APPENDIX 3B

TROUBLESHOOTING GUIDE

NO DISPLAY FOLLOWING POWER-UP

Provided the display is functioning properly and provided


system power is wired correctly, on Power-Up the
MicroPAC should display the Version Number and the
Version Date, as shown in Figure 1.

Note This screen message is followed by a second message


screen that identifies the unit as an Injector

If the unit powers-up and does correctly display the


messages as mentioned above, then the display and the
microprocessor controlling the display is functioning
correctly and the +5 volt DC power is available. If the
power-up messages DO NOT appear, check the +5VDC Normal Display
power by checking the RED LED on the power supply Figure 1
board (AC side) positioned above the output modules.

The +5 VDC LED is located forward of the +15 VDC LED,


as per Figure 2.

Note If the +5VDC LED is lit, then +5VDC power is available

The LED for +15VDC power indicates power is


available for Secondary Product (additive) flow meter
Hall-Effect sensor

Under normal circumstances, both the +5 VDC LED


and +15 VDC LED should be lit

Action 1
If neither LED is lit – check supply POWER +5 vdc LED
Note: +15 vdc LED to rear of +5 vdc LED
AC powered units
Figure 2
• Check J4 Pin 9 - should indicate 115/230 VAC/60hZ.

DC powered units (optional, special order)


• Check J4 Pin 9 - should indicate +12 Volts or
+24 Volts, as powered To correct this problem the user will have to perform a
SYSTEM REBOOT in accordance with procedures
outlined in APPENDIX 3C. A system REBOOT will cause
the default parameters to be reloaded into the memory. If
Action 2 this action fails to cause the unit’s display to operate
If the change from the initial display message does NOT properly, the unit should be replaced.
occur but the +5VDC LED is lit, this indicates that the main
processor has not taken over control of the display.
Reasons include the possibility that the memory may be Note If a SYSTEM REBOOT is performed, ensure that all
corrupted. modified parameters are re-entered into the program
parameters prior to entering the unit into service

Appendix 3B_Page 1 of 3
Chemtec ProPAC5M Additive Injector v1.2

Action 3
If the problem with the main processor appears The ON state of a power switch is indicated by the 4 LEDs
immediately after a U2 EPROM memory chip has been just to the right of the connector. The left most pin and left
changed, then make sure no pins on the integrated circuit most LED correspond to the top power switch (Output 1)
have been bent and ensure that the U2 EPROM circuit and the right most pin and the right most LED correspond
chip is correctly mounted using the alignment “notch”. to the bottom power switch (Output 4).

Note The controller unit has two replaceable socket mounted


microchips – the U2 is for the system firmware EPROM
and the U3 is for system RAM

Action 4
If the display is not powered but the wiring indicates the
proper voltage exists on J4 Pin 9 (i.e. 115 VAC), then
check the MAIN FUSE, which is located at the BOTTOM
of the fuse rack assembly.

Fuse identification and mounting orientation is note on


Figure 3 below.
Output Modules 1-4
1= Sol.A, 2 = Sol.B, 3 = Pump Start, 4 = Alarm/Error
Note Access to the fuse rack is accomplished by removing
the FUSE RACK cover Figure 4

FUSE RELATED PROBLEMS

Fuse location and purpose is described below. A SPARE


fuse is provided with each MicroPAC. Orientation of each
fuse defines whether POWER for the fuse is POWERED
directly from the MicroPAC, or supplied from a source
external to the unit

Example
User supplies power from a PLC to power the LOAD
PERMISSIVE OUTPUT signal. Based on this example the
MicroPAC is not providing the power for the switch, but merely
making a contact closure, therefore install as a DRY CONTACT.

Fuse Orientation & Definitions (Typical)


Figure 3 NO ADDITIVE FLOW OR UNDER-TREAT ERROR 9

• Ensure all system shut-off valves are OPEN


Note • Check additive pump pressure
Fuse Position – “Λ” SHAPE when MicroPAC provides output • Check all strainers and filters for obstruction
power as showm for solenoids for Additive A and Additive B • Ensure additive solenoid is opening on receipt of
above ARM signal
• Check additive meter to ensure gears are “free” and
Fuse Position – HORIZONTAL FOR Spare, Main Power and any turning uninhibited
output used as a DRY CONTACT. • Check additive meter Hall-Effect sensor for failure
PUMP START and ALARM/ERROR outputs commonly used as
DRY CONTACTS

UNAUTHORIZED ADDITIVE FLOW ERROR 3

“Additive flow when not expected”


OUTPUT RELATED PROBLEMS
With additive pump positioned ON, close outlet to process
If the unit appears to be functioning but there appears to and open test port to determine if additive flows when
be a problem associated with one of the four output relay solenoid is closed. If additive flows when the solenoid is
signals, then each replaceable output power module (AC closed, then check the following:
or DC) may be tested independently. ƒ open solenoid on MiniBLOCK and ensure no
trash is under seat
Located in the center of the power supply board near the ƒ inspect solenoid plunger seat for damage
top edge of the board is a 5-pin connector. Connecting ƒ remove fitting with through-hole in bottom of
any one of the first 4 pins (L-R) to the rightmost pin will solenoid cavity and re-tape using Teflon tape.
cause the respective power switch to be Positioned-ON. Reinstall fitting and reassemble solenoid to
MiniBLOCK

Appendix 3B_Page 2 of 3
Chemtec ProPAC5M Additive Injector v1.2

NO MAIN PRODUCT FLOW


ERROR 1

• Check Main Product meter pulse signal INPUT


wiring located on MicroPAC connector J1 Pins 7 & 8.
• Check program parameters relating to Main Product
K-Factors and Calibration Parameters

INJECTOR OVERALL BLEND RATIO ERROR


ERROR 5

• Check system dynamics for pressure and flow of


Main Product & Additive
• Check Parameters relating to blend ratios

EXCESSIVE ERRORS - SYSTEM LOCKUP


ERROR 20

• Check Parameters relating to ERRORS


• Reference ERROR DESCRIPTION for cause
determination

Note If ERROR 20 is activated, the ERROR can only


be reset by cycling POWER to the MicroPAC or
by serial COM command

All other ERRORS can be reset by new ARM input


signal, power cycle or serial command

Appendix 3B_Page 3 of 3