BATTERY SIZING DONE TO IEEE485 STANDARD

CUSTOMER Eaton Industries Sdn Bhd Date 17-10-2019


Sized by: SYED FIAMM MALAYSIA
PROJECT Battery for UPS in Cyberjaya
FIAMM Sizing Tool 2.1.22
DESIGN MINIMUM CELL ELECTROLYTE CELL TYPE:
TEMPERATURE: 20 °C VOLTAGE 1.750 Volt DENSITY DATI1 40
(1) (2) (3) (4) (5) (6) (7)
PERIOD LOAD CHANGE IN DURATION TIME TO END #VALUE!
LOAD KVA LOAD OF PERIOD OF SECTION #VALUE! #VALUE!
( minutes ) #VALUE!
Pos. Values Neg. Values

Section 1
1 A1 = 250.0 A1-0 = 250.0 M1 = 10 M1= 10 #VALUE! #VALUE! #VALUE!
Sub total #VALUE! #VALUE!
Total 1................ #VALUE!

#VALUE! Design Margin = 1.00 Aging Factor = 1.00


#VALUE!
#VALUE!
Capacity = 240 Ah () Number of cells = 2 x 40 Cell Type = 12 FLB 450 P

Requested Load Profile


300

250
250

200
KVA

150

100

50

0
0 2 4 6 8 10 12

MINUTES

480VDC