User Manual

External IEC61850 Box


TRENCH AUSTRIA GMBH
Paschinger Straße 49
A 4060 Leonding
Austria

Phone: (43) (732) 6793-0


Fax: (43) (732) 671341

Page 2 Version 1
External IEC 61850 Box March 2015
Table of Contents

1 General ..................................................................................................................... 4
1.1 Safety ........................................................................................................................................................ 4
1.2 Qualified personnel ..................................................................................................................................... 4
1.3 Range of delivery........................................................................................................................................ 5
2 Function .................................................................................................................... 5
2.1 Notification of the front panel ....................................................................................................................... 5
3 Electrical Data .......................................................................................................... 6
3.1 Power supply.............................................................................................................................................. 6
3.2 Interfaces ................................................................................................................................................... 6
3.3 Type tests .................................................................................................................................................. 7
4 Mechanical dimensions ........................................................................................... 8
5 Climate / protection degree ..................................................................................... 8
6 Mounting the external IEC 61850 Box .................................................................... 9
6.1 Mounting within the EFC50(i) 19” rack ......................................................................................................... 9
6.2 External mounting within a cabinet ............................................................................................................ 10
7 Setup of the external IEC 61850 box .................................................................... 11
7.1 Necessary hardware preparations ............................................................................................................. 11
7.2 Necessary program settings within the Trench device ................................................................................ 12
7.3 Handling of the „IEC 61850Configurator“ - program ................................................................................... 14

Version 1 Page 3
March 2015 External IEC 61850 Box
1 General
1.1 Safety

WARNING

During operation of electrical devices some parts of the devices are inevitably live. Disregarding the hints may lead
to severe injuries or damages.
Proper transport, storage, installation and mounting and furthermore careful control and maintenance are
mandatory for faultless and safe operation of the device. If it is assumed, that safe operation is not possible any
more, the device has to be switched off immediately and furthermore it has to be protected against unintentional
reuse.

It has to be assumed, that safe operation is not possible any more if the device:

is visibly damaged

has been exposed to unfavorable conditions i.e. for a period of time outside the rated climatic limits (e.g.
storage outside allowed climatic limits without adaptation to the indoor environment, moisture
condensation)

has been exposed to heavy transport stress (e.g. drop from great height without visible external damage)

1.2 Qualified personnel


Are defined as persons, which are acquainted to installing, mounting, putting into service and operating the product
and which have the respective qualifications, a.s.o.

Education resp. training and furthermore authorization according to safety standards to switch on, switch
off, to isolate, to earth and to mark circuits and devices.

Education resp. training and furthermore authorization according to safety standards for maintenance and
use of suitable safety equipment.

Training in first-aid.

The product leaves the factory in a condition fulfilling all safety requirements. To maintain this condition
and to allow safe operation the user has to follow the hints and warnings in this manual.

The operator has to insure, that the protective grounding of the device (marked with grounding symbol
( ) is connected to earth. Any internal or external disconnection of the protective conductor or
unintentional disconnection of the protective grounding may lead to dangerous conditions and is therefore
not allowed.

Before taking into operation it must be insured, that the supply voltage fits into the given ranges. Only
fuses of the correct type may be used. It is not allowed to use repaired fuses or to short circuit the fuse
holder.

Live parts may be exposed when opening cover parts or removing parts. If opening of the device is
necessary for adjustment, maintenance, repair or exchange of parts the device has to be disconnected
from all power supplies prior. If then adjustment, maintenance, repair or exchange of parts in live condition
is inevitable, this has to be performed by skilled personnel, acquainted to involved risks.

Page 4 Version 1
External IEC 61850 Box March 2015
1.3 Range of delivery
The following items are included at the delivering:
External IEC 61850 Box
Zero-Modem cable (3m)
Connector for Power Supply (3 pol.)
Top-hat rail adapter (already mounted at the backside)
CD with user manual and Firmware
User manual (hard copy)

Optional:
2 threaded stripes (approx. 200 mm each) / needed for mounting on an EFC50(i) device only

2 Function
In case of using SCADA protocol IEC 61850 at Trench protection devices an additional board is needed, which can
be mounted directly into the protection device by ordering both together.
If IEC 61850 protocol should be introduced later, the external IEC 61850 box might be used. By using this box it is
not necessary to send back the protection device to Trench Austria for including the IEC 61850 board.

The external IEC 61850 Box is designed as a retrofitting for Trench protection- and detection devices like EFC20(i),
EFC50(i), EFD20 and EFD500.

2.1 Notification of the front panel

X1… LAN interface to SCADA

Reset switch

Status of power supply

Communication indication of X2

COM L2 connected to device

COM L1 connected to device

RS232 interface X2

Power supply 100 – 240V / 50 – 60Hz

Communication indication of X3

RS232 interface X3

Grounding nut

Version 1 Page 5
March 2015 External IEC 61850 Box
3 Electrical Data
3.1 Power supply
Type A: Voltage: 100 - 240 V AC / 50 - 60 Hz or DC
max. Power consumption: 14.4 VA

Type B: Voltage: 20 - 72 V / DC
max. Power consumption: 13.5 VA

Hint
Please double check at the type plate on the right side of the device, if you received the suitable type of power
supply before powering on first time.

3.2 Interfaces
The external IEC 61850 Box is equipped with the following interfaces:

2 x RS 232, 2pcs. 9 pole Sub-D male, for communication between Trench Protection device and
external IEC 61850 Box

1 x Standard LAN port (RJ 45)

Page 6 Version 1
External IEC 61850 Box March 2015
3.3 Type tests
Following tests were performed and passed:

Tests Standards Technical data


Insulation tests Insulation test test voltage 2 kV, 50 Hz, 1min
IEC 255-5
Measurement of test voltage 500VDC
insulation resistance >100M
IEC 255-5
disturbing radio noise voltage 10m from housing 40 dBµV/m
emission EN 55011, IEC 255-25 30-230 MHz
230-1000 MHz 47 dBµV/m
radio noise voltage net lines quasipeak average
EN 55011, IEC 255-25 0,15-0,5 MHz 79 dBµV 66 dBµV
0,5-30 MHz 73 dBµV 60 dBµV
disturbing EM-Feld 80-1000 MHz 10 V/m AM 1kHz
immunity EN61000-4-3 1400-2000MHz 3 V/m AM 1kHz
housing IEC255-22-3 2000-3000MHz 1 V/m AM 1kHz
disturbing ESD contact 6 kV
immunity EN 61000-4-2 air 8 kV
lines IEC 255-22-2
high frequency fields amplitude modulated 3Vemk AM (1 kHz)
EN 61000-4-6 0,15-80 MHz 150 source resistance
IEC 60255-22-6
fast transient Tr/Th 5/50 ns 5 kHz
EN 61000-4-4 net lines 2 kV
IEC 255-22-4 In - and outputs 1 kV
EN 61000-4-5 Tr/Th 1,2/50µ s
Impulse voltage net lines longitudinal voltage 2,0 kV
only at cable length >10m transverse voltage 1,0 kV
In - and outputs longitudinal voltage 2,0 kV
transverse voltage 1,0 kV
supply voltage break net lines 100% reduction
IEC 60255-11 5, 10, 20, 50, 100, 200 ms
Magnetic fields at 50 and 30 A/m 60 s
60 Hz, EN61000-4-8 300 A/m 3s
damped sinus oscillation f0=1 Mhz, Tr = 75 ns
EN61000-4-18 net lines, push-pull 1 kV
net lines, common mode 2,5 kV
environmental chilliness transport and storage -25°C
tests operation 5°C
dry heat transport and storage 70°C
operation 55°C
cyclic temperature change 25°C with 97% rF
with humidity 40°C mit 93% rF
vibration 10 - 150 Hz
transport and storage 1g
operation 0,5g
shock transport and storage 15g 3 and 10g 1000 per axis
operation 5g 3 per axis
earth quake 5 - 35Hz 0,5 1 g

Version 1 Page 7
March 2015 External IEC 61850 Box
4 Mechanical dimensions

Front view Back view

A
C E
B

A B C D E F
81 mm 127 mm 170 mm 2 mm 76 mm 110 mm

5 Climate / protection degree

service: 0°C ... +40°C


storage: -25°C ... +55°C
transport: -25°C ... +70°C
class G according DIN 40040
IP20

Page 8 Version 1
External IEC 61850 Box March 2015
6 Mounting the external IEC 61850 Box

6.1 Mounting within the EFC50(i) 19” rack

A: Please fit in the two threaded stripes (included at the shipment, if ordered for mounting into EFC50(i) rack)
into the suitable rails of the EFC50(i) rack housing as demonstrated at the pictures below.

B: Fix the external IEC 61850 box at the EFC50(i) rack with help of the screws of the external IEC 61850 box
(marked at the picture below).
B

Hint
A visible grounding has to be connected at the designated grounding bolt on the device.

This grounding bolt is marked with .

Version 1 Page 9
March 2015 External IEC 61850 Box
6.2 External mounting within a cabinet

For mounting within a cabinet you will find a top-hat rail adapter located at the backside of the external IEC 61850
box. With help of this adapter you should be able to mount the device in a proper way.

Hint
A visible grounding has to be connected at the designated grounding bolt on the device.

This grounding bolt is marked with .

Page 10 Version 1
External IEC 61850 Box March 2015
7 Setup of the external IEC 61850 box

The SCADA protocol IEC 61850 allows communication and remote control of a Trench device (e.g. EFC50(i) or
EFD500). The connection of IEC 61850 is realized via the standard Ethernet interface plug RJ45.

Principal function:

External EFC50(i) or EFD500


IEC 61850 Box

To Scada network
or PC for configuration

RJ45 (Ethernet) RS232

The actual state of the Trench device is transferred via RS232 (external cable) to a software – model, which runs at
the external IEC 61850 box. The external box communicates with the SCADA via Ethernet and provides the
SCADA with the desired information. Commands, which were sent by SCADA, will be transferred further by the
external box to the Trench device via RS232.

7.1 Necessary hardware preparations

In case of using an EFC20(i) Trench device, please connect the rear interface COM1 and COM-L1 of the
external IEC 61850 box with help of the attached Zero-Modem cable.

In case of using an EFC50(i) Trench device, please connect the rear interface COM2 and COM-L2 of the
external IEC 61850 box with help of the attached Zero-Modem cable (see example picture below).

In case of using an EFD500 Trench device, please choose a free available RS 232 interface on the back
side and assign the SCADA related interface to the chosen port. Then connect the chosen COM port of
the EFD500 Trench device to COM-L2 of the external IEC 61850 box with the attached Zero-Modem cable.

Version 1 Page 11
March 2015 External IEC 61850 Box
LAN – IEC 61850

Zero-Modem cable

Hint
From factory side it is not foreseen to transfer IEC 61850 protocol via fiber optics. If you wish to realize the data
transfer in this way, please use an external Ethernet converter, which converts the electrical signals into optical
signals (not included at the shipment).

7.2 Necessary program settings within the Trench device

Please check, if the following items are adjusted within the display menu of your Trench device:

Press “X” with help of the scroll wheel on the front panel of the controller in order to enter the parameter menu.
Enter the standard password “3” (Password may freely be changed or deactivated, see user manual). Please
perform the following settings, if not already done.

Enable options SCADA Password for option = 1 (If 0, activate the option with the password, which
is written on the type plate of the Trench device or is delivered with the external IEC 61850 box)

Enable options SCADA SCADA protocol = IEC 61850

System configuration SCADA activated = YES

System configuration SCADA device SUB address = A

System configuration SCADA interface parameter SCADA to port = used COM port on the
backside of the device. (in case of this interface cannot be activated, please check, if the interface is not
already assigned somewhere else, see user manual)

System configuration SCADA interface parameter baud rate = 115200

System configuration SCADA interface parameter Stop bits = 1

System configuration SCADA LAN Parameter

Page 12 Version 1
External IEC 61850 Box March 2015
Several network parameters of the external IEC 61850 box may be set here. By pressing „SAVE“ all changes are
transferred to the card. Please consider that the new parameter settings will not be used by the device until the
parameter menu is left and the changes are stored (see example picture for EFC50(i) Trench device below).

You may also check the adjusted parameters in the IEC 61850- information screen (command line at item „I“ at the
example picture of an EFC50(i) Trench device below).

As next step the parameters of the external IEC 61850 box need to be configured. This can be done with the
attached PC-software tool „IEC 61850Configurator“.
Controller (at the RJ45 interface) and PC should be connected via LAN (with a “Cross-Over cable” in case of a
direct connection between the two devices or connection to a network with an ordinary LAN cable). Ethernet cables
are not included in the scope of supply.

Version 1 Page 13
March 2015 External IEC 61850 Box
7.3 Handling of the „IEC 61850Configurator“ - program

Install and start the „IEC 61850Configurator“:

A B

N J

L
I

H
K

G
C

D F

A.) If the program recognizes a device within the network, its MAC address will be shown in the upper left area of
the window. If a device is not found automatically, probably device and PC are not in the same network, but
separated by router, gateway, etc.

B.) In such case you might use “Alternate Search” (activate the small square left of “use”). Write in the IP-address,
which was already assigned within the menu of the Trench device. The factory standard address is
192.168.0.1. Then only the MAC address of the device with the selected IP address will appear.

C.) If necessary, this field may be used to load a new ICD-file on the device. First press on the button “Search..”
and enter the path of the ICD-file and open it. For initiating the data transfer please press “File Transfer” at the
menu point “Parameter”. After a successful transfer operation the file can be activated by pressing “Activate
Parameter / Reboot” at the same menu point as above.

Page 14 Version 1
External IEC 61850 Box March 2015
D.) If necessary, this field can be used to load the mapping – file (*.in) on the Trench device. First press the button
“Search..” and enter the path of mapping – file and open it. The file may be transferred with help of the
function “File Transfer” at the menu “Parameter”. After a successful transfer operation the file can be activated
by pressing “Activate Parameter / Reboot” at the same menu point as above.
Hint: Please enter the paths of the two items from C and D one by one and then activate and reboot
parameter together in one step.

E.) This field may be used to upload a new software version (*.rtb) for the external IEC 61850 box. Normally this
input field is grey, so it is not possible to enter data. For enabling this and other grey items, push the key
combination [Ctrl]+[Alt]+[P]. Then enter the password “*999*”. Please enter the right path and open the
suitable file. Transfer the file with the function „File Transfer“ at the menu point „Parameter”. Finally activate
the new software with the function „Activate Parameter / Reboot“.

F.) At this field the IED name and Access-Point name is displayed. This name must correspond with the ICD- and
mapping- file. After parameter transfer by pressing “Parameter Transfer”, the new parameters can be
activated by using the function „Activate Parameter / Reboot“.

G.) Indication of the ICD file name. This name has to be “Trench.icd”.

H.) IP address of the time server. This adjustment can be done in the menu of the Trench device as well.
Additionally the update interval (with the unit seconds) and the device which shall generate the time stamp
can be defined.

I,J.) Interface parameter of COM-L1 and COM-L2 of the external IEC 61850 box. At the Trench device a standard
baud rate of 115200 baud of COM-L2 is mandatory.

K.) At this area the suitable time zone may be adjusted, resp. the desired time shift may be defined. This time
shift will only be taken into consideration, if the little square of “use daylight time / normal time” is activated.

L.) By activating the square named „Use network parameters from icd file“ network parameters like IP address,
Subnet mask and Standard Gateway will be taken out of ICD-file which is stored at the external IEC 61850
box. If this square not activated, the network parameter will be taken directly from the external IEC 61850 box.
They might in this case also be adjusted at the Trench device directly (see point system configuration
SCADA LAN parameters).

Hint
The illustrated IP addresses of this manual are just examples. For choosing the suitable network parameters,
please contact your companies network engineer.

M.) At the area „Network“ the adjusted network parameters of the chosen device may be displayed, resp. changed.
If the desired device is not being displayed, a possible reason might be that your computer and the Controller
are not located in the same network (divided by Router, Gateway, etc.).

N.) With help of these buttons an ICD file, resp. mapping file which is located within the external IEC 61850 box
can be downloaded to your computer.

Version 1 Page 15
March 2015 External IEC 61850 Box