Вы находитесь на странице: 1из 10

Security Level:

DCDU power connection standard

www.huawei.com

HUAWEI TECHNOLOGIES CO., LTD. Huawei Confidential


DCDU/Power cable Connection failure Photo

BBU/RRU cable connector heat or burn up due to wrong installation


Lead to many sites power fail or down

HUAWEI TECHNOLOGIES CO., LTD. Page 2


One page inspection key points
1. Check the sheath stripping length follow with the 3. Check any power cable not fully insert or any wire come out or not like
standard or not, should be 18-20mm below showing:

2. Check the positive and negative cable is reversed by 4. Check the RRU power connection as well should follow above standard
mistake or, also check the screws tightened at 1.4N.m (there is also logo of standard marked length) like below showing:
or not like below showing:

HUAWEI TECHNOLOGIES CO., LTD.


Root Cause Analysis :
Scenario 1: the length of Strip sheath off not enough
 The length of Strip sheath off not enough, it cause the contact surface
Of the wire decreased, So the electric resistance increase, after Long-term use of heat
lead to burn 。(Q=I²Rt , “R “ increase,lead the Q increase)

Should follow the installation standard length

Page 4
HUAWEI TECHNOLOGIES CO., LTD.
Scenario 2: the loose of tighten connector or the cable exiting
after loosening
 Poor fastening of connector lead the contact surface Of the wire decreased, So the
electric resistance increase, after Long-term use of heat lead to burn 。(Q=I²Rt , “R
“ increase,lead the Q increase)

Page 5
HUAWEI TECHNOLOGIES CO., LTD.
RRU/DCDU Power connector installation quality
inspection and rectification guide

HUAWEI TECHNOLOGIES CO., LTD.


Inspection/Rectification Guide and Photo reference
 1. Check whether the  2. check the tail of the connector that no
cable of the connector tail scorching or blackening, Whether there is
and the connector are pressure to insulation, Use standard fastening
scorching or blackening; torque 1.4N.m to check if the screw is tightened;

1.4 N·m

Page 7
HUAWEI TECHNOLOGIES CO., LTD.
Inspection/Rectification Guide and Photo reference
 3. Removing power line of the abnormal parts, Reference installation guide to
install the wires again, replace the damaged connector;

EPC5 connector RRU power connector

Page 8
HUAWEI TECHNOLOGIES CO., LTD.
Inspection/Rectification Guide and Photo reference
 4. Tighten the screws to 1.4 N·m (12.39 lbf·in.) using a torque screwdriver;

1.4 N·m

 5. Check whether the wires are securely installed. If the wires are pulled out
a bit or exposed outside the holes, remove and cut the split wires, and then
strip the sheaths and install the wires again.