Академический Документы
Профессиональный Документы
Культура Документы
CHAPTER III
COOLING LOAD CALCULATIONS
Heat Transmission, Solar Radiation, Air Infiltration, Air Exchange, Lighting Loads, People
Loads and Equipment loads are parameters considered in cooling load calculations. This will
determine the capacity of the needed refrigeration system equipment to be used to attain the
desired conditions.
Temperature is an important factor in calculating for the total cooling load. Table 3.0
presents the design temperature considerations to be used. The outside temperature taken is
from the highest recorded temperature in the Philippines (380C) as provided by the database of
PAG-ASA. The Soil Temperature of 20 0C is recorded from Metro Manila.
For offices, comfortable maintaining temperature ranges from 22-270C, taking the
average and considering climate change we get 230C (ASHRAE, 2006).
Temperature (0C)
North 38.40C
1
East 38.50C
Outside Temperature
West 380C
South 38.30C
2
Soil Temperature 200C
3
Air-Conditioned Space Temperature 230C
4
Ambient Temperature 320C
*1 Source: PAG-ASA (http://www.pagasa.dost.gov.ph/)
*2 Source: http://www.visitmyphilippines.com
*3 Source: Stoecker, 1982
*4Source: PAG-ASA (http://www.pagasa.dost.gov.ph/)
13
Centralized Air-Conditioning System 2013
Heat load considerations are transmission load, Lightings, People load, Equipment load,
Solar Load, Air exchange and Air Infiltration. The calculation for the following design
parameters is presented below.
o The variation of the solar radiation intensity that is incident upon the surface
over a period of 24 hours.
The phenomenon is further complicated by the fact that the design considerations such
as walls, floor and roof has a thermal capacity due to which certain amount of heat passing
through it is stored and is transmitted to the outside and/or inside at some time later(Arora,
2009). In calculating transmission load the formula is given by:
Q=UAΔT
A = Area (m2)
Also, Total Transmission Load is equal to the summation of the transmission loads
calculated for each surface considered. We assume that the outside air film (hO) is equal to 22.7
W/m2-k, the inside air film (hI) is 8.29 W/m2-k and the soil convective heat transfer coefficient
(hs) is 71 W/m2-k.For the summary, refer to Table 3.1.
14
Centralized Air-Conditioning System 2013
Formula:
𝒍 𝟏
𝑹=∑ +∑
𝒌 𝒉
Where:
The conduction heat transfer through the wall or roof will depend on the thickness and
the thermal conductivity of the material used. In addition there will be convection and radiation
from both the outside and inside surfaces. Hence the steady heat transfer is expressed in terms
of an overall heat transfer coefficient (U) and overall temperature difference between the
outside and inside. In that case, U will incorporate the effect of all the materials (Arora, 2009).
Formula:
𝟏
𝑼=
𝑹
Where:
U = Overall Heat transfer Coefficient
R = Thermal Resistance
15
Centralized Air-Conditioning System 2013
Tables 3.2, 3.3, 3.4, 3.5 ,3.6 and 3.7 shows the material details and equivalent thermal
conductivities to compute for the transmission load. Also the following Tables presents the
resistances and overall heat transfer coefficient as calculated.
16
Centralized Air-Conditioning System 2013
Transmission load varies directly to the material used in the construction and its
orientation which changes the temperature difference. Transmission loads are from walls,
windows, doors, floors and ceilings.
o Through Walls
The total Transmission load through walls is 29076 watts or 29.076 KW.
Sample Calculation
𝑄𝑡 = 𝑈𝐴𝛥𝑇
𝑄𝑡 = 𝑄𝑁 + 𝑄𝐸 + 𝑄𝑊 + 𝑄𝑆
17
Centralized Air-Conditioning System 2013
Tables 3.8, 3.9 and 3.10 presents the transmission loads through walls for the 1 st, 2nd
and 3rd floors.
18
Centralized Air-Conditioning System 2013
o Through Doors
The total Transmission Load through doors is 133 watts or 0.133 KW.
Sample Calculation
1st Floor;
𝑄𝐷 = 𝑈𝐴𝛥𝑇
Tables 3.11 show the transmission loads through doors for the 1st, 2nd, 3rd Floor.
o Through Floors
The total Transmission Load through floors is 3602 watts or 3.602 KW.
Sample Calculation
𝑄𝐹 = 𝑈𝐴𝛥𝑇
𝑄𝐹 = (4.72)(17.78)(32 − 24.5)
19
Centralized Air-Conditioning System 2013
Table 3.12, 3.13 and 3.14 presents the transmission load through floors from 1st to 3rd
floor.
20
Centralized Air-Conditioning System 2013
o Through Ceiling
The total Transmission Load through Ceilings is 4949 watts or 4.949 KW.
Sample Calculation
𝑄𝐹 = 𝑈𝐴𝛥𝑇
𝑄𝐹 = (4.13)(4.73)(32 − 23)
𝑸𝑭 = 𝟎. 𝟏𝟔𝟐𝟒 𝑾𝒂𝒕𝒕𝒔
Table 3.15, 3.16 and 3.17 presents the transmission load through Ceiling from 1st to 3rd
floor.
21
Centralized Air-Conditioning System 2013
Lights provide illumination inside the office for people working while in operation.
Lighting does not need to be excessive to allow safe movement.
A typical fluorescent lamp used in an office has a rating of 20 watts and has 1300
lumens/m2. Figure 3.0 shows a typical light fixture inside an office.
Determination of the no. of lamps needed to illuminate the cold storage is calculated
using the formula given below. Also, the minimum requirement for illumination is 540
lumens/m2(Arora, 2009).
Formula:
𝑙𝑢𝑚𝑒𝑛𝑠
𝐴𝑟𝑒𝑎 𝑋 540 𝑚2
𝑁=
𝐿𝑢𝑚𝑒𝑛 𝑜𝑢𝑡𝑝𝑢𝑡 𝑜𝑓 𝐿𝑎𝑚𝑝
Sample Calculation
𝑵 = 𝟕. 𝟑𝟖 𝒍𝒊𝒈𝒉𝒕𝒔 𝒐𝒓 𝟖 𝒍𝒊𝒈𝒉𝒕𝒔
22
Centralized Air-Conditioning System 2013
Tables 3.18, 3.19 and 3.20 presents the number of lights needed by each office. The
total no of lights needed by the building is 100 lights.
To calculate for the light load, light watt rating, lighting use factor and lighting special
allowance factor should be available. The total light wattage is obtained from the ratings of all
lamps installed, both for general illumination and for display use.
The lighting use factor is the ratio of the wattage in use, for the conditions under which
the load estimate is being made, to the total installed wattage. For commercial applications
such as stores, the use factor would generally be unity (ASHRAE, 1997). For Lighting Special
Allowance Factor, 1.2 is used for most common fluorescent fixtures (Stoecker,1982).
23
Centralized Air-Conditioning System 2013
Formula:
QL = W(Ful)(Fsa)(N)
N = No. of Lights
Sample Calculation
𝑄𝐿 = 20(1)(1.2)(8)
The light loads for each room are presented on Tables 3.22, 3.23 and 3.24. The total
Light Load is 2400 watts or 2.4 KW.
24
Centralized Air-Conditioning System 2013
Workers continuously give off heat while inside the air conditioned space. An average
office operates for 8 hours thus the people load shall be calculated for this time being.
Formula:
Where:
N = No. of People
Also,
𝑄𝐿 = 𝐿𝑎𝑡𝑒𝑛𝑡 𝐻𝑒𝑎𝑡 𝑋 𝑁
Where:
N = No. of People
And,
𝑄𝑝 = 𝑄𝑠 + 𝑄𝐿
25
Centralized Air-Conditioning System 2013
Table 3.25 shows the design parameters and the assumptions made for the calculation
of both sensible and latent loads for occupants.
Sensible heat is heat exchanged by a body or thermodynamic system that has as its sole
effect a change of temperature.
To determine the number of people, we use the recommended number of person per
m2 of space. In this design we chose the single room for offices with 10 m2person and for the
Multi-purpose building an area of 0.6 m2 is chosen.
Sample Calculation
Tables 3.27, 3.28 and 3.29 presents the sensible cooling load values calculated. The total
Sensible Cooling load is 2636.2 watts or 2.6362 KW.
27
Centralized Air-Conditioning System 2013
Sample Calculation
𝑄𝑠 = 𝐿𝑎𝑡𝑒𝑛𝑡 𝐻𝑒𝑎𝑡 𝑋 𝑁
𝑄𝑠 = 75 𝑤𝑎𝑡𝑡𝑠 𝑋 2 𝑝𝑒𝑟𝑠𝑜𝑛
Table 3.30, 3.31 and 3.32 presents the latent cooling load values calculated. The total
Latent Load is 3635 watts or 3.635 KW.
Therefore the total People Load is equal to the sum of the total sensible and latent loads.
28
Centralized Air-Conditioning System 2013
Appliances such as computers, television, refrigerators and etc. emit heat which is
needed to be included in the cooling load calculation. The formula is given below.
𝑄𝐸 = 𝑁 𝑋 𝑊𝑅
Where:
N = No. of Equipment
Table 3.33 shows the wattage rating for the assumed equipment found inside a typical
office. Amongst the appliances are, desktop computers, television, coffee maker and a
refrigerator.
Sample Calculation
𝑸𝑬 = 𝟗𝟎𝟎 𝒘𝒂𝒕𝒕𝒔 𝒐𝒓 𝟎. 𝟗 𝑲𝑾
The complete calculation for the equipment load and the equivalent equipment loads
for each room on each floor is presented on Tables 3.34, 3.35 and 3.36. The total equipment
load for the building is 16703 watts or 16.703 KW.
29
Centralized Air-Conditioning System 2013
30
Centralized Air-Conditioning System 2013
Infiltration most commonly occurs because of air density differences between rooms.
For a typical case where the air mass flowing in equals the air mass flowing out minus any
condensed moisture, the room must be sealed except at the opening in question. If the cold
room is not sealed, air may flow directly through the door (ASHRAE, 2006).
To calculate for the sensible heat gain, the formula is given by the equation,
𝑸𝑺 = 𝟏. 𝟏 𝑿 𝑪𝑭𝑴 𝑿 ∆𝑻
Where:
∆𝑇 = Temperature Difference, K
Also, to compute for the Latent heat gain the formula is,
𝑸𝑳 = 𝟎. 𝟔𝟖𝑿 𝑪𝑭𝑴 𝑿 ∆𝝎
Where:
𝑽
𝑪𝑭𝑴 = 𝑨𝑪𝑯 𝑿
𝟔𝟎
Where:
31
Centralized Air-Conditioning System 2013
Design considerations and parameters for air exchange are enumerated as follows:
o Dry bulb Temperature – The average dry bulb temperature for an inside
condition is 230C or 73.40F and outside condition of 320C or 89.60F (chegg.com).
o Wet Bulb Temperature - The average wet bulb temperature for an inside
condition is 110C or 51.80F and outside condition of 300C or 860C (chegg.com).
𝑔𝑟𝑎𝑖𝑛𝑠 𝐻2 𝑜
o 𝜔i– Inside humidity ratio 17.4 (Engineering Tables and Charts).
𝐷𝑟𝑦 𝐴𝑖𝑟
𝑔𝑟𝑎𝑖𝑛𝑠 𝐻2 𝑜
o 𝜔o – Outside humidity ratio 170.1 (Engineering Tables and Charts).
𝐷𝑟𝑦 𝐴𝑖𝑟
Sample Calculation
𝑄𝑆 = 1.1 𝑋 𝐶𝐹𝑀 𝑋 ∆𝑇
𝑉
𝐶𝐹𝑀 = 𝐴𝐶𝐻 𝑋
60
2835.910𝑓𝑡 3
𝐶𝐹𝑀 = 0.5 𝑋
60
𝑓𝑡 3
𝐶𝐹𝑀 = 23.633
𝑚𝑖𝑛
And,
𝑓𝑡 3
𝑄𝑆 = 1.1 𝑋 23.633 𝑋 (89.6 − 73.4)𝐾
𝑚𝑖𝑛
𝒃𝒕𝒖
𝑸𝑺 = 𝟒𝟐𝟏. 𝟏𝟑𝟑 𝒐𝒓𝟎. 𝟏𝟐𝟑 𝑲𝑾
𝒉𝒓
The total sensible heat gain from infiltrating air is 5223.126 btu/hr or1.531KW.
32
Centralized Air-Conditioning System 2013
Table 3.37, 3.38 and 3.39 shows the sensible heat gain calculated per room.
Sample Calculation
𝑄𝐿 = 0.68 𝑋 𝐶𝐹𝑀 𝑋 ∆𝜔
33
Centralized Air-Conditioning System 2013
𝑓𝑡 3
𝐶𝐹𝑀 = 23.633
𝑚𝑖𝑛
And,
𝑓𝑡 3 𝑔𝑟𝑎𝑖𝑛𝑠 𝐻2 𝑜 𝑔𝑟𝑎𝑖𝑛𝑠 𝐻2 𝑜
𝑄𝑆 = 0.68 𝑋 23.633 𝑋 (170.1 − 17.4 )
𝑚𝑖𝑛 𝐷𝑟𝑦 𝐴𝑖𝑟 𝐷𝑟𝑦 𝐴𝑖𝑟
𝒃𝒕𝒖
𝑸𝑳 = 𝟐𝟒𝟓𝟑. 𝟗𝟏𝟑 𝒐𝒓 𝟎. 𝟕𝟏𝟗 𝑲𝑾
𝒉𝒓
Tables 3.40 , 3.41 and 3.42 presents the data for the latent heat gains in each floors.
The total latent heat gain from infiltrating air is 30434.825 watts or 8.919 KW.
34
Centralized Air-Conditioning System 2013
The primary weather-related variable influencing the cooling load for a building is solar
radiation. The effect of solar radiation is more pronounced and immediate in its impact on
exposed no opaque surfaces. The calculation of solar heat gain and conductive heat transfer
through various glazing materials and associated mounting frames, with or without interior
and/or exterior shading (ASHRAE, 2009).
Formula:
𝑄𝑠 = 𝐴 𝑋 𝑆𝐻𝐺𝐹 𝑋 𝑆𝐶 𝑋 𝐶𝐿𝐹
Where:
Qs = Solar Load
A = Area of the Transparent Surface
SHGF = Solar Heat Gain Factor
SC = Shading Coefficient
CLF = Cooling Load Factor
Determination of Solar Heat Gain Factor (SHGF), we assume that the sunlight is 400
north latitude and taking the hottest month of the year which is April (PAGASA).
35
Centralized Air-Conditioning System 2013
o Shading Coefficient
The total shading coefficient is a measure of the total amount of heat passing through
the glazing (known as the total solar heat transmittance) compared with that through a single
clear glass. The shading coefficient (SC) is derived by comparing the solar radiant heat
transmission properties of any glass with a clear float glass having a total solar heat
transmittance of 0.87 (i.e. clear float glass about 4mm thick)(ASHRAE, 2009).
In the Determination of the Shading Coefficient, the designer should be mindful of the
thickness of the glass and if it has shading. The glass is 6.32 mm thick considered as a single
glass, plate without any indoor shading. Therefore the shading coefficient is equal to 0.95.
One more factor must be considered since the solar energy entering the space does not
appear simultaneously as a load on the cooling system. The radiant energy is first absorb by the
surfaces in the space, during which time this surface temperature increase at a rate dependent
on their dynamic thermal characteristics. Thus, the solar energy absorbed is delayed before
being transferred to the air in the space by convection. Since this process may involve a
significant time lag, it is also usual practice to include a cooling load factor (CLF) in calculating
the cooling load attributable to radiation through glass.
36
Centralized Air-Conditioning System 2013
To determine the cooling load factor the solar time in hours and the direction to where
the window is facing should always be considered. The hottest time in the Philippines is from
12:00-5:00 PM, taking the average 3:00 PM or 15:00 (PAGASA).
Table 3.45 Cooling Load Factors for glass with interior shading, north latitudes
Table 3.46 shows the summary of the design parameters in calculating solar heat gain.
North 110
Solar Heat Gain East 690
Factors West 690
South 475
North 0.82
Cooling Load East 0.2
Factors West 0.72
South 0.5
Shading
0.95
Coefficient
Sample Calculation
𝑄𝑠 = 𝐴 𝑋 𝑆𝐻𝐺𝐹 𝑋 𝑆𝐶 𝑋 𝐶𝐿𝐹
𝑄𝑠 = [(0.84)(690)(0.95)(0.20)] + [(0.16)(475)(0.95)(0.5)]
𝑸𝒔 = 𝟏𝟒𝟔. 𝟐𝟐𝟒 𝑾𝒂𝒕𝒕𝒔 𝒐𝒓 𝟎. 𝟏𝟒𝟔𝟐𝟐𝟒 𝑲𝑾
37
Centralized Air-Conditioning System 2013
Tables 3.47 , 3.48 and 3.49 shows the complete solar load calculated per room and per
floor. The total solar load calculated for the entire building is 2944.3654 watts or 2.944 KW.
38
Centralized Air-Conditioning System 2013
The cooling load is summarized in Table 3.55. The total cooling load calculated is
68.55896 KW however; a factor of safety of 10% should be anticipated for overlooked
parameters (ASHRAE, 2009).
Factor of Safety
𝑭𝑺 = 𝟕. 𝟔𝟓𝟐𝟕 𝑲𝑾
𝑻𝑪𝑳 = 𝑪𝑳 + 𝑭𝑺
Where:
CL = Cooling Load, KW
FS = Factor of Safety
39
Centralized Air-Conditioning System 2013
The detailed cooling load per room is shown in Table 3.51 which will be used in the calculation for the flow rate per zone.
Walls Floors Ceiling Doors Light People (W) Air Infiltration (W) Equipment Solar TOTAL
FLOOR
(W) (W) (W) (W) Load (W) Load (W) Radiation (W) (W)
Latent Sensible Latent Sensible
1ST FLOOR
Room 1 2475.776 755.232 162.433 8.865 192 110 73.5 2453.912923 421.133 900 146.224 7699.076
Room 2 1042.493 732.780 139.016 8.865 192 110 73.5 2380.760461 408.578 900 123.834 6111.828
Room 3 1841.182 649.944 0.000 8.865 168 110 73.5 2111.496407 362.368 900 410.157 6635.513
Room 4 2547.408 634.226 0.000 8.865 168 110 73.5 2060.564849 353.628 2401 299.649 8656.841
Room 5 1079.360 485.546 0.000 8.865 120 110 73.5 1577.511124 270.727 900 189.525 4815.035
2ND FLOOR
Room 1 1841.182 0.000 136.414 8.865 168 110 73.5 2111.496407 362.368 900 410.157 6121.983
Room 2 1501.040 0.000 0.000 8.865 120 110 73.5 1577.511124 270.727 900 189.525 4751.168
Room 3 2261.872 0.000 0.000 8.865 168 110 73.5 2060.564849 353.628 2401 182.104 7619.533
MPH 4482.395 0.000 0.000 8.865 312 2205 1680.7 4050.746196 695.176 500 220.248 14155.13
3RD FLOOR
Room 1 2480.709 185.638 1101.471 8.865 192 110 73.5 2453.912923 421.133 900 146.224 8073.452
Room 2 1835.920 158.875 1068.638 8.865 192 110 73.5 2380.760461 408.578 900 123.834 7260.971
Room 3 1472.246 0.000 708.089 8.865 120 110 73.5 1577.511124 270.727 900 13.710 5254.649
Room 4 2830.965 0.000 924.914 8.865 168 110 73.5 2060.564849 353.628 2401 299.649 9231.085
Room 5 1383.443 0.000 708.089 8.865 120 110 73.5 1577.511124 270.727 900 189.525 5341.66
40