Вы находитесь на странице: 1из 1

200X60 cm 200X220 cm

VENTILATION CEMENT CLAUSTRA

690
20 200 80 20

NOTE :

100
270 -ROOM HEIGHT 3.5M MINIMUM CLEAR
360

150
- DOOR HEIGHT 3.0M MINIMUM FEL.
-200X220cm CEMENT CLAUSTRA FOR VENTILATION
150 100 160 100 -D1=300X270cm HOT DEEPED GALVANISED STEEL GRILL
120
TYPE DOOR
20 80
-D2=200X120cm ALUMINUM LOUVERED ( SINGLE LEAF )
DOOR
80 30 30 - ALL TRENCHES 80 cm DEEP MINIMUM

85
100
LIGHT -TRENCH COVER GALVANIZED IRON GRATING 5cm THICK
FITTIG EL -SLOT IN ROOF 25 cm WIDE AS SHOWN
-F.F.L OF SUB-STATION TO BE 35cm ABOVE WALK WAY
-ALL DIMENSIONS ARE IN CM. UNLESS OTHERWISE NOTED

250
170

80
490

TRM

85
TRANSFORMER
REQUIREMENT OF SUBMITAL OF SHOP DRAWINGS :
-FLOOR LAYOUT WITH ALL DIMENSION
80cm DEEP
-FRONT ELEVATION
130

CABLE TRENCH
-SECTIONAL ELEVATION
EL -TRENCH & TRENCH COVER DETAILS
13A S.SOCKET
- SLOT DETAILS
- APPLICATION ROAD REFER TO ADJACENT MAIN ROAD
100

25 x350cm SLOT ON
THE ROOF

65 120 180 270 ** Size ( 6.9 X 4.9 ) m


1X4" PVC DUCT ** Accepted min. size( 6.5 X 4.6 ) m
FOR EARTHING
D2 D1
3X6" PVC DUCT LIGHTING
SWITCH
FOR AADC CABLES