Академический Документы
Профессиональный Документы
Культура Документы
Outdoor System
.
356816.033
Information in this document is subject to change without notice and does not represent a commitment on
the part of Eltek Valere.
No part of this document may be reproduced or transmitted in any form or by any means — electronic or
mechanical, including photocopying and recording — for any purpose without the explicit written
permission of Eltek Valere.
“FP2 6kW 15U OD Fan” is a fan cooled outdoor cabinet that comes with a 6kW 48V DC
power system and space for one up to 100Ah 48V battery bank. The outdoor cabinet is a
compact cabinet designed for use in a wide temperature range and with ingress protection IP55.
It is referred to as the “outdoor cabinet” or “system” in the rest of this document.
The durable construction of the outdoor cabinet secures long lifetime and good protection under
various environmental conditions. The cabinet can be equipped with a plinth for floor mounting,
or with brackets for mounting on a pole or a wall.
ü Note! The cabinet may be equipped with more/less functions than described in
this document.
Definitions
ü WARNING: Text highlighted in this way provides the installer with information that
it will be DANGEROUS for people (including possible loss of life) and extensive
damage to the equipment if not all of the instructions in this special notice are
followed.
ü CAUTION: Text highlighted in this way provides the installer with information that it may
damage the equipment not to follow the instructions stated in this special notice.
ü Note: Text highlighted in this way signifies that the installer will be given additional
information or special instructions which are essential for the equipment or when
installation is being performed.
Abbreviations
CB - Circuit Breaker
FAC - Forced Air cooling
FP2 - Flatpack 2
HMS - Heat Management System
MCB- Magnetic Circuit Breaker
OD - Outdoor
SPD - Surge Protection Device
VRLA- Valve Regulated Lead Acid battery
Applicable standards
Electrical Safety
IEC 60950
UL 60950
CAN CSA-C22.2 No. 60950-1-03
EMC
ETSI EN 300 386 V.1.4.1 (2008-4) EMC for Telecommunication network equipment
EN 61000-6-1 (2007-01) Immunity for light industrial environments
EN 61000-6-2 (2005-01) Immunity for industrial environments
EN 61000-6-3 (2007-01) Emission for light industrial environments
EN 61000-6-4 (2007-01) Radiated and conducted emission
FCC part 15B Subpart 109 Radiated and conducted emission
Environment
ETS 300 019 2.1 Storage, 2.2 Transport, 2.4 Operation
Ingress protection: EN60529
2002/95/EC RoHS Compliant
WEEE compliant
Pole bracket
Cabinet
Wall
Filter bracket
Plinth
Heat Management system
Battery Shelf
Cable glands
Figure 1 – Cabinet Overview (example showing the Fan Filter solution in the door)
Cabinet
The cabinet is an aluminum single skinned outdoor enclosure for mounting on wall, pole or base
assembly. It is designed with adapters to fit 19” components and equipment. The cabinet
accommodates a dust protection rating of IP5x and a water protection rating depending of
cooling system. For a fan cooled door assembly the water protection is 5. The cable entry is
located at the bottom of the cabinet by means of a cable gland plate and cable tie brackets.
The Eltek Valere cabinet is designed with an over-pressure system to minimize the consequences
of leakage of dust and water into the cabinet caused by possible damages to gaskets or cable
glands.
ü Note! The rating of the heat management system within the cabinet is based on
the color that the cabinet was delivered with. If the color is altered with paint, dirt
etc the cooling may depreciate.
Equipment
Input Filter
Batteries
Fan
Or
Equipment
Cable Management
Cable glands / entries
The basic cabinet has cable glands making it possible to enter with a wide range of cable sizes.
The cabinet is delivered with the Multigate MC 25 as standard. However it is possible to use
other cable gland plates with FL21 size like Multigate MC 3 and Roxtec Comseal products. For
details on other optional cable glands/entries refer to their respective data sheets/documentation.
The Multigate MC 25 standard cable gland plate can receive the following cable/conductor
dimensions:
1 x 20-26 mm
12 x 10-14 mm
4 x 05-07 mm
4 x 14-20 mm
4 x 08-12 mm
The Multigate MC 25 is suitable for leading through both low and medium power current cables
as well as various types of tubing.
At the cable entrance (bottom of cabinet) there is placed two cable tie brackets (one on the
outside and one on the inside) for cable strain relief.
Note! Orientation/direction of the cable tie brackets may differ from the picture above.
Cable support
The Kit for Wall / Pole Mounting contains parts for fixing the OD cabinet securely to a wall or a
pole. The kit is designed to support the cabinet with one or two battery banks (MAX 400kg).
Make sure that the wall is able to hold the weight of the cabinet.
The screws/anchors (M8) for fixing the cabinet to the wall are not included in this kit due to
different material of wall (i.e. wood, steel, concrete etc).
By adding 2 crossbars with clamps to the wall mount brackets it is possible to fix the Outdoor
Cabinet securely to a pole. The minimum dimension / size of the pole is 60mmØ and the
maximum size is 115mmØ.
The screws/anchors (M8) for fixing the cabinet to the pole are included with the system.
Figure 8 - Plinth
The Kit for Floor Mounting makes it possible to fix the Outdoor Cabinet securely to the
pad/ground/floor. The kit is designed to support the cabinet with one or two battery banks (MAX
400kg).
The bolts/anchors for fixing the plinth to the pad/ground/floor are not included in this kit because
of the different materials used for pad constructions.
The plinth’s front and right/left side covers are removable for easy access when performing the
installation. These covers may remain withdrawn if cables and conduits are entered here. It is
also possible to open the 4 knock-outs per side and route cables through these holes.
CAN Bus
Flatpack2
rectifiers (BF) Telecom
equipment
LVBD
Load MCBs
DC
AC Fuses, distribution
external
Battery string #1
The system is fed from an external AC mains supply, and consists of rectifiers, control unit and
DC distribution unit. External battery banks may be connected to the system.
I/O Monitor
I/O Monitor
Input 6 Relay 1
The I/O monitor is operated and powered via the CAN bus. The 2 CAN ports are electrically
identical. The CAN bus has to be terminated with 120 Ohm resistors (60 Ohm bus impedance) at
each end. This is done to avoid data reflection. In the Power system the end-of-line-resistors are
mounted on the rectifier’s back-wiring card and inside a terminal plug on the I/O monitor.
The DIP switches are used to set the I/O monitor’s address on the CAN bus. The Smartpack
controller registers the I/O Monitor’s ID number which is set by DIP switches. All switches
should be OFF when only one I/O monitor is used. See picture below.
OFF
ON
Switch # 1 Switch # 8
Other systems may have more than one I/O monitor installed. When more than one I/O monitor
is installed their respective addresses are set by individual DIP switch settings (binary
addressing).
I/O monitor number one has all DIP switches OFF. I/O monitor number two has DIP switch 1
ON and the other OFF etc.
C Alarm Circuit 2
Alarm Relay Outputs
Temperature Sense 1 +
− 2
Fan Control
2
1.5 mm , max.
(Customer Connections) wire section
Out In
Standard Relays & Digital Inputs The alarm outputs from the I/O Monitor use the Fail-
Safe Operation Mode (relay coils energized in the
system’s normal operation mode). When the system is
Normal mode NO
Relays X
Com + in alarm mode, the alarm relay coils are de-energized.
NC
(Energized coil) —
Alarm mode NO
The figure shows the position of the relay contacts
Relays X (De- Com + when the relay coils are de-energized (PS system in
energized coil) NC
— alarm mode).
Power System
Correct Use of Alarm Outputs (example)
Normal Mode
Digital Input X + External Relay Y
— In order to implement monitored fail-safe digital inputs
(Normal mode) (Energized coil)
Digital Input X
+ Alarm Mode circuits, the external relay coil must be energized and
—
(Activated)
External Relay Y the contacts closed in the system’s normal mode of
(De-energized coil)
operation.
Power System
Correct Use of Digital Inputs (example)
Smartpack Control Unit — front keys, display, etc Flatpack2 Rectifier Module — front panel
Display: is in Status Mode (displays the system’s status) Power LED is OFF (mains unavailable), Flashing
or in Menu Mode (displays the menu structure). (controller accessing information) or ON (powered).
Operation: Press on the key to change from Status Warning LED is ON (de-rating or similar minor
Mode to Menu Mode. Press the or keys to scroll warning), Flashing (over-voltage mode) or OFF (OK)
up or down and navigate to find menu options (function
or parameter). Then press the key to select the Alarm LED is ON (shutdown or similar major alarm)
function. or OFF (OK, no alarm)
The ”XvX” references, if any, on the right hand of the option, are not shown in the display. They only
NomVolt Change Language à English ↓↑ 2v0
BoostVolt NomVolt ↓↑
↓↑
indicate the firmware version (402073.009 XvX) the option was first implemented.
LoBattMaj BoostVolt
VoltageInfo LoBattMin LoBattMaj ↓↑
Firmware 402073.009 2v00 Smartpack,
↓↑
Software Menus
LVLD 1.1
SoftwareInfoà VoltCalibration à VoltCal ↓↑
SerialNumberà ChangePassword à Password ↓↑
NoOfRects. nn SetManBoostTime à ↓↑
RectCurrent Start/StopBoost à
Rectifier Info RectSerialNumber Enable/Disable ↓↑ & Threshold
…
1. Install PowerSuite
1 Insert the CD in your PC drive, start the PowerSuite installation
and follow & accept the wizard default steps
2. Switch Smartpack ON and plug USB cable (Part 202073)
2 to Smartpack and to any available USB port in the PC
3. Wait for Windows to install USB drivers
Follow & accept the wizard default steps to automatically install
3 New hardware the USB drivers; the wizard runs twice
is ready to use
4. Start PowerSuite and establish connection
Select “Start > All Programs > Eltek Valere> PowerSuite”. On
4 the toolbar, click “Connect” button. On the Connection dialogue
box, click the “Connect” button
If PowerSuite fails communicating via the standard COM port, find the COMx assigned to
Smartpack (My Computer/ Properties/ Hardware/ Device Manager) and configure PowerSuite to
communicate via this COMx (read the instructions in the installation CD).
PowerSuite’s newest version is always available on our FTP server. Call your Eltek Valere’s
contact person.
For first time installations of rectifiers in power system, follow the scheme below:
1. Insert & hot-plug the rectifiers in the indicated positions (refer to the figures below)
one module at a time, allowing 2 seconds delay between them
and starting with ID number 1, 2 and 3.
PE (Protective Earth)
TE (Telecom Earth)
Earth connections are in particular important Link 2 EG (Exchange Ground)
AC Mains Input
(L1,L2,L3,N)
—
wires
—
AC Earth (PE) is connected to chassis. DC Earth (TE) is also
—
—
connected to chassis via “Link 2”. Remove the link (“floating
Negative DC
earth”) for compliance with other local earthing systems. Refer
Distribution to your system’s specific drawings to identify how these links
are implemented in your DC power system.
Common Positive DC Output Rail is usual in 48 and 60V DC supply systems: Negative DC
Distribution.
-48Vdc connection
for the optional
BTS MetroSite kit
-48Vdc connections
on the breakers
Load breakers
0Vdc positive
Battery breakers connections on the
copper rail
1 Toggle switch
2 Breaker 1 and 2 parallel
load breaker 2 connected
1
3
Linking bar
Battery compartment
The battery shelf is designed to accommodate standard 19” batteries. Standard 19” batteries are
approximately 105mm wide. The total width of the battery shelf is 445mm but do not mount
batteries wider than 105mm due to cooling reasons. There should always be a small gap of air
between the batteries for fan / Heater air to circulate.
Maximum depth is 400mm. Batteries deeper than 375mm will stick out in the front of the 19”
side rails. The battery Arrestor has to be removed before lifting the batteries onto the shelf. After
the batteries are placed on the battery shelf the battery arrestor can be mounted in 5 different
positions on the battery shelf and be slid into the front of the batteries. This will prevent the
batteries from moving. If 400mm deep batteries are used the Battery Arrestor is redundant.
Minimum battery depth for using the battery Arrestor is 232mm.
The battery compartment can accommodate maximum to 8U / 356mm high batteries. 8U
batteries will leave a 10mm gap between the top of the batteries and the underside of the DC
power system. There must always be some space between the top of the batteries and the bottom
of the DC Power System for safety reasons. The battery terminals must be at least 10mm from
chassis (0V).
Note! Installation of optional kits is described in manuals that are supplied with the kits.
Safety Precautions
Follow these precautions during installation, commissioning and general handling of Outdoor
Cabinet.
General Precautions
ü CAUTION: Even though the product incorporates protection circuitry and other
safeguards, it can be damaged, perform poorly or have a reduced lifecycle if it is
exposed to incorrect treatment during transport, installation or service.
ü CAUTION: The installer is responsible for ensuring that the EMC properties of this
product/ system do not deteriorate during installation, and that it is performed in
accordance with applying regulations.
Installations in USA and Canada must comply with NEC/CEC requirements.
ü WARNING: Opening the equipment may cause terminal injury — even if the mains
AC supply is disconnected. Hazardous voltages may be present inside, as large
capacitors may still be charged.
ü To be installed only in restricted access areas or the like, in accordance with articles
110-16, 110-17, and 110-18 of the National Electrical Code, ANSI/NFPA 70
For supply connectors use wires suitable for at least 75˚C (167˚F)
Type: FEPW, RH, RHW, THHW, THW, THWN, ZHHW, USE, ZX or similar.
Use copper conductors only
ü Installation in USA/Canada must comply with NEC/CEC. For other countries, local or
national requirements may apply.
ü The equipment represents an energy hazard and failure to observe this could cause
terminal injury and invalidate our warranty
ü Products into which our components are incorporated have to comply with a number of
requirements. Installation is to be in accordance with the recommendations herein
ü The enclosure must remain locked at all times, except when authorized service
personnel are present
ü Read and follow all installation, equipment grounding, usage, and service instructions
included in this manual
ü Use proper lifting techniques whenever handling the enclosure, equipment, parts, or
batteries
ü WARNING: For safety reasons (high leakage current and high touch current) you
must always connect the AC earth wire (PE) to the terminals, before you connect
the AC input cable(s).
Electrical Safety
ü Lethal voltages are present within the power supply and electrical boxes. Never assume
that an electrical connection or conductor is not energized. Check the circuit with a volt
meter with respect to the grounded portion of the enclosure (both AC and DC) prior to
any installation or removal procedure
ü The supply neutral conductor must be bonded to earth ground at the disconnect panel
ü Hazardous electrically live parts inside the enclosure are energized by batteries even
when the AC input power is disconnected. Make sure the power is removed via the
battery disconnect breaker before servicing any of the equipment
ü The internal equipment may be powered by AC circuits. Make sure power is removed
via the appropriate breaker before servicing any of the equipment
ü Prior to installation, verify that the AC input voltage to the enclosure and its equipment
with respect to voltage and frequency
ü Prior to installation, verify that the output voltage from the enclosure or its equipment
match the voltage requirements of the connected equipment loads
ü Prior to installation, verify that the enclosure’s utility service panel is equipped with a
properly rated circuit breaker for use with the equipment inside. Refer to the
manufacturer’s recommendations
ü Prior to installation, contact local utilities, local building maintenance departments, and
cable/piping locating services to ensure that installation does not interfere with existing
utilities or building cables/piping
ü Fuses/circuit breakers may not be provided with the equipment. Refer to the
documentation for the proper hardware. Use only the parts specified in the
documentation. Installing fuses or circuit breakers not specified for use in this equipment
may result in injury to service personnel or equipment damage
ü Where required for installations in the United States or Canada, use listed/certified
compression connectors to terminate listed/certified field-installed conductors. If the
proper connector for the country of installation is not provided, obtain the appropriate
connectors and follow all manufacturer and local requirements for proper connections
ü Torque the electrical connections to the values specified on labels or in the product
documentation
ü The DC distribution is considered a Safety Extra Low Voltage (SEL V) with the return
side connected to the chassis (earth ground) inside the enclosure
ü The supply neutral conductor must be grounded at the external service supply
disconnect panel
ü Do not use other methods for cable entry than what is specified in the documentation for
this product
ü Do not drill new holes or use other methods for cable entry than what is described in the
product documentation
Mechanical Safety
ü Keep hands, hardware and tools clear of the fans. Fans are thermostatically controlled
and will turn on automatically as a function of temperature
ü Rectifiers can reach extreme temperatures under load and normal operation
ü Do not climb on the enclosure to access the cable entrance. Always use the proper
ladder and safety precautions as dictated by the site conditions
Battery Safety
ü Always wear eye protection, rubber gloves, and a protective vest when working near
batteries. Remove all metallic objects from hands, wrists, and neck
ü Batteries contain dangerous voltages and current, as well as corrosive material. Battery
maintenance, service, and replacement must be performed by authorized personnel
only
ü Never use non-insulated tools or other conductive materials when installing, maintaining,
servicing, or replacing batteries
ü Prior to handling the batteries, touch a grounded metal object to dissipate any static
charge that may have developed in your body
ü Batteries contain or emit chemicals known to the State of California to cause cancer and
birth defects or other reproductive harm. Battery post terminals and related accessories
contain lean and lead compounds. Wash hands after handling
ü If any battery emission contacts the skin, wash immediately and thoroughly with water.
Follow your company’s approved chemical exposure procedures
ü Neutralize any spilled battery emission with a special solution contained in an approved
spill kit or with a solution of 1 lb bicarbonate of soda to 1 gallon of water. Report a
chemical spill using your company’s spill reporting procedures and seek medical
attention, if necessary
ü Battery cables must be dressed to avoid damage to the conductors. Damage or stress
can be caused by routing around sharp edges or in areas where wires could get pinched
ü Follow battery manufacturer’s approved instructions to set all battery related parameters
accordingly
Mechanical Installation
ü WARNING: Do NOT open the cabinet’s door before the cabinet is securely
fastened to the ground, as the door’s weight may overturn the cabinet.
ü Note! Do not install the batteries until the cabinet has been properly fastened
ü Note! Make sure that the lifting lugs has shrink tubes as shown in Figure 11 to
prevent scratching the cabinet paint.
Shrink Tubing
Figure 10 – Plinth dimensions (see cabinet details for dimensions that match the cabinet that has been ordered)
The wall bracket needs to be fastened to the wall before lifting the cabinet into position.
Enter the four M8 bolts in the available holes on rear side of the cabinet. See Figure 12. Let the
bolts stick out approximately 4-6mm. The wall bracket material is 3mm thick and the bolt heads
have to go into the key holes in the wall bracket and slide into position.
Wall Bracket
Pole Anchor
Mount the two wall brackets together with the two pole anchors by the use of 4 M8 screws,
washers and nuts. Torque 24 Nm.
The pole bracket needs to be fastened to the pole before lifting the cabinet into position.
Enter the four M8 bolts in the available holes on rear side of the cabinet. See Figure 12. Let the 4
bolts stick out about 4-6mm from the rear insert nuts.
Mount the bracket to the pole using M8 bolts and pole bracket that are included with the bracket.
Tighten the screws evenly on both sides. Torque 8 Nm.
Fix the four M8 bolts on the rear side of the cabinet with Torque 24 Nm.
ü Do not install the batteries until the cabinet has been properly fastened.
Start with removing the front by open the cabinet door and pull the front plate towards you.
Remove the desired side plate(s) by unfixing the 2 self locking M5 nuts from the inside of the
plinth. Push the side plate away from the cabinet and then pull the side plate towards you.
8. Battery Connections
ü Note! Improper handling of batteries can result in the batteries short-circuiting, which
can result in serious injury due to high energy levels. Excersise care when
working with batteries. This is also because of the batteries weight.
ü Note! Ensure that the battery circuit breakers are off.
Normally it is not necessary to fit venting tubes to VRLA batteries in a fan cooled cabinet since
any battery gas will be evacuated with the hot air through the cabinet door. However some
battery manufacturers always recommend installing venting tubs. Follow your battery supplier’s
recommendation.
If venting tubes are recommended please ensure battery manufacturer instructions with regard to
connection of the venting tubes are followed. Pull the tube out through the cabinet cable entry
from the inside and ensure that the tune is not bent or blocked in any way.
Figure 16 – Insert nuts on the 19” side rails for cabinet grounding.
Connect the grounding cable with a cable lug and M6 screw to one of the grounding points in the
cabinet. There are 4 insert nuts for grounding on both sides of the cabinet. Make sure that the
cables are secured tightly.
CAUTION:
- The modules may be warm, but do not hand-carry them by their handles
Device - Open the handles before inserting them into the power shelves (hot-pluggable)
hazard The rectifier incorporates a Mains fuse in each line. Double Pole / Neutral Fusing
Hole to release the Note that cables are plugged to the Smartpack’s rear panel.
Smartpack handle’s spring
controller mechanism When mounting the controller, you must plug the cables before
step 2. When removing it, unplug the cables during step 2.
FGFG Warning:
- Only mount rectifiers, part 241115.120, with the fan rotation symbol on the front!
- The modules are mounted vertically (see picture on front page)!
Screwdriver to
release the locking
tabs Removing Blind Panels
1. Release the panel’s upper and lower right corners by
inserting a small screwdriver into the panel’s upper right gap
and carefully press down and out to release the locking tabs.
Repeat on the lower right gap
2. Remove the blind panel by
using you hand to pull the panel loose
Blind panel’s
locking tabs
General Torque
Recommended tightening torque Carry out following steps sequentially:
Application, Torque 1. Make the system completely voltage free
Type & Size (Nm) o Switch OFF all load fuses, battery fuses (Fb1, Fbx), and
Circuit Breakers the external AC supply fuses
CBI 13 mm, QY, QF, QA 3.0 o Unscrew the Cable Entry Plate and route all cables
Siemens 18mm 5SY 3.5 through their suitable holes. Then, loosen fastening screw
DC Rail Terminals
AKG 35 (M6) 3.5
and extract the “AC Terminals plate” to Maintenance
AKG 70 (M8) 5.0 position.
Screws 2. AC Connections
o Connect the AC Earth wire (PE) to the terminal for AC
M6 5.0 Earth (PE).
M5 4.0
M4 2.0
o Connect the AC input cable(s) to the terminals marked L
M3 1.0 and N. Cable and terminal block labeling are to
correspond.
Mains ”PE” terminal block
shock
c Connect the other end of the (-) battery cable to the
battery string’s negative outer terminal (-)
d Verify that one end of the (+) battery cable is connected
to the common positive DC rail
e Connect the other end of the (+) battery cable to the
Temp. sensor
Battery
Cable
battery string’s positive outer terminal (+)
g Fix the temperature sensor (at the end of the cable) to
the warmest area of the installed battery bank
(to the center (width & depth) of the battery string)
- + - + - + - +
—
(-48V) Outer
Terminal
Block Block Block
+
0V Outer
Intercell links Terminal
2. Electrical:
The commissioning of the FP2 system consists of following stages:
I. Perform a pre-start check before the system is switched ON
II. Switch ON the system with disconnected load; adjust output voltage
III. Adjust the nominal output voltage with connected batteries and load
Pre-Start Check
Check off in the Commissioning Procedure, that you find in chapter 6 in this document.
If you have just finished the system installation successfully and the Installation Check List is
completed, jump over the Pre-Start Check and continue with stage II.
M6x12mm screw
11. Mount all Flatpack2 rectifier modules in the power shelves (keep original location)
o Push all rectifiers firmly inwards one module at a time, allowing a 2s delay to plug them in
the same shelf location. Lock their handles.
o Mount blanking panels over unused positions.
System Failures
Symptom Possible Error How to Find and Eliminate the Problem
1. All LED’s OFF ü No AC supply or Both input and output are disconnected from
(rectifiers and batteries present power sources.
Smartpack)
• Inspect connections and verify input voltage
and battery circuit breaker states
2. Excessive ü System fan error Locate the noise source.
audible noise
ü Rectifier fan error • If a rectifier module is creating the noise,
replace the rectifier with a new one
Gasket
Figure 18 - Gasket
Check and make sure that the gasket on the door is complete.
ü Note! It is of great importance that ONLY Eltek Valere original filters are used
when changing the filter, to keep the level of dust and water protection for the
equipment inside the cabinet. Contact your local representative for stock.
Eltek Valere recommends bi-monthly site checks during the first year of operation, to establish
actual filter replacement intervals for each individual site.
6. Connect the fan Turn on the breaker for See GA for actual position.
the fan, and verify that
the fan is running.
Site, name:
Serial No.: Software, version No.: Rectifiers, type & number of:
AC Input Voltage, measured: Battery Type: Battery Capacity: Installation carried out by, name:
Approval
Responsible of installation, sign.: Date: Approved by customer, sign.:
Site, name:
Serial No.: Software, version No.: Rectifiers, type & number of:
AC Input Voltage, measured: Battery Type: Battery Capacity: Commissioning carried out by, name:
1. Flatpack2 system installation is completed; The Flatpack2 Installation Check List is filled in.
All cabling is securely terminated with correct polarity o
2. All battery and load MCBs/ fuses are disconnected
o
I 3. AC input cable(s) and AC earth wire (PE) are terminated
o
Device
4. Site specific parameters and settings are known
o
hazard 5. AC supply and all MCBs/ fuses are switched OFF
o
Start-up, No-Load & Load Adjustments Power is ON!
CARRY OUT FOLLOWING: OK
1. Disconnect all rectifier modules, without removing them (keep original location)
o
2. Remove the Condensation Stopper
o
3. Switch ON the system (external AC fuses ON)
o
II 4. AC input voltage is correct; Measure and verify
o
5. Insert all Flatpack2 rectifiers in their original locations in the power shelves
o
Device
hazard
6. The Smartpack and all rectifier modules are working, LEDs are ON; Verify
o
7. Connect a PC to the PS system Install the PowerSuite software, if required
o
8. DC output voltage; Measure and adjust
o
9. Alarm relay test; Verify all alarm relays are working correctly
o
10. System Setup is in accordance with configuration Enter site spec. info in PowerSuite
o
11. Adjust DC output voltage to equal measured battery voltage Check correct polarity!
o
12. Unplug all rectifiers but one, and connect all battery fuses/ MCBs
o
13. Adjust DC output voltage to equal nominal battery or load voltage
o
14. Plug in again all rectifiers, and verify the rectifiers’ current sharing
o
15. Connect all load MCBs/ fuses, and verify no alarms are displayed
o
Approval
Responsible of commissioning, sign.: Date: Approved by customer, sign.:
Site, name:
Serial No.: Software, version No.: Rectifiers, type & number of:
AC Input Voltage, measured: Battery Type: Battery Capacity: Maintenance carried out by, name:
4. Alarm Relay Test; verify all alarm relays are working correctly.
From the Smartpack’s keypad or PC use the Relay Test function; verify activation of external equipment o
5. Battery bank control; measure and verify battery specifications.
Follow the recommendations of the actual battery manufacturer. o
Approval
Responsible of maintenance control, sign.: Date: Approved by customer, sign.:
BATTERY FUSES
FB2
- 150A LVBD Contactor
FB3
12U - 3 x 60A Battery breakers (FB1-FB3)
- 2 x 60A Load breakers (F1-F2)
- 2A MCB for fan
10U - 8U battery compartment
Battery and load breakers - Mains input terminals for 1ph230Vac TN
-Temp sensor for battery monitoring
6U
HxDxW: 736x581x585mm
Door
fan
MCB PE N L
61
- A4 1 of 1 2040397 3
General Assembly Drawing with Options
Single backwiring
0V
L1 JP2 + LVBD
N JP1 SH1
- - FB1
PE JP3 - +
HEATER KIT Y X
Con2, pin 1
End term
Con2, pin 2
OPTION - FB2
Powermodule pos 2
Single backwiring
PE L1 JP2 + - FB3
Thermostat N JP1
L N -
ϑ PE JP3
BTS kit
Con2, pin 1
Con2, pin 2
OPTION
Heater BTS Fuse
Heater Fuse
Powermodule pos 3 - F3
(Rightmost facing dist)
Single backwiring
- F4
L1 JP2 + System Connection Board
200625 *X5 - F1
N JP1
- Con 5A* System Connection
15 + 1 - F2
PE JP3 System Connections Power Input
- 2
+ 3 Diode
Battery Current
Con2, pin 1 - 4 Matrix
Con2, pin 2 Battery Fuse Fail + 5
SPD kit
Blue
Green
White/Blue
CAN Cable
NEG. DIST.
POS. DIST.
NEG. DIST.
POS. DIST.
OPTION JP1 JP2
1 2 3 1 2 3
L PE
11
14
N N
L
connections
63
T2 – Temp sense for door fan Sym. Alteration Date/Sign
Consultant Format Page Draw. No. Rev.
- A3 1 of 1 2040399 2
Smartpack Set-Up
Smartpack
Prepared by: ErBrNo System Part no.: C20315.001 Smartpack part no.: 242100.110 SW Rev: 3.01 Doc no.: 2054036 Doc rev: 1
Approved by: OlHuNO CTO: Mains input: 1PH 230Vac System type: 48V 24V
Note! If any customer changes are made in this document, they will overwrite the default values in the Smartpack.
3.1 PROG INPUT 1.1 Disabled Over Voltage Disabled Normally Over Voltage Major Alarm
Device closed Device
3.2 PROG INPUT 1.2 Disabled Door Open Enabled Normally Door Alarm Major Alarm
closed
3.3 PROG INPUT 1.3 Disabled
3.4 PROG INPUT 1.4 Disabled
3.5 PROG INPUT 1.5 Disabled
3.6 PROG INPUT 1.6 Disabled
CUSTOMER DEFINE
DEFAULT ALARM GROUP
Para Set Alarm Levels
VALUE NAME DEFAULT
Value Alarm Group Funtion
5.1 Default Relay Config: Normally Normally Latched Latched Normally Normally Normally Normally
activated activated contactor contactor activated activated activated activated
5.2 Customer Relay
Config:
CUSTOMER DEFINE
Para Alarm Groups DEFAULT VALUE
New Description Relay Relay Relay
8.1 Battery Table High end volt (ref 1) 1,90 V/cell 1,85
8.3 Min 15 30 60 120 180 240 300 360 420 480 540 600
8.4 Ref 1 157,4 101,7 61,7 35,7 25,4 20,0 16,4 14,0 12,3 11,3 10,2 9,3
8.5 Ref 2 176,5 109,7 64,8 36,6 26,0 20,2 16,6 14,1 12,4 11,5 10,3 9,4
Para System configuration DEFAULT VALUE CUSTOMER DEFINE VALUE
10.1 Note! The following paragraphs are set in the I/O monitor: 3.1 and 3.2 (digital inputs for "Door Open" and "AC Surge Protection")
Note! The following paragraphs are set in the I/O monitor: 6.1 and 6.3 to 6.9 (Alarm Relay Outputs). These new descriptions must contain Smartpack
10.2 alarm group configuration as well
Fan control1 settings: Configuration: Low point: Temperature=20ºC, Speed=10%; High point: Temperature=55ºC, Speed=80%;Calibration: Low
10.3 calibration point[A] - Voltage[V]=2, High calibration point[A] - Voltage[V]=10
10.4 Fan speed 81.1 settings: General: disabled Fan config: Max fan speed (RPM)=4000 pulses per revolution (PPR)=2