.53 / 67.20
ENTERINGWETBULB
LEAVINGDRY 59.15 / 58.80
BULB/LEAVINGWETBULB
CHILLEDWATERFLOW 5.0356
INGALLONSPER MINUTE
ENTERING/ 44 °F / 54 °F
LEAVINGCHILLEDWATERTEMP, °F

Estimate Flow for Chilled Water in Gallons per minute for Fan Coil
GIVEN:
𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦 (𝑓𝑜𝑟 𝐹𝑎𝑛 𝐶𝑜𝑖𝑙 𝑅𝑜𝑜𝑚 307) = (𝑐𝑜𝑛𝑣𝑒𝑟𝑡 𝐺𝑇𝐻)𝑇𝑜𝑛𝑠
𝑇𝑒𝑟𝑚𝑖𝑛𝑎𝑙 𝐷𝑖𝑓𝑓𝑒𝑟𝑒𝑛𝑐𝑒 (𝑇𝐷) = 10℉
12 000 𝑥 𝑇𝑅
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 𝑇𝐷
12 000 𝑥 2.0982
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 10

CHILLED WATER FLOW = 5.0356 GPM

25
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

FAN COILED SELECTED DATA


ITEM FANCOILUNIT(13.5Hours)
UNITMODEL/SIZE HFCA10C0010A /Size 10

NOMINALAIRFLOW 1000
GRANDTOTALHEAT(TC) 33465
TOTALSENSIBLEHEAT(SC) 26550
FINTYPE Louver
FINTYPEPERINCH 18
NO.OFROWCOIL 3
DRAINCONNECTIONSIZE 1/2
FANTYPE Centrifugal
NO.USED 2
DRIVETYPE Direct
MOTORPOWER,W 162
ENTERINGDRYBULB/ENTERINGWETBULB 80/ 67
LEAVINGDRYBULB/LEAVINGWETBULB 57.7/ 56.6
CHILLEDWATERFLOWINGALLONSPERMI
6.67
NUTE
WATERPRESSUREDROPPD,FTINWATER 8.70

26
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

SCHEMATICDIAGRAMOFFANCOILUNITSHOWINGTHE
DIFFERENT PARAMETERS
TRANECOOLINGCOILAIRSIDE
FCU307(13.5Hours)

27
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

HIGHLIGHTED SELECTED DATA ON THE BROCHURE

INTERPOLATING:
43 − 44 35.23 − 𝑇𝐶
= → 𝑻𝑪 = 𝟑𝟑. 𝟒𝟔𝟓
43 − 45 35.23 − 31.70
43 − 44 27.33 − 𝑆𝐶
= → 𝑺𝑪 = 𝟐𝟔. 𝟓𝟓
43 − 45 27.33 − 25.77
43 − 44 7.02 − 𝐺𝑃𝑀
= → 𝑮𝑷𝑴 = 𝟔. 𝟔𝟕
43 − 45 7.02 − 6.32
43 − 44 9.53 − 𝑃𝐷
= → 𝑷𝑫 = 𝟖. 𝟕𝟎
43 − 45 9.53 − 7.87

28
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

HOTEL ROOM 308


FAN COIL UNIT SELECTION DATA
ITEM FAN COIL UNIT ROOM 308
1.4500
CAPACITY INTONS
GRANDTOTALHEAT(TC) 17400.07

TOTALSENSIBLEHEAT(SC) 11146.27
481.45
DEHUMIDIFIEDCFM
ENTERINGDRY BULB/ 80.98 / 69.60
ENTERINGWETBULB
LEAVINGDRY 59.55 / 58.90
BULB/LEAVINGWETBULB
CHILLEDWATERFLOW 3.4800
INGALLONSPER MINUTE
ENTERING/ 44 °F / 54 °F
LEAVINGCHILLEDWATERTEMP, °F

Estimate Flow for Chilled Water in Gallons per minute for Fan Coil
GIVEN:
𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦 (𝑓𝑜𝑟 𝐹𝑎𝑛 𝐶𝑜𝑖𝑙 𝑅𝑜𝑜𝑚 305) = (𝑐𝑜𝑛𝑣𝑒𝑟𝑡 𝐺𝑇𝐻)𝑇𝑜𝑛𝑠
𝑇𝑒𝑟𝑚𝑖𝑛𝑎𝑙 𝐷𝑖𝑓𝑓𝑒𝑟𝑒𝑛𝑐𝑒 (𝑇𝐷) = 10℉
12 000 𝑥 𝑇𝑅
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 𝑇𝐷
12 000 𝑥 1.4500
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 10

29
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

CHILLED WATER FLOW = 3.4800 GPM

FAN COILED SELECTED DATA


ITEM FANCOILUNIT(13.5Hours)
UNITMODEL/SIZE HFCA06C000A /Size 06
NOMINALAIRFLOW 600
GRANDTOTALHEAT(TC) 19060
TOTALSENSIBLEHEAT(SC) 13720
FINTYPE Slit
FINTYPEPERINCH 12
NO.OFROWCOIL 3
DRAINCONNECTIONSIZE 1/2
FANTYPE Centrifugal
NO.USED 2
DRIVETYPE Direct
MOTORPOWER,W 47
ENTERINGDRYBULB/ENTERINGWETBULB 80/ 67
LEAVINGDRYBULB/LEAVINGWETBULB 57.7/ 56.6
CHILLEDWATERFLOWINGALLONSPERMI
3.80
NUTE
WATERPRESSUREDROPPD,FTINWATER 6.175

30
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

SCHEMATICDIAGRAMOFFANCOILUNITSHOWINGTHE
DIFFERENT PARAMETERS
TRANECOOLINGCOILAIRSIDE
FCU308(13.5Hours)

31
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

HIGHLIGHTED SELECTED DATA ON THE BROCHURE

INTERPOLATING:
43 − 44 20.12 − 𝑇𝐶
= → 𝑻𝑪 = 𝟏𝟗. 𝟎𝟔
43 − 45 20.12 − 18
43 − 44 14.14 − 𝑆𝐶
= → 𝑺𝑪 = 𝟏𝟑. 𝟕𝟐
43 − 45 14.14 − 13.30
43 − 44 4.01 − 𝐺𝑃𝑀
= → 𝑮𝑷𝑴 = 𝟑. 𝟖𝟎
43 − 45 4.01 − 3.59
43 − 44 6.79 − 𝑃𝐷
= → 𝑷𝑫 = 𝟔. 𝟏𝟕𝟓
43 − 45 6.79 − 5.56

32
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

HOTEL ROOM 309


FAN COIL UNIT SELECTION DATA
ITEM FAN COIL UNIT ROOM 309
1.9212
CAPACITY INTONS
23054.37
GRANDTOTALHEAT(TC)
TOTALSENSIBLEHEAT(SC) 16800.57
819.33
DEHUMIDIFIEDCFM
ENTERINGDRY BULB/ 78.93 / 67.50
ENTERINGWETBULB
LEAVINGDRY 59.04 / 58.40
BULB/LEAVINGWETBULB
CHILLEDWATERFLOW 4.6109
INGALLONSPER MINUTE
ENTERING/ 44 °F / 54 °F
LEAVINGCHILLEDWATERTEMP, °F

Estimate Flow for Chilled Water in Gallons per minute for Fan Coil
GIVEN:
𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦 (𝑓𝑜𝑟 𝐹𝑎𝑛 𝐶𝑜𝑖𝑙 𝑅𝑜𝑜𝑚 309) = (𝑐𝑜𝑛𝑣𝑒𝑟𝑡 𝐺𝑇𝐻)𝑇𝑜𝑛𝑠
𝑇𝑒𝑟𝑚𝑖𝑛𝑎𝑙 𝐷𝑖𝑓𝑓𝑒𝑟𝑒𝑛𝑐𝑒 (𝑇𝐷) = 10℉
12 000 𝑥 𝑇𝑅
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 𝑇𝐷
12 000 𝑥 1.9212
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 10

33
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

CHILLED WATER FLOW = 4.6109 GPM

FAN COILED SELECTED DATA


ITEM FANCOILUNIT(13.5Hours)
UNITMODEL/SIZE HFCA10C0010A /Size 10

NOMINALAIRFLOW 1000
GRANDTOTALHEAT(TC) 33465
TOTALSENSIBLEHEAT(SC) 26550
FINTYPE Louver
FINTYPEPERINCH 18
NO.OFROWCOIL 3
DRAINCONNECTIONSIZE 1/2
FANTYPE Centrifugal
NO.USED 2
DRIVETYPE Direct
MOTORPOWER,W 162
ENTERINGDRYBULB/ENTERINGWETBULB 80/ 67
LEAVINGDRYBULB/LEAVINGWETBULB 57.7/ 56.6
CHILLEDWATERFLOWINGALLONSPERMI
6.67
NUTE
WATERPRESSUREDROPPD,FTINWATER 8.70

34
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

SCHEMATICDIAGRAMOFFANCOILUNITSHOWINGTHE
DIFFERENT PARAMETERS
TRANECOOLINGCOILAIRSIDE
FCU309(13.5Hours)

35
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

HIGHLIGHTED SELECTED DATA ON THE BROCHURE

INTERPOLATING:
43 − 44 35.23 − 𝑇𝐶
= → 𝑻𝑪 = 𝟑𝟑. 𝟒𝟔𝟓
43 − 45 35.23 − 31.70
43 − 44 27.33 − 𝑆𝐶
= → 𝑺𝑪 = 𝟐𝟔. 𝟓𝟓
43 − 45 27.33 − 25.77
43 − 44 7.02 − 𝐺𝑃𝑀
= → 𝑮𝑷𝑴 = 𝟔. 𝟔𝟕
43 − 45 7.02 − 6.32
43 − 44 9.53 − 𝑃𝐷
= → 𝑷𝑫 = 𝟖. 𝟕𝟎
43 − 45 9.53 − 7.87

36
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

HOTEL ROOM 310


FAN COIL UNIT SELECTION DATA
ITEM FAN COIL UNIT ROOM 310
1.5557
CAPACITY INTONS
GRANDTOTALHEAT(TC) 18668.18

TOTALSENSIBLEHEAT(SC) 12414.38
522.96
DEHUMIDIFIEDCFM
ENTERINGDRY BULB/ 80.64 °F / 69.2 °F
ENTERINGWETBULB
LEAVINGDRY 59.54 °F / 58.8 °F
BULB/LEAVINGWETBULB
CHILLEDWATERFLOW 3.6089 GPM
INGALLONSPER MINUTE
ENTERING/ 44 °F / 54 °F
LEAVINGCHILLEDWATERTEMP, °F

Estimate Flow for Chilled Water in Gallons per minute for Fan Coil
GIVEN:
𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦 (𝑓𝑜𝑟 𝐹𝑎𝑛 𝐶𝑜𝑖𝑙 𝑅𝑜𝑜𝑚 310) = (𝑐𝑜𝑛𝑣𝑒𝑟𝑡 𝐺𝑇𝐻)𝑇𝑜𝑛𝑠
𝑇𝑒𝑟𝑚𝑖𝑛𝑎𝑙 𝐷𝑖𝑓𝑓𝑒𝑟𝑒𝑛𝑐𝑒 (𝑇𝐷) = 10℉
12 000 𝑥 𝑇𝑅
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 𝑇𝐷
12 000 𝑥 1.5037
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 10

CHILLED WATER FLOW = 3.6089 GPM

37
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

FAN COILED SELECTED DATA


ITEM FANCOILUNIT(13.5Hours)
UNITMODEL/SIZE HFCA06C000A /Size 06
NOMINALAIRFLOW 600
GRANDTOTALHEAT(TC) 19060
TOTALSENSIBLEHEAT(SC) 13720
FINTYPE Slit
FINTYPEPERINCH 12
NO.OFROWCOIL 3
DRAINCONNECTIONSIZE 1/2
FANTYPE Centrifugal
NO.USED 2
DRIVETYPE Direct
MOTORPOWER,W 47
ENTERINGDRYBULB/ENTERINGWETBULB 80/ 67
LEAVINGDRYBULB/LEAVINGWETBULB 57.7/ 56.6
CHILLEDWATERFLOWINGALLONSPERMI
3.80
NUTE
WATERPRESSUREDROPPD,FTINWATER 6.175

38
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

SCHEMATICDIAGRAMOFFANCOILUNITSHOWINGTHE
DIFFERENT PARAMETERS
TRANECOOLINGCOILAIRSIDE
FCU310(13.5Hours)

39
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
HIGHLIGHTED SELECTED DATA ON THE BROCHURE

INTERPOLATING:
43 − 44 20.12 − 𝑇𝐶
= → 𝑻𝑪 = 𝟏𝟗. 𝟎𝟔
43 − 45 20.12 − 18
43 − 44 14.14 − 𝑆𝐶
= → 𝑺𝑪 = 𝟏𝟑. 𝟕𝟐
43 − 45 14.14 − 13.30
43 − 44 4.01 − 𝐺𝑃𝑀
= → 𝑮𝑷𝑴 = 𝟑. 𝟖𝟎
43 − 45 4.01 − 3.59
43 − 44 6.79 − 𝑃𝐷
= → 𝑷𝑫 = 𝟔. 𝟏𝟕𝟓
43 − 45 6.79 − 5.56

40
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

HOTEL ROOM 311


FAN COIL UNIT SELECTION DATA
ITEM FAN COIL UNIT ROOM 311
1.9013
CAPACITY INTONS
GRANDTOTALHEAT(TC) 22815.33

TOTALSENSIBLEHEAT(SC) 16561.53
805.79
DEHUMIDIFIEDCFM
ENTERINGDRY BULB/ 78.93 / 67.50
ENTERINGWETBULB
LEAVINGDRY 59.04 / 58.40
BULB/LEAVINGWETBULB
CHILLEDWATERFLOW 4.5631
INGALLONSPER MINUTE
ENTERING/ 44 °F / 54 °F
LEAVINGCHILLEDWATERTEMP, °F

Estimate Flow for Chilled Water in Gallons per minute for Fan Coil
GIVEN:
𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦 (𝑓𝑜𝑟 𝐹𝑎𝑛 𝐶𝑜𝑖𝑙 𝑅𝑜𝑜𝑚 309) = (𝑐𝑜𝑛𝑣𝑒𝑟𝑡 𝐺𝑇𝐻)𝑇𝑜𝑛𝑠
𝑇𝑒𝑟𝑚𝑖𝑛𝑎𝑙 𝐷𝑖𝑓𝑓𝑒𝑟𝑒𝑛𝑐𝑒 (𝑇𝐷) = 10℉
12 000 𝑥 𝑇𝑅
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 𝑇𝐷
12 000 𝑥 1.9013
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 10

CHILLED WATER FLOW = 4.5613 GPM

41
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

FAN COILED SELECTED DATA


ITEM FANCOILUNIT(13.5Hours)
UNITMODEL/SIZE HFCA10C0010A /Size 10

NOMINALAIRFLOW 1000
GRANDTOTALHEAT(TC) 33465
TOTALSENSIBLEHEAT(SC) 26550
FINTYPE Louver
FINTYPEPERINCH 18
NO.OFROWCOIL 3
DRAINCONNECTIONSIZE 1/2
FANTYPE Centrifugal
NO.USED 2
DRIVETYPE Direct
MOTORPOWER,W 162
ENTERINGDRYBULB/ENTERINGWETBULB 80/ 67
LEAVINGDRYBULB/LEAVINGWETBULB 57.7/ 56.6
CHILLEDWATERFLOWINGALLONSPERMI
6.67
NUTE
WATERPRESSUREDROPPD,FTINWATER 8.70

42
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

SCHEMATICDIAGRAMOFFANCOILUNITSHOWINGTHE
DIFFERENT PARAMETERS
TRANECOOLINGCOILAIRSIDE
FCU311(13.5Hours)

43
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
HIGHLIGHTED SELECTED DATA ON THE BROCHURE

INTERPOLATING:
43 − 44 35.23 − 𝑇𝐶
= → 𝑻𝑪 = 𝟑𝟑. 𝟒𝟔𝟓
43 − 45 35.23 − 31.70
43 − 44 27.33 − 𝑆𝐶
= → 𝑺𝑪 = 𝟐𝟔. 𝟓𝟓
43 − 45 27.33 − 25.77
43 − 44 7.02 − 𝐺𝑃𝑀
= → 𝑮𝑷𝑴 = 𝟔. 𝟔𝟕
43 − 45 7.02 − 6.32
43 − 44 9.53 − 𝑃𝐷
= → 𝑷𝑫 = 𝟖. 𝟕𝟎
43 − 45 9.53 − 7.87

44
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

HOTEL ROOM 312


FAN COIL UNIT SELECTION DATA
ITEM FAN COIL UNIT ROOM 312
1.5849
CAPACITY INTONS
19018.54
GRANDTOTALHEAT(TC)
12764.74
TOTALSENSIBLEHEAT(SC)
541.13
DEHUMIDIFIEDCFM
ENTERINGDRY BULB/ 80.64 °F / 69.2 °F
ENTERINGWETBULB
LEAVINGDRY 59.54 °F / 58.8 °F
BULB/LEAVINGWETBULB
CHILLEDWATERFLOW 3.6089 GPM
INGALLONSPER MINUTE
ENTERING/ 44 °F / 54 °F
LEAVINGCHILLEDWATERTEMP, °F

Estimate Flow for Chilled Water in Gallons per minute for Fan Coil
GIVEN:
𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦 (𝑓𝑜𝑟 𝐹𝑎𝑛 𝐶𝑜𝑖𝑙 𝑅𝑜𝑜𝑚 312) = (𝑐𝑜𝑛𝑣𝑒𝑟𝑡 𝐺𝑇𝐻)𝑇𝑜𝑛𝑠
𝑇𝑒𝑟𝑚𝑖𝑛𝑎𝑙 𝐷𝑖𝑓𝑓𝑒𝑟𝑒𝑛𝑐𝑒 (𝑇𝐷) = 10℉
12 000 𝑥 𝑇𝑅
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 𝑇𝐷
12 000 𝑥 1.5037
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 10

CHILLED WATER FLOW = 3.6089 GPM

45
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

FAN COILED SELECTED DATA


ITEM FANCOILUNIT(13.5Hours)
UNITMODEL/SIZE HFCA06C000A /Size 06
NOMINALAIRFLOW 600
GRANDTOTALHEAT(TC) 19060
TOTALSENSIBLEHEAT(SC) 13720
FINTYPE Slit
FINTYPEPERINCH 12
NO.OFROWCOIL 3
DRAINCONNECTIONSIZE 1/2
FANTYPE Centrifugal
NO.USED 2
DRIVETYPE Direct
MOTORPOWER,W 47
ENTERINGDRYBULB/ENTERINGWETBULB 80/ 67
LEAVINGDRYBULB/LEAVINGWETBULB 57.7/ 56.6
CHILLEDWATERFLOWINGALLONSPERMI
3.80
NUTE
WATERPRESSUREDROPPD,FTINWATER 6.175

46
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

SCHEMATICDIAGRAMOFFANCOILUNITSHOWINGTHE
DIFFERENT PARAMETERS
TRANECOOLINGCOILAIRSIDE
FCU312(13.5Hours)

47
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
HIGHLIGHTED SELECTED DATA ON THE BROCHURE

INTERPOLATING:
43 − 44 20.12 − 𝑇𝐶
= → 𝑻𝑪 = 𝟏𝟗. 𝟎𝟔
43 − 45 20.12 − 18
43 − 44 14.14 − 𝑆𝐶
= → 𝑺𝑪 = 𝟏𝟑. 𝟕𝟐
43 − 45 14.14 − 13.30
43 − 44 4.01 − 𝐺𝑃𝑀
= → 𝑮𝑷𝑴 = 𝟑. 𝟖𝟎
43 − 45 4.01 − 3.59
43 − 44 6.79 − 𝑃𝐷
= → 𝑷𝑫 = 𝟔. 𝟏𝟕𝟓
43 − 45 6.79 − 5.56

48
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

HOTEL ROOM 313


FAN COIL UNIT SELECTION DATA
ITEM FAN COIL UNIT ROOM 313
1.9013
CAPACITY INTONS
22815.33
GRANDTOTALHEAT(TC)
16561.53
TOTALSENSIBLEHEAT(SC)
805.79
DEHUMIDIFIEDCFM
ENTERINGDRY BULB/ 78.93 / 67.50
ENTERINGWETBULB
LEAVINGDRY 59.04 / 58.40
BULB/LEAVINGWETBULB
CHILLEDWATERFLOW 4.5631
INGALLONSPER MINUTE
ENTERING/ 44 °F / 54 °F
LEAVINGCHILLEDWATERTEMP, °F

Estimate Flow for Chilled Water in Gallons per minute for Fan Coil
GIVEN:
𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦 (𝑓𝑜𝑟 𝐹𝑎𝑛 𝐶𝑜𝑖𝑙 𝑅𝑜𝑜𝑚 309) = (𝑐𝑜𝑛𝑣𝑒𝑟𝑡 𝐺𝑇𝐻)𝑇𝑜𝑛𝑠
𝑇𝑒𝑟𝑚𝑖𝑛𝑎𝑙 𝐷𝑖𝑓𝑓𝑒𝑟𝑒𝑛𝑐𝑒 (𝑇𝐷) = 10℉
12 000 𝑥 𝑇𝑅
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 𝑇𝐷
12 000 𝑥 1.9013
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 10

CHILLED WATER FLOW = 4.5613 GPM

49
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

FAN COILED SELECTED DATA


ITEM FANCOILUNIT(13.5Hours)
UNITMODEL/SIZE HFCA10C0010A /Size 10

NOMINALAIRFLOW 1000
GRANDTOTALHEAT(TC) 33465
TOTALSENSIBLEHEAT(SC) 26550
FINTYPE Louver
FINTYPEPERINCH 18
NO.OFROWCOIL 3
DRAINCONNECTIONSIZE 1/2
FANTYPE Centrifugal
NO.USED 2
DRIVETYPE Direct
MOTORPOWER,W 162
ENTERINGDRYBULB/ENTERINGWETBULB 80/ 67
LEAVINGDRYBULB/LEAVINGWETBULB 57.7/ 56.6
CHILLEDWATERFLOWINGALLONSPERMI
6.67
NUTE
WATERPRESSUREDROPPD,FTINWATER 8.70

50
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

SCHEMATICDIAGRAMOFFANCOILUNITSHOWINGTHE
DIFFERENT PARAMETERS
TRANECOOLINGCOILAIRSIDE
FCU313(13.5Hours)

51
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
HIGHLIGHTED SELECTED DATA ON THE BROCHURE

INTERPOLATING:
43 − 44 35.23 − 𝑇𝐶
= → 𝑻𝑪 = 𝟑𝟑. 𝟒𝟔𝟓
43 − 45 35.23 − 31.70
43 − 44 27.33 − 𝑆𝐶
= → 𝑺𝑪 = 𝟐𝟔. 𝟓𝟓
43 − 45 27.33 − 25.77
43 − 44 7.02 − 𝐺𝑃𝑀
= → 𝑮𝑷𝑴 = 𝟔. 𝟔𝟕
43 − 45 7.02 − 6.32
43 − 44 9.53 − 𝑃𝐷
= → 𝑷𝑫 = 𝟖. 𝟕𝟎
43 − 45 9.53 − 7.87

52
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

HOTEL ROOM 314


FAN COIL UNIT SELECTION DATA
ITEM FAN COIL UNIT ROOM 314
1.4500
CAPACITY INTONS
17400.07
GRANDTOTALHEAT(TC)
11146.27
TOTALSENSIBLEHEAT(SC)
481.45
DEHUMIDIFIEDCFM
ENTERINGDRY BULB/ 80.98 / 69.60
ENTERINGWETBULB
LEAVINGDRY 59.55 / 58.90
BULB/LEAVINGWETBULB
CHILLEDWATERFLOW 3.4800
INGALLONSPER MINUTE
ENTERING/ 44 °F / 54 °F
LEAVINGCHILLEDWATERTEMP, °F

Estimate Flow for Chilled Water in Gallons per minute for Fan Coil
GIVEN:
𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦 (𝑓𝑜𝑟 𝐹𝑎𝑛 𝐶𝑜𝑖𝑙 𝑅𝑜𝑜𝑚 305) = (𝑐𝑜𝑛𝑣𝑒𝑟𝑡 𝐺𝑇𝐻)𝑇𝑜𝑛𝑠
𝑇𝑒𝑟𝑚𝑖𝑛𝑎𝑙 𝐷𝑖𝑓𝑓𝑒𝑟𝑒𝑛𝑐𝑒 (𝑇𝐷) = 10℉
12 000 𝑥 𝑇𝑅
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 𝑇𝐷
12 000 𝑥 1.4500
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 10

CHILLED WATER FLOW = 3.4800 GPM

53
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

FAN COILED SELECTED DATA


ITEM FANCOILUNIT(13.5Hours)
UNITMODEL/SIZE HFCA06C000A /Size 06
NOMINALAIRFLOW 600
GRANDTOTALHEAT(TC) 19060
TOTALSENSIBLEHEAT(SC) 13720
FINTYPE Slit
FINTYPEPERINCH 12
NO.OFROWCOIL 3
DRAINCONNECTIONSIZE 1/2
FANTYPE Centrifugal
NO.USED 2
DRIVETYPE Direct
MOTORPOWER,W 47
ENTERINGDRYBULB/ENTERINGWETBULB 80/ 67
LEAVINGDRYBULB/LEAVINGWETBULB 57.7/ 56.6
CHILLEDWATERFLOWINGALLONSPERMI
3.80
NUTE
WATERPRESSUREDROPPD,FTINWATER 6.175

54
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

SCHEMATICDIAGRAMOFFANCOILUNITSHOWINGTHE
DIFFERENT PARAMETERS
TRANECOOLINGCOILAIRSIDE
FCU314(13.5Hours)

55
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
HIGHLIGHTED SELECTED DATA ON THE BROCHURE

INTERPOLATING:
43 − 44 20.12 − 𝑇𝐶
= → 𝑻𝑪 = 𝟏𝟗. 𝟎𝟔
43 − 45 20.12 − 18
43 − 44 14.14 − 𝑆𝐶
= → 𝑺𝑪 = 𝟏𝟑. 𝟕𝟐
43 − 45 14.14 − 13.30
43 − 44 4.01 − 𝐺𝑃𝑀
= → 𝑮𝑷𝑴 = 𝟑. 𝟖𝟎
43 − 45 4.01 − 3.59
43 − 44 6.79 − 𝑃𝐷
= → 𝑷𝑫 = 𝟔. 𝟏𝟕𝟓
43 − 45 6.79 − 5.56

56
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

HOTEL ROOM 315


FAN COIL UNIT SELECTION DATA
ITEM FAN COIL UNIT ROOM 315
1.9189
CAPACITY INTONS
23026.25
GRANDTOTALHEAT(TC)
16772.45
TOTALSENSIBLEHEAT(SC)
817.74
DEHUMIDIFIEDCFM
ENTERINGDRY BULB/ 78.93 / 67.50
ENTERINGWETBULB
LEAVINGDRY 59.04 / 58.40
BULB/LEAVINGWETBULB
CHILLEDWATERFLOW 4.6052
INGALLONSPER MINUTE
ENTERING/ 44 °F / 54 °F
LEAVINGCHILLEDWATERTEMP, °F

Estimate Flow for Chilled Water in Gallons per minute for Fan Coil
GIVEN:
𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦 (𝑓𝑜𝑟 𝐹𝑎𝑛 𝐶𝑜𝑖𝑙 𝑅𝑜𝑜𝑚 309) = (𝑐𝑜𝑛𝑣𝑒𝑟𝑡 𝐺𝑇𝐻)𝑇𝑜𝑛𝑠
𝑇𝑒𝑟𝑚𝑖𝑛𝑎𝑙 𝐷𝑖𝑓𝑓𝑒𝑟𝑒𝑛𝑐𝑒 (𝑇𝐷) = 10℉
12 000 𝑥 𝑇𝑅
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 𝑇𝐷
12 000 𝑥 1.9189
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 10

CHILLED WATER FLOW = 4.6052 GPM

57
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

FAN COILED SELECTED DATA


ITEM FANCOILUNIT(13.5Hours)
UNITMODEL/SIZE HFCA10C0010A /Size 10

NOMINALAIRFLOW 1000
GRANDTOTALHEAT(TC) 33465
TOTALSENSIBLEHEAT(SC) 26550
FINTYPE Louver
FINTYPEPERINCH 18
NO.OFROWCOIL 3
DRAINCONNECTIONSIZE 1/2
FANTYPE Centrifugal
NO.USED 2
DRIVETYPE Direct
MOTORPOWER,W 162
ENTERINGDRYBULB/ENTERINGWETBULB 80/ 67
LEAVINGDRYBULB/LEAVINGWETBULB 57.7/ 56.6
CHILLEDWATERFLOWINGALLONSPERMI
6.67
NUTE
WATERPRESSUREDROPPD,FTINWATER 8.70

58
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

SCHEMATICDIAGRAMOFFANCOILUNITSHOWINGTHE
DIFFERENT PARAMETERS
TRANECOOLINGCOILAIRSIDE
FCU315(13.5Hours)

59
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
HIGHLIGHTED SELECTED DATA ON THE BROCHURE

INTERPOLATING:
43 − 44 35.23 − 𝑇𝐶
= → 𝑻𝑪 = 𝟑𝟑. 𝟒𝟔𝟓
43 − 45 35.23 − 31.70
43 − 44 27.33 − 𝑆𝐶
= → 𝑺𝑪 = 𝟐𝟔. 𝟓𝟓
43 − 45 27.33 − 25.77
43 − 44 7.02 − 𝐺𝑃𝑀
= → 𝑮𝑷𝑴 = 𝟔. 𝟔𝟕
43 − 45 7.02 − 6.32
43 − 44 9.53 − 𝑃𝐷
= → 𝑷𝑫 = 𝟖. 𝟕𝟎
43 − 45 9.53 − 7.87

60
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

HOTEL ROOM 316


FAN COIL UNIT SELECTION DATA
ITEM FAN COIL UNIT ROOM 316
1.4928
CAPACITY INTONS
17914.08
GRANDTOTALHEAT(TC)
11660.28
TOTALSENSIBLEHEAT(SC)
509.53
DEHUMIDIFIEDCFM
ENTERINGDRY BULB/ 80.71 / 69.20
ENTERINGWETBULB
LEAVINGDRY 59.52 / 58.70
BULB/LEAVINGWETBULB
CHILLEDWATERFLOW 3.5828
INGALLONSPER MINUTE
ENTERING/ 44 °F / 54 °F
LEAVINGCHILLEDWATERTEMP, °F

Estimate Flow for Chilled Water in Gallons per minute for Fan Coil
GIVEN:
𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦 (𝑓𝑜𝑟 𝐹𝑎𝑛 𝐶𝑜𝑖𝑙 𝑅𝑜𝑜𝑚 306) = (𝑐𝑜𝑛𝑣𝑒𝑟𝑡 𝐺𝑇𝐻)𝑇𝑜𝑛𝑠
𝑇𝑒𝑟𝑚𝑖𝑛𝑎𝑙 𝐷𝑖𝑓𝑓𝑒𝑟𝑒𝑛𝑐𝑒 (𝑇𝐷) = 10℉
12 000 𝑥 𝑇𝑅
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 𝑇𝐷
12 000 𝑥 1.4928
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 10

CHILLED WATER FLOW = 3.5828 GPM

61
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

FAN COILED SELECTED DATA


ITEM FANCOILUNIT(13.5Hours)
UNITMODEL/SIZE HFCA06C000A /Size 06
NOMINALAIRFLOW 600
GRANDTOTALHEAT(TC) 19060
TOTALSENSIBLEHEAT(SC) 13720
FINTYPE Slit
FINTYPEPERINCH 12
NO.OFROWCOIL 3
DRAINCONNECTIONSIZE 1/2
FANTYPE Centrifugal
NO.USED 2
DRIVETYPE Direct
MOTORPOWER,W 47
ENTERINGDRYBULB/ENTERINGWETBULB 80/ 67
LEAVINGDRYBULB/LEAVINGWETBULB 57.7/ 56.6
CHILLEDWATERFLOWINGALLONSPERMI
3.80
NUTE
WATERPRESSUREDROPPD,FTINWATER 6.175

62
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

SCHEMATICDIAGRAMOFFANCOILUNITSHOWINGTHE
DIFFERENT PARAMETERS
TRANECOOLINGCOILAIRSIDE
FCU316(13.5Hours)

63
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
HIGHLIGHTED SELECTED DATA ON THE BROCHURE

INTERPOLATING:
43 − 44 20.12 − 𝑇𝐶
= → 𝑻𝑪 = 𝟏𝟗. 𝟎𝟔
43 − 45 20.12 − 18
43 − 44 14.14 − 𝑆𝐶
= → 𝑺𝑪 = 𝟏𝟑. 𝟕𝟐
43 − 45 14.14 − 13.30
43 − 44 4.01 − 𝐺𝑃𝑀
= → 𝑮𝑷𝑴 = 𝟑. 𝟖𝟎
43 − 45 4.01 − 3.59
43 − 44 6.79 − 𝑃𝐷
= → 𝑷𝑫 = 𝟔. 𝟏𝟕𝟓
43 − 45 6.79 − 5.56

64
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

HOTEL ROOM 317


FAN COIL UNIT SELECTION DATA
ITEM FAN COIL UNIT ROOM 317
1.8415
CAPACITY INTONS
22097.72
GRANDTOTALHEAT(TC)
15843.92
TOTALSENSIBLEHEAT(SC)
758.20
DEHUMIDIFIEDCFM
ENTERINGDRY BULB/ 79.17 / 68.00
ENTERINGWETBULB
LEAVINGDRY 58.92 / 58.50
BULB/LEAVINGWETBULB
CHILLEDWATERFLOW 4.4195
INGALLONSPER MINUTE
ENTERING/ 44 °F / 54 °F
LEAVINGCHILLEDWATERTEMP, °F

Estimate Flow for Chilled Water in Gallons per minute for Fan Coil
GIVEN:
𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦 (𝑓𝑜𝑟 𝐹𝑎𝑛 𝐶𝑜𝑖𝑙 𝑅𝑜𝑜𝑚 317) = (𝑐𝑜𝑛𝑣𝑒𝑟𝑡 𝐺𝑇𝐻)𝑇𝑜𝑛𝑠
𝑇𝑒𝑟𝑚𝑖𝑛𝑎𝑙 𝐷𝑖𝑓𝑓𝑒𝑟𝑒𝑛𝑐𝑒 (𝑇𝐷) = 10℉
12 000 𝑥 𝑇𝑅
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 𝑇𝐷
12 000 𝑥 1.8415
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 10

CHILLED WATER FLOW = 4.4195 GPM

65
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

FAN COILED SELECTED DATA


ITEM FANCOILUNIT(13.5Hours)
UNITMODEL/SIZE HFCA08C000A /Size 08
NOMINALAIRFLOW 800
GRANDTOTALHEAT(TC) 26130
TOTALSENSIBLEHEAT(SC) 13720
FINTYPE Slit
FINTYPEPERINCH 15
NO.OFROWCOIL 3
DRAINCONNECTIONSIZE 1/2
FANTYPE Centrifugal
NO.USED 2
DRIVETYPE Direct
MOTORPOWER,W 59
ENTERINGDRYBULB/ENTERINGWETBULB 80/ 67
LEAVINGDRYBULB/LEAVINGWETBULB 57.7/ 56.6
CHILLEDWATERFLOWINGALLONSPERMI
3.80
NUTE
WATERPRESSUREDROPPD,FTINWATER 6.175

66
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

SCHEMATICDIAGRAMOFFANCOILUNITSHOWINGTHE
DIFFERENT PARAMETERS
TRANECOOLINGCOILAIRSIDE
FCU317(13.5Hours)

67
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
HIGHLIGHTED SELECTED DATA ON THE BROCHURE

INTERPOLATING:
43 − 44 27.50 − 𝑇𝐶
= → 𝑻𝑪 = 𝟐𝟔. 𝟏𝟑
43 − 45 27.50 − 24.76
43 − 44 21.34 − 𝑆𝐶
= → 𝑺𝑪 = 𝟐𝟎. 𝟕𝟏
43 − 45 21.34 − 20.08
43 − 44 5.48 − 𝐺𝑃𝑀
= → 𝑮𝑷𝑴 = 𝟓. 𝟐𝟏
43 − 45 5.48 − 4.94
43 − 44 14.36 − 𝑃𝐷
= → 𝑷𝑫 = 𝟏𝟑. 𝟏𝟏𝟓
43 − 45 14.36 − 11.87

68
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

HOTEL ROOM 318


FAN COIL UNIT SELECTION DATA
ITEM FAN COIL UNIT ROOM 318
1.4500
CAPACITY INTONS
17400.12
GRANDTOTALHEAT(TC)
11146.32
TOTALSENSIBLEHEAT(SC)
481.46
DEHUMIDIFIEDCFM
ENTERINGDRY BULB/ 80.98 / 69.60
ENTERINGWETBULB
LEAVINGDRY 59.55 / 58.90
BULB/LEAVINGWETBULB
CHILLEDWATERFLOW 3.4800
INGALLONSPER MINUTE
ENTERING/ 44 °F / 54 °F
LEAVINGCHILLEDWATERTEMP, °F

Estimate Flow for Chilled Water in Gallons per minute for Fan Coil
GIVEN:
𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦 (𝑓𝑜𝑟 𝐹𝑎𝑛 𝐶𝑜𝑖𝑙 𝑅𝑜𝑜𝑚 305) = (𝑐𝑜𝑛𝑣𝑒𝑟𝑡 𝐺𝑇𝐻)𝑇𝑜𝑛𝑠
𝑇𝑒𝑟𝑚𝑖𝑛𝑎𝑙 𝐷𝑖𝑓𝑓𝑒𝑟𝑒𝑛𝑐𝑒 (𝑇𝐷) = 10℉
12 000 𝑥 𝑇𝑅
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 𝑇𝐷
12 000 𝑥 1.4500
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 10

CHILLED WATER FLOW = 3.4800 GPM

69
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

FAN COILED SELECTED DATA


ITEM FANCOILUNIT(13.5Hours)
UNITMODEL/SIZE HFCA06C000A /Size 06
NOMINALAIRFLOW 600
GRANDTOTALHEAT(TC) 19060
TOTALSENSIBLEHEAT(SC) 13720
FINTYPE Slit
FINTYPEPERINCH 12
NO.OFROWCOIL 3
DRAINCONNECTIONSIZE 1/2
FANTYPE Centrifugal
NO.USED 2
DRIVETYPE Direct
MOTORPOWER,W 47
ENTERINGDRYBULB/ENTERINGWETBULB 80/ 67
LEAVINGDRYBULB/LEAVINGWETBULB 57.7/ 56.6
CHILLEDWATERFLOWINGALLONSPERMI
3.80
NUTE
WATERPRESSUREDROPPD,FTINWATER 6.175

70
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

SCHEMATICDIAGRAMOFFANCOILUNITSHOWINGTHE
DIFFERENT PARAMETERS
TRANECOOLINGCOILAIRSIDE
FCU318(13.5Hours)

71
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
HIGHLIGHTED SELECTED DATA ON THE BROCHURE

INTERPOLATING:
43 − 44 20.12 − 𝑇𝐶
= → 𝑻𝑪 = 𝟏𝟗. 𝟎𝟔
43 − 45 20.12 − 18
43 − 44 14.14 − 𝑆𝐶
= → 𝑺𝑪 = 𝟏𝟑. 𝟕𝟐
43 − 45 14.14 − 13.30
43 − 44 4.01 − 𝐺𝑃𝑀
= → 𝑮𝑷𝑴 = 𝟑. 𝟖𝟎
43 − 45 4.01 − 3.59
43 − 44 6.79 − 𝑃𝐷
= → 𝑷𝑫 = 𝟔. 𝟏𝟕𝟓
43 − 45 6.79 − 5.56

72
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

HOTEL ROOM 319


FAN COIL UNIT SELECTION DATA
ITEM FAN COIL UNIT ROOM 319
1.9503
CAPACITY INTONS
23403.55
GRANDTOTALHEAT(TC)
17149.75
TOTALSENSIBLEHEAT(SC)
839.11
DEHUMIDIFIEDCFM
ENTERINGDRY BULB/ 78.86 / 67.40
ENTERINGWETBULB
LEAVINGDRY 59.03 / 58.40
BULB/LEAVINGWETBULB
CHILLEDWATERFLOW 4.6807
INGALLONSPER MINUTE
ENTERING/ 44 °F / 54 °F
LEAVINGCHILLEDWATERTEMP, °F

Estimate Flow for Chilled Water in Gallons per minute for Fan Coil
GIVEN:
𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦 (𝑓𝑜𝑟 𝐹𝑎𝑛 𝐶𝑜𝑖𝑙 𝑅𝑜𝑜𝑚 319) = (𝑐𝑜𝑛𝑣𝑒𝑟𝑡 𝐺𝑇𝐻)𝑇𝑜𝑛𝑠
𝑇𝑒𝑟𝑚𝑖𝑛𝑎𝑙 𝐷𝑖𝑓𝑓𝑒𝑟𝑒𝑛𝑐𝑒 (𝑇𝐷) = 10℉
12 000 𝑥 𝑇𝑅
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 𝑇𝐷
12 000 𝑥 1.9503
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 10

CHILLED WATER FLOW = 4.6807 GPM

73
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

FAN COILED SELECTED DATA


ITEM FANCOILUNIT(13.5Hours)
UNITMODEL/SIZE HFCA10C0010A /Size 10

NOMINALAIRFLOW 1000
GRANDTOTALHEAT(TC) 33465
TOTALSENSIBLEHEAT(SC) 26550
FINTYPE Louver
FINTYPEPERINCH 18
NO.OFROWCOIL 3
DRAINCONNECTIONSIZE 1/2
FANTYPE Centrifugal
NO.USED 2
DRIVETYPE Direct
MOTORPOWER,W 162
ENTERINGDRYBULB/ENTERINGWETBULB 80/ 67
LEAVINGDRYBULB/LEAVINGWETBULB 57.7/ 56.6
CHILLEDWATERFLOWINGALLONSPERMI
6.67
NUTE
WATERPRESSUREDROPPD,FTINWATER 8.70

74
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

SCHEMATICDIAGRAMOFFANCOILUNITSHOWINGTHE
DIFFERENT PARAMETERS
TRANECOOLINGCOILAIRSIDE
FCU319(13.5Hours)

75
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
HIGHLIGHTED SELECTED DATA ON THE BROCHURE

INTERPOLATING:
43 − 44 35.23 − 𝑇𝐶
= → 𝑻𝑪 = 𝟑𝟑. 𝟒𝟔𝟓
43 − 45 35.23 − 31.70
43 − 44 27.33 − 𝑆𝐶
= → 𝑺𝑪 = 𝟐𝟔. 𝟓𝟓
43 − 45 27.33 − 25.77
43 − 44 7.02 − 𝐺𝑃𝑀
= → 𝑮𝑷𝑴 = 𝟔. 𝟔𝟕
43 − 45 7.02 − 6.32
43 − 44 9.53 − 𝑃𝐷
= → 𝑷𝑫 = 𝟖. 𝟕𝟎
43 − 45 9.53 − 7.87

76
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

HOTEL ROOM 320


FAN COIL UNIT SELECTION DATA
ITEM FAN COIL UNIT ROOM 320
1.4574
CAPACITY INTONS
17488.40
GRANDTOTALHEAT(TC)
11383.74
TOTALSENSIBLEHEAT(SC)
494.42
DEHUMIDIFIEDCFM
ENTERINGDRY BULB/ 80.85 / 69.40
ENTERINGWETBULB
LEAVINGDRY 59.54 / 58.80
BULB/LEAVINGWETBULB
CHILLEDWATERFLOW 3.4977
INGALLONSPER MINUTE
ENTERING/ 44 °F / 54 °F
LEAVINGCHILLEDWATERTEMP, °F

Estimate Flow for Chilled Water in Gallons per minute for Fan Coil
GIVEN:
𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦 (𝑓𝑜𝑟 𝐹𝑎𝑛 𝐶𝑜𝑖𝑙 𝑅𝑜𝑜𝑚 303) = (𝑐𝑜𝑛𝑣𝑒𝑟𝑡 𝐺𝑇𝐻)𝑇𝑜𝑛𝑠
𝑇𝑒𝑟𝑚𝑖𝑛𝑎𝑙 𝐷𝑖𝑓𝑓𝑒𝑟𝑒𝑛𝑐𝑒 (𝑇𝐷) = 10℉
12 000 𝑥 𝑇𝑅
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 𝑇𝐷
12 000 𝑥 1.4574
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 10

CHILLED WATER FLOW = 3.4977 GPM

77
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

FAN COILED SELECTED DATA


ITEM FANCOILUNIT(13.5Hours)
UNITMODEL/SIZE HFCA06C000A /Size 06
NOMINALAIRFLOW 600
GRANDTOTALHEAT(TC) 19060
TOTALSENSIBLEHEAT(SC) 13720
FINTYPE Slit
FINTYPEPERINCH 12
NO.OFROWCOIL 3
DRAINCONNECTIONSIZE 1/2
FANTYPE Centrifugal
NO.USED 2
DRIVETYPE Direct
MOTORPOWER,W 47
ENTERINGDRYBULB/ENTERINGWETBULB 80/ 67
LEAVINGDRYBULB/LEAVINGWETBULB 57.7/ 56.6
CHILLEDWATERFLOWINGALLONSPERMI
3.80
NUTE
WATERPRESSUREDROPPD,FTINWATER 6.175

78
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

SCHEMATICDIAGRAMOFFANCOILUNITSHOWINGTHE
DIFFERENT PARAMETERS
TRANECOOLINGCOILAIRSIDE
FCU320(13.5Hours)

79
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
HIGHLIGHTED SELECTED DATA ON THE BROCHURE

INTERPOLATING:
43 − 44 20.12 − 𝑇𝐶
= → 𝑻𝑪 = 𝟏𝟗. 𝟎𝟔
43 − 45 20.12 − 18
43 − 44 14.14 − 𝑆𝐶
= → 𝑺𝑪 = 𝟏𝟑. 𝟕𝟐
43 − 45 14.14 − 13.30
43 − 44 4.01 − 𝐺𝑃𝑀
= → 𝑮𝑷𝑴 = 𝟑. 𝟖𝟎
43 − 45 4.01 − 3.59
43 − 44 6.79 − 𝑃𝐷
= → 𝑷𝑫 = 𝟔. 𝟏𝟕𝟓
43 − 45 6.79 − 5.56

80
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

HOTEL ROOM 321


FAN COIL UNIT SELECTION DATA
ITEM FAN COIL UNIT ROOM 321
1.4500
CAPACITY INTONS
17400.12
GRANDTOTALHEAT(TC)
11146.32
TOTALSENSIBLEHEAT(SC)
481.46
DEHUMIDIFIEDCFM
ENTERINGDRY BULB/ 80.98 / 69.60
ENTERINGWETBULB
LEAVINGDRY 59.55 / 58.90
BULB/LEAVINGWETBULB
CHILLEDWATERFLOW 3.4800
INGALLONSPER MINUTE
ENTERING/ 44 °F / 54 °F
LEAVINGCHILLEDWATERTEMP, °F

Estimate Flow for Chilled Water in Gallons per minute for Fan Coil
GIVEN:
𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦 (𝑓𝑜𝑟 𝐹𝑎𝑛 𝐶𝑜𝑖𝑙 𝑅𝑜𝑜𝑚 305) = (𝑐𝑜𝑛𝑣𝑒𝑟𝑡 𝐺𝑇𝐻)𝑇𝑜𝑛𝑠
𝑇𝑒𝑟𝑚𝑖𝑛𝑎𝑙 𝐷𝑖𝑓𝑓𝑒𝑟𝑒𝑛𝑐𝑒 (𝑇𝐷) = 10℉
12 000 𝑥 𝑇𝑅
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 𝑇𝐷
12 000 𝑥 1.4500
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 10

CHILLED WATER FLOW = 3.4800 GPM

81
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

FAN COILED SELECTED DATA


ITEM FANCOILUNIT(13.5Hours)
UNITMODEL/SIZE HFCA06C000A /Size 06
NOMINALAIRFLOW 600
GRANDTOTALHEAT(TC) 19060
TOTALSENSIBLEHEAT(SC) 13720
FINTYPE Slit
FINTYPEPERINCH 12
NO.OFROWCOIL 3
DRAINCONNECTIONSIZE 1/2
FANTYPE Centrifugal
NO.USED 2
DRIVETYPE Direct
MOTORPOWER,W 47
ENTERINGDRYBULB/ENTERINGWETBULB 80/ 67
LEAVINGDRYBULB/LEAVINGWETBULB 57.7/ 56.6
CHILLEDWATERFLOWINGALLONSPERMI
3.80
NUTE
WATERPRESSUREDROPPD,FTINWATER 6.175

82
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

SCHEMATICDIAGRAMOFFANCOILUNITSHOWINGTHE
DIFFERENT PARAMETERS
TRANECOOLINGCOILAIRSIDE
FCU321(13.5Hours)

83
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
HIGHLIGHTED SELECTED DATA ON THE BROCHURE

INTERPOLATING:
43 − 44 20.12 − 𝑇𝐶
= → 𝑻𝑪 = 𝟏𝟗. 𝟎𝟔
43 − 45 20.12 − 18
43 − 44 14.14 − 𝑆𝐶
= → 𝑺𝑪 = 𝟏𝟑. 𝟕𝟐
43 − 45 14.14 − 13.30
43 − 44 4.01 − 𝐺𝑃𝑀
= → 𝑮𝑷𝑴 = 𝟑. 𝟖𝟎
43 − 45 4.01 − 3.59
43 − 44 6.79 − 𝑃𝐷
= → 𝑷𝑫 = 𝟔. 𝟏𝟕𝟓
43 − 45 6.79 − 5.56

84
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

HOTEL ROOM 322


FAN COIL UNIT SELECTION DATA
ITEM FAN COIL UNIT ROOM 322
1.4928
CAPACITY INTONS
17914.08
GRANDTOTALHEAT(TC)
11660.28
TOTALSENSIBLEHEAT(SC)
509.53
DEHUMIDIFIEDCFM
ENTERINGDRY BULB/ 80.71 / 69.20
ENTERINGWETBULB
LEAVINGDRY 59.52 / 58.70
BULB/LEAVINGWETBULB
CHILLEDWATERFLOW 3.5828
INGALLONSPER MINUTE
ENTERING/ 44 °F / 54 °F
LEAVINGCHILLEDWATERTEMP, °F

Estimate Flow for Chilled Water in Gallons per minute for Fan Coil
GIVEN:
𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦 (𝑓𝑜𝑟 𝐹𝑎𝑛 𝐶𝑜𝑖𝑙 𝑅𝑜𝑜𝑚 306) = (𝑐𝑜𝑛𝑣𝑒𝑟𝑡 𝐺𝑇𝐻)𝑇𝑜𝑛𝑠
𝑇𝑒𝑟𝑚𝑖𝑛𝑎𝑙 𝐷𝑖𝑓𝑓𝑒𝑟𝑒𝑛𝑐𝑒 (𝑇𝐷) = 10℉
12 000 𝑥 𝑇𝑅
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 𝑇𝐷
12 000 𝑥 1.4928
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 10

CHILLED WATER FLOW = 3.5828 GPM

85
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

FAN COILED SELECTED DATA


ITEM FANCOILUNIT(13.5Hours)
UNITMODEL/SIZE HFCA06C000A /Size 06
NOMINALAIRFLOW 600
GRANDTOTALHEAT(TC) 19060
TOTALSENSIBLEHEAT(SC) 13720
FINTYPE Slit
FINTYPEPERINCH 12
NO.OFROWCOIL 3
DRAINCONNECTIONSIZE 1/2
FANTYPE Centrifugal
NO.USED 2
DRIVETYPE Direct
MOTORPOWER,W 47
ENTERINGDRYBULB/ENTERINGWETBULB 80/ 67
LEAVINGDRYBULB/LEAVINGWETBULB 57.7/ 56.6
CHILLEDWATERFLOWINGALLONSPERMI
3.80
NUTE
WATERPRESSUREDROPPD,FTINWATER 6.175

86
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

SCHEMATICDIAGRAMOFFANCOILUNITSHOWINGTHE
DIFFERENT PARAMETERS
TRANECOOLINGCOILAIRSIDE
FCU322(13.5Hours)

87
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
HIGHLIGHTED SELECTED DATA ON THE BROCHURE

INTERPOLATING:
43 − 44 20.12 − 𝑇𝐶
= → 𝑻𝑪 = 𝟏𝟗. 𝟎𝟔
43 − 45 20.12 − 18
43 − 44 14.14 − 𝑆𝐶
= → 𝑺𝑪 = 𝟏𝟑. 𝟕𝟐
43 − 45 14.14 − 13.30
43 − 44 4.01 − 𝐺𝑃𝑀
= → 𝑮𝑷𝑴 = 𝟑. 𝟖𝟎
43 − 45 4.01 − 3.59
43 − 44 6.79 − 𝑃𝐷
= → 𝑷𝑫 = 𝟔. 𝟏𝟕𝟓
43 − 45 6.79 − 5.56

88
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

HOTEL ROOM 323


FAN COIL UNIT SELECTION DATA
ITEM FAN COIL UNIT ROOM 323
1.8939
CAPACITY INTONS
22726.66
GRANDTOTALHEAT(TC)
16472.86
TOTALSENSIBLEHEAT(SC)
800.77
DEHUMIDIFIEDCFM
ENTERINGDRY BULB/ 79.00 / 67.40
ENTERINGWETBULB
LEAVINGDRY 59.95 / 59.00
BULB/LEAVINGWETBULB
CHILLEDWATERFLOW 4.5453
INGALLONSPER MINUTE
ENTERING/ 44 °F / 54 °F
LEAVINGCHILLEDWATERTEMP, °F

Estimate Flow for Chilled Water in Gallons per minute for Fan Coil
GIVEN:
𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦 (𝑓𝑜𝑟 𝐹𝑎𝑛 𝐶𝑜𝑖𝑙 𝑅𝑜𝑜𝑚 323) = (𝑐𝑜𝑛𝑣𝑒𝑟𝑡 𝐺𝑇𝐻)𝑇𝑜𝑛𝑠
𝑇𝑒𝑟𝑚𝑖𝑛𝑎𝑙 𝐷𝑖𝑓𝑓𝑒𝑟𝑒𝑛𝑐𝑒 (𝑇𝐷) = 10℉
12 000 𝑥 𝑇𝑅
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 𝑇𝐷
12 000 𝑥 1.8939
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 10

CHILLED WATER FLOW = 4.5453 GPM

89
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

FAN COILED SELECTED DATA


ITEM FANCOILUNIT(13.5Hours)
UNITMODEL/SIZE HFCA10C0010A /Size 10

NOMINALAIRFLOW 1000
GRANDTOTALHEAT(TC) 33465
TOTALSENSIBLEHEAT(SC) 26550
FINTYPE Louver
FINTYPEPERINCH 18
NO.OFROWCOIL 3
DRAINCONNECTIONSIZE 1/2
FANTYPE Centrifugal
NO.USED 2
DRIVETYPE Direct
MOTORPOWER,W 162
ENTERINGDRYBULB/ENTERINGWETBULB 80/ 67
LEAVINGDRYBULB/LEAVINGWETBULB 57.7/ 56.6
CHILLEDWATERFLOWINGALLONSPERMI
6.67
NUTE
WATERPRESSUREDROPPD,FTINWATER 8.70

90
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

SCHEMATICDIAGRAMOFFANCOILUNITSHOWINGTHE
DIFFERENT PARAMETERS
TRANECOOLINGCOILAIRSIDE
FCU323(13.5Hours)

91
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
HIGHLIGHTED SELECTED DATA ON THE BROCHURE

INTERPOLATING:
43 − 44 35.23 − 𝑇𝐶
= → 𝑻𝑪 = 𝟑𝟑. 𝟒𝟔𝟓
43 − 45 35.23 − 31.70
43 − 44 27.33 − 𝑆𝐶
= → 𝑺𝑪 = 𝟐𝟔. 𝟓𝟓
43 − 45 27.33 − 25.77
43 − 44 7.02 − 𝐺𝑃𝑀
= → 𝑮𝑷𝑴 = 𝟔. 𝟔𝟕
43 − 45 7.02 − 6.32
43 − 44 9.53 − 𝑃𝐷
= → 𝑷𝑫 = 𝟖. 𝟕𝟎
43 − 45 9.53 − 7.87

92
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

HOTEL ROOM 324


FAN COIL UNIT SELECTION DATA
ITEM FAN COIL UNIT ROOM 324
1.8331
CAPACITY INTONS
21997.59
GRANDTOTALHEAT(TC)
15743.79
TOTALSENSIBLEHEAT(SC)
752.58
DEHUMIDIFIEDCFM
ENTERINGDRY BULB/ 78.29 / 68.10
ENTERINGWETBULB
LEAVINGDRY 59.83 / 59
BULB/LEAVINGWETBULB
CHILLEDWATERFLOW 4.3184
INGALLONSPER MINUTE
ENTERING/ 44 °F / 54 °F
LEAVINGCHILLEDWATERTEMP, °F

Estimate Flow for Chilled Water in Gallons per minute for Fan Coil
GIVEN:
𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦 (𝑓𝑜𝑟 𝐹𝑎𝑛 𝐶𝑜𝑖𝑙 𝑅𝑜𝑜𝑚 324) = (𝑐𝑜𝑛𝑣𝑒𝑟𝑡 𝐺𝑇𝐻)𝑇𝑜𝑛𝑠
𝑇𝑒𝑟𝑚𝑖𝑛𝑎𝑙 𝐷𝑖𝑓𝑓𝑒𝑟𝑒𝑛𝑐𝑒 (𝑇𝐷) = 10℉
12 000 𝑥 𝑇𝑅
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 𝑇𝐷
12 000 𝑥 1.8331
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 10

CHILLED WATER FLOW = 4.3184 GPM

93
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

FAN COILED SELECTED DATA


ITEM FANCOILUNIT(13.5Hours)
UNITMODEL/SIZE HFCA08C000A /Size 08
NOMINALAIRFLOW 800
GRANDTOTALHEAT(TC) 26130
TOTALSENSIBLEHEAT(SC) 13720
FINTYPE Slit
FINTYPEPERINCH 15
NO.OFROWCOIL 3
DRAINCONNECTIONSIZE 1/2
FANTYPE Centrifugal
NO.USED 2
DRIVETYPE Direct
MOTORPOWER,W 59
ENTERINGDRYBULB/ENTERINGWETBULB 80/ 67
LEAVINGDRYBULB/LEAVINGWETBULB 57.7/ 56.6
CHILLEDWATERFLOWINGALLONSPERMI
3.80
NUTE
WATERPRESSUREDROPPD,FTINWATER 6.175

94
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

SCHEMATICDIAGRAMOFFANCOILUNITSHOWINGTHE
DIFFERENT PARAMETERS
TRANECOOLINGCOILAIRSIDE
FCU324(13.5Hours)

Dcfm = 800 cfm


Fan Type:
Centrifugal

95
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
HIGHLIGHTED SELECTED DATA ON THE BROCHURE

INTERPOLATING:
43 − 44 27.50 − 𝑇𝐶
= → 𝑻𝑪 = 𝟐𝟔. 𝟏𝟑
43 − 45 27.50 − 24.76
43 − 44 21.34 − 𝑆𝐶
= → 𝑺𝑪 = 𝟐𝟎. 𝟕𝟏
43 − 45 21.34 − 20.08
43 − 44 5.48 − 𝐺𝑃𝑀
= → 𝑮𝑷𝑴 = 𝟓. 𝟐𝟏
43 − 45 5.48 − 4.94
43 − 44 14.36 − 𝑃𝐷
= → 𝑷𝑫 = 𝟏𝟑. 𝟏𝟏𝟓
43 − 45 14.36 − 11.87

96
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

HOTEL ROOM 325


FAN COIL UNIT SELECTION DATA
ITEM FAN COIL UNIT ROOM 325
2.1536
CAPACITY INTONS
25842.65
GRANDTOTALHEAT(TC)
19588.85
TOTALSENSIBLEHEAT(SC)
986.29
DEHUMIDIFIEDCFM
ENTERINGDRY BULB/ 78.31 / 67.20
ENTERINGWETBULB
LEAVINGDRY 59.28 / 58.50
BULB/LEAVINGWETBULB
CHILLEDWATERFLOW 5.1685
INGALLONSPER MINUTE
ENTERING/ 44 °F / 54 °F
LEAVINGCHILLEDWATERTEMP, °F

Estimate Flow for Chilled Water in Gallons per minute for Fan Coil
GIVEN:
𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦 (𝑓𝑜𝑟 𝐹𝑎𝑛 𝐶𝑜𝑖𝑙 𝑅𝑜𝑜𝑚 325) = (𝑐𝑜𝑛𝑣𝑒𝑟𝑡 𝐺𝑇𝐻)𝑇𝑜𝑛𝑠
𝑇𝑒𝑟𝑚𝑖𝑛𝑎𝑙 𝐷𝑖𝑓𝑓𝑒𝑟𝑒𝑛𝑐𝑒 (𝑇𝐷) = 10℉
12 000 𝑥 𝑇𝑅
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 𝑇𝐷
12 000 𝑥 2.1536
𝐶ℎ𝑖𝑙𝑙𝑒𝑑 𝑊𝑎𝑡𝑒𝑟 𝐹𝑙𝑜𝑤 =
500 𝑥 10

CHILLED WATER FLOW = 5.1685 GPM

97
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

FAN COILED SELECTED DATA


ITEM FANCOILUNIT(13.5Hours)
UNITMODEL/SIZE HFCA10C0010A /Size 10

NOMINALAIRFLOW 1000
GRANDTOTALHEAT(TC) 33465
TOTALSENSIBLEHEAT(SC) 26550
FINTYPE Louver
FINTYPEPERINCH 18
NO.OFROWCOIL 3
DRAINCONNECTIONSIZE 1/2
FANTYPE Centrifugal
NO.USED 2
DRIVETYPE Direct
MOTORPOWER,W 162
ENTERINGDRYBULB/ENTERINGWETBULB 80/ 67
LEAVINGDRYBULB/LEAVINGWETBULB 57.7/ 56.6
CHILLEDWATERFLOWINGALLONSPERMI
6.67
NUTE
WATERPRESSUREDROPPD,FTINWATER 8.70

98
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION

SCHEMATICDIAGRAMOFFANCOILUNITSHOWINGTHE
DIFFERENT PARAMETERS
TRANECOOLINGCOILAIRSIDE
FCU325(13.5Hours)

99
MAPÚA UNIVERSITY
SchoolofMechanicalandManufacturingEngineering
ME150P/A1
EQUIPMENTSELECTION
HIGHLIGHTED SELECTED DATA ON THE BROCHURE

INTERPOLATING:
43 − 44 35.23 − 𝑇𝐶
= → 𝑻𝑪 = 𝟑𝟑. 𝟒𝟔𝟓
43 − 45 35.23 − 31.70
43 − 44 27.33 − 𝑆𝐶
= → 𝑺𝑪 = 𝟐𝟔. 𝟓𝟓
43 − 45 27.33 − 25.77
43 − 44 7.02 − 𝐺𝑃𝑀
= → 𝑮𝑷𝑴 = 𝟔. 𝟔𝟕
43 − 45 7.02 − 6.32
43 − 44 9.53 − 𝑃𝐷
= → 𝑷𝑫 = 𝟖. 𝟕𝟎
43 − 45 9.53 − 7.87

100